NON-FUSED SWITCHES FUSED SWITCHES
AACACBADAAFAFCAFFAFGAHUAICALAMAMPARCHARCSATATSAUX
BASBCBKRBLDG
CCBCCTVCFLCIRCLCLFCLGCOMMCONNCPTCuCT
DCDNDISC
AMPEREALTERNATING CURRENTAIR CIRCUIT BREAKERAMERICANS WITH DISABILITIES ACTAMP FRAMEABOVE FINISH CEILINGABOVE FINISHED FLOORABOVE FINISHED GRADEAIR HANDLING UNITAMPERE INTERRUPTING CAPACITYALUMINUMAMMETERAMPEREARCHITECTAREA OF REFUGE COMMUNICATION SYSTEMAMP TRIPAUTOMATIC TRANSFER SWITCHAUXILIARY
BUILDING AUTOMATION SYSTEMBRANCH CIRCUITBREAKERBUILDING
CONDUITCIRCUIT BREAKERCLOSED CIRCUIT TELEVISIONCOMPACT FLUORESCENT LAMPCIRCUITCENTERLINECURRENT LIMITING FUSECEILINGCOMMUNICATIONSCONNECTIONCONTROL POWER TRANSFORMERCOPPERCURRENT TRANSFORMER
DIRECT CURRENTDOWNDISCONNECT
DISTDSDWG
EEFELECELEVEMEMTENCLEOEQPTEWC
FFAFACPFCBFDRFLAFRAPFSFTLFVNR
GGECGFCIGFEP
HACRHOAHP
ICICCBIG
JB
DISTRIBUTIONDISCONNECT SWITCHDRAWING
EMERGENCYEXHAUST FANELECTRICALELEVATOREMERGENCYELECTRICAL METALLIC TUBINGENCLOSUREELECTRICALLY-OPERATEDEQUIPMENTELECTRIC WATER COOLER
FUSEFIRE ALARMFIRE ALARM CONTROL PANELFUSED CIRCUIT BREAKERFEEDERFULL LOAD AMPSFIRE ALARM REMOTE ANNUNCIATOR PANELFUSED DISCONNECT SWITCHFEED-THROUGH LUGSFULL-VOLTAGE NON-REVERSING
GROUNDGROUNDING ELECTRODE CONDUCTORGROUND FAULT CIRCUIT INTERRUPTERGROUND FAULT EQUIPMENT PROTECTION
HEATING, AIR CONDITIONING, REFRIGERATIONHAND-OFF-AUTOMATICHORSEPOWER
INTERRUPTING CAPACITYINSULATED-CASE CIRCUIT BREAKERISOLATED GROUND
JUNCTION BOX
kAkAICkcmilkVkVAkW
LALPSLTG
MAXMBJMCBMCCBMCPMECHMHMINMLOMTD
NNCNLNONTS
OCOCPD
PPAPBPNLPRIPTPWR
RMCRVS
KILOAMPEREKILOAMPERE INTERRUPTING CAPACITYTHOUSAND CIRCULAR MILSKILOVOLTKILOVOLT-AMPEREKILOWATT
LIGHTNING ARRESTORLIGHTNING PROTECTION SYSTEMLIGHTING
MAXIMUMMAIN BONDING JUMPERMAIN CIRCUIT BREAKERMOLDED-CASE CIRCUIT BREAKERMOTOR CIRCUIT PROTECTORMECHANICALMANHOLEMINIMUMMAIN LUGS ONLYMOUNTED
NEUTRALNORMALLY-CLOSEDNIGHT LIGHTNORMALLY-OPENNOT TO SCALE
ON-CENTEROVERCURRENT PROTECTION DEVICE
POLEPUBLIC ADDRESSPUSHBUTTONPANEL OR PANELBOARDPRIMARYPOTENTIAL TRANSFORMERPOWER
RIGID METAL CONDUITREDUCED-VOLTAGE STARTER
SBJSCCRSCWRSECSMRSPDSPDTSPSTSTSTBYSWSWBDSWGRSYS
T/DTELTLTVSSTYP
UCUPS
VVAVCBVFC
WWhWhMWMWPWT
XFERXFMR
XP
SYSTEM BONDING JUMPERSHORT CIRCUIT CURRENT RATINGSHORT CIRCUIT WITHSTAND RATINGSECONDARYSURFACE-MOUNTED RACEWAYSURGE PROTECTION DEVICESINGLE-POLE DOUBLE-THROWSINGLE-POLE SINGLE-THROWSHUNT-TRIPSTANDBYSWITCHSWITCHBOARDSWITCHGEARSYSTEM
TELEPHONE/DATATELEPHONETWIST-LOCKTRANSIENT VOLTAGE SURGE SUPPRESSIONTYPICAL
UNDERCOUNTERUNINTERRUPTIBLE POWER SUPPLY
VOLTVOLT-AMPEREVACUUM CIRCUIT BREAKERVARIABLE FREQUENCY CONTROLLER
WATT OR WIREWATTHOURWATTHOUR METERWATTMETERWEATHER-PROOFWATER-TIGHT
TRANSFERTRANSFORMER
EXPLOSION-PROOF
COMBINATION MOTOR CONTROLLER LEGEND
COMBINATION MOTOR CONTROLLER SCHEDULE
ELECTRICAL DRAWING LISTELECTRICAL ABBREVIATIONS
BRANCH CIRCUIT SCHEDULE (600-VOLT COPPER CONDUCTORS)FEEDER CIRCUIT SCHEDULE (600-VOLT COPPER CONDUCTORS)
ENCLOSED DISCONNECT SWITCH SCHEDULE
ENCLOSED DISCONNECT SWITCH LEGEND
LOW-VOLTAGE TRANSFORMER SCHEDULE
LOW-VOLTAGE TRANSFORMER SYMBOL LEGEND
ENCLOSED COMBINATION MAGNETIC MOTOR CONTROLLER. MSx INDICATES UNIT NUMBER;REFER TO MOTOR CONTROLLER SCHEDULE BELOW FOR RATINGS. COMBINATION CONTROLLERSSHOWN ON PLANS WITHOUT UNIT NUMBER INDICATED ARE TYPE MS1.MSx
CONTROLLERNUMBER
RATINGSMAXIMUM HP
MATCH CIRCUIT SERVING CONTROLLER
WIRE AND CONDUIT SIZEFROM CONTROLLER TO MOTOR208V 480V NEMA SIZE
MS1
FUNCTION
MS2
17.5 10
MS3
210 25
MS4
325 50
440 100
FVNR
FVNR
FVNR
FVNR MATCH CIRCUIT SERVING CONTROLLER
MATCH CIRCUIT SERVING CONTROLLER
MATCH CIRCUIT SERVING CONTROLLER
MATCH CIRCUIT SERVING CONTROLLERMS5 575 200 FVNR
MATCH CIRCUIT SERVING CONTROLLERMS6 6150 400 FVNR
MATCH CIRCUIT SERVING CONTROLLERMS7 7- 600 FVNR
MATCH CIRCUIT SERVING CONTROLLERMS8 8- 900 FVNR
NOTES:1. CONTROLLER NUMBERS ARE GENERAL DESIGNATIONS TO INDICATE CONTROLLER TYPE AND DO NOT INDICATE A UNIQUE
IDENTIFIER. REFER TO PLAN DRAWINGS FOR QUANTITIES OF EACH CONTROLLER TYPE REQUIRED. ALL CONTROLLERS ARE600V THREE-PHASE.
2. COORDINATE MOTOR CONTROLLER REQUIREMENTS WITH THE ASSOCIATED MOTOR AND CONTROL REQUIREMENTSINDICATED ELSEWHERE IN THE PROJECT DOCUMENTS. PROVIDE AUXILIARY CONTACTS, BUTTONS, INDICATING DEVICES,AND OTHER ACCESSORIES AS REQUIRED.
3. PROVIDE HAND-OFF-AUTOMATIC SWITCH FOR EACH COMBINATION MOTOR CONTROLLER THAT REQUIRES INTERLOCKS ORAUTOMATIC CONTROL. PROVIDE ON-OFF PUSHBUTTON STATION FOR ALL OTHER COMBINATION CONTROLLERS.
4. LOCATE COMBINATION CONTROLLERS AS CLOSE AS PRACTICABLE TO EQUIPMENT SERVED, AND IN ACCORDANCE WITHTHE NATIONAL ELECTRIC CODE. PROVIDE FINAL CONNECTIONS TO ASSOCIATED EQUIPMENT.
5. INTERNAL CONTROL WIRING SHALL BE TERMINATED ON SCREW-TYPE TERMINAL STRIPS. TERMINAL STRIPS SHALL BEPROPERLY IDENTIFIED FOR CONNECTING FIELD CONTROL WIRING.
6. PROVIDE TWO NORMALLY-OPEN AND TWO NORMALLY-CLOSED AUXILIARY CONTACTS WIRED TO INTERNAL TERMINALSTRIPS FOR EACH CONTROLLER.
7. PROVIDE GREEN "ON" AND RED "RUNNING" PILOT LIGHTS. PROVIDE ONE NORMALLY-ON AND ONE NORMALLY-OFF CONTACTFOR EACH CONTROLLER (ON/RUNNING) CONDITION.
8. PROVIDE PHASE-FAILURE AND ADJUSTABLE UNDERVOLTAGE PROTECTION (ON EACH PHASE) FOR EACH COMBINATIONCONTROLLER. ABNORMAL CONDITIONS SHALL BE INDICATED VIA PILOT LIGHTS.
9. CONTROLLER DISCONNECT SWITCHES SHALL BE RATED FOR THE MAXIMUM AVAILABLE FAULT CURRENT, AND SHALL BERATED IN HORSEPOWER TO MEET THE REQUIREMENTS OF THE EQUIPMENT SERVED.
10. PROVIDE FULLY-RATED EQUIPMENT GROUND LUGS FOR EACH COMBINATION MOTOR CONTROLLER.
11. PROVIDE NAMEPLATE FOR EACH COMBINATION MOTOR CONTROLLER MOUNTED ON FRONT OF UNIT ENCLOSURE.NAMEPLATE SHALL INDICATE CONTROLLER DESIGNATION, EQUIPMENT SERVED, AND UNIT RATINGS (HORSEPOWER,VOLTAGE, AND POLES.)
12. PROVIDE THE FOLLOWING COMBINATION CONTROLLER ACCESSORIES WHERE INDICATED: DM - DIGITAL METERING MONITOR TM - ELAPSED TIME METER
NOTES:
DS10
DS9
DS12
DS11
DS2
DS3
DS4
DS5
DS6
DS7
DS8
600
600
600
600
600
600
600
600
600
600
600
200
600
400
800
60
30
30
200
100
100
60
6
3
3
3
3
6
3
6
3
3
6
FS10
FS9
FS12
FS11
FS3
FS2
FS4
FS5
FS6
FS7
FS8
600
600
600
600
600
600
600
600
600
600
600
200
600
400
800
60
30
30
60
100
200
100
ENCLOSED NON-FUSED DISCONNECT SWITCH. DSx INDICATES SWITCH NUMBER;REFER TO ENCLOSED DISCONNECT SWITCH SCHEDULE BELOW FOR RATINGS.SWITCHES SHOWN ON PLANS WITHOUT SWITCH NUMBER INDICATED ARE TYPE DS2.
ENCLOSED FUSED DISCONNECT SWITCH. FSx INDICATES SWITCH NUMBER;REFER TO ENCLOSED DISCONNECT SWITCH SCHEDULE BELOW FOR RATINGS.SWITCHES SHOWN ON PLANS WITHOUT SWITCH NUMBER INDICATED ARE TYPE FS2.
SWITCHNUMBER
DS1
DSx
FSx
RATINGS
AMPERAGEVOLTAGE
600 30
POLES
2
SWITCHNUMBER
FS1
VOLTAGE
600
RATINGS
AMPERAGE
30
6
3
3
3
3
6
3
6
3
3
6
POLES
2
1. SWITCH NUMBERS ARE GENERAL DESIGNATIONS TO INDICATE SWITCH TYPE AND DO NOT INDICATE A UNIQUE IDENTIFIER.
REFER TO PLAN DRAWINGS FOR QUANTITIES OF EACH SWITCH TYPE REQUIRED.
2. LOCATE DISCONNECT SWITCHES AS CLOSE AS PRACTICABLE TO EQUIPMENT SERVED, AND IN ACCORDANCE WITH THE
NATIONAL ELECTRIC CODE. PROVIDE FINAL CONNECTIONS TO ASSOCIATED EQUIPMENT.
3. DISCONNECT SWITCHES SHALL BE RATED FOR THE MAXIMUM AVAILABLE FAULT CURRENT, AND SHALL BE RATED IN
HORSEPOWER TO MEET THE REQUIREMENTS OF THE EQUIPMENT SERVED.
4. DISCONNECT SWITCHES SHALL BE SERVICE-ENTRANCE RATED WHERE REQUIRED.
5. COORDINATE EXACT FUSE SIZE FOR FUSED DISCONNECT SWITCHES WITH THE REQUIREMENTS OF EQUIPMENT SERVED.
6. PROVIDE BUILT-IN FUSE PULLERS FOR FUSED DISCONNECT SWITCHES RATED 200A AND SMALLER.
7. PROVIDE FULLY-RATED EQUIPMENT GROUND LUGS FOR EACH DISCONNECT SWITCH.
8. PROVIDE 100%-RATED NEUTRAL LUGS IN DISCONNECT SWITCHES FOR CIRCUITS THAT CONTAIN NEUTRAL CONDUCTORS.
PROVIDE 200%-RATED NEUTRAL LUGS IN DISCONNECT SWITCHES FOR CIRCUITS THAT CONTAIN 200%-RATED NEUTRALCONDUCTORS.
9. FOR DISCONNECT SWITCHES CONNECTED TO THE LOAD SIDE OF VARIABLE FREQUENCY CONTROLLERS, PROVIDEAUXILIARY SWITCH CONTACTS AND INTERCONNECT WIRING IN CONDUIT BACK TO CONTROLLER TO PROHIBIT VFD
OPERATION WHEN ASSOCIATED DISCONNECT SWITCH IS OPEN.
10. FOR DISCONNECT SWITCHES CONNECTED TO THE LINE SIDE OF ELEVATOR CONTROLLERS, PROVIDE AUXILIARY SWITCH
CONTACTS AND INTERCONNECT WIRING IN CONDUIT BACK TO CONTROLLER TO PROHIBIT TRANSFER TO BATTERY WHENASSOCIATED DISCONNECT SWITCH IS OPENED FOR MAINTENANCE.
11. PROVIDE NAMEPLATE FOR EACH DISCONNECT SWITCH MOUNTED ON FRONT OF SWITCH ENCLOSURE. NAMEPLATE SHALLINDICATE SWITCH TYPE (NON-FUSED OR FUSED), EQUIPMENT SERVED, AND SWITCH RATINGS (VOLTAGE, CURRENT, ANDPOLES.)
12. PROVIDE THE FOLLOWING DISCONNECT SWITCH ACCESSORIES:
A2 - AUXILIARY CONTACTS (2NO AND 2 NC)N1 - 100%%%-RATED NEUTRAL LUGS
'TDS' INDICATES ENCLOSED FUSED DISCONNECT SWITCH SIZED AND FUSED IN ACCORDANCE WITHPRIMARY OVERCURRENT PROTECTIVE DEVICE INDICATED IN TRANSFORMER SCHEDULE.TDS
NOTES:1. GROUND TRANSFORMER TO NEAREST AVAILABLE EFFECTIVELY-GROUNDED STRUCTURAL STEEL ELEMENT OR OTHER
GROUNDING ELECTRODE PER NATIONAL ELECTRIC CODE. BOND NEUTRAL OF TRANSFORMER SECONDARY TOTRANSFORMER CASE WITH BONDING JUMPER PER NATIONAL ELECTRIC CODE.
2. PRIMARY OCPD DEVICE SHALL ACCOMMODATE ASSOCIATED TRANSFORMER IN-RUSH CURRENT. TRANSFORMERS WITHHIGHER THAN TYPICAL IN-RUSH CURRENTS MAY REQUIRE A LARGER PRIMARY OCPD; INCREASE PRIMARY OCPD ANDASSOCIATED WIRE AND CONDUIT SIZES IF NECESSARY.
3. PROVIDE SECONDARY OVERCURRENT PROTECTION DEVICE WITHIN TEN FEET OF TRANSFORMER SECONDARY TERMINALSEITHER IN A PANELBOARD MAIN DEVICE OR AN INDIVIDUALLY-MOUNTED OVERCURRENT DEVICE.
4. MOUNT TRANSFORMERS UTILIZING DOUBLE-DEFLECTION NEOPRENE ISOLATION MOUNTS WITH 0.50 INCH DEFLECTION.
5. MAKE CONDUIT CONNECTIONS TO TRANSFORMERS SO THAT TRANSFER OF NOISE AND VIBRATION IS MINIMIZED. UTILIZE AMINIMUM OF 18-INCHES OF FLEXIBLE CONDUIT WHEN CONNECTING CONDUIT TO TRANSFORMERS.
6. ADJUST PRIMARY AND SECONDARY TAP SETTINGS TO COMPENSATE FOR VOLTAGE VARIATIONS. ADJUST SETTINGS TOSATISFY OWNER-PROVIDED EQUIPMENT REQUIREMENTS.
7. PROVIDE MINIMUM 4-INCH HIGH CONCRETE HOUSEKEEPING PADS FOR FLOOR-MOUNTED TRANSFORMERS.
TRANSFORMER DESIGNATION
TRANSFORMER TAG (REFER TO SCHEDULE BELOW FOR ASSOCIATED RATINGS)
DOT INDICATES SECONDARY SIDE OF TRANSFORMER.
GEC (REFER TO SCHEDULE BELOW FOR SIZE)
K-RATING (BLANK INDICATES NON K-RATED TRANSFORMER)
SYMBOL DESCRIPTION
208V/1ɸ
3/4"C, 2#12 & 1#12G
CL ≤ 650ft 650ft < CL ≤ 1030ft - - -
CL ≤ 320ft 320ft < CL ≤ 520ft 520ft < CL ≤ 820ft 820ft < CL ≤ 1300ft -
CL ≤ 180ft 180ft < CL ≤ 300ft 300ft < CL ≤ 470ft 470ft < CL ≤ 750ft 750ft < CL ≤ 1200ft
208V/3ɸ CL ≤ 280ft 280ft < CL ≤ 450ft 450ft < CL ≤ 700ft 700ft < CL ≤ 1150ft -
CL ≤ 140ft 140ft < CL ≤ 220ft 220ft < CL ≤ 350ft 350ft < CL ≤ 560ft 560ft < CL ≤ 900ft
CL ≤ 80ft 80ft < CL ≤ 130ft120V/1ɸ
480V/1ɸ
480V/3ɸ
277V/1ɸ
130ft < CL ≤ 200ft 200ft < CL ≤ 320ft 320ft < CL ≤ 500ft
3/4"C, 3#12 & 1#12G
3/4"C, 4#12 & 1#12G
3/4"C, 2#10 & 1#10G
3/4"C, 3#10 & 1#10G
3/4"C, 4#10 & 1#10G
1"C, 2#8 & 1#8G
1"C, 3#8 & 1#8G
1"C, 4#8 & 1#8G
1"C, 2#6 & 1#6G
1"C, 3#6 & 1#6G
1-1/4"C, 4#6 & 1#6G
1-1/4"C, 2#4 & 1#4G
1-1/4"C, 3#4 & 1#4G
1-1/2"C, 4#4 & 1#4G
2w20
3w20
4w20
CL ≤ 680ft 680ft < CL ≤ 1100ft - - -
CL ≤ 340ft 340ft < CL ≤ 550ft 550ft < CL ≤ 860ft 860ft < CL ≤ 1350ft -
CL ≤ 200ft 200ft < CL ≤ 320ft 320ft < CL ≤ 500ft 500ft < CL ≤ 800ft 800ft < CL ≤ 1260ft
CL ≤ 300ft 300ft < CL ≤ 480ft 480ft < CL ≤ 750ft 750ft < CL ≤ 1200ft -
CL ≤ 150ft 150ft < CL ≤ 240ft 240ft < CL ≤ 380ft 380ft < CL ≤ 600ft 600ft < CL ≤ 960ft
CL ≤ 80ft 80ft < CL ≤ 130ft 130ft < CL ≤ 210ft 210ft < CL ≤ 350ft 350ft < CL ≤ 550ft
3/4"C, 2#10 & 1#10G
3/4"C, 3#10 & 1#10G
3/4"C, 4#10 & 1#10G
1"C, 2#8 & 1#8G
1"C, 3#8 & 1#8G
1"C, 4#8 & 1#8G
1"C, 2#6 & 1#6G
1-1/4"C, 3#6 & 1#6G
1-1/4"C, 4#6 & 1#6G
1-1/4"C, 2#4 & 1#4G
1-1/4"C, 3#4 & 1#4G
1-1/2"C, 4#4 & 1#4G
1-1/4"C, 2#2 & 1#2G
1-1/2"C, 3#2 & 1#2G
2"C, 4#2 & 1#2G
CL ≤ 820ft 820ft < CL ≤ 1300ft - - -
CL ≤ 420ft 420ft < CL ≤ 660ft 660ft < CL ≤ 1050ft - -
CL ≤ 240ft 240ft < CL ≤ 380ft 380ft < CL ≤ 600ft 600ft < CL ≤ 950ft -
CL ≤ 360ft 360ft < CL ≤ 570ft 570ft < CL ≤ 900ft - -
CL ≤ 180ft 180ft < CL ≤ 280ft 280ft < CL ≤ 450ft 450ft < CL ≤ 710ft 710ft < CL ≤ 890ft
CL ≤ 100ft 100ft < CL ≤ 160ft 160ft < CL ≤ 260ft 260ft < CL ≤ 410ft 410ft < CL ≤ 520ft
1"C, 2#8 & 1#10G
1"C, 3#8 & 1#10G
1"C, 4#8 & 1#10G
1"C, 2#6 & 1#8G
1-1/4"C, 3#6 & 1#8G
1-1/4"C, 4#6 & 1#8G
1-1/4"C, 2#4 & 1#6G
1-1/4"C, 3#4 & 1#6G
1-1/2"C, 4#4 & 1#6G
1-1/4"C, 2#2 & 1#4G
1-1/2"C, 3#2 & 1#4G
2"C, 4#2 & 1#4G
1-1/2"C, 2#1 & 1#2G
2"C, 3#1 & 1#2G
2"C, 4#1 & 1#2G
2w35
3w35
4w35
2w25
3w25
4w25
CL ≤ 1050ft - - - -
CL ≤ 520ft 520ft < CL ≤ 840ft 840ft < CL ≤ 1300ft - -
CL ≤ 300ft 300ft < CL ≤ 480ft 480ft < CL ≤ 760ft 760ft < CL ≤ 960ft -
CL ≤ 450ft 450ft < CL ≤ 720ft 720ft < CL ≤ 1150ft - -
CL ≤ 230ft 230ft < CL ≤ 360ft 360ft < CL ≤ 570ft 570ft < CL ≤ 720ft 720ft < CL ≤ 910ft
CL ≤ 130ft 130ft < CL ≤ 210ft 210ft < CL ≤ 330ft 330ft < CL ≤ 420ft 420ft < CL ≤ 520ft
1-1/4"C, 2#6 & 1#8G
1-1/4"C, 3#6 & 1#8G
1-1/4"C, 4#6 & 1#8G
1-1/4"C, 2#4 & 1#6G
1-1/4"C, 3#4 & 1#6G
1-1/4"C, 4#4 & 1#6G
1-1/2"C, 2#2 & 1#4G
1-1/2"C, 3#2 & 1#4G
1-1/2"C, 4#2 & 1#4G
1-1/2"C, 2#1 & 1#2G
2"C, 3#1 & 1#2G
2"C, 2#1 & 1#2G
2"C, 2#1/0 & 1#1G
2"C, 3#1/0 & 1#1G
2"C, 4#1/0 & 1#1G
CL ≤ 1150ft - - - -
CL ≤ 600ft 600ft < CL ≤ 940ft - - -
CL ≤ 340ft 340ft < CL ≤ 540ft 540ft < CL ≤ 680ft 680ft < CL ≤ 860ft 860ft < CL ≤ 1080ft
CL ≤ 510ft 510ft < CL ≤ 810ft 810ft < CL ≤ 1020ft - -
CL ≤ 260ft 260ft < CL ≤ 410ft 410ft < CL ≤ 520ft 520ft < CL ≤ 650ft 650ft < CL ≤ 810ft
CL ≤ 150ft 150ft < CL ≤ 240ft 240ft < CL ≤ 300ft 300ft < CL ≤ 370ft 370ft < CL ≤ 470ft
1-1/4"C, 2#4 & 1#8G
1-1/4"C, 3#4 & 1#8G
1-1/4"C, 4#4 & 1#8G
1-1/4"C, 2#2 & 1#6G
1-1/2"C, 3#2 & 1#6G
1-1/2"C, 4#2 & 1#6G
1-1/2"C, 2#1 & 1#4G
2"C, 3#1 & 1#4G
2"C, 4#1 & 1#4G
1-1/2"C, 2#1/0 & 1#2G
2"C, 3#1/0 & 1#2G
2"C, 4#1/0 & 1#2G
2"C, 2#2/0 & 1#1G
2"C, 3#2/0 & 1#1G
2-1/2"C, 4#2/0 & 1#1G
2w45
3w45
4w45
2w60
3w60
4w60
208V/1ɸ
208V/3ɸ
120V/1ɸ
480V/1ɸ
480V/3ɸ
277V/1ɸ
208V/1ɸ
208V/3ɸ
120V/1ɸ
480V/1ɸ
480V/3ɸ
277V/1ɸ
208V/1ɸ
208V/3ɸ
120V/1ɸ
480V/1ɸ
480V/3ɸ
277V/1ɸ
208V/1ɸ
208V/3ɸ
120V/1ɸ
480V/1ɸ
480V/3ɸ
277V/1ɸ
2w30
3w30
4w30
2w40
3w40
4w40
2w50
3w50
4w50
2w70
3w70
4w70
NOTES:
1. THIS SCHEDULE DEFINES MINIMUM WIRE AND CONDUIT SIZES FOR EACH CIRCUIT TAG INDICATED. WHEREVER CIRCUIT TAGSARE INDICATED ON DRAWINGS, DETERMINE MINIMUM WIRE AND CONDUIT SIZE REQUIRED BY SELECTING THE APPROPRIATEROW FOR ACTUAL CIRCUIT VOLTAGE/PHASE AND THEN SELECTING THE APPROPRIATE COLUMN FOR ACTUAL CABLE LENGTHOF CIRCUIT (CL) BASED ON PROPOSED FIELD ROUTING. ONCE THE APPROPRIATE COLUMN IS SELECTED, THE REQUIREDMINIMUM WIRE AND CONDUIT SIZES ARE IDENTIFIED BY THE INTERSECTION OF THAT COLUMN AND THE ROW FOR THEASSOCIATED CIRCUIT TAG.
2. WIRE AND CONDUIT TAGS REPRESENT BASE AMPACITY AND NUMBER OF WIRES (NOT INCLUDING GROUNDS.) BASEAMPACITIES INDICATED ARE VALID FOR 90°C RATED COPPER CONDUCTORS (APPLIED AT THEIR 60°C RATING) IN 30°C AMBIENTTEMPERATURE. INCREASE WIRE AND CONDUIT SIZES TO COMPENSATE FOR LOWER TEMPERATURE RATED WIRES AND HIGHERAMBIENT TEMPERATURES.
3. WHERE OVERSIZED CONDUCTORS ARE TOO LARGE TO DIRECTLY CONNECT TO SOURCE OR DEVICE TERMINALS, TRANSITIONTO SMALLER CONDUCTORS (NO LESS THAN MINIMUM SIZE SHOWN FOR THAT CIRCUIT TAG IN SCHEDULE ABOVE) TOACCOMMODATE REQUIRED TERMINATIONS. PROVIDE SPLICES, WIRE REDUCERS OR POWER BLOCKS IN APPROPRIATELY SIZEDJUNCTION BOXES TO TRANSITION BETWEEN DIFFERENT SIZE CONDUCTORS. LENGTHS OF CONDUCTOR BETWEEN TRANSITIONTO SMALLER CABLE AND FINAL TERMINATION SHOULD BE LIMITED TO NO MORE THAN 10 FEET WHEREVER POSSIBLE.
4. 240V/1Ø CIRCUITS SHALL USE WIRE AND CONDUIT SIZES INDICATED ABOVE FOR 208V/1Ø CIRCUITS, EXCEPT MAXIMUMALLOWABLE DISTANCES INDICATED MAY BE INCREASED BY 15%.
