model numbering system | da seriesthe carnes da series adjustable slot diffusers are available in...

33
Linear, Plenum & Lt. Troffer S&R www.carnes.com A-173 MODEL NUMBERING SYSTEM | DA Series OPTIONS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 D A S C 0 6 2 4 B 1 N 0 6 D - Diffuser A - Adjustable S - Supply without Center “T” (1 & 2 Slot Only) M - Supply (Donn Fineline) R - Supply with Center “T” H - Return without Center “T” (1 & 2 Slot Only) K - Return (Donn Fineline) V - Return with Center “T” Return P - Combination Supply Return (Donn Fineline) N - Combination Supply/ Return Standard T-bar DESIGN SERIES INLET SIZE 00 - (Return Models Only) 05 - 5” 06 - 6” 08 - 8” 10 - 10” 12 - 12” DIFFUSER LENGTH 24 - 24” 30 - 30” 36 - 36” 48 - 48” 60 - 60” 4N - 48” With Center Notch SLOT WIDTH A - 3/4” B - 1” D - 1-1/2” SLOT QUANTITY 1 - 1 Slots 2 - 2 Slots 3 - 3 Slots 4 - 4 Slots INSULATION R - Insulated N - Uninsulated FINISHES 11 - Bright White 01 - White 06 - Flat Black (Default) V - Volume Control Damper 1 2 3 4 5 6 7 8 9 10 11 12 D A F B 0 6 2 4 B 1 0 6 D - Diffuser A - Adjustable F - Fire Damper DESIGN SERIES INLET SIZE 06 - 6” 07 - 7” 08 - 8” 10 - 10” DIFFUSER LENGTH 24 - 24” 48 - 48” SLOT WIDTH A - 3/4” B - 1” C - 1-1/4” SLOT QUANTITY 1 - 1 Slots 2 - 2 Slots FINISHES 11 - Bright White 01 - White 06 - Flat Black (Default) UNDERWRITERS’ LABORATORIES, INC® CLASSIFIED AIR TERMINAL UNITS FIRE RESISTANCE CLASSIFICATION DESIGN NOS. — SEE PRODUCT CATEGORY IN UL FIRE RESISTANCE DIRECTORY CONTROL NO. 241Y Only Available on DAR, DAM, DAK, DAV t DA Series — Adjustable Pattern t Fire Slot — Adjustable Pattern

Upload: others

Post on 06-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-173

MODEL NUMBERING SYSTEM | DA Series

OPTIONS1 2 3 4 5 6 7 8 9 10 11 12 13 14

D A S C 0 6 2 4 B 1 N 0 6

D - Diffuser

A - Adjustable

S - Supply without Center “T”(1 & 2 Slot Only)

M - Supply (Donn Fineline)R - Supply with Center “T”H - Return without Center “T”

(1 & 2 Slot Only)K - Return (Donn Fineline)V - Return with Center “T”

ReturnP - Combination Supply

Return (Donn Fineline)N - Combination Supply/

Return Standard T-bar

DESIGNSERIES INLET

SIZE00 - (Return

ModelsOnly)

05 - 5”06 - 6”08 - 8”10 - 10”12 - 12”

DIFFUSERLENGTH24 - 24”30 - 30”36 - 36”48 - 48”60 - 60”4N - 48”

WithCenterNotch

SLOTWIDTH

A - 3/4”B - 1”D - 1-1/2”

SLOTQUANTITY

1 - 1 Slots2 - 2 Slots3 - 3 Slots4 - 4 Slots

INSULATIONR - InsulatedN - Uninsulated

FINISHES11 - Bright White01 - White06 - Flat Black (Default)

V - Volume Control Damper

1 2 3 4 5 6 7 8 9 10 11 12

D A F B 0 6 2 4 B 1 0 6

D - Diffuser

A - Adjustable

F - Fire Damper

DESIGNSERIES INLET

SIZE06 - 6”07 - 7”08 - 8”10 - 10”

DIFFUSERLENGTH24 - 24”48 - 48”

SLOTWIDTH

A - 3/4”B - 1”C - 1-1/4”

SLOTQUANTITY1 - 1 Slots2 - 2 Slots

FINISHES11 - Bright White01 - White06 - Flat Black (Default)

UNDERWRITERS’ LABORATORIES, INC®CLASSIFIED

AIR TERMINAL UNITSFIRE RESISTANCE CLASSIFICATION

DESIGN NOS. — SEE PRODUCT CATEGORYIN UL FIRE RESISTANCE DIRECTORY

CONTROL NO. 241Y

Only Available onDAR, DAM, DAK, DAV

� DA Series — Adjustable Pattern

� Fire Slot — Adjustable Pattern

Page 2: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

DESCRIPTIONS & SPECIFICATIONS | Adjustable Slot Diffusers

Linear, Plenum & Lt. Troffer S&R

A-174 www.carnes.com

Carnes DA Series Adjustable Slot Diffusers providean economical method to incorporate horizontal orvertical discharge for either perimeter or interior zoneapplication. Superior design makes the DA Seriesexcellent for use in VAV systems. It will hold a

horizontal pattern at less than 10% of nominal CFM(50 CFM per linear foot of slot). When set for verticaldischarge, it provides an air curtain effect along exterior walls and windows.

DESCRIPTION — DA SeriesThe Carnes DA Series Adjustable Slot Diffusers areavailable in one, two, three or four slots for exposedT-bar ceilings. Models are also available for DonnFineline type ceilings. The available slot widths are3/4”, 1” and 1-1/2”. The DA Series Slot Diffuser uti-lizes an adjustable pattern control in each slot to con-trol the direction of air discharge, either parallel withor perpendicular to the diffuser face. The adjustmentfrom the face of the diffuser allows for control in a full180° range for either right or left, horizontal or vertical. The four foot and five foot diffusers have asplit pattern control in each slot. This enables one toobtain both horizontal left and horizontal right air flowfrom a single slot unit. These units are available withinsulated or uninsulated plenums. The insulationused on the one slot units is 1/4” thick 3 pound density. The two, three and four slot units use 1/2”thick 1-1/2 pound density material. All insulation isinternally mounted fiberglass with matte faced to prevent erosion. The insulation conforms to UL 181and NFPA 90A requirements. The DA Series is available with 6”, 8”, 10” or 12” inlets. The duct collaris 1-3/4” deep for ease of flex duct connection.

DESCRIPTION — Model DAFBThe Carnes DAFB Adjustable Slot Diffusers areavailable in one or two slots for exposed T-bar ceilings. The available slot widths are 3/4”, 1” and 1-1/4”. The diffusers are constructed of 22 gaugegalvanized steel and are available in 24” and 48”lengths. The diffuser face is painted flat black. TheModel DAFB has all the features of air pattern adjustment that are available on the other DA SeriesSlots. The Model DAFB comes insulated as standardwith 1/2” thick 1-1/2 lb. density fiberglass internallymounted and mat-faced to prevent erosion. Theinstallation conforms to UL 181 and NFPA 90Arequirements. When installed in accordance with theinstallation instructions, the diffusers are UL classified with a 3 hour fire rating.

SPECIFICATIONS — DA SeriesCarnes DA Series Adjustable Slot Diffusers shall beinstalled at each location as shown on the drawings.All diffusers are to have performance ratings of CFM,static pressure, noise criteria and throw as shown onthe drawings. Each slot shall be equipped with anindividually adjustable pattern control to insure full180° air pattern. Unit sizes 48” and 60” shall have asplit pattern control so two-way throw can beobtained from a single slot unit. The diffuser shall beconstructed of 24 gauge galvanized steel with inletsize as specified. The inlet collar is to be 1-3/4” deepfor easy flex duct connection. The diffuser plenumcan be thermally and acoustically insulated with 1/4”3 lb. density fiberglass internally mounted and mattefaced to prevent erosion. The insulation must conform to UL 181 and NFPA 90A requirements.

SPECIFICATIONS — Model DAFBThe Carnes Model DAFB, UL classified firedampered slot diffuser shall be installed at eachlocation as shown on the drawings. All diffusers areto have performance ratings in CFM, static pressure,noise criteria and throw as shown on the drawings.Each slot shall be equipped with an individuallyadjustable pattern control to insure full 180° air pattern. Unit size 48” shall have a split pattern control so two-way throw can be obtained from a single slot unit. The diffuser shall be constructed of22 gauge galvanized steel with inlet size as specified. The inlet collar is to be 1-3/4” deep foreasy flex duct connection. The diffuser plenum shallbe thermally and acoustically insulated with 1/2”thick 1-1/2 lb. density fiberglass internally mountedand matte faced to prevent erosion. The insulationmust conform to UL 181 and NFPA 90A requirement.

Page 3: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-175

OVERVIEW | Plenum Slot Diffusers - Supply (DA_C)

DASC

DAMC

DARC

ONE SLOT TWO SLOTS

ONE SLOT TWO SLOTS THREE SLOTS FOUR SLOTS

TWO SLOTS THREE SLOTS FOUR SLOTS

ExistingCeiling T-bar

Specification Sheet 18643 Specification Sheet 18644

Specification Sheet18801

Specification Sheet18802

Specification Sheet 18813

Specification Sheet 18800

Specification Sheet 18814

Specification Sheet 18810 Specification Sheet 18811

Page 4: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

OVERVIEW | Plenum Slot Diffusers - Supply (DA_C)

Linear, Plenum & Lt. Troffer S&R

A-176 www.carnes.com

DASC

DAMC

DARC

Model DASC is a supply adjustable pattern T-barslot diffuser. It is compatible with most convention-al T-bar ceilings and is available with one or twoslots.Each slot has an individually adjustable patterndeflector to allow full 180 degree air pattern adjustment. Available slot widths are 3/4”, 1” and1-1/2”. The Model DASC is available in nominal24”, 30”, 36”, 48” and 60” diffuser lengths. Inletsizes 5”, 6”, 7” and 8” are round. Inlets above size8” are oval.These units are constructed of 24 gauge Galvanealed steel and are available with insulated or uninsulated plenums. Insulation for

the one slot unit is 1/4” - 3 pound density. The twoslot units have 1/2” thick 1-1/2 pound density insulation. The insulation is internally mounted andmatte faced to prevent erosion. The insulation conforms to UL 181 and NFPA 90A requirements.The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.The one slot unit is installed along side the main T-bar and one additional T-bar is required. The twoslot unit is installed straddling the main T-bar andtwo additional T-bars are required. All additional T-bars are by others.

