MiniTrainerSchool
For the MicroPLC from Lovato Electric Basics of Ladder Diagram and Function Block Diagram programming with
the Lovato software LRXSW with many practical exercises on Lovato-MiniTrainer
Zeitrelais T1 Time relay T1 LAD4
Enable
Reset
Output
I2 Start
Q2
I4
��������� ���������������� ������������
�������� ��������������� ����������
������� � �������������� ���� �������������
MODE
T01
LRD 12
���������������������� �����������
Silo / Tank
IA1
Q1
Q3
PWM
Silo / tank
LRD12
FBD14I1 Start/Stopp
Voll
Enable
M
2
3
This exercise book serves as an introduction to the world of MicroPLC
LRD12 and LRD20 of Lovato Electric.
It provides a modern small controller that offers many ways to implement a customer-
centric automation.
Thanks to the various programming languages the LRD… provides something for
everyone. Along with the MiniTrainer, it offers an ideal practice and learning platform
for education and training.
In this exercise book, the basic building blocks of the ladder diagram and function
block programming can be learned with many training examples.
Of course, individuals are free to reshape the exercises or expand.
On the enclosed CD there is a proposed solution offered to each exercise. The
exercise cards for the MiniTrainers are enclosed in two versions. On one hand, the
Lovato-MiniTrainer with the LRD12 and on the other hand for the Lovato-
MiniTrainerXL with the LRD120, with more I / O points.
Lovato Electric GmbH (Germany) Im Ermlisgrund 30, 76337 Waldbronn Tel.: +49 (0) 72 43.76 69 37-0 Fax: +49 (0) 72 43.76 69 37-9 E-Mail: [email protected] Web-Site from Lovato-Electric: www.lovato.co.uk Author: Klaus Machalek 1 Edition 2014 (02/14) All rights, including translation, are reserved. No part of this book may be reproduced in any form (print, photocopy, microfilm or any other process) without the written permission of the author or processed using electronic systems, duplicated or distributed. Of these, which expressly referred to in § 53, 54 of the Copyright Act except the cases are not affected.
4
Table of Contents
1. Hardware construction 7
1.1 Exercise equipment 7 1.2 Technical data of the exercise equipment 7 1.2.1 MicroSPS: LRD12TD024 7
1.2.2 MicroPLC: LRD20TD024 8 1.3 Lovato-MiniTrainer 8 1.3.1 Assignment of inputs and outputs on the Lovato-MiniTrainer 9 1.4 Lovato-MiniTrainerXL 9
1.4.1 Assignment of inputs and outputs on the Lovato-MiniTrainerXL 10 1.5 Selecting the programming software 11
2. Ladder diagram (LAD) 12 2.1 circuit diagram window 15 2.2 Creating a circuit diagram 15 2.3 Series circuit 17 2.4 Parallel circuit 17
2.5 Digital outputs Q/Y and markers M/N 18 2.6 Boolean algebra as a basis 19
2.6.1 Logical combinations in the LAD Editor 20 2.6.1.1 AND-operation 20 2.6.1.2 OR-operation 21 2.6.1.3 AND- before OR operation 22
. 2.6.1.4 OR before AND operation 23 Exercise: Basic circuits with the LAD Editor: LAD 1a / LAD 1b / LAD 1c 24
2.6.1.5 Latching 25 Exercise: Latching: LAD2, LAD3 26
2.6.1.6 Priority processing - dominant 27 2.7 Simulation 28 2.7.1 Simulation on the virtual controller 29 2.8 Der Online-Test 30
2.8.1 Coupling 30 2.8.2 Program transfer 31
2.9 Time relay (timer) T 32 2.9.1 Configuration window of time relay (timer) 32 2.9.2 Setpoint input at time relay 34 2.9.3 Presentation of the timer in the circuit diagram LAD 35 2.9.4 Display of the timer on the display of LRD… 35 2.9.5 Change the setpoint on display?. 36
Exercises: Time Relay T: LAD4, LAD4a, LAD4b, LAD5a, LAD5b, LAD6, LAD7 37 2.10 Differential Instruction D 39 2.11 Counter C 40 Exercises: Counter C: LAD8, LAD8a, LAD8b, LAD9 42
2.12 Shift register S01 43 Exercises: shift register S01:LAD10, LAD11, 44 2.13 Analog comparator G 45 Exercises: Analog comparator G: LAD12, LAD13, 46
2.14 Real Time Clock R 47 Exercise: Real Time Clock R : LAD14 48
2.15 Arithmetic blocks AS (ADD / SUB) and MD (MUL / DIV) 49 Exercise arithmetic AS: LAD15 50
2.16 Data register DR 51 Exercise: Data register DR: LAD9a 51
2.17 Multiplexer MX 52
5
2.18 Text display H 53 Exercise: Text display H:LAD16 55
2.19 Comments for coil and contacts 56 2.20 Headlines and comments in the Ladder Diagram 57
3. Function block diagram FBD 58
3.1 Creating a function block diagram 60 3.1.1 draw connections 61
3.2 Logic sets in the FBD-Editor 62 3.2.1 AND operation 62 3.2.2 AND NOT-operation (NAND) 63
3.2.3 OR operation 64 3.2.4 AND before OR operation 65 3.2.5 OR before AND function 66 3.2.6 OR-NOT operation (NOR) 67 3.2.7 Exclusive-OR (XOR) 68
Exercises: Logic blocks: FBD1a, FBD1b, FBD1c 69 3.2.8 Latching function 70
Exercise: latching function:FDB2a, FDB2b, 71 3.3 Selection menu of the Function Blocks 72
3.3.1 Timing relay T 72 3.3.2 Pulse relay 74
Exercise: Timer relay: FBD3, FBD4a, FBD5 75 3.3.3 Counter C 76
Exercise: Counter: FBD6a, FBD6b, FBD6c, FBD7a, FBD7b 78 3.3.4 Shift register S01 79
Exercise: Shift register: FBD8a, FBD8b 79 3.3.5 Analog comparator G 80
Exercise: Analog comparator: FBD9a, FBD9b, FBD9c 81 3.3.6 Multiplexer MX 82
Exercise Multiplexer: FBD10 82 3.3.7 Boolean function BL 83
Exercise Boolean function BL: FBD11, FBD12 83 3.3.8 Pulse-width modulation (PWM) P 85
Exercise PWM: FBD13, FBD13a, FBD14 85 3.3.9 Text H 87 3.3.10 Display backlight 87
4. Useful information 88
6
Contents of the CD
Solutions In LADDER diagram (LAD) in Function block diagram (FBD)
7
1. Hardware construction 1.1 Exercise equipment Lovato Electric GmbH, the manufacturer of MicroPLC LRD12 and LRD20, offers a wide range of different devices. Starting on the number of input and output points of extensibility to the different supply voltages. In this basic course, the devices LRD12 and LRD20 will apply. Once the low cost LRD12 with the small Lovato-MiniTrainer and another with the LRD20 and the Lovato-MiniTrainerXL for more inputs and outputs. Thus, both versions offer a simple and inexpensive way to implement the exercises here used in the book and also to supplement. 1.2 Technical data of the exercise equipment
1.2.1 The MicroPLC LRD12TD024 This MicroPLC provides eight digital 24 VDC inputs in addition to the 24 VDC supply. Of these, the inputs A1 and A2 can be alternatively used as analog inputs.
Note: For the MiniTrainer can either be used the LRD12TD024 with 4 relay- or 4 transistor outputs.
The display offers the representation of LAD, FBD and text.
Power supply 24 VDC
8 inputs 24 VDC A1 and A2 digital and alternatively usable as analog inputs 0 ... 10V
4 relay or 4 transistor outputs
USB interface to PC
Cursor key activated as Z inputs
Figure 1.1 LRD12TD024
8
1.2.2 MicroPLC: LRD20TD024
Firstly, this exercise utilises the larger design controller. This makes it possible to use more inputs and outputs and thus to make the exercise offer interesting and varied. The MiniTrainer now has the designation Lovato-MiniTrainerXL.
Preferably, the transistor variant LRD20TD024 should be used, that way you can also use the PWM functionality better.
1.3 Lovato-MiniTrainer
Figure 1.3 Lovato MiniTrainer
Figure 1.2 LRD20TD025
9
1.3.1 Assignment of inputs and outputs on the Lovato-MiniTrainer:
1.4 Lovato-MiniTrainerXL The MiniTrainerXL offers in addition to the 8 latching / momentary switches (I1 to I6 / I9 and A1) or 2 push buttons (red) as the changer inputs I7 / I8 and IB / IC operate. They are as shown in the sketch, wired: Latching/momentary switches By using the buttons X1 - X4 as real wire break simulations, start-stop functions can be implemented.
I7 I8 IB IC
24 VDC-power supply
The NC I8 and IC can be switched off via the slide switch. Thus all inputs via the interface connector are available and have no default
I9 IA
Figure 1.4 MiniTrainer simulation field Figure 1.5 I/O assignment of LRD12
Figure 1.6 addition button on the Lovato-MiniTrainersXL
10
1.4.1 Assignment of inputs and outputs on the Lovato-MiniTrainerXL:
Lovato-MiniTrainer XL
I9 IA IB IC
Figure 1.7 MiniTrainerXL simulation field
Figure 1.8 I/O assignment of LRD20
Figure 1.9 Lovato-MiniTrainerXL
11
1.5 Selecting the programming software The first part of this book deals with the ladder diagram programming. In the second part of the function block is handled. The software offers comfortable implementation of control and regulation functions in the standard PLC languages: Ladder Diagram (LAD) and function block diagram (FBD). To create a new project, first the desired programming language must be selected. Either ladder programming (LAD) or function block programming (FBD).
