multi-objective optimization of low charge liquid overfeed … · is whether the optimal design of...

9
General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights. Users may download and print one copy of any publication from the public portal for the purpose of private study or research. You may not further distribute the material or use it for any profit-making activity or commercial gain You may freely distribute the URL identifying the publication in the public portal If you believe that this document breaches copyright please contact us providing details, and we will remove access to the work immediately and investigate your claim. Downloaded from orbit.dtu.dk on: Apr 26, 2020 Multi-objective optimization of low charge liquid overfeed ammonia evaporators for industrial refrigeration Kærn, Martin R.; Markussen, Wiebke B.; Kristófersson, Jóhannes Published in: Proceedings of the 8th Conference on Ammonia and CO<sub>2</sub> Refrigeration Technologies Link to article, DOI: 10.18462/iir.nh3-co2.2019.0011 Publication date: 2019 Document Version Peer reviewed version Link back to DTU Orbit Citation (APA): Kærn, M. R., Markussen, W. B., & Kristófersson, J. (2019). Multi-objective optimization of low charge liquid overfeed ammonia evaporators for industrial refrigeration. In Proceedings of the 8th Conference on Ammonia and CO 2 Refrigeration Technologies (pp. 86-93 ). International Institute of Refrigeration. Institut International du Froid. Bulletin https://doi.org/10.18462/iir.nh3-co2.2019.0011

Upload: others

Post on 24-Apr-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Multi-objective optimization of low charge liquid overfeed … · is whether the optimal design of the evaporator changes as recirculation ratio decrease or not. The objective is

General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.

Users may download and print one copy of any publication from the public portal for the purpose of private study or research.

You may not further distribute the material or use it for any profit-making activity or commercial gain

You may freely distribute the URL identifying the publication in the public portal If you believe that this document breaches copyright please contact us providing details, and we will remove access to the work immediately and investigate your claim.

Downloaded from orbit.dtu.dk on: Apr 26, 2020

Multi-objective optimization of low charge liquid overfeed ammonia evaporators forindustrial refrigeration

Kærn, Martin R.; Markussen, Wiebke B.; Kristófersson, Jóhannes

Published in:Proceedings of the 8th Conference on Ammonia and CO<sub>2</sub> Refrigeration Technologies

Link to article, DOI:10.18462/iir.nh3-co2.2019.0011

Publication date:2019

Document VersionPeer reviewed version

Link back to DTU Orbit

Citation (APA):Kærn, M. R., Markussen, W. B., & Kristófersson, J. (2019). Multi-objective optimization of low charge liquidoverfeed ammonia evaporators for industrial refrigeration. In Proceedings of the 8th Conference on Ammoniaand CO

2 Refrigeration Technologies (pp. 86-93 ). International Institute of Refrigeration. Institut International du

Froid. Bulletin https://doi.org/10.18462/iir.nh3-co2.2019.0011

Page 2: Multi-objective optimization of low charge liquid overfeed … · is whether the optimal design of the evaporator changes as recirculation ratio decrease or not. The objective is

8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, Ohrid, 2019

PAPER ID: XXX[Paper ID] DOI: 10.18462/iir.[organisers to request DOI from IIR].XXX[DOI Number]

Multi-objective optimization of low charge liquid overfeed ammonia evaporators for industrial refrigeration

Martin R. KÆRN(a), Wiebke B. MARKUSSEN(a), Jóhannes KRISTÓFERSSON(b) (a) Technical University of Denmark, Lyngby, Denmark, e-mail: [email protected]

(b) Danish Technological Institute, Høje Taastrup, Denmark

ABSTRACT

Charge minimization in ammonia refrigeration systems is pertinent due to safety restrictions associated to these systems. The objective of the present research is to minimize the ammonia charge and the required heat transfer area of evaporators in large-scale ammonia refrigeration systems by numerical optimization. The studied evaporator is a traditional flooded inline finned tube evaporator operated with pumped liquid recirculation rated to 22 kW cooling capacity. The optimization involved the interaction between heat-exchanger design parameters such as transverse tube pitch, longitudinal tube pitch, tube diameter and number of tube circuits, and operation parameters such as ammonia circulation ratio. The boundary conditions were the given required cooling capacity, the air volume flow rate and the frontal area, and provided the same cooling load and air throw length in a given cold store for each solution of the optimization. Furthermore, the airside pressure drop was constraint to less than 55 Pa, and the fin spacing was fixed at 12 mm to accommodate freezing conditions. The results show that a significant reduction in refrigerant charge and heat transfer area is possible through smaller tube diameters, a higher number of tubes per row and more refrigerant circuits.

