model numbering system | da seriesthe carnes da series adjustable slot diffusers are available in...
TRANSCRIPT
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-173
MODEL NUMBERING SYSTEM | DA Series
OPTIONS1 2 3 4 5 6 7 8 9 10 11 12 13 14
D A S C 0 6 2 4 B 1 N 0 6
D - Diffuser
A - Adjustable
S - Supply without Center “T”(1 & 2 Slot Only)
M - Supply (Donn Fineline)R - Supply with Center “T”H - Return without Center “T”
(1 & 2 Slot Only)K - Return (Donn Fineline)V - Return with Center “T”
ReturnP - Combination Supply
Return (Donn Fineline)N - Combination Supply/
Return Standard T-bar
DESIGNSERIES INLET
SIZE00 - (Return
ModelsOnly)
05 - 5”06 - 6”08 - 8”10 - 10”12 - 12”
DIFFUSERLENGTH24 - 24”30 - 30”36 - 36”48 - 48”60 - 60”4N - 48”
WithCenterNotch
SLOTWIDTH
A - 3/4”B - 1”D - 1-1/2”
SLOTQUANTITY
1 - 1 Slots2 - 2 Slots3 - 3 Slots4 - 4 Slots
INSULATIONR - InsulatedN - Uninsulated
FINISHES11 - Bright White01 - White06 - Flat Black (Default)
V - Volume Control Damper
1 2 3 4 5 6 7 8 9 10 11 12
D A F B 0 6 2 4 B 1 0 6
D - Diffuser
A - Adjustable
F - Fire Damper
DESIGNSERIES INLET
SIZE06 - 6”07 - 7”08 - 8”10 - 10”
DIFFUSERLENGTH24 - 24”48 - 48”
SLOTWIDTH
A - 3/4”B - 1”C - 1-1/4”
SLOTQUANTITY1 - 1 Slots2 - 2 Slots
FINISHES11 - Bright White01 - White06 - Flat Black (Default)
UNDERWRITERS’ LABORATORIES, INC®CLASSIFIED
AIR TERMINAL UNITSFIRE RESISTANCE CLASSIFICATION
DESIGN NOS. — SEE PRODUCT CATEGORYIN UL FIRE RESISTANCE DIRECTORY
CONTROL NO. 241Y
Only Available onDAR, DAM, DAK, DAV
� DA Series — Adjustable Pattern
� Fire Slot — Adjustable Pattern
DESCRIPTIONS & SPECIFICATIONS | Adjustable Slot Diffusers
Linear, Plenum & Lt. Troffer S&R
A-174 www.carnes.com
Carnes DA Series Adjustable Slot Diffusers providean economical method to incorporate horizontal orvertical discharge for either perimeter or interior zoneapplication. Superior design makes the DA Seriesexcellent for use in VAV systems. It will hold a
horizontal pattern at less than 10% of nominal CFM(50 CFM per linear foot of slot). When set for verticaldischarge, it provides an air curtain effect along exterior walls and windows.
DESCRIPTION — DA SeriesThe Carnes DA Series Adjustable Slot Diffusers areavailable in one, two, three or four slots for exposedT-bar ceilings. Models are also available for DonnFineline type ceilings. The available slot widths are3/4”, 1” and 1-1/2”. The DA Series Slot Diffuser uti-lizes an adjustable pattern control in each slot to con-trol the direction of air discharge, either parallel withor perpendicular to the diffuser face. The adjustmentfrom the face of the diffuser allows for control in a full180° range for either right or left, horizontal or vertical. The four foot and five foot diffusers have asplit pattern control in each slot. This enables one toobtain both horizontal left and horizontal right air flowfrom a single slot unit. These units are available withinsulated or uninsulated plenums. The insulationused on the one slot units is 1/4” thick 3 pound density. The two, three and four slot units use 1/2”thick 1-1/2 pound density material. All insulation isinternally mounted fiberglass with matte faced to prevent erosion. The insulation conforms to UL 181and NFPA 90A requirements. The DA Series is available with 6”, 8”, 10” or 12” inlets. The duct collaris 1-3/4” deep for ease of flex duct connection.
DESCRIPTION — Model DAFBThe Carnes DAFB Adjustable Slot Diffusers areavailable in one or two slots for exposed T-bar ceilings. The available slot widths are 3/4”, 1” and 1-1/4”. The diffusers are constructed of 22 gaugegalvanized steel and are available in 24” and 48”lengths. The diffuser face is painted flat black. TheModel DAFB has all the features of air pattern adjustment that are available on the other DA SeriesSlots. The Model DAFB comes insulated as standardwith 1/2” thick 1-1/2 lb. density fiberglass internallymounted and mat-faced to prevent erosion. Theinstallation conforms to UL 181 and NFPA 90Arequirements. When installed in accordance with theinstallation instructions, the diffusers are UL classified with a 3 hour fire rating.
SPECIFICATIONS — DA SeriesCarnes DA Series Adjustable Slot Diffusers shall beinstalled at each location as shown on the drawings.All diffusers are to have performance ratings of CFM,static pressure, noise criteria and throw as shown onthe drawings. Each slot shall be equipped with anindividually adjustable pattern control to insure full180° air pattern. Unit sizes 48” and 60” shall have asplit pattern control so two-way throw can beobtained from a single slot unit. The diffuser shall beconstructed of 24 gauge galvanized steel with inletsize as specified. The inlet collar is to be 1-3/4” deepfor easy flex duct connection. The diffuser plenumcan be thermally and acoustically insulated with 1/4”3 lb. density fiberglass internally mounted and mattefaced to prevent erosion. The insulation must conform to UL 181 and NFPA 90A requirements.
SPECIFICATIONS — Model DAFBThe Carnes Model DAFB, UL classified firedampered slot diffuser shall be installed at eachlocation as shown on the drawings. All diffusers areto have performance ratings in CFM, static pressure,noise criteria and throw as shown on the drawings.Each slot shall be equipped with an individuallyadjustable pattern control to insure full 180° air pattern. Unit size 48” shall have a split pattern control so two-way throw can be obtained from a single slot unit. The diffuser shall be constructed of22 gauge galvanized steel with inlet size as specified. The inlet collar is to be 1-3/4” deep foreasy flex duct connection. The diffuser plenum shallbe thermally and acoustically insulated with 1/2”thick 1-1/2 lb. density fiberglass internally mountedand matte faced to prevent erosion. The insulationmust conform to UL 181 and NFPA 90A requirement.
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-175
OVERVIEW | Plenum Slot Diffusers - Supply (DA_C)
DASC
DAMC
DARC
ONE SLOT TWO SLOTS
ONE SLOT TWO SLOTS THREE SLOTS FOUR SLOTS
TWO SLOTS THREE SLOTS FOUR SLOTS
ExistingCeiling T-bar
Specification Sheet 18643 Specification Sheet 18644
Specification Sheet18801
Specification Sheet18802
Specification Sheet 18813
Specification Sheet 18800
Specification Sheet 18814
Specification Sheet 18810 Specification Sheet 18811
OVERVIEW | Plenum Slot Diffusers - Supply (DA_C)
Linear, Plenum & Lt. Troffer S&R
A-176 www.carnes.com
DASC
DAMC
DARC
Model DASC is a supply adjustable pattern T-barslot diffuser. It is compatible with most convention-al T-bar ceilings and is available with one or twoslots.Each slot has an individually adjustable patterndeflector to allow full 180 degree air pattern adjustment. Available slot widths are 3/4”, 1” and1-1/2”. The Model DASC is available in nominal24”, 30”, 36”, 48” and 60” diffuser lengths. Inletsizes 5”, 6”, 7” and 8” are round. Inlets above size8” are oval.These units are constructed of 24 gauge Galvanealed steel and are available with insulated or uninsulated plenums. Insulation for
the one slot unit is 1/4” - 3 pound density. The twoslot units have 1/2” thick 1-1/2 pound density insulation. The insulation is internally mounted andmatte faced to prevent erosion. The insulation conforms to UL 181 and NFPA 90A requirements.The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.The one slot unit is installed along side the main T-bar and one additional T-bar is required. The twoslot unit is installed straddling the main T-bar andtwo additional T-bars are required. All additional T-bars are by others.
Model DAMC is a supply adjustable pattern T-barslot diffuser. It is designed for installation in DonnFineline type grid systems and is available withone, two, three or four slots.Each slot has an individually adjustable patterndeflector to allow full 180 degrees air patternadjustment. Available slot widths are 3/4”, 1” and1-1/2”. The Model DAMC is available in nominal24”, 30”, 36” 48” and 60” diffuser lengths. Inletsizes 5”, 6”, 7” and 8” are round. Inlets above size8” are oval.These units are constructed of 24 gaugeGalvanealed steel and are available with insulatedor uninsulated plenums. Insulation for the one slot
unit is 1/4” thick 3 pound density. The two, threeand four slot models have 1/2” thick 3 pound density. The insulation is internally mounted andmatte faced to prevent erosion. The insulation conforms to UL 181 and NFPA 90A requirements.The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.The slots of the diffuser are separated by standard15/16” wide T-bar which are installed in the unitand painted number 01 white. The units areequipped with T-bar clips on each side that hookover the T-bar. All models require one additional T-bar. All additional T-bars are by others.