LAD=LadderDiagram=(LD) FBD = Function Block Diagram language
LAD (LADDER) FBD
Note: A ladder diagram (LAD) is not in a function block diagram (FBD), or convertible and vice versa!
Figure 1.10 LAD- and FBD-Button
12
2. The Ladder diagram (LAD) (in the Software called „LADDER“) The corresponding button is clicked to reach the LAD Editor. The next step is to select the right MicroPLC. This is necessary in order to assign the right program of the controller. For this purpose, the "NEW" button is clicked.
LADDER LAD
Picture 2.1 Start-Menu of the LRXSW for opening LAD
Picture 2.2 Start-Button
13
The selection is based on the device type identifier: Note: This choice is also possible later on in the "Operation" -> "Module System Set" Is the correct device selected via the pull-down button will be confirmed with OK and the LAD Editor opens. The Ladder Editor is divided into the following areas: circuit diagram window Information on the circuit diagram Operations
Selection of contacts and coil
Assignment list of contacts and coils
It appears in the device selection window:
Picture 2.3 device Selection
14
In order to interpret correctly the symbols you place the mouse on the icon, and after a moment the icon's function appears. The symbol for the outputs Q/Y and the markers M/N again shows the contact and once the coils function. Cursor keys (Z) on the MicroPLC
External inputs (X) digital (extension) inputs (I) In the left window of the editor, the contacts and coils used are displayed. Clicking the button opens the complete selection table. Note: The individual short names (Y, M, T, C, R, G, H, ..) are explained in the relevant exercises.
Picture 2.5 Contact- and coil function
Picture 2.6 Occupancy list
15
1 2 3 4 5 6 7 8 9 etc.
2.1 Circuit diagram window The ladder program is created in the circuit diagram window. It can be constructed of a maximum of 300 rungs with a maximum of three contacts and one coil. If you need more than 3 contacts in a rung you need a temporary result memory, a marker M or N.
2.2 Creating a circuit diagram Use the mouse pointer to select the contact icon. As an example, we select the input. When the icon is left appears as a crayon. Using the mouse, now the contact to the right position is out in the rung. This is the "pen" and as long as provided with a prohibitory sign, as long as no contact inserted, the field is reached. Only when the prohibition sign is gone, the contact can be set. If the position is reached, the contact with the left mouse button "placed". It opens directly the selection window "Edit contact" through which you enter the parameter.
Indication of the remaining open spots
Picture 2.7 The Schematic window
Picture 2.8 describe contact
16
This window will also determine whether the contact is normally open or normally closed. A subsequent correction is possible in this menu. With OK the configured contact in the ladder diagram is visible. Note: Unless the right mouse button or the ESC key is pressed, the "pen" is retained and it may be the next position to be selected. In the toolbar, there are a lot of contacts and coils of different functions. In this book, some are handled. But experience shows that many functions even tell if you have worked through the book.
Note: In the circuit diagram the name of contacts appears different: NO (normally open) NC (normally closed)
Picture 2.9 Toolbar
Picture 2.10 N.O.-contact Picure 2.11 N.C.-contact
17
2.3 Series circuit As a first example to three NO contacts switch the output Q01 in series:
If you want to associate less than 3 contacts in series, one needs an "AND-Line". This function is as an icon button in the bottom toolbar: AND-Line
Note: This connection is used instead of a contact!
2.4 Parallel circuit For this example, we use the previous example of the series circuit and add this with two parallel contacts I04 and I05. For this purpose, the software in the toolbar “OR-Line” button for the parallel branch: OR-Line Example of a parallel circuit:
Shows the occupied contacts and coils with a star
Picture 2.12 First line
Pictue 2.13 AND-Line
Picture 2.14 OR-Line
Picture 2.15 parallel circuit
18
2.5 Digital outputs Q/Y and markers M/N The digital outputs and markers of MicroPLC can be set in different functions. As standard the selected output or marker is used as a dynamic coil. This means that the output or marker behaves as a contactor. Further functions are:
Set-function Reset-function
P = puls-function These different opportunities are illustrated in the circuit diagram as follows: Dyn. coil: -[ = Set-coil = Reset-coil = Puls-coil =
Note: The function of the output can be changed at any time by double clicking on the corresponding coil function.
Picture 2.16 discribe coils
Pictur 2.17 coils
19
2.6 Boolean algebra as a basis The primary task of MicroPLC LRD is the linking of several NO and NC contacts after a certain logic. This logic corresponds to a series (AND circuit) or a parallel (OR circuit) in a wired contactor or relay control. The link can be specified in the LRD either
Ladder Diagram = LAD or function block diagram = FBD.
This plan is stored in non-volatile semiconductor memory of the LRD. It is important to note that the MicroPLC cannot detect whether an incoming signal from the outside of a make or break comes. The LRD "remembers" only if the 24 VDC voltage is applied to the inputs or not. In the circuit diagram or logic diagram, the logic state of the inputs is always queried and not the function of the actuator.
20
Picture 2.18 AND-operation Picture2.19 Wiring to the PLC
Picture 2.20 AND-operation in LAD
2.6.1 Logical combinations in the LAD Editor
2.6.1.1 AND-operation
The AND-operation corresponds to the series circuit in a conventional wired contactor control that means the output is switched on when all switches are closed. The following example shows a better understanding of how an AND-operation takes place in old fashion wired contactor technology and how the implementation of the LRD12. Example: Logical AND-operation with three switches: Realization in wired contactor circuit Realization with the LRXSW:
The output signal (H1), an AND-operation is then logic "1" when all the input signals (S. ..) have the state "1". The "1" stands for an actuated normally open or a normally closed contact is not actuated. True list: FBS: Logic algebra: S1 S2 S3 H1 0 0 0 0 1 0 0 0 0 1 0 0 1 1 0 0 0 0 1 0 1 0 1 0 0 1 1 0 1 1 1 1 Presentation in the LRXSLAD:
ZelioLogic2
H1 H1
S1
S2
S3
Relay 1
AND
S1 S2 S3
H1
H1 = S1 & S2 & S3
LAD
S1 S2 S3
I1 I2 I3
LRD12
Q1
21
Picture 2.21 OR-operation Picture2.22 Wiring to the PLC
Picture 2.23 OR-operation in LAD
2.6.1.2 OR-operation The OR-operation corresponds to the parallel circuit in a conventional wired relay control, that is, the output is then turned on when at least one of the switches is closed. The following example shows a better understanding of how an OR operation in old fashioned wired contactor technology and how the implementation of the LRD 12 takes place. Example: logic OR-operation with three switches Realization in wired contactor circuit Realization with the LRXSW: The output signal (H1), an OR operation is then logic "1" if at least one or more input signals (S. ..) have the state "1". The "1" stands for an actuated normally open contact or a non-actuated normally closed contact. True list: FBS: Logic algebra: S1 S2 S3 H1 0 0 0 0 1 0 0 1 0 1 0 1 1 1 0 1 0 0 1 1 1 0 1 1 0 1 1 1 1 1 1 1 Presentation in the LRXSLAD:
S1 S2 S3
Relay1
H1 H1
OR
S1 S2 S3
H1 H1 = S1 V S2 V S3
LAD
S1 S2 S3
I1 I2 I3
LRD 12
Q1
22
Picture 2.24 AND before OR operation Picture2.25 Wiring to the PLC
Picture 2.26 AND before OR operation in LRXSLAD
2.6.1.3 The AND- before OR operation
The three switches to be logically combined in AND and OR. The input of this logic is based on the basic rule of Boolean algebra:
Point are performed before addition and subtraction
In the implementation in the wiring logic, this means:
Series circuit is going on parallel circuit The following example shows the implementation a combined AND-OR circuit according to the rule above mentioned: Realization in wired contactor circuit Realization with the LRXSW: S1 S3
True list: FBS: Logic algebra: S1 S2 S3 H1 0 0 0 0 1 0 0 0 0 1 0 0 1 1 0 1 0 0 1 1 1 0 1 1 0 1 1 1 1 1 1 1
Relay1 H1
H1
H1 = S1 & S2 V S3
AND
S1 S2
S3
H1 OR
LAD
S1 S2 S3
S2
Q1
I1 I2 I3
LRD 12
23
Picture2.28 Wiring to the PLC Picture2.27 OR before AND operation
2.6.1.4 The OR before AND operation
Four switches will be connected in logic OR and logic AND: The input of this logic is also called conjunctive form. Since the Boolean rule applies here, it must be used with braces. Thus, it specifies that the OR operation is processed first. The representation in the application program corresponds to the international standard IEC 61131. The following example shows the implementation a combined AND-OR circuit following the rule above mentioned: Realization in wired contactor circuit Realization with the LRXSW
True list: FBS: Logic algebra: S1 S2 S3 S4 H1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 1 1 0 0 0 0 0 1 0 0 1 0 1 0 1 0 1 1 0 1 1 1 1 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 1 1 1 1 0 1 1 0 0 1 1 0 1 0 1 1 1 0 1 1 1 1 1 1 1 1 1
Relay1
LRD 12
I1 I2 I3 I4
Q1
H1
H1
S1 S2 S3 S4
S1 S2
S3 S4
H1 = (S1 V S2) & ( S3 V S4)
OR
OR
AND H1
S1 S2 S3 S4
24
Picture2.29 OR before AND operation in LAD
Presentation in the LRXSLAD:
Exercise: Basic circuits with the LAD Editor LAD 1a / LAD 1b / LAD 1c
LAD
I1 I2 I3
I4
I5 I6
I9 I0A
Q1
Q2
Q3
Q4
LAD 1a
LRD12
I1 I2 I0A
I3
I4 I6
I5 I9
Q1LAD1b
LRD 12
I1 I2
I3
I4
I5 I6
I9 I0A
Q1LAD 1c
LRD12
Q2
Picture 2.30 Exercise card LAD1a
Picture 2.31 Exercise card LAD1b
Picture 2.32 Exercise card LAD1a
25
Picture 2.33 dyn. latching in LAD
Picture 2.34 static latching in LAD
2.6.1.5 Latching In control engineering, the function of latching is often use, especially when using buttons will execute a stored function. A typical task is the turning on and off of a motor. The ON button is always a normally open and the OFF button always normally closed. Why the OFF button is normally closed, has something to do with the wire breakage. The VDE regulations state that in the event of a wire break in the relevant section a motor must be switched off immediately and must not be turned on. To realize a latching in the LRD12 and LRD20 the MicroPLC offers two variants. 1. The dynamic control of the output: If the result of logic operation (RLO) is on , the output is on, too. If the RLO is low , the output is low, too.
