© BELIMO Aircontrols Basic Hydronic Training 1

Belimo Aircontrols, Inc. (USA)

Basic Hydronic Training

Page 2: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 2

System Components

Page 3: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 3

Components in a Hydronic System

1. Pump

2. Load

3. Control Valve

4. Balancing Valve

5. Source

6. Air Removal System

7. Expansion Unit

17

3

4

5

Sourc

e

Lo

ad

2

6

Page 4: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 4

Source Carrier Load

Source Load

Water, Air, Refrigerant, Electricity

Heating Load

Cooling LoadHeating

Cooling

Page 5: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 5

Hydronic Systems

Ch

ille

r

Co

oli

ng

Co

il

40F

43F

45F

55F57FB

oil

er

He

ati

ng

Co

il

250F

245F

240F

190F185F

Cooling Heating

Page 6: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 6

Water Systems

So

urc

e

Lo

ad

Expansion

Chamber

Closed System Open System

So

urc

e

Lo

ad

Page 7: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 7

Closed Water Systems

• Low Temperature Water (LTW)

- Max. 160PSI and max. 250F

• Medium Temperature Water (MTW)

-Max. 160PSI / 250F to 350F

• High Temperature Water (HTW)

-Max. 300 PSI and max. 350F

• Chilled Water Systems (CWS)

- Max. 120 PSI / 40F to 55F (44F or 45F)

Page 8: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 8

Piping Circuits

• Two Pipe System

• Three Pipe System

• Four Pipe System

• Direct and Reverse Return Systems

• Primary-Secondary System

Page 9: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 9

Two Pipe System

• Main Supply Chilled Water or Heat Water

• Supply one pipe, Return one pipe

• Cooling or heating at source

• Loads must all require cooling or heating

coincidentally

Page 10: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 10

Two Pipe SystemB

oile

r

Lo

ad

Ch

ille

r

Lo

ad

Lo

ad

Page 11: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 11

Two Pipe System

Page 12: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 12

Three Pipe SystemB

oile

r

Lo

ad

Ch

ille

r

Lo

ad

Lo

ad

Page 13: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 13

Three Pipe System

Page 14: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 14

Three-Pipe System

Page 15: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 15

Four Pipe System

Page 16: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 16

Four Pipe System with One Coil

Page 17: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 17

Four Pipe System with H&C Coil

Page 18: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 18

Cost for Four Pipe System

• High first cost due to the second water system and the

need for either two coils or more costly control valves

at each terminal unit.

• High operating cost due to the two pumps operating,

but do provide good flexibility in meeting varying loads.

Page 19: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 19

• All year availability of heating and cooling with individual

zone temperature control

• Chilled and hot water are typically only simultaneously

supplied during the Spring and Fall seasons

• Elimination of zoning cost and complexity

Simpler changeover decisions

• The lowest and quietest fan speed is adequate most of

the time.

Advantages of Four Pipe Systems

Page 20: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 20

Coil #4

0 - 100 gpm

Coil #3

0 - 100 gpm

Coil #1

0 - 100 gpm

Coil #2

0 - 100 gpm

Source

Piping - Direct Return Piping

Page 21: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 21

Coil #4

0 - 100 gpm

Coil #3

0 - 100 gpm

Coil #1

0 - 100 gpm

Coil #2

0 - 100 gpm

Source

Piping - Reverse Return Piping

Page 22: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 22

Primary – Secondary SystemS

ou

rce

Lo

ad

So

urc

e

So

urc

e

Lo

ad

Lo

ad

Page 23: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 23

Pipe Design

Page 24: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 24

.constpp dynstat

Bernoulli’s Law

The Bernoulli’s law is stating the principle of

energy conservation. The sum of the two energies

represented by static pressure and dynamic

pressure is constant between two points in the

pipe, assuming no energy exchange with the

exterior or transformation of energy into heat by

friction between these two points.