Model DARC is a supply adjustable pattern T-bar slot diffuser. It is compatible with most conventional T-bar ceilings and is available withtwo, three or four slots.Each slot has an individually adjustable patterndeflector to allow full 180 degree air pattern adjustment. Available slot widths are 3/4”, 1” and1-1/2”. The Model DARC is available in nominal24”, 30”, 36”, 48” and 60” diffuser lengths. Inletsizes 5”, 6”, 7” and 8” are round. Inlets above 8”are oval.These units are constructed of 24 gauge Galvanealed steel and are available with
insulated or uninsulated plenums. Insulation is 1/2”thick 1-1/2 pound density. The insulation is internally mounted and matte faced to prevent erosion. The insulation conforms to UL 181 andNFPA 90A requirements.The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.The slots of the diffuser are separated by standard15/16” T-bar which are installed in the unit andpainted number 01 white. The Model DARC isinstalled along side main T-bar and one additionalis required. All additional T-bars are by others.
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-177
OVERVIEW | Plenum Slot Diffusers - Supply (DA_B)
UNDERWRITERS’ LABORATORIES, INC ®CLASSIFIED
AIR TERMINAL UNITSFIRE RESISTANCE CLASSIFICATION
DESIGN NOS. — SEE PRODUCT CATEGORYIN UL FIRE RESISTANCE DIRECTORY
CONTROL NO. 241Y
ONE SLOT TWO SLOTSSpecification Sheet 18664 Specification Sheet 18665
23-7/8”
47-3/4”
DAFB
Unit with CenterNotch
DARC - SpecificationSheet 18812
DASC - SpecificationSheet 18680
DANC-DAPC
Specification Sheet 18808 Specification Sheet 18809
OVERVIEW | Plenum Slot Diffusers - Supply (DAFB, DANC, DAPC)
Linear, Plenum & Lt. Troffer S&R
A-178 www.carnes.com
DAFBThe Model DAFB is a UL classified adjustable pattern T-bar slot diffuser. They are available oneor two slots wide. The available slot widths are3/4”, 1” and 1-1/4”. The diffusers are constructedof 22 gauge galvanized steel and are available in24” and 48” lengths. The Model DAFB has all thefeatures of air pattern adjustment that are available on the other DA Series Diffusers. TheDAFB comes insulated as standard with 1/2” thick
- 1-1/2 pound density fiberglass internally mountedand matte-faced to prevent erosion. The insulationconforms to UL 181 and NFPA 90A requirements.The diffuser face is painted 06 flat black as standard. Number 01 white and Number 11 brightwhite are optional. When installed in accordancewith the installation instructions, the diffusers areUL classified with a three hour fire rating.
DANC — DAPCThe Models DANC and DAPC are combinationsupply/return slot diffusers. The DANC is compatible with most conventional T-bar ceilings.The DAPC is designed for installation in DonnFineline type grid systems. Both models consist ofone slot supply and one return slot.The supply slot has an adjustable pattern deflectorto allow horizontal or vertical air pattern adjustment. The return slot which is equal in widthto the supply slot returns air to ceiling Plenums.Available slot widths are 3/4”, 1” and 1-1/2”.Diffusers are available in nominal 24”, 30” 36”,48”and 60” lengths. Inlet sizes 5”, 6”, 7” and 8” onthe supply side are round. Inlets above 8” are oval.
These units are constructed of 24 gauge Galvanealed steel and are available with insulated or uninsulated plenums. The insulation is1/4” thick 3 pound density. The insulation is internally mounted and matte-faced to prevent erosion. The insulation conforms to UL 181 andNFPA 90A requirements.The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.These units are installed along side the main grid member and one additional grid member isrequired. All additional grid members are by others.
UNITS WITH CENTER NOTCHAll DA series adjustable T-bar slot diffusers, bothsupply and return models, size 48” are availablewith center notch. Some job specifications will callfor a four foot adjustable T-bar slot diffuser to be
mounted in a ceiling that has grid members on twofoot centers. The DA series when ordered with listed size 4N will accomplish this.
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-179
OVERVIEW | Plenum Slot Diffusers - Return (DAHC, DAVC, DAKC)
DAHC (No center T’s)
DAVC (Factory installed center T’s)
DAKC (Fits Donn® Fineline® ceiling, factory installed center T’s)
ONE SLOT TWO SLOTS
TWO SLOTS THREE SLOTS FOUR SLOTS
TWO SLOTS THREE SLOTS FOUR SLOTS
Specification Sheet 18803 Specification Sheet 18804
Specification Sheet 18805 Specification Sheet 18815 Specification Sheet 18816
Specification Sheet 18817 Specification Sheet 18818Specification Sheet 18807ONE SLOT
Specification Sheet 18806
OVERVIEW | Plenum Slot Diffusers - Return (DAHC, DAVC, DAKC)
Linear, Plenum & Lt. Troffer S&R
A-180 www.carnes.com
DAHC
DAVC
DAKC
Model DAHC is a return slot diffuser. It is compati-ble with most conventional T-bar ceilings. It is thematching return for the DASC supply diffuser andis available with one or two slots.Available slot widths are 3/4”, 1” and 1-1/2”. TheModel DAHC is available in nominal 24”, 30”, 36”,48” and 60” diffuser lengths.They are constructed of 24 gauge Galvanealedsteel and are available with insulated or uninsulat-ed plenums. Insulation for the one slot is 1/4” thick3 pound density. The two slot units have 1/2” thick1-1/2 pound density insulation. The insulation is
internally mounted and matte faced to prevent erosion. The insulation confirms to UL 181 andNFPA 90A requirements. The face of the unit ispainted number 06 flat black as standard. Number01 white and Number 11 bright white are optional.The one slot unit is installed along side the main T-bar and one additional T-bar is required. The twoslot is installed straddling the main T-bar and twoadditional T-bars are required. All additional T-barsare by others.
The Model DAVC is a return slot diffuser. It is com-patible with most conventional T-bar ceilings. It isthe matching return for Model DARC supply dif-fuser and is available with two, three or four slots.Available slot widths are 3/4”, 1” and 1-1/2”.The Model DAVC is available in nominal 24”, 30”,36”, 48” and 60” diffuser lengths. They are constructed of 24 gauge Galvanealed steel andare available with insulated or uninsulatedplenums. Insulation is 1/2” thick 1-1/2 pound density. The insulation is internally mounted andmatte faced to prevent erosion. The insulation confirms to UL 181 and NFPA 90A requirements.
The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.The slots of the diffuser are separated by standard15/16” T-bar which are installed in the unit andpainted number 11 bright white. The Model DAVBis installed along side the main T-bar and one additional T-bar is required. All additional T-barsare by others.
Model DAKC is a return T-bar slot diffuser. It isdesigned for installation in Donn Fineline grid systems. It is the matching return for Model DAMCsupply diffuser and is available with one, two, threeor four slots. Available slot widths are 3/4”, 1” and1-1/2”.The Model DAKC is available in nominal 24”, 30”,36”, 48” and 60” diffuser lengths. They are constructed of 24 gauge Galvanealed steel andare available with insulated or uninsulatedplenums. Insulation for the one slot unit is 1/4”thick 3 pound density. The two, three, and four slotmodels have 1/2” thick 1-1/2 pound density
insulation. The insulation is internally mounted andmatte faced to prevent erosion. The insulation conforms to UL 181 and NFPA 90A requirements. The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.The slots of the diffuser are separated by standard15/16” T-bar which are installed in the unit andpainted Number 01 white. The units are equippedwith T-bar clips on each side that hook over the T-bar. All models require one additional T-bar. Alladditional T-bars are by others.
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-181
PERFORMANCE DATA | Supply Plenum Slot Diffusers - Size 24 (DA_C, DAFB)
3/4” Flow 25 50 75 100 125 150
Slot 6”, 8” Total Pressure .015 .063 .142 .253 .397 .575
WidthInlet NC — 20 31 39 46 51
Throw 3-6-12 9-13-19 13-16-23 15-18-26 16-20-29 18-22-311” Flow 25 50 75 100 125 150
1 Slot 6”, 8” Total Pressure .009 .036 .081 .145 .230 .333Slot
WidthInlet NC — 13 24 32 38 44
Throw 2-5-11 7-11-18 12-16-22 15-18-25 16-20-28 17-21-301-1/2” Flow 50 75 100 150 200 250
Slot 6”, 8” Total Pressure .009 .042 .075 .168 .303 .475
WidthInlet NC — 15 23 35 43 49
Throw 5-9-17 8-13-20 11-16-24 17-21-29 19-23-33 21-26-373/4” Flow 50 75 100 150 200 250
Slot 6”, 8” Total Pressure .019 .042 .075 .168 .303 .475
WidthInlet NC — 15 23 35 43 49
Throw 5-9-17 8-13-20 11-16-24 17-21-29 19-23-33 21-26-371” Flow 50 75 100 150 200 250
2 Slot 6”, 8” Total Pressure .013 .029 .053 .118 .209 .334Slots
WidthInlet NC — — 16 28 36 43
Throw 3-7-16 6-11-19 9-14-22 15-20-28 19-23-32 20-25-361-1/2” Flow 100 150 200 250 300 350
Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401
WidthInlet NC — 20 28 34 39 44
Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-403/4” Flow 100 150 200 250 300 350
Slot 6”, 8” Total Pressure .046 .104 .185 .292 .418 .575
WidthInlet NC 14 25 34 40 45 50
Throw 8-13-22 14-19-27 19-23-32 20-25-36 23-28-39 24-29-411” Flow 100 150 200 250 300 350
3 Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401Slots
WidthInlet NC — 20 28 34 39 44
Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-401-1/2” Flow 150 200 250 300 400 500
Slot 8”, 10” Total Pressure .046 .082 .128 .187 .332 .521
WidthInlet NC 11 19 26 31 39 46
Throw 7-13-25 11-18-29 14-21-33 18-25-36 23-29-41 26-32-453/4” Flow 100 150 200 250 300 350
Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401
WidthInlet NC — 20 28 34 39 44
Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-401” Flow 150 200 250 300 400 500
4 Slot 8”, 10” Total Pressure .052 .094 .147 .212 .379 .592Slots
WidthInlet NC 14 22 28 34 42 48
Throw 8-14-25 12-19-30 15-22-33 20-26-36 24-29-41 26-32-461-1/2” Flow 200 300 400 500 600 700
Slot 8”, 10” Total Pressure .059 .134 .238 .374 .542 .735
WidthInlet NC 14 26 34 40 46 50
Throw 8-15-28 14-22-35 20-28-40 25-31-44 28-35-49 30-37-52
Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Total Pressure is inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts. • Throw is in feet to terminal velocities of 150-100-50 FPM for isothermal conditions.• Throws listed are for one way pattern. For two-way pattern choose the number of slots in each direction and
distribute the total air flow proportionally.
