northwest rail electrified segment - fastracks · northwest rail electrified segment overall...

11
3 0 5 + 0 0 3 0 7 + 4 7 3 0 7 + 4 7 3 07 + 4 6 . 9 4 POB 285 + 00 29 0 + 0 0 295 + 00 300 + 0 0 B C NORTHWEST RAIL ELECTRIFIED SEGMENT OVERALL ELECTRICAL SITE PLAN ES-300 JCC JCC JAB 50 100 150 0 SCALE IN FEET TRAIN CONTROL HOUSE COMM HOUSE RTD EQUIPMENT CASE RE: ES-330 TO ES-332 RE: ES-320 TO ES-322 STATION PLATFORM A KSP JEK WESTMINSTER STATION L C EC NB/SB TRACK BNSF TRACK C RELOCATED L RE: ES-350 & ES-351 UNDERPASS ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A XCEL TRANSFORMER PCC 05/29/14 08/08/14 08/08/14 RE: ES-361 FARE COLLECTION EQUIPMENT RE: ES-360 STATION SHELTER STATION CANOPY ABOVE ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14 Pending JAB 08/08/14 ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C NUMBER: REFERENCE SHEET REVISIONS CHECKED BY: APPROVED BY: DATE: DATE: DESIGNED BY: DRAWN BY: USER: J Ca r n e y c :\ p wwo r k i ng \ r t d_ ea g l e _p3 \j ca r n e y \ d ms 51302 \ 7 B- 09 . 06 B_ NW ES- E- ES- 300 . dgn PARTNERS TRANSIT DENVER eagle P3 DATE: DATE: NO. BY DATE GLOBAL DESIGN CONSULTANTS 8 / 7 / 2014

Upload: dodien

Post on 25-May-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

305+

00

307+

47

307+

47

307+46.9

4

PO

B

285+

00

290+

00

295+

00

300+

00

B

C

NORTHWEST RAIL ELECTRIFIED SEGMENT

OVERALL ELECTRICAL SITE PLAN ES-300

JCC

JCC

JAB

50 100 1500

SCALE IN FEET

TRAIN CONTROL HOUSE

COMM HOUSE

RTD EQUIPMENT CASE

RE: ES-330 TO ES-332

RE: ES-320 TO ES-322

STATION PLATFORM

A

KSP

JEK

WESTMINSTER STATION

LC EC NB/SB TRACK

BNSF TRACK

C RELOCATEDL

RE: ES-350 & ES-351

UNDERPASS

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A

XCEL TRANSFORMER

PCC

05/29/14

08/08/14

08/08/14

RE: ES-361

FARE COLLECTION EQUIPMENT

RE: ES-360

STATION SHELTER

STATION CANOPY ABOVE

ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14

Pending

JAB 08/08/14ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

00.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/7/2

014

8 16 240

SCALE IN FEET

B

C

NORTHWEST RAIL ELECTRIFIED SEGMENT

ES-320

MA

TC

HLIN

E S

EE E

S-3

21

CONDUIT ROUTING PLAN

TRAIN CONTROL HOUSE

JCC

JCC

JABTRANSITION PLAZA/PLATFORM

CONDUIT KEY NOTES: (APPLIES TO SHEETS ES-320 TO ES-322) DRAWING NOTES: (APPLIES TO SHEETS ES-320 TO ES-322) GENERAL NOTES: (APPLIES TO SHEETS ES-320 TO ES-322)

1

2

3

4

5

6

COMM HOUSE TRANSFORMER

XCEL ENERGY CASE

RTD EQUIPMENT

A

KSP

JEK

WESTMINSTER STATION

BNSF TRACK

C RELOCATEDL

LC NWES NB/SB TRACK

PCC

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A

05/29/14

STATIONS:(1)4" VMS POWER, (1)4" ETHERNET/FIBER, (1)4" PA SPEAKER, (3)4" SPARE.

SYSTEMS WIDE: FO-N02116(1-7 CELL MICRO), (1)4" RTD SCADA.

STATIONS:(1)4" VMS POWER, (1)4" ETHERNET/FIBER, (1)4" PA SPEAKER, (3)4" SPARE, (1)2" GROUND GRID.

OF 36" BELOW TOP OF TIE.

ALL CONDUITS ROUTED UNDER TRACKS TO BE IN CONCRETE ENCASED DUCT BANK, BURIED MINIMUM

REFERENCE DETAIL 3/ES-380 FOR TVM/SAV/E-TEL SCHEMATIC.

(1)1-1/4" QUAD DUCT (COMM), AND (1)2" SPARE (COMM).

(1)1-1/4" QUAD DUCT (POWER), AND (1)2" SPARE (POWER).

NOT ALL KEY SYMBOLS APPEAR ON EVERY SHEET.

