modularity in ups design what does it mean, what are the ... · ups system design low mttr = high...

33
Modularity in UPS Design What does it Mean, What are the Pro’s and Con’s? Mike Elms Technical Manager Uninterruptible Power Supplies Ltd www.upspower.co.uk

Upload: others

Post on 24-Aug-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Modularity in UPS Design –What does it Mean, What are the Pro’s and Con’s?Mike Elms

Technical Manager

Uninterruptible Power Supplies Ltd

www.upspower.co.uk

Page 2: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Modularity in UPS Design –What does it Mean, What are the Pro’s and Con’s?

1995 20162002 2007 2014

From Inefficient, Large-Footprint Transformer UPS…

…To Efficient, Small-Footprint Transformerless UPS

Standalone UPS Technology Innovation

Modular UPS Technology Innovation

Page 3: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Modular

Definition of Modular?

Definition of modular:

Adjective

Employing or involving a module or

modules as the basis of design or

construction

Oxford English dictionary

Page 4: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Modular

Interpretation of Definition of Modular?

100 kWRedundant

Capacity

100 kWRedundant

Capacity

33 kWRedundant

Capacity

33 kWRedundant

Capacity

33 kWRedundant

Capacity

Redundant

Capacity

200kVA N + 1

2 x 200kVA 3 x 100kVA

Page 5: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Modular

Interpretation of Definition of Modular? Bypass Switch

UPS 1

UPS 2

UPS 3

UPS 4

Page 6: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Modular

Interpretation of Definition of Modular?

Power Modules

Static Switch

Rectifier

Page 7: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Modular

Interpretation of Definition of Modular?

Static Switch

Rectifier

Power Modules

Page 8: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

UPS Evolution

UPSL Definition of Modular?

==

==

Bypass input

CriticalLoad

Rectifier input

Each module is a

complete UPS:

• IGBT rectifier and inverter

• Control logic and display

• Battery converter

• Static bypass switch

Page 9: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

UPS Evolution

UPSL Definition of Modular?

Page 10: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Definition of Modular

De-Centralised Parallel Architecture

• Dual feed rectifier / static switch

• No common static switch

• No common control logic

Rectifier

input

Output to

the

critical

load

Bypass

input

=

===

UPS module

Control logic

DISPLAY

=

===

UPS module

Control logic

DISPLAY

=

===

UPS module

Control logic

DISPLAY

Designed to distribute the UPS

Hardware and Software into

modules in order to reduce

the single points of failure

Page 11: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Selecting a UPS

“N” System

UPS Capacity = Load

N = 200 kW

=

Page 12: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Selecting a UPS

“N + 1” System

A

N+1 = 200kW + 200kW

Standalone Modular

B

Redundant

Capacity

N 1+

200kW

N+1 = 200kW + 100kW

Load = 200kW

= =100 kW

Redundant

Capacity

100 kW

Redundant

Capacity

Load = 200kW

200kW

200kW

Redundant

Capacity

100 kW

Redundant

Capacity

A = B = 200 kW

Page 13: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Selecting a UPS

“N + N” or “2N” SystemUPS Capacity = LoadUPS Capacity = Load

2N = 2 x 200kW

=

Standalone Modular

=A B

Lo

ad

=

200kW

2N = 2 x 200kW

A

N N

A = B = 200 kW

Redundant

CapacityRedundant

Capacity

100 kW

Redundant

Capacity

100 kW

Redundant

Capacity

Page 14: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Selecting a UPS

“2(N+1)” SystemUPS Capacity = Load

2(N+1) = 2(200kW + 200kW)

Standalone Modular

2(N+1) = 2(200kW + 100kW)

= =

Lo

ad

=

200kW

RedundantCapacity

RedundantCapacity

RedundantCapacity

RedundantCapacity

+N 1 +N 1

Lo

ad

=

200kW

150 kW

Redundant

Capacity

150 kW

Redundant

Capacity

150 kW

Redundant

Capacity

150 kW

Redundant

Capacity

200 kW 200 kW 200 kW 200 kW

200 kWRedundant

Capacity

100kW

200 kWRedundant

Capacity

100kW

Lo

ad

=

200kW

BA BA

A = B = 200 kW

Page 15: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

UPS System

Design Criteria

Static UPS System:

200kVA

N+1

Battery Autonomy:

15 mins

Page 16: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Standalone

Topology (2 x 200kVA)

A B

RedundantCapacity

Load = 200kVA

RedundantCapacity

A = B = 200 kVA

Bypass Switch

UPS 1

UPS 2

Page 17: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Standalone

Topology (3 x 100kVA)

A = B = C = 100 kVA

A B

RedundantCapacity

Load = 200kVA

RedundantCapacity

C

RedundantCapacity

Bypass Switch

UPS 1

UPS 2

UPS 3

Page 18: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Standalone

Topology (5 x 50kVA)

Bypass Switch

MODULAR

UPS 1

50kVA

50kVA

50kVA

50kVA

50kVALoad = 200kVA

5 X 50kVA

Page 19: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Modular

Topology (3 x 100kVA)

Load = 200kVA

3 X 100kVA

Bypass Switch

MODULAR

UPS 1

Spare

100kVA

100kVA

100kVA

Spare

Page 20: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Standalone

Battery Options 2 x 200KVA

Page 21: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Standalone

Battery Options 3 x 100KVA

Page 22: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Standalone

Separate Battery Options

Page 23: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Standalone

Separate Battery Options

Page 24: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Standalone

Battery Options Standalone

200KVA

Battery = 200KVA per unit = 400KVA in total

Standalone – 200 KVA (N+1)

200KVA 100KVA

Battery = 100KVA per unit = 300KVA in total

Standalone – 200 KVA (N+1)

100KVA 100KVA

Page 25: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Standalone

Battery Options Modular

Battery = 50KVA per unit

= 250kvA in total

Battery = 100KVA per unit = 300kvA in total

Page 26: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

200KVA N+1 Standalone

Footprint

Page 27: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

UPS System Design

Ease of Repair- Problem off Site!

Elapsed Time

10+ Hours?

Service Plan – 4 Hour Response

Spares Kit Defective UPS Identified

Diagnosis & Fix – 1, 2…6+ Hours?

Standalone

27

Service Plan – 4 Hour Response

Spare Module Defective Module Identified

Defective Module Replaced = <30 mins

HOTSWAP

<5 Hours Max

Page 28: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

UPS System Design

Rightsizing

Modularity in design allows the power protection capacity to be added when needed

to meet the existing/actual demand, instead total up front deployment.

▲ ▲ ▲ ▲ ▲start year 1 year 2 year 3 year 4

oversized power

Load curve?

Page 29: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

UPS System Design

Hot Swap Modularity

Safe Removal and/or Insertion of ModulesNo Risk to Critical LoadNo Power Down RequiredSimple Power Upgrade‘Right-Sizing’ to Match Load

Page 30: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

UPS System Design

Low MTTR = High Availability

RELIABILITY

Measure of ability for a system to run without

failures

Mean time between failures (MTBF)

Mean time to fail (MTTF)

SERVICEABILITY

The easiness and speed at which maintenance

and service can be performed

Mean time to repair / recover (MTTR)

Page 31: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

UPS System Design

Low MTTR = High Availability

10xAvailability

Improvement

Standalone 2 x 400 kW (1+1) Redundant Configuration

Modular, 4 x 100 kW (3+1) Redundant Configuration

Standalone

6nines99.9999%

Availability

Availability = MTBFUPS / (MTBFUPS + MTTRUPS)

MTBFUPS 600,000h 400,000h

MTTRUPS 6h 0.5h

Availability 99.999% (5 Nines) 99.9999% (6 Nines)

MTBF : Mean Time Between FailuresMTTR : Mean Time To Repair

Page 32: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

1. Definition of Modular UPS - De-Centralised Parallel Architecture

2. Battery Options for Standalone and Modular– Capex and Opex

3. Footprint – UPS/Switchgear/Battery System

4. Rightsizing/Scalability/Flexibility

5. Ease of Servicing/Repair = High Availability

6. Modular technology is available for large data centres now, with 100KVA

modules and 500KVA building blocks

Key Points to Take Away

Page 33: Modularity in UPS Design What does it Mean, What are the ... · UPS System Design Low MTTR = High Availability 10x Availability Improvement Standalone 2 x 400 kW (1+1) Redundant Configuration

Thank you for your time, any questions?

Visit us at Stand L31 & in

the Green Data Centre