PERFORMANCE DATA | Supply Plenum Slot Diffusers - Size 30 (DA_C, DAFB)
Linear, Plenum & Lt. Troffer S&R
A-182 www.carnes.com
3/4” Flow 25 50 75 100 125 150
Slot 6”, 8” Total Pressure .010 .041 .092 .166 .262 .377
WidthInlet NC — 14 26 34 40 45
Throw 2-5-11 8-12-18 12-16-22 15-18-25 16-20-28 18-22-311” Flow 50 75 100 150 200 250
1 Slot 6”, 8” Total Pressure .025 .056 .100 .227 .405 .638Slot
WidthInlet NC — 19 27 39 47 53
Throw 6-10-17 10-14-21 13-17-24 17-21-30 20-24-34 22-27-381-1/2” Flow 50 75 100 150 200 250
Slot 6”, 8” Total Pressure .014 .032 .057 .128 .227 .363
WidthInlet NC — 10 18 30 38 44
Throw 4-8-16 7-12-20 10-15-23 16-20-28 19-23-32 20-25-363/4” Flow 50 75 100 150 200 250
Slot 6”, 8” Total Pressure .014 .032 .057 .128 .227 .363
WidthInlet NC — 10 18 30 38 44
Throw 4-8-16 7-12-20 10-15-23 16-20-28 19-23-32 20-25-361” Flow 100 150 200 250 300 350
2 Slot 6”, 8” Total Pressure .040 .091 .162 .254 .367 .504Slots
WidthInlet NC 12 23 31 38 43 48
Throw 8-13-22 12-18-27 17-22-31 20-25-35 22-27-38 24-29-411-1/2” Flow 150 200 250 300 400 500
Slot 8”, 10” Total Pressure .057 .101 .158 .228 .408 .638
WidthInlet NC 15 23 30 35 43 50
Throw 9-15-25 13-19-30 17-24-34 20-26-37 24-29-41 27-33-463/4” Flow 100 150 200 250 300 350
Slot 6”, 8” Total Pressure .036 .080 .143 .226 .326 .445
WidthInlet NC 10 21 29 36 41 45
Throw 7-12-21 11-17-27 16-22-31 20-25-35 22-27-38 23-28-401” Flow 150 200 250 300 400 500
3 Slot 8”, 10” Total Pressure .057 .101 .158 .228 .408 .638Slots
WidthInlet NC 15 23 30 35 43 50
Throw 9-15-25 13-19-30 17-24-34 20-26-37 24-29-41 27-33-461-1/2” Flow 200 300 400 500 600 700
Slot 8”, 10” Total Pressure .064 .144 .257 .404 .585 .790
WidthInlet NC 16 27 36 42 47 52
Throw 9-16-28 15-23-35 20-28-40 25-31-44 28-35-49 31-38-533/4” Flow 150 200 250 300 400 500
Slot 8”, 10” Total Pressure .057 .101 .158 .228 .408 .638
WidthInlet NC 15 23 30 35 43 50
Throw 9-15-25 13-19-30 17-24-34 20-26-37 24-29-41 27-33-461” Flow 200 300 400 500 600 700
4 Slot 8”, 10” Total Pressure .073 .163 .294 .460 .665 .915Slots
WidthInlet NC 18 29 38 44 49 54
Throw 10-17-29 17-24-36 22-28-40 26-32-45 28-35-49 31-38-531-1/2” Flow 300 400 500 600 700 800
Slot 10”, 12” Total Pressure .103 .187 .288 .413 .562 .735
WidthInlet NC 22 30 37 42 46 50
Throw 12-20-34 17-25-39 21-29-43 26-34-48 29-36-51 32-39-55
Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Total Pressure is inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts. • Throw is in feet to terminal velocities of 150-100-50 FPM for isothermal conditions.• Throws listed are for one way pattern. For two-way pattern choose the number of slots in each direction and
distribute the total air flow proportionally.
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-183
PERFORMANCE DATA | Supply Plenum Slot Diffuser - Size 36 (DA_C, DAFB)
3/4” Flow 25 50 75 100 125 150
Slot 6”, 8” Total Pressure .007 .029 .066 .118 .187 .268
WidthInlet NC — 10 21 28 35 41
Throw 2-4-10 7-11-18 12-15-22 15-18-25 16-19-27 17-21-301” Flow 50 75 100 150 200 250
1 Slot 6”, 8” Total Pressure .019 .042 .075 .168 .303 .475Slot
WidthInlet NC — 15 23 35 43 49
Throw 5-9-17 8-13-20 11-16-24 17-21-29 19-23-33 21-26-371-1/2” Flow 100 150 200 250 300 350
Slot 6”, 8” Total Pressure .046 .104 .185 .292 .418 .575
WidthInlet NC 14 25 34 40 45 50
Throw 8-13-22 14-19-27 19-23-32 20-25-36 23-28-39 24-29-413/4” Flow 100 150 200 250 300 350
Slot 6”, 8” Total Pressure .046 .104 .185 .292 .418 .575
WidthInlet NC 14 25 34 40 45 50
Throw 8-13-22 14-19-27 19-23-32 20-25-36 23-28-39 24-29-411” Flow 100 150 200 250 300 350
2 Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401Slots
WidthInlet NC — 20 28 34 39 44
Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-401-1/2” Flow 150 200 250 300 400 500
Slot 8”, 10” Total Pressure .046 .082 .128 .187 .332 .521
WidthInlet NC 11 19 26 31 39 46
Throw 7-13-25 11-18-29 14-21-33 18-25-36 23-29-41 26-32-453/4” Flow 150 200 250 300 400 500
Slot 6”, 8” Total Pressure .064 .113 .178 .258 .460 .721
WidthInlet NC 17 25 32 37 45 52
Throw 10-16-26 14-20-30 18-24-34 21-26-37 24-30-42 27-33-461” Flow 150 200 250 300 400 500
3 Slot 8”, 10” Total Pressure .046 .082 .128 .187 .332 .521Slots
WidthInlet NC 11 19 26 31 39 46
Throw 7-13-25 11-18-29 14-21-33 18-25-36 23-29-41 26-32-451-1/2” Flow 200 300 400 500 600 700
Slot 8”, 10” Total Pressure .051 .115 .206 .322 .465 .632
WidthInlet NC 12 24 32 38 44 48
Throw 7-14-28 13-21-34 18-26-39 23-31-44 27-34-48 30-37-523/4” Flow 150 200 250 300 400 500
Slot 8”, 10” Total Pressure .046 .082 .128 .187 .332 .521
WidthInlet NC 11 19 26 31 39 46
Throw 7-13-25 11-18-29 14-21-33 18-25-36 23-29-41 26-32-451” Flow 200 300 400 500 600 700
4 Slot 8”, 10” Total Pressure .059 .134 .238 .374 .542 .735Slots
WidthInlet NC 14 26 34 40 46 50
Throw 8-15-28 14-22-35 20-28-40 25-31-44 28-35-49 30-37-521-1/2” Flow 300 400 500 600 700 800
Slot 10”, 12” Total Pressure .083 .148 .232 .334 .455 .603
WidthInlet NC 19 27 33 38 43 47
Throw 10-18-33 14-23-38 19-28-43 22-32-47 28-36-51 31-38-54
Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Total Pressure is inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts. • Throw is in feet to terminal velocities of 150-100-50 FPM for isothermal conditions.• Throws listed are for one way pattern. For two-way pattern choose the number of slots in each direction and
distribute the total air flow proportionally.