5. FOR CIRCUIT LENGTHS EXCEEDING MAXIMUM LENGTHS SHOWN IN SCHEDULE ABOVE, UPSIZE WIRE AND CONDUIT SIZES ASREQUIRED TO LIMIT VOLTAGE DROP TO NO MORE THAN 3% (FOR BRANCH CIRCUITS) AT 70% CIRCUIT LOADING. (FOR EXAMPLE,20-AMP CIRCUIT CONDUCTORS ARE ASSUMED TO BE CARRYING 14 AMPS.) VOLTAGE DROP SHALL BE LIMITED TO 2% WHENCIRCUITS ARE TO BE USED AS FEEDERS.
6. WHERE CIRCUITS ARE TO BE USED FOR FEEDERS, RATHER THAN BRANCH CIRCUITS, VOLTAGE DROP SHALL BE LIMITED TO NOMORE THAN 2%. ALLOWABLE MAXIMUM DISTANCES INDICATED IN SCHEDULE ABOVE SHALL BE REDUCED BY 33%.
7. CONDUIT SIZES INDICATED ARE VALID FOR THHN/THWN AND XHHW CONDUCTOR TYPES INSTALLED IN EMT, ENT, FMC, IMC,LFMC, RMC AND RIGID PVC (SCHEDULE 80, SCHEDULE 40, TYPE A, AND TYPE EB) CONDUIT TYPES. INCREASE CONDUIT SIZESAS REQUIRED TO COMPENSATE FOR CONDUCTOR TYPES WITH LARGER OVERALL DIAMETERS AND FOR CONDUIT TYPES WITHSMALLER INTERNAL DIAMETERS.
8. CONDUIT SIZES INDICATED ARE REQUIRED MINIMUM SIZES AND MAY BE INCREASED FOR LONG RUNS OR WHERE MULTIPLEBENDS ARE NECESSARY.
9. CONDUITS SMALLER THAN 3 INCHES SHALL BE UPGRADED TO THE NEXT LARGER TRADE SIZE WHEN USED FORDIRECT-BURIED AND IN-SLAB INSTALLATIONS.
10. UPGRADE CONDUIT SIZES FOR CIRCUITS RUN IN CONCRETE-ENCASED UNDERGROUND DUCTBANKS TO THE SIZES INDICATEDFOR THE DUCTBANK CONDUITS.
11. TAGS WITH ISOLATED GROUND (+IG) INDICATED SHALL INCLUDE A SEPARATE IG CONDUCTOR, SAME SIZE AS ASSOCIATEDCIRCUIT GROUND CONDUCTOR, TIED TO THE IG BUS. CONDUIT SIZES INDICATED IN SCHEDULE ABOVE ARE LARGE ENOUGH TOACCOMMODATE AN IG CONDUCTOR IN ADDITION TO CONDUCTORS SHOWN.
3w4004"C, 3-600kcmil
& 1#2 G
3w3503-1/2"C, 3-500kcmil
& 1#2 G
3w3003"C, 3-350kcmil
& 1#3 G
3w2502-1/2"C, 3-250kcmil
& 1#3 G
3w225 2-1/2"C, 3#4/0 & 1#4 G
3w200 2"C, 3#3/0 & 1#4 G
3w175 2"C, 3#2/0 & 1#4 G
2"C, 3#1/0 & 1#4 G
1-1/2"C, 3#1 & 1#6 G
3w90 1-1/4"C, 3#2 & 1#6 G
3w80 1-1/4"C, 3#3 & 1#6 G
3w4000(10) 4"C, 3-600kcmil &
1-500kcmil G
3w3000(8) 4C, 3-500kcmil &
1-400kcmil G
3w2500(6) 4"C, 3-600kcmil &
1-350kcmil G
3w2000(5) 4"C, 3-600kcmil &
1-250kcmil G4w2000
(5) 4"C, 4-600kcmil &1-250kcmil G
5w2000(6) 4"C, 5-500kcmil &
1-250kcmil G
3w1600(4) 4"C, 3-600kcmil &
1#4/0 G
3w1200(3) 4"C, 3-600kcmil &
1#3/0 G
3w1000(3) 3"C, 3-400kcmil &
1#2/0 G
3w800(2) 4"C, 3-600kcmil &
1#1/0 G
3w700(2) 3-1/2"C, 3-500kcmil &
1#1/0 G
3w600(2) 3"C, 3-350kcmil
& 1#1 G
3w500(2) 3"C, 3-250kcmil
& 1#2 G
3w450(2) 2-1/2"C, 3#4/0
& 1#2 G
NOTES:
1. WIRE AND CONDUIT TAGS REPRESENT BASE AMPACITY AND NUMBER OF WIRES (NOT INCLUDING GROUNDS.)
2. BASE AMPACITIES INDICATED ARE VALID FOR 90°C RATED COPPER CONDUCTORS (APPLIED AT THEIR 60°C RATING FOR #1AWGAND SMALLER; APPLIED AT THEIR 75°C RATING FOR #1/0AWG AND LARGER) IN 30°C AMBIENT TEMPERATURE. INCREASE WIREAND CONDUIT SIZES TO COMPENSATE FOR LOWER TEMPERATURE RATED WIRES AND HIGHER AMBIENT TEMPERATURES.
3. INCREASE WIRE AND CONDUIT SIZES AS REQUIRED TO LIMIT VOLTAGE DROP FOR FEEDERS TO NO GREATER THAN 2% ANDFOR BRANCH CIRCUITS TO NO GREATER THAN 3%. CALCULATE VOLTAGE DROP AT 70% CIRCUIT LOADING. (FOR EXAMPLE,80-AMP CIRCUIT CONDUCTORS ARE ASSUMED TO BE CARRYING 56 AMPS.)
4. CONDUIT SIZES INDICATED ARE VALID FOR THHN/THWN AND XHHW CONDUCTOR TYPES INSTALLED IN EMT, ENT, FMC, IMC,LFMC, RMC AND RIGID PVC (SCHEDULE 80, SCHEDULE 40, TYPE A, AND TYPE EB) CONDUIT TYPES UNLESS INDICATEDOTHERWISE. INCREASE CONDUIT SIZES AS REQUIRED TO COMPENSATE FOR CONDUCTOR TYPES WITH LARGER OVERALLDIAMETERS AND FOR CONDUIT TYPES WITH SMALLER INTERNAL DIAMETERS.
5. FOR CIRCUITS INDICATED, INCREASE CONDUIT SIZE TO 5-INCHES WHEN USING RIGID PVC SCHEDULE 80.
6. CONDUIT SIZES INDICATED ARE REQUIRED MINIMUM SIZES AND MAY BE INCREASED FOR LONG RUNS OR WHERE MULTIPLEBENDS ARE NECESSARY.
7. CONDUITS SMALLER THAN 3 INCHES SHALL BE UPGRADED TO THE NEXT LARGER TRADE SIZE WHEN USED FORDIRECT-BURIED AND IN-SLAB INSTALLATIONS.
8. UPGRADE CONDUIT SIZES FOR CIRCUITS RUN IN CONCRETE-ENCASED UNDERGROUND DUCTBANKS TO THE SIZES INDICATEDFOR THE DUCTBANK CONDUITS.
9. TAGS WITH ISOLATED GROUND (+IG) INDICATED SHALL INCLUDE A SEPARATE IG CONDUCTOR, SAME SIZE AS ASSOCIATEDCIRCUIT GROUND CONDUCTOR, TIED TO THE IG BUS. CONDUIT SIZES INDICATED IN SCHEDULE ABOVE ARE LARGE ENOUGH TOACCOMMODATE AN IG CONDUCTOR IN ADDITION TO CONDUCTORS SHOWN.
4w80 1-1/2"C, 4#3 & 1#6 G 5w80 1-1/2"C, 5#3 & 1#6 G
4w90 1-1/2"C, 4#2 & 1#6 G 5w90 2"C, 5#2 & 1#6 G
2"C, 4#1 & 1#6 G 2"C, 5#1 & 1#6 G
2"C, 4#1/0 & 1#4 G 2"C, 5#1/0 & 1#4 G
4w175 2"C, 4#2/0 & 1#4 G 5w175 2-1/2"C, 5#2/0 & 1#4 G
4w200 2-1/2"C, 4#3/0 & 1#4 G 5w200 2-1/2"C, 5#3/0 & 1#4 G
4w225 2-1/2"C, 4#4/0 & 1#4 G 5w225 3"C, 5#4/0 & 1#4 G
4w2503"C, 4-250kcmil
& 1#3 G5w250
3"C, 5-250kcmil& 1#3 G
4w3003-1/2"C, 4-350kcmil
& 1#3 G5w300
3-1/2"C, 5-350kcmil& 1#3 G
4w3504"C, 4-500kcmil
& 1#2 G5w350
4"C, 5-500kcmil& 1#2 G
4w4004"C, 4-600kcmil
& 1#2 G5w400
4"C, 5-600kcmil& 1#2 G
4w2500(6) 4"C, 4-600kcmil &
1-350kcmil G5w2500
(8) 4"C, 5-500kcmil &1-350kcmil G
4w3000(8) 4"C, 4-500kcmil &
1-400kcmil G5w3000
(9) 4"C, 5-500kcmil &1-400kcmil G
4w4000(10) 4"C, 4-600kcmil &
1-500kcmil G5w4000
(12) 4"C, 5-500kcmil &1-500kcmil G
4w1600(4) 4"C, 4-600kcmil &
1#4/0 G5w1600
(5) 4"C, 5-500kcmil &1#4/0 G
4w1200(3) 4"C, 4-600kcmil &
1#3/0 G5w1200
(4) 3-1/2"C, 5-400kcmil &1#3/0 G
4w1000(3) 3-1/2"C, 4-400kcmil &
1#2/0 G5w1000
(3) 4"C, 5-500kcmil &1#2/0 G
4w800(2) 4"C, 4-600kcmil &
1#1/0 G5w800
(2) 4"C, 5-600kcmil &1#1/0 G
4w700(2) 4"C, 4-500kcmil &
1#1/0 G5w700
(2) 4"C, 5-500kcmil &1#1/0 G
4w600(2) 3-1/2"C, 4-350kcmil
& 1#1 G5w600
(2) 3-1/2"C, 5-350kcmil& 1#1 G
4w500(2) 3"C, 4-250kcmil
& 1#2 G5w500
(2) 3"C, 5-250kcmil& 1#2 G
4w450(2) 2-1/2"C, 4#4/0
& 1#2 G5w450
(2) 3"C, 5#4/0& 1#2 G
NOTE 5
NOTE 5
NOTE 5
NOTE 5
NOTE 5
NOTE 5
NOTE 5
3w110
3w100
3w125
3w150
4w110
4w100
4w125
4w150
5w110
5w100
5w125
5w150
2"C, 3#1/0 & 1#6 G 2"C, 4#1/0 & 1#6 G 2"C, 5#1/0 & 1#6 G
SYMBOL DESCRIPTION
WIRE ANDCONDUIT
3w1000
3w600
3w450
3w300
3w225
3w150
3w90
3w60
3w30
3w20
XFMRTAG
T10
T9
T8
T7
T6
T5
T4
T3
T2
T1
SIZE(kVA)
500
300
225
150
112.5
75
45
30
15
9
PRIOCPD
1000A/3P
600A/3P
450A/3P
300A/3P
225A/3P
150A/3P
90A/3P
60A/3P
30A/3P
20A/3P
WIRE ANDCONDUIT
GECSIZE
SECOCPD
1600A/3P
1000A/3P
800A/3P
500A/3P
400A/3P
250A/3P
150A/3P
100A/3P
50A/3P
35A/3P
#3/0
#3/0
#3/0
#2/0
#1/0
#2
#6
#6
#8
#8
WIRE ANDCONDUIT
GECSIZE
#3/0
#3/0
#2/0
#1/0
#2
#4
#6
#8
#8
K-RATEDNON K-RATED
SECONDARY(208Y/120V)
PRIMARY(480V)
(4)4"C, 4-600kcmil& 1#4/0 G
(3)4"C, 4-400kcmil& 1#3/0 G
(2)4"C, 4-600kcmil& 1#3/0 G
(2)3"C, 4-250kcmil& 1#2/0 G
4"C, 4-600kcmil& 1#1/0 G
3"C, 4-250kcmil& 1#2 G
2"C, 4#1/0& 1#6 G
2"C, 4#1& 1#6 G
1"C, 4#6& 1#8 G
3/4"C, 4#8& 1#8 G
(6)4"C, 5-350kcmil &1-300kcmil G
(3)4"C, 5-500kcmil& 1#4/0 G
(3)4"C, 5-350kcmil& 1#3/0 G
(2)4"C, 5-300kcmil& 1#2/0 G
(2)3"C, 5#4/0& 1#1/0 G
4"C, 5-300kcmil& 1#2 G
2-1/2"C, 5#2/0& 1#4 G
2"C, 3#1, 2#1/0N& 1#6 G
1-1/2"C, 3#4, 1#1N& 1#8 G
1-1/4"C, 3#6, 1#3N& 1#8 G
#3/0
2 3 SBJSIZE
#4/0
#3/0
#3/0
#2/0
#1/0
#2
#6
#6
#8
#8
SBJSIZE
#4/0
#3/0
#2/0
#1/0
#2
#4
#6
#8
#8
300kcmil
DWG
E-001
E-002E-003
E-100
E-201
E-202E-203E-204
E-301
E-302E-303E-304
E-401
E-501
E-601
E-602
E-701E-702
E-801E-802E-803
SCALE
NO SCALE
NO SCALENO SCALE
1"=20'-0"
1/8" = 1' - 0"
1/8" = 1' - 0"1/8" = 1' - 0"1/8" = 1' - 0"
1/8" = 1' - 0"
1/8" = 1' - 0"1/8" = 1' - 0"1/8" = 1' - 0"
NO SCALE
NO SCALE
1/8" = 1' - 0"
NO SCALE
NO SCALENO SCALE
NO SCALENO SCALENO SCALE
DRAWING TITLE
ELECTRICAL LEGEND SHEET 1
ELECTRICAL LEGEND SHEET 2LIGHTING FIXTURE SCHEDULE
ELECTRICAL SITE PLAN
LEVEL 1 ELECTRICAL PLAN - POWER
LEVEL 2 ELECTRICAL PLAN - POWERLEVEL 3 ELECTRICAL PLAN - POWERROOF ELECTRICAL PLAN - POWER
LEVEL 1 ELECTRICAL PLAN - LIGHTING
LEVEL 2 ELECTRICAL PLAN - LIGHTINGLEVEL 3 ELECTRICAL PLAN - LIGHTINGROOF ELECTRICAL PLAN - LIGHTING
POWER DISTRIBUTION SINGLE LINE DIAGRAM
GROUNDING RISER DIAGRAM
LIGHTNING PROTECTION PLAN
LIGHTNING PROTECTION DETAILS
ELECTRICAL DETAILSELECTRICAL DETAILS
ELECTRICAL PANEL SCHEDULESELECTRICAL PANEL SCHEDULESELECTRICAL PANEL SCHEDULES
T3K-13
NT1
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
NTS
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-001
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
ELECTRICAL LEGENDSHEET 1
S
S
S
S
S SS
S S
X
NEMA DESIGNATIONSYMBOL
5-15R
14-30R
14-20R
14-15R
6-50R
6-30R
5-30R
5-20R
SYMBOL
15-30R
L14-20R
L6-20R
L5-30R
L5-20R
15-60R
15-50R
NEMA DESIGNATION
L14-30R
L6-30R
14-50R L15-20R
14-60R L15-30R
15-15R L16-20R
15-20R L16-30R
5-50R
6-15R
6-20R
L5-15R
L6-15R
SPECIAL PURPOSE RECEPTACLE SCHEDULE
2
3
4
5
6
7
8
9
1
17
18
19
20
21
22
23
24
16
10 25
11 26
12 27
13 28
14 29
15 30
F1
F2
PCR
NT1
POWER CONNECTION FOR AUTOMATIC DOORS.AD
M
MECHANICAL EQUIPMENT TAG, REFER TO SCHEDULES ON MECHANICAL DRAWINGS FOREQUIPMENT RATINGS AND REQUIREMENTS.
2
*
S
S
FL
WIRE AND CONDUIT TAG. "2" INDICATES NUMBER OF CONDUCTORS (NOT INCLUDING GROUNDS)AND "20" INDICATES BASE AMPACITY OF CIRCUIT. REFER TO BRANCH CIRCUIT SCHEDULE ANDFEEDER SCHEDULE FOR COMPLETE LIST OF WIRE AND CONDUIT TAGS.
DH
FA
FSD
1. WORK SHOWN ON THESE PLANS IS NEW UNLESS NOTED OTHERWISE.
2. COMPONENTS SHOWN ON THE RISER DIAGRAMS, BUT NOT ON THE PLAN OR VICE VERSA, SHALL BE INCLUDED AS IFSHOWN ON BOTH.
3. PROVIDE ELECTRICAL CONNECTIONS FOR EQUIPMENT SHOWN ON CONTRACT DOCUMENTS OF OTHER TRADES. REFERTO THOSE DOCUMENTS TO DETERMINE ELECTRICAL CONNECTION REQUIREMENTS AND MOUNTING LOCATIONS FOR
EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS.
4. REFER TO ARCHITECTURAL CONTRACT DOCUMENTS FOR PROJECT PHASING, AND FOR MOUNTING HEIGHTS AND
LOCATIONS OF ELECTRICAL EQUIPMENT AND DEVICES.
5. ELECTRICAL COMPONENTS, DEVICES AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70,
ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION, AND MARKED FOR INTENDEDUSE.
6. COMPLY WITH NFPA 70 AND ALL OTHER APPLICABLE CODES AND STANDARDS.
7. DRAWINGS INDICATE MAXIMUM DIMENSIONS FOR ELECTRICAL COMPONENTS AND EQUIPMENT, INCLUDING CLEARANCESBETWEEN ENCLOSURES, ADJACENT SURFACES AND OTHER ITEMS. COMPLY WITH INDICATED MAXIMUM DIMENSIONS.
8. COORDINATE LAYOUT AND INSTALLATION OF ELECTRICAL EQUIPMENT AND COMPONENTS WITH OTHER CONSTRUCTION,INCLUDING CONDUIT, PIPING, EQUIPMENT, AND ADJACENT SURFACES. MAINTAIN REQUIRED WORKSPACE CLEARANCESAND REQUIRED CLEARANCES FOR EQUIPMENT ACCESS DOORS AND PANELS.
9. BRANCH CIRCUITING HOMERUNS SHOWN ON THE DRAWINGS WITH MORE THAN 3 CURRENT-CARRYING CONDUCTORSARE SHOWN DIAGRAMATICALLY. DO NOT INSTALL MORE THAN 3 CURRENT-CARRYING CONDUCTORS IN A RACEWAY
UNLESS DONE SO STRICTLY BY THE NATIONAL ELECTRIC CODE. IN ADDITION, ALL CIRCUITS SHALL BE PROVIDED PERTHE PANELBOARD SCHEDULES AND SINGLE-LINE DIAGRAMS. DO NOT USE SHARED NEUTRALS UNLESS SPECIFICALLY
INDICATED.
10. OBTAIN APPROVALS FROM STRUCTURAL ENGINEER PRIOR TO EMBEDDING ELECTRICAL CONDUITS IN FLOOR SLABS AND
IN OTHER STRUCTURAL ELEMENTS. CONDUITS EMBEDDED IN FLOOR SLABS SHALL BE RUN IN MIDDLE THIRD OF SLABTHICKNESS.
11. CONDUITS AND RACEWAYS SHALL BE RUN CONCEALED; EXCEPT EXPOSED RACEWAYS AND CONDUITS ARE ACCEPTABLEWITHIN ELECTRICAL AND MECHANICAL ROOMS. RECESS-MOUNT WIRING DEVICES (RECEPTACLES, SNAP SWITCHES,DIMMING SWITCHES, ETC), AND BACKBOXES UNLESS OTHERWISE NOTED.
12. PROVIDE RECESSED PANELBOARDS WITH (4) 1-1/2" SPARE CONDUITS STUBBED UP TO 6 INCHES ABOVE FINISHEDCEILING. PROVIDE PULLSTRINGS AND CAP CONDUITS.
13. RACEWAYS RUNNING THROUGH BUILDING EXPANSION JOINTS SHALL BE EQUIPPED WITH EXPANSION FITTINGS.
14. EMPTY (SPARE) CONDUIT SHALL BE DEBURRED, CLEANED, CAPPED, TAGGED, AND FURNISHED WITH PULL WIRES.
15. SUBMIT VENDOR DESIGNED AND APPROVED LAYOUT DRAWINGS OF OCCUPANCY AND DAYLIGHT SENSORS AS PART OFOCCUPANCY AND DAYLIGHT SENSOR PRODUCT DATA SUBMITTAL PACKAGE. LOCATIONS OF SENSORS SHOWN ON THESEDRAWINGS IS GENERIC AND MAY REQUIRE MODIFICATION TO MEET VENDOR-SPECIFIC REQUIREMENTS OR LIMITATIONS.
SENSOR QUANTITIES SHOWN ON DRAWINGS ARE MINIMUM QUANTITIES; PROVIDE ADDITIONAL SENSORS AS REQUIREDTO ENSURE ADEQUATE COVERAGE.
16. PROVIDE AND COORDINATE WITH STRUCTURAL ENGINEER ALL CORE DRILLS, CONDUIT SLEEVES, RISER SLEEVES ANDOTHER PENETRATIONS REQUIRED TO ACCOMMODATE ROUTING OF ELECTRICAL CONDUITS, CONDUCTORS AND OTHER
PATHWAY ELEMENTS. PATCH AND SEAL ALL PENETRATIONS, AND PROVIDE FIRESTOPPING AS REQUIRED. SEALPENETRATIONS THROUGH INSULATED PARTITION WALLS WITH APPROPRIATE CAULK OR HIGH-DENSITY PUTTY,FIRE-RATED AS REQUIRED.
17. IN INSULATED PARTITION WALLS, LOCATE ELECTRICAL OUTLETS AND DEVICE BACKBOXES IN ADJACENT SPACES NOCLOSER THAN 24 INCHES APART AND IN SEPARATE STUD SPACES. UTILIZE ACOUSTICAL CAULKING TO SEAL GAPS
BETWEEN OUTLET AND OTHER DEVICE BACKBOXES AND DRYWALL.
18. PROVIDE BRACING AND SUPPORTS FOR ELECTRICAL EQUIPMENT AND DEVICES. BOND AND GROUND METALLIC BRACES
AND SUPPORTS.
19. PROVIDE CONCRETE HOUSEKEEPING PADS FOR FREESTANDING EQUIPMENT. MINIMUM DIMENSIONS: 4 INCHES LARGERIN BOTH DIRECTIONS THAN SUPPORTED UNIT AND AT LEAST 4 INCHES HIGH.
20. COORDINATE LAYOUT AND INSTALLATION OF ALL ELECTRICAL WORK WITH OTHER TRADES. ASSIST IN THE PREPARATIONOF COORDINATION DRAWINGS THAT ARE TO INCLUDE THE WORK OF ALL TRADES. MAINTAIN A SET OF UP-TO-DATECOORDINATION DRAWINGS AS CONSTRUCTION PROGRESSES.
21. MAINTAIN A CURRENT SET OF "AS-BUILT" DRAWINGS ON-SITE AS THE WORK PROGRESSES. THE OWNER OR ENGINEERMAY REQUEST TO SEE THESE "AS-BUILT" DRAWINGS AT ANY TIME. PROVIDE A SET OF FINAL "AS-BUILT" DRAWINGS TO
THE OWNER IN AUTOCAD FORMAT AT THE END OF THE PROJECT.
22. RETAIN THE SERVICES OF A LICENSED ROOFING CONTRACTOR, WHO IS CERTIFIED BY THE MANUFACTURER OF THEROOF BEING PENETRATED, TO PERFORM REQUIRED ROOF PENETRATIONS.
23. PROVIDE VIBRATION ISOLATION FOR ELECTRICAL EQUIPMENT IN ACCORDANCE WITH VIBRATION ISOLATION SCHEDULEON MECHANICAL DRAWINGS.
24. COORDINATE CONDUCTOR SIZES AND QUANTITIES INDICATED WITH ASSOCIATED EQUIPMENT TERMINAL LUGS TOENSURE COMPATIBILITY. PROVIDE LUGS TO ACCEPT CONDUCTORS INDICATED, OR UTILIZE ALTERNATE CONDUCTORCONFIGURATION THAT IS APPROPRIATE FOR LUGS PROVIDED. ALTERNATE CONDUCTOR CONFIGURATION USED SHALL
PROVIDE AN EQUAL OR GREATER CURRENT-CARRYING CAPACITY TO THAT INDICATED. REVISE ASSOCIATED CONDUITSIZES AND QUANTITIES AS REQUIRED.
*
*
*
FA
BAS
ES
N S
VV
BH
*
**
*
*
TP
TM
PM
U
R
GENERAL ELECTRIC SYMBOLS GENERAL ELECTRICAL NOTESGENERAL ELECTRICAL SYMBOLSGENERAL ELECTRIC SYMBOLS
SYMBOL DESCRIPTION SYMBOL DESCRIPTIONSYMBOL DESCRIPTION
X
NP1-2
TC
HOMERUN TO PANEL "NP1" CIRCUIT 2.
FIXED-MOUNTED CIRCUIT BREAKER
FLUSH FLOOR MOUNTED NEMA 5-20R DUPLEX RECEPTACLE.
HOMERUN TO PANEL "NP1" CIRCUITS 1, 3, AND 5.THIS INDICATES THREE INDIVIDUAL CIRCUITS.
NP1-1,3,5
DENOTES ELECTRICAL PANEL THAT SERVICES THE AREA DESIGNATED OR THE GIVEN ROOM,UNLESS INDICATED OTHERWISE.
K
AUTOMATIC TRANSFER SWITCH WITH BYPASS ISOLATION SWITCH; CONFIGURED FOROPEN-TRANSITION TRANSFER; DESIGNATION AND RATINGS AS INDICATED. PROVIDE CONTROLAND COMMUNICATIONS WIRING IN CONDUIT (OR MI CABLE WHERE SHOWN OR REQUIRED)BETWEEN TRANSFER SWITCH AND ASSOCIATED REMOTE EQUIPMENT FOR ALL REQUIREDTRANSFER SWITCH FUNCTIONS AND MONITORING INCLUDING GENERATOR START-UP ANDSHUT-DOWN, ELEVATOR EMERGENCY MODE OPERATION, ELEVATOR RE-TRANSFER DELAY,REMOTE ANNUNCIATORS, ETC.
DRAW-OUT CIRCUIT BREAKER
J
CP
VFD
J
J
LOW-VOLTAGE SWITCH AND FUSE
SYSTEM GROUND OR EQUIPMENT GROUND
LIGHTNING ARRESTORLA
POWER MONITOR (ELECTRONIC MULTI-FUNCTION MULTI-METER)
TENANT (APARTMENT) METER,E-MON/D-MON CLASS 5000 WITH MODBUS TCP/IP CONNECTION TO BAS
POTENTIAL TRANSFORMER (PT)
CURRENT TRANSFORMER (CT)
CONTROL PANEL FOR PACKAGED EQUIPMENT
VARIABLE FREQUENCY DRIVE ( VARIABLE FREQUENCY CONTROLLER)
MOTOR. REFER TO ASSOCIATED EQUIPMENT SCHEDULE FOR HORSEPOWER RATING
FRACTIONAL HORSEPOWER MANUAL MOTOR CONTROLLER
PANELBOARD, SURFACE-MOUNTED, 208Y/120 VOLT
PANELBOARD, RECESSED-MOUNTED, 208Y/120 VOLT
PANELBOARD, SURFACE-MOUNTED, 480Y/277V VOLT
PANELBOARD, RECESSED-MOUNTED, 480Y/277V VOLT
WALL-MOUNTED JUNCTION BOX. PROVIDE FINAL CONNECTIONS TO ASSOCIATED EQUIPMENT.SYMBOL WITH "S" DENOTES RECEPTACLE CONNECTED TO STANDBY CIRCUIT.
CEILING-MOUNTED JUNCTION BOX. PROVIDE FINAL CONNECTIONS TO ASSOCIATED EQUIPMENT.SYMBOL WITH "S" DENOTES RECEPTACLE CONNECTED TO STANDBY CIRCUIT.
TIME CLOCK/SWITCH
ST SHUNT-TRIP
KEY-INTERLOCK
FUSE, RATING AND CLASS AS INDICATED
NEMA 5-20R DUPLEX RECEPTACLE, IN SURFACE-MOUNTED RACEWAY.
NEMA 5-20R SIMPLEX RECEPTACLE
NEMA 5-20R DOUBLE-DUPLEX (QUAD) RECEPTACLE.