Keywords: Low-charge, Ammonia, Liquid overfeed evaporator, Design, Optimization

1. INTRODUCTION

Ammonia is widely used as the refrigerant in industrial refrigeration systems due to its superior thermodynamic and heat transfer properties (Hrnjak and Park, 2007; Pearson, 2008). On the other hand, ammonia is toxic and flammable, and consequently national authorities have implemented regulations to restrict the amount of charge in industrial refrigeration systems in many countries. Today the charge limit in Denmark is 5000 kg. Exceeding this limit leads to significant increase in cost of the plant, both installation, maintenance and operation costs, due to increased safety precautions. It provides an incentive for refrigeration engineers and equipment manufacturers to target their research and development towards low-charge ammonia systems.

Most industrial refrigeration systems using ammonia as the refrigerant are centralized systems, typically with long distribution and return pipelines from the evaporators. These systems are equipped with either liquid overfeed evaporators or dry expansion evaporators. Dry expansion systems have a higher potential for charge minimization, but come with a performance penalty of necessary superheat. On the other hand, liquid overfeed evaporators usually operate at constant pump speed and result in recirculation ratios of 3-5. The recirculation ratio is defined as the ratio between the refrigerant mass flow rate through the evaporator and the vaporized refrigerant mass flow rate. Consequently, liquid overfeed systems contain a much larger ammonia charge, not only in the evaporator but also in the return pipeline.

Recently, Kristófersson et al., (2017a) published measurements of the ammonia charge as function of the recirculation ratio for a traditional liquid overfeed evaporator (bottom fed). It was found that the charge could be reduced by a factor of 2 to 3 by reducing the recirculation ratio from 5 to 1.5, depending on the evaporation temperature and without sacrificing cooling capacity. Furthermore, Kristófersson et al., (2017b) indicated that the compressor power consumption could be reduced by 4.9 %, if the recirculation ratio was reduced from 4 to 1.5 in a large distributed cold storage in Denmark that was recently built.

This paper focusses on the charge minimization in liquid overfeed systems by exploring the effect of key evaporator design parameters numerically. The considered parameters are transverse tube pitch, longitudinal

Page 3: Multi-objective optimization of low charge liquid overfeed … · is whether the optimal design of the evaporator changes as recirculation ratio decrease or not. The objective is

8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, Ohrid, 2019

tube pitch, tube diameter and number of tube circuits as well as recirculation ratio. The main research question is whether the optimal design of the evaporator changes as recirculation ratio decrease or not.

The objective is to minimize the ammonia charge as well as the evaporator cost, here exemplified by heat transfer area, by employing a multi-objective genetic algorithm to optimize a numerical model of the evaporator. The evaporator specified in Kristófersson et al., (2017a) was used as the baseline for the optimization. The cooling capacity, air-volume flow and frontal area were fixed to the baseline values, and provide the same cooling load and air throw length in a given cold store for each solution of the optimization. Moreover, the required heat transfer area was solved for at each combination of heat exchanger design parameters (transverse tube pitch, longitudinal tube pitch, tube diameter) and the optimization was carried out at several recirculation ratios and number of tube circuits. Furthermore, the airside pressure drop was constraint to less than 55 Pa, and the fin spacing is fixed at 12 mm to accommodate freezing conditions.

The outline of the paper is as follows. Section 2 introduces the numerical model and presents a validation with experiments. Section 3 presents the results at -30 °C evaporation temperature. Finally, the results are discussed in Section 4 and followed up by the conclusions in Section 5.