2. The static control of the output Latching function with SET and RESET commands. Both commands work with the rising edge.
26
Picture 2.35 Exercise card LAD2
Picture 2.36 Exercise card LAD3
Exercise: Latching
Exercise LAD2: Latching with dynamic triggering of Q2 (Like the classic relay and contactor control)
Exercise LAD3: Latching with static triggering of Q2 (Like classical electronic controls via flip-flops)
With these exercise cards the topic of wire breakage is practiced. For all programmable logic controllers (PLCs) you must make sure which switch or push button is installed on the machine or plant. Is it a N.O. or N.C. contact? This is important because according to VDE 0113 turn off must be by opening a circuit. By using an N.C. to the input terminal of a PLC, this always has power at the input terminal in the non-actuated state. If you were to now integrate the input by an N.C. in the schematic, so you return the signal of the external switch. This has the consequence that e.g. a motor off by opening the circuit at the input of the PLC. This can be life-threatening. Thus, we conclude that one must always think twice when you include one outside the PLC wired N.C. in the program as N.O. or N.C. to be failsafe.
I5
I3
I4Q2
Selbsthal teschal tung seal-in circui t LAD 2
Start Stop Bimetall
Q2
Bei der Programmerstellung ist auf die Drahtbruchsicherheit zu achten!
In case of programming pay attentionto the fail-save c ircuit
LRD 12
I6
I3
I5
Q2
Selbsthal teschal tung mit SET und RESET Seal-in circui t wi th SET and RESET LAD 3
Start
Bei der Programmerstellung ist auf
S
R
die Drahtbruchsicherheit zu achten!
In case of programming pay attentionto the fail-save c ircuit
LRD 12
27
1a
1b
1c
1b
1c
1a
Picture 2.37 Priority processing in LAD
2.6.1.6 Priority processing - dominant Another important overview is the priority of functions. The program processing is always from top to bottom, is in the ascending line numbering. The example shows how important it is in which line the output or marker are standing. This is also important with respect to the priority in the setting and reset command. If I1 and I2 are pressed simultaneously, the RESET command has priority. I3 and I4 are pressed simultaneously, the SET command has priority. If a coil is several times assigned,it is also true that the ascending line numbers, the last assign which affects the coil to the outside. Internally, the coil of the output or marker "1" or "0" as long as no change is made in the following lines.
28
Picture 2.38 Tools in LAD
Picture 2.39 View menue
Picture 2.40 OR-Line and AND-Line
2.7 Simulation After the last link is ready, this is simulated with the help of LRXSW, i.e. tested without control (off-line). For this we change into the SIMULATION MODE:
Depending on the settings more windows are opened simultaneously. Since we are interested only in the inputs, the other windows can be closed. This takes place using the "View" “ By clicking on the fields, tools can show or hide!
By clicking the button icons in the "Input Status Tool", the corresponding switch in the LAD is displayed in green. If the rung is virtually closed, that is, from left to right is a continuous green line, then the output is also available in green. (The connecting lines "OR-Line" and "AND-Line" always appear in green)
29
Picture 2.41 keypad button
Picture 2.42 Keypad-Simulator
2.7.1 Simulation on the virtual controller In addition to simulating the circuit diagram, the controller also provides a pictorial representation of LRD12 with the connected switches and lamps. You can reach this simulation by clicking the "keypad"
By clicking the "Run" button, the program can now be tested on the simulator. Click switch Current paths, the bold appear to be "flown through" virtual power!
Outputs
With the mouse, you can also use the cursor buttons to operate virtually and thus retrieve the LRD12 the menu and use. Note: In this virtual control simulator parameters can be changed, but the function of a function block cannot.
Run
30
Picture 2.43 Cuppling to the PC
Picture 2.44 Link Com Port…
Picture 2.45 Select Link Com Port…
Picture 2.46 Connect successfully
2.8 The Online Test 2.8.1 Coupling Before the transfer of a program can be done in the controller, some settings must be checked, or set. These settings, bring the selected control to meet the actual control system. If this is not the case, the LRXSW recognizes and cannot connect. The USB programming cable is plugged into one of the USB ports of the PC. If the connection is made, and power is connected, then the coupling of the software can be made: 1. Click "Operation"
2. Click "Link COM Port" 3. Select the interface "COM port"
4. Click Connect "link"!
If the coupling was successful, this is indicated by a message on the screen.
The exact type of control can be found on the left side wall! example: LRD12TD024
The protective cover should be pulled out and the plug inserted carefully. The cable goes from the left.
31
Picture 2.47 Read and Write Button
Picture 2.48 Message
Picture 2.49 Transfer o.k.
Picture 2.50 Run and Stop Button
Picture 2.51 Message
2.8.2 Program transfer The next step is to transfer the program into the controller. For this the LAD editor provides two buttons. One to write the program into the control "write" and another to read the program again from the controller back to the PC "read". Read from the LRD… write into the LRD… After a safety prompt with the hint that you could possibly overwrite a program in the control (clear).
If you confirm with "Yes", the program is transferred to the controller. Then you acknowledged with the “OK” for transfer: With the "Run" button the program starts in the controllerand with the "Stop" button, the program can be stopped anytime from the PC. If you click "Run", the system asks whether the program should be read back from the controller. This makes sense if you just want to see the online status display.
32
Picture 2.52 Tools
Picture 2.53 Timer select
Picture 2.54 Timer mode1
Picture 2.55 Timer mode2
2.9 Time relay (timer) T The MicroSPS LRD… provides 30 timing relays with different possible functions. The button "T" is chosen from the lower function selection panel to open the configuration window for the functions and their settings.
2.9.1 Configuration window of time relay (timer):
Selection of 30 possible timer addresses: 01…09, 0A…0F, 10…19,1A…1F
Function of the output coil of the timer (Output Type):
–[ = Dynamic coil (in the example selected) P = Pulse output
Function of the timer depending on the output coil
(Output Type): Mode 0 – 6 for : –[ Mode 7 for : P
Mode 0: internal coil (like a marker)
Mode 1: On-delay timer
Flow diagram
Mode 2: ON-delay timer with reset input. If the enable is off, the timer stops. Only if the Enable is "ON" the time is running on again.
33
Picture 2.56 Timer mode3
Picture 2.57 Timer mode4
Picture 2.58 Timer mode5
Picture 2.59 Timer mode6
Picture 2.60 Timer mode7
Mode 3: OFF-delay timer.If the rising edge of Enable (0 -> 1), the output is "ON". Time is running only when the Enable flank falls (1 -> 0). If Enable is turned on again during the running time, the actual value is set to "0". The timer can be restarted.
Mode 4: OFF-delay timer. When a falling edge of Enable (1 -> 0), the output is "ON" and the time is running out. If Enable is turned on again during the running time, the Actual value of the timer is reset to "0". The timer can be restarted.
Mode 5: Synchronous flasher (1:1) (ON-time = OFF-time) The output of the timer flashes while the Enable "ON".
D Mode 6: Synchronous flasher (1:1) M (ON-time = OFF-time) The output of the
Ö timer flashes once to Enable an edge G change from 0 - done> 1. The output D flash until an edge change from 0 -> 1 F at the Reset input is done.
Mode 7: Asynchronous flasher (1: n) (ON-time is not equal the OFF-time) The output of the timer flashes while the Enable "ON".
34
Picture 2.61 Timer parameter
Picture 2.62 Timer mode7
2.9.2 Setpoint input at time relay The input for the time functions are also included in the menu window of the timer corresponding to the mode that is set.
By default, the time base is set to 10ms. That the smallest default value for the timer is 10 ms.
„PresetValue“ Setpoint input with consideration of the time base (SEConds or MINuntes)
"Preset Type" is used when the target value from another block comes. So, for example, is "A" for analog input or "C" for a counter output. If setpoint "Preset Value" is specified, the Preset Type = "N" (Not)
For the asynchronous flasher (Mode 7) Two setpoints are required. Accordingly, two setting ranges (T01 and T02) are provided.
