mv2 - pbsigroup.com

6
www.pbsigroup.com PBSI Group Ltd manufactured in Manchester, UK MV2 Comparison Document

Upload: others

Post on 16-May-2022

16 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MV2 - pbsigroup.com

www.pbsigroup.com

PBSI Group Ltd manufactured in

Manchester, UK

MV2ComparisonDocument

Page 2: MV2 - pbsigroup.com

Issue: 1MV2 SPAM 150C comparison

P&Bs SPAM 150C relay retro�t provides a quick and direct replacement for your current SPAM relay.

The easy to navigate interface and design reliability provide users with total peace of mind.

P&Bs retro�t approach provides risk-free customised solution for breakdown, life extension and obsolescence challenges faced by many of the worlds operators and end users.

INTELLIGENT DESIGN

P&Bs SPAM 150C retro�t uses the latest MV2 technology which follows an evolving product lifecycle based upon

functional safety and use in critical applications.MV2 is designed for fault free and long life operation in

challenging high duty and high ambient temperature environments.

www.pbsigroup.com

PIN FOR PINALTERNATIVE

SAME CASE FORMAT

PIN FOR PIN

ALTERNATIVE

lATEST IEC

STANDARDS

SAME CASE

FORMAT

SPAM RETROFIT

Page 3: MV2 - pbsigroup.com

0044 (0)161 230 6363P&B Reception Sales Manager - Paul crawfordSales and Technical support - Ross Dyson

[email protected]

P&B LtdManchester, UK

SPAMC

The

150Retro�t

MV2

Comparison Document

Replacement Relays for on going equipment support

CASE DIMENSIONS Panel Mounted142x162x216mm

Panel Mounted142x162x216mm

DISPLAY 4 digit display, LED indictaor

Fully Graphic LCD display, 2 tri-color LED’s and 4 software driven function

keys

DIGTIAL INPUTS 1x semi-programmable

12xProgrammeable inputs

OUTPUT RELAYS 5xNO & 1xCO or 4xNO, 1NC & 1xCO-

semi-con�gurable contacts

4x Con�gurable change

over contacts

ANALOGUE 4x CT 1A or 5A rated 4x CT 1A or 5A rated1x Vref input

SUPPLYVOLTAGE

80-265V AC/DC or 18-80V DC

80-265V AC/DC24-75Vdc LV PSU available

COMMUNICATION RS232 RS485 rear port and USB front port Modbus RTU /

P&B protocol.

Pg. 1

The MV2 SPAM 150C (Retro�t) uses a vertical Motor vision (MV2) that is wired as per the original unit adopting the same terminal connections making this a direct pin for pin alternative. The replacement relay is mounted within a pre- wired chassis so no changes would need to be made to the panel aperture, a direct and fast �t solution minimalizing the downtime during on site installation.

Issue: 1MV2 SPAM 150C comparison

The SPAM retro�t can be used to replace the ABB Spam 150C.The SPAM retro�t uses a vertically mounted Motorvision (MV2) protection relay complete with terminal adaptor assembly which converts the standard MV2 terminal connections to become pin for pin to the SPAM relay.The MV2 is mounted within an adaptor plate which simpli�es the installation and mechanical �t to the starter tray. Therefore, no wiring changes and no panel aperture changes are required. P&Bs SPAM retro�t is a direct and fast �t solution minimising the downtime during on site installation.

Page 4: MV2 - pbsigroup.com

Replacement Relays for on going equipment support

MM2 (MV2) MM2 RETROFIT

Motor full loud current (FLC)Setting range (of CT Primary)-Setting step-

t6xSetting range-Setting step-

Hot/cold ratioSetting range-Setting step-

Cool timer factorSetting range-Setting step-

Pre alarmSetting range-Setting step-

Overload levelSetting range-Setting step-

Cuto� MultipleSetting range-Setting step-

ResetSetting range

Trip level (% of FLC)Setting range-Setting step-

Trip timeSetting range-Setting step-

ResetSetting range

Motor full loud current setting ISetting range-Setting resolution-

Safe stall time setting t , operate time from cold state at 6xISetting range-Setting resolution as handled by algorithm-Time count increments for the thermal unit-