Model DAMC is a supply adjustable pattern T-barslot diffuser. It is designed for installation in DonnFineline type grid systems and is available withone, two, three or four slots.Each slot has an individually adjustable patterndeflector to allow full 180 degrees air patternadjustment. Available slot widths are 3/4”, 1” and1-1/2”. The Model DAMC is available in nominal24”, 30”, 36” 48” and 60” diffuser lengths. Inletsizes 5”, 6”, 7” and 8” are round. Inlets above size8” are oval.These units are constructed of 24 gaugeGalvanealed steel and are available with insulatedor uninsulated plenums. Insulation for the one slot

unit is 1/4” thick 3 pound density. The two, threeand four slot models have 1/2” thick 3 pound density. The insulation is internally mounted andmatte faced to prevent erosion. The insulation conforms to UL 181 and NFPA 90A requirements.The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.The slots of the diffuser are separated by standard15/16” wide T-bar which are installed in the unitand painted number 01 white. The units areequipped with T-bar clips on each side that hookover the T-bar. All models require one additional T-bar. All additional T-bars are by others.

Model DARC is a supply adjustable pattern T-bar slot diffuser. It is compatible with most conventional T-bar ceilings and is available withtwo, three or four slots.Each slot has an individually adjustable patterndeflector to allow full 180 degree air pattern adjustment. Available slot widths are 3/4”, 1” and1-1/2”. The Model DARC is available in nominal24”, 30”, 36”, 48” and 60” diffuser lengths. Inletsizes 5”, 6”, 7” and 8” are round. Inlets above 8”are oval.These units are constructed of 24 gauge Galvanealed steel and are available with

insulated or uninsulated plenums. Insulation is 1/2”thick 1-1/2 pound density. The insulation is internally mounted and matte faced to prevent erosion. The insulation conforms to UL 181 andNFPA 90A requirements.The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.The slots of the diffuser are separated by standard15/16” T-bar which are installed in the unit andpainted number 01 white. The Model DARC isinstalled along side main T-bar and one additionalis required. All additional T-bars are by others.

Page 5: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-177

OVERVIEW | Plenum Slot Diffusers - Supply (DA_B)

UNDERWRITERS’ LABORATORIES, INC ®CLASSIFIED

AIR TERMINAL UNITSFIRE RESISTANCE CLASSIFICATION

DESIGN NOS. — SEE PRODUCT CATEGORYIN UL FIRE RESISTANCE DIRECTORY

CONTROL NO. 241Y

ONE SLOT TWO SLOTSSpecification Sheet 18664 Specification Sheet 18665

23-7/8”

47-3/4”

DAFB

Unit with CenterNotch

DARC - SpecificationSheet 18812

DASC - SpecificationSheet 18680

DANC-DAPC

Specification Sheet 18808 Specification Sheet 18809

Page 6: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

OVERVIEW | Plenum Slot Diffusers - Supply (DAFB, DANC, DAPC)

Linear, Plenum & Lt. Troffer S&R

A-178 www.carnes.com

DAFBThe Model DAFB is a UL classified adjustable pattern T-bar slot diffuser. They are available oneor two slots wide. The available slot widths are3/4”, 1” and 1-1/4”. The diffusers are constructedof 22 gauge galvanized steel and are available in24” and 48” lengths. The Model DAFB has all thefeatures of air pattern adjustment that are available on the other DA Series Diffusers. TheDAFB comes insulated as standard with 1/2” thick

- 1-1/2 pound density fiberglass internally mountedand matte-faced to prevent erosion. The insulationconforms to UL 181 and NFPA 90A requirements.The diffuser face is painted 06 flat black as standard. Number 01 white and Number 11 brightwhite are optional. When installed in accordancewith the installation instructions, the diffusers areUL classified with a three hour fire rating.

DANC — DAPCThe Models DANC and DAPC are combinationsupply/return slot diffusers. The DANC is compatible with most conventional T-bar ceilings.The DAPC is designed for installation in DonnFineline type grid systems. Both models consist ofone slot supply and one return slot.The supply slot has an adjustable pattern deflectorto allow horizontal or vertical air pattern adjustment. The return slot which is equal in widthto the supply slot returns air to ceiling Plenums.Available slot widths are 3/4”, 1” and 1-1/2”.Diffusers are available in nominal 24”, 30” 36”,48”and 60” lengths. Inlet sizes 5”, 6”, 7” and 8” onthe supply side are round. Inlets above 8” are oval.

These units are constructed of 24 gauge Galvanealed steel and are available with insulated or uninsulated plenums. The insulation is1/4” thick 3 pound density. The insulation is internally mounted and matte-faced to prevent erosion. The insulation conforms to UL 181 andNFPA 90A requirements.The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.These units are installed along side the main grid member and one additional grid member isrequired. All additional grid members are by others.

UNITS WITH CENTER NOTCHAll DA series adjustable T-bar slot diffusers, bothsupply and return models, size 48” are availablewith center notch. Some job specifications will callfor a four foot adjustable T-bar slot diffuser to be

mounted in a ceiling that has grid members on twofoot centers. The DA series when ordered with listed size 4N will accomplish this.

Page 7: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-179

OVERVIEW | Plenum Slot Diffusers - Return (DAHC, DAVC, DAKC)

DAHC (No center T’s)

DAVC (Factory installed center T’s)

DAKC (Fits Donn® Fineline® ceiling, factory installed center T’s)

ONE SLOT TWO SLOTS

TWO SLOTS THREE SLOTS FOUR SLOTS

TWO SLOTS THREE SLOTS FOUR SLOTS

Specification Sheet 18803 Specification Sheet 18804

Specification Sheet 18805 Specification Sheet 18815 Specification Sheet 18816

Specification Sheet 18817 Specification Sheet 18818Specification Sheet 18807ONE SLOT

Specification Sheet 18806

Page 8: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

OVERVIEW | Plenum Slot Diffusers - Return (DAHC, DAVC, DAKC)

Linear, Plenum & Lt. Troffer S&R

A-180 www.carnes.com

DAHC

DAVC

DAKC

Model DAHC is a return slot diffuser. It is compati-ble with most conventional T-bar ceilings. It is thematching return for the DASC supply diffuser andis available with one or two slots.Available slot widths are 3/4”, 1” and 1-1/2”. TheModel DAHC is available in nominal 24”, 30”, 36”,48” and 60” diffuser lengths.They are constructed of 24 gauge Galvanealedsteel and are available with insulated or uninsulat-ed plenums. Insulation for the one slot is 1/4” thick3 pound density. The two slot units have 1/2” thick1-1/2 pound density insulation. The insulation is

internally mounted and matte faced to prevent erosion. The insulation confirms to UL 181 andNFPA 90A requirements. The face of the unit ispainted number 06 flat black as standard. Number01 white and Number 11 bright white are optional.The one slot unit is installed along side the main T-bar and one additional T-bar is required. The twoslot is installed straddling the main T-bar and twoadditional T-bars are required. All additional T-barsare by others.

The Model DAVC is a return slot diffuser. It is com-patible with most conventional T-bar ceilings. It isthe matching return for Model DARC supply dif-fuser and is available with two, three or four slots.Available slot widths are 3/4”, 1” and 1-1/2”.The Model DAVC is available in nominal 24”, 30”,36”, 48” and 60” diffuser lengths. They are constructed of 24 gauge Galvanealed steel andare available with insulated or uninsulatedplenums. Insulation is 1/2” thick 1-1/2 pound density. The insulation is internally mounted andmatte faced to prevent erosion. The insulation confirms to UL 181 and NFPA 90A requirements.

The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.The slots of the diffuser are separated by standard15/16” T-bar which are installed in the unit andpainted number 11 bright white. The Model DAVBis installed along side the main T-bar and one additional T-bar is required. All additional T-barsare by others.

Model DAKC is a return T-bar slot diffuser. It isdesigned for installation in Donn Fineline grid systems. It is the matching return for Model DAMCsupply diffuser and is available with one, two, threeor four slots. Available slot widths are 3/4”, 1” and1-1/2”.The Model DAKC is available in nominal 24”, 30”,36”, 48” and 60” diffuser lengths. They are constructed of 24 gauge Galvanealed steel andare available with insulated or uninsulatedplenums. Insulation for the one slot unit is 1/4”thick 3 pound density. The two, three, and four slotmodels have 1/2” thick 1-1/2 pound density

insulation. The insulation is internally mounted andmatte faced to prevent erosion. The insulation conforms to UL 181 and NFPA 90A requirements. The face of the unit is painted number 06 flat blackas standard. Number 01 white and Number 11bright white are optional.The slots of the diffuser are separated by standard15/16” T-bar which are installed in the unit andpainted Number 01 white. The units are equippedwith T-bar clips on each side that hook over the T-bar. All models require one additional T-bar. Alladditional T-bars are by others.