Page 25: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 25

Bernoulli’s Law

ptotal1

ptotal2

pstatic1 pstatic2

pdyn1 pdyn2

Page 26: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 26

V2 P2 2

V1 P1 1

Z1

Z2

hL

LhP

g

VZ

P

g

VZ

2

2

2

22

1

1

2

11

22

Page 27: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 27

Pipe Sizing and Pressure Drop Equations

g

V

D

Lfh

2

2

Darcy-Weisbach Equation

2ft/sec 32.2 constan, nalgravitatio g

ft/sec velocity,average Fluid

in pipe, ofDiameter Internal D

ft pipe, ofLength L

)Moody (from essdimensionl factor,friction f

ftin drop, pressureΔh

V

Page 28: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 28

Sizing a Piping System Pipe Friction Loss

• Suggested head loss in range from 1 to 4ft per 100ft

- 1997 ASHRAE Handbook-Fundamentals

• Max. 4 ft/sec velocity in pipe 2”

• Suggested 4 ft/sec velocity in pipes larger than 2”

Page 29: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 29

Simplified Method

• D = Pipe Diameter

• Q = Flow Rate, GPM

• S = Pipe Sizing Constant

- S= 0.44, assuming 4 ft head drop/100ft

- S = 0.5 assuming 2 ft head drop/ 100ft

4.0QSD

Page 30: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 30

Examples

Load: 100GPM

D = SQ0.4 = 0.44 x 1000.4 = 2.78” 3”

Load: 200GPM

D = SQ0.4 = 0.44 x 2000.4 = 3.66” 4”

Load: 300GPM

D = SQ0.4 = 0.44 x 3000.4 = 4.31” 4”

Load: 400GPM

D = SQ0.4 = 0.44 x 4000.4 = 4.83” 5”

Page 31: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 31

Head Loss Calculation

Pipes (Friction Loss for Water in Commercial Steel Pipe

(Schedule 40)

Strainers, Fitting, Elbows, Reduction, etc

Valves, Balancing Valves (Valve - Manufacturer)

Head loss Load (Coil, etc.)

Head loss Source (Chiller, etc.)

=Total Head Loss

Page 32: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 32

Head Loss in Pipes

Pipes (Friction Loss for Water in

Commercial Steel Pipe (Schedule 40)

Head Loss

2.5ft

Flo

w R

ate

10

0G

PM

hspec =…ft/100ft pipe

Total h=L x hspec /100

Page 33: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 33

Fittings

h = head loss in feet of water

k = resistance coefficient for valve or fitting

V2/2g = velocity head, ft based on flow gpm in connect pipe (example Figure

2 – 15 for 2 in)

V = fluid velocity, ft/sec

g = 32.2 ft/sec2, gravitational constant

g

Vkh

2

2

Page 34: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 34

Page 35: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 35

Which pump do we choose?

Total Pipe length = 300 ft

BTU/HR = 500,000 BTU/HR

T = 10F

GPM = ?

Ch

ille

r

Co

il

500T

BTUHGPM

GPMxT

BTUHGPM 100

50010

500000

500

Page 36: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 36

What is the pipe size?

Required Flow: 100GPM

Pipe Diameter: ?

D = Pipe Diameter

Q = Flow Rate, GPM

S = Pipe Sizing Constant

S= 0.44, assuming 4 ft head loss/100ft

S = 0.5 assuming 2 ft head loss/ 100ft

4.0QSD D = SQ0.4 = 0.44 x 1000.4 = 2.78” 3”

Page 37: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 37

Head loss elbows?

Pipe: 3”, Steel Pipe, screwed

Head loss of total elbows?

Ch

ille

r

Co

il

4 Elbow 0.8ft

g

Vkh

2

2

fth 2.02.322

48.0

2

Page 38: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 38

Head loss pipe?

Pipe: 3”, Steel Pipe, screwed

Total Pipe length = 300 ft

Ch

ille

r

Co

il

h = 300 x 2.5 /100 = 7.5ft

Pipes (Friction Loss for Water in Commercial Steel Pipe (Schedule 40)Figure 2-14 Friction Loss - Water

2.5 ft/100ft

Page 39: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 39

Total head loss?