GENERAL: THESE CONDUIT KEY NOTES APPLY ALL CONDUIT ROUTING PLANS ES-320 TO ES-322.

#

SECURITY SHALL BE COORDINATED WITH THE CITY'S PLANS FOR THE NORTH PLAZA.

3. ELEVATION AND LOCATION OF CONDUIT FOR COMMUNICATIONS AND LIFE SAFETY AND

LOCATIONS. REFERENCE AND COORDINATE WITH FINAL DESIGN CCTV SYSTEMS PLANS.

THESE PLANS ARE NOT MEANT TO INDICATE CAMERA TYPES, DIRECTION OR EXACT

2. CCTV CAMERAS SHOWN ARE APPROXIMATE LOCATIONS FOR CONDUIT ROUTING ONLY.

CONDUIT REQUIREMENTS.

CDRL#7B-21.12.03. REFERENCE SHEETS ES-360, 361, 370, 380, 381 FOR ADDITIONAL

FOR POWER, COMM, VMS, PA WITH XORAIL PLANS AND SYSTEMS WIDE CONDUIT PLANS,

NECESSARY FOR COMPLETE INSTALLATION. COORDINATE ALL BRANCH CONDUIT

PLATFORMS AND TRANSITION PLANS. PLANS DO NOT INDICATE ALL CONDUITS

ARRANGEMENT OF MAIN POWER/COMMUNICATIONS PULLBOXES AT STATIONS

1. CONDUIT ROUTING PLANS ARE DIAGRAMMATICAL AND INDICATE GENERAL

08/08/14

08/08/14

ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14

Pending

JAB 08/08/14

WALL FOOTING. COORDINATE WITH CITY OF WESTMINSTER.

11. PROVIDE (2) 6" PVC SCHEDULE 80 CONDUITS AT 0.5% SLOPE TO SOUTH. EXTEND 3'-0" BEYOND RETAINING

7B-21.12(.00,.01,.03). REFER TO WESTMINSTER STATION COMM AND TES CONDUIT ONE-LINE DIAGRAM.

HANDHOLES, PULL BOXES AND SYSTEMS CONDUIT. CDRL# 7B-21.03, 7B-21.11(.00,.01,.02,.03),

10. REFER TO TRACTION ELECTRIFICATION SYSTEM PLANS AND SYSTEMS CONDUIT ROUTING PLANS FOR ALL

9. REFERENCE SHEET ES-351 FOR J-BOX AND CONDUIT REQUIREMENTS FOR FUTURE ARCHITECTURAL LIGHTING.

CDRL# 7B-21-12.03.

SYSTEMS PLANS AND SHOP DRAWINGS PRIOR TO ROUGH-IN. REFER TO SYSTEMS WIDE CONDUIT PLANS

8. COORDINATE CONDUIT STUB UP LOCATIONS FOR ALL COMM SHELTERS AND ENCLOSURES WITH FINAL

XORAIL PASSENGER INFORMATION SYSTEM PLANS.

7. SPEAKERS: CONDUIT PER PLANS TO NEAREST COMM PULLBOX. REFER TO COMMUNICATIONS PLANS AND

REFER TO COMMUNCATIONS PLANS, AND XORAIL SYSTEMS PLANS.

6. CAMERAS: CONDUIT PER PLANS TO NEAREST COMM PULLBOX. LABEL CONDUITS "SECURITY CONDUITS".

TO PHONES.

PUBLIC PHONES & EMERGENCY PHONES, REFERENCE DETAIL 3/ES-380 FOR CONDUIT REQUIREMENTS

5. REFERENCE ARCHITECTURAL SIGNAGE AND COMMUNICATION SYSTEMS PLANS FOR LOCATIONS OF

4. FUTURE FARE COLLECTION EQUIPMENT LOCATION. REFERENCE CONDUIT REQUIREMENTS ON DETAIL 3/ES-380.

3. POWER AND COMMUNICATIONS HAND HOLE. REFERENCE DETAIL 2/ES-380.

UNDER PLATFORM WITH CONDUIT ROUTED IN CRAWLSPACE. RE:ES-340.

2. POWER AND COMMUNICATIONS PULLBOX. REFERENCE DETAIL 1/ES-381. BOX TO BE LOCATED

1. POWER AND COMMUNICATIONS PULLBOX. REFERENCE DETAIL 1/ES-380.

NOT ALL KEY SYMBOLS APPEAR ON EVERY SHEET.

GENERAL: THESE DRAWING NOTES APPLY TO ALL CONDUIT ROUTING PLANS ES-320 TO ES-322.

ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

20.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/7/2

014

8

8

(1)1-1/2"(POWER)

8(2)2"(POWER)

(3) 4"C (2 COMM, 1 POWER)

RTD (2) 4"C (1 COMM, 1 POWER)

10

5

10

10

6

10

10

10

1 2

7

(1)1"(POWER)

(2)1"(COMM)

1

10

MH MH

MH

MH, TYPE 2, 4X4

INTERFACE

STATION

HH

MH

MH-SC-G04263

305+00

295+008 16 240

SCALE IN FEET

B

C

NORTHWEST RAIL ELECTRIFIED SEGMENT

MA

TC

HLIN

E S

EE E

S-3

20

ES-321

# CONDUIT KEY NOTES

DRAWING NOTES:

CONDUIT ROUTING PLANS ES-320 TO ES-322.

REFERENCE SHEET ES-320 FOR ALL CONDUIT KEYNOTES. APPLIES TO

CONDUIT ROUTING PLANS ES-320 TO ES-322.

REFERENCE SHEET ES-320 FOR ALL DRAWING NOTES. APPLIES TO

MA

TC

HLIN

E S

EE E

S-3

22

CONDUIT ROUTING PLAN

JCC

JCC

JABTRANSITION PLAZA/PLATFORM

ON NORTH SIDE OF UNDERPASS IN PLAZA AREA.

BY SOUTH WESTMINSTER DEVELOPER

EXACT LOCATION TO BE DETERMINED

A

KSP

JEK

WESTMINSTER STATION

LC EC NB/SB TRACK

BNSF TRACK

C RELOCATEDL

RE: ES-350, ES-351

UNDERPASS

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A

05/29/14

08/08/14

08/08/14

ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14

Pending

LINE OF CANOPY ABOVE

JAB 08/08/14

RE: ES-350, ES-352

ROOM UNDER STAIRS

ELEVATOR MACHINE

RE: ES-350, ES-352

UNDER STAIRS

ELECTRICAL ROOM

RE: ES-350

UNDER STAIRS

STORAGE ROOM

ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

21.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/7/2

014

7

JB1

JB

2

JB

2

FOR FUTURE CCTV.

(3)4"C(2 COMM, 1 POWER)

EQUIPMENT.

FOR FAIR COLLECTION

RTD (2)4"C(1 COMM, 1 POWER)

4

1

5

6

77

7 7

6

P

4

J J

9

J J

9

11

CC

COMM CASE

21 2

1 21 2

JB

2

E

4

6

6

6LOWER LEVEL. RE: ES-350

TO PULLBOX BELOW AT

5E

6

6 (1)1"(POWER)

(1)1"(COMM)

3

1 2

(1)1"(POWER)

(1)1"(COMM)

3

(1)1"(POWER)

(2)1"(COMM)(1)1"(POWER)

(2)1"(COMM) (1)1"(POWER)

(2)1"(COMM)(1)1"(POWER)

(2)1"(COMM)

(1)1"(POWER)

(2)1"(COMM)

(1)1"(POWER)

(1)1"(COMM)

(2)1"(POWER)

(1)1"(COMM)

(1)1"(POWER)

(2)2"(COMM)

7

(1)1"(POWER)

(2)1"(COMM)

6ABOVE.

MOUNTED TO CANOPY

ABOVE.

MOUNTED TO CANOPY

6

(1)1"(POWER)

(2)1"(COMM)

(1)1"(POWER)

(1)1"(COMM)

(1)1"(POWER)

(2)1"(COMM)

(1)1"(DMX CONTROL)

(1)1"(POWER)

(2)1"(COMM)

(1)1"(POWER)

(1)1"(COMM)

RE:ES-352

BELOW STAIRS.

TO ELECTRICAL ROOM

(1)1"(DMX CONTROL)

RE:ES-352

BELOW STAIRS.

TO ELECTRICAL ROOM

(1)1"(DMX CONTROL)

7

WALL MOUNTED WALL MOUNTED

11

8 16 240

SCALE IN FEET

B

C

NORTHWEST RAIL ELECTRIFIED SEGMENT

MA

TC

HLIN

E S

EE E

S-3

21

ES-322

# CONDUIT KEY NOTES

DRAWING NOTES:

CONDUIT ROUTING PLANS ES-320 TO ES-322.

REFERENCE SHEET ES-320 FOR ALL CONDUIT KEYNOTES. APPLIES TO

CONDUIT ROUTING PLANS ES-320 TO ES-322.