2. METHODOLOGY

2.1. Numerical model

The model of the evaporator was implemented in Matlab2017a. Figure 1 illustrates a sketch of the studied evaporator having an inline tube arrangement, where the transverse tube pitch, , longitudinal tube pitch, , and tube diameter, , are to be optimized at several recirculation ratios and number of tube circuits.

Lt

L

Xtair

d

s

Figure 1: Sketch of the evaporator

The model assumes identical refrigerant circuits, which alleviates the constraints of the tube circuiting during the design phase. Moreover, the model solves for the global airside heat transfer coefficient, fin efficiency and overall surface efficiency, and employs them to a single refrigerant circuit as illustrated in Figure 2. The refrigerant circuit was discretized using an upwinded approximation of cell center/average variables ( ). Each cell energy equation was formulated as

, , , , , , , , Eq. (1)

In Equation 1, denotes the effectiveness and was computed by the effectiveness-NTU relation for evaporators with NTU , , , ,⁄ , where and denote the heat transfer coefficient and overall surface efficiency of the fins, respectively. The model neglects heat transfer resistance in the tube wall as well as fouling on the fluid surfaces. Furthermore, refrigerant gravitational and accelerational pressure drops were neglected. Correlations for heat transfer, pressure drop and void fraction are summarized in Table 1. We used general well-known or dedicated correlations for ammonia where applicable. For the airside with inline tube arrangement and large fin spacing, only the heat transfer correlation is applicable, while the pressure drop correlation is developed at lower fin spacing. On the other hand, the pressure drop correlations by Webb and

Page 4: Multi-objective optimization of low charge liquid overfeed … · is whether the optimal design of the evaporator changes as recirculation ratio decrease or not. The objective is

8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, Ohrid, 2019

co-authors employ a superposition method of the bare tube bundle and fin contributions, and we expect it to be applicable at larger fin spacing also. Thermophysical properties of the fluids were computed using Coolprop 4.2.

The model solves for each control volume following the refrigerant flow direction, cell by cell, and resolving local refrigerant heat transfer, void fraction and pressure drop. The inlet refrigerant pressure was adjusted by iteration according to the outlet pressure boundary condition, which was fixed by the outlet saturation temperature. The inlet enthalpy was also fixed at the bubble point corresponding to the outlet pressure, and the mass flow rate was fixed by the recirculation ratio . These refrigerant boundary conditions correspond to pumped circulation systems with a small amount of inlet liquid subcooling due to refrigerant pressure drop. The frontal area of the evaporator was fixed by and , as indicated in Figure 1, and the longitudinal length of the evaporator was adjusted by iteration in order to reach the fixed cooling capacity. Furthermore, the air volume flow rate was fixed and provided, together with the fixed frontal area, the same air throw length in a given cold store for each solution.

Finally, the fin spacing was fixed at 12 mm to accomodate freezing conditions. The model assumes dry air conditions always for simplicity and computational speed during optimization. No particular consideration was addressed towards the frost build-up during optimization, and may be addressed once the dry conditions optimal results were obtained (similar to a tube circuiting optimization).

Figure 2: Sketch of the refrigerant flow discretization, denote the approximated variable

Table 1. Employed correlations for air and refrigerant. Air side heat transfer coefficient Kim and Kim, 2005 Air side pressure drop Kim et al., 1997 Single-phase refrigerant heat transfer coefficient Gnielinski, 1976 Single-phase refrigerant pressure drop Blasius, 1913 Two-phase refrigerant heat transfer coefficient Fenton, 1999 Two-phase refrigerant pressure drop Müller-Steinhagen and Heck, 1986 Two-phase refrigerant void fraction Zivi, 1964

2.2. Validation

The baseline evaporator has been presented in Kristófersson et al. (2017a) and is bottom fed. The main dimensions are given in Table 2. The tube and fin materials are AISI 304 and aluminum, respectively, and the fins are wavy. The heat exchanger length was fixed to that of the baseline for the validation, thus the cooling capacity was not fixed in the validation as it was for the optimization. The volume flow rate of air was fixed to 19390 m3/hr, and was estimated by using the energy balance obtained from the measurements. The number of discretization cells was chosen to be 100.