PERFORMANCE DATA | Supply Plenum Slot Diffuser - Size 48 (DA_C, DAFB)
Linear, Plenum & Lt. Troffer S&R
A-184 www.carnes.com
3/4” Flow 50 75 100 150 200 250
Slot 6”, 8” Total Pressure .019 .042 .075 .168 .303 .475
WidthInlet NC — 15 23 35 43 49
Throw 5-9-17 8-13-20 11-16-24 17-21-29 19-23-33 21-26-371” Flow 50 75 100 150 200 250
1 Slot 6”, 8” Total Pressure .013 .029 .053 .118 .209 .334Slot
WidthInlet NC — — 16 28 36 43
Throw 3-7-16 6-11-19 9-14-22 15-20-28 19-23-32 20-25-361-1/2” Flow 100 150 200 250 300 350
Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401
WidthInlet NC — 20 28 34 39 44
Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-403/4” Flow 100 150 200 250 300 350
Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401
WidthInlet NC — 20 28 34 39 44
Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-401” Flow 150 200 250 300 400 500
2 Slot 8”, 10” Total Pressure .052 .094 .147 .212 .379 .592Slots
WidthInlet NC 14 22 28 34 42 48
Throw 8-14-25 12-19-30 15-22-33 20-26-36 24-29-41 26-32-461-1/2” Flow 200 300 400 500 600 700
Slot 8”, 10” Total Pressure .059 .134 .238 .374 .542 .735
WidthInlet NC 14 26 34 40 46 50
Throw 8-15-28 14-22-35 20-28-40 25-31-44 28-35-49 30-37-523/4” Flow 150 200 250 300 400 500
Slot 8”, 10” Total Pressure .046 .082 .128 .187 .332 .521
WidthInlet NC 11 19 26 31 39 46
Throw 7-13-25 11-18-29 14-21-33 18-25-36 23-29-41 26-32-451” Flow 200 300 400 500 600 700
3 Slot 8”, 10” Total Pressure .059 .134 .238 .374 .542 .735Slots
WidthInlet NC 14 26 34 40 46 50
Throw 8-15-28 14-22-35 20-28-40 25-31-44 28-35-49 30-37-521-1/2” Flow 300 400 500 600 700 800
Slot 10”, 12” Total Pressure .083 .148 .232 .334 .455 .603
WidthInlet NC 19 27 33 38 43 47
Throw 10-18-33 14-23-38 19-28-43 22-32-47 28-36-51 31-38-543/4” Flow 200 300 400 500 600 700
Slot 8”, 10” Total Pressure .059 .134 .238 .374 .542 .735
WidthInlet NC 14 26 34 40 46 50
Throw 8-15-28 14-22-35 20-28-40 25-31-44 28-35-49 30-37-521” Flow 300 400 500 600 700 800
4 Slot 10”, 12” Total Pressure .095 .168 .266 .381 .519 .682Slots
WidthInlet NC 21 29 35 40 45 49
Throw 11-19-34 16-25-39 20-29-43 25-33-47 29-36-51 32-39-551-1/2” Flow 400 500 600 700 800 900
Slot 10”, 12” Total Pressure .105 .164 .238 .322 .424 .540
WidthInlet NC 22 28 34 38 42 45
Throw 11-20-37 15-25-42 19-29-46 22-33-50 26-37-53 30-40-57
Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Total Pressure is inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts. • Throw is in feet to terminal velocities of 150-100-50 FPM for isothermal conditions.• Throws listed are for one way pattern. For two-way pattern choose the number of slots in each direction and
distribute the total air flow proportionally.
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-185
PERFORMANCE DATA | Supply Plenum Slot Diffuser - Size 60 (DA_C, DAFB)
3/4” Flow 50 75 100 150 200 250
Slot 6”, 8” Total Pressure .014 .032 .057 .128 .227 .363
WidthInlet NC — 10 18 30 38 44
Throw 4-8-16 7-12-20 10-15-23 16-20-28 19-23-32 20-25-361” Flow 100 150 200 250 300 350
1 Slot 6”, 8” Total Pressure .040 .091 .162 .254 .367 .504Slot
WidthInlet NC 12 23 31 38 43 48
Throw 8-13-22 12-18-27 17-22-31 20-25-35 22-27-38 24-29-411-1/2” Flow 150 200 250 300 400 500
Slot 8”, 10” Total Pressure .057 .101 .158 .228 .408 .638
WidthInlet NC 15 23 30 35 43 50
Throw 9-15-25 13-19-30 17-24-34 20-26-37 24-29-41 27-33-463/4” Flow 150 200 250 300 400 500
Slot 8”, 10” Total Pressure .057 .101 .158 .228 .408 .638
WidthInlet NC 15 23 30 35 43 50
Throw 9-15-25 13-19-30 17-24-34 20-26-37 24-29-41 27-33-461” Flow 200 300 400 500 600 700
2 Slot 8”, 10” Total Pressure .073 .163 .294 .460 .665 .915Slots
WidthInlet NC 18 29 38 44 49 54
Throw 10-17-29 17-24-36 22-28-40 26-32-45 28-35-49 31-38-531-1/2” Flow 300 400 500 600 700 800
Slot 10”, 12” Total Pressure .103 .187 .288 .413 .562 .735
WidthInlet NC 22 30 37 42 46 50
Throw 12-20-34 17-25-39 21-29-43 26-34-48 29-36-51 32-39-553/4” Flow 200 300 400 500 600 700
Slot 8”, 10” Total Pressure .064 .144 .257 .404 .585 .790
WidthInlet NC 16 27 36 42 47 52
Throw 9-16-28 15-23-35 20-28-40 25-31-44 28-35-49 31-38-531” Flow 300 400 500 600 700 800
3 Slot 10”, 12” Total Pressure .103 .187 .288 .413 .562 .735Slots
WidthInlet NC 22 30 37 42 46 50
Throw 12-20-34 17-25-39 21-29-43 26-34-48 29-36-51 32-39-551-1/2” Flow 400 500 600 700 800 900
Slot 10”, 12” Total Pressure .115 .180 .259 .352 .459 .588
WidthInlet NC 23 30 35 40 43 47
Throw 12-21-37 15-25-42 20-30-46 24-34-50 28-38-54 31-40-573/4” Flow 300 400 500 600 700 800
Slot 10”, 12” Total Pressure .103 .187 .288 .413 .562 .735
WidthInlet NC 22 30 37 42 46 50
Throw 12-20-34 17-25-39 21-29-43 26-34-48 29-36-51 32-39-551” Flow 300 400 500 600 700 800
4 Slot 10”, 12” Total Pressure .073 .133 .205 .296 .404 .527Slots
WidthInlet NC 17 25 31 37 41 45
Throw 8-17-33 13-22-38 17-26-42 21-31-47 26-35-50 30-38-541-1/2” Flow 500 600 700 800 900 1000
Slot 10”, 12” Total Pressure .127 .183 .252 .327 .417 .517
WidthInlet NC 25 30 35 38 42 45
Throw 12-22-41 15-26-45 19-30-49 22-34-52 25-37-56 30-42-59
Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Total Pressure is inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts. • Throw is in feet to terminal velocities of 150-100-50 FPM for isothermal conditions.• Throws listed are for one way pattern. For two-way pattern choose the number of slots in each direction and
distribute the total air flow proportionally.
PERFORMANCE DATA | Return Plenum Slot Diffuser - Size 24 (DA_C)
Linear, Plenum & Lt. Troffer S&R
A-186 www.carnes.com
3/4” Flow 31 50 75 100 125 150Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 15 24 30 351 1” Flow 42 67 100 133 167 200
Slot Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 17 26 32 371-1/2” Flow 63 100 150 200 250 300Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 18 27 33 383/4” Flow 63 100 150 200 250 300Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 18 27 33 382 1” Flow 83 133 200 267 333 400
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 20 29 35 401-1/2” Flow 125 200 300 400 500 600Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 10 21 30 36 413/4” Flow 94 150 225 300 375 450Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 20 29 35 403 1” Flow 125 200 300 400 500 600
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 11 22 31 37 421-1/2” Flow 188 300 450 600 750 900Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 12 23 32 38 433/4” Flow 125 200 300 400 500 600Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 10 21 30 36 414 1” Flow 167 267 400 533 667 800
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 12 23 32 38 431-1/2” Flow 250 400 600 800 1000 1200Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 13 24 33 39 44
Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Static pressure is negative inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts.
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-187
PERFORMANCE DATA | Return Plenum Slot Diffuser - Size 30 (DA_C)
3/4” Flow 39 63 94 125 156 188Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 15 24 30 351 1” Flow 52 83 125 167 208 250
Slot Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 17 26 32 371-1/2” Flow 78 125 188 250 313 375Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 18 27 33 383/4” Flow 78 125 188 250 313 375Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 18 27 33 382 1” Flow 104 167 250 333 417 500
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 20 29 35 401-1/2” Flow 156 250 375 500 625 750Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 10 21 30 36 413/4” Flow 117 188 281 375 469 563Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 20 29 35 403 1” Flow 156 250 375 500 625 750
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 11 22 31 37 421-1/2” Flow 234 375 563 750 938 1125Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 12 23 32 38 433/4” Flow 156 250 375 500 625 750Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 10 21 30 36 414 1” Flow 208 333 500 667 833 1000
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 12 23 32 38 431-1/2” Flow 313 500 750 1000 1250 1500Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 13 24 33 39 44
Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Static pressure is negative inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts.
PERFORMANCE DATA | Return Plenum Slot Diffuser - Size 36 (DA_C)
Linear, Plenum & Lt. Troffer S&R
A-188 www.carnes.com
3/4” Flow 47 75 113 150 188 225Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 15 24 30 351 1” Flow 63 100 150 200 250 300
Slot Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 17 26 32 371-1/2” Flow 94 150 225 300 375 450Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 18 27 33 383/4” Flow 94 150 225 300 375 450Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 18 27 33 382 1” Flow 125 200 300 400 500 600
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 20 29 35 401-1/2” Flow 188 300 450 600 750 900Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 10 21 30 36 413/4” Flow 141 225 338 450 563 675Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 20 29 35 403 1” Flow 188 300 450 600 750 900
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 11 22 31 37 421-1/2” Flow 281 450 675 900 1125 1350Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 12 23 32 38 433/4” Flow 188 300 450 600 750 900Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 10 21 30 36 414 1” Flow 250 400 600 800 1000 1200
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 12 23 32 38 431-1/2” Flow 375 600 900 1200 1500 1800Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 13 24 33 39 44
Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Static pressure is negative inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts.