Page 9: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-181

PERFORMANCE DATA | Supply Plenum Slot Diffusers - Size 24 (DA_C, DAFB)

3/4” Flow 25 50 75 100 125 150

Slot 6”, 8” Total Pressure .015 .063 .142 .253 .397 .575

WidthInlet NC — 20 31 39 46 51

Throw 3-6-12 9-13-19 13-16-23 15-18-26 16-20-29 18-22-311” Flow 25 50 75 100 125 150

1 Slot 6”, 8” Total Pressure .009 .036 .081 .145 .230 .333Slot

WidthInlet NC — 13 24 32 38 44

Throw 2-5-11 7-11-18 12-16-22 15-18-25 16-20-28 17-21-301-1/2” Flow 50 75 100 150 200 250

Slot 6”, 8” Total Pressure .009 .042 .075 .168 .303 .475

WidthInlet NC — 15 23 35 43 49

Throw 5-9-17 8-13-20 11-16-24 17-21-29 19-23-33 21-26-373/4” Flow 50 75 100 150 200 250

Slot 6”, 8” Total Pressure .019 .042 .075 .168 .303 .475

WidthInlet NC — 15 23 35 43 49

Throw 5-9-17 8-13-20 11-16-24 17-21-29 19-23-33 21-26-371” Flow 50 75 100 150 200 250

2 Slot 6”, 8” Total Pressure .013 .029 .053 .118 .209 .334Slots

WidthInlet NC — — 16 28 36 43

Throw 3-7-16 6-11-19 9-14-22 15-20-28 19-23-32 20-25-361-1/2” Flow 100 150 200 250 300 350

Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401

WidthInlet NC — 20 28 34 39 44

Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-403/4” Flow 100 150 200 250 300 350

Slot 6”, 8” Total Pressure .046 .104 .185 .292 .418 .575

WidthInlet NC 14 25 34 40 45 50

Throw 8-13-22 14-19-27 19-23-32 20-25-36 23-28-39 24-29-411” Flow 100 150 200 250 300 350

3 Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401Slots

WidthInlet NC — 20 28 34 39 44

Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-401-1/2” Flow 150 200 250 300 400 500

Slot 8”, 10” Total Pressure .046 .082 .128 .187 .332 .521

WidthInlet NC 11 19 26 31 39 46

Throw 7-13-25 11-18-29 14-21-33 18-25-36 23-29-41 26-32-453/4” Flow 100 150 200 250 300 350

Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401

WidthInlet NC — 20 28 34 39 44

Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-401” Flow 150 200 250 300 400 500

4 Slot 8”, 10” Total Pressure .052 .094 .147 .212 .379 .592Slots

WidthInlet NC 14 22 28 34 42 48

Throw 8-14-25 12-19-30 15-22-33 20-26-36 24-29-41 26-32-461-1/2” Flow 200 300 400 500 600 700

Slot 8”, 10” Total Pressure .059 .134 .238 .374 .542 .735

WidthInlet NC 14 26 34 40 46 50

Throw 8-15-28 14-22-35 20-28-40 25-31-44 28-35-49 30-37-52

Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Total Pressure is inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts. • Throw is in feet to terminal velocities of 150-100-50 FPM for isothermal conditions.• Throws listed are for one way pattern. For two-way pattern choose the number of slots in each direction and

distribute the total air flow proportionally.

Page 10: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

PERFORMANCE DATA | Supply Plenum Slot Diffusers - Size 30 (DA_C, DAFB)

Linear, Plenum & Lt. Troffer S&R

A-182 www.carnes.com

3/4” Flow 25 50 75 100 125 150

Slot 6”, 8” Total Pressure .010 .041 .092 .166 .262 .377

WidthInlet NC — 14 26 34 40 45

Throw 2-5-11 8-12-18 12-16-22 15-18-25 16-20-28 18-22-311” Flow 50 75 100 150 200 250

1 Slot 6”, 8” Total Pressure .025 .056 .100 .227 .405 .638Slot

WidthInlet NC — 19 27 39 47 53

Throw 6-10-17 10-14-21 13-17-24 17-21-30 20-24-34 22-27-381-1/2” Flow 50 75 100 150 200 250

Slot 6”, 8” Total Pressure .014 .032 .057 .128 .227 .363

WidthInlet NC — 10 18 30 38 44

Throw 4-8-16 7-12-20 10-15-23 16-20-28 19-23-32 20-25-363/4” Flow 50 75 100 150 200 250

Slot 6”, 8” Total Pressure .014 .032 .057 .128 .227 .363

WidthInlet NC — 10 18 30 38 44

Throw 4-8-16 7-12-20 10-15-23 16-20-28 19-23-32 20-25-361” Flow 100 150 200 250 300 350

2 Slot 6”, 8” Total Pressure .040 .091 .162 .254 .367 .504Slots

WidthInlet NC 12 23 31 38 43 48

Throw 8-13-22 12-18-27 17-22-31 20-25-35 22-27-38 24-29-411-1/2” Flow 150 200 250 300 400 500

Slot 8”, 10” Total Pressure .057 .101 .158 .228 .408 .638

WidthInlet NC 15 23 30 35 43 50

Throw 9-15-25 13-19-30 17-24-34 20-26-37 24-29-41 27-33-463/4” Flow 100 150 200 250 300 350

Slot 6”, 8” Total Pressure .036 .080 .143 .226 .326 .445

WidthInlet NC 10 21 29 36 41 45

Throw 7-12-21 11-17-27 16-22-31 20-25-35 22-27-38 23-28-401” Flow 150 200 250 300 400 500

3 Slot 8”, 10” Total Pressure .057 .101 .158 .228 .408 .638Slots

WidthInlet NC 15 23 30 35 43 50

Throw 9-15-25 13-19-30 17-24-34 20-26-37 24-29-41 27-33-461-1/2” Flow 200 300 400 500 600 700

Slot 8”, 10” Total Pressure .064 .144 .257 .404 .585 .790

WidthInlet NC 16 27 36 42 47 52

Throw 9-16-28 15-23-35 20-28-40 25-31-44 28-35-49 31-38-533/4” Flow 150 200 250 300 400 500

Slot 8”, 10” Total Pressure .057 .101 .158 .228 .408 .638

WidthInlet NC 15 23 30 35 43 50

Throw 9-15-25 13-19-30 17-24-34 20-26-37 24-29-41 27-33-461” Flow 200 300 400 500 600 700

4 Slot 8”, 10” Total Pressure .073 .163 .294 .460 .665 .915Slots

WidthInlet NC 18 29 38 44 49 54

Throw 10-17-29 17-24-36 22-28-40 26-32-45 28-35-49 31-38-531-1/2” Flow 300 400 500 600 700 800

Slot 10”, 12” Total Pressure .103 .187 .288 .413 .562 .735

WidthInlet NC 22 30 37 42 46 50

Throw 12-20-34 17-25-39 21-29-43 26-34-48 29-36-51 32-39-55

Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Total Pressure is inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts. • Throw is in feet to terminal velocities of 150-100-50 FPM for isothermal conditions.• Throws listed are for one way pattern. For two-way pattern choose the number of slots in each direction and

distribute the total air flow proportionally.

Page 11: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-183

PERFORMANCE DATA | Supply Plenum Slot Diffuser - Size 36 (DA_C, DAFB)

3/4” Flow 25 50 75 100 125 150

Slot 6”, 8” Total Pressure .007 .029 .066 .118 .187 .268

WidthInlet NC — 10 21 28 35 41

Throw 2-4-10 7-11-18 12-15-22 15-18-25 16-19-27 17-21-301” Flow 50 75 100 150 200 250

1 Slot 6”, 8” Total Pressure .019 .042 .075 .168 .303 .475Slot

WidthInlet NC — 15 23 35 43 49

Throw 5-9-17 8-13-20 11-16-24 17-21-29 19-23-33 21-26-371-1/2” Flow 100 150 200 250 300 350

Slot 6”, 8” Total Pressure .046 .104 .185 .292 .418 .575

WidthInlet NC 14 25 34 40 45 50

Throw 8-13-22 14-19-27 19-23-32 20-25-36 23-28-39 24-29-413/4” Flow 100 150 200 250 300 350

Slot 6”, 8” Total Pressure .046 .104 .185 .292 .418 .575

WidthInlet NC 14 25 34 40 45 50

Throw 8-13-22 14-19-27 19-23-32 20-25-36 23-28-39 24-29-411” Flow 100 150 200 250 300 350

2 Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401Slots

WidthInlet NC — 20 28 34 39 44

Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-401-1/2” Flow 150 200 250 300 400 500

Slot 8”, 10” Total Pressure .046 .082 .128 .187 .332 .521

WidthInlet NC 11 19 26 31 39 46

Throw 7-13-25 11-18-29 14-21-33 18-25-36 23-29-41 26-32-453/4” Flow 150 200 250 300 400 500

Slot 6”, 8” Total Pressure .064 .113 .178 .258 .460 .721

WidthInlet NC 17 25 32 37 45 52

Throw 10-16-26 14-20-30 18-24-34 21-26-37 24-30-42 27-33-461” Flow 150 200 250 300 400 500

3 Slot 8”, 10” Total Pressure .046 .082 .128 .187 .332 .521Slots

WidthInlet NC 11 19 26 31 39 46

Throw 7-13-25 11-18-29 14-21-33 18-25-36 23-29-41 26-32-451-1/2” Flow 200 300 400 500 600 700

Slot 8”, 10” Total Pressure .051 .115 .206 .322 .465 .632

WidthInlet NC 12 24 32 38 44 48

Throw 7-14-28 13-21-34 18-26-39 23-31-44 27-34-48 30-37-523/4” Flow 150 200 250 300 400 500

Slot 8”, 10” Total Pressure .046 .082 .128 .187 .332 .521

WidthInlet NC 11 19 26 31 39 46

Throw 7-13-25 11-18-29 14-21-33 18-25-36 23-29-41 26-32-451” Flow 200 300 400 500 600 700

4 Slot 8”, 10” Total Pressure .059 .134 .238 .374 .542 .735Slots

WidthInlet NC 14 26 34 40 46 50

Throw 8-15-28 14-22-35 20-28-40 25-31-44 28-35-49 30-37-521-1/2” Flow 300 400 500 600 700 800

Slot 10”, 12” Total Pressure .083 .148 .232 .334 .455 .603

WidthInlet NC 19 27 33 38 43 47

Throw 10-18-33 14-23-38 19-28-43 22-32-47 28-36-51 31-38-54

Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Total Pressure is inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts. • Throw is in feet to terminal velocities of 150-100-50 FPM for isothermal conditions.• Throws listed are for one way pattern. For two-way pattern choose the number of slots in each direction and

distribute the total air flow proportionally.