SPECIAL PURPOSE RECEPTACLE.
"X" INDICATES TYPE, REFER TO SPECIAL PURPOSE RECEPTACLE SCHEDULE ON THIS SHEET.* INDICATES ONE OF THE FOLLOWING:
E = EMERGENCY CIRCUIT
S = STANDBY CIRCUITD = ELECTRIC CLOTHES DRYER
IG = ISOLATED GROUNDH = RECEPTACLE MOUNTED IN PARTIAL HEIGHT WALL. ROUTE BRANCH CIRCUITING IN
ACCESSIBLE CEILING ON FLOOR BELOW.
NEMA 5-20R DUPLEX RECEPTACLE: "2" DENOTES CIRCUIT NUMBER, * INDICATES ONE OF THE FOLLOWING:
E = EMERGENCY CIRCUITG = GROUND FAULT CIRCUIT INTERRUPTER
IG = ISOLATED GROUNDWP = GFCI OUTLET WITH WEATHERPROOF LOCKABLE DIE-CAST ALUMINUM COVERS = STANDBY CIRCUIT
VD = DEDICATED RECEPTACLE FOR VIDEO DISPLAY MOUNTED IN AV BACKBOX ENCLOSURE. REFER TOAV DRAWINGS FOR ADDITIONAL INFORMATION.
SM = SURFACE MOUNTED
TR = TAMPER RESISTANTAF = ARC FAULT CIRCUIT INTERRUPTER
U = COMBINATION NEMA 5-20R (LEVITON T5832) SINGLE RECEPTACLE WITH TWO STANDARD TYPE AUSB PORTS.
EWC = ELECTRIC WATER COOLER. COORDINATE MOUNTING OF RECEPTACLE WITH ELECTRIC WATER
COOLER INSTALLATION REQUIREMENTS.
JWALL-MOUNTED POWER FEED FOR POWERED FAUCET/FLUSH VALVE. PROVIDE FINALCONNECTIONS TO FAUCET/FLUSH VALVE TRANSFORMERS. COORDINATE AND PROVIDE
QUANTITY OF BACKBOXES REQUIRED WITH QUANTITY OF TRANSFORMERS PROVIDED .
UTILITY METERING EQUIPMENT
SINGLE-CHANNEL SURFACE-MOUNTED RACEWAY WITH QUANTITY AND TYPES OF RECEPTACLES ASINDICATED ON FLOOR PLANS. RACEWAY CIRCUIT WIRING SHALL BE #10 AWG MINIMUM. PROVIDE AT LEASTONE CONDUIT AND WIRING ENTRANCE POINT (PER CHANNEL) FOR EVERY TEN LINEAR FEET OF RACEWAY.COORDINATE RACEWAY LENGTHS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS. PROVIDEWIREMOLD AL3000 SERIES OR APPROVED EQUAL.
ENCLOSED CIRCUIT BREAKER, RATINGS AS INDICATED
2w20
2w20OR
J 120-VOLT POWER FEED FOR DOOR HOLD-OPENS.
J 120-VOLT POWER FEED FOR FIRE ALARM PANEL. COORDINATE EXACT LOCATION AND QUANTITYOF REQUIRED CONNECTION POINTS WITH FIRE ALARM PANELS PROVIDED.
J120-VOLT POWER FEED FOR SMOKE DAMPER AND FIRE SMOKE DAMPER CIRCUITS. COORDINATEEXACT LOCATION AND QUANTITY OF REQUIRED CONNECTION POINTS WITH DAMPER ANDDAMPER CIRCUITS PROVIDED. REFER TO HVAC DRAWINGS FOR ADDITIONAL INFORMATION ANDQUANTITY OF CONNECTIONS..
FLUSH FLOOR MOUNTED NEMA 5-20R DOUBLE-DUPLEX (QUAD) RECEPTACLE.
CEILING MOUNTED 5-20R DUPLEX RECEPTACLE, * INDICATES ONE OF THE FOLLOWING:
E = EMERGENCY CIRCUITG = GROUND FAULT CIRCUIT INTERRUPTER
IG = ISOLATED GROUNDWP = GFCI OUTLET WITH WEATHERPROOF (IN-USE) COVER AND ENCLOSURE
S = STANDBY CIRCUITP = RECEPTACLE SERVING PROJECTOR. COORDINATE EXACT LOCATION AND MOUNTING OF
PROJECTOR WITH ARCHITECTURAL DRAWINGS.
PS = RECEPTACLE SERVING PROJECTION SCREENIT = RECEPTACLE SERVING IT RACK. COORDINATE EXACT LOCATION AND MOUNTING REQUIREMENTS
WITH OWNER, PRIOR TO ROUGH-IN
VD = DEDICATED RECEPTACLE FOR VIDEO DISPLAY MOUNTED IN AV BACKBOX ENCLOSURE. REFER TOAV DRAWINGS FOR ADDITIONAL INFORMATION.
EMERGENCY LIGHTING FIXTURES, "EM" DENOTES FIXTURE CIRCUITED TOUNSWITCHED EMERGENCY LIGHTING BRANCH CIRCUIT.
LIGHTING FIXTURES, REFER TO LIGHTING FIXTURE SCHEDULE.
EM EM EM EM
4
3
b
THREE-WAY LIGHT SWITCH, 120/277V
FOUR-WAY LIGHT SWITCH, 120/277V
SINGLE-POLE LIGHT SWITCH, 120/277V. "b" DENOTES SWITCH CONTROL
LINE VOLTAGE OVERRIDE SWITCH FOR OCCUPANCY SENSOR 120/277V. OVERRIDE SWITCHTO BE TIED IN DOWN STREAM OF OCCUPANCY SENSOR POWER PACK. "3" INDICATES 3-WAYSWITCHING OPERATION. "4" INDICATES 4-WAY SWITCHING OPERATION.
OR3
OR4
DDIMMER SWITCH, RATINGS AND LOAD-TYPE AS REQUIRED. DIMMER SHALL BE TIED IN DOWNSTREAM OFOCCUPANCY SENSOR POWER PACK. COORDINATE COLOR WITH ARCHITECT.
CEILING-MOUNTED DUAL-TECHNOLOGY OCCUPANCY SENSOR WITH INTEGRAL LIGHT LEVEL SENSORAND ISOLATED RELAY OUTPUTS [(1) NORMALLY OPEN AND (1) NORMALLY CLOSED CONTACT].WATTSTOPPER MODEL DT-200 OR EQUAL. PROVIDE POWER PACKS AS REQUIRED. ARROW INDICATESDIRECTION OF SENSOR. COORDINATE COLOR WITH ARCHITECT. PROVIDE WALL-MOUNTED OVERRIDESWITCHES WHERE INDICATED. OCC SENSOR TO CONTROL ALL FIXTURES IN SPACE, UNLESS NOTEDOTHERWISE.
CEILING-MOUNTED LOW VOLTAGE DUAL-TECHNOLOGY OCCUPANCY SENSOR WITH INTEGRAL LIGHTLEVEL SENSOR AND ISOLATED RELAY OUTPUTS [(1) NORMALLY OPEN AND (1) NORMALLY CLOSEDCONTACT]. WATTSTOPPER MODEL DT-300 OR EQUAL. PROVIDE POWER PACKS AS REQUIRED.COORDINATE COLOR WITH ARCHITECT. PROVIDE WALL-MOUNTED OVERRIDE SWITCHES WHEREINDICATED. OCC SENSOR TO CONTROL ALL FIXTURES IN SPACE, UNLESS NOTED OTHERWISE.
OS2
OS1
OR
PROGRAMMABLE PUSH-BUTTON DIGITAL TIMER WALL SWITCH WITH INTERVAL RANGE FROM 5 MINUTESTO 12 HOURS, POWER FAILURE MEMORY AND TIME-OUT VISUAL WARNING FLASH. WATTSTOPPER TS-400OR APPROVED EQUAL. "3" INDICATES 3-WAY SWITCHING CONFIGURATION. PROVIDE LOW-VOLTAGEMODEL #TS-400-24 FOR 3-WAY SWITCHING CONFIGURATION. PROVIDE POWER PACKS AS REQUIRED FORLOW-VOLTAGE MODEL. DIGITAL TIMER SWITCH TO CONTROL ALL FIXTURES IN SPACE, UNLESS NOTEDOTHERWISE.
T T3
OCCUPANCY SENSOR/DAYLIGHT SENSOR CONTROL ZONE. OCCUPANCY SENSORS/DAYLIGHT SENSORSLOCATED WITHIN THIS BOUNDARY SHALL CONTROL ALL NON-LIFE SAFETY LIGHTING WITHIN THIS ZONE.
CEILING MOUNTED SPECIAL PURPOSE RECEPTACLE.
"X" INDICATES TYPE, REFER TO SPECIAL PURPOSE RECEPTACLE SCHEDULE.* INDICATES ONE OF THE FOLLOWING:
E = EMERGENCY CIRCUITS = STANDBY CIRCUITIG = ISOLATED GROUND
IT = RECEPTACLE SERVING IT RACK. COORDINATE EXACT LOCATION AND MOUNTING REQUIREMENTSWITH OWNER, PRIOR TO ROUGH-IN
J
NP1-1DENOTES ELECTRICAL PANEL AND CIRCUIT NUMBER THAT SERVICES THE AREA DESIGNATED OR THEGIVEN ROOM, UNLESS INDICATED OTHERWISE.
NP1
J BRANCH CIRCUIT AND POWER CONNECTION FOR BUILDING AUTOMATION SYSTEM (BAS). PROVIDE BRANCHCIRCUITS FOR BAS CONTROLLERS AS REQUIRED BASED ON FINAL APPROVED BAS SYSTEM LAYOUT.COORDINATE EXACT LOCATION OF CONTROLLERS, PRIOR TO ROUGH-IN.
120V NORMAL POWER FOR ELECTRIC STRIKEJ
CURRENT TRANSFORMER WITH SHUNT BLOCK
DRAWOUT POTENTIAL TRANSFORMER
MEDIUM VOLTAGE RELAY
OS3
EM EM
EM
MTSPST 24-HOUR TIME SWITCH, NEMA I LOCKABLE METAL ENCLOSURE AND CLOCKMOTOR OF VOLTAGE COMPATIBLE WITH CONTROL CIRCUIT. TORK#1102 277 VOLTOR EQUAL.
POWER TRANSFORMER. "NT1" INDICATES TRANSFORMER NAME.
6-INCH RECESSED POKE-THRU DEVICE FOR POWER, AV, AND TELECOMMUNICATIONS WITH HINGEDSURFACE STYLE COVER PLATE. PROVIDE WIREMOLD EVOLUTION 6AT SERIES POKE-THRU DEVICE.CENTER MOUNT TELECOMMUNICATIONS DEVICE PLATE AND SIDE MOUNT (2) NEMA 5-20RRECEPTACLES. PROVIDE (1) 3/4" CONDUIT FOR POWER. PROVIDE (1) 1-1/4" CONDUIT FORTELECOMMUNICATIONS/AV CABLING WITH PULLSTRING. STUB POWER AND TELECOMMUNICATIONS/AVCONDUITS ABOVE ACCESSIBLE CEILING. COORDINATE COLOR WITH ARCHITECT.
CEILING-MOUNTED LOW VOLTAGE DUAL-TECHNOLOGY OCCUPANCY SENSOR WITH INTEGRAL LIGHTLEVEL SENSOR AND ISOLATED RELAY OUTPUTS [(1) NORMALLY OPEN AND (1) NORMALLY CLOSEDCONTACT]. WATTSTOPPER MODEL DT-300 OR EQUAL. PROVIDE POWER PACKS AS REQUIRED.COORDINATE COLOR WITH ARCHITECT. PROVIDE WALL-MOUNTED OVERRIDE SWITCHES WHEREINDICATED. OCC SENSOR TO CONTROL ALL FIXTURES IN SPACE, UNLESS NOTED OTHERWISE.
RECESSED ON GRADE FLOOR BOX FOR POWER, AV, AND TELECOMMUNICATIONS WITH HINGED COVERPLATE. PROVIDE WIREMOLD EVOLUTION EFB6S-OG. PROVIDE (2) NEMA 5-20R RECEPTACLES. PROVIDE(1) 3/4" CONDUIT FOR POWER. PROVIDE (2) 1-1/4" CONDUIT FOR TELECOMMUNICATIONS/AV CABLINGWITH PULLSTRING. STUB POWER AND TELECOMMUNICATIONS/AV CONDUITS ABOVE ACCESSIBLECEILING. COORDINATE COLOR WITH ARCHITECT.
RETRACTABLE EXTENSION CORD-REEL WITH RECEPTACLE AT END, MOUNTED TO UNISTRUT. REFERTO DETAIL IN E-700 SERIES.
120-VOLT POWER FEED FOR VAV TRANSFORMERS.J
J POWER CONNECTION FOR BASEBOARD ELECTRIC HEATER. COORDINATE EXACT LOCATION AND FINALQUANTITY OF CONNECTIONS WITH EQUIPMENT PROVIDED.
P
WALL-MOUNTED, POWER BASE FEED FOR SYSTEMS FURNITURE. PROVIDE 4" x 4" RECESSEDJUNCTION BOX AT INFEED LOCATION WITH END WHIP CONNECTION TO FURNITURE;COORDINATE EXACT END WHIP CONNECTION REQUIREMENTS WITH FURNITUREMANUFACTURER.
120-VOLT POWER FEED FOR TRAP PRIMER.J
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
NTS
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-002
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
ELECTRICAL LEGENDSHEET 2
MOUNTING DESCRIPTION MANUFACTURER ORDERING No. QTY.WATTS/ LAMP LAMP TYPE LUMENS QTY.
INTEGRAL/REMOTE FACTOR
TOTALWATTS VOLTAGE CONTROL
MOUNTINGHEIGHT COMMENTS
LOCATION(CLASSROOM. B.)
F 3A
RECESSED CEILING (GRID)REFER TO ARCHITECTURALDRAWINGS FOR GRID TYPESELECTION.
6FT LONG 8" PROFILE LENSED SLOT FIXTURE.. NOM.: 6"H, 8"W. PROVIDED WITH (1) LAMP IN CROSS SECTION,PRE-PAINTED 20 GA STEEL HOUSING,PAINTED STEEL REFLECTOR 92% REFLECTANCE, ACRYLIC LENS,PREWIRED WITH QUICK CONNECT PLUGS AND INTEGRAL ELECTRONIC 0.78 BALLAST FACTOR BALLAST.LISTING: UL, CUL DAMP LOCATIONS
LINEAR LIGHTING
RC68-D-1ET8-277-AL-G**-BW-MODBALLAST-6FT
BALLAST: PHILIPS OPTIUM, IOPA-2P32-LW-N
2 25
T8
F25T8TL835/ALTOPHILIPS
4,080 1 INTEGRAL 0.78 39 277 SWREFER TO ARCHITECTURAL PLANS FOR CEILING GRID TYPE FINALCOORDINATION.
2ND FLOOR FACULTYOFFICES
F 3AEM
RECESSED CEILING (GRID)REFER TO ARCHITECTURALDRAWINGS FOR GRID TYPESELECTION.
6FT LONG 8" PROFILE LENSED SLOT FIXTURE.. NOM.: 6"H, 8"W. PROVIDED WITH (1) LAMP IN CROSS SECTION,PRE-PAINTED 20 GA STEEL HOUSING,PAINTED STEEL REFLECTOR 92% REFLECTANCE, ACRYLIC LENS,PREWIRED WITH QUICK CONNECT PLUGS, INTEGRAL ELECTRONIC 0.78 BALLAST FACTOR BALLAST ANDEMERGENCY BATTERY PACKLISTING: UL, CUL DAMP LOCATIONS
LINEAR LIGHTING
RC68-D-1ET8-277-AL-G**-BW-MODBALLAST-6FT-EM
BALLAST: PHILIPS OPTIUM, IOPA-2P32-LW-N
2 25
T8
F25T8TL835/ALTOPHILIPS
4,080 1 INTEGRAL 0.78 39 277 SWREFER TO ARCHITECTURAL PLANS FOR CEILING GRID TYPE FINALCOORDINATION.
2ND FLOOR DEAN'SSUITE
F 3B
RECESSED CEILING (GRID)REFER TO ARCHITECTURALDRAWINGS FOR GRID TYPESELECTION.
4FT LONG 8" PROFILE LENSED SLOT FIXTURE.. NOM.: 6"H, 8"W. PROVIDED WITH (1) LAMP IN CROSS SECTION,PRE-PAINTED 20 GA STEEL HOUSING,PAINTED STEEL REFLECTOR 92% REFLECTANCE, ACRYLIC LENS,PREWIRED WITH QUICK CONNECT PLUGS AND INTEGRAL ELECTRONIC 0.77 BALLAST FACTOR BALLAST.LISTING: UL, CUL DAMP LOCATIONS
LINEAR LIGHTING
RC68-D-1ET8-277-AL-G**-BW-MODBALLAST-4FT
BALLAST: PHILIPS OPTIUM, IOPA-1P32-LW-N
1 32
T8
F32T8TL835/ALTOPHILIPS
2,040 1 INTEGRAL 0.77 25 277 SWREFER TO ARCHITECTURAL PLANS FOR CEILING GRID TYPE FINALCOORDINATION.
2ND FLOOR , DEAN'SOFFICE 217
F 5 CEILING PENDANT
SURFACE/CHAIN HANGED INDUSTRIAL FIXTURE. NOM.: 7"H, 14"W, 50"L. PROVIDED WITH (2) LAMPS INCROSS SECTION COLD-ROLLED STEEL HOUSING 10% APERTURE REFLECTOR, MOUNTING ACCESORIES FORCHAIN HANG OR SURFACE MOUNTED APPLICATION AND INTEGRAL ELECTRONIC BALLAST.LISTING: UL DRY LOCATIONS.
LITHONIA AF10-232-MVOLT-GEB10IS-WGAFPV
2 32T8
F32T8TL835/ALTOPHILIPS
5,000 1 INTEGRAL 1.00 64 277 SW COORDINATE WITH EQUIPMENT LOCATION.WIREGUARD: 4' WHITE (ORDER 2 FOR 8' FIXTURES)
MER, IT
F 5EM CEILING PENDANT
SURFACE/CHAIN HANGED INDUSTRIAL EMERGENCY FIXTURE. NOM.: 7"H, 14"W, 50"L. PROVIDED WITH (2)LAMPS IN CROSS SECTION COLD-ROLLED STEEL HOUSING 10% APERTURE REFLECTOR, MOUNTINGACCESORIES FOR CHAIN HANG OR SURFACE MOUNTED APPLICATION, INTEGRAL ELECTRONIC BALLAST AND(2) BODINE EMERGENCY BATTERY PACK FOR 1735 LUM EA.LISTING: UL DRY LOCATIONS.
LITHONIAAF10-232-MVOLT-GEB10IS-WGAFPV-EL (MOD. FOR 2-BODINEBATTERY PACKS)
2 32
T8
F32T8TL835/ALTOPHILIPS
5,000 1 INTEGRAL 1.00 64 277 SWCOORDINATE WITH EQUIPMENT LOCATION.
WIREGUARD: 4' WHITE (ORDER 2 FOR 8' FIXTURES)MER, IT, LEVEL 3
F 5W CEILING PENDANT
SURFACE/CHAIN HANGED INDUSTRIAL WET LOCATION FIXTURE. NOM.: 4"H, 6"W, 42"L. PROVIDED WITH (2)LAMPS IN CROSS SECTION, INJECTION MOLDED UV STABILIZED POLYCARBONATE HOUSING,POLYCARBONATE LENS, MOUNTING ACCESORIES FOR CHAIN HANG OR SURFACE MOUNTED APPLICATIONAND INTEGRAL ELECTRONIC BALLAST.LISTING: UL WET LOCATIONS, IP66.
SLS-LINDA SLS-LIN-2X32-T8 2 32
T8
F32T8TL835/ALTOPHILIPS
5,000 1 INTEGRAL 1.00 64 277 SWCOORDINATE WITH EQUIPMENT LOCATION.
WATER ENTRY ROOM
F 5WEM CEILING PENDANT
SURFACE/CHAIN HANGED INDUSTRIAL WET LOCATION EMERGENCY FIXTURE. NOM.: 4"H, 6"W, 42"L.PROVIDED WITH (2) LAMPS IN CROSS SECTION, INJECTION MOLDED UV STABILIZED POLYCARBONATEHOUSING, POLYCARBONATE LENS, MOUNTING ACCESORIES FOR CHAIN HANG OR SURFACE MOUNTEDAPPLICATION, INTEGRAL ELECTRONIC BALLAST AND EMERGENCY BATTERY PACK FOR 1-LAMP.LISTING: UL WET LOCATIONS, IP66.
SLS- LINDA
SLS-LIN-2X32-T8-EBP
EM BATTERY: POWER SENTRY PS1400
2 32
T8
F32T8TL835/ALTOPHILIPS
5,000 1 INTEGRAL 1.00 64 277 SWCOORDINATE WITH EQUIPMENT LOCATION.
WATER ENTRY ROOM
F 8 RECESSED CEILING
6" ROUND COMPACT FLUORESCENT DOWNLIGHT. NOM.: 7"H, 15"W, 16"L. PROVIDED WITH, STEELCONSTRUCTION, WHITE PAINTED FLANGE, SEMI-SPECULAR MATTE DIFFUSE FINISH, PRISMATIC LENS ANDINTEGRAL ELECTRONIC BALLAST.LISTING: UL DAMP LOCATION
GOTHAM AF-1/32TRT-GAR-T73-277-TRW 1 32
CFL TRIPLE TUBEPL-T 32W/835/A/
4P/ALTOPHILIPS
2,040 1 INTEGRAL 1.00 32 277 SW N/ACOORDINATE MOUNTING WITH CEILING TYPE AND CONDITIONS.
COLOR FINISH OF FIXTURE FLANGE TO BE APPROVED BY ARCHITECT.
SEMINAR ROOM,BATHROOMS, CAFE.
F 8EM RECESSED CEILING
6" ROUND COMPACT FLUORESCENT EMERGENCY DOWNLIGHT. NOM.: 7"H, 15"W, 16"L. PROVIDED WITH,STEEL CONSTRUCTION, WHITE PAINTED FLANGE, SEMI-SPECULAR MATTE DIFFUSE FINISH, PRISMATIC LENS,INTEGRAL ELECTRONIC BALLAST AND EMERGENCY BATTERY PACK WITH REMOTE TEST SWITCH.LISTING: UL DAMP LOCATION
GOTHAM AF-1/32TRT-GAR-T73-277-TRW-ELR
1 32
CFL TRIPLE TUBEPL-T 32W/835/A/
4P/ALTOPHILIPS
2,040 1 INTEGRAL 1.00 32 277 SW N/ACOORDINATE MOUNTING WITH CEILING TYPE AND CONDITIONS.
COLOR FINISH OF FIXTURE FLANGE TO BE APPROVED BY ARCHITECT.
SEMINAR ROOM,BATHROOMS, CAFE.
F 8B RECESSED CEILING
6" ROUND COMPACT FLUORESCENT DOWNLIGHT. NOM.: 7"H, 15"W, 16"L. PROVIDED WITH STEELCONSTRUCTION, WHITE PAINTED FLANGE, SEMI-SPECULAR MATTE DIFFUSE FINISH, PRISMATIC LENS ANDINTEGRAL ELECTRONIC BALLAST.LISTING: UL DAMP LOCATION
GOTHAM AF-1/26TRT-GAR-T73-277-TRW 1 26
CFL TRIPLE TUBEPL-T 26W/835/A/
4P/ALTOPHILIPS
1,530 1 INTEGRAL 1.00 26 277 SW N/ACOORDINATE MOUNTING WITH CEILING TYPE AND CONDITIONS.
COLOR FINISH OF FIXTURE FLANGE TO BE APPROVED BY ARCHITECT.
VESTIBULES, LOBBY,CIRCULATION AREAS
F 8BEM RECESSED CEILING
6" ROUND COMPACT FLUORESCENT DOWNLIGHT. NOM.: 7"H, 15"W, 16"L. PROVIDED WITH STEELCONSTRUCTION, WHITE PAINTED FLANGE, SEMI-SPECULAR MATTE DIFFUSE FINISH, PRISMATIC LENS,INTEGRAL ELECTRONIC BALLAST AND EMERGENCY BATTERY PACK WITH REMOTE TEST SWITCH.
LISTING: UL DAMP LOCATION
GOTHAM AF-1/26TRT-GAR-T73-277-TRW-ELR
1 26
CFL TRIPLE TUBE
PL-T 26W/835/A/4P/ALTOPHILIPS
1,530 1 INTEGRAL 1.00 26 277 SW N/ACOORDINATE MOUNTING WITH CEILING TYPE AND CONDITIONS.
COLOR FINISH OF FIXTURE FLANGE TO BE APPROVED BY ARCHITECT.
VESTIBULES, LOBBY,CIRCULATION AREAS
F 10 SEMI-RECESSED
DECORATIVE33" DIAMETER FLUORESCENT ROUND LIGHT
LZF
LZF-SAT-SM-MULTIV UL-28-WHITETOP DIFFUSER, BOTTOM MATTSATIN ACRYLICCANOPY COLOR (MOD WHITE)STEEL SUSPENTION CABLE
3 2424W T5
3500K5,550 72 277 SW TBD
COORDINATE MOUNTING WITH ARCH CEILING TYPEFIXTURE TO BE MOUNTED AS INDICATED IN ARCHITECTEURAL DETAILS.
ALL COLOR FINISH TO BE APPROVED BY ARCHITECT.
CIRCULATION /SITTING AREA
F 12
RECESSED CEILING (GRID)REFER TO ARCHITECTURALDRAWINGS FOR GRID TYPESELECTION.
4" PROFILE LENSED SLOT FIXTURE. NOM.: 4"H, 5"W, 4FT LONG. PROVIDED WITH (1) LAMP IN CROSSSECTION, EXTRUDED ALUMINUM HOUSING, WHITE POWDER COAT FINISH, 0.40 FORMED ALUMINUMREFLECTOR, ACRYLIC LENS AND INTEGRAL ELECTRONIC BALLAST.LISTING: UL, CUL DAMP LOCATIONS
ALWLP3.5RT (GRID)-**-4FT-T8-STD-1-277-WD-WH-*
1 32T8 (PLUS SERIES)
F32T8TL835/PLUS/ALTOPHILIPS
2,500 1 INTEGRAL 32 277 SWCOORDINATE MOUNTING WITH ARCH. CEILING TYPE AND CONDITIONS.ALL COLOR FINISH TO BE APPROVED BY ARCHITECT.
CORRIDORS
F 12EM
RECESSED CEILING (GRID)REFER TO ARCHITECTURALDRAWINGS FOR GRID TYPESELECTION.
4" PROFILE LENSED SLOT FIXTURE. NOM.: 4"H, 5"W, 4FT LONG. PROVIDED WITH (1) LAMP IN CROSSSECTION, EXTRUDED ALUMINUM HOUSING, WHITE POWDER COAT FINISH, 0.40 FORMED ALUMINUMREFLECTOR, ACRYLIC LENS, INTEGRAL ELECTRONIC BALLAST AND INTEGRAL EMERGENCY BATTERY PACKFOR 1 LAMP.LISTING: UL, CUL DAMP LOCATIONS
ALWLP3.5RT (GRID)-**-4FT-T8-STD-1-277-WD-WH-*-EM 1 32
T8 (PLUS SERIES)F32T8TL835/PLUS/ALTO
PHILIPS2,500 1 INTEGRAL 32 277 SW
COORDINATE MOUNTING WITH ARCH. CEILING TYPE AND CONDITIONS.ALL COLOR FINISH TO BE APPROVED BY ARCHITECT. CORRIDORS
F 12 [R]
RECESSED CEILING (GRID)
REFER TO ARCHITECTURALDRAWINGS FOR GRID TYPESELECTION.
4" PROFILE LENSED SLOT FIXTURE. NOM.: 4"H, 5"W, LENGTH AS INDICATED IN ARCHITECTURAL DRAWINGS.PROVIDED WITH (1) LAMP IN CROSS SECTION, EXTRUDED ALUMINUM HOUSING, WHITE POWDER COAT FINISH,0.40 FORMED ALUMINUM REFLECTOR, ACRYLIC LENS AND INTEGRAL ELECTRONIC BALLAST.LISTING: UL, CUL DAMP LOCATIONS
ALW LP3.5RT (GRID)-**-LENGTH-T8-STD-1-277-WD-WH-*
1 32
T8 (PLUS SERIES)
F32T8TL835/PLUS/ALTOF25T8TL835/PLUS/ALTO
PHILIPS
2,500 1 INTEGRAL 32 277 SW
SYSTEM LENGTH. USE THE BEST COBINATION OF 3FT AND 4FT LAMPS TOCOMPLETE RUNS
COORDINATE MOUNTING WITH ARCH. CEILING TYPE AND CONDITIONS.ALL COLOR FINISH TO BE APPROVED BY ARCHITECT.
