4
Technical Data 96738 Fluid chilled or hot water, up to 60% glycol, steam Flow characteristic modified equal percentage Controllable flow range 90° rotation, A – AB open ccw, B – AB open cw Valve Size [mm] 2” [50] Pipe connector SAE NPT (female connections) Housing Stainless steel A351-CF8M 316 Housing seal PTFE Ball 316 stainless steel Stem 316 stainless steel Stem seal RPTFE Spindle bearing RPTFE Lock nut stainless steel Seat RPTFE Body Pressure Rating 1500 psig WOG Maximum Inlet Pressure (Steam) 50 psi Max Differential Pressure (Steam) 50 psi Close-off pressure ps 1000 psi Maximum Velocity 15 FPS Cv 108 Weight 6.17 lb [2.8 kg] Fluid Temp Range (water) -22...298°F [-30...148°C] Leakage rate ANSI Class VI Flow/Mounting Details Application These threaded valves are designed to provide modulating or two position control of hot or chilled water and saturated steam systems under 50 psi. Typical applications include reheat coils, VAV terminal control, unit ventilators, and air handlers, especially in areas which have minimum profile requirements. Up to 50 psi steam 1/2” - 2000 PSIG WOG, Cold Non-Shock Federal Specification: WW-V-35C, Type II Composition: SS Style: 3 Suitable Actuators Non-Spring Spring Electronic fail-safe B249VSS GMB(X), PRB(X) AF PKRB(X) Safety Notes WARNING: This product can expose you to lead which is known to the State of California to cause cancer and reproductive harm. For more information go to www.p65warnings.ca.gov B249VSS Stainless Steel Body, Ball and Stem 800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 08/18/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.

Upload: others

Post on 21-Oct-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: new - Home | Belimo

Technical Data 96738

Fluid chilled or hot water, up to 60% glycol, steam

Flow characteristic modified equal percentageControllable flow range 90° rotation, A – AB open ccw, B – AB

open cwValve Size [mm] 2” [50]Pipe connector SAE NPT (female connections)Housing Stainless steel A351-CF8M 316Housing seal PTFEBall 316 stainless steelStem 316 stainless steelStem seal RPTFESpindle bearing RPTFELock nut stainless steelSeat RPTFEBody Pressure Rating 1500 psig WOGMaximum Inlet Pressure (Steam) 50 psiMax Differential Pressure (Steam) 50 psiClose-off pressure ∆ps 1000 psiMaximum Velocity 15 FPSCv 108 Weight 6.17 lb [2.8 kg]Fluid Temp Range (water) -22...298°F [-30...148°C]Leakage rate ANSI Class VI

Flow/Mounting Details

ApplicationThese threaded valves are designed to provide modulating or two position control of hot or chilled water and saturated steam systems under 50 psi.Typical applications include reheat coils, VAV terminal control, unit ventilators, and air handlers, especially in areas which have minimum profile requirements.Up to 50 psi steam1/2” - 2000 PSIG WOG, Cold Non-ShockFederal Specification: WW-V-35C, Type IIComposition: SSStyle: 3

Suitable Actuators Non-Spring Spring Electronic fail-safeB249VSS GMB(X), PRB(X) AF PKRB(X)

Safety NotesWARNING: This product can expose you to lead which is known to the State of California to cause cancer and reproductive harm. For more information go to www.p65warnings.ca.gov

B249VSSStainless Steel Body, Ball and Stem

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

Date

cre

ated

, 08/

18/2

020

- Sub

ject

to c

hang

e. ©

Bel

imo

Airc

ontro

ls (U

SA),

Inc.

Page 2: new - Home | Belimo

Technical Data 2196

Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%Power consumption in operation 4.5 WPower consumption in rest position

1.5 W

Transformer sizing 7 VA (class 2 power source)Electrical Connection 18 GA plenum cable, 3 ft [1 m], with 1/2”

conduit connector (10 ft [3 m] and 15 ft [5 m] available)

Overload Protection electronic throughout 0...95° rotationOperating Range 2...10 V (default), 4...20 mA w/ ZG-R01 (500

Ω, 1/4 W resistor), variable (VDC, on/off, floating point)

Operating range Y variable Start point 0.5...30 V End point 2.5...32 V

Input Impedance 100 kΩ for 2...10 V (0.1 mA), 500 Ω for 4...20 mA, 1500 Ω for PWM, On/Off and Floating point