Page 12: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

PERFORMANCE DATA | Supply Plenum Slot Diffuser - Size 48 (DA_C, DAFB)

Linear, Plenum & Lt. Troffer S&R

A-184 www.carnes.com

3/4” Flow 50 75 100 150 200 250

Slot 6”, 8” Total Pressure .019 .042 .075 .168 .303 .475

WidthInlet NC — 15 23 35 43 49

Throw 5-9-17 8-13-20 11-16-24 17-21-29 19-23-33 21-26-371” Flow 50 75 100 150 200 250

1 Slot 6”, 8” Total Pressure .013 .029 .053 .118 .209 .334Slot

WidthInlet NC — — 16 28 36 43

Throw 3-7-16 6-11-19 9-14-22 15-20-28 19-23-32 20-25-361-1/2” Flow 100 150 200 250 300 350

Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401

WidthInlet NC — 20 28 34 39 44

Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-403/4” Flow 100 150 200 250 300 350

Slot 6”, 8” Total Pressure .032 .073 .130 .205 .295 .401

WidthInlet NC — 20 28 34 39 44

Throw 6-11-21 10-16-26 15-21-31 20-25-35 22-27-38 23-28-401” Flow 150 200 250 300 400 500

2 Slot 8”, 10” Total Pressure .052 .094 .147 .212 .379 .592Slots

WidthInlet NC 14 22 28 34 42 48

Throw 8-14-25 12-19-30 15-22-33 20-26-36 24-29-41 26-32-461-1/2” Flow 200 300 400 500 600 700

Slot 8”, 10” Total Pressure .059 .134 .238 .374 .542 .735

WidthInlet NC 14 26 34 40 46 50

Throw 8-15-28 14-22-35 20-28-40 25-31-44 28-35-49 30-37-523/4” Flow 150 200 250 300 400 500

Slot 8”, 10” Total Pressure .046 .082 .128 .187 .332 .521

WidthInlet NC 11 19 26 31 39 46

Throw 7-13-25 11-18-29 14-21-33 18-25-36 23-29-41 26-32-451” Flow 200 300 400 500 600 700

3 Slot 8”, 10” Total Pressure .059 .134 .238 .374 .542 .735Slots

WidthInlet NC 14 26 34 40 46 50

Throw 8-15-28 14-22-35 20-28-40 25-31-44 28-35-49 30-37-521-1/2” Flow 300 400 500 600 700 800

Slot 10”, 12” Total Pressure .083 .148 .232 .334 .455 .603

WidthInlet NC 19 27 33 38 43 47

Throw 10-18-33 14-23-38 19-28-43 22-32-47 28-36-51 31-38-543/4” Flow 200 300 400 500 600 700

Slot 8”, 10” Total Pressure .059 .134 .238 .374 .542 .735

WidthInlet NC 14 26 34 40 46 50

Throw 8-15-28 14-22-35 20-28-40 25-31-44 28-35-49 30-37-521” Flow 300 400 500 600 700 800

4 Slot 10”, 12” Total Pressure .095 .168 .266 .381 .519 .682Slots

WidthInlet NC 21 29 35 40 45 49

Throw 11-19-34 16-25-39 20-29-43 25-33-47 29-36-51 32-39-551-1/2” Flow 400 500 600 700 800 900

Slot 10”, 12” Total Pressure .105 .164 .238 .322 .424 .540

WidthInlet NC 22 28 34 38 42 45

Throw 11-20-37 15-25-42 19-29-46 22-33-50 26-37-53 30-40-57

Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Total Pressure is inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts. • Throw is in feet to terminal velocities of 150-100-50 FPM for isothermal conditions.• Throws listed are for one way pattern. For two-way pattern choose the number of slots in each direction and

distribute the total air flow proportionally.

Page 13: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-185

PERFORMANCE DATA | Supply Plenum Slot Diffuser - Size 60 (DA_C, DAFB)

3/4” Flow 50 75 100 150 200 250

Slot 6”, 8” Total Pressure .014 .032 .057 .128 .227 .363

WidthInlet NC — 10 18 30 38 44

Throw 4-8-16 7-12-20 10-15-23 16-20-28 19-23-32 20-25-361” Flow 100 150 200 250 300 350

1 Slot 6”, 8” Total Pressure .040 .091 .162 .254 .367 .504Slot

WidthInlet NC 12 23 31 38 43 48

Throw 8-13-22 12-18-27 17-22-31 20-25-35 22-27-38 24-29-411-1/2” Flow 150 200 250 300 400 500

Slot 8”, 10” Total Pressure .057 .101 .158 .228 .408 .638

WidthInlet NC 15 23 30 35 43 50

Throw 9-15-25 13-19-30 17-24-34 20-26-37 24-29-41 27-33-463/4” Flow 150 200 250 300 400 500

Slot 8”, 10” Total Pressure .057 .101 .158 .228 .408 .638

WidthInlet NC 15 23 30 35 43 50

Throw 9-15-25 13-19-30 17-24-34 20-26-37 24-29-41 27-33-461” Flow 200 300 400 500 600 700

2 Slot 8”, 10” Total Pressure .073 .163 .294 .460 .665 .915Slots

WidthInlet NC 18 29 38 44 49 54

Throw 10-17-29 17-24-36 22-28-40 26-32-45 28-35-49 31-38-531-1/2” Flow 300 400 500 600 700 800

Slot 10”, 12” Total Pressure .103 .187 .288 .413 .562 .735

WidthInlet NC 22 30 37 42 46 50

Throw 12-20-34 17-25-39 21-29-43 26-34-48 29-36-51 32-39-553/4” Flow 200 300 400 500 600 700

Slot 8”, 10” Total Pressure .064 .144 .257 .404 .585 .790

WidthInlet NC 16 27 36 42 47 52

Throw 9-16-28 15-23-35 20-28-40 25-31-44 28-35-49 31-38-531” Flow 300 400 500 600 700 800

3 Slot 10”, 12” Total Pressure .103 .187 .288 .413 .562 .735Slots

WidthInlet NC 22 30 37 42 46 50

Throw 12-20-34 17-25-39 21-29-43 26-34-48 29-36-51 32-39-551-1/2” Flow 400 500 600 700 800 900

Slot 10”, 12” Total Pressure .115 .180 .259 .352 .459 .588

WidthInlet NC 23 30 35 40 43 47

Throw 12-21-37 15-25-42 20-30-46 24-34-50 28-38-54 31-40-573/4” Flow 300 400 500 600 700 800

Slot 10”, 12” Total Pressure .103 .187 .288 .413 .562 .735

WidthInlet NC 22 30 37 42 46 50

Throw 12-20-34 17-25-39 21-29-43 26-34-48 29-36-51 32-39-551” Flow 300 400 500 600 700 800

4 Slot 10”, 12” Total Pressure .073 .133 .205 .296 .404 .527Slots

WidthInlet NC 17 25 31 37 41 45

Throw 8-17-33 13-22-38 17-26-42 21-31-47 26-35-50 30-38-541-1/2” Flow 500 600 700 800 900 1000

Slot 10”, 12” Total Pressure .127 .183 .252 .327 .417 .517

WidthInlet NC 25 30 35 38 42 45

Throw 12-22-41 15-26-45 19-30-49 22-34-52 25-37-56 30-42-59

Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Total Pressure is inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts. • Throw is in feet to terminal velocities of 150-100-50 FPM for isothermal conditions.• Throws listed are for one way pattern. For two-way pattern choose the number of slots in each direction and

distribute the total air flow proportionally.

Page 14: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

PERFORMANCE DATA | Return Plenum Slot Diffuser - Size 24 (DA_C)

Linear, Plenum & Lt. Troffer S&R

A-186 www.carnes.com

3/4” Flow 31 50 75 100 125 150Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 15 24 30 351 1” Flow 42 67 100 133 167 200

Slot Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 17 26 32 371-1/2” Flow 63 100 150 200 250 300Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 18 27 33 383/4” Flow 63 100 150 200 250 300Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 18 27 33 382 1” Flow 83 133 200 267 333 400

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 20 29 35 401-1/2” Flow 125 200 300 400 500 600Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 10 21 30 36 413/4” Flow 94 150 225 300 375 450Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 20 29 35 403 1” Flow 125 200 300 400 500 600

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 11 22 31 37 421-1/2” Flow 188 300 450 600 750 900Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 12 23 32 38 433/4” Flow 125 200 300 400 500 600Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 10 21 30 36 414 1” Flow 167 267 400 533 667 800

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 12 23 32 38 431-1/2” Flow 250 400 600 800 1000 1200Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 13 24 33 39 44

Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Static pressure is negative inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts.

Page 15: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-187

PERFORMANCE DATA | Return Plenum Slot Diffuser - Size 30 (DA_C)

3/4” Flow 39 63 94 125 156 188Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 15 24 30 351 1” Flow 52 83 125 167 208 250

Slot Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 17 26 32 371-1/2” Flow 78 125 188 250 313 375Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 18 27 33 383/4” Flow 78 125 188 250 313 375Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 18 27 33 382 1” Flow 104 167 250 333 417 500

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 20 29 35 401-1/2” Flow 156 250 375 500 625 750Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 10 21 30 36 413/4” Flow 117 188 281 375 469 563Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 20 29 35 403 1” Flow 156 250 375 500 625 750

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 11 22 31 37 421-1/2” Flow 234 375 563 750 938 1125Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 12 23 32 38 433/4” Flow 156 250 375 500 625 750Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 10 21 30 36 414 1” Flow 208 333 500 667 833 1000

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 12 23 32 38 431-1/2” Flow 313 500 750 1000 1250 1500Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 13 24 33 39 44

Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Static pressure is negative inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts.