REFERENCE SHEET ES-320 FOR ALL DRAWING NOTES. APPLIES TO

CONDUIT ROUTING PLAN

JCC

JCC

JABTRANSITION PLAZA/PLATFORM

A

KSP

JEK

WESTMINSTER STATION

BNSF TRACK

C RELOCATEDL

LC EC NB/SB TRACK

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A 05/29/14

08/08/14

08/08/14

ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14

Pending

JAB 08/08/14ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

22.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/7/2

014

JB

2

6

7

7

(1)1"(POWER)

(2)1"(COMM)

(1)1"(POWER)

(2)1"(COMM)

7

(1)1"(POWER)

(2)1"(COMM)

(1)1"(POWER)

(2)1"(COMM)

(2)1"(POWER)

(1)1"(COMM)

(1)1"(POWER)

(1)1"(COMM)

8 16 240

SCALE IN FEET

B

C

NORTHWEST RAIL ELECTRIFIED SEGMENT

ES-330

MA

TC

HLIN

E S

EE E

S-3

21

JCC

JCC

JAB

ELECTRICAL PLAN

TRANSITION PLAZA/PLATFORM

TRAIN CONTROL HOUSE

COMM HOUSE

PCC

TRANSFORMER

XCEL ENERGY

DRAWING NOTES: (APPLIES TO SHEETS ES-ES-330 TO ES-332)

CASE

RTD EQUIPMENT

A

KSP

JEK

WESTMINSTER STATION

BNSF TRACK

C RELOCATEDL

LC NWES NB/SB TRACK

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A

05/29/14

08/08/14

08/08/14

Pending

ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14

JAB 08/08/14

BASE IS LEVEL WITH TOP OF RAMP AT EACH LOCATION. REFERENCE POLE DETAILS SHEET ES-383.

8. CONCRETE BASES FOR POLES ALONG RAMP TO EXTEND TALLER THAN STANDARD BASES SO THAT TOP OF

RE: ES-340.

#CKMDV SERIES OR EQUAL). SURFACE MOUNT RECEPTACLE IN CRAWLSPACE NEAR ACCESS DOOR LOCATIONS.

7. PROVIDE WEATHER PROOF GFI RECEPTACLE WITH ALUMINUM "IN-USE" COVER (THOMAS & BETTS, "REDDOT",

REFERENCE ES-390 FOR LIGHT FIXTURE SCHEDULE.

6. FOR PLATFORM LIGHT POLES REFERENCE STRUCTURAL DRAWINGS FOR CONCRETE BASE FOUNDATIONS.

FOR LOCATIONS PRIOR TO ROUGH-IN.

5. PROVIDE 277V CONNECTION TO PLATFORM SIGNAGE CABINET. REFERENCE FINAL SIGNAGE PACKAGE

REFERENCE ARCHITECTURAL PLANS, CCTV SYSTEM PLANS & PASSENGER INFORMATION PLANS.

PLANS. LABEL THESE CONDUITS "SECURITY CONDUITS". FOR CAMERA & SPEAKER LOCATIONS

4. PLATFORM LIGHT POLES WITH CAMERAS OR SPEAKERS. PROVIDE CONDUIT PER THE CONDUIT ROUTING

CABINET. USE (2-#8, 1-#8 GND) 3/4"C.

#CKMSV SERIES OR EQUAL). RECEPTACLE MOUNTED INTEGRAL TO THE PLATFORM SIGNAGE

3. PROVIDE 30A, 208V RECEPTACLE WITH ALUMINUM "IN-USE" COVER (THOMAS & BETTS, "REDDOT",

OR EQUAL).

USE (2-#8, 1-#8 GND) 3/4"C. PROVIDE "IN-USE" COVER (THOMAS & BETTS, "REDDOT", #CKMDV SERIES

2. PROVIDE DUPLEX GFI RECEPTACLE MOUNTED INTEGRAL TO THE PLATFORM SIGNAGE CABINET.

COORDINATE FINAL LOCATIONS OF ALL FARE COLLECTION EQUIPMENT PRIOR TO ROUGH-IN.

1. TVM/SAV EQUIPMENT LOCATED AT TICKET KIOSK. RE: SHEET ES-361 AND DETAIL 3/ES-380. FIELD

NOT ALL KEY SYMBOLS APPEAR ON EVERY SHEET.

GENERAL: THESE DRAWING NOTES APPLY TO ALL PLANS ES-330 TO ES-332.

ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

30.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/7/2

014

307+47 307+47

307+46.9

4P

OB

8

PER NOTE 4.

(2-#10, 1-#10 GND) 1" C AND SPARE CONDUITS

TYPICAL TO ALL LIGHT POLES THIS CIRCUIT

(2-#10, 1-#10 GND)1"C.

HL-5

PL

PL

PL

PL

PL

PL

PL

PL

PL

PL PL

PL

PL

(2-#10, 1-#10 GND)1"C.

HL-21

PL

PL

PLPER NOTE 4.

