01Protection Relays
The MiCOM range of relays offers varying levels of functionality and hardware options to best suit the protection requirements, and allows the customer to choose the most cost effective solution for their application.
The 20, 30 and 40 series hardware platforms are the building blocks of the MiCOM protection relay range providing the capability for a wide variety of protection, control, measurement, monitoring and communication functions.
The versatile hardware allows for application in many installations and a common relay management software (MiCOM S1) makes for easy configuration and application.
A standard and simple user interface across the range makes this ideal in any environment, from the more complex bay level control and mimic to the more simple LCD display and interrogation facility.
Numerous integrated communication protocols allow easy interfacing to most substation control or SCADA systems. The majority of MiCOM 30 and 40 series relays can be supplied with ethernet, to allow a full IEC 61850 solution for the substation.
THE MICOM RANGE OFFERS COMPREHENSIVE PROTECTION SOLUTIONS AT ALL POWER SYSTEM LEVELS SUCH AS :Generation
• IntegratedGeneratorProtection
TransmissionandDistribution
• DistanceProtection• LineDifferential• TransformerManagement• BusbarProtection• StandAloneBreakerFailProtection• Directional/Non-DirectionalOvercurrent• FeederManagementandOneBoxSolutions• Loadshedding• Voltage&FrequencyProtection
Industrial
• MotorManagement• InterconnectionProtection
Railway
• FeederManagement• TransformerManagement• DistanceProtection
MiCOM Protection20, 30 and 40 Series Relays Key Features
Customer Benefits•One single configuration
software - MiCOM S1•1A/5A dual rated inputs•Scalable hardware•Flexible mounting options•Standardized user interfaces•Wide range of communication
protocols
02MiCOM Px20, Px30, Px40Protection Relays
KEY FEATURESTheMiCOMrangeofrelaysfulfilstherequirementsatallvoltagelevelsfromLVtoEHVforIndustrial,DistributionandTransmissionSystems.
COMMON FEATURES
• 1A/5AdualratedCT’s
• EventandDisturbanceRecording
• Variouscasingandmountingoptions
• RelayshaverearRS485portwithchoiceofprotocolsandfrontRS232forlocalsetting
• Anumberofauxiliarysupplyanddigitalinputvoltageoptions
20SeriesRelays(Px2x)
Itwillfulfilthebasicrequirementsofindustrial,transmissionanddistributionsystemsprovidingsimplicityandeaseofapplicationinawiderangeofinstallations.
• Scalablesolutionswheretypeandquantityofprotectionfeaturesismodeldependent
• Flexiblelogicequationsavailableonmostmodels
• Compacthardwareoptionsforeasyinstallation
• Commonfunctionsthroughouttherange
• Multi-languageHMI
• AdvancedprotectionfunctionsonPhase2hardware
30SeriesRelays(Px3x)
DesignedtomeettherigorousrequirementsofMV,HVandEHVsystemswithparticularfocusonfeederandtransformerprotectionandcontrol.
• ProtectionwithBaylevelcontroloptionstofacilitatefeedermanagement
• Input/Outputquantityselectablebasedonrequirements
• AnumberofRearPorthardwareoptionsavailablewithawiderangeofProtocolsselectableviasoftware
• Protectionfunctionsavailableforunearthed/petersencoilearthedsystems
• Surfaceandflushmounted(incudingdetachableHMIoption)aswellascompactcasemodelsavailableintherange
• FullProgrammableSchemeLogicandFunctionkeys
40SeriesRelays(Px4x)
ItwillfulfiltheprotectionrequirementsforawidemarketofMV,HV,EHVandindustrialsystemsandoffersawiderangeofprotectionfunctions.• FullProgrammableSchemelogicavailable
withGraphicConfigurationToolforeasysetting
• ScalableInput/Outputhardwaredependingonrequirements
• OperatingvoltageselectableviaSoftwareforOptoinputs
• Hardwareaccessoriesavailableforeasymountinginracksorpanels.