CLASSROOMS,WORK ROOM 102A,MOCK-UP PATIENTROOMS, SEMINARROOMS
F 12 [R]EM
RECESSED CEILING (GRID)
REFER TO ARCHITECTURALDRAWINGS FOR GRID TYPESELECTION.
4" PROFILE LENSED SLOT FIXTURE. NOM.: 4"H, 5"W, LENGTH AS INDICATED IN ARCHITECTURAL DRAWINGS.PROVIDED WITH (1) LAMP IN CROSS SECTION, EXTRUDED ALUMINUM HOUSING, WHITE POWDER COAT FINISH,0.40 FORMED ALUMINUM REFLECTOR, ACRYLIC LENS, INTEGRAL ELECTRONIC BALLAST AND INTEGRALEMERGENCY BATTERY PACK FOR 1 LAMP (LOCATION OF EM ON ROWS AS INDICATED IN ELECTRICALDRAWINGS).LISTING: UL, CUL DAMP LOCATIONS
ALWLP3.5RT (GRID)-**-LENGTH-T8-STD-1-277-WD-WH-*-EM
1 32
T8 (PLUS SERIES)
F32T8TL835/PLUS/ALTOF25T8TL835/PLUS/ALTO
PHILIPS
2,500 1 INTEGRAL 32 277 SW
SYSTEM LENGTH. USE THE BEST COBINATION OF 3FT AND 4FT LAMPS TOCOMPLETE RUNS
COORDINATE MOUNTING WITH ARCH. CEILING TYPE AND CONDITIONS.ALL COLOR FINISH TO BE APPROVED BY ARCHITECT.
CLASSROOMS
F 12C
RECESSED CEILING IN GWB
REFER TO ARCHITECTURALDRAWINGS FOR CEILING TYPE.
4" PROFILE LENSED SLOT FIXTURE. NOM.: 4"H, 5"W, LENGTH AS INDICATED IN ARCHITECTURAL DRAWINGS.PROVIDED WITH (1) LAMP IN CROSS SECTION, EXTRUDED ALUMINUM HOUSING, WHITE POWDER COAT FINISH,0.40 FORMED ALUMINUM REFLECTOR, ACRYLIC LENS AND INTEGRAL ELECTRONIC BALLAST.LISTING: UL, CUL DAMP LOCATIONS
ALWLP3.5RT (DRY)-**-LENGTH-T8-STD-1-277-WD-WH-* 1 32
T8 (PLUS SERIES)
F32T8TL835/PLUS/ALTOPHILIPS
2,500 1 INTEGRAL 32 277 SWSYSTEM LENGTH
FOR CEILING TYPE: GWBVESTIBULE 1V3
F 16 SURFACE WALL
4 FT LED LINEAR FIXTURE. NOM.: 6" H x 5"H x 4' LONG. PROVIDED WITH HIGH IMPACT ACRYLIC LENS,INTEGRAL END MOUNTED PASSIVE INFRARED OCCUPANCY SENSOR AND INTEGRAL ELECTRONIC DRIVER FORNON-DIMMING APPLICATIONS.LISTING: UL, ETL DAMP LOCATIONS
HE WILLIAMS
SLF-4-LED*UT31-HIA-OCCSS SBR-10-277
DRIVER: ED+UT
1 30WHITE LED,
82CRI, 35K3,100 1 INTEGRAL 30 277 SW 8'-0" INTEGRAL OC SENSOR
REFER TO ARCH STAIRCASE SECTIONS FOR FINAL COUNT.STAIRCASE
F 16EM SURFACE WALL
4 FT LED LINEAR EMERGENCY FIXTURE. NOM.: 6" H x 5"H x 4' LONG. PROVIDED WITH HIGH IMPACT ACRYLICLENS, INTEGRAL END MOUNTED PASSIVE INFRARED OCCUPANCY SENSOR, INTEGRAL EMERGENCY LEDDRIVER (1300 LUMENS MODULE).LISTING: UL, ETL DAMP LOCATIONS
HE WILLIAMS
SLF-4-LED*UT31-HIA-OCCSS SBR-10-277EM/BSL310
DRIVER: ED+UT
1 30WHITE LED,
82CRI, 35K3,100 1 INTEGRAL 30 277 SW 8'-0"
INTEGRAL OC SENSORREFER TO ARCH STAIRCASE SECTIONS FOR FINAL COUNT.
STAIRCASE
F 17 SURFACE WALL3FT LINEAR FLUORESCENT FIXTURE. PROVIDED WITH INTEGRAL OCCUPANCY SENSOR.
LISTING: UL, DRY OR DAMP LOCATIONSHE WILLIAMS
SLF-3-1-25-HIA-OCCSS SBR-10-EB1-UNV 1 25
T8F25T8TL835/ALTO
PHILIPS2,300 1 INTEGRAL 25 277 SW
INTEGRAL OC SENSORCLOSET
F 18 RECESSED CEILING
10" WIDE LINEAR FLUORESCENT PERIMETER LENSED SLOT. NOM.: 7"H, 10"W, LENGTH AS INDICATED INARCHITECTURAL PLANS. PROVIDED WITH (1) LAMP IN CROSS SECTION, 20GA STEEL HOUSING, WITHALUMINUM WALL RAIL, GLOSS WHITE FINISH, TELESCOPING LAMP ROW TO ILLUMINATE END TO END,PRISMATIC ACRYLIC LENS, SPECULAR ALUMINUM REFLECTOR AND INTEGRAL ELECTRONIC BALLAST.LISTING: UL DAMP LOCATION
PRUDENTIAL LIGHTINGP80i 1T8-RXX-PRA-S-SC-277-MOUNT-**
1 32
T8
F32T8TL835/ALTOPHILIPS
2,500 1 INTEGRAL 32 277 SWCOORDINATE MOUNTING WITH CEILING TYPE AND CONDITIONS.
COLOR FINISH OF FIXTURE FLANGE TO BE APPROVED BY ARCHITECT.BATHROOMS
F 19SURFACE MOUNTED INARCHITECTURAL MULLION
CUSTOM LENGTH, MULLION MOUNTED LINEAR HIGH OUTPUT LED FIXTURE. NOM.: 2"H, 2"W, LENGTH ASINDICATED IN ARCHITECTURAL DRAWINGS FOR EACH FIXTURE ASSEMBLY. PROVIDED WITH (1) ROW OF LEDSIN CROSS SECTION, ASYMMETRICAL LIGHT DISTRIBUTION, DIFUSSE LENS (DUST COVER,) EXTRUDEDALUMINUM HOUSING, POWDER COAT FINISH (COLOR TO BE APPROVED BY ARCHITECT), INTEGRALSTANDARD 0-10V DIMMING DRIVER.WINDOW MULLION: POWER RUNS THROUGH SPECIAL END CAP INTO ADJACENT WALL.LISTING: UL, CUL DAMP LOCATIONS
A-LIGHTACL4-M 16'-3"/M 12'-7"-P-16'-3" x12'-7"-LH-3500K-U-N-M**-FINISH 28 10
LED, 85CRI, 35K(10 WATTS/FT)
1164 lm/ft1,164 1 INTEGRAL 0.97 272 277 SW
MULLIONSEE ARCHDETAILS
COORDINATE MOUNTING WITH ARCHITECTURAL DETAILS AND MULLIONSPECIFICATION (SIZE).COORDINATE RIGHT OR LEFT END FEED WITH ELECTRICAL DRAWINGS.FIXTURE REQUIRES DETAIL LINE DRAWING SUBMITALLS BY MANUFACTURERFOR FINAL APPROVAL BEFORE FABRICATION.COLOR FINISH OF FIXTURE TO BE APPROVED BY ARCHITECT.
STAIR 1
F 19EMSURFACE MOUNTED INARCHITECTURAL MULLION
CUSTOM LENGHT, MULLION MOUNTED LINEAR H. OUTPUT LED EMERGENCY FIXTURE . NOM.: 2"H, 2"W,LENGTH AS INDICATED IN ARCHITECTURAL DRAWINGS FOR EACH FIXTURE ASSEMBLY. PROVIDED WITH (1)ROW OF LEDS IN CROSS SECTION, ASYMMETRICAL LIGHT DISTRIBUTION, DIFUSSE LENS (DUST COVER,)EXTRUDED ALUMINUM HOUSING, POWDER COAT FINISH (COLOR TO BE APPROVED BY ARCHITECT),INTEGRAL STANDARD 0-10V DIMMING DRIVER.WINDOW MULLION: POWER RUNS THROUGH SPECIAL END CAP INTO ADJACENT WALL.PROVIDED WITH EMERGENCY BATTERY PACK(S) FOR 12 FT FIXTURE. MANUFACTURER TO DETERMININEQUANTITY.LISTING: UL, CUL DAMP LOCATIONS
A-LIGHTACL4-M 16'-3"/M 12'-7"-P-16'-3" x12'-7"-LH-3500K-U-N-M**-FINISH -E2
12 10LED, 85CRI, 35K1,164 LUM/WATT(10 WATTS/FT)
1,164 1 INTEGRAL 0.97 116 277 SWMULLION
SEE ARCHDETAILS
COORDINATE MOUNTING WITH ARCHITECTURAL DETAILS AND MULLIONSPECIFICATION (SIZE).COORDINATE RIGHT OR LEFT END FEED WITH ELECTRICAL DRAWINGS.FIXTURE REQUIRES DETAIL LINE DRAWING SUBMITALLS BY MANUFACTURERFOR FINAL APPROVAL BEFORE FABRICATION.COLOR FINISH OF FIXTURE TO BE APPROVED BY ARCHITECT.
STAIR 1
F 19BEM SURFACE WALL
4FT WALL MOUNTED LINEAR HIGH OUTPUT LED FIXTURE WITH INTEGRAL EM BATTERY. NOM.: 2"H, 2"W,48"L. PROVIDED WITH (1) ROW OF LEDS IN CROSS SECTION, ASYMMETRICAL LIGHT DISTRIBUTION, DIFUSSELENS (DUST COVER,) EXTRUDED ALUMINUM HOUSING, POWDER COAT FINISH (COLOR TO BE APPROVED BYARCHITECT), INTEGRAL STANDARD 0-10V DIMMING DRIVER AND (1) IOTA ISl CP-12 EMERGENCY BATTERYPACK LOCATED AT THE END OF THE FIXTURE.
LISTING: UL, CUL DAMP LOCATIONS
A-LIGHTACL4-40-LH-3500K-N-D-U-R-FINISH-E1 4 10
LED, 85CRI, 35K(10 WATTS/FT)
1164 lm/ft1,164 1 INTEGRAL 0.97 39 277 SW
WALLMOUNTED.SEE ARCHDETAILS
COORDINATE MOUNTING WITH ARCHITECTURAL DETAILS.COLOR FINISH OF FIXTURE TO BE APPROVED BY ARCHITECT. STAIR 2
F 20 CEILING/CABLE PENDANT
17" DIAMETER LOW BAY FIXTURE. PROVIDED WITH SPUN ANODIZED ALUMINUM HOUSING, FROSTED LENS,AIRCRAFT CABLES, SEPARATE SWITCHING AND 4 ELECTRONINC INTEGRAL/REMORE BALLAST.
LISTING: UL, DRY DELRAY
7810-4-42CF-SS (3)BALLAST--**
BALLAST: PHILIPS SMARTMATE(1 LAMP), ICF-2S26-HI-LD(2 LAMP), ICF-2S42-M2-LD
4 42
CFL TRIPLE TUBE
PL-T 42W/835/A/4P/ALTOPHILIPS
10,000 4INTEGRAL &
REMOTE 0.98 165 277 SW 12'-0"
ALLOW 6FT SUSPENTION CABLE PER FIXTURE TO BE ADJUSTED ON SITE.AVOID USE NEAR HVAC VENTS.ALLOW FIXTURE TO BE CONTROLLED WITH 2 INDEPENDENT CIRCUITS.CKT 1: 2 LAMPSCKT1: 1 LAMPCKT 2: 1 LAMPCOORDINATION OF REMOTE BALLAST LOCATION REQUIRED
SUSTAINABILITY 101
F 21SURFACE IN ARCHITECTURALSLOT/COVE
ASYMETRICAL DISTRIBUTION LED LINEAR FIXTURE. NOM.: 6"H, 3"W, LENGTH AS INDICATED INARCHITECTURAL PLANS. PROVIDED WITH EXTRUDED ALUMINUM HOUSING, ACRYLIC LENS, HOLOGRAPHICDIFFUSER, ROTATION LOCKING CAPABILITY, LED ENGINE WITH "FRAQTIR" ASYMETRICAL OPTIC ANDINTEGRAL LED DRIVERS. 5 YEARS WARRANTY.FIXTURES TO RUN IN CONTINUOUS ROWS. PROVIDE FIXTURES WITH CONNECTORS AND END PLATES ASREQUIRED FOR A COMPLETE WORKING SYSTEM.LISTING: UL DRY LOCATIONS
ELLIPTIPARSTYLE S305S305R-04L/01L-S-0-8-00-35-00 4 7
LED, 85CRI450 LUM/FT
(7 WATTS/FT)1,800 INTEGRAL 28 277 SW N/A
REFER TO ARCHITECTURAL PLANS AND ARCHITECTURAL DETAILS FORMOUNTIONG COORDINATION.
CENTRAL STAIRCASEWALL
F 22CABLE SUSPENDED IN WOODCEILING
8FT LINEAR DIRECT FLUORESCENT FIXTURE. NOM.: 4"H, 4"W. PROVIDED WITH 1-LAMP IN CROSS SECTION,DIE FORMED WELDED STEEL HOUSING, STEEL WHITE PAINTED REFLECTOR, STEEL NO HOLES ORKNOCKOUTS ENDCAPS, FIELD ADJUSTABLE AIRCRAFT SUSPENSION CABLE, STRAP ATTACHMENT FORHORIZONTAL ADJUSTMENT, INTEGARL PRESET DIM IN FACTORY ELECTRONIC BALLAST.
LISTING: UL, CUL DAMP LOCATIONS
LITECONTROLP-D-44-1-8 T8-SLG-(MOD)SILVER-(MOD) SET BALLAST-1-**-277 2 32
T8
F32T8TL835/ALTOPHILIPS
5,000 INTEGRAL 64 277 SW 10'-6"
REFER TO ARCHITECTURAL PLANS FOR CEILING TYPE AND MOUNTIONGCOORDINATION.
CANOPY TO BE RAL COLOR TO MATCH WOOD CEILING.
MOUNTING: BOTTOM OF THE FIXTURE TO ALIGN WITH CEILING HEIGHT OF THEADJACENT (ACT) CEILING IN CORRIDOR
LEVEL 2 AND LEVEL3 CORRIDORS 2C1AND 3C2
F 24SURFACE/UNDERCABINETFURNITURE MOUNT
2FT LINEAR UNDERCABINET LED LINE VOLTAGE FIXTURE. NOM.: 1"H, 3"W. PROVIDED WITHANODIZEDALUMINUM HOUSING, INTEGRAL OCCUPANCY SENSOR, QUICK CONNECT, (DEFAULT 1% DIM). HARDWIRE ONEACH END SECTION.LISTING: UL DAMP LOCATIONS
BOCA FLASHERTASK
TASK-M-22-35000-120-W-NS-L-HW+QUICK CONNECT CABLES 4 6
LED, 82CRI, 35K(6 WATTS/FT) 2,120 N/A 24 120 SW/OC FURN PROVIDE HIDDEN HARD WIRE TO ON EACH DESK AREA.
SUSTAINABILITYROOM
F 25 RECESSED IN DRY WALL
2FT LED WALL RECESSED VANITY FIXTURE. NOM. 23"L x 2"H x 3" DEEP. PROVIDED WITH EXTRUDE WHITEACRYLIC DIFFUSER, INTEGRAL POWER SUPPLY LOCATED IN RECESSED BACK BOX.LISTING: UL, ETL DAMP LOCATIONS
VISA LIGHTINGWAND CB5400-LNW1700 (277V)-BA 1 26
WHITE LED(BY MANUFACTURER)
82CRI, 35K1,200 1 INTEGRAL 26 277 SW
ABOVEMIRROR
COORDINATE MOUNTING WITH MIRROR LOCATION.REQUIRES PRIOR INSTALLATION OF BACK BOX IN DRY WALL
SMALL BATHROOMS
F 30SURFACE WALL/VERTICALMOUNT
4 FT LINEAR FLUORESCENT VAPORTIGHT FIXTURE. NOM.: 3"H, 8"W, 48"L. PROVIDED WITH (2) LAMPS INCROSS SECTION, PRECISION STAMPED 20GA CRS HOUSING, 100% NEOPRENE GASKET, WHITE HIGH IMPACTBLEND VIRGIN ACRYLIC LENS AND INTEGRAL HPF INSTANT START ELECTRONIC BALLAST.LISTING: UL, CUL WET LOCATIONS AND HAZARDOUS LOCATIONS (CLASS I, DIV 2 GROUPS A,B,C,D) IBEWLABEL
KURTZON HL-C-1-40-2T8-277V 2 32
T8
F32T8TL835/ALTOPHILIPS
5,000 1 INTEGRAL 64 277 SW N/A
COORDINATE MOUNTING WITH EQUIPMENT LOCATION AND SPACECONDITIONS.LIGHTING CONTROL SWITH TO BE LOCATED NEXT TO FIXTURE.
ELEVATOR PIT(1ST FLOOR & TOPFLOOR)
F 30EMSURFACE WALL/VERTICALMOUNT
4 FT LINEAR EMERGENCY FLUORESCENT VAPORTIGHT FIXTURE. NOM.: 3"H, 8"W, 48"L. PROVIDED WITH (2)LAMPS IN CROSS SECTION, PRECISION STAMPED 20GA CRS HOUSING, 100% NEOPRENE GASKET, WHITE HIGHIMPACT BLEND VIRGIN ACRYLIC LENS, INTEGRAL HPF INSTANT START ELECTRONIC BALLAST AND 2-LAMPBATTERY PACK (1400 LUMENS).
LISTING: UL, CUL WET LOCATIONS AND HAZARDOUS LOCATIONS (CLASS I, DIV 2 GROUPS A,B,C,D) IBEWLABEL
KURTZON HL-C-1-40-2T8-277V- H2/EM 2 32
T8
F32T8TL835/ALTOPHILIPS
5,000 1 INTEGRAL 64 277 SW N/A
COORDINATE MOUNTING WITH EQUIPMENT LOCATION AND SPACECONDITIONS.LIGHTING CONTROL SWITH TO BE LOCATED NEXT TO FIXTURE.
LOCATION AS INDICATED ON ELECTRICAL PLANS
ELEVATOR PIT(1ST FLOOR & TOPFLOOR)
F 32 RECESSED CEILING
4" SQUARE 9W LED FIXED DOWNLIGHT. NOM.: 7"H, 13"W, 22"L. PROVIDED WITH, 20 GA. GALVANIZED STEELHOUSING, ALWAYS SQUARE FEATURE ALLOWS FOR SQ. APERTURE ALIGNMENT (20° ROTATION), 1"REGRESSED BEVEL, 1/2" WHITE PAINTED FLANGE, INJECTION MOLDED POLYCARBONATE 25° REFLECTOR,SOLITE LENS AND INTEGRAL ELECTRONIC DRIVER. LED IS RATED FOR 50.000 HOURS AND 70% LUMENMAINTENANCE (L70) AND 5 YEARS WARRANTY.LISTING: UL/CUL DRY DAMP LOCATIONS
USAi
TRIM: 3111-B1-S-10
HOUSING:LST4-9009-C3-35KS-25-NC-277-DIML2-CB**-
1 9
WHITE LEDBY MANUFACTURER
80CRI, 35K850 LUM
850 1 INTEGRAL 9 277 SW N/A
REFER TO ARCHITECTURAL PLANS FOR CEILING GRID TYPE FINALCOORDINATION.
COLOR FINISH OF FIXTURE TO BE APPROVED BY ARCHITECT.
CORRIDOR 1C2
F 32EM RECESSED CEILING
4" SQUARE 9W LED FIXED EMERGENCY DOWNLIGHT. NOM.: 7"H, 13"W, 22"L. PROVIDED WITH, 20 GA.GALVANIZED STEEL HOUSING, ALWAYS SQUARE FEATURE ALLOWS FOR SQ. APERTURE ALIGNMENT (20°ROTATION), 1" REGRESSED BEVEL, 1/2" WHITE PAINTED FLANGE, INJECTION MOLDED POLYCARBONATE 25°REFLECTOR, SOLITE LENS, INTEGRAL ELECTRONIC DRIVER AND EMERGENCY BATTERY PACK. LED IS RATEDFOR 50.000 HOURS AND 70% LUMEN MAINTENANCE (L70) AND 5 YEARS WARRANTY.LISTING: UL/CUL DRY DAMP LOCATIONS
USAi
TRIM: 3111-EML-B1-S-10
HOUSING:LST4-9009-C3-35KS-25-NC-277-DIML2-CB**-EML
1 9
WHITE LEDBY MANUFACTURER
80CRI, 35K850 LUM
850 1 INTEGRAL 9 277 SW N/A
REFER TO ARCHITECTURAL PLANS FOR CEILING GRID TYPE FINALCOORDINATION.
COLOR FINISH OF FIXTURE TO BE APPROVED BY ARCHITECT.
CORRIDOR 1C2
F 32A RECESSED CEILING
4" SQUARE 9W LED ADJUSTABLE DOWNLIGHT. NOM.: 7"H, 13"W, 22"L. PROVIDED WITH, 20 GA.GALVANIZED STEEL HOUSING, ALWAYS SQUARE FEATURE ALLOWS FOR SQ. APERTURE ALIGNMENT (20°ROTATION), 1" REGRESSED BEVEL, 1/2" WHITE PAINTED FLANGE, INJECTION MOLDED POLYCARBONATE 25°REFLECTOR AND 35° BEAM OPTICAL LENS, TRUE HOT AIMING, 0°-40° VERTICAL TILT, 362° ROTATION ANDINTEGRAL ELECTRONIC DRIVER. LED IS RATED FOR 50.000 HOURS AND 70% LUMEN MAINTENANCE (L70) AND5 YEARS WARRANTY.LISTING: UL/CUL DRY DAMP LOCATIONS
USAi
TRIM: 3131-B1-*-10-AL20F
HOUSING:LSTA4-8409-C3-35KS-25-NC-277-DIML2-CB**-
1 9
WHITE LEDBY MANUFACTURER
80CRI, 35K850 LUM
850 1 INTEGRAL 9 277 SW N/A
REFER TO ARCHITECTURAL PLANS FOR CEILING GRID TYPE FINALCOORDINATION.
COLOR FINISH OF FIXTURE TO BE APPROVED BY ARCHITECT.
CORRIDOR 1C2
F 32D RECESSED CEILING
4" SQUARE 9W LED FIXED DOWNLIGHT. NOM.: 7"H, 13"W, 22"L. PROVIDED WITH, 20 GA. GALVANIZED STEELHOUSING, ALWAYS SQUARE FEATURE ALLOWS FOR SQ. APERTURE ALIGNMENT (20° ROTATION), 1"REGRESSED BEVEL, 1/2" WHITE PAINTED FLANGE, INJECTION MOLDED POLYCARBONATE 25° REFLECTOR,SOLITE LENS AND INTEGRAL ELECTRONIC DRIVER. LED IS RATED FOR 50.000 HOURS AND 70% LUMENMAINTENANCE (L70) AND 5 YEARS WARRANTY.0-10V DIMMER IS STANDARD FOR THIS LED FIXTURE.LISTING: UL/CUL DRY DAMP LOCATIONS
USAi
TRIM: 3111-B1-S-10
HOUSING:LST4-9009-C3-35KS-25-NC-277-DIML2-CB**-
1 9
WHITE LEDBY MANUFACTURER
80CRI, 35K850 LUM
850 1 INTEGRAL 9 277 DIM N/A
REFER TO ARCHITECTURAL PLANS FOR CEILING GRID TYPE FINALCOORDINATION.
COLOR FINISH OF FIXTURE TO BE APPROVED BY ARCHITECT.
LOCAL CONTROL WALL BOX DIMMER (ONE FOR EACH CONTROL AREA)
OUTSIDE SIMULATIONAND MOCK UPROOMS
F 33
RECESSED CEILING (TECHZONEMETAL GRID)REFER TO ARCHITECTURALDRAWINGS FOR GRID TYPESELECTION.
4" PROFILE LENSED SLOT FIXTURE. NOM.: 4"H, 5"W, 4FT LONG. PROVIDED WITH (1) LAMP IN CROSSSECTION, EXTRUDED ALUMINUM HOUSING, RAL COLOR POWDER COAT FINISH (TO BE FINAL APPROVED BYARCHITECT), 0.40 FORMED ALUMINUM REFLECTOR, ACRYLIC LENS, SPECIAL MOUNTING ON METAL CEILINGAND INTEGRAL ELECTRONIC BALLAST.LISTING: UL, CUL DAMP LOCATIONS
ALWLP3.5RT(GRID-ATZ-SLOT-*)-4FT-T8-STD-1-277-WD-RAL (MATCH THEMETAL CEILING)
1 32T8
F32T8TL835/ALTOPHILIPS
2,500 1 INTEGRAL 32 277 SW N/A
COORDINATE MOUNTING WITH CEILING TYPE AND CONDITIONS.FINAL FINISH TO BE APPROVED BY ARCHITECT.FOR CEILING TYPE: APC-7 (ARMSTRONG METALWORKS TECHZONE, SQUARETEGULAR 6643M15SIA)"SILVERLUME" 12" x 48" 9/16" SUPRAFINE XL SUSPENSION SYSTEM, SILVERSATIN
BRIDGE
F 35 RECESSED CEILING
4" SQUARE LED ADJUSTABLE DOWNLIGHT. NOM.: 7"H, 13"W, 22"L. PROVIDED WITH, 20 GA. GALVANIZEDSTEEL HOUSING, ALWAYS SQUARE FEATURE ALLOWS FOR SQ. APERTURE ALIGNMENT (20° ROTATION), 1"REGRESSED BEVEL, 1/2" WHITE PAINTED FLANGE, INJECTION MOLDED POLYCARBONATE 25° REFLECTORAND SOLITE LENS ASSEMBLY PLUS ADDED 10 DEG LENS OPTICAL LENS, TRUE HOT AIMING, 0°-40° VERTICALTILT, 362° ROTATION AND INTEGRAL ELECTRONIC DRIVER. LED IS RATED FOR 50.000 HOURS AND 70%LUMEN MAINTENANCE (L70) AND 5 YEARS WARRANTY.LISTING: UL/CUL DRY DAMP LOCATIONS
USAi
TRIM: 3131-B1-S-10-AL10E
HOUSING: LSTA4-8416-C3-35KS-25-NC-277-DIML2-CB**-
1 16
WHITE LED(BY MANUFACTURER)
80CRI, 35K 1,300 1 INTEGRAL 16 277 SW N/ACOORDINATE MOUNTING WITH CEILING TYPE AND CONDITIONS.
ALL COLOR FINISH TO BE APPROVED BY ARCHITECT.CORRIDOR 1C2
F 38 SURFACE/WALL MOUNTED
3FT MULTI FUNCTIONAL PATIENT ROOM FIXTURE. NOM.: 5"H, 10"W, 36"LONG. PROVIDED WITH MARINEGRADE ALUMINUM BODY, HOUSING ATTACHED TO EXTRUDED CRS WALL MOUNTED BASE PLATE WITHINTEGRAL WIRING, HIGH IMPACT EXTRUDED LINEAR ACRYLIC LENS, MATTE WHITE ANTIMICROBIAL FINISH,AND TWO INTEGRAL ELECTRONIC BALLAST.LISTING: CUL, UL LISTED FOR DAMP LOCATIONS.
KENALL MPWF-36-MW-2/1-F25T8-DCC-277 3 25
T8
F25T8TL835/ALTOPHILIPS
887 2 INTEGRAL 75 277 DIM
COORDINATE MOUNTING WITH WALL ELEVATION DETAILS AND WALLMATERIALSFIXTURE TO BE MOUNTED ABOVE BED.