Restart Inhibit level θ for thermal overload Setting range-

Cooling time multiplier k for motor at standstillSetting range-

Thermal prior alarm level θSetting range-

Start-up current I Setting range-

Start-up time tSetting range-

When operating as de�nite timeovercurrent relay:Reset time, typ.-Drop-o�/pick-up ratio-

Or when operating as start-up thermal stress relay:Reset time, typ.-Shortest possible operate time-

0.50 - 1.50xI0.01xI

2.0 – 120s0.5s0.5s

20 – 80% of thermal trip level θ

1 – 64 times heating time constant

50 – 100% of thermal trip level θ

1.0 – 10.0xI

0.3 – 80s

50ms0.96

200msabout 300ms

Thermal Overload unit (49)

Start-up supervision unit (14/48/51)

Thermal Model _26/49)

10 – 250% 0.01A/0.1A/1A

0.5 – 120s0.1s

20 – 80%1%

25 – 2000%5%

55 – 99%1%

105 – 130%1%

6, 8,10, 12x2x

Auto, Panel, Serial, Remote

400 – 1200%5%

0.1 – 4.0s0.1s

Auto, Panel, Serial, Remote

SPAM 150C (MV2) SPAM 150C RETROFIT

θ

n

n

6x

θ

i

t

c

a

s

s

n

t

Pg. 2

Issue: 1MV2 SPAM 150C comparison

HS Overcurrent (50/51)

Page 5: MV2 - pbsigroup.com

Replacement Relays for on going equipment support

Start current I>> Setting range

Start time typ.

Operate timeSetting rangeReset time, typ.Drop-o�/pick-up ratio

Start current ISetting rangeStart time

Operate timeSetting rangeReset time, typ.Drop-o�/pick-up ratio

Start current ∆ISetting range

Operate time at lowest possible setting 10%Setting range

Reset time, typ.

Operate time for a singlephasing condition

Operate time at incorrect phase sequence

0.5 – 20.0xI or ∞, in�nitetyp. 50ms

0.04 – 30s50ms0.96

1.0 – 100% I50ms

0.05 – 30s50ms0.96

10 – 40% I or ∞, in�nite

20 – 120s, inverse time 200ms

1s

600ms

SPAM 150C MV2 SPAM 150C (RETROFIT)High-set overcurrent unit (50)

Earth-fault unit (51N)

Trip level (% of FLC)Setting rangeSetting step

Trip timeSetting rangeSetting step

ResetSetting range

CharacteristicSetting range

Trip levelSetting range Setting step

Time multiplierSetting range Setting step

Trip time (DEFT ONLY)Setting range Setting step

ResetSetting range

Trip level (% of FLC)Setting rangeSetting step

Trip timeSetting rangeSetting step

ResetSetting range

Trip time (�xed)

ResetSetting range

400 – 1200%5%

0.1 – 4.0s0.1s

Auto, Panel, Serial, Remote

DEFT, NINV, VINV, EINV

1 – 40%0.1%

0.10-10s0.1

0.1 – 5.0s0.1s

Auto, Panel, Serial, Remote

10 – 40%5%

1 – 60s1s

Auto, Panel, Serial, Remote

1s

Auto, Panel, Serial, Remote

High-set overcurrent unit (50)

Unbalance (46)

Single phase (46SP)

Unbalance/phase reversal unit (46)

Pg. 3

n

n0

L

Issue: 1MV2 SPAM 150C comparison

Page 6: MV2 - pbsigroup.com

Replacement Relays for on going equipment support

SPAM 150C MV2 SPAM 150C (RETROFIT)

Start-up time counter unit

Pg. 4

q

Starting value I<Setting range

Operate time t<Setting rangeReset time, typ.Drop-o�/pick-up ratio, typ.

Restart inhibiting start count setting ∑t

Countdown rate of start-up time counter ∆∑t /∆t

Trip level (% of ARC)Setting rangeSetting step

Trip timeSetting rangeSetting step

U/C reset delaySetting rangeSetting step

ResetSetting range

Trip timeSetting rangeSetting step

ResetSetting range

30 – 80% I or o�

2 – 600s200ms1.1

5 – 500s

2 – 250s/h

30 – 95%5%

1 – 60s1s

0 – 1200s10s

Auto, Panel, Serial, Remote

1 – 250s1s

Auto, Panel,Serial, Remote

Undercurrent unit (37) Undercurrent (37)

si

s

Issue: 1MV2 SPAM 150C comparison

Maximum start time (14/48)