Page 16: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

PERFORMANCE DATA | Return Plenum Slot Diffuser - Size 36 (DA_C)

Linear, Plenum & Lt. Troffer S&R

A-188 www.carnes.com

3/4” Flow 47 75 113 150 188 225Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 15 24 30 351 1” Flow 63 100 150 200 250 300

Slot Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 17 26 32 371-1/2” Flow 94 150 225 300 375 450Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 18 27 33 383/4” Flow 94 150 225 300 375 450Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 18 27 33 382 1” Flow 125 200 300 400 500 600

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 20 29 35 401-1/2” Flow 188 300 450 600 750 900Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 10 21 30 36 413/4” Flow 141 225 338 450 563 675Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 20 29 35 403 1” Flow 188 300 450 600 750 900

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 11 22 31 37 421-1/2” Flow 281 450 675 900 1125 1350Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 12 23 32 38 433/4” Flow 188 300 450 600 750 900Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 10 21 30 36 414 1” Flow 250 400 600 800 1000 1200

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 12 23 32 38 431-1/2” Flow 375 600 900 1200 1500 1800Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 13 24 33 39 44

Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Static pressure is negative inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts.

Page 17: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-189

PERFORMANCE DATA | Return Plenum Slot Diffuser - Size 48 (DA_C)

3/4” Flow 63 100 150 200 250 300Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 15 24 30 351 1” Flow 83 133 200 267 333 400

Slot Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 17 26 32 371-1/2” Flow 125 200 300 400 500 600Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 18 27 33 383/4” Flow 125 200 300 400 500 600Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 18 27 33 382 1” Flow 167 267 400 533 667 800

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 20 29 35 401-1/2” Flow 250 400 600 800 1000 1200Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 10 21 30 36 413/4” Flow 188 300 450 600 750 900Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 20 29 35 403 1” Flow 250 400 600 800 1000 1200

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 11 22 31 37 421-1/2” Flow 375 600 900 1200 1500 1800Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 12 23 32 38 433/4” Flow 250 400 600 800 1000 1200Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 10 21 30 36 414 1” Flow 333 533 800 1067 1333 1600

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 12 23 32 38 431-1/2” Flow 500 800 1200 1600 2000 2400Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 13 24 33 39 44

Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Static pressure is negative inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts.

Page 18: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

PERFORMANCE DATA | Return Plenum Slot Diffuser - Size 60 (DA_C)

Linear, Plenum & Lt. Troffer S&R

A-190 www.carnes.com

3/4” Flow 78 125 188 250 313 375Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 15 24 30 351 1” Flow 104 167 250 333 417 500

Slot Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 17 26 32 371-1/2” Flow 156 250 375 500 625 750Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 18 27 33 383/4” Flow 156 250 375 500 625 750Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 18 27 33 382 1” Flow 208 333 500 667 833 1000

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — — 20 29 35 401-1/2” Flow 313 500 750 1000 1250 1500Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 10 21 30 36 413/4” Flow 234 375 563 750 938 1125Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — — 20 29 35 403 1” Flow 313 500 750 1000 1250 1500

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 11 22 31 37 421-1/2” Flow 469 750 1125 1500 1875 2250Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 12 23 32 38 433/4” Flow 313 500 750 1000 1250 1500Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 10 21 30 36 414 1” Flow 417 667 1000 1333 1667 2000

Slots Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224Width NC — 12 23 32 38 431-1/2” Flow 625 1000 1500 2000 2500 3000Slot S. P. (Neg.) .010 .025 .056 .100 .156 .224

Width NC — 13 24 33 39 44

Notes on Performance Data• Performance shown is based on testing in accordance with ANSI/ASHRAE Standard 70-1991.• Flow is CFM of standard air.• Static pressure is negative inches of water gage.• NC is noise criteria based on a room absorption of 10db re. 10-12 watts.

Page 19: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-191

SUGGESTED INSTALLATION INSTRUCTIONS

Carnes DA Series Adjustable Pattern Slot Diffusersare designed for use in most standard exposed suspended grid systems. The Model DASC two slotstraddles the main T-bar and is supported by T-barson the diffuser perimeter. The Model DASC one slotis supported on one side by the main T-bar and onthe other side by an additional T-bar. Models DARCand DAMC have center T-bars as part of the unit sothey are installed in the same method as the Model

DASC one slot.In order to maintain color continuity all required additional T-bars are by others. Although support isprovided by the T-bar, additional support may beadvisable. Supply units are provided with a wire support screw in each end of the diffuser plenum.These can be used to connect wire supports from theT-bar or from structural support.

STRUCTURAL SUPPORT

T-BAR BY OTHERS

Model DAFBCarnes Model DAFB UL Classified Slot Diffuser isdesigned for use in most standard exposed T-barceilings. The two slot models straddle the main T-barand are supported by T-bars on the diffuser perimeter. One slot units are supported on one side

by the main T-bar and on the other side by an additional T-bar. In order to maintain color continuity,all required T-bars are by others. When installed inaccordance with the installation instructions, theModel DAFB is UL Classified with a 3 hour fire rating.

Page 20: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

FEATURES | Fixed Pattern Slot Diffuser

Linear, Plenum & Lt. Troffer S&R

A-192 www.carnes.com

DFSB — Fixed Pattern Slot Diffuser — DFRB

Carnes Matched Fixed Pattern Slot Diffuser and Return Air Slot

Model DFSB — Supply Model DFRB — Return

Features

�� Eliminates drafts. Maintain horizontal air flow at levels below 10% of nominal CFM (50 CFM per

linear foot of slot.

�� The diffuser, in conjunction with return air slot, produces a high level of air induction to cause

rapid and complete mixing of room air.

�� Supplies uniform air distribution along the entire length of the slot (well within 10%).

�� Available in one, two, three or four slots in four diffuser lengths.

�� The T-bar type diffuser fits over T’s, eliminating the need to add or remove grid members.

�� Lower installation costs due to Carnes’ innovative design of the linear slot diffuser eliminating

50% of the tile cost.

�� Visual conformity. Linear slot diffusers and return air slots are identical in appearance.

Page 21: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-193

INTRODUCTION & DESCRIPTION | Models DFSB and DFRB

INTRODUCTIONCarnes Models DFSB supply and DFRB return arefixed horizontal pattern slot diffusers for use in mostexposed T-bar ceilings. The DFSB will hold a hori-zontal air pattern at less than 10% of nominal CFM

(50 per linear foot of slot). The return diffuser ModelDFRB is identical in appearance to the DFSB toallow for complete continuity to ceiling appearance.

2 Slots — 2 Ways 3 Slots — 2 Ways 4 Slot — 2 Ways

1 Slot — 1 Way 2 Slots — 1 Way 3 Slots — 1 Way

DESCRIPTIONCarnes fixed horizontal pattern slot diffusers areavailable in 1, 2, 3 or 4 slot models, and can beordered in 24”, 30”, 48” and 60” lengths. The DFSBsupply and DFRB return diffusers are constructed of24 gauge painted formed galvanealed steel. Thebright white finish matches most ceiling T-bars andtile. The integral insulated plenum is of 24 gauge galvanized construction. The plenum insulation is1/4” - 3 lb. density fiberglass internally mounted andmatte faced to prevent erosion. The insulation meetsUL 181 and NFPA 90A requirements. Each supply

diffuser can be furnished with a 5”, 6”, 7” or 8” roundplenum inlet. The 10” inlet, when specified, has anoval configuration. The supply diffuser plenum inletcollar is 1-3/4” deep for easy flex duct connections.The return diffuser plenum is also insulated and hasopen sides to return air to the ceiling plenum. TheCarnes DFSB has an excellent air distribution pattern, no butterfly pattern. Slot velocity is uniformand sound levels are very low, giving you an efficientdiffuser with excellent performance.

Page 22: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

SPECIFICATION | Models DFSB and DFRB

Linear, Plenum & Lt. Troffer S&R

A-194 www.carnes.com

SPECIFICATION GUIDELINES

Carnes Models DFSB Supply and DFRB Return, horizontal pattern slot diffusers shall be installed ateach location as shown on the drawings. All diffusersto have performance ratings of CFM, static pressure,noise criteria and throw as shown on the drawings.The diffusers shall be formed galvanealed steel con-struction in 1, 2, 3 or 4 slots.They shall be of 1 or 2

way throw patterns, with diffuser length as shown onthe drawings. The diffuser plenum shall be thermally and acoustically insulated with 1/4” thick 3lb. density fiberglass internally mounted and mattefaced to prevent erosion. The insulation shall meetUL 181 and NFPA 90A requirements.

� MODEL NUMBERING SYSTEM — Models DFSB and DFRB

OPTION1 2 3 4 5 6 7 8 9 10 11 12 13

D F S B 0 6 4 8 2 1 1 1

D - Diffuser

F - Fixed

S - Supply R - Return

DESIGNSERIES INLET

SIZE00 - (DFRA

Only)05 - 5”06 - 6”07 - 7”08 - 8”10 - 10” (Oval)

DIFFUSERLENGTH

24 - 24”30 - 30”48 - 48”60 - 60”4N - 48”

(WithCenterNotch)

SLOTQUANTITY1 - 1 Slot2 - 2 Slots3 - 3 Slots4 - 4 Slots

(2 WayOnly)

DEFLECTION PATTERN

1 - One Way2 - Two Way

FINISHES11 - Bright White (Default)01 - White06 - Black

V - Volume Control Damper

Page 23: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-195

DIMENSIONAL DATA | Fixed Pattern Slot Diffuser - Supply (DFSB)

Patent 3,406,623

B

AC

EE

DD

F F

1-3/4”

TWO SLOTTWO-WAY

TWO SLOTONE-WAY

Resting OnMain-TAdjoining Tile

Cut To FitT-bar ofStandardCeiling Grid

1/4” — 3 lb.Density Insulation

Air Flow

Model (Inches)DFSB C24 - 05 9-1/424 - 06 8-3/424 - 07 8-1/424 - 08 7-3/424 - 09 6-7/824 - 10 11-7/824 - 12 11-7/824 - 14 11-7/830 - 05 12-1/430 - 06 11-3/430 - 07 11-1/430 - 08 10-3/430 - 09 9-7/830 - 10 9-1/830 - 12 14-7/830 - 14 14-7/848 - 05 21-1/448 - 06 20-3/448 - 07 20-1/448 - 08 19-3/448 - 09 18-7/848 - 10 18-1/848 - 12 16-5/848 - 14 1560 - 05 27-1/460 - 06 26-3/460 - 07 26-1/460 - 08 25-3/460 - 09 24-7/860 - 10 24-1/860 - 12 22-5/860 - 14 21