SIMULATION ANDMOCK UP ROOMS
F 39 RECESSED CEILING
4" SQUARE 24W LED ADJUSTABLE DOWNLIGHT. NOM.: 7"H, 13"W, 22"L. PROVIDED WITH, 20 GA.GALVANIZED STEEL HOUSING, ALWAYS SQUARE FEATURE ALLOWS FOR SQ. APERTURE ALIGNMENT (20°ROTATION), 1" REGRESSED BEVEL, 1/2" WHITE PAINTED FLANGE, INJECTION MOLDED POLYCARBONATE 25°REFLECTOR AND 25° BEAM OPTICAL LENS, TRUE HOT AIMING, 0°-40° VERTICAL TILT, 362° ROTATION ANDINTEGRAL ELECTRONIC DRIVER. LED IS RATED FOR 50.000 HOURS AND 70% LUMEN MAINTENANCE (L70) AND5 YEARS WARRANTY.DIMMING: 0-10V DIMMINGLISTING: UL/CUL DRY DAMP LOCATIONS
USAi
TRIM: 3131-B1-*-10-AL30E
HOUSING:LSTA4-8424-C3-35KS-25-NC-277-DIML2-CB**-
1 24
WHITE LEDBY MANUFACTURER
80CRI, 35K1800 LUM
1,800 1 INTEGRAL 24 277 DIM N/A
REFER TO ARCHITECTURAL PLANS FOR CEILING GRID TYPE FINALCOORDINATION. COORDINATE WITH FURNITURE/BED AND TABLES LOCATION(ALLOW NO MORE THAT 3FT RADIOUS FROM CENTER OF AIMING POINT)
COLOR FINISH OF FIXTURE TO BE APPROVED BY ARCHITECT.
MOCK UP PATIENTROOMS
F 8A EXTERIOR RECESSED CANOPY
6" ROUND COMPACT FLUORESCENT WET LOCATION DOWNLIGHT. NOM.: 7"H, 15"W, 16"L. PROVIDED WITH,STEEL CONSTRUCTION, PAINTED FLANGE (COLOR TO BE APPROVED BY ARCHITECT), SEMI-SPECULAR MATTEDIFFUSE FINISH, WET LOATION LENS AND INTEGRAL ELECTRONIC BALLAST RATED FOR LOWTEMPERATURES.LISTING: UL WET LOCATION (UNDER CANOPY)
GOTHAMAF-1/32TRT-6AR-LD-FOL-277-(MOD) COLD WEATHER BALLAST-FLANGE COLOR-WL
1 32
CFL TRIPLE TUBEPL-T 32W/835/A/
4P/ALTOPHILIPS
2,040 32 277 SW N/ACOORDINATE MOUNTING WITH CEILING TYPE AND CONDITIONS.
COLOR FINISH OF FIXTURE FLANGE TO BE APPROVED BY ARCHITECT.EXTERIOR CANOPY
F 8AEM EXTERIOR RECESSED CANOPY
6" ROUND COMPACT FLUORESCENT WET LOCATION DOWNLIGHT. NOM.: 7"H, 15"W, 16"L. PROVIDED WITH,STEEL CONSTRUCTION, PAINTED FLANGE (COLOR TO BE APPROVED BY ARCHITECT), SEMI-SPECULAR MATTEDIFFUSE FINISH, WET LOATION LENS, INTEGRAL ELECTRONIC BALLAST RATED FOR LOW TEMPERATURESAND EMERGENCY BATTERY PACK WITH REMOTE TEST SWITCH.LISTING: UL WET LOCATION (UNDER CANOPY)
GOTHAMAF-1/32TRT-6AR-LD-FOL-277-(MOD) COLD WEATHER BALLAST-FLANGE COLOR-WL-ELR
1 32
CFL TRIPLE TUBEPL-T 32W/835/A/
4P/ALTOPHILIPS
2,040 32 277 SW N/ACOORDINATE MOUNTING WITH CEILING TYPE AND CONDITIONS.
COLOR FINISH OF FIXTURE FLANGE TO BE APPROVED BY ARCHITECT.EXTERIOR CANOPY
F 36 SURFACE/WALL MOUNTED
EXTERIOR RATED LED WALLPACK FIXTURE. NOM.: 17"H,10"W, 16" DEEP. PROVIDED WITH DIE-CASTALUMINUM HOUSING, ALUMINUM REMOVABLE ALUMINUM DOOR, ONE PIECE SILICONE GASKET GRAY COLORFINISH, LM70 AND LM-79 AND INTEGRAL HIGH EFFICIENCY ELECTRONIC DRIVER.LISTING: UL, CUL FOR WET LOCATIONS, IP65 COOPER LUMARK LD-WP-FC-2A-277V-BK-WG/WPFC 1 28
WHITE LED(BY MANUFACTURER)
80CRI, 35K 1,090 1 INTEGRAL 28 277 SW7'-0" &
3'-0"
COORDINATE MOUNTING WITH ARCHITECTURAL WALL ELEVATION DETAILSAND WALL MATERIALSFIXTURE TO BE MOUNTED:ABOVE DOOR: 7'-0" ABOVE THE SLAB.PARAPET WALL: 3'-0" ABOVE TOP OF SLAB ELEVATION.J-BOX BY OTHERS.
ROOF
F 37 SURFACE/WALL MOUNTED
6" DIAMETER CYLINDER LED EXTERIOR RATED FIXTURE. NOM.: 12"H, 8"W. PROVIDED WITH DIE-CASTALUMINUM BODY, MACHINE ALUMINUM MOUNTING PLATE, GRAY COLOR FINISH, (1) LED ENGINE RATED L70AND LM-79, 30° BEAM ANGLE AND ADJUSTABLE REFLECTOR (20°), AND INTEGRAL HIGH EFFICIENCYELECTRONIC DRIVER.LISTING: CUL, IP65
SISTEMALUX S.3940-UNV-14-** 1 18WHITE LED
(BY MANUFACTURER)80CRI, 40K
887 18 277 SW N/A
COORDINATE MOUNTING WITH ARCHITECTURAL WALL ELEVATION DETAILSAND WALL MATERIALSFIXTURE TO BE MOUNTED ABOVE DOOR.J-BOX BY OTHERS
1RST FLOOR SIDEEXIT
F 37EM ONLY AVAILABLE WITH REMOTE INVETER
F 37EM (alt) SURFACE/WALL MOUNTED
LED EXTERIOR RATED FIXTURE WITH EMERGENCY CAPABILITY. NOM.: 8"H, 17"W, 8" DEEP. PROVIDED WITHDIE-CAST ALUMINUM HOUSING, 4" BACK BOX FOR INTEGRAL EMERGENCY BATTERY AND INTEGRAL DRIVERFOR COLD WEATHER OPERATION.
LISTING: CUL, UL WET LOCATION
EATON Mc GRAW-EDISON ISW-E01-LED-E1-BL2 (SLL/SLR)-BK-
BBB-277V- 3000K1 21
WHITE LED(BY MANUFACTURER)
80CRI, 30K
2,435 1 INTEGRAL 1.00 21 277 SW N/A
COORDINATE MOUNTING WITH ARCHITECTURAL WALL ELEVATION DETAILSAND WALL MATERIALS.COORDINATE LOCATION OF SPILL ELIMINATOR LEFT AND RIGHT FORFIXTURE LOCATED INSIDE VESTIBULES. SPILL ELIMINATOR TO BE PROVIDEDON FIXTURE SIDE ADJACENT TO THE BUILDING.FIXTURE TO BE MOUNTED ABOVE DOOR.
1RST FLOOR SIDEEXIT
EX 1 SURFACE / CEILING MOUNTEDSURFACE MOUNTED LED EXIT LIGHT. PROVIDED WITH 18-GA STEEL HOUSING COOPER ATLITE
MARATHON SERIES SCM-A1/2-6-RC-WH-ARROW N/A 0 277 SW N/ACOORDINATE MOUNTING WITH CEILING TYPE AND CONDITIONS.COLOR FINISH TO BE APPROVED BY ARCHITECT.ARROW DIRECTIONS AS INDICATED IN ARCHITECTURAL PLANS
GENERAL
EX 2 SURFACE / WALL MOUNTEDSURFACE MOUNTED LED EXIT LIGHT. PROVIDED WITH 18-GA STEEL HOUSING COOPER ATLITE
MARATHON SERIES SEM-A1/2-6-RC-WH-ARROW N/A 0 277 SWABOVEDOOR
COORDINATE MOUNTING WITH CEILING TYPE AND WALL CONDITIONS.COLOR FINISH TO BE APPROVED BY ARCHITECT.ARROW DIRECTIONS AS INDICATED IN ARCHITECTURAL PLANS
MER
EX 3 SURFACE / WALL MOUNTEDSURFACE MOUNTED EXTERIOR LED EXIT LIGHT. PROVIDED WITH DIE CAST ALUMINUM HOUSING, 120/277 V,UNIVERSAL MOUNTING HOUSING.LISTING: IP66 RATED, NEMA 4 RATED
COOPER ATLITEINDUSTRIAL UXA-6-D-R-1-X-SDL--UXPKA/VRSD N/A 0 277 SW
ABOVEDOOR
COORDINATE MOUNTING WITH WALL CONDITIONS.ROOF
EXIT SIGNS
EXTERIOR LIGHTING
LAMP
TYPE
LIGHTING FIXTURE SCHEDULE
BALLAST/DRIVER
2
2
2
2
“
”
”
” ”
2
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
DATENO. ISSUE
KEY PLAN
Acoustical Consultant:
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
101 VERA King Farris DriveGalloway, NJ 08205
101 Vera King Farris DriveGalloway, NJ 08205
515 Grove StreetHaddon Heights, NJ, 08035
326 Ward StreetDunmore, PA 18512
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
417 Fifth AvenueNew York, NY 10016
06/01/2016
ISSUED FOR CONSTRUCTION
NO SCALE
LIGHTINGFIXTURESCHEDULE
04/22/162 ADDENDUM #2
EXISTING MANHOLE,MH-2. APPROXIMATELOCATION.
CLASSROOM PAD-MOUNTEDTRANSFORMER ON CONCRETE PAD.PAD DIMENSIONS APPROXIMATELY4-IN LARGER IN WIDTHAND DEPTH OF TRANSFORMERDIMENSIONS PER MANUFACTURERSRECOMMENDATIONS.
FRON
T
MAIN ELECTRICALROOM
MAIN DISTRIBUTIONSWITCHBOARD
4-WAY 6-INCH UNDERGROUND CONCRETEENCASED ELECTRICAL DUCTBANK
6-WAY, 4-INCHUNDERGROUND CONCRETEENCASED ELECTRICALDUCTBANK
TYPICAL CONCRETE-ENCASED ELECTRICALDUCTBANK DETAIL
INTERMEDIATE DUCT SEPARATOR AT 4' SPACING
FINISH GRADE
CONCRETE WITH RED DYE RAKED INTO TOP 2INCHES, MINIMUM 2500 LB TEST
NO. 5 RE-BAR CONTINUOUS (TYPICAL)
YELLOW PLASTIC WARNING TAPE "HIGHVOLTAGE POWER LINES"
NOTE 3
EPC DUCT (TYPICAL)
BASE DUCT SEPARATORAT 4' SPACING
BACKFILL
NOTES:1. PROVIDE CONDUIT SIZE, NUMBER OF WAYS, AND DUCT CONFIGURATION AS INDICATED ON PLANS.
2. PROVIDE A MINIMUM SPACE OF 3 INCHES BETWEEN INDIVIDUAL DUCTS, AND A MINIMUM SPACEOF 3 INCHES BETWEEN DUCTS AND EXTERIOR ENVELOPE WALL.
3. INSTALL TOP OF DUCT BANK AT LEAST 24 INCHES BELOW FINISHED GRADE IN AREAS NOTSUBJECT TO DELIBERATE TRAFFIC, AND AT LEAST 30 INCHES BELOW FINISHED GRADE INDELIBERATE TRAFFIC PATHS FOR VEHICLES, UNLESS OTHERWISE INDICATED.
4. INTERFACE DUCTBANK STEEL REINFORCING RODS WITH BUILDING FOUNDATIONS, MANHOLE ANDHANDHOLE WALLS, AND CABLE VAULT WALLS TO MINIMIZE SHEARING.
5. MAINTAIN A MINIMUM OF 12" SEPARATION BETWEEN POWER AND COMMUNICATIONS DUCTS.
EXISTING 12.47kVFEEDER D
EXISTINGMANHOLEMH-2
3E100 NTS
SCALE:MEDIUM-VOLTAGE SITE POWER
DISTRIBUTION SCHEMATIC DIAGRAM
EXISTING 12.47kVFEEDER C
3-500kcmil (15kV) IN 6-INCHUNDERGROUND DUCTBANKD
3-500kcmil (15kV) IN 6-INCHUNDERGROUND DUCTBANKC
D
C
NOTES:1. PROVIDE SEPARABLE CONNECTOR
SPLICE OF EXISTING MEDIUM-VOLTAGECAMPUS FEEDERS AS INDICATED.
2. COORDINATE NECESSARY POWERSHUT-DOWNS WITH OWNER.
3. COORDINATE EXACT CABLE TYPE WITHSTOCKTON AND ATLANTIC CITYELECTRIC.
C
D
T0 CLASSROOM BUILDINGOUTDOOR PAD-MOUNTED
TRANSFORMER. REFERTO POWER DISTRIBUTION
SINGLE-LINE DIAGRAMDRAWIG E-401 FOR
ADDITIONAL DETAILS
EXISTING 12.47kVFEEDER D
EXISTING 12.47kVFEEDER C
SEE NOTES 1 & 2
EXISTING MANHOLE,MH-1. APPROXIMATELOCATION. PLAN
NORTH
NOTES:1. ELECTRICAL SITE PLAN DRAWING IS DIAGRAMMATIC. REFER TO CIVIL ENGINEER'S DRAWINGS FOR EXACT
LOCATIONS OF NEW AND EXISTING MANHOLES AND OTHER ABOVEGROUND AND UNDERGROUNDSTRUCTURES, FINAL DUCTBANK ROUTING, FINAL DUCTBANK TERMINATION LOCATIONS, AND REROUTING ORREMOVAL OF ANY EXISTING UNDERGROUND UTILITIES. COORDINATE DUCTBANK ROUTING WITH OTHERTRADES AND UTILITIES.
2. REFER TO CIVIL ENGINEER'S SITE LIGHTING PLAN FOR FIXTURE SPECIFICATIONS AND MOUNTING DETAILS.COORDINATE ROUTING OF SITE LIGHTING BRANCH CIRCUITS WITH OTHER TRADES AND UTILITIES.
3. UNDERGROUND CIRCUITING FOR SITE LIGHTING SHALL UTILIZE XHHW CONDUCTORS IN DIRECT-BURIEDSCHEDULE 40 PVC CONDUITS. CIRCUITING SHOWN ON DRAWINGS IS DIAGRAMMATIC AND DOES NOT INDICATEACTUAL PATH OR ROUTING REQUIRED.
4. SITE LIGHTING FIXTURES SHALL BE CONTROLLED VIA BUILDING-MOUNTED PHOTOCELL. PROVIDE PHOTOCELLCONTROLLED CONTACTOR IN MAIN ELECTRICAL ROOM TO CONTROL SITE LIGHTING FIXTURES.
5. MANHOLES SHALL BE MINIMUM 8' x 8' x 6' DEEP INSIDE DIMENSION, UNLESS OTHERWISE NOTED.6. MOUNT OUTDOOR ELECTRICAL EQUIPMENT, INCLUDING TRANSFORMERS, GENERATORS AND GENERATOR
LOAD BANKS, ON MINIMUM 6-INCH THICK STEEL-REINFORCED CONCRETE PADS. PROVIDE GROUND LOOPAROUND EACH OUTDOOR CONCRETE PAD IN ACCORDANCE WITH PROJECT SPECIFICATIONS AND CONNECTINTO MAIN BUILDING GROUND LOOP IN AT LEAST TWO DIAMETRICALLY-OPPOSED LOCATIONS.
E100 1" = 20'-0"1 ELECTRICAL SITE PLAN
2E100 NTS
SCALE:
(3) 277V 20ABRANCHCIRCUITS FROMPANEL NP1A
NP1A-18
UNDERGROUND CIRCUITINGFOR SITE LIGHTING (TYPICAL)
UNDERGROUNDCIRCUITING FORSITE LIGHTING(TYPICAL)
POWER FOR EMERGENCYCALL BOX (TYPICAL)J
J
EA1-7
SITE-LIGHTING INTHIS AREA SERVEDFROM USC2.
CB
CB
M1
M1
M1M1
M1
M1
FLDFLD
FLD
M1
M1
ELECTRICAL SYMBOLS LEGEND
WM
M1
FLD
EA1-8
NEW 8'L x 8'W x 7'H MANHOLE, MH-2A.SEE DETAIL 11 ON DRAWING E-701FOR ADDITIONAL DETAIL.
P2
M1 WMWM
WM
WM WM
P2
P2
P2
P2
P2 P2 P2
P2
P2
P2
P2
P2
P2
P2
FLD
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
DATENO. ISSUE
KEY PLAN
Acoustical Consultant:
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
101 VERA King Farris DriveGalloway, NJ 08205
101 Vera King Farris DriveGalloway, NJ 08205
515 Grove StreetHaddon Heights, NJ, 08035
326 Ward StreetDunmore, PA 18512
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
417 Fifth AvenueNew York, NY 10016
06/01/2016
ISSUED FOR CONSTRUCTION
1" = 20'-0"
ELECTRICAL SITEPLAN
G
G
G
G
GG
GP
JMP
JMP
P
PCR
PCR
PCR
PCR
PCR
PCR
PCR
PCR
PCR
PCR
F2
F2F2
G G
VD VD
VD
VD
G
J
J
JVV
JVV
JVV
JVV
JVV
JVV
JVV
PCRWP
WP
WP
WP
WP
WP
WP
J
J
J
JHD
JH
DJ
HD
JHD
G F
GG
EWC
VD VD VD
M
M M
M
JTP
JTP
JTP
J
J
J
J
J
J
STAIR 2
1S2
VESTIBULE
1V1
STAIR 1
1S1
CLASSROOM
104
EXERCISE ROOM
102
SUSTAINABILITY
101
OFFICE
101A
WATER ENTRY /MECH CHW
1M1ELECTRICAL
ROOM
1E3
VESTIBULE
1V2 MEN'S TOILETS
1T3
CORRIDOR
1C2
WOMEN'STOILETS
1T4
STOR.
102BJAN.
1T1
LOBBY
1L1
CORRIDOR
1C3
IT
1E1
ELECTRICAL
1E2
LACTATION
1T5
WASTE HOLDING
1T6
VENDING
1T7
TOILET
1T2
STOR.
101B
OFFICE
101C
VESTIBULE
1V3
STOR.
101E
WORK ROOM
102A
1
2
5
5
5
6
4 4
6
20
1
1
20
1
1
2
2
2
2
6
6
6
5
5
3
3
28
4
7
7
14,16,18
8,10,12
9,11,13
CUH
1
AC
1
AC
2
UH
1
UH
1
7
AC
7
POWER FORELEVATOR SP-1
CUH
2
15
15
17NA1A - 8
NA1C
6 6
14
14
4
15
16
20
20
20
17
21 21
18
18
18
1919
2323 23 23
24242424
22
NA1A
NA1A
NA1B - 1 NA1B - 2
NA1B - 6
NA1B - 7
NA1C
NA1B - 8
NA1B - 8
NA1B - 3 NA1B - 3 NA1B - 3 NA1B - 4 NA1B - 4 NA1B - 4
NA1B - 5
NA1B - 5
NA1B
9
9
9
NA1B - 10 NA1B - 10
NA1C - 26
NA1C - 26
11 12
NA1B
CUH
2
HAC
2
HAC
1
NA1B - 13
NA1B - 13
3
NA1B - 14
NA1B - 13
19
19
NA1C4
NA1B
15
15
15
NA1D - 1
NA1D - 1
NA1D - 1
NA1D - 1
NA1D - 2
NA1D - 2
NA1D - 2
NA1A - 25
52 3 4 961
C
B
A
14
11
F
H
13
8
G
10
B.5
12
7
15
E
B.6
NA1D - 6
NA1D - 8
NP3B - 31,33,35
NP1A - 1,3,5
NP3B - 32,34,36
NA1D - 10
NP1A - 2,4,6
NA1C - 21
NA1C - 22
NA1B - 19
NA1B - 18
NA1B - 20
NA1B - 17
NA1B - 16
E-2013
E-2012
NA
1D -
18,
20
NA1D - 18,20
NA1B - 24
NA1B - 23
NA1B - 21
NA1B - 22
E-2014
NA1B - 5
POWER FOR SPLIT SYSTEM ACUNIT POWERED BY CONDENSINGUNIT CU-2 ON ROOF.
20
NP1A - 24,26,28
AC
8POWER FOR SPLIT SYSTEM ACUNIT POWERED BY CONDENSINGUNIT CU-3 ON ROOF.
10
29
5
15
15
283
3
29
NA1B - 10 NA1B - 10
NA1C - 27
15
9
9
9
9
3
3
3
3
23 23 24
25
25
NA1C
MOUNTED INAV CABINET
NA1C
11
12 13 26
4
NA1A - 28
NA
1A -
28
NA
1A -
28
NA1A - 30
BP
1
NA
1C -
30
NA1C - 30
NA1C - 30
NP1A - 25,27,29
2
2
2
IT
1E1
ELECTRICAL
1E2
9
NA1A NA1B NP1A
NDA1 NA1C NA1D
NX1
GROUND BUS
NA1D4 4
IT
1E1POE SWITCH
FA REMOTEPOWER SUPPLY
FA REMOTEAMPLIFIER CABINET
ELECTRIFIED DOORLOCK CONNECTION
SECURITY PANELCONNECTION
FA CONTROL PANEL
11
3 NA1D
3 17
3
16
7
13
912
15
14
ELECTRICALROOM
1E3
B
7
GROUND BUS
5
5
5
NA1D
MDS
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
As indicated
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-201
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
LEVEL 1 ELECTRICALPLAN - POWER
24'8'0'
1/8" = 1'-0"1
LEVEL 1 ELECTRICAL PLAN - POWER
12'4'0'
1/4" = 1'-0"3
LEVEL 1 - ENLARGED ELECTRICAL 1E2
12'4'0'
1/4" = 1'-0"2
LEVEL 1 - ENLARGED IT 1E1
12'4'0'
1/4" = 1'-0"4
LEVEL 1 - ENLARGED ELECTRICAL 1E3
2 04/22/16 ADDENDUM #2
EWC
G
JMP
JMP
P
G
F1
F1F1
F1
VD
VD
VD
JB
H
JVV
JVV
JVV
JVV
JVV
JVV
JVV
JVV
JVV
JVV
JVV
JHD
JHD
JH
DJ
HD
G
G
G
VD
VD
G
P
MW
VD
P
G
F1
VD
F
F
G
M M
M
JT
P
JTP
VF
D
VF
D
VF
D
VF
D
JJ
STAIR 2
2S2
CLASSROOM
201
STAIR 1
2S1
DEAN'S OFFICE
217
ASSIST. DEANOFFICE
218
ASSIST. DEANOFFICE
219
CORRIDOR
2C2
MECHANICAL
2M1
STOR.
212
FACULTY CONF.ROOM
216
MAIL ROOM
222
FILE STORAGE
220
IT
2E2
ELECTRICALROOM
2E1
SEMINAR ROOM
201B
WOMEN'STOILETS
2T2
MEN'S TOILETS
2T1
JAN.
2T3
CORRIDOR
2C1
SIMULATIONROOM
204
DEAN'S SUITE
215
WORK ROOM
221
SIMULATIONSUITE
202
SIMULATIONROOM
203
DISPENSARY/STOR.
211
POST CONF.ROOM
205
OFFICE
206
PRE CONF. ROOM
207
TOILET CHANG'GROOM
213
GOWNED WTG.
212
MOCK PATIENTBED ROOM
208
MOCK PATIENTEXAM ROOM
210
MOCK PATIENTEXAM ROOM
209
CLOSET
223
CONTROLCORRIDOR
202A
1
6
3
3
3
4 4 4
2
5
5
5
6
1
7
EFTR
1
MOUNTED INAV CABINET
AC
4
AC
3
NA2A
NA2C
13
3
NA2C
33
6
33
5
6
5
NA2C
NA2C
8
7
13
7
12
12
14
18
18
16
20
NA2B - 1
171
16
19
NA2B - 1
19
5
NA2B - 1
NA2B - 8
NA2B - 9 NA2B - 9 NA2B - 9 NA2B - 9 NA2B - 9 NA2B - 9 NA2B - 10 NA2B - 10 NA2B - 10
NA2B - 10
NA2B
11
1111
NA2A
10
NA2B - 12
NA2B - 12
NA2B - 14
NA2B - 17
17
13
15
15
14
15
16
15
NA2D
2
2
NA2D - 3
NA2D - 4NA2D - 4
52 3 4 961
C
B
A
14
11
F
H
13
8
G
10
B.5
12
7
15
E
B.6
B.2
NA
2A -
15,
17
NA2A - 15,17
NA2C - 32
NA2C - 18
NA2C - 19
NA2C - 20
NA2B - 18
NA2D - 5
NA2B - 19
NA2B - 20
NA2B - 21
NA2A - 22
NA2A - 23NA2A - 24
E-2023
E-2022
NA2D - 9
NA2D - 10
NA2D - 11
NA2D - 12
NA2B - 10
24
POWER FOR BAS HEAD END
POWER FOR SPLIT SYSTEM ACUNIT POWERED BY CONDENSINGUNIT CU-3 ON ROOF.
AC
9
12
13 13
NA2B - 1
22
8
8
8
17
17
17
17 5
5
6
6
6
19
NA2B - 1
18
1818
716
2322
2223
7
NA2B - 1
2
2
9
18 4
4
4
3
3
3
5
2
31
31
7
24
24
28
29
30
33
10
26
11
1
1
2
2
2
10
NA2D - 4
4
9
12
17
NA2B - 10
NA2D - 20
NA2D - 20NA2D - 21NA2D - 21
NA2B - 25
NA2B - 25NA2B - 25
NA2A
NA2A
NA2C
NA2C
NA2C
2
2
NA2D
22
NA2DNA2B
NA2BNA2B
NA2A
NA2A
22
22
NA2B - 2
NA2B - 26
NA2B - 2
NA2B - 26
NA2B - 2
NA2B - 26
NA2C-21,23,25,27
PROVIDE POKETHRU WITHELECTRIC WHIP FOR SURFACEMOUNTED RACEWAY AT TABLELEG. REFER TO ARCH. DWGS.FOR ADDITIONAL INFORMATION.
NA2B - 15
NA2B - 15
NA2B - 15
31
SHWP
2
SHWP
1
HWP
2
HWP
1
NA
2B -
27
NA
2B -
27
NA1A - 30
NA2B - 28
NA
2B -
28
NP
3A -
38,
40,4
2
NP
3A -
32,
34,3
6
NP
3A -
20,
22,2
4
NP
3A -
8,1
0,12
2 2
2 2
2
2
31 31
NA2B NA2B
2 2
29
29
2
2
292
2
2
2
NA2B - 13
NA2B - 13
2
33
5
2
22
2
2
ELECTRICALROOM
2E1
9
NP2A NDA2
NA2ANA2BNA2CNA2D
NX2
GROUND BUS
NA2D
8
8
IT
2E2
POE SWITCH
FA REMOTE POWERSUPPLY
7
7
716
15
14
NA2D
6
13
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
As indicated
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-202
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
LEVEL 2 ELECTRICALPLAN - POWER
24'8'0'
1/8" = 1'-0"1
LEVEL 2 ELECTRICAL PLAN - POWER
12'4'0'
1/4" = 1'-0"3
LEVEL 2 - ENLARGED ELECTRICAL 2E1
12'4'0'
1/4" = 1'-0"2
LEVEL 2 - ENLARGED IT 2E2
2 04/22/16 ADDENDUM #2
VFD VFD
M
M M
JTP
M
M
JJ
STAIR 1
3S1
STAIR 2
3S2
IT
3E2
ELECTRICALROOM
3E1
MECHANICAL
3M1
ELEV.
3EL
B
2
B
1
AC
6
AC
5
TO EF-1 TO EF-2
NP
3B -
14,
16,1
8
NP
3B -
13,
15,1
7
FS1
FS4
ELEVATOR CONTROLLOR POWER.
ELEVATOR CAB/LTG POWER.