(2-#10, 1-#10 GND) 1" C AND SPARE CONDUITS

TYPICAL TO ALL LIGHT POLES THIS CIRCUIT

4

8

8

8

4

305+00

295+00

8 16 240

SCALE IN FEET

B

C

NORTHWEST RAIL ELECTRIFIED SEGMENT

MA

TC

HLIN

E S

EE E

S-3

30

ES-331

DRAWING NOTES:

MA

TC

HLIN

E S

EE E

S-3

32

JCC

JCC

JAB

PLATFORM & TRANSITION PLAZA ELECTRICAL PLANS ES-330 TO ES-332.

REFERENCE SHEET ES-330 FOR ALL DRAWING NOTES. APPLIES TO

ELECTRICAL PLAN

TRANSITION PLAZA/PLATFORM

RE: ES-350

UNDERPASS

A

KSP

JEK

WESTMINSTER STATION

BNSF TRACK

C RELOCATEDL

LC EC NB/SB TRACK

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A

05/29/14

08/08/14

08/08/14

STAIRS RE: ES-350

STORAGE ROOM UNDER

ABOVE

CANOPY STRUCTURE

Pending

ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14

JAB 08/08/14

UNDER STAIRS RE: ES-350, ES-352

ELEVATOR MACHINE ROOM

STAIRS RE: ES-350, ES-352

ELECTRICAL ROOM UNDER

ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

31.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/7/2

014

2

30A,208V

WP, GFI3

1

LA-1,3

LA-7(PART)

6 (TYP.)

2

WP, GFIHL-2(PART) J

5

7

WP, GFI

LA-2(PART)

IN CRAWLSPACE

RECEPTACLE LOCATED

6

(TYP.)

1

PL

PL

PL

PL

PL

PLPL

PL4 PL4 PL4 PL4

PL PL

EW

EWSEWSEWS

6

(TYP.)

(2-#10, 1-#10 GND)1"C.

HL-7

(2-#10, 1-#10 GND)1"C.

HL-23

STRUCTURE ABOVE.

MOUNTED TO CANOPY

ES-333 FOR FIXTURES

REFERENCE SHEET

PL4

EWS

EW EWS EWS

PL4

PL

JB

ADDITIONAL INFORMATION.

CONDUIT ROUTING PLANS FOR

TYPICAL, PULL BOX, REFERENCE

JB JB

SPARE CONDUITS PER NOTE 4.

CIRCUIT (2-#10, 1-#10 GND) 1" C AND

TYPICAL TO ALL LIGHT POLES THIS

SPARE CONDUITS PER NOTE 7.

CIRCUIT (2-#10, 1-#10 GND) 1" C AND

TYPICAL TO ALL LIGHT POLES THIS

ELA-14(PART)

8

4

4

EWS EWS

LA-7(PART)

8 16 240

SCALE IN FEET

B

C

NORTHWEST RAIL ELECTRIFIED SEGMENT

MA

TC

HLIN

E S

EE E

S-3

31

ES-332

JCC

JCC

JAB

ELECTRICAL PLAN

DRAWING NOTES:

PLATFORM & TRANSITION PLAZA ELECTRICAL PLANS ES-330 TO ES-332.

REFERENCE SHEET ES-330 FOR ALL DRAWING NOTES. APPLIES TO

TRANSITION PLAZA/PLATFORMA

KSP

JEK

WESTMINSTER STATION

BNSF TRACK

C RELOCATEDL

LC NWES NB/SB TRACK

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A

05/29/14

08/08/14

08/08/14

RE: ES-360

TYPICAL SHELTER

Pending

ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14

JAB 08/08/14ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

32.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/7/2

014

2

LA-7(PART)

LA-11

WP, GFI

HB-1

WP, GFI

PLPL

PL

PL

PL

PL

PL

PL

PL

PL

PLPL

PL

PL PL PL

PL

PL

PL

JB

PL

ADDITIONAL INFORMATION.

CONDUIT ROUTING PLANS FOR

TYPICAL, PULL BOX, REFERENCE

8 8 8 8

B

C

NORTHWEST RAIL ELECTRIFIED SEGMENT

ES-333

JCC

JCC

JABA

KSP

JEK

WESTMINSTER STATION

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A

05/29/14

08/08/14

08/08/14

CANOPY ELECTRICAL PLAN

4 8 120

SCALE IN FEET

ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14

Pending

JAB 08/08/14ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

GENERAL NOTES:

BID ALTERNATE NOTES:

ONLY THE "EFW, EFW2, EFWN" WHITE LED FIXTURES ON THE CANOPY.

ASSOCIATED CONTROLLERS, CONDUIT AND WIRE FROM THE SCOPE. LEAVING

1. PROVIDE ALTERNATE PRICE TO REMOVE THE TYPE "EFC" FIXTURES AND

INFORMATION.