Model Nominal Slot Pattern DIMENSIONS LISTED IN INCHESDFSB Length Quantity Deflection A B D E F2411 24 1 One Way 23-13/16 23-1/8 1-7/8 2-5/8 2-7/82421 24 2 One Way 23-13/16 23-1/8 3-15/32 3-23/32 4-1/22422 24 2 Two Way 23-13/16 23-1/8 4-1/16 4-1/8 5-1/162431 24 3 One Way 23-13/16 23-1/8 5-1/16 5-5/16 6-1/162432 24 3 Two Way 23-13/16 23-1/8 5-21/32 5-29/32 6-21/322442 24 4 Two Way 23-13/16 23-1/8 7-1/4 7-1/2 8-1/43011 30 1 One Way 29-13/16 29-1/8 1-7/8 2-5/8 2-7/83021 30 2 One Way 29-13/16 29-1/8 3-15/32 3-23/32 4-1/23022 30 2 Two Way 29-13/16 29-1/8 4-1/16 4-1/8 5-1/163031 30 3 One Way 29-13/16 29-1/8 5-1/16 5-5/16 6-1/163032 30 3 Two Way 29-13/16 29-1/8 5-21/32 5-29/32 6-21/323042 30 4 Two Way 29-13/16 29-1/8 7-1/4 7-1/2 8-1/44811 48 1 One Way 47-13/16 47-1/8 1-7/8 2-5/8 2-7/84821 48 2 One Way 47-13/16 47-1/8 3-15/32 3-23/32 4-1/24822 48 2 Two Way 47-13/16 47-1/8 4-1/16 4-1/8 5-1/164831 48 3 One Way 47-13/16 47-1/8 5-1/16 5-5/16 6-1/164832 48 3 Two Way 47-13/16 47-1/8 5-21/32 5-29/32 6-21/324842 48 4 Two Way 47-13/16 47-1/8 7-1/4 7-1/2 8-1/46011 60 1 One Way 59-13/16 59-1/8 1-7/8 2-5/8 2-7/86021 60 2 One Way 59-13/16 59-1/8 3-15/32 3-23/32 4-1/26022 60 2 Two Way 59-13/16 59-1/8 4-1/16 4-1/8 5-1/166031 60 3 One Way 59-13/16 59-1/8 5-1/16 5-5/16 6-1/166032 60 3 Two Way 59-13/16 59-1/8 5-21/32 5-29/32 6-21/326042 60 4 Two Way 59-13/16 59-1/8 7-1/4 7-1/2 8-1/4

NOTES:1. Inlet size to be specified.2. Inlet sizes 5”, 6”, 7” and 8” are round. Size 9” & 10” (12” & 14” available) inlet is oval.3. Diffuser is 24 gauge formed steel, painted.4. Plenum is 24 gauge galvanized steel.5. Plenums are insulated with 1/4” thick 3 lb. density matte-faced insulation.6. Not recommended for 9/16” flat T-bar.

Page 24: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

DIMENSIONAL DATA | Fixed Pattern Slot Diffuser - Return (DFRB)

Linear, Plenum & Lt. Troffer S&R

A-196 www.carnes.com

Patent 3,406,623

Model Nominal Slot Pattern DIMENSIONS LISTED IN INCHESDFRB Length Quantity Deflection A B C D2411 24 1 One Way 23-13/16 23-1/8 1-7/8 2-7/82421 24 2 One Way 23-13/16 23-1/8 3-15/32 4-1/22422 24 2 Two Way 23-13/16 23-1/8 4-1/16 5-1/162431 24 3 One Way 23-13/16 23-1/8 5-1/16 6-1/162432 24 3 Two Way 23-13/16 23-1/8 5-21/32 6-21/322442 24 4 Two Way 23-13/16 23-1/8 7-1/4 8-1/43011 30 1 One Way 29-13/16 29-1/8 1-7/8 2-7/83021 30 2 One Way 29-13/16 29-1/8 3-15/32 4-1/23022 30 2 Two Way 29-13/16 29-1/8 4-1/6 5-1/163031 30 3 One Way 29-13/16 29-1/8 5-1/16 6-1/163032 30 3 Two Way 29-13/16 29-1/8 5-21/32 6-21/323042 30 4 Two Way 29-13/16 29-1/8 7-1/4 8-1/44811 48 1 One Way 47-13/16 47-1/8 1-7/8 2-7/84821 48 2 One Way 47-13/16 47-1/8 3-15/32 4-1/24822 48 2 Two Way 47-13/16 47-1/8 4-1/16 5-1/164831 48 3 One Way 47-13/16 47-1/8 5-1/16 6-1/164832 48 3 Two Way 47-13/16 47-1/8 5-21/32 6-21/324842 48 4 Two Way 47-13/16 47-1/8 7-1/4 8-1/46011 60 1 One Way 59-13/16 59-1/8 1-7/8 2-7/86021 60 2 One Way 59-13/16 59-1/8 3-15/32 4-1/26022 60 2 Two Way 59-13/16 59-1/8 4-1/16 5-1/166031 60 3 One Way 59-13/16 59-1/8 5-1/16 6-1/166032 60 3 Two Way 59-13/16 59-1/8 5-21/32 6-21/326042 60 4 Two Way 59-13/16 59-1/8 7-1/4 8-1/4

NOTES:1. Diffuser is 24 gauge formed galvanealed steel painted.2. Light baffle is 24 gauge galvanized steel.3. Not recommended for 9/16” flat T-bar.

A

C C

DD

B

1”1”

Adjoining TileCut To Fit

Resting OnMain -T

T-bar PartOf StandardCeiling Grid

4” 4”

Page 25: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-197

PERFORMANCE DATA | Fixed Pattern Slot Diffuser - Supply (DFSB)

Front View

Static THROW FEETPressure Distance From Discharge Device, When FPM Equals Sound Power db

Model Nominal Number Drop Octave BandDFSB Length of Slot CFM (Inches) 50 FPM 75 FPM 100 FPM 150 FPM 2 3 4 5 6 7 NC

25 .01 5 2 1 1 — — — — — — —50 .02 13 9 5 2 — — — — — — —

2411 24” 1 75 .06 19 13 10 5 — 36 32 — — — —100 .11 22 18 13 9 47 45 40 33 27 — 24125 .20 24 20 16 11 49 49 45 40 35 30 30

50 .01 12 5 3 1 — — — — — — —100 .04 22 15 10 5 — 34 — — — — —

2421 24” 2 150 .09 28 22 17 10 47 44 36 34 25 — 23200 .15 32 27 22 15 48 50 44 42 28 — 31250 .24 35 30 24 19 49 55 50 48 31 — 37

50 .01 7 4 2 1 — — — — — — —100 .03 14 9 7 4 — 30 — — — — —

2422 24” 2 150 .06 22 14 10 7 — 41 35 30 — — 20200 .15 25 19 14 10 45 48 42 40 35 — 29250 .22 28 23 18 12 50 52 48 46 42 33 35

75 .01 18 14 7 4 — — — — — — —150 .03 28 23 18 12 — 34 — — — — —

2431 24” 3 225 .07 36 28 24 18 — 44 37 33 — — 23300 .13 40 33 28 23 47 50 44 42 34 27 31375 .20 46 36 33 25 51 57 49 49 42 36 37

1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2 Slot75 .01 5 12 2 5 1 3 1 1 — — — — — — —

150 .03 13 22 9 15 5 10 2 5 — 33 — — — — —2432 24” 3 225 .07 19 28 13 22 10 17 5 10 — 42 36 — — — 22

300 .14 22 32 18 27 13 22 9 15 47 49 43 42 37 30 31375 .23 24 35 20 30 16 24 11 19 51 58 48 49 45 38 38100 .01 12 5 3 1 — — — — — — —200 .05 22 15 10 5 48 35 29 — — — —

2442 24” 4 300 .11 28 22 17 10 50 45 39 36 26 — 25400 .19 32 27 22 15 51 52 46 44 38 31 33500 .29 35 30 24 19 53 58 52 51 47 38 39

Static THROW FEETPressure Distance From Discharge Device, When FPM Equals Sound Power db

Model Nominal Number Drop Octave BandDFSB Length of Slot CFM (Inches) 50 FPM 75 FPM 100 FPM 150 FPM 2 3 4 5 6 7 NC

25 .01 5 2 1 — — — — — — — —50 .02 9 4 2 1 — — — — — — —

3011 30” 1 75 .05 20 9 5 2 — 35 28 — — — —100 .09 24 18 10 4 44 43 37 27 — — 22125 .15 27 22 13 6 47 48 43 36 27 — 26

50 .01 3 2 1 — — — — — — — —100 .02 15 6 3 2 — 30 — — — — —

3021 30” 2 150 .05 21 15 8 3 44 41 33 27 — — 20200 .09 24 19 15 6 44 47 39 36 28 — 26250 .14 27 23 18 10 50 52 46 41 34 29 32

50 .01 4 2 1 — — — — — — — —100 .02 9 6 4 2 — 27 — — — — —

3022 30” 2 150 .05 14 9 7 4 — 38 28 — — — —200 .09 17 12 9 6 44 45 37 33 28 — 24250 .14 19 15 11 8 49 50 43 40 36 28 30100 .01 12 9 5 2 — — — — — — —200 .03 23 17 12 9 — 37 29 — — — —

3031 30” 3 300 .09 28 23 19 12 44 47 40 37 27 — 27400 .16 33 27 24 17 49 53 50 48 41 37 36500 .25 37 31 26 21 52 58 56 55 52 42 44

1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2 Slot100 .01 2 3 1 2 1 1 — — — — — — — — —200 .03 9 15 4 6 2 3 1 2 — 34 — — — — —

3032 30” 3 300 .08 20 21 9 15 5 8 2 3 — 44 37 35 28 — 24400 .15 24 24 18 19 10 15 4 6 48 51 45 44 39 32 33500 .23 27 27 22 23 13 18 6 10 51 56 51 52 48 38 30150 .01 3 1 1 — — — — — — — —300 .04 12 6 3 1 — 41 34 30 — — —