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-189
PERFORMANCE DATA | Return Plenum Slot Diffuser - Size 48 (DA_C)
3/4” Flow 63 100 150 200 250 300Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 15 24 30 351 1” Flow 83 133 200 267 333 400
Slot Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 17 26 32 371-1/2” Flow 125 200 300 400 500 600Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 18 27 33 383/4” Flow 125 200 300 400 500 600Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 18 27 33 382 1” Flow 167 267 400 533 667 800
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 20 29 35 401-1/2” Flow 250 400 600 800 1000 1200Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 10 21 30 36 413/4” Flow 188 300 450 600 750 900Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 20 29 35 403 1” Flow 250 400 600 800 1000 1200
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 11 22 31 37 421-1/2” Flow 375 600 900 1200 1500 1800Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 12 23 32 38 433/4” Flow 250 400 600 800 1000 1200Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 10 21 30 36 414 1” Flow 333 533 800 1067 1333 1600
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 12 23 32 38 431-1/2” Flow 500 800 1200 1600 2000 2400Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 13 24 33 39 44
Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Static pressure is negative inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts.
PERFORMANCE DATA | Return Plenum Slot Diffuser - Size 60 (DA_C)
Linear, Plenum & Lt. Troffer S&R
A-190 www.carnes.com
3/4” Flow 78 125 188 250 313 375Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 15 24 30 351 1” Flow 104 167 250 333 417 500
Slot Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 17 26 32 371-1/2” Flow 156 250 375 500 625 750Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 18 27 33 383/4” Flow 156 250 375 500 625 750Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 18 27 33 382 1” Flow 208 333 500 667 833 1000
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 20 29 35 401-1/2” Flow 313 500 750 1000 1250 1500Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 10 21 30 36 413/4” Flow 234 375 563 750 938 1125Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — — 20 29 35 403 1” Flow 313 500 750 1000 1250 1500
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 11 22 31 37 421-1/2” Flow 469 750 1125 1500 1875 2250Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 12 23 32 38 433/4” Flow 313 500 750 1000 1250 1500Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 10 21 30 36 414 1” Flow 417 667 1000 1333 1667 2000
Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 12 23 32 38 431-1/2” Flow 625 1000 1500 2000 2500 3000Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224
Width NC — 13 24 33 39 44
Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Static pressure is negative inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts.
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-191
SUGGESTED INSTALLATION INSTRUCTIONS
Carnes DA Series Adjustable Pattern Slot Diffusersare designed for use in most standard exposed suspended grid systems. The Model DASC two slotstraddles the main T-bar and is supported by T-barson the diffuser perimeter. The Model DASC one slotis supported on one side by the main T-bar and onthe other side by an additional T-bar. Models DARCand DAMC have center T-bars as part of the unit sothey are installed in the same method as the Model
DASC one slot.In order to maintain color continuity all required additional T-bars are by others. Although support isprovided by the T-bar, additional support may beadvisable. Supply units are provided with a wire support screw in each end of the diffuser plenum.These can be used to connect wire supports from theT-bar or from structural support.
STRUCTURAL SUPPORT
T-BAR BY OTHERS
Model DAFBCarnes Model DAFB UL Classified Slot Diffuser isdesigned for use in most standard exposed T-barceilings. The two slot models straddle the main T-barand are supported by T-bars on the diffuser perimeter. One slot units are supported on one side
by the main T-bar and on the other side by an additional T-bar. In order to maintain color continuity,all required T-bars are by others. When installed inaccordance with the installation instructions, theModel DAFB is UL Classified with a 3 hour fire rating.
FEATURES | Fixed Pattern Slot Diffuser
Linear, Plenum & Lt. Troffer S&R
A-192 www.carnes.com
DFSB — Fixed Pattern Slot Diffuser — DFRB
Carnes Matched Fixed Pattern Slot Diffuser and Return Air Slot
Model DFSB — Supply Model DFRB — Return
Features
�� Eliminates drafts. Maintain horizontal air flow at levels below 10% of nominal CFM (50 CFM per
linear foot of slot.
�� The diffuser, in conjunction with return air slot, produces a high level of air induction to cause
rapid and complete mixing of room air.
�� Supplies uniform air distribution along the entire length of the slot (well within 10%).
�� Available in one, two, three or four slots in four diffuser lengths.
�� The T-bar type diffuser fits over T’s, eliminating the need to add or remove grid members.
�� Lower installation costs due to Carnes’ innovative design of the linear slot diffuser eliminating
50% of the tile cost.
�� Visual conformity. Linear slot diffusers and return air slots are identical in appearance.
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-193
INTRODUCTION & DESCRIPTION | Models DFSB and DFRB
INTRODUCTIONCarnes Models DFSB supply and DFRB return arefixed horizontal pattern slot diffusers for use in mostexposed T-bar ceilings. The DFSB will hold a hori-zontal air pattern at less than 10% of nominal CFM
(50 per linear foot of slot). The return diffuser ModelDFRB is identical in appearance to the DFSB toallow for complete continuity to ceiling appearance.
2 Slots — 2 Ways 3 Slots — 2 Ways 4 Slot — 2 Ways
1 Slot — 1 Way 2 Slots — 1 Way 3 Slots — 1 Way
DESCRIPTIONCarnes fixed horizontal pattern slot diffusers areavailable in 1, 2, 3 or 4 slot models, and can beordered in 24”, 30”, 48” and 60” lengths. The DFSBsupply and DFRB return diffusers are constructed of24 gauge painted formed galvanealed steel. Thebright white finish matches most ceiling T-bars andtile. The integral insulated plenum is of 24 gauge galvanized construction. The plenum insulation is1/4” - 3 lb. density fiberglass internally mounted andmatte faced to prevent erosion. The insulation meetsUL 181 and NFPA 90A requirements. Each supply
diffuser can be furnished with a 5”, 6”, 7” or 8” roundplenum inlet. The 10” inlet, when specified, has anoval configuration. The supply diffuser plenum inletcollar is 1-3/4” deep for easy flex duct connections.The return diffuser plenum is also insulated and hasopen sides to return air to the ceiling plenum. TheCarnes DFSB has an excellent air distribution pattern, no butterfly pattern. Slot velocity is uniformand sound levels are very low, giving you an efficientdiffuser with excellent performance.
SPECIFICATION | Models DFSB and DFRB
Linear, Plenum & Lt. Troffer S&R
A-194 www.carnes.com
SPECIFICATION GUIDELINES
Carnes Models DFSB Supply and DFRB Return, horizontal pattern slot diffusers shall be installed ateach location as shown on the drawings. All diffusersto have performance ratings of CFM, static pressure,noise criteria and throw as shown on the drawings.The diffusers shall be formed galvanealed steel con-struction in 1, 2, 3 or 4 slots.They shall be of 1 or 2
way throw patterns, with diffuser length as shown onthe drawings. The diffuser plenum shall be thermally and acoustically insulated with 1/4” thick 3lb. density fiberglass internally mounted and mattefaced to prevent erosion. The insulation shall meetUL 181 and NFPA 90A requirements.
� MODEL NUMBERING SYSTEM — Models DFSB and DFRB
OPTION1 2 3 4 5 6 7 8 9 10 11 12 13
D F S B 0 6 4 8 2 1 1 1
D - Diffuser
F - Fixed
S - Supply R - Return
DESIGNSERIES INLET
SIZE00 - (DFRA
Only)05 - 5”06 - 6”07 - 7”08 - 8”10 - 10” (Oval)
DIFFUSERLENGTH
24 - 24”30 - 30”48 - 48”60 - 60”4N - 48”
(WithCenterNotch)
SLOTQUANTITY1 - 1 Slot2 - 2 Slots3 - 3 Slots4 - 4 Slots
(2 WayOnly)
DEFLECTION PATTERN
1 - One Way2 - Two Way
FINISHES11 - Bright White (Default)01 - White06 - Black
V - Volume Control Damper
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-195
DIMENSIONAL DATA | Fixed Pattern Slot Diffuser - Supply (DFSB)
Patent 3,406,623
B
AC
EE
DD
F F
1-3/4”
TWO SLOTTWO-WAY
TWO SLOTONE-WAY
Resting OnMain-TAdjoining Tile
Cut To FitT-bar ofStandardCeiling Grid
1/4” — 3 lb.Density Insulation
Air Flow
Model (Inches)DFSB C24 - 05 9-1/424 - 06 8-3/424 - 07 8-1/424 - 08 7-3/424 - 09 6-7/824 - 10 11-7/824 - 12 11-7/824 - 14 11-7/830 - 05 12-1/430 - 06 11-3/430 - 07 11-1/430 - 08 10-3/430 - 09 9-7/830 - 10 9-1/830 - 12 14-7/830 - 14 14-7/848 - 05 21-1/448 - 06 20-3/448 - 07 20-1/448 - 08 19-3/448 - 09 18-7/848 - 10 18-1/848 - 12 16-5/848 - 14 1560 - 05 27-1/460 - 06 26-3/460 - 07 26-1/460 - 08 25-3/460 - 09 24-7/860 - 10 24-1/860 - 12 22-5/860 - 14 21
Model Nominal Slot Pattern DIMENSIONS LISTED IN INCHESDFSB Length Quantity Deflection A B D E F2411 24 1 One Way 23-13/16 23-1/8 1-7/8 2-5/8 2-7/82421 24 2 One Way 23-13/16 23-1/8 3-15/32 3-23/32 4-1/22422 24 2 Two Way 23-13/16 23-1/8 4-1/16 4-1/8 5-1/162431 24 3 One Way 23-13/16 23-1/8 5-1/16 5-5/16 6-1/162432 24 3 Two Way 23-13/16 23-1/8 5-21/32 5-29/32 6-21/322442 24 4 Two Way 23-13/16 23-1/8 7-1/4 7-1/2 8-1/43011 30 1 One Way 29-13/16 29-1/8 1-7/8 2-5/8 2-7/83021 30 2 One Way 29-13/16 29-1/8 3-15/32 3-23/32 4-1/23022 30 2 Two Way 29-13/16 29-1/8 4-1/16 4-1/8 5-1/163031 30 3 One Way 29-13/16 29-1/8 5-1/16 5-5/16 6-1/163032 30 3 Two Way 29-13/16 29-1/8 5-21/32 5-29/32 6-21/323042 30 4 Two Way 29-13/16 29-1/8 7-1/4 7-1/2 8-1/44811 48 1 One Way 47-13/16 47-1/8 1-7/8 2-5/8 2-7/84821 48 2 One Way 47-13/16 47-1/8 3-15/32 3-23/32 4-1/24822 48 2 Two Way 47-13/16 47-1/8 4-1/16 4-1/8 5-1/164831 48 3 One Way 47-13/16 47-1/8 5-1/16 5-5/16 6-1/164832 48 3 Two Way 47-13/16 47-1/8 5-21/32 5-29/32 6-21/324842 48 4 Two Way 47-13/16 47-1/8 7-1/4 7-1/2 8-1/46011 60 1 One Way 59-13/16 59-1/8 1-7/8 2-5/8 2-7/86021 60 2 One Way 59-13/16 59-1/8 3-15/32 3-23/32 4-1/26022 60 2 Two Way 59-13/16 59-1/8 4-1/16 4-1/8 5-1/166031 60 3 One Way 59-13/16 59-1/8 5-1/16 5-5/16 6-1/166032 60 3 Two Way 59-13/16 59-1/8 5-21/32 5-29/32 6-21/326042 60 4 Two Way 59-13/16 59-1/8 7-1/4 7-1/2 8-1/4
NOTES:1. Inlet size to be specified.2. Inlet sizes 5”, 6”, 7” and 8” are round. Size 9” & 10” (12” & 14” available) inlet is oval.3. Diffuser is 24 gauge formed steel, painted.4. Plenum is 24 gauge galvanized steel.5. Plenums are insulated with 1/4” thick 3 lb. density matte-faced insulation.6. Not recommended for 9/16” flat T-bar.