The time base
from … to 0,01 … 999,9 s 0,1 … 9999 s 1 … 9999 s 1 … 9999 min
35
Picture 2.63 Timer in LAD
Picture 2.64 Timer in Run
Picture 2.66 LRD… Menue
Picture 2.67 LRD-Display Timer in Run
2.9.1 Presentation of the timer in the circuit diagram LAD If the timer is configured, it is shown in the circuit diagram as follows: Mode (0…7)
Current value Setpoint
In the run status of the timer is displayed as follows: Current value
2.9.4 Display of the timer on the display of LRD… In addition to the status display on the screen, it is particularly convenient when for example you can read the value of the timer and the controller. This is often a great help for setup or troubleshooting. For this purpose, proceed as follows: If the controller is in Run mode, it comes with pressing the button in the following menu: The cursor key leads to the circuit diagram. There you go using the arrow keys on the corresponding block and confirm . Use the key to get back into the schematic.
��������
������������
������������
�������
36
Picture 2.67 LRD-Display: in Stop mode
2.9.5 Change the setpoint on display? Many times it happens in the everyday life of a machine or system that a value needs to be adjusted, but there is no PC for set-point modification. For this the controller offers, thanks to its built-in display among other things, the possibility to change settings. The change is ALWAYS in STOP mode. With the keys is now the timer component T1 called:
1. Press the key.
2. Go with the Cursor-key up and confirm.
3. Use the cursor button to repeatedly tap to the left until the position is reached at which point the value is to be changed.
4. Pressing the button, the position is confirmed and the cursor line below the number flashes.
5. Use the cursor keys and now the new value can be set.
6. If the value is correct, you confirmed with and leave the menu with
37
Picture 2.68 Exercise card LAD4
Picture 2.69 Exercise card LAD4a+b
Picture 2.70 Exercise card LAD5a+b
Exercises: Time Relay T
LAD4: With the exercise card " Time relay T1" first we test all the modes of a timer!
LAD 4a: Based on the adjacent exercise card is a reflector light barrier (I02) four monitoring lights (Q1 ... Q4) switch for 10s. To switch on it is enough if, for example, a person shortly interrupts the light barrier. With each new interruption of the photocell, the timer is restarted. Which mode is useful here? LAD 4b: The interrupt pulse of the light barrier is to be fixed at 0.2 s.
LAD 5 a: A toilet light and fan control is to be implemented using the LRD…. If someone enters the bathroom and switched on the light, after 4s the fan runs on as well. Only when the toilet is left and the light is switched off, the fan runs for 8s and then switches off.
LAD 5b: In addition to LAD 5a, the fan should now run after 20 s, when the toilet is used for longer than 20 seconds and the light is longer than 24s on.
?
Zeitre lais T1 Time relay T1 LAD4
Enable
Reset
Output
I2 Start
Q2
I4
��������� ���������������� ������������
�������� ��������������� ����������
������� � ������������������ �������������
MODE
T01
LRD 12
���������������������� �����������
Toi letten -Licht-LüftersteuerungToi let -Light-and-Fan Control
Controlador de la luz y el venti lador de un bano
S5
Licht
lampluz
Lüfter
fanventi lador
Schalterswi tchin terruptor
Q1
Q2
~
LRD 12
LAD 5a + b
38
Picture 2.72 Exercise card LAD7
Picture 2.71 Exercise card LAD6
0 1 2 3 4 5 6 15s
LAD 6 - Lighthouse: On the North Sea coast are navigation beacons for safe orientation. These can be seen from a distance and in the dark they have different identifiers to see which beacon is which. They are the broken fire (Oc), the common-mode fire (iso) and the flashing light (LFI). These three identifiers will now be realized with the help of exercise LAD6 card. 1) Lighthouse from Westerheversand - Oc(3) 15:
3 dark phases of 1s and the two pauses of 1 s. Then is permanent light. The repeat is done every 15s. 2) Lighthouse from Büsum- Iso 6s: 0 3 6s
On 3s and off 3s 3) Lighthouse from Helgoland- LFI 5s: 0 5s
all 5s a flash fire <1s (600ms)
LRD 12
Q1
Leuchtfeuer / Navigational l ight
Q2
Q3
I1
I2
I3
Westerheversand
Büsum
Helgoland
LRD12
Ampel / Traffic light LAD 7 LAD7:
In metropolitan areas, side road access to highways is controlled in heavy traffic with a traffic light. The traffic light shows RED when the main switch I01 is turned on. An induction loop in the road surface before the traffic light detects an incoming vehicle. With 1s delay starts the traffic light cycle, which also takes 1 sec each for the individual phases. At the end of the traffic light cycle the lights are back on RED. If the induction loop is connected constantly, so the traffic lights cycle runs through the 1 sec intervals.
39
Picture 2.73 D puls when ON
Picture 2.74 D-puls when OFF
2.10 Differential Instruction D The "positive" pulse is for one program cycle "ON" if the series contact switches from OFF -> ON.
The same function but with the opposite sign is the inverse of the "D" contact.
40
Picture 2.75 counter parameter
Picture 2.76 counter in LAD
Picture 2.77 Reset Input of the counter
2.10 Counter C
Like the timer, the counter is also a function block that needs to be configured only. The MicroPLC offers 30 counter blocks, each with 8 different modes.
Mode 0: internal coil (like a marker) Mode 1: up-down counter without overflow. If the setpoint = actual counting up is blocked. The counting is stopped if the actual value = 0. The actual value is non-retentive. It loses its value when you turn off the controller. Setpoint input (0 ... 999999) Variables specification (for example: the result of arithmetic) Note: In LAD circuit diagram ONLY be linked the counting coil and the switching output of the counter. The specification of the counting direction (Direction set) and the reset Input of the counter value can be selected in the configuration window and displayed as in the example:
"Low" = "0" = no specification The representation in the LAD editor provides the following information:
If you want to reset the counter and / or changing direction, then the menu offers various options: Low = not specified for example: Reset Input
I = Input base unit X = Input expansion unit Z = cursor keys (arrows) as inputs etc
Counting coil
Switching output of the counter
Mode
Direction
Reset Input
Setpoint
Actual value
41
Picture 2.78 counter mode2 Picture 2.79 counter in stop
Picture 2.80 counter in Run mode
Mode 2: up-down counter with overflow.
If the setpoint = actual value of the count input is not locked. The counter continues to count. The actual value is non-retentive. It loses its value when you turn off the controller.
Example, in the LAD representation:
Note to "reset input" and "Direction Set" in Mode 2:
• "Reset input" has two functions. When pressed while counting the reset, the current value of the counter is set to "0". When pressed while counting down the reset, then the setpoint "Preset Value" is set!
• If the setpoint is reached when counting, the output switches the counter to "ON". Now, if the direction is switched, the output switches to "OFF" and again until the actual value = "0", the output is switched to "ON". Now, if the direction switched again, the output switches back to "OFF" until the setpoint is reached again.
Mode 3: Like Mode 1, but the actual value is retentive. It stores its actual value when you turn off the controller. Mode 4: Like Mode 2, but the actual value is retentive. It stores its actual value when you turn off the controller. Mode 5: Like Mode 2, but with the reset value is always set to "0", irrespective of the direction. Mode 6: Like Mode 5 but retentive. Mode 7: High-speed counter, which is used either as pure up counter on the high- speed counter inputs I1 or I2.
Mode 8: 1 KHz-speed counter, which is used either as pure up counter on the high- speed counter inputs I1 or I2.
42
Picture 2.82 Exercise card LAD8a+b
Picture 2.81 Exercise card LAD8
Picture 2.83 Exercise card LAD9a+b
Exercises: Counter C
LAD8 Should be tested before the following exercises are done with the exercises card "counter C01", all modes.
LAD9: A car park entrance is controlled by display. A total of 20 parking spaces available. If all are occupied, the display shows "Busy". Otherwise, the display is set to "FREE". The caretaker also has the option, regardless of the allocation to close the driveway with a roller door. Is the roller door down, the display shows "CLOSED" on. Contact entrance : I01 Contact exit : I02 Contact door below : I03 Display “FREE“ : Q01 Display „BUSY“ : Q02 Display „CLOSED“ : Q03
LRD12
Parkhaus / Park ing garage LAD 9
Ein fahrtentranceI1
Ausfahrtexi tI2
I3
FREI / FREE
BELEGT / BUSY
Geschlossen /closed
LAD8a: Using an up-down counter of the setpoint value for a timer from 0 to 50 sec ... be adjustable. As the setting buttons Z keys are used. With Z01 is forward (UP), with Z03 backward (DOWN) counted. LAD8b: Extension The setpoint and the actual value of the timer should be displayed on the display of the LRD. Setpoint
Actual value
Q1I2
I3Reset
Direction
I1 Puls
Mode
Preset Value
Zähler C01 counter C01
LAD8
Counter
UP
DOWN
Min=0
Max=50
Timer 2
START
I1 Q1
LRD20
Preset Value
Sollwertvorgabe mit Vor-Rückwärtszähler setpoint via up-down counter LAD8a/8b / FBD7a /7b
43
Picture 2.84 Shift register in LAD
Picture 2.85 Parameter of S01
2.12 Shift register S01 The function block "shift register" is a bit shift register and is available once. It can max. be 8 steps high. The start-coil defines the first step in the shift register. It can be an output (Q, Y) or relays (M, N). If you have chosen a variable, all outputs or markers that are defined with "Select 1-8", assigned. The clock-coil "Pulse Coil" defines the shift clock. It can be any variable in NO or NC function. In this example, the outputs Q1-Q4 are occupied by the shift register. The shift register operates as a shift register ring. This means in this example that the fourth time clock with the output Q01 I02 back "ON".