Position Feedback 2...10 V, Max. 0.5 mA, VDC variableAngle of rotation Max. 95°, adjustable with mechanical stopTorque motor 360 in-lb [40 Nm]Direction of motion motor selectable with switch 0/1Position indication Mechanically, 30...65 mm strokeManual override external push buttonRunning Time (Motor) default 150 s, variable 90...150 sAmbient humidity max. 95% r.H., non-condensingAmbient temperature -22...122°F [-30...50°C]Storage temperature -40...176°F [-40...80°C]Degree of Protection IP54, NEMA 2Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA

E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU

Noise level, motor 45 dB(A)Servicing maintenance-freeQuality Standard ISO 9001Weight 4.9 lb [2.2 kg]

†Rated Impulse Voltage 800V, Type action 1, Control Pollution Degree 3.

GMX24-MFT-X1 Technical Data SheetModulating, Non-Spring Return, 24 V, Multi-Function Technology®

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

Date

cre

ated

, 04/

03/2

020

- Sub

ject

to c

hang

e. ©

Bel

imo

Airc

ontro

ls (U

SA),

Inc.

Page 3: new - Home | Belimo

Wiring Diagrams

INSTALLATION NOTES

A Actuators with appliance cables are numbered.

Provide overload protection and disconnect as required.

Actuators may also be powered by 24 VDC.

Only connect common to negative (-) leg of control circuits.

A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC.

Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line.

For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller; the actuator internal common reference is not compatible.

IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155).

46Actuators may be controlled in parallel. Current draw and input impedance must be observed.

47Master-Slave wiring required for piggy-back applications. Feedback from Master to control input(s) of Slave(s).

Meets cULus requirements without the need of an electrical ground connection.

! WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

Blk (1)

Red (2)

Pnk (4)

Wht (3)

Org (5)

LineVolts

24 VAC Transformer

PositionFeedback VDC (+)

(–)

Common

+ Hot

Y2 Input

Y1 Input

U Output

A 1 3 46 47

On/Off

24 VAC Transformer (AC Only)

Blk (1) Common

Red (2) + Hot

Wht (3) Y1 Input

Org (5) U Output

Pnk (4) Y2 Input

LineVolts

(–)(+)

Position Feedback VDC

1 10 46 47

Floating Point

Blk (1) Common

Red (2) + Hot

Pnk (4) Y2 Input

Wht (3) Y1 Input

Org (5) U Output

(–)(+)

LineVolts

24 VAC Transformer

500 1/4 watt

Control Signal

VDC / mA

A 1 3 5 46 47

7

(+) Feedback

VDC/mA Control

Blk (1) Common

Red (2) + Hot

Wht (3) Y1 Input

Pnk (4) Y2 Input

Org (5) U Output

Line

Volts

24 VAC Transformer (AC only)

(–) (+)

PositionFeedback VDC

A 1 8 46 47

PWM Control

GMX24-MFT-X1 Technical Data SheetModulating, Non-Spring Return, 24 V, Multi-Function Technology®

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

Date

cre

ated

, 04/

03/2

020

- Sub

ject

to c

hang

e. ©

Bel

imo

Airc

ontro

ls (U

SA),

Inc.

Page 4: new - Home | Belimo

Functions

0%

50%

100%

Control mode acc. to Y1

Min

Mid

Max

Normal

a b c Org (5)

24 VAC Transformer (AC Only)

U Output

1 5

Blk (1) Common

Red (2) + Hot

Pnk (4)

Wht (3) (–)(+)

LineVolts

B

C

A

VDC / mAControl Signal

Y2 Input

Y1 Input

127

Ω

182

Override Control

Blk (1) Common

Red (2) + Hot

Wht (3) Y1 Input

Org (5) U Output

Master24 VAC Transformer

Line Volts

Control Signal (–)

(+)

Blk (1) Common

Red (2) + Hot

Wht (3) Y1 Input

Org (5) U Output

Ω

1 5 46 47

7

Slave 1

Master - Slave

GMX24-MFT-X1 Technical Data SheetModulating, Non-Spring Return, 24 V, Multi-Function Technology®

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

Date

cre

ated

, 04/

03/2

020

- Sub

ject

to c

hang

e. ©

Bel

imo

Airc

ontro

ls (U

SA),

Inc.