Table 2. Baseline heat exchanger specifications Tube arrangement Inline Tube outer diameter 15.6 mm Tube rows 8 Longitudinal tube pitch 50 mm Tubes per row 18 Transverse tube pitch 50 mm Tube circuits 6 Fin spacing 12 mm Tube length 1360 mm Fin thickness 0.35 mm Tube inner diameter 14.6 mm Tube coil volume 34.5 L

. . . . . .

. . .

, . . . ,

, ,

Page 5: Multi-objective optimization of low charge liquid overfeed … · is whether the optimal design of the evaporator changes as recirculation ratio decrease or not. The objective is

8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, Ohrid, 2019

Figure 3a shows the comparison of the cooling capacity and the charge as function of the circulation ratio. The air inlet temperature was -20 °C and the refrigerant inlet and outlet saturation temperature was -30 °C. The comparison indicated a reasonable match of both the values and trends. The model predicted somewhat higher capacity as wells as charge, and it is likely due to the idealized tube circuits assumption, and possible differences in inlet subcoling. For the optimization of the heat exchanger design parameters herein, the model was considered valid. In Figure 3b, the temperature profiles of the model are shown. The temperature of the refrigerant increases in the beginning of the circuit, where subcooled liquid is heated towards saturation. As the two-phase region occurs, the temperature decreases due to pressure drop. It may be observed that the temperature difference between air and refrigerant (heat transfer driving potential) decreases with increasing recirculation due to refrigerant pressure drop. This further reduces the cooling capacity, even though the two-phase heat transfer coefficient increases due to higher refrigerant mass flux and flow.

Figure 3: Comparison of capacity and charge vs. recirculation (a) and temperature profiles vs. circuit length (b)

2.3. Optimization procedure

The optimization was performed using the multi-objective optimization algorithm in Matlab2017a. This algorithm uses a controlled, elitist genetic algorithm that favors individuals that can help increase the diversity of the population even if they have a lower fitness value. We used default options and recommended values for the population size etc. The multi-objective functions, decision variables, lower and upper bounds were:

,

, ,

0.034 , 0.034 , 0.012

0.060 , 0.060 , 0.018

Notice that we fixed the recirculation ratio ( ) to 1.25, 2, 3 and 6 and the number of tube circuits ( ) to 6, 9 and 12, respectively, to better observe and visualize the optimal geometry as function of recirculation ratio and number of tube circuits. This resulted in 4x3 optimization runs. Furthermore, the airside pressure drop was constraint to less than 55 Pa, as the baseline airside pressure drop was calculated to be 54 Pa.

3. RESULTS

Figure 4 shows the pareto fronts of the optimizations (minimizations) of area and charge for each recirculation ratio ( 1.25, 2, 3and6 and the number of tube circuits ( 6, 9and12 , respectively. The results were obtained at a fixed cooling capacity of 22.5 kW, saturation temperature of -30 °C and inlet air temperature of -20 °C. The capacity corresponds to the maximum value of the baseline capacity curve (Figure 3a). The colors of the pareto fronts in Figure 4 indicate airside pressure drop (a), tube outer diameter (b), longitudinal tube pitch (c) and transverse tube pitch (d). Furthermore, the baseline calculation is indicated by a red filled circle. Figure 5 show corresponding pareto fronts, where colors indicate longitudinal heat exchanger length (a), number of total tubes (b), gas velocity (c) and liquid velocity (d).

Ca

pa

city

, kW

Ch

arg

e, k

g

Tem

pe

ratu

re, C

,

,

Increasing recirculation

a b

Page 6: Multi-objective optimization of low charge liquid overfeed … · is whether the optimal design of the evaporator changes as recirculation ratio decrease or not. The objective is

8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, Ohrid, 2019

Figure 4: Charge vs. area pareto fronts for different recirculation ratio and number of tube circuits. Colors represent airside pressure drop (a), tube diameter (b), longitudinal tube pitch (c) and transverse tube pitch (d)

a

b

c

d

Page 7: Multi-objective optimization of low charge liquid overfeed … · is whether the optimal design of the evaporator changes as recirculation ratio decrease or not. The objective is