„Start Coil“
Q01 Q02 Q03 Q04
Number of shift increments „Select 1-8“
„Pulse Coil“
„Start Coil“
44
Picture 2.86a Exercise card LAD10 for LRC20
Picture 2.86b Exercise card LAD10 for LRC12
Picture 2.87 Exercise card LAD11
Exercises: shift register S01
LAD10: We have a shift register with eight steps. The training card shows all necessary variables. The shift register shifts first from M01 to M08. The markers then drive the outputs Q1 ... Q8. Since the LRD12 has only 4 physical outputs, the remaining 4 outputs are virtually visible on the display. The shift clock (T1) of 1s becomes active when I1 is actuated. After 8 steps of shift clock starts again while I1 is switched off.
LAD11: In this exercise, the shift register is to be extended from LAD10 as traffic light control. Once I1 is turned on runs the traffic lights cycle from according to the diagram. 1 2 3 4 5 6 7 sec.
LRD20
Schieberegiste r / Shiftregister LAD 10
I1 Start Q1
Q2
Q3
Q4
Pulsecoil
Start Coil
S01
M01
M02
M03
M04
M05
M06
M07
M08
T1
Q5
Q6
Q7Q8
LRD12
Schieberegister / Shiftregister LAD 10
I1 Start
Q1
Q2
Q3
Q4
Pulsecoil
Start Coil
S01
M01
M02
M03
M04
M05
M06
M07
M08
T1
Dis
p lay
LRD12
Ampel mit SchieberegisterTraffic light with shiftregister
LAD 11
I1 Start
S01
45
Picture 2.88 Parameter of Ax
Picture 2.89 Parameter of Ay
2.13 Analog comparator G The 24VDC base unit LRD12 provides two analog inputs A1 and A2. The analog value from 0 to 10V is applied to an analog to digital converter on the inputs, and converted into a binary number. The converted value can be compared via the analog-comparator block G with different values. The analog comparator values offers 8 modes
Mode 0: is always an internal coil. Mode 1: (Ay-Ref.) <= Ax <= (Ay+Ref.)
Ax and Ay can be assigned differently. With the direct assignment to the potentiometer of the MiniTrainer we can easily try out the formula. Ax = e.g.: A01 Ay = e.g.: A02 Example:
If the reference value is set to 03:00 and the potentiometer A2 to 6V, the output of the analog comparator switched on by turning the potentiometer A1 of at 3V and at 9V.
Mode 2: (Ax <= Ay) The output of the block "G" is "1", if the analog value of A1 is less than or equal to the value of A2.
Ax = Adjustable example: A1 Ay = A2
The other functions: Mode 3: (Ax> = Ay) Ax greater than, equal Ay Mode 4: (Ax <= Ref.) Ax less than, equal a fixed value Mode 5: (Ax >= Ref.) Ax greater than, equal a fixed
value Mode 6: (Ax = Ref.) Ax equal a fixed value
Mode 7: (Ax> <Ref.) Ax smaller or larger but not equal to a fixed value.
46
Picture 2.90 Exercise card LAD12
Picture 2.91 Exercise card LAD13/15
Exercises: Analog comparator G
Note: If you use LRD20 , the outputs are differently:
LRD12 LRD20 Q1 = Q1 Q2 = Q3 Q3 = Q5
Mode 1
A1 A2
Q1Analogwertevergleicher Analog comparator LAD12
LRD12
LAD12: Using the analog comarator G in mode 1, to switch Q1 when the difference between A01 and A02 is <= 3V. For checking the status display is used to display the LRD...
LRD12
Wassertank Water tank LAD 13 /15
A1
Q2
Q3
50°C
Q1
ON/OFF
Heizungheating
Alarm
LAD13: The temperature of a water tank is to be kept at 50 ° C -2 ° C. I1 is used as the main switch. The heating is controlled by Q2. The temperature curve of the sensor corresponds to the sketch. If the temperature is above 55 ° C or below 45 ° C then the alarm rings (Q3).
°C 90 55
50 45
0 ? ? ? 10V
47
Picture 2.95 RTC – Mode 3
2.14 Real Time Clock R The clock module in small controllers, such as the MicroPLC represents a fixed function in many applications. It can be used to realize time-, and date-dependent switching functions. The Real Time Clock (RTC) provides in MicroPLC LRD… four different modes:
Mode 1: weekly timer The daily set on and off time applies for the set period every day. The entry is in hours and minutes (00:00 to 23:59)
MO TU WE TH FR SA SU Picture 2.93 RTC mode 1
Mode 2: weekly timer The selected on time may be at a different day than the off time. The set period applies max. for one week. The input is as in Mode 1 MO TU WE TH FR SA SU
Picture 2.92 RTC menu
Picture 2.94 RTC mode 2
Mode 3: Year time switch The set switch-on is on a day and is always at 00:00 clock. The off time is usually on a different day at 23:59 clock. The period may extend over several years.
ON OFF
48
Picture 2.96 RTC – Mode 4
Picture 2.97 Exercise card 14
Mode 4: pulse clock
On Thursday (TU) at 16:25 clock for a period of 14 sec, the output of the real-time clock is switched "ON".
Exercise: Real Time Clock R
LAD14:
The outdoor advertising (Q1) of a shoe shop will be switch on and off automatically over the real time clock. The times are set as follows: Mon-Fri at 7:00 A.M. ON and at 6:30 P.M. OFF Thu additionally at 7:00 P.M. ON and at 10:30 P.M. OFF
LRD20
Real Time Clock RTC LAD14
Q1
Day ON OFFMonday 7:00 a.m. 6:30 p.m.Tuesday 7:00 a,m, 6:30 p.m.Wednesday 7:00 a.m. 6:30 p.m.Thursday 7:00 a.m. 6:30 p.m. 8:00 p.m 10:30 p.m.Friday 7:00 a.m. 6:30 p.m.
49
Result = = V1 * V2 / V3
Picture 2.98 Tools
Picture 2.99 MD function
Picture 2.100 AS function
2.15 Arithmetic blocks AS (ADD / SUB) and MD (MUL / DIV) If you want to compare different values or limit values in a particular area, then you have to rely on the arithmetic. The four basic arithmetic operations are divided into two functional blocks. First, the addition (ADD) and subtraction (SUB) and on the other hand, the multiplication (MUL) and the division (DIV).
ADD / SUB MUL / DIV Example: The example shows a timing of a timing relay that between 10 and 50 seconds over the potentiometer A1 should be adjustable: If we assume that the analog input A01 from 0 ... 1023 has been set, then the result for the delta of 40s (10 ... 50s), the following formula (MD01): A1 x 10 256 Analog input A1 multiplied (MUL) with 10, divided (DIV) by 256 V1 * V2 / V3 This requires the MD01 module with the entries for V1, V2 and V3: With the next formula (AS01) is added to the offset of 10s the result of MD01 added:
50
Picture 2.101 Simulation of arithmetic
Picture 2.102 Exercise card LAD13/15
The result is now as required between 10 .... 50. If we now have the time base of the timer set to "sec", then the task is complete and can be tested with the simulator:
Exercise arithmetic AS
LAD15: In addition to LAD13 the temperature is shown on the online display on the PC's screen. In the next step, if the chapter "Text display" has been processed, the temperature should be displayed on the display of the LRD (LAD16).
°C 90 50 0 ? ? ? 10V
LRD12
Wassertank Water tank LAD 13/15
A1
Q2
Q3
50°C
Q1
ON/OFF
Heizungheating
Alarm
Picture 2.103 Online status display
Picture 2.104 What is the voltage at which Temperature at the analog input?
51
2.16 Data register DR In contrast to markers (M and N) in which one can store only one bit (0/1), max offer. 225 data register values also with the option to save. These data registers are to be parameterized in other blocks. Example: The result of an arithmetic calculation is to be displayed on the screen of the controller.
1 Step: The result is stored in the data register DR01.
2. Step: In the HMI / Text editor of this DR01 is included in the display
Exercise: Data register DR
LAD9a: Is in addition to the display of the LAD9 now LRD... take over the display and the remaining free parking spaces is shown
Note: Display of remaining free parking
LRD12
Parkhaus / Park ing garage LAD 9
Ein fahrtentranceI1
Ausfahrtexi tI2
I3
FREI / FREE
BELEGT / BUSY
Geschlossen /closed
FREE
Picture 2.105 DR menu
Picture 2.106 Content of DR to the text display
Exercise 2.108 Text on the Display of the LRD…
Picture 2.107 Exercise card LAD9 Picture 2.109 Online display
52
2.17 Multiplexer MX Each of the 30 Multiplexer blocks offers the possibility to assign up to 4 variables to a setpoint input. The query of the variables is binary, using two bits. Example: A timer T01 to run at 4 different times depending on the application. The four variables (setpoints) are to be pre-selected by the two inputs I1 and I2. Prefix: I1 I2 Setpoint 0 0 1 1 0 10 0 1 100 1 1 200 I Depending on the combination of the switches I1 and I2 corresponding to the setpoint, it is assigned to the timer. The timer module T01 at the setpoint input, the reference to the multiplexer module is entered MX01.
Picture 2.110 Multiplexer Menu
Bild 2.111 Multiplexer in LAD
53
2.18 Text display H The MicroPLC offers the possibility of process-dependent texts with and without displaying variables together with the built-in display. For this the text module H is called in the program. Mode 1: MicroPLC with display Mode 2: MicroPLC without display, that means for an external display To enter text you will see in the menu bar of the software, the button "HMI / text" to be "clicked". It opens the following menu: Note: The display of the LRD ... offers 4 lines with 16 characters each.