3042 30” 4 450 .11 18 12 7 3 50 53 47 46 39 32 35600 .21 22 17 12 6 55 59 56 55 50 42 44750 .35 25 20 16 8 59 65 63 62 58 52 51

Page 26: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

PERFORMANCE DATA | Fixed Pattern Slot Diffuser - Supply (DFSB)

Linear, Plenum & Lt. Troffer S&R

A-198 www.carnes.com

Front ViewStatic THROW FEET

Pressure Distance From Discharge Device, When FPM Equals Sound Power dbModel Nominal Number Drop Octave BandDFSB Length of Slot CFM (Inches) 50 FPM 75 FPM 100 FPM 150 FPM 2 3 4 5 6 7 NC

50 .01 6 3 1 1 — — — — — — —100 .04 15 10 6 3 — 29 — — — — —

4811 48” 1 150 .10 21 16 11 6 — 39 35 28 — — —200 .18 24 20 15 10 46 44 41 37 31 27 24250 .30 27 22 19 12 48 50 46 43 39 37 30100 .015 12 8 5 2 — — — — — — —200 .07 20 16 12 8 — 40 34 30 — — —

4821 48” 2 300 .16 25 20 18 12 45 49 44 44 36 29 33400 .29 29 24 20 16 49 54 50 51 46 38 39500 .44 33 26 22 18 52 59 56 57 54 46 46100 .01 8 4 2 1 — 33 — — — — —200 .05 17 11 8 4 — 36 29 — — — —

4822 48” 2 300 .12 22 17 13 8 46 46 41 39 31 — 28400 .24 25 21 17 11 49 52 48 47 43 34 36500 .38 28 23 20 14 52 56 53 54 51 45 43150 .01 20 13 8 4 — — — — — — —300 .07 28 22 20 13 — 40 33 — — — —

4831 48” 3 450 .15 35 28 24 20 45 50 44 44 37 28 33600 .21 40 33 28 22 51 56 52 54 48 40 43750 .40 45 36 31 25 56 61 58 62 57 49 51

1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2 Slot150 .01 6 12 3 8 1 5 1 2 — — — — — — —300 .05 15 20 10 16 6 12 3 8 — 38 30 — — — —

4832 48” 3 450 .13 21 25 16 20 11 18 6 12 44 50 42 42 34 — 31600 .23 24 29 20 24 15 20 10 16 51 55 52 51 45 38 39750 .36 27 33 22 26 19 22 12 18 56 62 59 58 54 47 47200 .015 12 8 5 2 — — — — — — —400 .07 20 16 12 8 — 43 36 35 26 25 24

4842 48” 4 600 .17 25 20 18 12 47 52 49 49 42 35 37800 .32 29 24 20 16 52 57 55 56 52 45 45

1000 .50 33 26 22 18 60 62 62 62 60 53 51

Static THROW FEETPressure Distance From Discharge Device, When FPM Equals Sound Power db

Model Nominal Number Drop Octave BandDFSB Length of Slot CFM (Inches) 50 FPM 75 FPM 100 FPM 150 FPM 2 3 4 5 6 7 NC

50 .01 4 2 1 — — — — — — — —100 .04 12 8 4 2 — 29 — — — — —

6011 60” 1 150 .10 15 12 9 4 — 39 33 31 — — 20200 .18 17 14 12 8 — 47 39 38 34 27 26250 .26 19 16 14 10 46 50 44 42 42 39 31100 .01 9 6 3 2 37 30 — — — — —200 .04 15 13 9 6 39 41 30 27 — — —

6021 60” 2 300 .04 19 15 13 9 43 48 42 40 33 — 29400 .20 22 17 15 13 47 53 50 49 44 34 37500 .31 25 20 16 14 52 57 56 55 53 48 44100 .01 3 2 1 — — — — — — — —200 .05 10 6 3 2 — 37 28 — — — —

6022 60” 2 300 .10 15 10 3 2 44 46 39 36 29 — 24400 .18 18 14 10 6 48 52 48 45 41 32 32500 .28 19 16 13 9 53 57 53 51 48 43 39150 .01 10 5 3 1 44 — — — — — —300 .04 24 17 10 5 46 39 30 30 — — —

6031 60” 3 450 .10 30 24 19 10 47 49 42 42 35 — 31600 .18 33 28 24 17 50 54 50 51 46 35 39750 .33 38 30 26 21 53 61 56 56 54 45 45

1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2-Slot 1-Slot 2 Slot150 .01 4 7 2 6 1 3 — 2 — — — — — — —300 .04 12 15 8 13 4 9 2 6 — 37 27 24 — — —

6032 60” 3 450 .10 15 19 12 15 9 13 4 9 44 47 39 39 31 — 28600 .18 17 22 14 17 12 15 8 13 50 52 47 48 41 35 36750 .27 19 25 16 20 14 16 10 14 58 58 53 53 49 43 42200 .01 9 6 3 2 — — — — — — —400 .04 15 13 9 6 48 35 31 32 — — —

6042 60” 4 600 .10 19 15 13 9 53 51 46 47 36 30 32800 .20 22 17 15 13 57 59 51 52 48 40 40

1000 .34 25 20 16 14 60 65 57 58 57 48 48

Page 27: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-199

PERFORMANCE DATA | Return Slot Diffuser (DFRB)

Sound Power db Model Nominal Number Static Pressure Octave BandDFRB Length of Slots CFM Drop (Inches) 2 3 4 5 6 7 NC

25 .01 — — — — — — —50 .06 — 31 27 24 — — —2411 24” 175 .11 40 39 36 34 32 — 23

100 .24 46 45 43 42 41 32 3250 .01 — 25 — — — — L

100 .07 — 34 30 27 — — L2421 24” 2150 .17 43 42 39 37 35 26 26200 .33 49 48 47 45 44 35 35

50 .01 — — — — — — —100 .05 — 30 22 — — — —2422 24” 2150 .11 43 41 34 31 30 23 21200 .25 47 48 44 40 38 31 29

75 .01 — 24 — — — — L150 .05 — 43 29 26 — — L2431 24” 3225 .12 45 44 38 35 35 27 26300 .23 48 46 45 42 43 33 34

75 .01 — — — — — — L150 .05 — 37 28 25 — — L2432 24” 3225 .12 46 45 39 35 31 27 23300 .24 49 51 47 43 39 31 32100 .01 — 24 — — — — L200 .05 — 33 25 — — — L2442 24” 4300 .13 46 44 37 34 33 26 24400 .25 50 51 47 43 41 34 32

Front View

Sound Power db Model Nominal Number Static Pressure Octave BandDFRB Length of Slots CFM Drop (Inches) 2 3 4 5 6 7 NC

30 .01 — — — — — — L65 .06 — 31 27 24 — — L3011 30” 195 .11 — 41 37 35 33 — 25

125 .24 47 46 44 43 42 33 3365 .01 — 26 — — — — L

125 .07 — 35 31 28 — — L3021 30” 2190 .17 44 42 39 37 35 26 26250 .23 50 49 48 46 45 36 36

65 .01 — — — — — — L125 .05 — 31 23 — — — L3022 30” 2190 .13 44 42 35 32 31 24 21250 .25 48 49 45 50 39 32 29

95 .01 — 25 — — — — L190 .05 — 44 29 26 — — L3031 30” 3280 .12 46 45 39 36 36 27 27375 .23 49 47 46 43 44 34 35

95 .01 — — — — — — L190 .05 — 37 29 26 — — L3032 30” 3280 .12 47 46 40 36 32 28 24375 .24 50 52 48 44 40 32 33125 .01 — 25 — — — — L250 .05 — 34 26 — — — L3042 30” 4375 .13 47 45 38 35 34 27 25500 .25 51 52 48 44 42 35 33

Page 28: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

PERFORMANCE DATA | Return Slot Diffuser (DFRB)

Linear, Plenum & Lt. Troffer S&R

A-200 www.carnes.com

Sound Power db Model Nominal Number Static Pressure Octave Band

Number Length of Slots CFM Drop (Inches) 2 3 4 5 6 7 NC50 .01 — — — — — — —

100 .06 — 34 27 24 — — —4811 48” 1150 .11 43 39 36 34 32 — 26200 .24 49 48 46 45 44 35 35100 .01 — — — — — — —200 .06 52 45 36 30 27 25 244821 48” 2300 .15 56 51 46 41 35 28 37400 .26 60 62 55 50 44 34 42100 .01 — — — — — — —200 .06 — 33 25 — — — —4822 48” 2300 .14 46 44 37 34 33 26 24400 .26 50 51 47 43 41 34 32150 .02 — — — — — — —300 .09 52 44 38 31 24 — 234831 48” 3450 .19 58 56 48 45 37 27 36600 .32 61 66 55 51 49 38 47150 .01 — — — — — — —300 .06 50 42 41 25 — — 254832 48” 3450 .15 54 56 44 39 31 — 36600 .25 64 63 54 48 40 31 43200 .025 — 28 — — — — —400 .09 55 46 35 31 27 26 274842 48” 4600 .19 58 58 49 45 41 31 38800 .31 64 65 58 53 45 37 46

Front View

Sound Power db Model Nominal Number Static Pressure Octave Band

Number Length of Slots CFM Drop (Inches) 2 3 4 5 6 7 NC63 .01 — — — — — — —

125 .06 — 35 28 25 — — —6011 60” 1190 .11 44 40 37 35 33 — 27250 .24 50 49 47 45 45 46 36125 .01 — — — — — — —250 .07 53 46 37 31 28 26 256021 60” 2375 .15 57 58 47 42 36 29 38500 .28 61 63 56 51 45 35 43125 .01 — — — — — — —250 .06 — 34 26 — — — —6022 60” 2375 .14 47 45 38 35 34 27 25500 .26 51 52 48 46 42 35 33190 .02 — — — — — — —375 .09 53 45 39 32 25 — 246031 60” 3560 .19 59 57 49 46 38 28 37750 .32 62 67 56 52 50 39 48190 .01 — — — — — — L375 .06 51 43 42 26 — — 266032 60” 3560 .15 55 57 45 40 31 — 37750 .25 65 64 55 49 41 32 44250 .03 — 28 — — — — L500 .09 56 47 36 33 28 27 286042 60” 4750 .19 59 59 50 46 42 32 39

1000 .31 65 66 59 54 46 38 47

Page 29: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-201

SUGGESTED INSTALLATION INSTRUCTIONS | Models DFSB & DFRB

Carnes Fixed Pattern Slot Diffusers Models DFSBSupply and DFRB Return are designed to be supported by the T-bar ceiling grid system. The diffuser utilizes the “T” for control of the air distribution pattern. If T-bars with a face dimension ofless than 15/16” are used, there may be dumping ofsupply air at low CFM’s.