8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, Ohrid, 2019

Figure 5: Charge vs. area pareto fronts for different recirculation ratio and number of tube circuits. Colors represent longitudinal HX length (a), number of total tubes (b), gas velocity (c) and liquid velocity (d)

a

b

c

d

Page 8: Multi-objective optimization of low charge liquid overfeed … · is whether the optimal design of the evaporator changes as recirculation ratio decrease or not. The objective is

8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, Ohrid, 2019

The results show that a decrease in recirculation ratio from 6 to 1.25, decreases the charge significantly. This is in principle the same observation as in Figure 3a. A further reduction is possible, if the tube diameter is reduced (following the pareto front, Figure 4b), but comes with an increasing heat exchanger area (longitudinal length increase, Figure 5a) and the transverse tube pitch (Figure 4d) increase as well. If both the diameter is decreased toward 12 mm and the number of tube circuits is increased from 6 to 12, a further reduction of the charge is possible even with a smaller heat exchanger area. This is especially an important result because it indicates that the charge and the cost of the heat exchanger, assuming the heat transfer area is proportional to the heat exchanger cost, can be reduced simultaneously, although the total number of tubes increases (see Figure 5b).

The pareto fronts tend to become flat as the recirculation ratio decrease, but it is likely due to the lower bound of the longitudinal tube pitch and tube diameter (Figure 4b and 4c), which in principle could have been lower, thereby given rise to even lower heat transfer areas or lower refrigerant charge.

Interestingly, the baseline geometry is optimal at a low recirculation ratio and 6 tube circuits, and falls directly on top of the pareto front. However, as the recirculation ratio increases, the baseline geometry gets further away from the pareto front. It should be noted, that the model solves for the required longitudinal length of the heat exchanger in order to deliver the required cooling capacity. This means that the gap between 22.5 kW and the capacity curve in Figure 3a are eliminated by adjusting the longitudinal length. This is why the airside pressure drop increases as the recirculation ratio increases too (Figure 4a, text in red).

Two very important evaporator design parameters are the gas and liquid velocities, respectively, as shown in Figure 5c and 5d and calculated at the evaporator outlet with the slip ratio correlation by Zivi. Because Zivi assumes a constant slip ratio, the values in these two figures differ by the slip ratio directly, calculated to be 9. These values (Figure 5c and 5d) do not seem to decrease significantly as the recirculation ratio decreases and it ensures that oil is not retained inside the evaporator as well as a reasonable heat transfer coefficient. Moreover, general rule of thumb indicate on the order 10 m/s for gaseous ammonia (Granryd et al., 2009).

4. DISCUSSION

The presented results serves as guidelines for evaporator manufacturers and control equipment suppliers. The results show how the main geometry (tube outer diameter, longitudinal tube pitch and transverse tube pitch) change with the recirculation ratio as well as the number of tube circuits. It is difficult to point directly at a specific optimal point on the pareto front, and this is likely subjective choice depending on a choice of trade-off between charge and heat exchanger area.

Some tools exist to analytically calculate knee points of pareto fronts, which provides a compromise between the two objective functions. In the current study, the knee does not reveal exactly at the lowest recirculation ratio (1.25) and highest number of tube circuits (12), because the lower bound of the longitudinal tube pitch is reached. Choosing a point close to an imaginable knee, say 70 m2 area, corresponds to 1.20 kg charge, and

38.5 mm, 43.4 mm, 12.3 mm, 7.4 (7), 23.4 (23) and ∆ 54.7 Pa. This result show that the optimized evaporator is more compact compared to the baseline evaporator. However, it should also be noted that the proposed evaporator is more prone to have refrigerant mal-distribution.

The methodology used herein provides 12 pareto fronts for several recirculation ratio and number of tube circuits. If these values were included in a single optimization, and the genetic algorithm would converge at the lowest recirculation and the highest number of tube circuit constraints, and it would not indicate a reasonable overview of the effect of these important parameters.