1 Chiller 9 ft (4PSI, Info Manuf.)

1 Cooling Coil 9 ft (4PSI, Info Manuf.)

1 Control Valve 9 ft (4PSI)

1 Balance Valve 3 ft (1PSI)

4 Elbows each 0.2 ft 0.8 ft

1 Pipe System 7.5 ft

Ch

ille

r

Co

il

Total Head Loss of 38.3ft at 100GPM

Page 40: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 40

System Curve

0 80 120 160 200

10

20

40

60

80

20 40 60 100 140 180

Flow – GPM

Head (

ft) System Point at

design load

Head Loss of 38.3 at 100GPM

Page 41: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 41

Pumps in HVAC

Page 42: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 42

Pumps in HVAC

Single Suction Double Suction

Volute Type Axial Flow Type

Centrifugal Special Effect

Dynamic

Reciprocating Rotary Pumps

Displacement

Pumps

Page 43: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 43

Impeller

BladeInlet

Flow

Outlet Flow

Page 44: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 44

Pump Curve

V

Pump Characteristic

100% Volume

Operating Point

Pump

Head

System

Head

Ch

ille

r

Co

il

Page 45: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 45

Pump Curve (Steep)

p

V

Pump Characteristic

100%Volume

Operating Point

Ch

ille

r

Co

il

Page 46: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 46

Pump Curve (Flat)

p

V

Pump Characteristic

100%

Ch

ille

r

Co

il

25%

Volume

Operating Point

Page 47: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 47

Operating Point

p

V

Load 100% Flow

100%

Ch

ille

r

Co

il Operating Point

System Head

Curve

Pump Head

Capacity Curve

Page 48: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 48

System Curves for a Pump Type

0 80 120 160 200

10

20

40

60

80

20 40 60 100 140 180

Flow – GPM

Head (

ft)

70%65%60%7.0

6.5

6.0

5.5

5.0

Motor Horsepower

55%

Page 49: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 49

Minimum Flow of Pump

• Depends on pump construction and energy generated

by pump

• Not enough flow could result in overheating and

cavitation

• Some low power pumps can operate at zero flow

• Installation of bypass circuit

Page 50: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 50

Valves in HVAC

Page 51: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 51

What Control Characteristic is Preferred?

0 40 60 80 100

20

40

60

80

100

10

30

50

70

90

10 20 30 50 70 90

Control Signal (%)

Hea

t O

utp

ut

(%)

Heat Output

Page 52: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 52

What are the Coil Characteristics?

0 40 60 80 100

20

40

60

80

100

10

30

50

70

90

10 20 30 50 70 90

Valve Opening (%)

Heat O

utp

ut

(%)

Characteristic of

a coil

Heat Output

Page 53: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 53

What are the Valve Characteristics?100

0 40 60 80 100

20

40

60

80

10

30

50

70

90

10 20 30 50 70 90

Signal (%)

Flo

w,

Heat O

utp

ut (%

)

Heat Output

Characteristic of

a Coil

Characteristic of

Control Valve

Page 54: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 54

Valve Opening (Signal) (%)

0 40 60 80 100

20

40

60

80

100

10

30

50

70

90

10 20 30 50 70 90

Flo

w (

%)