APPLICATIONS
Px2xSeries
Theintegratedfunctionsreflectthedifferentrequirementsinsystemprotection.Thepreferredapplicationsareasfollows:• P12x:UniversalOvercurrentprotectionfor
mainorback-upprotectiononMVandHVsystems
• P22x:MotorProtectionSeriesforLVandMVsystems
• P52x:LineDifferentialprotectionforMVandHVsystemswithmultiplecommunicationoptions
• P821:DedicatedBreakerFailureProtectionsuitableforEHV,HVandMVsystems
• P92x:Voltageandfrequencyprotectionsuitableforgenerators,motorsandfeeders
Px3xSeries
30Seriesprotectiondevicesprovideawiderangeofprotectionandcontrolfunctionsmeetingstringentmarketsegments.Therangeisespeciallysuitableforpetersencoilearthingrequirements.Thepreferredapplicationsare:• P13x:Feedermanagementrelaysandone
boxsolutionforMVandHVsystems(includingrailwayfeeder)
• P43x:DistanceprotectionforMV,HVandEHVsystemsandrailcatenaryrequirements
• P53x:LinedifferentialprotectionforMVandHVsystems
• P63x:Differentialprotectionfortransformers,generatorsandmotors(includingrailwaytransformers).
03MiCOM Px20, Px30, Px40Protection Relays
Px4xSeries
40Seriesprotectiondevicesprovideawiderangeofprotectionandcontrolfunctionsandmeetstherequirementsofawidemarketsegment.Thepreferredapplicationsare:• P14x:Feedermanagementrelaysuitablefor
MVandHVsystems
• P24x:RotatingMachineManagementrelayforapplicationonawiderangeofsynchronousandinductionmachines
• P34x:Generatorprotectionforsmalltosophisticatedgeneratorsystemsandinterconnectionprotection
• P44x:FullschemeDistanceprotectionrelaysforMV,HVandEHVsystems.
• P54x:LineDifferentialprotectionrelaysforHV/EHVsystemswithmultiplecommunicationoptionsaswellphasecomparisonprotectionforusewithPLC.
• P74x:NumericalBusbarprotectionsuitableforapplicationonMV,HVandEHVbusbars
• P94x:Frequencyprotectionforloadshedding,loadrestorationandgeneratorabnormaldetection
CONTROLProgrammableschemelogic
Simplelogicequationsaswellasblocklogicisavailableinanumberof20seriesrelays,seefigure1.Powerfulgraphicallogicavailableinthe30and40seriesrelaysallowstheusertocustomizetheprotectionandcontrolfunctionsoftherelay.Itisalsousedtoprogramthefunctionalityoftheopto-isolatedinputs,relayoutputs,LEDanduseralarms.TheProgrammableSchemeLogiccanbeusedtoimplementadditionalsupervisionfeatures,suchastripcircuitsupervisionorimplementcomplexlogicsuchasfrequencyrestorationschemes.Schemeshavebeendevelopedcapableofsupervisingthetripcoilandcircuitwiththecircuit
breakeropenorclosed.ThePx40gatelogicincludesOR,AND,NOTandmajoritygatefunctions,withtheabilitytoinverttheinputsandoutputs,andprovidefeedback.Anumberofgeneralpurposelogictimersarealsoavailableaswellasthosetimersusedtoconditiontherelaycontacts.Thesystemisoptimized(eventdriven)toensurethattheprotectionoutputsarenotdelayedbythePSLoperation.TheProgrammableSchemeLogicisconfiguredusingthegraphicalMiCOMS1PCsoftware,asshowninFigure2ThePx30logiccanbecreatedusingBoolean
Figure3,ProgrammablelogicforPx30
Figure2,ProgrammablelogicforPx40
Figure1,FlexiblelogicforPx20
Equationsoragraphicalinterfaceasshowninfigure3.