5. CONCLUSION

The multi-objective optimization showed that a large reduction of refrigerant charge is possible by considering solely the recirculation ratio. If a further reduction of charge is favoured, a simultaneous reduction of the tube diameter as well as increase of tube circuits are necessary and it is even possible with decreased heat exchanger size and volume. Furthermore, the gas and liquid velocities at the outlet of the evaporator does not raise concerns about possible oil retention or weak two-phase heat transfer.

Page 9: Multi-objective optimization of low charge liquid overfeed … · is whether the optimal design of the evaporator changes as recirculation ratio decrease or not. The objective is

8th IIR Conference: Ammonia and CO2 Refrigeration Technologies, Ohrid, 2019

ACKNOWLEDGEMENTS

The research has been funded by the Danish Energy Agency (DEA) through the Energy Technology Development and Demonstration Programme (EUDP), project number: 64017-05128 - FARSevap. The funding is greatly acknowledged.

NOMENCLATURE

Roman Subscripts area (m2) gas capacitance flow (W/K) liquid diameter (m) longitudinal specific enthalpy (J/kg) outer pressure (Pa) recirculation length (m) transverse mass flow rate (kg/s) tube circuits number (-) heat flow rate (W) Greek fin spacing (m) heat transfer coefficient (W/m2K) temperature (°C) effectiveness (-) velocity (m/s) efficiency (-) tube pitch (m) quality (-)

REFERENCES

Blasius, H., 1913. Das Aehnlichkeitsgesetz bei Reibungsvorgängen in Flüssigkeiten, in: Mitteilungen Über Forschungsarbeiten Auf Dem Gebiete Des Ingenieurwesens 131. Springer, Berlin, Germany, pp. 1–41.

Fenton, D., 1999. In-tube evaporation of ammonia in smooth and enhanced tubes with and without miscible oil. ASHRAE RP-866.

Gnielinski, V., 1976. New equation for heat and mass transfer in turbulent pipe and channel flow. Int. Chem. Eng. 16, 359–368.

Granryd, E., Kungliga Tekniska högskolan. Institutionen för energiteknik, KTH Industrial Engineering and Management, Royal Institute of Technology, K.D. of E.T., 2009. Refrigerating engineering. Royal Institute of Technology, KTH, Department of Energy Technology, Division of Applied Thermodynamics and Refrigeration.

Hrnjak, P.S., Park, C.Y., 2007. In-tube heat transfer and pressure drop characteristics of pure NH3 and CO2 in refrigeration systems., in: IIR Ammonia Refrigeration Technology for Today and Tomorrow. Ohrid, Macedonia.

Kim, N., Yun, J., Webb, R., 1997. Heat transfer and friction correlations for wavy plate fin-and-tube heat exchangers. J. Heat Transfer 119, 560–567. doi:10.1115/1.2824141

Kim, Y., Kim, Y., 2005. Heat transfer characteristics of flat plate finned-tube heat exchangers with large fin pitch. Int. J. Refrig. 28, 851–858. doi:10.1016/j.ijrefrig.2005.01.013

Kristófersson, J., Vestergaard, N.P., Skovrup, M., Reinholdt, L., 2017a. Ammonia charge reduction potential in recirculating systems - Calculations, in: IIR Ammonia Refrigeration Conference. Ohrid, Macedonia, pp. 80–87. doi:10.18462/iir.nh3-co2.2017.0005

Kristófersson, J., Vestergaard, N.P., Skovrup, M., Reinholdt, L., 2017b. Ammonia charge reduction potential in recirculating systems - System benefits, in: IIR Ammonia Refrigeration Conference. Ohrid, Macedonia, pp. 80–87. doi:10.18462/iir.nh3-co2.2017.0005

Müller-Steinhagen, H., Heck, K., 1986. A Simple Friction Pressure Drop Correlation for Two-Phase Flow in Pipes. Chem. Eng. Process. Process Intensif. 20, 297–308.

Pearson, A., 2008. Refrigeration with ammonia. Int. J. Refrig. 31, 545–551. doi:10.1016/j.ijrefrig.2007.11.011

Zivi, S.M., 1964. Estimation of steady-state steam void-fraction by means of the principle of minimum entropy production. J. Heat Transf. 86, 247–252.