DIMENSIONAL DATA | Fixed Pattern Slot Diffuser - Return (DFRB)
Linear, Plenum & Lt. Troffer S&R
A-196 www.carnes.com
Patent 3,406,623
Model Nominal Slot Pattern DIMENSIONS LISTED IN INCHESDFRB Length Quantity Deflection A B C D2411 24 1 One Way 23-13/16 23-1/8 1-7/8 2-7/82421 24 2 One Way 23-13/16 23-1/8 3-15/32 4-1/22422 24 2 Two Way 23-13/16 23-1/8 4-1/16 5-1/162431 24 3 One Way 23-13/16 23-1/8 5-1/16 6-1/162432 24 3 Two Way 23-13/16 23-1/8 5-21/32 6-21/322442 24 4 Two Way 23-13/16 23-1/8 7-1/4 8-1/43011 30 1 One Way 29-13/16 29-1/8 1-7/8 2-7/83021 30 2 One Way 29-13/16 29-1/8 3-15/32 4-1/23022 30 2 Two Way 29-13/16 29-1/8 4-1/6 5-1/163031 30 3 One Way 29-13/16 29-1/8 5-1/16 6-1/163032 30 3 Two Way 29-13/16 29-1/8 5-21/32 6-21/323042 30 4 Two Way 29-13/16 29-1/8 7-1/4 8-1/44811 48 1 One Way 47-13/16 47-1/8 1-7/8 2-7/84821 48 2 One Way 47-13/16 47-1/8 3-15/32 4-1/24822 48 2 Two Way 47-13/16 47-1/8 4-1/16 5-1/164831 48 3 One Way 47-13/16 47-1/8 5-1/16 6-1/164832 48 3 Two Way 47-13/16 47-1/8 5-21/32 6-21/324842 48 4 Two Way 47-13/16 47-1/8 7-1/4 8-1/46011 60 1 One Way 59-13/16 59-1/8 1-7/8 2-7/86021 60 2 One Way 59-13/16 59-1/8 3-15/32 4-1/26022 60 2 Two Way 59-13/16 59-1/8 4-1/16 5-1/166031 60 3 One Way 59-13/16 59-1/8 5-1/16 6-1/166032 60 3 Two Way 59-13/16 59-1/8 5-21/32 6-21/326042 60 4 Two Way 59-13/16 59-1/8 7-1/4 8-1/4
NOTES:1. Diffuser is 24 gauge formed galvanealed steel painted.2. Light baffle is 24 gauge galvanized steel.3. Not recommended for 9/16” flat T-bar.
A
C C
DD
B
1”1”
Adjoining TileCut To Fit
Resting OnMain -T
T-bar PartOf StandardCeiling Grid
4” 4”
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-197
PERFORMANCE DATA | Fixed Pattern Slot Diffuser - Supply (DFSB)
Front View
Static THROW FEETPressure Distance From Discharge Device, When FPM Equals Sound Power db
Model Nominal Number Drop Octave BandDFSB Length of Slot CFM (Inches) 50 FPM 75 FPM 100 FPM 150 FPM 2 3 4 5 6 7 NC
25 .01 5 2 1 1 — — — — — — —50 .02 13 9 5 2 — — — — — — —
2411 24” 1 75 .06 19 13 10 5 — 36 32 — — — —100 .11 22 18 13 9 47 45 40 33 27 — 24125 .20 24 20 16 11 49 49 45 40 35 30 30
50 .01 12 5 3 1 — — — — — — —100 .04 22 15 10 5 — 34 — — — — —
2421 24” 2 150 .09 28 22 17 10 47 44 36 34 25 — 23200 .15 32 27 22 15 48 50 44 42 28 — 31250 .24 35 30 24 19 49 55 50 48 31 — 37
50 .01 7 4 2 1 — — — — — — —100 .03 14 9 7 4 — 30 — — — — —
2422 24” 2 150 .06 22 14 10 7 — 41 35 30 — — 20200 .15 25 19 14 10 45 48 42 40 35 — 29250 .22 28 23 18 12 50 52 48 46 42 33 35
75 .01 18 14 7 4 — — — — — — —150 .03 28 23 18 12 — 34 — — — — —
2431 24” 3 225 .07 36 28 24 18 — 44 37 33 — — 23300 .13 40 33 28 23 47 50 44 42 34 27 31375 .20 46 36 33 25 51 57 49 49 42 36 37
1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2 Slot75 .01 5 12 2 5 1 3 1 1 — — — — — — —
150 .03 13 22 9 15 5 10 2 5 — 33 — — — — —2432 24” 3 225 .07 19 28 13 22 10 17 5 10 — 42 36 — — — 22
300 .14 22 32 18 27 13 22 9 15 47 49 43 42 37 30 31375 .23 24 35 20 30 16 24 11 19 51 58 48 49 45 38 38100 .01 12 5 3 1 — — — — — — —200 .05 22 15 10 5 48 35 29 — — — —
2442 24” 4 300 .11 28 22 17 10 50 45 39 36 26 — 25400 .19 32 27 22 15 51 52 46 44 38 31 33500 .29 35 30 24 19 53 58 52 51 47 38 39
Static THROW FEETPressure Distance From Discharge Device, When FPM Equals Sound Power db
Model Nominal Number Drop Octave BandDFSB Length of Slot CFM (Inches) 50 FPM 75 FPM 100 FPM 150 FPM 2 3 4 5 6 7 NC
25 .01 5 2 1 — — — — — — — —50 .02 9 4 2 1 — — — — — — —
3011 30” 1 75 .05 20 9 5 2 — 35 28 — — — —100 .09 24 18 10 4 44 43 37 27 — — 22125 .15 27 22 13 6 47 48 43 36 27 — 26
50 .01 3 2 1 — — — — — — — —100 .02 15 6 3 2 — 30 — — — — —
3021 30” 2 150 .05 21 15 8 3 44 41 33 27 — — 20200 .09 24 19 15 6 44 47 39 36 28 — 26250 .14 27 23 18 10 50 52 46 41 34 29 32
50 .01 4 2 1 — — — — — — — —100 .02 9 6 4 2 — 27 — — — — —
3022 30” 2 150 .05 14 9 7 4 — 38 28 — — — —200 .09 17 12 9 6 44 45 37 33 28 — 24250 .14 19 15 11 8 49 50 43 40 36 28 30100 .01 12 9 5 2 — — — — — — —200 .03 23 17 12 9 — 37 29 — — — —
3031 30” 3 300 .09 28 23 19 12 44 47 40 37 27 — 27400 .16 33 27 24 17 49 53 50 48 41 37 36500 .25 37 31 26 21 52 58 56 55 52 42 44
1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2 Slot100 .01 2 3 1 2 1 1 — — — — — — — — —200 .03 9 15 4 6 2 3 1 2 — 34 — — — — —
3032 30” 3 300 .08 20 21 9 15 5 8 2 3 — 44 37 35 28 — 24400 .15 24 24 18 19 10 15 4 6 48 51 45 44 39 32 33500 .23 27 27 22 23 13 18 6 10 51 56 51 52 48 38 30150 .01 3 1 1 — — — — — — — —300 .04 12 6 3 1 — 41 34 30 — — —
3042 30” 4 450 .11 18 12 7 3 50 53 47 46 39 32 35600 .21 22 17 12 6 55 59 56 55 50 42 44750 .35 25 20 16 8 59 65 63 62 58 52 51
PERFORMANCE DATA | Fixed Pattern Slot Diffuser - Supply (DFSB)
Linear, Plenum & Lt. Troffer S&R
A-198 www.carnes.com
Front ViewStatic THROW FEET
Pressure Distance From Discharge Device, When FPM Equals Sound Power dbModel Nominal Number Drop Octave BandDFSB Length of Slot CFM (Inches) 50 FPM 75 FPM 100 FPM 150 FPM 2 3 4 5 6 7 NC
50 .01 6 3 1 1 — — — — — — —100 .04 15 10 6 3 — 29 — — — — —
4811 48” 1 150 .10 21 16 11 6 — 39 35 28 — — —200 .18 24 20 15 10 46 44 41 37 31 27 24250 .30 27 22 19 12 48 50 46 43 39 37 30100 .015 12 8 5 2 — — — — — — —200 .07 20 16 12 8 — 40 34 30 — — —
4821 48” 2 300 .16 25 20 18 12 45 49 44 44 36 29 33400 .29 29 24 20 16 49 54 50 51 46 38 39500 .44 33 26 22 18 52 59 56 57 54 46 46100 .01 8 4 2 1 — 33 — — — — —200 .05 17 11 8 4 — 36 29 — — — —
4822 48” 2 300 .12 22 17 13 8 46 46 41 39 31 — 28400 .24 25 21 17 11 49 52 48 47 43 34 36500 .38 28 23 20 14 52 56 53 54 51 45 43150 .01 20 13 8 4 — — — — — — —300 .07 28 22 20 13 — 40 33 — — — —
4831 48” 3 450 .15 35 28 24 20 45 50 44 44 37 28 33600 .21 40 33 28 22 51 56 52 54 48 40 43750 .40 45 36 31 25 56 61 58 62 57 49 51