10.7

Equal %

010.70

6.513.410

131720

19.52130

262640

333350

414160

515170

646480

808090

100100100

Corrected

Flow

Theoretical

Flow

Lift

Linear Curve

Valve Characteristics

Modified Equal Percentage

Page 55: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 55

Valve Authority

Page 56: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 56

Authority of Control Valves

with Variable Flow Through the Coil

• Authority of two way control valves

• Authority of three way control valves

Page 57: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 57

3-way Control Valve

Const

4 4 12

5.08

4A

leFlowVariabv

v

pp

pA

100

100

0

100

v

v

p

pA

20 psi

Page 58: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 58

3-way Control Valve

Const

20 psi

4 4 12

5.08

4A

leFlowVariabv

v

pp

pA

100

100

0

100

v

v

p

pA

A

B

Page 59: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 59

3-way Control Valve

Const

41 45 121450%

01

20 psi

Page 60: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 60

Valve Authority - Flow 100%P

Term

inal

P V

alv

e

Coil

P Terminal =const

Page 61: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 61

Valve Authority - Flow 50%P

Term

inal

P V

alv

e

Coil

P Terminal =const

Page 62: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 62

Valve Authority - Flow 0%P

Term

inal

P V

alv

e

Coil

P Terminal =const

Page 63: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 63

2.020

4A

leFlowVariabv

v

pp

pA

100

100

0

100

v

v

p

pA

2-way Control Valve

VFD

4 4 12

20 psi

Page 64: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 64

2-way Control Valve

VFD

41 416 123

20 psi

50%

Page 65: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 65

Valve Authority - Flow 100%

Coil

P T

erm

inal

P V

alv

e

Page 66: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 66

Valve Authority - Flow 50%

Coil

P T

erm

inal

P V

alv

e

Page 67: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 67

Valve Authority - Flow 0%

Coil

P T

erm

ina

l

P V

alv

e

P Terminal =const

Page 68: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 68

Sizing Rules

Min. pvalve = 0.25 p pumphead

Authority = 0.4 to 0.5

Page 69: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 69

Authority Distortion of Linear Flow

Characteristics

0 40 60 80 100

20

40

60

80

100

10

30

50

70

90

10 20 30 50 70 90

Valve Opening (%)

Flo

w (

%)

0.1

0.2

0.4

0.6

0.8

1

Page 70: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 70

Authority Distortion of Equal Percentage

Flow Characteristics

0 40 60 80 100

20

40

60

80

100

10

30

50

70

90

10 20 30 50 70 90

Valve Opening (%)

Flo

w (

%)

0.1

0.2

1

0.4

0.6

0.8

Page 71: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 71

Counter-flow, cross-flow or parallel-flow heat exchangers are used

depending on the application. They have different efficiencies.

Counter-Flow Cross-Flow Parallel-Flow

Page 72: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 72

Constant or Variable Flow

Regardless of valve position, the

full water flow is always circulating

through the heat exchanger

=> Temperature control

Depending of valve position,

0..100% of the water flow

circulates through the heat

exchanger

=> Flow control

e.g. air

Page 73: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 73

Large outside flow?

Temperature control

constant Flow

Variable temperature

Are different temperature

levels in coil acceptable?

Flow Control

Constant Temperature

Variable Flow

yes

no

yes

Constant or Variable Flow

Dehumidification

yes

no

yes yes

Prevention of

freezing

nono

Page 74: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 74

Diverting Circuit with Mixing Valve

pV100

pFV

Coil

100%100%

var

var

var

Page 75: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 75

Diverting Circuit with Diverting Valve

pV100

pFV

Coil

100%100%

var

varvar

Page 76: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 76

Throttling Circuit

pV100

pFV

Coil

varvar

Page 77: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 77

Mixing Circuit with Mixing Valve

pv100

Coil

100%100%

var

varvar

Page 78: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 78

Application a-Value

Pre Heating Coil

0.25 to 0.4

Heating Coil 0.15 to 0.4

Cooling Coil 0.25 to 0.5

Radiators 0.5 to 0.65

Converters 0.5 – 3.0

0 40 60 80 100

20

40

60

80

100

10

30

50

70

90

10 20 30 50 70 90

Flow (%)

Energ

y (

%)

3

21.5

10.8

0.60.4

0.05

0.15

0.25

Heat Exchanger Characteristics

Page 79: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 79

0 40 60 80 100

20

40

60

80

100

10

30

50

70

90

10 20 30 50 70 90

Flow (%)

Ene

rgy (

%)

Heat Exchanger Characteristics

Constant Flow

Variable Flow

Page 80: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 80

0 40 60 80 100

20

40

60

80

100

10

30

50

70

90

10 20 30 50 70 90

Flow (%)