IndependentProtectionSettingsGroups
Uptotwosettinggroupsaresupportedinthe20Serieswhereasthe30and40seriescanofferuptofourindependentsettinggroups.Thesecanbeactivatedlocally,remotelyorviaadedicatedinputandareusedtoallowfordifferentsystemoperatingconditionsandwhereadaptiverelayingisapplied.
04MiCOM Px20, Px30, Px40Protection Relays
Measurement&PostFaultAnalysis
TheMiCOMRangeofrelaysarecapableofmeasuringandstoringawiderangeofsystemquantitiessuchasCurrent,Voltage,Frequency,Poweretc.dependingontherelayfunctionality.Allevent,faultanddisturbancerecordsaretimetaggedtoaresolutionof1msusingtheinternalrealtimeclockandarestoredinnon-volatilememory.Asupervisedlithiumbatteryensuresthattherealtimeclockandrecordsaremaintainedduringauxiliarysupplyinterruptions.WhererelaysarecommunicatingtoaSCADAsystem,theprotocols’telegramscanbeusedforexternaltimesynchronizationoralternativelyanoptionalIRIG-BportisavailableforaccuratetimesynchronizationonallPx30andPx40MiCOMrelays.Somerelayscanalsouseanoptoinputtosynchronizetherelay’sclock.
PowerSystemMeasurement
Acomprehensivesetofmeasurementvaluesincludinginstantaneousandderivedvaluesareavailableontherelays.ThesemeasuredvaluescanbedisplayedonthefrontLCDdisplayortransferredlocallyorremotelyaspertheuserrequirements.
POST FAULT ANALYSISEventrecords
Thesearegeneratedforstatuschangestologicinputsandoutputs,modificationstooneormoresettingparametersandalarmsignals.Alleventsaretime-taggedandstoredinchronologicalorderinacyclicmemorywheretheoldestrecordisoverwrittenoncetherelay’smaximumeventcountisexceeded.ThesearereadilyavailableforviewingontheLCD,orextractionviathecommunicationports.
Figure4,OscillographyanalysisusingMiCOMS1SoftwareforOptimumresults
Figure5,Atypicalsubstationcontrolsystem
Faultrecords
Atleast5recordsaresupportedonallrelaysandforeveryfault,thefollowinginformationiscapturedintherelayrecords• Afaultnumber• Thedateandtime• Theactivesettinggroup• Thefunctionthatissuedthetrip• Themagnitudeofthecurrent/voltagethatgave
risetothetripcommand
Disturbancerecords
Theinternaldisturbancerecorderwillrecordthesampledvaluesofallanaloginputvariablessuchasphasecurrentsandvoltagesetc.whereapplicableduringafault.OscillographicanalysiscanbeperformedusingMICOMS1whichwillprovidethemeanstoquicklyanalyseanaloganddigitalsignalsonthesametime-scaleforconvenience.DisturbancerecordscanbeextractedfromtherelayviathecommunicationportsandsavedintheCOMTRADEformat.
RELAY COMMUNICATIONSAsstandard,afrontcommunicationportisavailableforlocalaccesstotherelay.Anauxiliaryrearcommunicationportisavailableasanoptiononrelaysprovidinganengineeringportforeasyaccesstosettings,recordsandmeasurementsforprotectionengineers.AmainrearcommunicationsportisalsoavailableforinterfacetoaSCADAsystem.Anumberofprotocolsareavailableasanoptionforthispurpose.(Seecorteccodeforeachrelay)
SCADAInterface
SCADAInterface
MasterClock(GPS)
IRIG-Bport
Modem(remoteaccess)
EAI232(localaccess)
05MiCOM Px20, Px30, Px40Protection Relays
LocalCommunication
ThefrontEIA(RS)232communicationporthasbeendesignedforusewiththeMiCOMS1softwareandisprimarilyforconfiguringtherelaysettingsandprogrammableschemelogic.Itisalsousedtolocallyextractevent,faultanddisturbancerecordinformationandcanbeusedasacommissioningtoolbyviewingallrelaymeasurementssimultaneously.InPx20/Px30thefrontEIA(RS)232isalsousedtoupgraderelaysoftware.InPx40aseparatefrontparallelportisusedforthis.