11. REFERENCE FIXTURE SCHEDULE SHEET ES-390 FOR ADDITIONAL

INCLUDE WIRING DIAGRAMS SPECIFIC TO THIS DESIGN.

10. PROVIDE MANUFACTURER SHOP DRAWINGS FOR ENTIRE LED LIGHTING SYSTEM.

LOWER LEVEL ENLARGED MACHINE ROOM PLAN ES-352 FOR LOCATION.

OTHER COMPONENTS. LOCATE IN ELECTRICAL ROOM BELOW STAIRS. REFERENCE

9. PROVIDE ENCLOSURE TO HOUSE DMX CONTROLLER AND SPLITTERS AND ANY

INTEGRAL CLOCK, INFRA-RED RECEIVER FOR REMOTE CONTROL.

DISPLAY SCREEN, SD CARD FOR MEMORY, RS232 SERIAL PORT, OUTPUT RELAY,

ETHERNET PORT, (8) CONTACT CLOSURE INPUTS, USER INTERFACE KEYPAD AND

BUT NOT LIMITED TO POWER SUPPLIES, SOFTWARE, (2)DMX OUTPUTS, USB PORT,

8. LED CONTROLLER SYSTEM TO INCLUDE ALL NECESSARY COMPONENTS, INCLUDING

SOFTWARE, AND TRAINING FOR FACILITY PERSONNEL TO OPERATE SYSTEM.

PROGRAMMING KIT, ADDITIONAL DMX SPLITTERS AS REQUIRED, MANUFACTURER

BUT NOT LIMITED TO POWER/DATA JUMPER CABLES, DMX SPLITTER/LED

BELOW STAIRS, RE:ES-352. PROVIDE COMPLETE OPERATING SYSTEM INCLUDING

CONTROLLED TOGETHER. DMX CONTROLLER LOCATED IN ELECTRICAL ROOM

7. ALL "EFC" RGB COLOR LED FIXTURES TO BE CONNECTED TO SAME CIRCUIT AND

AND CONTROLLED TOGETHER.

6. ALL "EFW, EFW2, EFWN" WHITE LED FIXTURES CONNECTED TO SAME CIRCUIT

5. ALL EXPOSED CONDUIT AND J-BOXES TO BE PAINTED TO MATCH CANOPY.

TO REDUCE J-BOX AND CONDUIT QUANTITIES.

LIGHTING MANUFACTURER'S POWER/DATA JUMPER CABLES FROM FIXTURE TO

4. J-BOXES SURFACE MOUNTED AT PURLINS, NOT ALL SHOWN FOR CLARITY. USE

NEXT PURLIN. REFERENCE CANOPY ARCHTECTURAL AND STRUCTURAL PLANS.

OPENINGS IN PURLINS WILL BE PROVIDED FOR CONDUIT PASS THROUGH TO

TO PURLINS. PROVIDE CONDUIT FROM J-BOX TO J-BOX AT PURLIN TO PURLIN.

FIRST PURLIN. CONDUIT AND J-BOXES TO BE SURFACE MOUNTED ON EXTERIOR

GIRDER BASE ROUTED INSIDE GIRDER TO J-BOX AT EXTERIOR OF CANOPY AT

3. USE MC CABLE FOR POWER FEED AND DMX CABLE FOR CONTROL FEED FROM

REFERENCE CONDUIT ROUTING PLANS FOR ADDITIONAL INFORMATION.

2. POWER AND DMX CONTROL FEED TO ROUTE IN CONDUIT TO MAIN GIRDER BASE.

ARE TO BE AIMED DOWNWARD AT PLATFORM.

WITH MARLA STAUTH AT FRANKLY LIGHTING. ALL OTHER WHITE LED FIXTURE

1. TYPE "EFC" FIXTURES ARE TO BE AIMED UPWARD AT CANOPY, COORDINATE AIMING

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

33.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/8/2

014

COORDINATE AIMING WITH FRANKLY LIGHTING.

ARE TO BE MOUNTED AIMING DOWNWARD.

AIMED UPWARD AT GLASS PANELS. ALL OTHERS

MOUNTING DETAILS. EFC FIXTURES ARE TO BE

REFERENCE ARCHITECTURAL PLANS FOR

FIXTURE MOUNTED TO SIDE OF OUTRIGGER.

EFW, EFWN, EFW2 & EFC (TYP.)

USE (2-#10, 1-#10GND).

ALL "EFW , EFW2, EFWN" FIXTURES CONNECTED TO HL-19.

ALL "EFC" FIXTURES CONNECTED TO HL-17.

CANOPY LIGHTING HOME RUNS:

J J J J J J J

RE: CONDUIT ROUTING PLANS.

GIRDER FROM J-BOX AT CANOPY.