NA
3A -
2
NA3A - 2 NA3A - 2
NA3A - 2
NA
3A -
2
NA
3A -
3
NA
3A -
2
NA3A - 1
NA3A - 1
52 3 4 961
C
B
A
14
11
F
H
13
8
G
10
B.5
12
7
15
E
B.6
B.2
NA3A - 17,19
NA
3A -
17,
19 E-2032
E-2033
POWER FOR SPLIT SYSTEM ACUNIT POWERED BY CONDENSINGUNIT CU-3 ON ROOF.AC
10
NA3A - 1
NA3A - 1
NP3B - 20,22,24
NA1A - 30
NA
3A -
21
NA
3A -
21
NA3A - 23 NA3A - 24
NA3A - 15
NA3A - 25
GWH
1NA3A - 26
NA3A - 28
POWER FOR HWCP-1
ELECTRICALROOM
3E1
9
NP3ANA3A NP3B
NA3A
13
13
13
POE SWITCH
FA REMOTE POWERSUPPLY
7
7
710
9
8
NA3A
11
12
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
As indicated
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-203
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
LEVEL 3 ELECTRICALPLAN - POWER
24'8'0'
1/8" = 1'-0"1
LEVEL 3 ELECTRICAL PLAN - POWER
12'4'0'
1/4" = 1'-0"2
LEVEL 3 - ENLARGED ELECTRICAL 3E1
12'4'0'
1/4" = 1'-0"3
LEVEL 3 - ENLARGED IT 3E2
WPSM
WP
SM
WP SMWP SMWP SM
WP
SM
WPSM WPSM
WP
SM
WP SM
VFD VFD VFD VFD
STAIR 2
4S2
CU
1
EF
1
CU
2
EF
2
TO MDP INELECTRICAL 1E2
TO MDP INELECTRICAL 1E2
NA3A - 14,16
NP3A - 26,28,30
TO VFD INMECHANICAL 3M1
TO VFD INMECHANICAL 3M1
NA3A - 6
NA
3A -
6
NA3A - 6
NA3A - 5
NA3A - 4 NA3A - 4
NA3A - 5
NA
3A -
5
NA3A - 4
NA3A - 5
52 3 4 961
C
B
A
14
11
F
H
13
8
G
10
B.5
12
7
15
E
B.6
B.2
NP
3A -
2,4
,6
NP
3A -
2,4
,6
NP
3A -
14,
16,1
8
NP
3A -
14,
16,1
8
CU
3
NA3A - 18,20,22
AHU
1
AHU
2
POWER FOR HWP-3
POWER FOR HWP-4
POWER FOR HWP-5
POWER FOR HWP-6
2
2
2
2
2
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
1/8" = 1'-0"
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-204
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
ROOF ELECTRICALPLAN - POWER
24'8'0'
1/8" = 1'-0"1
ROOF ELECTRICAL PLAN - POWER
2 04/22/16 ADDENDUM #2
TT
T
3 a3 b
3a
3a
OS2 OS2
T
T
OS2OS2OS2OS2
T
OS2
OS2
OS2
OS3OS3 OS3
OS2
T3a3b
T
T
T
WP
3b
3b
3c
3c
3a3b
3 a3 b
OS2OS2
OS1
OS2
OS1
OS1
OS2
J
STAIR 2
1S2
VESTIBULE
1V1
STAIR 1
1S1
CLASSROOM
104
EXERCISE ROOM
102
SUSTAINABILITY
101
OFFICE
101A
WATER ENTRY /MECH CHW
1M1ELECTRICAL
ROOM
1E3
VESTIBULE
1V2 MEN'S TOILETS
1T3
CORRIDOR
1C2
WOMEN'STOILETS
1T4
STOR.
102BJAN.
1T1
LOBBY
1L1
CORRIDOR
1C3
IT
1E1
ELECTRICAL
1E2
LACTATION
1T5
WASTE HOLDING
1T6
VENDING
1T7
TOILET
1T2
STOR.
101B
OFFICE
101C
VESTIBULE
1V3
STOR.
101E
WORK ROOM
102A
EMERGENCY DISCHARGE LIGHT (TYPICAL OF 5).WET-LISTED, VAPORTIGHT/GASKETED, COMPACT
FLUORESCENT WITH DUAL BALLAST. ELCAST1490-14"-175MHPS-ETI OR EQUIVALENT.
F12REMa
F12R
F12R
F12R
F12R
F12R
F12R F12R
F12R
F12R
F12R
F12REM F12R F12R
F12R
F12R
F12R
F12RF12R
F12R
F12R
F12R
b
b
b
b
b
b b b b
b
b
b
b b
b
b
b b
b
b
b
F12R
F12R
F12R
F12R
F12REM F12R
F12R
F12R
F12R
F12R F12R
F12R
F12R
F12R
F12R F12REM
F12R
F12R
F12R
F12REMF12R
F12R
F12R
F12R F12REM
F12R
F12R
F12R
b
b
b
b
b b
b
b
b
b b
b
b
b
b b
b
b
b
b
b
b
b
b
b
b
F12R
F12R
F12R
F12R
F12REM F12R
F12R
F12R
F12R
F12R F12R
F12R
F12R
F12R
F12R F12R
F12R
F12R
F12R
F12R F12
F12
F12
F12
F12 F12EM
F12
F12
F12
F12
a b
a
a
a
a
b
b
b
b
b b
b
b
b
b b
b
b
b
b b
b
b
b
b
b
b
b
b
F12 F12EM F12 F12 F12EM F12 F12 F12EM F12 F12 F12EM F12 F12 F12EM F12 F12 F12EM F12 F12
F12EM
F12
F12
F12EM
F3A
F3A
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F20
F8B
F8BEM
F8B
F8BEM
F8B
F8BF8B
F8BEM
F8B
F8BEM
F8
F8EM F8EM
F8
F8BEM
F8EM F8
F8B
F8BF8B
F8A F8A
F8BEM
F8BEM
F10
F10
F10
F5EM F5EM
F5EM F5EM
F5EM
F5EM
EM
F5EM
F5EM
F5WEM F5WEM
F5WEMF5WEM
F18F18 F18
F18
F18F18
F17
F17F12CEM
F16EM
F16EM
F8
F8
F8EM
F17
F17
F17
F17
F17
F20
F8BEM
F8B
F8BEM
F8B
F8EM
F8EM
F32F32EMF32
F32F32
F32A F32EM
F32F32A
F32F32A
F24
F20
F8A F8A F8A F8A F8A F8A F8A F8A F8A F8A
F8A
F8A
F8A
F8A
F8AEM
F8AEM
F8AEM
F30EM
PHOTOCELL CONTROLLED. REFERTO DETAIL 4 ON DWG. E-702.
52 3 4 961
C
B
A
14
11
F
H
13
8
G
10
B.5
12
7
15
E
B.6F12R
F12R
F12R
F12R
b
b
b
bF12R
F12R
F12R
F12R
a
a
a
a
F37EM
F37EM
F37EM F37F37EMEM
F37
F37
EM
EM
NP1A- 7
NP1A- 8 NP1A- 9 NP1A- 10
NP1A- 11 NP1A- 11
NP1A- 11
NP1A- 12
NP1A- 12
NP1A- 13
NP1A- 12
PHOTOCELLCONTROLLED. REFER TODETAIL 4 ON DWG. E-702.
NP1A- 14
NP1A- 14
NP1A- 19
NP1A- 14
NP1A- 15
NP1A- 15
NP1A- 15
NP1A- 17
NP1A- 15
NP1A- 16
NP1A- 12
NP1A- 8
NP1A- 14
NP1A- 7
F17
NP1A- 20
NP1A- 22
F25
NP1A- 9
NP1A- 21
F19EM
F19EM
NOTES:1. ALL EXIT SIGNS ARE TYPE EX1, UNLESS
NOTED OTHERWISE.
F5
NP1A- 11
22
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
1/8" = 1'-0"
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-301
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
LEVEL 1 ELECTRICALPLAN - LIGHTING
24'8'0'
1/8" = 1'-0"2
LEVEL 1 ELECTRICAL PLAN - LIGHTING
2 04/22/16 ADDENDUM #2
T
3a3b
3 b3 a
OS2
OS3OS3
OS2
OS2OS2
T
OS2
OS2OS2
OS2
OS2
OS2
OS2
OS2
OS2 OS2
OS1
OS3 OS3 OS3 OS3
T
OS2
T
T
T
T
OS3
OS2 OS2 OS2 OS1
OS1
OS1
OS2
OS2
D D Db c
d e d e
D b c
OS2
DDD
D b
D
D bD
de
DbD
OS1
J
STAIR 2
2S2
CLASSROOM
201
STAIR 1
2S1
DEAN'S OFFICE
217
ASSIST. DEANOFFICE
218
ASSIST. DEANOFFICE
219
CORRIDOR
2C2
MECHANICAL
2M1
STOR.
212
FACULTY CONF.ROOM
216
MAIL ROOM
222
FILE STORAGE
220
IT
2E2
ELECTRICALROOM
2E1
SEMINAR ROOM
201B
WOMEN'STOILETS
2T2
MEN'S TOILETS
2T1
JAN.
2T3
CORRIDOR
2C1
SIMULATIONROOM
204
DEAN'S SUITE
215
WORK ROOM
221
SIMULATIONSUITE
202
SIMULATIONROOM
203
DISPENSARY/STOR.
211
POST CONF.ROOM
205
OFFICE
206
PRE CONF. ROOM
207
TOILET CHANG'GROOM
213
GOWNED WTG.
212
MOCK PATIENTBED ROOM
208
MOCK PATIENTEXAM ROOM
210
MOCK PATIENTEXAM ROOM
209
CLOSET
223
CONTROLCORRIDOR
202A
F12REM F12R
F12R
F12R
F12R
F12R
F12R
F12R F12R
F12R
F12R
F12R
F12R
F12R
F12R
F12REM
F12R
F12R
F12R
F12R
F12R
F12R
b
a
b
b
b
b
b
b
b b
b
b
b
b
b
b a
a
a
a
a
a
F12
F12R
F12R F12R
F12R
F12EM
F12R
F12
F12R
F12R F12R
F12R
F12EMF12 F12
F12R
F12R F12R
F12R
F12 F12EM
F12R
F12R F12R
F12R
F12 F12EM
F12R
F12
F12R
F12R
F12
F12R F12R
F12EM
F12R
F12R
F12R
F12R
F12R
F12RF12R
F12R
F12EM
F12
F12
F12EM
F12
F12
F12EM
F12
F12
F12EM
F12
F12F12F12EMF12F12F12EMF12F12F12EMF12F12F12EMF12F12F12EMF12F12F12EMF12F12F12EMF12F12F12EMF12F12F12EM
F3B
F3B
F3B
F3B
F3A
F3A
F3A
F3A
F3A
F3A
F3A
F3A
F3A
F3A
F3A
F3A
F12R
F12R
F12R
F5EM
F5EM F5EM
F5EM F5EM
F5EM
F5EM
F5EM
F5EMF5EM
F5EM
F5EMF5EM
F5EM
F5EMF5
F5
F5
F17
F10
F10
F17
F3B
F3B
F18
F18 F18
F18
F18F18
F22
F22
F22
F22
F8
F8
F8
F8EM
F8 F8
F8EM
F8
F8BF8B
F8B
F8B
F8BEM
F8EM
F8EM
F3AF3A
F35
F8EM
F8EM
EM
EM
52 3 4 961
C
B
A
14
11
F
H
13
8
G
10
B.5
12
7
15
E
B.6
B.2
F19BEM
F19BEM
F12R
F12R
F12R
F12R
F12R
F12R
b
b
b
b
b
b
NP2A- 1
NP2A- 5NP2A- 5
NP2A- 7
NP2A- 7
NP2A- 7
NP2A- 7
NP2A- 7
NP2A- 9
NP2A- 10
NP2A- 7
NP2A- 7
NP2A- 5
F10
F8B
F8BEM
F8BF32D F32D
F8 F8EM
F8EMF8
F8B
F8BEM
F8B
F12R F12R F12R
F12RF12RF12R
F32D
F32D F32D
F32D
F35
F35 F35
F35 F35
F35 F35
F3A
F3AEM
F3A
F3A
F3AEM
F3B
F3B
F3B
F3B
F12R
F12R
F12R
F8B
F8B
F8BEM
F8B
F8BEM
NP2A- 5
NP2A- 5
NP2A- 5 NP2A- 5
NP1A- 23
NP1A- 23
NP1A- 23
NP1A- 23
NP1A- 23NP1A- 23 NP1A- 23
NP2A- 9
NP2A- 1
NP1A- 23
NP2A- 9
NP1A- 20
NP2A- 7
NP2A- 7
F19EM
F19EM
NP1A- 21
F39F39
F39
NP2A- 6
F24 F24
F12R
F38
F12R
F12R
F8D F8D3 3
a a
d,e
b
bc
NP1A- 23 NP1A- 23
b
bc
aa
F38 d,e
a3
a
3
aa
3
a
3
a
3
3ac
b
b b
bc
3
a3
c
b b
c
F12Rb
F38d,e
a a aa3
c
c
b
F8B
F8B
F3A
NOTES:1. ALL EXIT SIGNS ARE TYPE EX1, UNLESS
NOTED OTHERWISE.
F21
F39c
2
2
F12Rb
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
1/8" = 1'-0"
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-302
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
LEVEL 2 ELECTRICALPLAN - LIGHTING
24'8'0'
1/8" = 1'-0"2
LEVEL 2 ELECTRICAL PLAN - LIGHTING
2 04/22/16 ADDENDUM #2
T T
T
WP
J
STAIR 1
3S1
STAIR 2
3S2
IT
3E2
ELECTRICALROOM
3E1
MECHANICAL
3M1
ELEV.
3EL
F5EM F5EM F5EM
F5EMF5EMF5EMF5EM
F5EM
F5EM F5EM F5EM F5EM
F5EM F5EM
F5EMF5EMF5EM
F5EM
F8EM
F8EM
F30EM
F8BEM
F8BEM
52 3 4 961
C
B
A
14
11
F
H
13
8
G
10
B.5
12
7
15
E
B.6
B.2
F19BEM
F19BEM
F5EM F5EM F5EM F5EM F5EM F5EM F5
F5
F5 F5 F5 F5 F5EM
F5
F5EM
F5
F5EM
F5
F5
F5EM
NP1A- 20
NP1A- 21
NP3A- 1
NP3A- 1
NP3A- 1
NP3A- 1
NP1A- 22
F19EM
F19EM
NOTES:1. ALL EXIT SIGNS ARE TYPE EX1, UNLESS
NOTED OTHERWISE.
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
1/8" = 1'-0"
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-303
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
LEVEL 3 ELECTRICALPLAN - LIGHTING
24'8'0'
1/8" = 1'-0"2
LEVEL 3 ELECTRICAL PLAN - LIGHTING
3W
P
3WP
STAIR 2
4S2
F16
F16
F36
F36
F36 F36 F36 F36 F36 F36
F36
F36F36F36F36F36
F36
GENERAL NOTES:1. ALL NORMAL LIGHTING FIXTURE CIRCUITS FED FROM PANEL NP3A. REFER TO PANEL SCHEDULES FOR CIRCUITING.
EM
EM
52 3 4 961
C
B
A
14
11
F
H
13
8
G
10
B.5
12
7
15
E
B.6
B.2
F36
F36
F36
F36
NP1A- 20
NOTES:1. ALL EXIT SIGNS ARE TYPE EX1, UNLESS
NOTED OTHERWISE.
EX2
EX3
EX3
2
2
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
1/8" = 1'-0"
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-304
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
ROOF ELECTRICALPLAN - LIGHTING
24'8'0'
1/8" = 1'-0"1
ROOF ELECTRICAL PLAN - LIGHTING
2 04/22/16 ADDENDUM #2
400AMCB
PANELNDA3
150AMLO
PANELNA3B
150AMLO
PANELNA3C
150AMLO
PANELNA3D
NP2A
SPARE
SPARE
SPARE
NP3A
---
LOAD SERVEDCIRCUITNUMBER
kVADEMAND
kWDEMAND
kWCONN
NDA1 (VIA NX1)
NDA2 (VIA NX2)
NP1A
AHU-2
SPARE
SPARE
---
233210210
201819
---SPARE
---SPARE
kVADEMAND
kWDEMAND
kWCONN
LOAD SERVEDCIRCUITNUMBER
SURGE PROTECTIVE DEVICE
233210210
---SPARE SPARE
AHU-1
877
---
---
---
595381
373353
---
665971
---
T1
T6
T6
NO SCALE
POWER DISTRIBUTION SINGLE-LINE DIAGRAME1
E2
TOTAL CONNECTED kW: 651 TOTAL DEMAND kVA:TOTAL DEMAND kW: 590 656
'MDP' ELECTRICAL LOAD ESTIMATE SUMMARY
MAIN DISTRIBUTIONSWITCHBOARD "MDS"480Y/277V, 3PH, 4W, 1600A Cu BUS, 65kAIC SYM
MINIMUM. MAIN AND FEEDER CIRCUIT BREAKERS
SHALL BE EQUIPPED WITH FULLY-ADJUSTABLE (LSIG)
ELECTRONIC TRIP UNITS.
a
b
n
c
3 5 7
4 6 8
1
2
0
M
9 11
10 12
13
14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
0
PAD-MOUNTEDTRANSFORMER
225A
400A
225A
400A
225A
225A
400A
1200A
NEUTRAL BUS
MAIN DISTRIBUTIONSWITCHGEAR
TOGROUNDINGELECTRODE
SYSTEM
#3/0 Cu MBJ
#4/0 Cu GEC
GROUND BUS
MAIN XFMR
400A
225A
225A
350A
350A
225A
350A
LEVEL 1
LEVEL 3
ROOF
225A3P
225A3P
PM
MAIN DISTRIBUTION SWITCHGEARGROUNDING DIAGRAM
LEVEL 2
LEVEL 1
LEVEL 3
ROOF
LEVEL 2
1000kVA
12.47kV
480Y277V
12.47kV, 500kcmil FEEDERS "C" AND "D" TO MANHOLE AT LOT 4ENTRANCE VIA CONCRETE-ENCASED UNDERGROUND ELECTRICALDUCTBANK
350A3P
350A3P
225A3P
PANELNP1A
225AMCB
NOTES:1. FEEDER ROUTING SHOWN IS DIAGRAMMATIC AND NOT INDICATIVE OF ACTUAL REQUIRED FEEDER ROUTING.
2. EQUIPMENT AND DEVICES, INCLUDING SWITCHES AND CIRCUIT BREAKERS, ARE 3-POLE UNLESS OTHERWISE INDICATED.
TVSS
160kA PERMODE
NX2
K-13
NX1
K-13SPARE
PANELNP3A
400AMCB
400AMCB
PANELNDA1
150AMLO
PANELNA1A
150AMLO
PANELNA1B
150AMLO
PANELNA1C
150AMLO
PANELNA1D
400AMCB
PANELNDA2
150AMLO
PANELNA2A
150AMLO
PANELNA2B
150AMLO
PANELNA2C
150AMLO
PANELNA2D
4w225
5w150
5w1503w225
3w225
4w225
4w400
5w150
5w150
(4) 4-600kcmil RUN IN CONCRETEENCASED DUCTBANK
SPARE
SPARE
AHU-1 AHU-2
3w350
SPARE SPARE SPARE
150AMLO
PANELNA3A
PANELNP3B
400AMLO
PANELNP2A
225AMCB
3w225
EQUIPMENT PROVIDEDIN FUTURE FIT-OUT
PANEL NA3A TO BE REFED INFUTURE FIT-OUT
5w150
2
2
2
2
2
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
NTS
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-401
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
POWERDISTRIBUTIONSINGLE LINEDIAGRAM
2 04/22/16 ADDENDUM #2
NO SCALE
GROUNDING RISER DIAGRAME1
3BUILDING GROUNDING ELECTRODE SYSTEM DETAIL
SCALE: NONE
BUILDING SYSTEM GROUND BUS DETAIL4
NONESCALE:
GROUNDING RISER NOTES :
1. GROUND CONDUCTORS SHALL BE MINIMUM #4/0 COPPER UNLESS
INDICATED OTHERWISE. REFER TO GROUNDING AND BONDINGSPECIFICATIONS FOR ADDITIONAL GROUNDING REQUIREMENTS.
2. GROUND CONDUCTORS RUN INDOORS SHALL BE TYPE THHN-THWNWITH GREEN INSULATION IN MINIMUM 1-1/2 INCH CONDUIT UNLESS
OTHERWISE INDICATED. BOND GROUND CONDUCTOR TO EACH ENDOF CONDUIT USING CONDUIT GROUNDING BUSHINGS. GROUNDCONDUCTORS RUN IN ELECTRICAL ROOMS MAY BE RUN EXPOSED
PROVIDED CONDUCTOR IS PROPERLY SUPPORTED ONTHREE-FOOT INTERVALS.
3. INSTALL GROUNDING CONNECTIONS TO BUILDING STRUCTURE ANDWATER PIPES AT MAIN SPRINKLER PIPING LOCATIONS THAT AREVISIBLE AND ACCESSIBLE FOR INSPECTION, MAINTENANCE, AND
TESTING.
4. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACHMETALLIC SERVICE ENTRANCE CONDUIT. BOND TO GROUND BUSUSING CONDUCTOR THAT IS SIZED BASED ON NEC TABLE 250-66
USING THE SERVICE PHASE CONDUCTOR SIZE.
5. INSTALL AN INSULATED THROAT GROUNDING BUSHING ON EACH
METALLIC FEEDER CONDUIT. BOND TO GROUND BUS USINGCONDUCTOR THAT IS SIZED BASED ON NEC TABLE 250-122 USINGTHE FEEDER CIRCUIT OVERCURRENT DEVICE SIZE OR THE
SEPARATELY DERIVED SYSTEM OVERCURRENT DEVICE SIZE.
6. BOND HOT AND COLD WATER PIPING SYSTEMS.
7. OTHER SYSTEMS TO BE BONDED TO GROUNDING ELECTRODE
SYSTEM.
A) LIGHTNING PROTECTION.
B) INTERIOR METALLIC GAS PIPE.C) ANTENNAS.D) TELEPHONE SERVICE.
E) INTERIOR METAL WATER PIPE.F) OTHER METAL INTERIOR PIPING.G) MAIN SPRINKLER SYSTEM PIPING
8. ALL GROUNDED (NEUTRAL) AND EQUIPMENT GROUNDING
CONDUCTOR SIZES ARE SHOWN ON RISERS.
9. DRAWINGS REFLECT 2008 EDITION OF NATIONAL ELECTRIC CODE.
10. THIS DETAIL INDICATES GENERAL ARRANGEMENT OF GROUNDINGREQUIREMENTS ONLY. FOR COMPLETE DISTRIBUTION REFER TO
POWER RISER DIAGRAM.
CONNECTION TO MAIN PIPE WITHIN 5 FT OFENTRANCE. REFER TO PLUMBINGDRAWINGS FOR FURTHER INFORMATION.
TYPICALTELECOMMUNICATIONSGROUND BAR. REFERTO TELECOM PLANS
FOR QUANTITIES.
TO MAIN DISTRIBUTIONSWITCHBOARDGROUND BUS.
EXOTHERMICCONNECTION(TYPICAL)
MAIN ELECTRICAL ROOMLEVEL 1 ROOM
LEVEL 2 ELECTRICAL ROOM
LEVEL 3 ELECTRICAL ROOM
TEST WELLTYPICAL GROUNDING CONNECTIONFOR EQUIPMENT PAD
MGBGB
LIGHTNING PROTECTIONSYSTEM ROOF CONDUCTOR
LIGHTNINGPROTECTIONAIR TERMINAL(TYPICAL)
GB
GB
EXISTING CONCRETEFOUNDATION FOOTING(TYPICAL)
BOND CONNECTIONTO BUILDING STEEL.(TYPICAL)
GROUND ROD (TYPICAL)CONNECTION TO FOOTING FOUNDATION REBAR (ONE PEREVERY OTHER PERIMETER FOOTING/FOUNDATION)
EXOTHERMIC BONDCONNECTION TOSTRUCTURAL STEELCOLUMN (TYPICAL.)
COUNTERPOISE GROUNDINGCONDUCTOR
FILE: ED800201
REFER TO BUILDING GROUNDING ELECTRODE SYSTEM DETAIL FOR EXACT CONFIGURATION.
GROUNDING CONDUCTOR.
INSULATED COPPER
DETAIL FOR ADDITIONAL
SEE BUILDING GROUNDING
CONDUCTOR IN CONDUIT.
INSULATED GROUNDING
NOTES:
1.
INFORMATION.
CONDUCTOR.
GROUNDING
BARE COPPER
BUSHING (TYPICAL).
GROUNDING
FRONT ELEVATION
A
A
SIZED TO THE
BONDING CONDUCTOR
LARGEST GROUND
CONDUCTOR IN
GROUP (TYPICAL)
MOUNTED TO WALL WITH INSULATORS.
EXOTHERMIC WELD
CONNECTION, (TYPICAL).
SECTION "A-A"
2"1/4"
x 2" LONG. RED IN COLOR.
(i.e. G2, G8) COPPER GROUND BUS.
3/8" MOUNTING BOLT.
COPPER GROUND BUS.
INSULATOR. 1 3/4" DIA.
POLYESTER/FIBERGLASS
1/4" x 2" x LENGTH AS SCHEDULED
#4/0 AWG COPPER GROUND CONDUCTOR ENCASED IN CONCRETE.
INDICATES BOLTED CONNECTION.
3/4" x 10'-0" LONG COPPER-CLAD GROUND ROD.
INDICATES EXOTHERMIC WELD CONNECTION, COMPATIBLE WITH MATERIALS BEING JOINED.
3
4
1
2
LEGEND:
3
3
NEUTRAL BUS
MAIN BONDING
JUMPER
GROUND BUS
1
1
1
1
1
TO ADDITIONALTELECOMMUNICATIONSEQUIPMENT GROUNDBUSES AS REQUIRED
TELECOMMUNICATIONSEQUIPMENT GROUND BUS
MAIN ELECTRICALGROUND BUS IN MAINELECTRICAL ROOM,MINIMUM 1/4" x 4" x 48"
TWO-BOLT GROUNDINGCLAMP WITHIN 5 FEET OFENTRANCE POINT OF PIPE
WATER SERVICE ATSTREET SIDE OFWATER METER.UNDERGROUNDMETAL WATER PIPEGREATER THAN 10FEET LONG
CONNECTION TOCONCRETE ENCASEDELECTRODE
BUILDINGEXTERIORWALL.
4
1
5
5TYPICAL POWER SYSTEM GROUND BUS, MINIMUM 1/4" x 4" x 24". PROVIDE GROUND BUS AT EACHELECTRICAL ROOM AND TRANSFORMER LOCATION, AND OTHER LOCATIONS INDICATED ON PLANS.
#4/0 AWG INSULATED COPPER GROUND CONDUCTOR IN 1-1/4" CONDUIT. PROVIDE GROUNDING BUSHINGSAT EACH END OF CONDUIT AND BOND TO ASSOCIATED GROUND CONDUCTOR.
2
#4/0 AWG BARE COPPER GROUND CONDUCTOR, PROVIDE 1" PVC CONDUIT SLEEVE WHEN RUNNINGCONDUCTOR THROUGH EXTERIOR WALL OR FOOTINGS.
TYPICAL FOR MEDIUM-VOLTAGESWITCHGEAR ANDSWITCHBOARDS
LEVEL 1
ROOF
LEVEL 3
LEVEL 1
ROOF
LEVEL 3
LEVEL 2 LEVEL 2
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
NTS
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-501
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
GROUND RISERDIAGRAM
52 3 4 961
C
B
A
14
11
F
H
13
8
G
10
B.5
12
7
15
E
B.6
B.2
B.3
C.2
8.8
NO SCALE
LIGHTNING PROTECTION PLANE1
LIGHTNING PROTECTION AIR TERMINAL/BONDING CONNECTION
LIGHTNING PROTECTION LEGEND
LIGHTNING PROTECTION SYSTEM ROOF CONDUCTOR
ROOF DOWN CONDUCTOR CONNECTION TO BUILDING STEEL.REFER TO DETAILS 9 ON E-602.
UNDERGROUND GROUNDING CONDUCTOR/LOOP.
GROUND ROD
GROUND ROD CONNECTION AT TEST WELL.TW
TW
TW
GROUND ROD CONNECTION TOEBUILDING STEEL(TYPICAL). REFERTO DETAIL 10 ON E-602.
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
NTS
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-601
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
LIGHTNINGPROTECTION PLAN
SCALE:
SCALE:
SCALE:
SCALE:
83
NONE
SCALE:
SCALE:
VISE-GRIP TEE SPLICER DETAIL6
NONE
SCALE:
PARAPET MOUNTED VERTICAL AIR TERMINAL5
NONE
MULTI-PURPOSE AIR TERMINAL BASE DETAIL9
NONE
AIR TERMINAL - FLAT ROOF MOUNT DETAIL7
NONE
BASE MOUNTED HORIZONTALLY WITH ADHESIVE2
NONE
LIGHTNING PROTECTION NOTES1
NONESCALE:
TYPICAL LIGHTNING PROTECTION SYSTEM ROOF PENETRATION DETAIL9
NONE
SCALE:
TYPICAL LIGHTNING PROTECTION SYSTEM GROUNDING/FOOTING DETAIL10
NONE
LPS ROOF PENETRATIONASSEMBLY CONNECTION TO
LPS ROOFCONDUCTOR
ROOF
INTERIOR
EXTERIOR
EXOTHERMIC BONDCONNECTION TOSTRUCTURAL STEELCOLUMN
EXTERIOR WALL
STEEL COLUMN
SLAB
GRADE
EXOTHERMIC BONDCONNECTION TOSTRUCTURAL STEELCOLUMN
INTERIOR EXTERIOR
EXOTHERMIC BONDCONNECTION
FILE: ED940700
FILE: ED940200
AIR TERMINAL
CABLE
PRESSURE CABLE CONNECTOR
MULTI-PURPOSE BASE
CABLE
CABLE
AIR TERMINAL
ONLY.