1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2 Slot150 .01 6 12 3 8 1 5 1 2 — — — — — — —300 .05 15 20 10 16 6 12 3 8 — 38 30 — — — —
4832 48” 3 450 .13 21 25 16 20 11 18 6 12 44 50 42 42 34 — 31600 .23 24 29 20 24 15 20 10 16 51 55 52 51 45 38 39750 .36 27 33 22 26 19 22 12 18 56 62 59 58 54 47 47200 .015 12 8 5 2 — — — — — — —400 .07 20 16 12 8 — 43 36 35 26 25 24
4842 48” 4 600 .17 25 20 18 12 47 52 49 49 42 35 37800 .32 29 24 20 16 52 57 55 56 52 45 45
1000 .50 33 26 22 18 60 62 62 62 60 53 51
Static THROW FEETPressure Distance From Discharge Device, When FPM Equals Sound Power db
Model Nominal Number Drop Octave BandDFSB Length of Slot CFM (Inches) 50 FPM 75 FPM 100 FPM 150 FPM 2 3 4 5 6 7 NC
50 .01 4 2 1 — — — — — — — —100 .04 12 8 4 2 — 29 — — — — —
6011 60” 1 150 .10 15 12 9 4 — 39 33 31 — — 20200 .18 17 14 12 8 — 47 39 38 34 27 26250 .26 19 16 14 10 46 50 44 42 42 39 31100 .01 9 6 3 2 37 30 — — — — —200 .04 15 13 9 6 39 41 30 27 — — —
6021 60” 2 300 .04 19 15 13 9 43 48 42 40 33 — 29400 .20 22 17 15 13 47 53 50 49 44 34 37500 .31 25 20 16 14 52 57 56 55 53 48 44100 .01 3 2 1 — — — — — — — —200 .05 10 6 3 2 — 37 28 — — — —
6022 60” 2 300 .10 15 10 3 2 44 46 39 36 29 — 24400 .18 18 14 10 6 48 52 48 45 41 32 32500 .28 19 16 13 9 53 57 53 51 48 43 39150 .01 10 5 3 1 44 — — — — — —300 .04 24 17 10 5 46 39 30 30 — — —
6031 60” 3 450 .10 30 24 19 10 47 49 42 42 35 — 31600 .18 33 28 24 17 50 54 50 51 46 35 39750 .33 38 30 26 21 53 61 56 56 54 45 45
1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2 Slot150 .01 4 7 2 6 1 3 — 2 — — — — — — —300 .04 12 15 8 13 4 9 2 6 — 37 27 24 — — —
6032 60” 3 450 .10 15 19 12 15 9 13 4 9 44 47 39 39 31 — 28600 .18 17 22 14 17 12 15 8 13 50 52 47 48 41 35 36750 .27 19 25 16 20 14 16 10 14 58 58 53 53 49 43 42200 .01 9 6 3 2 — — — — — — —400 .04 15 13 9 6 48 35 31 32 — — —
6042 60” 4 600 .10 19 15 13 9 53 51 46 47 36 30 32800 .20 22 17 15 13 57 59 51 52 48 40 40
1000 .34 25 20 16 14 60 65 57 58 57 48 48
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-199
PERFORMANCE DATA | Return Slot Diffuser (DFRB)
Sound Power db Model Nominal Number Static Pressure Octave BandDFRB Length of Slots CFM Drop (Inches) 2 3 4 5 6 7 NC
25 .01 — — — — — — —50 .06 — 31 27 24 — — —2411 24” 175 .11 40 39 36 34 32 — 23
100 .24 46 45 43 42 41 32 3250 .01 — 25 — — — — L
100 .07 — 34 30 27 — — L2421 24” 2150 .17 43 42 39 37 35 26 26200 .33 49 48 47 45 44 35 35
50 .01 — — — — — — —100 .05 — 30 22 — — — —2422 24” 2150 .11 43 41 34 31 30 23 21200 .25 47 48 44 40 38 31 29
75 .01 — 24 — — — — L150 .05 — 43 29 26 — — L2431 24” 3225 .12 45 44 38 35 35 27 26300 .23 48 46 45 42 43 33 34
75 .01 — — — — — — L150 .05 — 37 28 25 — — L2432 24” 3225 .12 46 45 39 35 31 27 23300 .24 49 51 47 43 39 31 32100 .01 — 24 — — — — L200 .05 — 33 25 — — — L2442 24” 4300 .13 46 44 37 34 33 26 24400 .25 50 51 47 43 41 34 32
Front View
Sound Power db Model Nominal Number Static Pressure Octave BandDFRB Length of Slots CFM Drop (Inches) 2 3 4 5 6 7 NC
30 .01 — — — — — — L65 .06 — 31 27 24 — — L3011 30” 195 .11 — 41 37 35 33 — 25
125 .24 47 46 44 43 42 33 3365 .01 — 26 — — — — L
125 .07 — 35 31 28 — — L3021 30” 2190 .17 44 42 39 37 35 26 26250 .23 50 49 48 46 45 36 36
65 .01 — — — — — — L125 .05 — 31 23 — — — L3022 30” 2190 .13 44 42 35 32 31 24 21250 .25 48 49 45 50 39 32 29
95 .01 — 25 — — — — L190 .05 — 44 29 26 — — L3031 30” 3280 .12 46 45 39 36 36 27 27375 .23 49 47 46 43 44 34 35
95 .01 — — — — — — L190 .05 — 37 29 26 — — L3032 30” 3280 .12 47 46 40 36 32 28 24375 .24 50 52 48 44 40 32 33125 .01 — 25 — — — — L250 .05 — 34 26 — — — L3042 30” 4375 .13 47 45 38 35 34 27 25500 .25 51 52 48 44 42 35 33
PERFORMANCE DATA | Return Slot Diffuser (DFRB)
Linear, Plenum & Lt. Troffer S&R
A-200 www.carnes.com
Sound Power db Model Nominal Number Static Pressure Octave Band
Number Length of Slots CFM Drop (Inches) 2 3 4 5 6 7 NC50 .01 — — — — — — —
100 .06 — 34 27 24 — — —4811 48” 1150 .11 43 39 36 34 32 — 26200 .24 49 48 46 45 44 35 35100 .01 — — — — — — —200 .06 52 45 36 30 27 25 244821 48” 2300 .15 56 51 46 41 35 28 37400 .26 60 62 55 50 44 34 42100 .01 — — — — — — —200 .06 — 33 25 — — — —4822 48” 2300 .14 46 44 37 34 33 26 24400 .26 50 51 47 43 41 34 32150 .02 — — — — — — —300 .09 52 44 38 31 24 — 234831 48” 3450 .19 58 56 48 45 37 27 36600 .32 61 66 55 51 49 38 47150 .01 — — — — — — —300 .06 50 42 41 25 — — 254832 48” 3450 .15 54 56 44 39 31 — 36600 .25 64 63 54 48 40 31 43200 .025 — 28 — — — — —400 .09 55 46 35 31 27 26 274842 48” 4600 .19 58 58 49 45 41 31 38800 .31 64 65 58 53 45 37 46
Front View
Sound Power db Model Nominal Number Static Pressure Octave Band
Number Length of Slots CFM Drop (Inches) 2 3 4 5 6 7 NC63 .01 — — — — — — —
125 .06 — 35 28 25 — — —6011 60” 1190 .11 44 40 37 35 33 — 27250 .24 50 49 47 45 45 46 36125 .01 — — — — — — —250 .07 53 46 37 31 28 26 256021 60” 2375 .15 57 58 47 42 36 29 38500 .28 61 63 56 51 45 35 43125 .01 — — — — — — —250 .06 — 34 26 — — — —6022 60” 2375 .14 47 45 38 35 34 27 25500 .26 51 52 48 46 42 35 33190 .02 — — — — — — —375 .09 53 45 39 32 25 — 246031 60” 3560 .19 59 57 49 46 38 28 37750 .32 62 67 56 52 50 39 48190 .01 — — — — — — L375 .06 51 43 42 26 — — 266032 60” 3560 .15 55 57 45 40 31 — 37750 .25 65 64 55 49 41 32 44250 .03 — 28 — — — — L500 .09 56 47 36 33 28 27 286042 60” 4750 .19 59 59 50 46 42 32 39
1000 .31 65 66 59 54 46 38 47
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-201
SUGGESTED INSTALLATION INSTRUCTIONS | Models DFSB & DFRB
Carnes Fixed Pattern Slot Diffusers Models DFSBSupply and DFRB Return are designed to be supported by the T-bar ceiling grid system. The diffuser utilizes the “T” for control of the air distribution pattern. If T-bars with a face dimension ofless than 15/16” are used, there may be dumping ofsupply air at low CFM’s.