Ene

rgy (

%)

Heat Exchanger Characteristics

T = 10F

T = 30F

Page 81: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 81

0 40 60 80 100

20

40

60

80

100

10

30

50

70

90

10 20 30 50 70 90

Flow (%)

Ene

rgy (

%)

Heat Exchanger Characteristics

Heating Coil

Cooling Coil

Page 82: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 82

Influencing Factors

Base Valve

Characteristic

Hydraulic

System

System Valve

CharacteristicCoil

Characteristic

Resulting

Characteristic

Valve with

Hydraulics

Heat

Exchanger

Page 83: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 83

Conventional Sizing Methods

Page 84: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 84

Coil #4

0 - 100 gpm

Coil #3

0 - 100 gpm

Coil #1

0 - 100 gpm

Coil #2

0 - 100 gpm

20 psi

30 psi

40 psi

p =4 psi

p =4 psi

p=4 psi

p=4 psi

p=12 psi

p=2 psi

p=32 psi

p=22 psi

Pressure Differential Sensor

Chiller

20 psi

p=4 psi

p=4 psi

p=4 psi

p=4 psi

VFD-Pump

10 psi10 psi

30 psi

40 psi

Application

Page 85: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 85

A=4/10=0.4

A=4/20=0.2

A=4/30=0.14

A=4/40=0.1

Signal

Flo

w/H

ea

t o

utp

ut %

Coil #4

0 - 100 gpm

Coil #3

0 - 100 gpm

Coil #1

0 - 100 gpm

Coil #2

0 - 100 gpm

20 psi

30 psi

40 psi

p=12 psi

p=2 psi

p=32 psi

p=22 psi

Pressure Differential Sensor

Chiller

p=4 psi

p=4 psi

p=4 psi

p=4 psi

VFD-Pump

10 psip =4 psi

p =4 psi

p=4 psi

p=4 psi

Application

Authority

Page 86: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 86

Shift to Variable Supply with VFD-Pumps

and Two-way Valves

Const

20 psi

4 4 12

VFD

20 psi

44

12

Page 87: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 87

Authority Method

Page 88: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 88

A=0.5

A=0.5

A=0.5

A=0.5

Signal

Flo

w/H

ea

tou

tpu

t

Coil #1

0 - 100 gpm

Coil #2

0 - 100 gpm

Coil #4

0 - 100 gpm

Coil #3

0 - 100 gpm

20 psi

30 psi

40 psi

p=6 psi

p=2 psi

p=16 psi

p=11 psi

Pressure Differential Sensor

Chiller

p=4 psi

p=4 psi

p=4 psi

p=4 psi

VFD-Pump

10 psip =4 psi

p =10psi

p=15 psi

p=20 psi

Application

Page 89: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 89

Current Concepts for Valve Sizing

Correct sized components

Generally less expensive components, like valves

Complex procedures for all involved

More detailed information is required

Consideration of diversity factors

No feedback of sized devices from suppliers

Very simple rule

Used by all involved in the project

Good base for price comparison

Oversized valves overpriced valves

Bad authority

Hunting

Instable control loops

Exact

calculation

f( p and V)

Rule:

pvalve = pCoil

Rule:

pvalve= 3 – 5 psi

Page 90: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 90

Additional Valve Sizing Considerations

For the selection of the valve bodies it is

necessary to consider elevation of

system, pump pressure and fill pressure

Two-way valves:

• For the close-off pressure the pump

head needs to be considered.

Three-way valves:

• Pressure difference valve

Page 91: Basic Traininghydronics by Belimo

© BELIMO Aircontrols Basic Hydronic Training 92

Reference Literature

• Total Hydronic Balancing

Robert Petitjean, Tour & Andersson Hydronic AB

• HVAC Pump Handbook

James B. Rishel, McGraw-Hill

• ASHRAE Handbooks

• HVAC Equations, Data, and Rules of Thumb

Bell, McGraw-Hill

Page 92: Basic Traininghydronics by Belimo