BASE
BOND WITH ADHESIVE CEMENTCABLE CONNECTOR (BRONZE).BASE WITH PRESSURE TYPEFLAT SURFACE AIR TERMINAL
CABLE
STAINLESSSTEEL METAL
SCREWS
BONDING PLATE WITHPRESSURE TYPE CABLECONNECTION. PROVIDE FORALL METAL OBJECTS WITHIN6'-0" OF THE LIGHTNINGPROTECTION SYSTEM.
GROUND
#4/0 AWG COPPER
BUILDING STRUCTURALSTEEL COLUMN.
#4/0 AWG COPPER GROUNDINSTALLED IN CONDUITFROM STEEL COLUMN BASETO 1'-0" BELOW GRADE.
EXOTHERMIC CONNECTIONTO 3/4"x10'-0" LONGCOPPERCLAD GROUNDROD AT BUILDINGEXTERIOR
#4/0 AWGCOPPER TOGROUND LOOPCONDUCTOR
CABLE.
UNIVERSAL AIR TERMINAL
BASE WITH CABLE CLAMP.
LIGHTNING PROTECTION
CABLE FASTENER.
SAFETY TIP AIR
TERMINAL.SAFETY TIP AIR TERMINAL.
CABLE CLAMP
CABLE.
UNIVERSAL AIR TERMINAL
BASE WITH CABLE CLAMP.
LIGHTNING PROTECTION
THE ELECTRICAL SUB-CONTRACTOR SHALL PROVIDE A COMPLETE LIGHTNING PROTECTION SYSTEM ASPER THE SPECIFICATIONS. THE ELECTRICAL SUB-CONTRACTOR SHALL RETAIN THE SERVICES OF A FIRMACTIVELY ENGAGED IN THE INSTALLATION OF MASTER LABELED LIGHTNING PROTECTION SYSTEMS ANDSHALL BE SO LISTED BY UNDERWRITERS LABORATORIES, INC.
THE COMPLETED SYSTEM SHALL COMPLY WITH THE LATEST EDITIONS OF THE "INSTALLATIONREQUIREMENTS FOR LIGHTNING PROTECTION SYSTEMS, UL96A" AND THE "LIGHTNING PROTECTIONCODE, NFPA 780."
ALL MATERIALS USED IN THIS INSTALLATION SHALL BE LABELED OR LISTED BY UL FOR USE IN MASTERLABELED LIGHTNING PROTECTION SYSTEMS.
GENERALLY ALL MATERIALS SHALL BE OF COPPER AND/OR COPPER/BRONZE. REFER TOSPECIFICATION FOR REQUIREMENTS OF SYSTEM COMPONENTS MOUNTED ON ALUMINUMMATERIALS.
MATERIALS SHALL BE SIZED IN ACCORDANCE WITH NFPA 780 AND UL96A. CLASS I MATERIALS SHALL BEUSED FOR SYSTEMS ON STRUCTURES NOT EXCEEDING 75 FEET IN HEIGHT, AND CLASS II MATERIALSSHALL BE USED FOR SYSTEMS ON STRUCTURES EXCEEDING 75 FEET ABOVE GRADE.
AIR TERMINALS SHALL BE PROVIDED SO AS TO ENCLOSE THE ENTIRE BUILDING WITHIN A ZONE OFPROTECTION. REFER TO SPECIFICATION FOR ADDITIONAL INFORMATION.
MAIN CONDUCTORS SHALL BE SIZED IN ACCORDANCE WITH THE SPECIFICATION AND SHALLPROVIDE A TWO-WAY PATH FROM EACH AIR TERMINAL HORIZONTALLY OR DOWNWARD TOCONNECTIONS WITH GROUND TERMINALS.
DOWN LEAD CONDUCTORS SHALL BE COPPER AND SHALL BE CONCEALED IN THE EXTERIOR WALLCONSTRUCTION. REFER TO SPECIFICATION.
THE BUILDING'S STRUCTURAL STEEL FRAME CONSTRUCTION SHALL BE USED AS THE DOWNCONDUCTOR. ROOF CONDUCTORS SHALL BE CONNECTED TO THE STRUCTURAL STEEL FRAME ATINTERVALS AVERAGING NOT MORE THAN 100 FEET AROUND THE PERIMETER. CONNECTIONS TO THESTEEL STRUCTURE SHALL BE BY EXOTHERMIC WELD CONNECTIONS. REFER TO SPECIFICATION.
ROOF PENETRATIONS REQUIRED FOR DOWN CONDUCTORS OR FOR CONNECTIONS TO THESTRUCTURAL STEEL FRAME SHALL BE MADE USING THRU-ROOF ASSEMBLIES WITH SOLID BARS ANDAPPROPRIATE ROOF FLASHING. CONDUCTORS SHALL NOT PASS DIRECTLY THROUGH THE ROOF.
COMMON GROUNDING OF ALL GROUND MEDIUMS WITHIN THE BUILDING SHALL BE ENSURED BYINTERCONNECTING WITH MAIN SIZE CONDUCTORS AND FITTINGS.
GROUND TERMINATIONS SHALL BE PROVIDED FOR EACH DOWN CONDUCTOR. GROUND RODS SHALLBE LOCATED 2' BELOW GRADE AND EXTEND A MINIMUM OF 10' VERTICALLY IN THE EARTH. REFER TOSPECIFICATION.
UPON COMPLETION OF THE INSTALLATION THE ELECTRICAL SUB-CONTRACTOR SHALL FURNISH THEMASTER LABEL ISSUED BY UL FOR THIS SYSTEM.
REFER TO THE SPECIFICATION FOR ADDITIONAL REQUIREMENTS. THE EXACT LAYOUT OF THELIGHTNING PROTECTION SYSTEM SHALL NOT BE SHOWN ON THE DRAWINGS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
LIGHTNING PROTECTION NOTES
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
NTS
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-602
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
LIGHTNINGPROTECTIONDETAILS
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
SCALE:
6DROP CORD REEL RECEPTACLE DETAIL
SCALE: NONE
11SCALE: NOT TO SCALE
TYPICAL PRECAST CONCRETE ELECTRICAL MANHOLE DETAIL
J J J J
ON
OFF
ON
OFF
ON
OFF
PANEL
"L41A"
PANEL
"L41A"
PANEL
"L41A"
"L41A"
PANEL
PANEL
"L41A"
"L41A"
PANEL
"L41A"
PANEL
PANEL
"L41A"
"L41A"
"L41A"
PANEL
"L41A"
PANEL
"L41A"
PANEL
"L41A"
PANEL
"L41A"
PANEL
PANEL
"L41A"
480Y/277V, 3∅, 4W
FED FROM D41A
480Y/277V, 3∅, 4W
FED FROM D41A
"L41A" FED FROM D41A
480Y/277V, 3∅, 4W
"L41A"
FED FROM D41A
480Y/277V, 3∅, 4W
"L41A"
TYPICAL NAMEPLATE DETAIL5
NONE
TYPICAL PANEL NAMEPLATE LOCATIONS2
NONE
TYPICAL DEVICE MOUNTING HEIGHTS8
NONESCALE:
ROOF TOP MECHANICAL EQUIPMENT LIGHTING & RECEPTACLE DETAIL1
NONE
MOTOR DISCONNECTING MEANS MOUNTING DETAIL3
NONE
REQUIRED CLEARANCE FOR ELECTRICAL EQUIPMENT10
NONE
TYPICAL DETAIL FOR LABELING SYSTEM ON DEVICE PLATES7
N.T.S.SCALE:
TYPICAL LIGHTING FIXTURE DESIGNATION DETAIL
NONE4
TYPICAL ELEVATOR MACHINE ROOM LAYOUT6
NONESCALE:
10"
39"
50"
32"
2"1 1/
16" O.C.
BETWEEN7" MINIMUM
RACKS
7/8"
2-3/4"
8-1/2"
5"
9"
(TYPICAL)
ELECTRIC
FILE: ED900200
FILE: ED120100
BACK SPLASH
MECHANICAL
REQUIRED.PROVIDE METAL CHANNEL WHERE
WEATHERPROOF LIGHTING FIXTURE WITH
CIRCUITRY IN RIGID METAL CONDUIT
GUARD (HUBBELL #VWX-152-VCG-15)
ROOF
AND INSULATION
ROOF DECK
ROOF MEMBRANE
6'-6"
ROOF CURB
LB FITTING
REFER TO DRAWINGS FORBRANCH CIRCUIT HOMERUN
AND LIGHT SWITCH IN WEATHERPROOF BOX120 VOLT DUPLEX, GROUND FAULT RECEPTACLE
PITCH POCKET FURNISHEDBY ELECTRICAL CONTRACTORAND INSTALLED BY ROOFINGCONTRACTOR
EQUIPMENT
G
W
FLOOR MOUNTED TRANSFORMER
*
6"
FRONT
6"
*
WALL MOUNTED PANELS
(TYPICAL)
PACKED TO 90%1'-0" OF GRAVEL
3/4"x10'-0"COPPERCLADGROUND ROD
#4/0 BARE COPPER
AROUND PERIMETER OF
TO WALL AS REQUIRED
GROUND WIRE RUN
MANHOLE. ATTACH
MANHOLE COVER & FRAME
ARRANGEMENT OF CABLE RACKS
TYPICAL CABLE RACK
(LOCATED ON ALL WALLS)
KNOCKOUT (TYPICAL)
PLAN
#4/0 BARE COPPERGROUND WITHIN
#4/0 BARE COPPER
ATTACH TO SIDE
EXOTHERMIC CONNECTION(TYPICAL)
ELEVATIONSUMP12-1/2" DIA. x 4" DEEP
MANHOLEWALL OF
TYPE RACKSPORCELAIN SADDLE
PULLING IRONS
LETTERING "ELECTRIC-HV"
MANHOLE COVER AND FRAME 30"DIAMETER CLEAR OPENING WITH
FINISH GRADE
PRECAST RING
PULLING EYE
FLOOR LEVEL
DUCTBANK (TYPICAL)
DUCTBANK
KNOCKOUT(TYPICAL)
WALLS AS REQUIRED
GROUND WIRE
PRE-CAST8'x8'x7' HIGH
HANDHOLE
NOTES:1. ELECTRIC MANHOLE SHALL BE PROVIDED WITH FRAME AND COVER, PULLING
IRONS IN FLOOR AND SUMP PIT IN CENTER BOTTOM. PROVIDE CABLE RACKSON WALLS INDICATED AND #4/0 BARE COPPER GROUND FROM DUCTBANKS -
LOOPED AROUND ALL FOUR WALLS AND CONNECTED TO A 10'-0" X 3/4"COPPERCLAD GROUND ROD.
2. PULLING IRONS SHALL BE LOCATED OPPOSITE KNOCKOUT WINDOWS.
3. PROVIDE (1) ONE SPARE GRID KNOCKOUT PER FACE GENERALLY AS SHOWNON PLAN VIEW.
1. REFER TO ELEVATOR CONSULTANTS DRAWINGS FOR EXACT LOCATION OF ALL EQUIPMENT.
2. PROVIDE CONTACT, 3/4"C AND WIRE TO ELEVATOR AUTOMATIC TRANSFER SWITCH TO INITIATE ELEVATORSTANDBY MODE.
3. PROVIDE 1" EMPTY CONDUIT WITH PULL STRING TO TELEPHONE CLOSET.
4. PROVIDE 1" EMPTY CONDUIT WITH PULL STRING TO SECURITY RISER.
5. PROVIDE 3/4"C AND CONTROL WIRING FOR SHUNT TRIP OF ELEVATOR FEEDER BREAKER PER ELEVATOR
CODES.
6. ALL DISCONNECT SWITCHES WITHIN THE ELEVATOR MACHINE ROOM SHALL BE LOCKABLE IN THE "OFF"
POSITION AND SHALL HAVE TWO (2) "NO" AUXILIARY CONTACTS FOR ELEVATOR CONTRACTOR USE.
7. THE ELEVATOR DISCONNECT SWITCH FINAL FUSE SELECTION SHALL BE PROVIDED PER ELEVATORMANUFACTURERS SHOP DRAWINGS SUBMITTAL AND SPECIFICATIONS.
8. FEEDER BREAKER TO EACH ELEVATOR SHALL BE EQUIPPED WITH SHUNT TRIP OPERATOR.
9. REFER TO POWER RISER DIAGRAM FOR ADDITIONAL INFORMATION.
NOTES:
HEAVY DUTY CORD REELREFER TOARCHITECTURALDRAWINGS ANDSPECIFICATIONS.
SINGLE GANG OUTLET BOX WITH SIMPLEX NEMA 5-20R RECEPTACLEANCHORED TO UNISTRUT OR STRUCTURAL STEEL - FACE TO THESIDE OR UP - DO NOT INSTALL WITH RECEPTACLE FACING DOWN.
UNISTRUT ORSTRUCTURAL STEEL
FINISHED CEILING
PANEL NAME ANDCIRCUIT NUMBER.
AND PHASE.
VOLTAGE, POLES
1/4" LETTERS
1. REFER TO SPECIFICATIONS FOR ADDITIONAL NAMEPLATE REQUIREMENTS.
NAMEPLATE TO BE 1/16" THICK WHITE PLASTIC WITH BLACK CENTER LAMINATE. FACE SHALL BE WHITE,ENGRAVED LETTERS SHALL BE BLACK.
SECURE NAMEPLATE TO SURFACES WITH (2) FLAT HEAD BRASS SCREWS. ADHESIVE CEMENT SHALL NOTBE ALLOWED.
NAMEPLATE INFORMATION SHALL INCLUDE DEVICE NAME, SUPPLY VOLTAGE, AMPERAGE AND LOCATIONFED FROM.
NOTES:
4.
3.
2.
FED FROM D4NL1 (TYPICAL)
1 "2/1
3/4"
480Y/277V, 3Φ, 4W, 100A
LIGHTING PANEL
"L41A"
/ 24 "1
5"
SCREWS
DISTRIBUTION PANEL
TYPICAL NAMEPLATE
PANEL
DETAIL
DISCONNECT
BREAKER FEED NAMEPLATE SHALL INDICATE WHAT IT
IS SERVING AND SIZE OF CIRCUIT BREAKER.
TYPICAL NAMEPLATE DETAIL
DEVICE LOCATIONS AND MOUNTING HEIGHTS SHALL BE CHECKED AGAINST THE ARCHITECTURAL PLANS AND ELEVATIONS PRIOR TOROUGH-IN IN ORDER TO AVOID INTERFERENCE'S WITH CASEWORK, FURNITURE, WINDOWS, MIRRORS, EQUIPMENT, ETC.
REFER TO THE ARCHITECT'S ELEVATION DETAILS FOR EXACT MOUNTING HEIGHT AND LENGTH OF SURFACE RACEWAYS. RECEPTACLEMOUNTING HEIGHT ABOVE COUNTERS SHALL BE COORDINATED WITH CASEWORK HEIGHTS.
DEVICES SHALL BE CENTERED IN A COMMON VERTICAL PLANE. HEIGHT SHALL BE MEASURED FROM FINISHED FLOOR TO CENTERLINEOF DEVICE EXCEPT EXIT SIGNS, AND FIRE ALARM SIGNALS. COORDINATE LOCATION WITH MATERIALS SUCH AS MASONRY UNITS.
4.
3.
1.
NOTES:
2"
1'-6"
4'-6"
4'-0"
2"
8'-6"
COMMUNICATION OUTLETS
RECEPTACLES
WALL TELEPHONES
SWITCHES
6'-3/4"
PANEL BOARD
3'-8"
COUNTER. SEE NOTE 4
LOCATIONS OF OUTLETS AND EQUIPMENT AS INDICATED ON THE DRAWINGS ARE APPROXIMATE. THE EXACT CENTER OF ALL OUTLETSSHALL BE PLACED IN COOPERATION WITH THE GENERAL CONTRACTOR AND ARCHITECT. CONTRACTOR SHALL EXAMINE ALL INTERIORDETAILS OF THE CONSTRUCTION DRAWINGS FOR OUTLET LOCATIONS NOT CONFORMING TO THE DETAIL ABOVE. WHERE DETAILED TOSPECIFIC LOCATIONS, THE ARCHITECTURAL DRAWINGS SHALL TAKE PRECEDENCE. IF AN OUTLET IS INSTALLED IN SUCH A LOCATIONAS TO BE OUT OF PROPER RELATION TO WALLS OR DETAILS OF THE BUILDING, ITS LOCATION SHALL BE CORRECTED BY AND AT THEEXPENSE OF THE CONTRACTOR UNDER THE DIRECTION OF THE ARCHITECT OR ENGINEER.
2.
REQUIRED.
PROVIDE PENDANT WHERE
EXIT SIGN
FINISHED CEILING
FINISHED FLOOR
EXPANSION ANCHORS (TYPICAL).
LENGTH AS REQUIRED.
METAL STRUT FASTENED TO FLOOR,
TWO HOLE OPEN ANGLE BRACKET.
LENGTH AS REQUIRED. SEE NOTE #1.
ANGLED SUPPORT METAL STRUT,
TWO HOLE OPEN ANGLE BRACKET.
MOTOR START SWITCHES OR JUNCTION BOX. REFER TO FLOOR PLANS.
THE TERM "DISCONNECTING MEANS" FOR THIS DETAIL MAY REFER TO DISCONNECT SWITCHES,
USE OF ANGLED SUPPORT SHOWN IN SIDE ELEVATION IS REQUIRED FOR DISCONNECTING MEANS
MAXIMUM LENGTH 36".
FLEXIBLE LIQUID-TIGHT CONDUIT,
FOR FOUR (4).
EXPANSION ANCHORS, TYPICAL
WITH FOUR (4) BOLTS IN FLOOR.
METAL STRUT POST BASE, 6" SQUARE
REQUIRED. SEE NOTE #1.
METAL STRUT SUPPORT HEIGHT AS
SEE FLOOR PLANS (TYPICAL).
MOTOR DISCONNECTING MEANS.
IS NOT ACCEPTABLE.
ADDITIONAL REQUIREMENTS. EMT
FEEDER. SEE SPECIFICATION FOR
RIGID STEEL CONDUIT FOR MOTOR
2.
RATED 100A AND LARGER.
30°
SIDE ELEVATION
FRONT ELEVATION
1.
NOTES:
60°
PAD BY OTHERS.
HOUSEKEEPING
EQUIPMENT AND
MOTOR TERMINAL BOX.
SEE NOTE #4.
NOTES:
INTERCOM SYSTEM CAR LIGHT AND FAN
120V-1Φ30A-1P
CONTROL
ELEVATOR
120V-1Φ 120V-1Φ
SEE NOTE #3.
SEE NOTE #5.SEE NOTE #2.
TERMINATIONS WITH
COORDINATE FINAL
ELEVATOR MANUFACTURER
120V-1Φ
SEE NOTE #9.
SEE NOTES #7 & 8.
SEE NOTES#9 & 10.
CONTROL ANDSIGNAL SYSTEMS.
6" MIN. REAR CLEARANCE
- 3 1/2 FT. FOR 150-600 VOLT TO GROUND (CONDITION 2 "LIVE TO GROUND")
THE MINIMUM HEADROOM OF WORKING SPACE SHALL BE 6 1/2 FT.
- 4 FT. FOR 150-600 VOLT TO GROUND (CONDITION 3 "LIVE EQUIPMENT TO LIVE EQUIPMENT")
- 3 FT. FOR 0-150 VOLT TO GROUND ELECTRIC EQUIPMENT
" " DENOTES MINIMUM WORKING CLEARANCE (IN THE DIRECTION OF ACCESS TO LIVE PARTS)
REQUIRED BY N.E.C. 110-26(a).
2.
1.
FOR ADEQUATE VENTILATION
(INCLUDING POWER PANELS, CONTACTORS, CONTROL
TIME CLOCK AND SIMILAR ELECTRIC EQUIPMENT)
CABINETS, DISCONNECT SWITCHES, MOTOR STARTERS,
WALL OR NON-COMBUSTIBLE MATERIAL
30" MIN.
WALL OR NON-COMBUSTIBLE MATERIAL
FRONT
*
WALL
NOTE: REFER TO SPECIFICATIONS FOR LABEL MATERIAL REQUIREMENTS.
FIXTURE DESIGNATION A
b
3 or R3
SWITCH CONTROL
CIRCUIT NUMBER. "R"INDICATES RELAY.
TYPICAL 120V
RECEPTACLE
208V 2P 1Φ
TYPICAL 208V
RECEPTACLE
P23E-3 P23W-5,7
TYPICAL 120V
OPTIONAL STANDBY
S12B1-14
RECEPTACLE
STANDBY
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
NTS
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-701
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
ELECTRICALDETAILS
SCALE:
TYPICAL LIGHTING FIXTURE CONNECTION DETAIL3
NONE
TYPICAL OCCUPANCY SENSOR AND PHOTOCELL CONTROL NOTES2
NONESCALE:
TYPICAL OCCUPANCY SENSOR CONTROL DETAIL1
NONESCALE:
SCALE:4
NONE
TYPICAL EXTERIOR LIGHTING PHOTOCELL CONTROLLED DETAIL
Neutral
Blk/Brn
Wht
Load
Power
Pack
Control Output
Common
+24VDC
Cap
Orn
Blk
Brn
Blu
Hot Red
Red
Gry
Cap
Any3-Wire24VDCOccupancySensor
ALL GENERALLIGHTING WITHINROOM ORLIGHTINGCONTROL ZONE.
TYPICAL LOCALOVERRIDESWITCH/DIMMER.QUANTITY AND TYPE ASINDICATED ON DRAWINGS.
PC
CONTRACTOR SHALL FIELD ADJUST SENSITIVITY ON ALL SENSORS PER THE MANUFACTURER'SCALIBRATION PROCEDURE TO PREVENT SENSING OCCUPANTS THROUGH DOORS IN THE ADJACENTSPACES.
GENERAL LOCATION OF OCCUPANCY AND PHOTOCELL SENSORS ARE SHOWN ON FLOOR PLANS.CONTRACTOR SHALL ADJUST LOCATIONS AS REQUIRED TO ADEQUATELY COVER THE SPACE ANDMINIMIZE SENSING THROUGH DOOR OPENINGS INTO ADJACENT SPACES.
CONTRACTOR SHALL INSTALL AND WIRE ALL OCCUPANCY AND PHOTOCELL SENSORS PERMANUFACTURERS INSTALLATION AND WIRING INSTRUCTIONS.
CONTRACTOR SHALL PROVIDE ALL POWER AND SLAVE PACKS REQUIRED TO CONTROL LIGHTINGFIXTURES PER THE DESIGNATED SWITCH LEGS ON FLOOR PLANS.
OCCUPANCY AND PHOTOCELL SENSOR CONTROL NOTES:
4.
3.
2.
1.
N
C
C
C
EMERGENCY LIGHTINGSHUNT RELAY
EMERGENCYPOWERBRANCHCIRCUITSUPPLY
N
EXTERIOREMERGENCY POWER
FIXTURES
NORMALPOWERBRANCHCIRCUITSUPPLY N
EXTERIORNORMAL POWER
FIXTURES
NORMALPOWERBRANCHCIRCUITSUPPLY
ELECTRICALLY-HELDLIGHTING CONTACTOR.PROVIDE NUMBER OF POLESAS REQUIRED FOR QUANTITYOF ASSOCIATED SWITCHEDCIRCUITS PLUS 20% SPARE.
ELECTRICALLY-HELDLIGHTING CONTACTOR.PROVIDE NUMBER OF POLESAS REQUIRED FOR QUANTITYOF ASSOCIATED SWITCHEDCIRCUITS PLUS 20% SPARE.
RECESSED FIXTURE
(TYPICAL).
FIXTURES SHALL BE RATED FOR THRU WIRING.
NOTE:
MAXIMUM LENGTH 6'-0"
METAL CLAD FLEXIBLE
GROUND FIXTURE WHIP.CONDUIT WITH FULL INSULATED
(TYPICAL).
(TYPICAL).
SUSPENDEDCEILING.
STRUCTURAL CEILING.
JUNCTION BOX (TYPICAL).REFER TO SPECIFICATIONS.
FIXTURE SUPPORT.
CONDUIT-EMT
PHOTOCELL TORK SERIES 2100277V WITH 1/2" CONDUITMOUNTING POINT TOWARD NORTHREFER TO DRAWING E-304 FORLOCATION.
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
NTS
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-702
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
ELECTRICALDETAILS
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-801
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
ELECTRICAL PANELSCHEDULES
NA1D
NA1C
NA1B NP1A
NDA1
NA1A
NOTES:
1. PANEL SCHEDULES ARE BEING ISSUED WITH CONSTRUCTION DOCUMENTS FORUSE BY THE CONTRACTOR DURING CONSTRUCTION. AFTER ISSUANCE WITHCONSTRUCTION DOCUMENTS, THE CONTRACTOR SHALL BE RESPONSIBLE FORMAINTAINING UPDATED PANEL SCHEDULES THAT REFLECT INSTALLED CONDITIONS,INCLUDING CHANGES MADE TO THE DESIGN DURING THE CONSTRUCTION PHASE.THE ENGINEER WILL NOT ISSUE REVISED PANEL SCHEDULES DURING THECONSTRUCTION PROCESS UNLESS DEEMED NECESSARY BY THE ENGINEER.