The two way blow units straddle the main T-bar andare either wired to the T-bars that run perpendicularto the diffuser at each end or wired to structural supports above. The methods are shown below.
One way blow units are set along side the T-bar withthe air pattern blowing away from the T-bar. The oneway blow units are supported in the same manner asthe two way units.
After the slot diffusers are installed the support tilemust be trimmed and laid on the edge of the louverto fill out the opening. No additional T-bars arerequired.
STRUCTURAL SUPPORT
ONE WAY BLOWTWO WAY BLOW
FIXED PATTERN SLOT DIFFUSERS | Models DFCA & DFDA
Linear, Plenum & Lt. Troffer S&R
A-202 www.carnes.com
Features� High induction horizontal air flow.
� Center down blow provides a vertical air pattern for exterior walls or glass.
� Supply/Return combination diffuser allows room air to be returned to ceiling plenums.
� Choice of 24”, 36”, 48” and 60” sizes.
� Choice of insulated or uninsulated units.
� Constructed of 24 gauge galvanealed steel. Deflector vane is extruded aluminum.
� Exposed surfaces painted flat black.
INLET SIZE06 - 6” Oval07 - 7” Oval08 - 8” Oval10 - 10” Oval12 - 12” Oval
INSULATIONN - UninsulatedR - Internal
Insulation
D - Down Blow(Sizes 36”, 48” and 60” Only)(Only Available on Model DFCA
FINISH06 - Flat Black (Default)11 - Bright White 01 - White
OPTIONS 1 2 3 4 5 6 7 8 9 10 11
D F C A 0 8 4 8 N 0 6
D - Diffuser
F - FixedPattern
DESIGNSERIES
C - Supply T-barDiffuser
D - CombinationSupply/ReturnDiffuser
DIFFUSERLENGTH24 - 24”36 - 36”48 - 48”60 - 60” V - Volume
ControlDamper
� MODEL NUMBERING SYSTEM —FIXED PATTERN - Models DFCA & DFDA
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-203
DIMENSIONAL DATA | Fixed Pattern Slot Diffuser (DFCA)
MODEL DFCA — PRODUCT DESCRIPTION
MODEL DFCA — PERFORMANCE DATA
A
11/2”
A =11/16”
7/8”3/8”
Vane Detail(T-bar by Others)
INLET DIFFUSERSIZE HEIGHT (H)
6 8”8, 10 9”
Model DFCA is a one slot, one way, fixed pattern T-bar slotdiffuser. The Model DFCA is an excellent device forperimeter application and performs equally well for con-stant volume or variable air volume application. The ModelDFCA is constructed of zinc coated steel with an extrudedaluminum fixed air pattern deflector. The exposed face ofthe unit is painted No. 06 flat black as standard. The unitface can be painted No. 11 bright white. Units are available
in nominal 24”, 36”, 48” and 60” lengths. Standard inletsizes are 6”, 8” 10” and 12”. All inlets are oval construction.The Model DFCA is uninsulated as standard, but availablewith 1/2” black matte internal insulation.An optional inlet mounted volume control damper is alsoavailable.
CFM 60 80 100 120 140 160 180 20024” Ps .02 .03 .06 .08 .11 .14 .19 .23
LENGTH Throw 13 16 19 22 24 25 26 29NC (20) (20) (20) (20) (20) 22 26 29
CFM 90 120 150 180 210 240 270 30036” Ps .03 .04 .07 .10 .14 .18 .23 .29
LENGTH Throw 13 16 20 22 24 26 27 29NC (20) (20) (20) 22 25 29 32 35
CFM 120 160 200 240 280 320 360 40048” Ps .03 .05 .09 .12 .17 .22 .29 .36
LENGTH Throw 11 14 17 19 21 23 24 25NC (20) (20) 21 26 29 33 37 40
CFM 150 200 250 300 350 400 450 50060” Ps .03 .05 .10 .13 .18 .24 .31 .39
LENGTH Throw 9 11 14 15 17 18 19 20NC (20) 21 25 29 33 37 41 44
Ps — Static Pressure in inches of waterThrow — Distances in feet to terminal velocity of 50 fpm.NC — Noise Criteria based on 10 db room absorption.
DIMENSIONS
Size -1/4”
23/4”
H
DIMENSIONAL DATA | Pattern Slot Diffuser w/Option D (DFCA)
Linear, Plenum & Lt. Troffer S&R
A-204 www.carnes.com
MODEL DFCA w/OPTION D — PRODUCT DESCRIPTION
MODEL DFCA w/OPTION D — PERFORMANCE DATA
B
BA
A
1-1/2”
2-3/4”
2-13/16”
1-1/2”
11/16”
Vane Detail(T-bar by Others)
INLET DIFFUSERSIZE HEIGHT (H)
6 8”8, 10 9”
Model DFCA with Option “D” has all the features of thestandard Model DFCA with the addition of a 12” long downblow section located in the center of the diffuser. With thedown blow option air is delivered both horizontally and vertically. Both end sections of the diffuser deliver entering
air in a horizontal air pattern effective distribution through-out the space. The vertical air pattern delivered by thedown blow section projects entering air down over the surface of a wall or window. The Model DFCA with option“D” is available in nominal 36”, 48” and 60” lengths.
CFM 90 120 150 180 210 240 270 30036” Ps .03 .06 .09 .13 .18 .23 .29 .35
LENGTH Throw H 11 16 19 22 24 26 27 29Throw V 4 5 5 6 6 7 7 8
NC 20 25 31 35 40 43 45 48CFM 120 160 200 240 280 320 360 400
48” Ps .03 .06 .09 .13 .18 .23 .29 .36LENGTH Throw H 11 16 19 22 25 26 27 29
Throw V 4 5 5 6 6 7 7 8NC (20) 24 30 33 39 42 45 48
CFM 150 200 250 300 350 400 450 50060” Ps .03 .06 .09 .14 .19 .24 .30 .38
LENGTH Throw H 11 16 19 21 24 25 26 27Throw V 4 5 5 6 6 7 7 8
NC (20) 24 30 33 38 42 44 47
Ps — Static Pressure in inches of waterThrow — Distances in feet to terminal velocity of 50 fpm.NC — Noise Criteria based on 10 db room absorption.Vertical throw values are based on standard 12” long down blow slot and 3/8” width setting.
DIMENSIONS
H H
Size -1/4”
View A-A View B-B
Linea
r, Plen
um &
Lt. T
roffer
S&R
www.carnes.com A-205
DIMENSIONAL DATA | Fixed Pattern Slot Diffuser (DFDA)
MODEL DFDA — PRODUCT DESCRIPTION
MODEL DFDA — PERFORMANCE DATA
Vane Detail(T-bar by Others)
INLET DIFFUSERSIZE HEIGHT (H)
6 8”8, 10 9”
Model DFDA is a combination supply/return T-bar slot diffuser. Itcombines the Model DFCA supply fixed pattern one slot diffuserwith an integral return air slot. The Model DFDA offers an excellent and cost effective method to supply conditioned air tothe space and return air to the ceiling plenum.The Model DFDA is constructed of zinc coated steel on the supply and return sections. The air slot has an extruded aluminum fixed air pattern deflector. The exposed face of the unit
is painted No. 06 flat black as standard. The unit face can bepainted No. 11 bright white.Units are available in nominal 24”, 36” 48” and 60” lengths.Standard inlet sizes are 6”, 8”, 10” and 12”. All inlets are oval construction.The Model DFDA is uninsulated as standard, but is available with1/2” thick black matte internal insulation. An optional inlet mounted volume control damper is available on the supply inlet.
CFM 60 80 100 120 140 160 180 20024” Ps .02 .03 .06 .08 .11 .14 .19 .23
LENGTH Throw 13 16 19 22 24 25 26 29NC (20) (20) (20) (20) (20) 22 26 29
CFM 90 120 150 180 210 240 270 30036” Ps .03 .04 .07 .10 .14 .18 .23 .29
LENGTH Throw 13 16 20 22 24 26 27 29NC (20) (20) (20) 22 25 29 32 35
CFM 120 160 200 240 280 320 360 40048” Ps .03 .05 .09 .12 .17 .22 .29 .36
LENGTH Throw 11 14 17 19 21 23 24 25NC (20) (20) 21 26 29 33 37 40
CFM 150 200 250 300 350 400 450 50060” Ps .03 .05 .10 .13 .18 .24 .31 .39
LENGTH Throw 9 11 14 15 17 18 19 20NC (20) 21 25 29 33 37 41 44
Ps — Static Pressure in inches of waterThrow — Distances in feet to terminal velocity of 50 fpm.NC — Noise Criteria based on 10 db room absorption.Vertical throw values are based on standard 12” long down blow slot and 3/8” width setting.
Internal Insulation(Optional)
CFM PER FOOT 30 40 50 60 70 80 90 100NEGATIVE Ps .01 .02 .03 .04 .06 .07 .09 .11
RETURN SLOT PERFORMANCE
1-1/2”
11/16”
5-1/4”
2-3/4”