Picture 2.112 Text block
Block-No.: 1 up 1F = 30 Text displays
Picture 2.113 To enter Text
Picture 2.114 Text input menu
54
If the display is activated (hook set), the user can view the SEL button to select the text. Use the ESC key, the text is cut off again. Here, the variable can be with their unit select (Timer / counter / clock and analog comparator). Here, the coil state of I, M, X and Z are shown. If you select the representation with the operand, then it is displayed as follows:
e.g.: I01(unit)
If no operands are selected e.g. "I01", only the state is shown:
„Analog Display Set“ : Here, another menu opens in
which the amplification factor (gain) (1 ~ 999) and / or the offset (-50 ~ +50) is set.
1
2
3
4
1
2
3 4
Picture 2.115 Text input
Picture 2.116 a+b Variable input
55
a)
b)
The example will now show how the analog input A1, with a gain of 100, and an offset of 50 in the display is visible. With the input I1, the variable to be displayed on the display of LRD12. The program is as follows: Once the program is created, the HMI / Text window is opened and provided with the following entries: 1. step The gain and offset of A1 defined: (e.g. Gain = 100 and Offset = 50) 2. step a) Where the value should appear in the "HMI / Text" menu, enter text and click the cursor to the position. b) Then click on the selection window of the analog inputs and "A1" to select. 3. step Possibly one more text to add. 4. step Transfer and storage in the control Exercise: Text display LRD 16: As a supplement to LAD13 and LAD15 the temperature is shown in addition to the display of the LRD.
Picture 2.117 Text block in LAD
Picture 2.118 Analog Set - menu
Picture 2.119 Embed variable in the text
Picture 2.120 Display in the LRD…
56
2.19 Comments for coil and contacts In practice, it often is not appropriate to use the coil and contacts with the names in the schematic. An appropriate comment increases the clarity and the reference to the machine and plant. Under the menu item "Edit" you will find the "Symbol ..." If you click on "Symbol ..." you open a selection window in which you can select the desired coil and contacts and provide comments. These then appear on the LAD chart below the contact and the coil.
Text input
Picture 2.121 open Text Input Picture 2.122 Text Input
Picture 2.123 Text representation
57
2.20 Headlines and comments in the Ladder Diagram In a project it is very important that some program sections are commented. This makes the start-up and later troubleshooting much easier, thus saving costly downtime of a machine or system. For commenting the software offers the button "Note"
If you have clicked this button, it will be like a coil or a contact to the location of the circuit diagram set. Then open the window for entering the text. There are 4 lines of 50 characters each available to you. Note: Each comment is always uses one line in the ladder diagram.
Pictures 2.124 Comment Input Button
Pictures 2.125 Comment Input Menu
Picture 2.126 Comment representation
58
3. Function block diagram FBD If you want to create this project in function block language you have to click the button "FBD" just after opening the software. One comes directly into the selection menu for the control. As in the LAD editor, we select the correct device LRD12TD024
Function block diagram FBD
Picture 3.1 Start Menu of the LRXSW to FBD
Picture 3.2 Device selection menu
59
Click "OK" to return into the FBD editor. If the operating window is too small, it can be adjusted either under the "View" menu, "Zoom In" or drag the "Zoom Out" larger or smaller, or you can use the zoom function button:
To make all the icons visible click the button
Picture 3.5 All symbols Like in the LAD editor most of the symbols in the respective chapters are explained.
Working window
If the operating windows are multiplied, that is made possible by on-click of the button.
Picture 3.3 Zoom function
Picture 3.4 Customize the working window
60
3.1 Creating a function block diagram With the mouse pointer you select a logic symbol. As an example, we select the input. When the icon is selected it will appear on the field of work on mouse-pointer following logic symbol . When it is directed to the appropriate location, click on the left mouse button and the proper logic symbol is "stored". This is now stored with each click until you press the right mouse button or selecting a different icon. If you want to delete a logic icon again, it is clicked with the right mouse button. The following menu appears: Or can be deleted with the "delete" key. With a double click of the left mouse button on the icon, a menu selection where one operand number appears. May change (input number) and store an operand text (icon).
Picture 3.6 Delete
Picture 3.7 Parameter Input
61
In addition to the operand text, it is possible to store a general comment and to displace it with the mouse. To do this click with the right mouse button in the free field of work. The following window appears: If you click "Insert Comments" first appears next to the mouse pointer a "T". You position it by clicking the left mouse button, the input window appears: This comment is always displaced by clicking it with the left mouse button. It is marked with four red corners and can be moved around now. If you want to delete it again one uses the "Del" key on the PC keyboard. This also applies to all the logic symbols and connections. 3.1.1 Draw connections If you have placed at least two logic modules, you can connect them logically. For this, the link button is clicked and dragged to the field of work. Now you go with the mouse pointer to the quasi-dependents of the wiring to the module input or output. Whether you have "hit" the corresponding input or output can be recognized by a small square. One click and the connection can be drawn.
Note: If you have a straight logic symbol placed you can directly drag the link without having to click on the link button.
Picture 3.8 To comment entry
Picture 3.9 Comment Input
Picture 3.10 Draw connections
62
3.2 Logic sets in the FBD-Editor
3.2.1 AND operation
The AND operation corresponds to the series circuit in a conventional, wired contactor control, the output is switched on when all switches are closed. Example: Logical AND operation with three digital inputs
The output signal (H1), an AND operation is then "1" when all the input signals (S. ..) have the state "1". The "1" stands for an actuated normally open N.O. or a normally closed N.C. contact is not actuated.
True list: FBS: Logic algebra: S1 S2 S3 H1 0 0 0 0 1 0 0 0 0 1 0 0 1 1 0 0 0 0 1 0 1 0 1 0 0 1 1 0 1 1 1 1
S1 S2 S3
H1
H1 = S1 & S2 & S3
FBD
This "AND" supplies at the output (H1) for a cycle length a "1". The block can also be used as pulsemodule!
H1
Picture 3.11 AND-operation
Picture 3.12 AND operation in FBD
63
3.2.2 AND NOT-operation (NAND) The NAND operation corresponds to the series circuit in a conventional-wired contactor control, the output is turned off when all the switches are closed. Example: Logical NAND with three digital inputs The output signal (H1) of a NAND is always "0" if all the input signals (S. ..) have the state "1". The "1" stands for an actuated normally open or a normally closed contact is not actuated. True list: FBS: Logic algebra: S1 S2 S3 H1 0 0 0 1 1 0 0 1 0 1 0 1 1 1 0 1 0 0 1 1 1 0 1 1 0 1 1 1 1 1 1 0
S1 S2 S3
H1
H1 = S1 & S2 & S3
This "NAND" the output only delivers a "1" if a pulse of the input "0".
FBD
Picture 3.13 NAND operation
Picture 3.14 NAND operation in FBD
64
3.2.3 OR operation The OR operation corresponds to the parallel circuit in a conventional wired voltage control, that is, the output is turned on when at least one of the three switches is closed.
Example: Logical OR operation with three digital inputs The output signal (H1), an OR operation is then logic "1" if at least one or more input signals (S. ..) have the state "1". The "1" stands for an actuated normally open contact or a non-actuated normally closed contact.
True list: FBS: Logic algebra: S1 S2 S3 H1 0 0 0 0 1 0 0 1 0 1 0 1 1 1 0 1 0 0 1 1 1 0 1 1 0 1 1 1 1 1 1 1
S1 S2 S3
H1
H1 = S1 V S2 V S3
FBD
Picture 3.15 OR operation
Picture 3.16 OR operation in FBD
65
3.2.4 AND before OR operation
The three switches to be logically combined in AND and OR: The input of this logic is based on the fundamental rule of Boolean algebra:
Point are performed before addition and subtraction
In the implementation in the wiring logic, this means:
Series is going on in parallel Example: It shows the implementation of a combined AND-OR circuit according to the rule mentioned above: True list: FBS: Logic algebra: S1 S2 S3 H1 0 0 0 0 1 0 0 0 0 1 0 0 1 1 0 1 0 0 1 1 1 0 1 1 0 1 1 1 1 1 1 1
H1 = S1 & S2 V S3
S1 S2
S3
H1
Picture 3.17 AND before OR operation
Picture 3.18 AND before OR operation in FBD
FBD
66
3.2.5 OR before AND function The four switches to be logically combined in OR and AND: The input of this logic is also called conjunctive form. Since the Boolean rule applies here, must be used with braces. Thus, it specifies that the OR operation is processed first. The representation in the application program corresponds to the international standard IEC 61131. Example: It shows the implementation of a combined AND-OR circuit according to the rule mentioned above: True list: FBS: Logic algebra: S1 S2 S3 S4 H1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 1 1 0 0 0 0 0 1 0 0 1 0 1 0 1
0 1 1 0 1 1 1 1 0 1 0 0 0 1 0 1 0 0 1 1
0 1 0 1 1 1 1 0 1 1 0 0 1 1 0 1 0 1 1 1 0 1 1 1 1 1 1 1 1 1
H1 = (S1 V S2) & ( S3 V S4)
FBD
H1
S1 S2 S3 S4
Picture 3.19 OR before AND operation
Picture 3.20 OR before AND operation in FBD
67
3.1.4 OR-NOT operation (NOR) Three switches should be logically linked in NOR: The representation in the application program corresponds to the international standard IEC 61131. Example: It shows the implementation of a combined NOR circuit according to the truth table: True list: FBS: Logic algebra: S1 S2 S3 H1 0 0 0 1 1 0 0 0 S2 0 1 0 0 1 1 0 0 0 0 1 0 1 0 1 0 0 1 1 0 1 1 1 0
H1 = S1 V S2 V S3
S1 S3
H1
FBD
Picture 3.21 OR-NOT operation
Picture 3.22 OR-NOT operation in FBD
68
3.2.7 Exclusive-OR (XOR) The most used exclusive OR circuit, the Exclusive-OR circuit having two inputs. It differs to the OR operation to the effect that the output only becomes "1" when one of the two inputs are "1". If both inputs are "1", the output is "0". With such a circuit you can realize an interlocking of two input signals very simply. Example: Logical Exclusive-OR operation with two switches True list: FBS: Logic algebra: S1 S2 H1 0 0 0 1 0 1 0 1 1 1 1 0
H1 = (S1 & S2) V ( S1 & S2)
H1 S1 S2
Picture 3.23 Exclusive-OR operation
Picture 3.24 Exclusive-OR operation in FBD
FBD
69
Exercises: Logic blocks FBD1a, FBD1b, FBD1c: These logical links provides a good introduction to the FBD language of LRD12 or LRD20 from Lovato Electric
FBD 1c
LRD12
I2
I3
I4
I5
I6
NAND
NOR&
Q2
FBD 1b
LRD12
I2
I3
I4
I5
I6
>=1
&
=1
Q1
LRD12
I2
I3
I4
I5
I6
I1&
>=1
>=1
&Q2
Picture 3.25 Exercise card FBD1a
Picture 3.26 Exercise card FBD1b
Picture 3.27 Exercise card FBD1c
70
3.2.8 Latching function In control engineering, the latching function is often used. Especially when using buttons will execute a stored function. A typical task is the on and off of a motor. The ON button is always a contact and the OFF button always an opener. Why the OFF button is normally closed, has something to do with the wire breakage. The VDE regulations state that in the event of a wire break, the relevant section (e.g. a motor) must be switched off immediately and must not be turned on. To realize a latching function in the MicroSPS offers the LRD ... two variants. 1. The dynamic control of the output: If the result of logic operation (RLO) = 1, then the output = 1 If the RLO = 0, the output = 0. 2. The static control of the output: Latching function with commands SET and RESET . Both commands work with the positive edge. In both examples, it is ensured that while pressing both buttons ON and OFF, the output = 0. The wire breakage is protected , as in the case of a wire break in the "OFF" line drops the output in any case.