The two way blow units straddle the main T-bar andare either wired to the T-bars that run perpendicularto the diffuser at each end or wired to structural supports above. The methods are shown below.

One way blow units are set along side the T-bar withthe air pattern blowing away from the T-bar. The oneway blow units are supported in the same manner asthe two way units.

After the slot diffusers are installed the support tilemust be trimmed and laid on the edge of the louverto fill out the opening. No additional T-bars arerequired.

STRUCTURAL SUPPORT

ONE WAY BLOWTWO WAY BLOW

Page 30: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

FIXED PATTERN SLOT DIFFUSERS | Models DFCA & DFDA

Linear, Plenum & Lt. Troffer S&R

A-202 www.carnes.com

Features� High induction horizontal air flow.

� Center down blow provides a vertical air pattern for exterior walls or glass.

� Supply/Return combination diffuser allows room air to be returned to ceiling plenums.

� Choice of 24”, 36”, 48” and 60” sizes.

� Choice of insulated or uninsulated units.

� Constructed of 24 gauge galvanealed steel. Deflector vane is extruded aluminum.

� Exposed surfaces painted flat black.

INLET SIZE06 - 6” Oval07 - 7” Oval08 - 8” Oval10 - 10” Oval12 - 12” Oval

INSULATIONN - UninsulatedR - Internal

Insulation

D - Down Blow(Sizes 36”, 48” and 60” Only)(Only Available on Model DFCA

FINISH06 - Flat Black (Default)11 - Bright White 01 - White

OPTIONS 1 2 3 4 5 6 7 8 9 10 11

D F C A 0 8 4 8 N 0 6

D - Diffuser

F - FixedPattern

DESIGNSERIES

C - Supply T-barDiffuser

D - CombinationSupply/ReturnDiffuser

DIFFUSERLENGTH24 - 24”36 - 36”48 - 48”60 - 60” V - Volume

ControlDamper

� MODEL NUMBERING SYSTEM —FIXED PATTERN - Models DFCA & DFDA

Page 31: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-203

DIMENSIONAL DATA | Fixed Pattern Slot Diffuser (DFCA)

MODEL DFCA — PRODUCT DESCRIPTION

MODEL DFCA — PERFORMANCE DATA

A

11/2”

A =11/16”

7/8”3/8”

Vane Detail(T-bar by Others)

INLET DIFFUSERSIZE HEIGHT (H)

6 8”8, 10 9”

Model DFCA is a one slot, one way, fixed pattern T-bar slotdiffuser. The Model DFCA is an excellent device forperimeter application and performs equally well for con-stant volume or variable air volume application. The ModelDFCA is constructed of zinc coated steel with an extrudedaluminum fixed air pattern deflector. The exposed face ofthe unit is painted No. 06 flat black as standard. The unitface can be painted No. 11 bright white. Units are available

in nominal 24”, 36”, 48” and 60” lengths. Standard inletsizes are 6”, 8” 10” and 12”. All inlets are oval construction.The Model DFCA is uninsulated as standard, but availablewith 1/2” black matte internal insulation.An optional inlet mounted volume control damper is alsoavailable.

CFM 60 80 100 120 140 160 180 20024” Ps .02 .03 .06 .08 .11 .14 .19 .23

LENGTH Throw 13 16 19 22 24 25 26 29NC (20) (20) (20) (20) (20) 22 26 29

CFM 90 120 150 180 210 240 270 30036” Ps .03 .04 .07 .10 .14 .18 .23 .29

LENGTH Throw 13 16 20 22 24 26 27 29NC (20) (20) (20) 22 25 29 32 35

CFM 120 160 200 240 280 320 360 40048” Ps .03 .05 .09 .12 .17 .22 .29 .36

LENGTH Throw 11 14 17 19 21 23 24 25NC (20) (20) 21 26 29 33 37 40

CFM 150 200 250 300 350 400 450 50060” Ps .03 .05 .10 .13 .18 .24 .31 .39

LENGTH Throw 9 11 14 15 17 18 19 20NC (20) 21 25 29 33 37 41 44

Ps — Static Pressure in inches of waterThrow — Distances in feet to terminal velocity of 50 fpm.NC — Noise Criteria based on 10 db room absorption.

DIMENSIONS

Size -1/4”

23/4”

H

Page 32: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

DIMENSIONAL DATA | Pattern Slot Diffuser w/Option D (DFCA)

Linear, Plenum & Lt. Troffer S&R

A-204 www.carnes.com

MODEL DFCA w/OPTION D — PRODUCT DESCRIPTION

MODEL DFCA w/OPTION D — PERFORMANCE DATA

B

BA

A

1-1/2”

2-3/4”

2-13/16”

1-1/2”

11/16”

Vane Detail(T-bar by Others)

INLET DIFFUSERSIZE HEIGHT (H)

6 8”8, 10 9”

Model DFCA with Option “D” has all the features of thestandard Model DFCA with the addition of a 12” long downblow section located in the center of the diffuser. With thedown blow option air is delivered both horizontally and vertically. Both end sections of the diffuser deliver entering

air in a horizontal air pattern effective distribution through-out the space. The vertical air pattern delivered by thedown blow section projects entering air down over the surface of a wall or window. The Model DFCA with option“D” is available in nominal 36”, 48” and 60” lengths.

CFM 90 120 150 180 210 240 270 30036” Ps .03 .06 .09 .13 .18 .23 .29 .35

LENGTH Throw H 11 16 19 22 24 26 27 29Throw V 4 5 5 6 6 7 7 8

NC 20 25 31 35 40 43 45 48CFM 120 160 200 240 280 320 360 400

48” Ps .03 .06 .09 .13 .18 .23 .29 .36LENGTH Throw H 11 16 19 22 25 26 27 29

Throw V 4 5 5 6 6 7 7 8NC (20) 24 30 33 39 42 45 48

CFM 150 200 250 300 350 400 450 50060” Ps .03 .06 .09 .14 .19 .24 .30 .38

LENGTH Throw H 11 16 19 21 24 25 26 27Throw V 4 5 5 6 6 7 7 8

NC (20) 24 30 33 38 42 44 47

Ps — Static Pressure in inches of waterThrow — Distances in feet to terminal velocity of 50 fpm.NC — Noise Criteria based on 10 db room absorption.Vertical throw values are based on standard 12” long down blow slot and 3/8” width setting.

DIMENSIONS

H H

Size -1/4”

View A-A View B-B

Page 33: MODEL NUMBERING SYSTEM | DA SeriesThe Carnes DA Series Adjustable Slot Diffusers are available in one, two, three or four slots for exposed T-bar ceilings. Models are also available

Linea

r, Plen

um &

Lt. T

roffer

S&R

www.carnes.com A-205

DIMENSIONAL DATA | Fixed Pattern Slot Diffuser (DFDA)

MODEL DFDA — PRODUCT DESCRIPTION

MODEL DFDA — PERFORMANCE DATA

Vane Detail(T-bar by Others)

INLET DIFFUSERSIZE HEIGHT (H)

6 8”8, 10 9”

Model DFDA is a combination supply/return T-bar slot diffuser. Itcombines the Model DFCA supply fixed pattern one slot diffuserwith an integral return air slot. The Model DFDA offers an excellent and cost effective method to supply conditioned air tothe space and return air to the ceiling plenum.The Model DFDA is constructed of zinc coated steel on the supply and return sections. The air slot has an extruded aluminum fixed air pattern deflector. The exposed face of the unit

is painted No. 06 flat black as standard. The unit face can bepainted No. 11 bright white.Units are available in nominal 24”, 36” 48” and 60” lengths.Standard inlet sizes are 6”, 8”, 10” and 12”. All inlets are oval construction.The Model DFDA is uninsulated as standard, but is available with1/2” thick black matte internal insulation. An optional inlet mounted volume control damper is available on the supply inlet.

CFM 60 80 100 120 140 160 180 20024” Ps .02 .03 .06 .08 .11 .14 .19 .23

LENGTH Throw 13 16 19 22 24 25 26 29NC (20) (20) (20) (20) (20) 22 26 29

CFM 90 120 150 180 210 240 270 30036” Ps .03 .04 .07 .10 .14 .18 .23 .29

LENGTH Throw 13 16 20 22 24 26 27 29NC (20) (20) (20) 22 25 29 32 35

CFM 120 160 200 240 280 320 360 40048” Ps .03 .05 .09 .12 .17 .22 .29 .36

LENGTH Throw 11 14 17 19 21 23 24 25NC (20) (20) 21 26 29 33 37 40

CFM 150 200 250 300 350 400 450 50060” Ps .03 .05 .10 .13 .18 .24 .31 .39

LENGTH Throw 9 11 14 15 17 18 19 20NC (20) 21 25 29 33 37 41 44

Ps — Static Pressure in inches of waterThrow — Distances in feet to terminal velocity of 50 fpm.NC — Noise Criteria based on 10 db room absorption.Vertical throw values are based on standard 12” long down blow slot and 3/8” width setting.

Internal Insulation(Optional)

CFM PER FOOT 30 40 50 60 70 80 90 100NEGATIVE Ps .01 .02 .03 .04 .06 .07 .09 .11

RETURN SLOT PERFORMANCE

1-1/2”

11/16”

5-1/4”

2-3/4”