POWER/DATA TO BE ROUTE INSIDE

LIGHTS, DMX CONTROL AND CAMERA

TYPICAL, HOMERUN FOR POWER TO

(1)1" (COMM) FOR CAMERAS.

(1)1" (DATA) FOR DMX CONTROL,

(1)1" (POWER) FOR LIGHTING.

TYPICAL

CLARITY. REFER TO GENERAL NOTES

TO PURLIN. NOT ALL SHOWN FOR

TYPICAL, SURFACE MOUNT J-BOXES

FIRST PURLIN.

(1)1" (COMM) TO J-BOX AT

CAMERA TYPICAL,

J JJJJJJJ J

CLARITY.

TO FIXTURE. NOT ALL SHOWN FOR

CABLE CONNECTION FROM FIXTURE

TYPICAL, POWER /DATA JUMPER

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFWN

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC EFC EFC EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFCEFCEFCEFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFC

EFWN

EFW2

EFWN

EFW2

EFWNEFW2 EFW2

EFW2

EFW2

EFW2

EFW2

EFW

EFW

EFW

EFW2

EFW2

EFW2

EFW2

EFW

EFW

EFW

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

40.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/7/2

014

1 2

3

4

1

NORTHWEST RAIL ELECTRIFIED SEGMENT

ES-340PLATFORM CROSS SECTIONJAB

4 8 120

SCALE IN FEET

JCC

JCC KSP

JEK

C

DRAWING NOTES:

A

B

WESTMINSTER STATION

PER PLANS.

4. WEATHER PROOF GFI RECEPTACLE WITH ALUMINUM "IN-USE" COVER AT +18" A.F.G. LOCATIONS

STRUCTURAL PLANS.

3. ACCESS COVERS IN PLATFORM SLAB. RE: DETAIL 1/ES-181. REFERENCE ARCHITECTURAL AND

SLAB TENDONS.

PANELS WITHOUT COORDINATION AND APPROVAL WITH STRUCTURAL ENGINEER, SO NOT TO HIT

FASTENERS ARE NOT TO PROJECT MORE THAN 1" INTO PRECAST PANEL. NO DRILLING OF PRECAST

2. COORDINATE ALL MOUNTING OF CONDUITS, DEVICES, J-BOXES, LIGHTS UNDER STATION PLATFORM.

1. POWER AND COMMUNICATIONS PULLBOX. REFERENCE DETAIL 1/ES-181.

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A

05/29/14

08/08/14

08/08/14

Pending

JAB 07/10/14ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B

JAB 08/08/14ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

B

C

1

NORTHWEST RAIL ELECTRIFIED SEGMENT

ES-350

8 16 240

SCALE IN FEET

STORAGE ROOM

JCC

JCC

DRAWING NOTES:

JABA

NTS

KSP

JEK

WESTMINSTER STATION

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A

05/29/14

LOWER LEVEL AND UNDERPASS ELECTRICAL PLAN

LOWER LEVEL AND UNDERPASS ELECTRICAL PLAN

08/08/14

08/08/14

MACHINE ROOM.

ELEVATOR

ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14

Pending

1/ES-380.

4. POWER AND COMMUNICATIONS PULLBOX. REFERENCE DETAIL

AND CCTV SYSTEM PLANS FOR EXACT QUANTITIES & LOCATIONS.

NEAREST COMM PULLBOX. REFERENCE ARCHITECTURAL PLANS

3. CAMERAS: PROVIDE J-BOX AND CONDUIT FROM CAMERA TO

SYSTEMS PLANS FOR SYSTEMS DESIGN.

CONTROL, AND INTRUSION DETECTORS. REFERENCE COMM

SYSTEM INTERFACE WITH FIRE AND SMOKE DETECTION, ACCESS

2. PROVIDE 2" CONDUIT TO NEAREST COMM PULLBOX FOR SCADA

FOR CONDUIT REQUIREMENTS TO PHONES.

PHONES & EMERGENCY PHONES, REFERENCE DETAIL 3/ES-380

COMMUNICATIONS SYSTEMS PLANS FOR LOCATIONS OF PUBLIC

1. REFERENCE ARCHITECTURAL SIGNAGE PLANS AND

ROOM

ELECTRICAL

JAB 08/08/14ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

50.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/7/2

014

305+00

LA-39,41J

E

EUH-2

2

3

3

3

1

3

E 1

3

3

JB4

ES-321.

PLATFORM LEVEL. RE:

TO PULLBOX ABOVE AT

(1)1"(COMM)

(1)1"(POWER)

E

1

4 (1)1"(COMM)

(1)1"(POWER)

(1)1"(COMM)

(1)1"(POWER)

(1)1"(COMM)

(1)1"(POWER)

(1)1"(COMM)

(1)1"(POWER)

(1)1"(COMM)

(1)1"(POWER)J

SP-1

LA-10,12

SUMP PIT

LA-14(PART)

(1)1"(COMM)

(1)1"(POWER)

ROOM EQUIPMENT.