Picture 3.28 Dyn. latching function
Picture 3.29 Static latching function
71
Exercise: latching function
FBD2a: Latching with dynamic control of Q2. (As in the contactor technology)
FBD2b: Latching static drive of Q3. (As with the conventional electronic controls on the flip-flops)
LRD12
Selbsthal tung /seal-in-circu it
I3
I4
I5
I6
>=1
&Start
StoppQ2
S
R
Q3
Bei der Programmerstellung ist auf die Drahtbruchsicherheit zu achten!
In case of programming pay attentionto the fail-save circuit
Picture 3.30 Exercise card FBD2a+b
72
3.3 Selection menu of the Function Blocks In the FBD editor, the MicroPLC provides the same function as building blocks in the LADDER editor. Timer(Tx) Counter(Cx) RTC(x) ADD/SUB(AS) MUL/DIV(MD) PID controller(PID) multiplexer(MX) Analog ramp(AR) data register(DR)
3.3.1 Timing relay T Start (Enable) input switching output Setpoint input "t" actual value actual value: setpoint value:
Double-click on the block to reach the following window: The timer offers 8 modes: Time base: 0,01s / 0,1s / 1s / 1 Min. Setpoint time: 0,01s up 9999 Min. Note: The setpoint "Preset Value" of a timer can also come from an analog input or other device. More in "processing analog values"
time base actual value setpoint value
Picture 3.31 Function blocks in FBD
Picture 3.32 Timer-Function block in FBD
Picture 3.33 Timer-Function block
73
Mode 0: Internal coil (like a marker) Mode 1: On-delay timer
Mode 2: On-delay timer with reset input. If the enable is off, the timer stops. Only if the enable is switch "ON" again the timer continues to run. Mode 3: OFF-delay timer. The rising edge of Enable (0 -> 1), the output is "ON". Time is running out only when the enable the edge falls (1 -> 0). If enable is turned on again during the running time, the value is set to "0". The timer can be restarted. Mode 4: OFF-delay timer. If a falling edge of Enable (1 -> 0), the output is "ON" and the time is running out. If enable is activated again during the elapsed time, the actual value of the timer is reset to "0". The timer can be restarted.
Picture 3.34a Timer Mode 1
Picture 3.34b Timer Mode 2
Picture 3.34c Timer Mode 3
Picture 3.34d Timer Mode 4
Enable Output
Enable Output Reset
Enable Output Reset
Enable Output
74
Mode 5: Synchronous clock generator The synchronous clock starts with the rising edge (0->1) and stops at the LOW edge (1 -> 0) to enable. The ON-time and OFF-time on the output are the same.
Mode 6: Synchronous clock generator with reset Mode 7: Asynchronous clock generator
The asynchronous clock starts with the rising edge (0 ->1) and stops at the LOW edge (1 -> 0) to enable. The ON-time "t1" and the OFF-time "t2" at the output are equal.
3.3.2 Pulse relay A special function of the timing relay is the pulse relays or latching relay. This function is shown in the diagram of the button: Example: With the switch I1 can be the output by briefly pressing on Q1. A new brief press of I1 Q1 turns off again. Q1= ON Q1= OFF Q1
t1 t2
Picture 3.34e Timer Mode 5
Enable Output
Enable Output Reset
Picture 3.34f Timer Mode 6
Picture 3.34g Timer Mode 7
Enable Output
ON
ON ON ON OFF
OFF OFF
OFF OFF OFF
Picture 3.35 Pulse relay
75
Exercise: Timer relay
FBD3: With this exercise card all the modes of the timing relay with internal setpoint (e.g. 10 s) should be implemented.
FBD4a: This motor controller uses information given on the training card inputs and outputs. The change from clockwise to anti-clockwise rotation is only about stop and vice versa. The time is 5 seconds.
I2
I4
Q2
Enable
Mode 1... 7
Pre Value: 10.00 Cur Value
Reset
LRD12
Wende-Stern-Dreieckscha lter reversing star-delta swi tch FBD 4
I1 Sicherungfuse
I2 STOPPStop
I3Rechtsright turn
I4Linksleft turn
Rechtslauf
Q1
clockwise
Stern
star
Dreieck
delta
Linkslaufanti-clockwise
Q3
Q2
Q4
FBD5 (like exercise LAD7):
In metropolitan areas, side road access to highways is controlled in heavy traffic with a traffic light. The traffic light shows RED when the main switch I01 is turned on. An induction loop in the road surface before the traffic light detects an incoming vehicle. With 1s delay starts the traffic light cycle, which also takes 1 sec each for the individual phases. At the end of the traffic light cycle the lights are back on RED. If the induction loop is connected constantly, so the traffic lights cycle runs through the 1 sec intervals.
LRD12
Ampel / Traffic light LAD 7
Picture 3.36 Exercise card FBD3
Picture 3.37 Exercise card FBD4a
Picture 3.38 Exercise card FBD7/5
76
3.3.3 Counter C As with the timer the counter is a system component that needs to be configured simply. The MicroPLC offers a total of 30 counter blocks, each with 8 different modes. The presentation in the FBD editor provides the following information: Counting input Counting direction switching output Setpoint actual value actual value setpoint value Counter-No.: The counter of LRD... Offers, like in the Ladder diagram, 8 different modes: Mode 0: internal coil (like a marker) Mode 1: up-down counter without overflow. If the setpoint = actual value the counting input is disabled. The actual value is non-retentive. It loses its value when you turn off the controller. Setpoint input (0 ... 999999) Variables specification (e.g.: the result of arithmetic) Note: Compared with the LAD circuit diagram, the counting coil, the output of the counter, the counting direction and reset of the counter value in the FBD program be linked as shown in the example:
Picture 3.39 Counter in FBD
Picture 3.40a Counter mode1
77
Mode 2: up-down counter with overflow. If the setpoint = actual value of the count input is not locked. The counter continues to count. The actual value is non-retentive. It loses its value when you turn off the controller. Note to "Reset Input" and "Direction Set" in Mode 2
• "Reset input" has two functions. During counting up the reset is switched on, the current value of the counter is set to "0". When pressed while counting down the reset, then the setpoint "Preset Value" is set!
• If the setpoint is reached when counting up the output switches of the counter. Now, if the direction is switched, the output switches to "OFF" and again until the actual value = "0", the output is switched to "ON". If the direction is switched on again, the output switches back to "OFF" until the setpoint is reached again.
Example: Mode 2 Mode 3: Like Mode 1, but the actual value is non-volatile. It stores its actual value when you turn off the controller. Mode 4: Like Mode 2, but the actual value is non-volatile. It stores its actual value when you turn off the controller. Mode 5: Like Mode 2, but with the reset value is always set to "0", regardless of the direction. Mode 6: Like Mode 5, but non-volatile. Mode 7: High-speed counter, which is used either as pure forward counter of the fast inputs I1 or I2. Mode 8: 1 KHz-speed counter, which is used purely as an up-counter on the inputs I1 and I2.
Picture 3.40b Counter Mode 2
78
Exercise: Counter
FBD6a: The counter C1 is to be counted on the input I2 forward. If the value reaches 12, the counting should be interrupted. Only after the counter is reset by I6, I2 can be recounted again. Which mode is used to set? FBD6b: The exercise FBD6a is extended by the I3. With I3 can change the direction of the counter.
a) How does Q3 behave when changing direction at the switching output of the counter?
b) What happens if it is actuated while counting the reset?