2. PROVIDE 20A/1P BREAKERS IN ALL BLANK POLE SLOTS IN BRANCH CIRCUIT PANELS.
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
L 13.07 13.07 M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 18.37
R 0.5 0.5 L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 19.57
M 6 4.8 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 5.14 7.96 6.46
41 0 0 42
39 0 0 40
37
-- SPARE -- -- 20 3
0 0
3 20 -- -- SPARE --
38
35 36
33 34
31 32
29 1.67 30
27 1.67 0.17 28
25
M BP-1 (5HP) 3W20 20 3
1.67 0.17 26
23 L LTG WEST 2W20 20 1 1.23 0.17
3 20 3W20 SP-1 (0.5HP) ELEVATOR M
24
21 L LTG STAIR 1 2W20 20 1 1.05 0.13 1 20 2W20 LTG ELEV 1 L 22
19 L LTG VESTIBULE 1V1 2W20 20 1 0.05 0.46 1 20 2W20 LTG STAIR 2 L 20
17 L LTG SUSTAINABILITY 101 2W20 20 1 1.18 1.15 1 20 2W20 SITE LIGHTING L 18
15 L LTG SUSTAINABILITY 101 2W20 20 1 1.21 1.68 1 20 2W20 LTG SUSTAINABILITY 101 L 16
13 L LTG EXTERIOR; VESTIBU... 2W20 20 1 0.06 0.91 1 20 2W20 LTG CORR. 1C3 / 1L1 L 14
11 L LTG TOILETS 1T3/1T4 2W20 20 1 0.41 0.33 1 20 2W20 LTG CORR. 1C2 L 12
9 L LTG CLASSROOM 105 2W20 20 1 0.83 0.9 1 20 2W20 LTG CLASSROOM 104 L 10
7 L LTG EXTERIOR ENTRY 2W20 20 1 0.54 0.95 1 20 2W20 LTG CLASSROOM 106 L 8
5 0.17 0.17 6
3 0.17 0.17 4
1
RUNIT HEATERSSUSTAINABILITY
3W20 20 3
0.17 0.17
3 20 3W20UNIT HEATERSSUSTAINABILITY
M
2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL 1E2 SUB-FEED LUGS: NEUTRAL:
ST MAIN: IG GND:SUPPLY FROM: MOUNTING: Surface A.I.C. RATING: 65 kAIC
MAIN: 225A MCB DISTRIBUTION: 480Y/277V, 3PH, 4W
PANEL: NP1A BUS AMPS: 225
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
LH = LOCKING HASP
ST = SHUNT TRIP
A = ARC FAULT
G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 33.57
G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 53.67
BLANK = STANDARD
BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 16.59 18.72 18.37
41 0 0 42
39 0 0 40
37
SPD (160kA) -- -- 60 3
0 0
3 150 -- -- SPARE
38
35 0 0 36
33 0 0 34
31
SPARE -- -- 150 3
0 0
3 150 -- -- SPARE
32
29 0 0 -- -- -- -- SPACE 30
27 0 0 -- -- -- -- SPACE 28
25
SPARE -- -- 150 3
0 0 -- -- -- -- SPACE 26
23 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 24
21 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 22
19 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 20
17 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 18
15 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 16
13 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 14
11 7.04 1.85 12
9 7.4 1.92 10
7
NA1C SLD 150 3
7.14 3.03
3 150 SLD NA1D
8
5 6.88 2.6 6
3 5.58 3.82 4
1
NA1A SLD 150 3
3.64 2.78
3 150 SLD NA1B
2
CKT DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION CKT
FEED-THRU LUGS:LOCATION: ELECTRICAL 1E2 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NX1 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: 400A MCB DISTRIBUTION: 208Y/120V, 3PH, 4W
DIST. PANEL: NDA1 BUS AMPS: 400
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 13.7
R 13.94 11.97 L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 16.1
M 2.16 1.73 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 3.64 5.58 6.88
41 42
39 40
37 38
35 36
33 34
31 32
29 -- FIRE SMOKE DAMPERS -- -- 20 1 0 1.08 1 20 2W20 CONDENSATE PUMPS M 30
27 -- FIRE SMOKE DAMPERS -- -- 20 1 0 1.08 1 20 2W20 CONDENSATE PUMP M 28
25 R REC STORAGE 101D 2W20 20 1 0.18 0.18 1 20 2W20 VIDEO DEVICE 102 R 26
23 R FLOORBOXES 104 2W20 20 1 0.72 0.72 1 20 2W20 FLOORBOXES 104 R 24
21 R REC CLASSROOM 104 2W20 20 1 0.72 0.18 1 20 2W20 FLOORBOX 104 R 22
19 R REC CLASSROOM 104 2W20 20 1 0.72 1.08 1 20 2W20 REC CLASSROOM 104 R 20
17 R PROJ. SCREEN 104 2W20 20 1 0.4 1.08 1 20 2W20 REC CLASSROOM 104 R 18
15 R FLOORBOX 102 2W20 20 1 0.36 0.18 1 20 2W20 PROJECTOR 104 R 16
13 R VIDEO DEVICE 102 2W20 20 1 0.18 0.36 1 20 2W20 REC CLASSROOM 105 R 14
11 R REC CLASSROOM 105 2W20 20 1 0.36 0.18 1 20 2W20 VIDEO DEVICE 102 R 12
9 R FLOORBOX 102 2W20 20 1 0.72 0.36 1 20 2W20 AV CABINET CLASSRM 104 R 10
7 R FLOORBOX 106 2W20 20 1 0.18 0.18 1 20 2W20 REV ELEVATOR R 8
5 R REC CLASSROOM 105 2W20 20 1 1.08 1.26 1 20 2W20 REC CLASSROOM 105 R 6
3 R FLOORBOX 102 2W20 20 1 0.72 1.26 1 20 2W20 REC CLASSROOM 105 R 4
1 R PROJECTOR 106 2W20 20 1 0.18 0.4 1 20 2W20 PROJ. SCREEN 106 R 2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL 1E2 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NDA1 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: MLO DISTRIBUTION: 208Y/120V, 3PH, 4W
PANEL: NA1A BUS AMPS: 150
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 9.2
L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 9.2
R 9.2 9.2 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 2.78 3.82 2.6
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 R HAND DRYER 1T1 2W20 20 1 0.18 0.18 1 20 2W20 HAND DRYER 1T1 R 24
21 R HAND DRYER 1T3 2W20 20 1 0.18 0.18 1 20 2W20 HAND DRYER 1T3 R 22
19 R VAV LOBBY 2W20 20 1 0.4 0.4 1 20 2W20 VAV VENDING R 20
17 R VAV CORRDIOR 2W20 20 1 0.4 0.4 1 20 2W20 VAV CORRIDOR R 18
15 R REC LACTATION 1T5 2W20 20 1 0.72 0.4 1 20 2W20 VAV CORRIDOR R 16
13 R RECS CORR. 1C2, 1T6 2W20 20 1 0.54 0.36 1 20 2W20 REC STOR. 101B/C R 14
11 R VENDING 1T7 2W20 20 1 0.36 0.36 1 20 2W20 VENDING 1T7 R 12
9 R REC MECH. 1M1 2W20 20 1 0.54 0.72 1 20 2W20 REC TOILET 1T3, 1T4 R 10
7 R VIDEO DEVICE 1L1 2W20 20 1 0.18 0.54 1 20 2W20 REC LOBBY 1L1 R 8
5 R FLOOR BOX 1L1 2W20 20 1 0.54 0.18 1 20 2W20 VIDEO DEVICE 1L1 R 6
3 R FLOOR BOX 1C3 2W20 20 1 0.54 0.54 1 20 2W20 FLOOR BOX 1C3 R 4
1 R VIDEO DEVICE 1C3 2W20 20 1 0.18 0.18 1 20 2W20 VIDEO DEVICE 1C3 R 2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL 1E2 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NDA1 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: MLO DISTRIBUTION: 208Y/120V, 3PH, 4W
PANEL: NA1B BUS AMPS: 150
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 15.79
L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 21.58
R 21.58 15.79 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 7.14 7.4 7.04
41 0 0 42
39 0 0 40
37
-- SPARE -- -- 60 3
0 0
3 60 -- -- SPARE --
38
35 0 36
33 0 34
31
-- SPARE -- -- 60 3
0 32
29 R REC SUSTAINABILITY 101 2W20 20 1 0.54 0.3 1 20 2W20 TRAP PRIMERS R 30
27 R EWC CORRIDOR 1C2 2W20 20 1 0.18 0.72 1 20 2W20 REC OFFICE 101A,101C R 28
25 R REC WORKRM 102A 2W20 20 1 0.36 0.36 1 20 2W20 REC TOILET 1T1, 1T2 R 26
23 R REC WORKRM 102A 2W20 20 1 0.36 0.5 1 20 2W20 FRIDGE WORKRM 102A R 24
21 R VAV SUSTAINABILITY 2W20 20 1 0.4 0.4 1 20 2W20 VAV SUSTAINABILITY R 22
19 R FLOOR BOX SUST. 101 2W20 20 1 0.72 0.54 1 20 2W20 REC SUSTAINABILITY 101 R 20
17 R REC SUSTAINABILITY 101 2W20 20 1 0.18 1 18
15 R REC SUSTAINABILITY 101 2W20 20 1 1.08 1 16
13 1 1
3 60 3W60 SUSTAINABILITY 101 R
14
11 1 1 12
9
R SUSTAINABILITY 101 3W60 60 3
1 1 10
7 R REC SUSTAINABILITY 101 2W20 20 1 0.72 1
3 60 3W60 SUSTAINABILITY 101 R
8
5 R REC SUSTAINABILITY 101 2W20 20 1 1.08 1.08 1 20 2W20 REC SUSTAINABILITY 101 R 6
3 R REC OFFICE 101A/101C 2W20 20 1 1.08 0.54 1 20 2W20 REC SUSTAINABILITY 101 R 4
1 R CORD REEL 101 2W20 20 1 0.72 0.72 1 20 2W20 CORD REEL 101 R 2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL 1E2 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NDA1 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: MLO DISTRIBUTION: 208Y/120V, 3PH, 4W
PANEL: NA1C BUS AMPS: 150
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
C 1 1.25 M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 6.82
R 4.68 4.68 L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 6.79
M 1.11 0.89 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 3.03 1.92 1.85
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 0.11 20
17 R REC IT 1E1 2W20 20 1 0.36 0.112 20 2W20 AC-1, AC-2 M
18
15 R SECURITY PANEL 1E1 2W20 20 1 0.18 0.36 1 20 2W20 REC IT 1E1 R 16
13 R FA AMP. CABINET 1E1 2W20 20 1 0.18 1 1 20 2W20 FA CONTROL PANEL 1E1 C 14
11 R REC IT 1E1 2W20 20 1 0.36 0.18 1 20 2W20 DOOR LOCK CONN. 1E1 R 12
9 R POE SWITCH 1E1 2W20 20 1 0.18 0.3 1 20 2W20 CUH-1 M 10
7 R FA POWER SUPPLY 1E1 2W20 20 1 0.18 0.3 1 20 2W20 CUH-2 M 8
5 R REC ELECTRICAL 1E3 2W20 20 1 0.54 0.3 1 20 2W20 CUH-2 M 6
3 R REC IT 1E1 2W20 20 1 0.54 0.36 1 20 2W20 REC ELEC. 1E2 R 4
1 R RECS BLDG. EXTERIOR 2W20 20 1 0.72 0.54 1 20 2W20 RECS BLDG. EXTERIOR R 2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL 1E2 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NDA1 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: MLO DISTRIBUTION: 208Y/120V, 3PH, 4W
PANEL: NA1D BUS AMPS: 150
2
22
2
2
2 04/22/16 ADDENDUM #2
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-802
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
ELECTRICAL PANELSCHEDULES
NA2D
NA2C
NA2B NP2A
NDA2
NA2A
NOTES:
1. PANEL SCHEDULES ARE BEING ISSUED WITH CONSTRUCTION DOCUMENTS FORUSE BY THE CONTRACTOR DURING CONSTRUCTION. AFTER ISSUANCE WITHCONSTRUCTION DOCUMENTS, THE CONTRACTOR SHALL BE RESPONSIBLE FORMAINTAINING UPDATED PANEL SCHEDULES THAT REFLECT INSTALLED CONDITIONS,INCLUDING CHANGES MADE TO THE DESIGN DURING THE CONSTRUCTION PHASE.THE ENGINEER WILL NOT ISSUE REVISED PANEL SCHEDULES DURING THECONSTRUCTION PROCESS UNLESS DEEMED NECESSARY BY THE ENGINEER.
2. PROVIDE 20A/1P BREAKERS IN ALL BLANK POLE SLOTS IN BRANCH CIRCUIT PANELS.
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 7.48
Lighting 0 0 L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 7.48
L 7.48 7.48 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 2.41 2.7 2.35
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 L LTG CORR. 2C2 2W20 20 1 1.55 1.15 1 20 2W20 LTG CORR. 2C1 L 10
7 L LTG EAST 2W20 20 1 1.27 8
5 L;... LTG TOILETS 2T1/2T2 2w20 20 1 1.67 0.68 1 20 2W20 LTG DEAN'S SUITE L 6
3 4
1 L LTG CLASSROOM 201 2W20 20 1 1.14 2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL ROOM 2E1 SUB-FEED LUGS: NEUTRAL:
ST MAIN: IG GND:SUPPLY FROM: MOUNTING: Surface A.I.C. RATING: 65 kAIC
MAIN: 225A MCB DISTRIBUTION: 480Y/277V, 3PH, 4W
PANEL: NP2A BUS AMPS: 225
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
LH = LOCKING HASP
ST = SHUNT TRIP
A = ARC FAULT
G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 53.62
G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 83.22
BLANK = STANDARD
BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 28.58 28.28 26.37
41 0 0 42
39 0 0 40
37
SPD (160kA) -- -- 60 3
0 0
3 150 -- -- SPARE
38
35 0 0 36
33 0 0 34
31
SPARE -- -- 150 3
0 0
3 150 -- -- SPARE
32
29 0 0 -- -- -- -- SPACE 30
27 0 0 -- -- -- -- SPACE 28
25
SPARE -- -- 150 3
0 0 -- -- -- -- SPACE 26
23 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 24
21 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 22
19 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 20
17 10.53 0 -- -- -- -- SPACE 18
15 9.51 0 -- -- -- -- SPACE 16
13
NA3A SLD 150 3
10 0 -- -- -- -- SPACE 14
11 4.96 2.38 12
9 5.6 3.02 10
7
NA2C SLD 150 3
6.58 3.78
3 150 SLD NA2D
8
5 4.51 4 6
3 3.61 6.54 4
1
NA2A SLD 150 3
2.38 5.84
3 150 SLD NA2B
2
CKT DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION CKT
FEED-THRU LUGS:LOCATION: ELECTRICAL ROOM 2E1 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NX2 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: 400A MCB DISTRIBUTION: 208Y/120V, 3PH, 4W
DIST. PANEL: NDA2 BUS AMPS: 400
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 10.31
R 10.28 10.14 L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 10.49
M 0.21 0.17 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 2.38 3.61 4.51
41 42
39 40
37 38
35 36
33 34
31 32
29 -- FIRE SMOKE DAMPERS -- -- 20 1 0 30
27 -- FIRE SMOKE DAMPERS -- -- 20 1 0 28
25 26
23 R VAV CLASSROOM 2W20 20 1 0.4 0.4 1 20 2W20 VAV CLASSROOM R 24
21 0.4 1 20 2W20 VAV CLASSROOM R 22
19 0.36 1 20 2W20 REC OFFICE 206 R 20
17 0.11 0.9 1 20 2W20 REC CLASSROOM R 18
15M AC-3, AC-4 2W20 20 2
0.11 0.4 1 20 2W20 PROJ. SCREEN 221 R 16
13 R REC CONF RM 205 2W20 20 1 0.54 0.18 1 20 2W20 FLOOR BOX 205 R 14
11 0.9 1 20 2W20 REC CONF RM 205 R 12
9 R VIDEO DEVICE CONF RM... 2W20 20 1 0.18 0.36 1 20 2W20 REC MAIL RM 222 R 10
7 R FLOOR BOX 201 2W20 20 1 0.18 0.54 1 20 2W20 REC OFFICE 206 R 8
5 R REC CLASSROOM 201 2W20 20 1 1.08 0.72 1 20 2W20 REC CLASSROOM 201 R 6
3 R REC CLASSROOM 201 2W20 20 1 1.08 1.08 1 20 2W20 REC CLASSROOM 201 R 4
1 R PROJECTOR 201 2W20 20 1 0.18 0.4 1 20 2W20 PROJ. SCREEN 201 R 2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL ROOM 2E1 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NDA2 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: MLO DISTRIBUTION: 208Y/120V, 3PH, 4W
PANEL: NA2A BUS AMPS: 150
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 13.41
R 15.66 12.83 L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 16.38
M 0.72 0.58 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 5.84 6.54 4
41 42
39 40
37 38
35 36
33 34
31 R REC SIM ROOM 203,204 2W20 20 1 0.36 32
29 R REC EXAM ROOM 208-210 2W20 20 1 0.54 30
27 M CONDENSATE PUMPS 2W20 20 1 0.72 0.2 1 20 2W20 TRAP PRIMERS R 28
25 R REC SIMULATION SUITE... 2W20 20 1 0.9 0.54 1 20 2W20 REC CORRIDOR 2C1 R 26
23 R REC SIMULATION ROOM... 2W20 20 1 0.36 0.18 1 20 2W20 BAS HEAD END MECH 2M1 R 24
21 R VAV CLASSROOM 2W20 20 1 0.4 0.54 1 20 2W20 REC SIMULATION ROOM... R 22
19 R VAV MECHANICAL 2W20 20 1 0.4 0.4 1 20 2W20 VAV CORRIDOR R 20
17 R REC CORR. 2ND FL. 2W20 20 1 0.18 0.4 1 20 2W20 VAV CORRIDOR R 18
15 R REC CORRIDOR 2C1 2W20 20 1 1.08 0.36 1 20 2W20 REC SIMULATION ROOM... R 16
13 R FLOOR BOX 2ND FL. 2W20 20 1 0.72 0.18 1 20 2W20 VIDEO DEVICE 2ND FL. R 14
11 R REC MECH. 2M1 2W20 20 1 0.54 0.72 1 20 2W20 REC LOBBY; 201H R 12
9 R REC CORR. 2C2 2W20 20 1 1.08 1.08 1 20 2W20 RECS 2C2; 212 R 10
7 R REC SIMULATION ROOM... 2W20 20 1 0.54 0.18 1 20 2W20 VIDEO DEVICE 2C2 R 8
5 R REC PATIENT ROOM 208 2W20 20 1 0.54 0.54 1 20 2W20 REC PATIENT ROOM 208 R 6
3 R REC EXAM ROOM 210 2W20 20 1 0.54 0.54 1 20 2W20 REC EXAM ROOM 209 R 4
1 R REC SIMUL SUITE 202 2W20 20 1 1.08 0.54 1 20 2W20 REC CORRIDOR 2C1 R 2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL ROOM 2E1 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NDA2 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: MLO DISTRIBUTION: 208Y/120V, 3PH, 4W
PANEL: NA2B BUS AMPS: 150
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 13.57
L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 17.14
R 17.14 13.57 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 6.58 5.6 4.96
41 42
39 40
37 38
35 36
33 R REC 218 2W20 20 1 0.72 34
31 R REC WORK RM 221 2W20 20 1 0.54 1 1 20 2W20 EFTR-1 R 32
29 R REC DEAN'S SUITE 215 2W20 20 1 0.36 0.18 1 20 2W20 MICRO WORK RM 221 R 30
27 R FURNITURE FEED 215 2W20 20 1 1 0.36 1 20 2W20 REC DEAN'S SUITE 215 R 28
25 R FURNITURE FEED 215 2W20 20 1 1 0.36 1 20 2W20 REC DEAN'S SUITE 215 R 26
23 R FURNITURE FEED 215 2W20 20 1 1 0.36 1 20 2W20 REC DEAN'S SUITE 215 R 24
21 R FURNITURE FEED 215 2W20 20 1 1 0.72 1 20 2W20 REC DEAN'S SUITE 215 R 22
19 R VAV OFFICES 2W20 20 1 0.4 0.4 1 20 2W20 VAV OFFICES R 20
17 R REC DEANS SUITE 215 2W20 20 1 0.36 0.4 1 20 2W20 VAV SEMINAR RM R 18
15 R REC SEMINAR 201B 2W20 20 1 0.72 0.18 1 20 2W20 VIDEO DEVICE 201B R 16
13 R FLOOR BOX 201B 2W20 20 1 0.18 0.36 1 20 2W20 AV CABINET 201B R 14
11 R REC OFFICE 217 2W20 20 1 0.36 0.5 1 20 2W20 FRIDGE WORK RM 221 R 12
9 R VIDEO DEVICE 216 2W20 20 1 0.18 0.18 1 20 2W20 VIDEO DEVICE 217 R 10
7 R REC WORK RM 221 2W20 20 1 0.36 0.36 1 20 2W20 REC WORK RM 221 R 8
5 R REC 219 2W20 20 1 0.72 0.72 1 20 2W20 REC 218, 219 R 6
3 R REC 207. 208 2W20 20 1 0.36 0.18 1 20 2W20 FLOOR BOX 216 R 4
1 R REC OFFICE 217 2W20 20 1 0.72 0.9 1 20 2W20 REC CONF RM 216 R 2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL ROOM 2E1 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NDA2 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: MLO DISTRIBUTION: 208Y/120V, 3PH, 4W
PANEL: NA2C BUS AMPS: 150
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 9.18
L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 9.18
R 9.18 9.18 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 3.78 3.02 2.38
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 R REC CORRIDOR 202A 2W20 20 1 0.72 0.5 1 20 2W20 FRIDGE STOR 211 R 22
19 R REC STOR 211 2W20 20 1 0.54 0.72 1 20 2W20 REC CORRIDOR 202A R 20
17 R REC CONF RM 207 2W20 20 1 1.26 0.18 1 20 2W20 VIDEO DEVICE 207 R 18
15 R REC IT 2E2 2W20 20 1 0.36 0.36 1 20 2W20 REC IT 2E2 R 16
13 R FA POWER SUPPLY 2E2 2W20 20 1 0.18 0.36 1 20 2W20 REC IT 2E2 R 14
11 R HAND DRYER 2T1 2W20 20 1 0.18 0.18 1 20 2W20 HAND DRYER 2T1 R 12
9 R HAND DRYER 2T2 2W20 20 1 0.18 0.18 1 20 2W20 HAND DRYER 2T2 R 10
7 R REC IT 2E2 2W20 20 1 0.54 0.36 1 20 2W20 REC ELECTRICAL 2E1 R 8
5 R VAV BATHROOMS 2W20 20 1 0.4 0.18 1 20 2W20 POE SWITCH 2E2 R 6
3 R EWC CORR. 2C2 2W20 20 1 0.18 0.54 1 20 2W20 REC TOILET 2T1, 2T2 R 4
1 R FLOOR BOX 207 2W20 20 1 0.18 0.9 1 20 2W20 REC STORAGE 220 R 2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL ROOM 2E1 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NDA2 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: MLO DISTRIBUTION: 208Y/120V, 3PH, 4W
PANEL: NA2D BUS AMPS: 150
2W20
2W20
2
2
22
2
2
2 04/22/16 ADDENDUM #2
115 FIFTH AVENUENEW YORK, NY 10003T. 212.353.7200F. 212.353.7676
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
Owner:
DATENO. ISSUE
KEY PLAN
Civil / Site:
Structural:
Mechanical, Electrical & Plumbing:
Acoustical Consultant:
Stockton University
101 Vera King Farris DriveGalloway, NJ 08205
Pennoni Associates Inc.
515 Grove StreetHaddon Heights, NJ 08035
Reuther + Bowen
326 Ward StreetDunmore, PA 18512
R.G. Vanderweil Engineers, PC
1001 Avenue of the Americas, 21st FloorNew York, NY 10018
Shen Milsom & Wilke LLC
417 Fifth AvenueNew York, NY 10016
58680.00
STOCKTONUNIVERSITYCLASSROOMBUILDING
06/01/2016
E-803
101 Vera King Farris DriveGalloway, NJ 08205
ISSUED FOR CONSTRUCTION
ELECTRICAL PANELSCHEDULES
NP3A
NP3B
NA3A
NOTES:
1. PANEL SCHEDULES ARE BEING ISSUED WITH CONSTRUCTION DOCUMENTS FORUSE BY THE CONTRACTOR DURING CONSTRUCTION. AFTER ISSUANCE WITHCONSTRUCTION DOCUMENTS, THE CONTRACTOR SHALL BE RESPONSIBLE FORMAINTAINING UPDATED PANEL SCHEDULES THAT REFLECT INSTALLED CONDITIONS,INCLUDING CHANGES MADE TO THE DESIGN DURING THE CONSTRUCTION PHASE.THE ENGINEER WILL NOT ISSUE REVISED PANEL SCHEDULES DURING THECONSTRUCTION PROCESS UNLESS DEEMED NECESSARY BY THE ENGINEER.
2. PROVIDE 20A/1P BREAKERS IN ALL BLANK POLE SLOTS IN BRANCH CIRCUIT PANELS.
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
L 2.97 2.97 M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 58.85
R 12 11 L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 71.07
M 56.1 44.88 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 25.13 23.23 22.7
41 2.5 42
39 2.5 40
37 2.5
3 20 3W20 SHWP-2 (7.5HP) M
38
35 2.5 36
33 2.5 34
31 2.5
3 20 3W20 SHWP-1 (7.5HP) M
32
29 3.1 30
27 3.1 28
25 3.1
3 20 3W20 CU-1 M
26
23 3.33 24
21 3.33 22
19 3.33
3 30 3W20 HWP-2 (10HP) M
20
17 0.67 18
15 0.67 16
13 0.67
3 20 3W20 HWP-5 (1HP), HWP-6 (1HP) M
14
11 3.33 12
9 3.33 10
7 3.33
3 30 3W20 HWP-1 (10HP) M
8
5 0.67 6
3 L LTG ROOF 2W20 20 1 0.53 0.67 4
1 L LTG 3RD FLOOR 2W20 20 1 2.43 0.67
3 20 3W20 HWP-3 (1HP), HWP-4 (1HP) M
2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: Yes SPD:LOCATION: ELECTRICAL ROOM 3E1 SUB-FEED LUGS: NEUTRAL:
ST MAIN: IG GND:SUPPLY FROM: MOUNTING: Surface A.I.C. RATING: 65 kAIC
MAIN: 400A MCB DISTRIBUTION: 480Y/277V, 3PH, 4W
PANEL: NP3A BUS AMPS: 400
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 25.54
R 7.58 7.58 L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 30.03
M 22.45 17.96 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 10 9.51 10.53
41 42
39 40
37 38
35 36
33 34
31 32
29 -- FIRE SMOKE DAMPER -- -- 20 1 0 30
27 -- FIRE SMOKE DAMPER -- -- 20 1 0 0.12 1 20 2W20 HWCP-1 (1/8HP) M 28
25 R TRAP PRIMERS 2W20 20 1 0.1 0.5 1 20 2W20 GWH-1 M 26
23 M B-2 2W30 30 1 2.4 2.4 1 30 2W30 B-1 M 24
21 M CONDENSATE PUMP 2W20 20 1 0.72 4 22
19 0.11 4 20
17M AC-5, AC-6 2W20 20 2
0.11 4
3 50 3W50 CU-3 & AC-8,9,10 M
18
15 R ELEVATOR CAB/LTG 2W20 20 1 1 2.05 16
13 R REC ELECTRICAL 3E1 2W20 20 1 0.54 2.052 20 2W20 CU-2 & AC-7 M
14
11 R POE SWITCH 3E2 2W20 20 1 0.18 0.18 1 20 2W20 FA POWER SUPPLY 3E2 R 12
9 R REC IT 3E2 2W20 20 1 0.36 0.36 1 20 2W20 REC IT 3E2 R 10
7 R REC IT 3E2 2W20 20 1 0.54 0.36 1 20 2W20 REC IT 3E2 R 8
5 R REC ROOF 2W20 20 1 0.72 0.54 1 20 2W20 REC ROOF R 6
3 R BAS HEAD END MECH 3M1 2W20 20 1 0.36 0.54 1 20 2W20 REC ROOF R 4
1 R REC SHELL 2W20 20 1 0.72 1.08 1 20 2W20 REC MECH 3M1 R 2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL ROOM 3E1 SUB-FEED LUGS: NEUTRAL: 200%
ST MAIN: IG GND:SUPPLY FROM: NDA2 MOUNTING: Surface A.I.C. RATING: 22 kAIC
MAIN: MLO DISTRIBUTION: 208Y/120V, 3PH, 4W
PANEL: NA3A BUS AMPS: 150
2W20
2W20
NOTE 2: SLD = REFER TO SINGLE-LINE DIAGRAMS FOR FEEDER SIZE.
NOTE 1: XFMR = REFER TO SINGLE-LINE DIAGRAMS FOR TRANSFORMER SIZE AND REFER TO TRANSFORMER SCHEDULE FOR PRIMARY AND SECONDARY FEEDER SIZES.
N = NONCONTINUOUS LH = LOCKING HASP
C = CONTINUOUS ST = SHUNT TRIP
K = KITCHEN A = ARC FAULT
M = MECH/EQUIP G = GROUND FAULT 5 Ma (PERSONNEL) DEMAND LOAD: 17.24
R 12 11 L = LIGHTING G3 = GROUND FAULT 30 Ma (EQUIP) CONNECTED LOAD: 19.8
M 7.8 6.24 R = RECEPTACLE BLANK = STANDARD
LOAD TYPE CONNECTED DEMAND/ADJUSTED LOAD TYPE KEY BREAKER TYPE KEY PANEL TOTALS
PHASE LOAD (kW): 6.6 6.6 6.6
41 0 0 42
39 0 0 40
37
-- SPARE -- -- 90 3
0 0
3 40 -- -- SPARE --
38
35 0.43 0.67 36
33 0.43 0.67 34
31
M HAC-2 (2X0.5HP) 2W20 20 3
0.43 0.67
3 20 2W20 HAC-1 (3X0.5HP) M
32
29 0 0 30
27 0 0 28
25
-- SPARE -- -- 40 3
0 0
3 20 -- -- SPARE --
26
23 0 4 24
21 0 4 22
19
-- SPARE -- -- 20 3
0 4
3 40 3W40 ELEVATOR CONTROL R
20
17 1 0.5 18
15 1 0.5 16
13
M EF-2 (3HP) 3W20 20 3
1 0.5
3 20 3W20 EF-1 (1.5HP) M
14
11 0 0 12
9 0 0 10
7
-- SPARE -- -- 20 3
0 0
3 40 -- -- SPARE --
8
5 0 0 6
3 0 0 4
1
-- SPARE -- -- 40 3
0 0
3 20 -- -- SPARE --
2
CKT TYPE DESCRIPTIONBKRTYPE
WIRE TRIP POLE A B C POLE TRIP WIREBKRTYPE
DESCRIPTION TYPE CKT
FEED-THRU LUGS: SPD:LOCATION: ELECTRICAL ROOM 3E1 SUB-FEED LUGS: NEUTRAL:
ST MAIN: IG GND:SUPPLY FROM: NP3A MOUNTING: Surface A.I.C. RATING: 65 kAIC
MAIN: 400A MLO DISTRIBUTION: 480Y/277V, 3PH, 4W
PANEL: NP3B BUS AMPS: 400
2
2 04/22/16 ADDENDUM #2