AND ELEVATOR MACHINE

RE: ES-352 FOR ELECTRICAL

B

C

1

NORTHWEST RAIL ELECTRIFIED SEGMENT

ES-351

8 16 240

SCALE IN FEET

JCC

JCC

DRAWING NOTES:

JABA

NTS

KSP

JEK

WESTMINSTER STATION

ISSUED FOR OSR #1, CDRL #7B-09.06B, REV A

05/29/14

LOWER LEVEL AND UNDERPASS LIGHTING PLAN

LOWER LEVEL AND UNDERPASS LIGHTING PLAN

08/08/14

08/08/14

ISSUED FOR OSR #2, CDRL #7B-09.06B, REV B JAB 07/10/14

Pending

JAB 08/08/14

6. CONNECT 90 MINUTE BATTERY AHEAD OF LOCAL SWITCHLEG.

IN UNDERPASS. TYPICAL 4 CORNERS OF UNDERPASS.

UP TO GRADE LEVEL. CAP CONDUIT FOR FUTURE USE. NO EXPOSED CONDUIT

1-1/2" RIGID CONDUIT STUBBED TO 1'-0" OUTSIDE UNDERPASS WALL AND

AT 6'-8" A.F.F. FOR FUTURE UNDERPASS ARTWORK LIGHTING. PROVIDE

5. PROVIDE 6"X6" J-BOX RECESSED FLUSH IN CONCRETE UNDERPASS WALL

FIXTURES.

FROM INVERTER TO UL 924 RELAY. OUTPUT OF UL 924 RELAY TO LIGHT

FROM BREAKER TO PRIMARY INPUT OF INVERTER. CONNECT OUTPUT

CONTROL PANEL TO UL 924 RELAY. CONNECT UNSWITCHED HOT LEG

CONNECT SWITCHED HOT LEG FROM MOTORIZED BREAKER IN LIGHTING

ROOM. PROVIDE UL 924 RELAY ON SECONDARY SIDE OF LIGHTING INVERTER.

EMERGENCY LIGHTING INVERTER AND UL 924 RELAY LOCATED IN ELECTRICAL

4. CIRCUIT FOR FIXTURES IN UNDERPASS TO BE CONNECTED VIA

WITH ARCHITECTURAL, STRUCTURAL AND CONSPAN BRIDGE SYSTEMS.

CONDUIT IN UNDERPASS. COORDINATE EXACT PLACEMENT OF J-BOXES

OUTSIDE THE UNDERPASS STRUCTURE FOR HOMERUN. NO EXPOSED

UNDERPASS. PROVIDE 1" CONDUIT FROM LIGHT TO LIGHT ROUTED

PROVIDE DOUBLE GANG 4"X4" J-BOX RECESSED FLUSH IN CONCRETE

3. FIXTURE SURFACE MOUNTED TO UNDERSIDE OF UNDERPASS CEILING.

2. HANG FIXTURE AT 10'-0" A.F.F.

WATT STOPPER PW-100 OR EQUAL.

1. PROVIDE PASSIVE INFRARED OCCUPANCY SENSOR, WALL BOX STYLE,

ISSUED FOR CONST REVIEW, CDRL #7B-09.06B , REV C

NUMBER:

REFERENCE

SHEET

REVISIONS

CHECKED BY:

APPROVED BY:

DATE:

DATE:

DESIGNED BY:

DRAWN BY:

US

ER:

JCarn

ey

c:\p

ww

orkin

g\rtd

_eagle

_p3\jcarn

ey\d

ms51302\7

B-0

9.0

6B_

NW

ES-E-E

S-3

51.d

gn

PARTNERS

TRANSIT

DENVER

eagle P3

DATE:

DATE:

NO. BY DATE

GLOBAL DESIGN CONSULTANTS

8/7/2

014

5

ETRETR

ETR ETR

ETR

ETR

ED ED ED ED

(2-#12, 1-#12GND) 1"C.

HL-13

4

(2-#10, 1-#10GND) 1"C.

HL-9,11

CIRCUIT. (2-#10, 1-#10GND)

TYPICAL ALL LIGHTS THIS

OS

A1E

A1 A1 A1E

(TYP) 21

(TYP) 3

J J

5 5

J J

OS

A1

A1A1A1

(TYP)2

1

ED

OF PLATFORM

MOUNTED TO UNDERSIDE

TYPICAL ALL "ED" FIXTURES

ED ED ED

6

6

(2-#12, 1-#12 GND)1"C.

HL-15

5