FBD6c: Like the exercise FBD6b, now to be automated changes of direction. If the counter reaches the value 12, it automatically switches to count down. If the counter value reaches the value "0", it switches back to counting up. It is changing until the count clock of 0.5 Hz is switched off by I02.
FBD7a: Using an up-down counter of the target value for a timer from 0 to 50 sec ... To be adjustable. As the adjustment buttons Z keys are used with Z01 is forward (UP), with Z03 backward (DOWN) counted. FBD7b: Extension The setpoint and the actual value of the timer should be displayed on the display of the LRD.
Picture 3.41 Exercise card FBD6a/6b/6c
Zähler / counter FBD 6a/6b/6c
zählen
Richtung
Q3
Count
Direction
löschen
Reset
Sollwertpre = 12
value
C1
I2
I4
I6
CNT
C1
LRD12
Mode1 ... 8
Counter
UP
DOWN
Min=0
Max=50
Timer 2
START
I1 Q1
LRD20
Preset Value
Sollwertvorgabe mit Vor-Rückwärtszähler setpoint via up-down counter LAD8a/8b / FBD7a /7b
Picture 3.42 Exercise card FBD7a+b
79
3.3.4 Shift register S01 The function block "shift register S01" is a bit shift register and is available once. It can maximum be 8 steps high. Enable Sift input The start-coil "Start Coil" defines the first step in the shift register. It can be an output (Q, Y) or relays (M, N). If you have decided on a variable, all outputs or marker that have been defined with "Select 1-8", assigned. In this example, the outputs Q1-Q4 are occupied by the shift register The shift register operates as a ring shift register. This means in this example that the fourth time clock with the the input I02 the output Q01 is "ON" again. Exercise: Shift register
„Start Coil“
Q01 Q02 Q03 Q04
FBD8b: Create accordance with the exercise FBD5 with shift register.
Picture 3.43 Shift register in FBD
Picture 3.44 Shift register menu
Picture 3.45 Exercise FBD8a
80
3.3.5 Analog comparator G The 24VDC base unit LRD ... offers two analog inputs A1 and A2. The analog value of from 0 to 10V is applied to an analog to digital converter on the inputs, and converted into a binary number. The converted value can be compared over the analog values to comparator block G with different values. The analog comparator values offers 8 modes, the mode 0 is always an internal coil. Mode 1: (Ay-Ref.) <= Ax <= (Ay+Ref.)
Ax and Ay can be assigned different. With the direct assignment to the potentiometer of the MiniTrainer you can easily try out the formula. Example: Ax = A01(0…10V) Ay = e.g.: 7V Ref.= 2V d.h.: 5V <= Ax <= 9V
If the reference value is set to 2V and you turn the potentiometer A1, then the output of the analog comparator is switch on at 5V, and switch off at 9V again.
Mode 2: (Ax <= Ay) The output of the block "G" is "ON" when the analog value of A1 is less than or equal to the value of A2. A1 A2 Ax = Adjustable example via the potentiometer A1 Ay = Adjustable example via the potentiometer A2 Additional functions: Mode 3: (Ax> = Ay) Ax greater than, equal Ay Mode 4: (Ax <= ref) Ax less than, equal a fixed value. Mode 5: (Ax >= Ref.) Ax greater than, equal a fixed value. Mode 6: (Ax = Ref.) Ax equal a fixed value. Mode 7: (Ax> <ref) Ax smaller or larger but not the same.
Picture 3.46 Example Analog comparator
Picture 3.47 Potentiometer on the MiniTrainer(XL)
81
Exercise: Analog comparator
FBD9a+b: a) Two analog values to be compared. Once the
comparator output is ON, Q2 is on and Q1 flashing at 0.5 Hz.
Ax >= Ay (Mode …)
b) In this exercise AI01 should be compared to a
constant value of 25 according to the sketch (mode ....).
Ai01
500
Q2=“1“ 0 value= 25
FBD9c: This motor controller is using the informations given from the training card inputs and outputs. The change from clockwise to anti-clockwise rotation is only about stop and vice versa. The star to delta transition time is variably adjustable via the analog input A1 between 5 and 20s. Note: Since the potentiometer A1 is not of MiniTrainer very accurate, the maximum value in result cannot be achieved exactly 20s.
Q1Analogwerteverg leicher Analog comparator FBD 9a+b
01 02
LRD12
Ai01 >= Ai02
0,5Hz
Q2
LRD12
Wende-Stern-Dreieckscha lter reversing star-delta swi tch FBD 9c
I1 Sicherungfuse
I2 STOPPStop
I3Rechtsright turn
I4Linksleft turn
Rechtslauf
Q1
clockwise
Stern
star
Dreieck
delta
Linkslaufanti-clockwise Q3
Q2
Q4
A1
5 20s
Picture 3.48 Exercise card FBD9a+b
Picture 3.49 Exercise card FBD9c
82
3.3.6 Multiplexer MX Each of the 30 multiplexers provide the ability to assign up to 4 variable to a setpoint input. The query variable is binary, using two bits. The program example will illustrate this: The timer T01 to run at 4 different times depending on the application. The four variables (setpoints) are to be preselectable by the two inputs I2 and I3. Prefix: (Vorwahl) I2 I3 Setpoints V1…3 0 0 10 1 0 15 0 1 20 1 1 25
Depending on the switch combination of I2 and I3 the corresponding setpoint is assigned to the timer T01. The setpoint input of the timer module T01 is connected to the output of the multiplexer block MX01.
Picture 3.50 MX function block
Picture 3.51 Exercise Multiplexer FBD10
83
3.3.7 Boolean function BL The MicroPLC offers a Boolean logic unit. The standard block can be 4 digital input signals combined (16 possibilities). The 16 possibilities are represented in binary code: The output of the block is one bit and can be optionally specified with "1" or "0". Example: Using the BL block to create a code lock. The code consists of a number between 0 and 9 (1 decade). If the code is correct, the output Q01 of 0.5 s will be "ON".
Output Input 1 Input 2 Input 3 Input 4
0
2 = 2 1
2 = 4 2
2 = 8 4
Picture 3.52 BL function block in FBD
Picture 3.53 BL Binary code
Picture 3.54 Exercise code lock FBD11
84
Exercise: Boolean Functions
FBD12 Based on the training card you will be programming a Boolean block for an exclusive OR with 4 inputs. That is, the output of Q01 is "1" if only one input is "1".
I3
I4
I5
Q3
I2
=1
XOR mit 4 Eingängen XOR with 4 inputs
FBD12
LRD20
Picture 3.55 Exercise card FBD12
85
3.3.8 Pulse-width modulation (PWM) P The MicroSPS with transistor outputs offers the option of the digital output Q01 via the pulse width modulation block (P) to drive. The PWM block offers two modes: Mode 1:
Pulse width modulation is a convenient way to have a digital output, e.g. a frequency converter to control a motor in the speed or control.
To get to know this function, you can realize a simple link. It performs both analog signals A1 and A2 of the MiniTrainers as set values (preset value) to the module. This is done by setting the variable type "A" by selecting the "Preset Type". Where A1 is the time in milliseconds (ms) for the frequency and A2, the time indication for the high signal also in milliseconds.
Selection of profiles
Note: "T" must be always greater than "t" and can not be "0", that is, A01 must always be greater than A02.
If you choose, however, the variable Type "N" then constant values can be used (0. 32767) for the profile of "T" and "t" to enter. Select 1 is always the profile that is activated by enable. The two inputs Sel1 and Sel2 of the PWM module allow an additional two profiles retrieve.
Enable Sel 1 Sel 2 Level 0
Q01
FBD 13: I1 = Enable = Select 1 = T= 200ms t=50ms I2 = Select 2: T= 400ms t=50ms I3 = Selekt 3: T= 400ms t=10ms I4 = Stop
Picture 3.57 P function block in FBD (Mode 1)
Picture 3.56 P Menu Mode 1
Picture 3.58 P Menu Mode 1
86
Mode 2: In Mode 2, a frequency PF is output (in Hz) for a predetermined time period PN. FBD 13a For testing the function both analog inputs of the MiniTrainers are used: Exercise: PWM
FBD14: This exercise is to regulate a pump for filling a tank. The level is recorded as a measure via the analog input IA1. The tank is emptied through the manual outlet, the filling level and the analog value is lowered and falls to 0V. With the input I1, the system is switched on and off. The pump controller consists of the release of Q3 and the PWM - output Q1. If the level reading reached IA1 the value of 9.5 V, the release of Q3 is removed. The fuller the tank, the slower the pump. If the tank is empty, the pump runs at full speed. If the tank is full, the speed is zero. IA1= ~10V 0V ~0,5Hz …………………….~500Hz (PWM)
Enable Q01
Silo / Tank
IA1
Q1
Q3
PWM
Silo / tank
LRD12
FBD14I1 Start/Stopp
Voll
Enable
M
Picture 3.59 P function block in FBD (Mode 2)
Picture 3.60 PWM funktions
Picture 3.61 Exercise card FBD14
87
3.3.9 Text H The text block can be used 30x. Mode1 means with display and Mode2 means without display Enable The editor for text entry is located, as in the LAD editor, in the "Edit" menu -> "HMI / Text"
3.3.10 Display backlight The display of the LRD ... can remain switched on for the program. For this, the menu offers "Operation" in the stop mode or in offline mode from the submenu: "Module System Set ..." the possibility of program-related backlight
Picture 3.62 H Text block
Picture 3.63 Text Input
Picture 3.65 Display backlight
Picture 3.64 To adjust the backlight