RearCommunication
TherearcommunicationportisbaseduponEIA(RS)485voltagelevelsandisdesignedforpermanentmultidropconnectiontonetworkcontrolanddataacquisitionsystems.Anoptionalfiberopticcommunicationsportisalsosupportedonthe30and40platforms.Ingeneral,thefollowingprotocolsareavailableatorderingorviasettingselectionontherelays.• Courier/K-Bus• Modbus• IEC60870-5-103• DNP3.0ThefollowingprotocolisonlyavailableonPx30/Px40relaymodelswithanEthernetportcurrently.• IEC61850Fig5illustratestheflexibilitywithwhichtheMICOMrangeofrelayscanbeintegratedintoaSCADAsystemaswellasprovideengineeringdataforremoteaccessbyutilityengineers.
USER INTERFACESTheuserinterfaceandmenutextareavailableinEnglish,French,GermanandSpanishasstandard.OtherlanguagessuchasforexampleRussianandItalianaresupportedonsomerelaysdependingonmarketrequirements.TheabilitytocustomizethemenutextandalarmdescriptionsarealsosupportedonPx30andPx40.
3
5
4
8
6 1
Figure6,Px40seriesuserinterface7
2
1
5
4
2
3
10
Figure7,Compactcaseuserinterface
7
3
2
6 1
9
5
4
8
Figure8,Px30seriesuserinterfacewithbaycontrol
Thefrontpaneluserinterfaces,asshowninFigures6,7&8comprise:(1)Aback-litliquidcrystaldisplay(20,30,40series)GraphicLCDdisplay(30seriesonly)(2)FourfixedfunctionLEDs(20,40series)FivefixedfunctionLEDs(30series)(3)UptoFouruserprogrammableLEDs(20series)UptoEightuserprogrammableLEDs(40series)TwelveuserprogrammableLEDs(30series)(4)Menunavigationanddataentrykeys.(5)“READ”and“CLEAR”keysforviewingandresetofalarms(6)Anuppercoveridentifyingtheproductname,whichmayberaisedtoviewfullproductmodelnumber,serialnumberandratinginformation.(7)AlowercoverconcealingthefrontEIA(RS)232port,download/monitorportandbatterycompartment.Covernotavailableoncompactcase.(8)Facilityforfittingasecurityseal(9)Baycontrolkeysupto6bayscontrol(30series)(10)ProgrammableFunctionkeys(compactrangeand30series)
06MiCOM Px20, Px30, Px40Protection Relays
SELF MONITORINGComprehensiveSelfmonitoringprocedureswithinthedeviceensurethatinternalhardwareandsoftwareerrorsaredetectedthusensuringahighdegreeofreliability.Automatictestsareperformedduringstart-upandacyclicselfmonitoringtestsareperformedduringoperation.Anydeviationsarestoredinnon-volatilememoryandtheresultofthefaultdiagnosisdetermineswhetherablockingofthedevicewilloccurorwhetheranalarmisonlyissued.
MECHANICAL DESCRIPTIONCases
TheMiCOMseriesrelaysarehousedinaspeciallydesignedcaseprovidingahighdensityoffunctionalitywithintheproduct.Communicationportsandmodel/serialnumberinformationisconcealedbyupperandlowercovers.Physicalprotectionofthefrontpaneluserinterfaceandpreventionofcasualaccessisprovidedbyanoptionaltransparentfrontcover,whichcanbefittedoromittedaccordingtochoice,sincethefrontpanelhasbeendesignedtoIP52protectionagainstdustandwaterThecasesaresuitableforeitherrackorpanelmountingasshowninFig.9.
Anoptionforsurfacemountingisalsosupportedonthe30seriesrangeandacompactcaseoptionisavailableonafew20and30seriesrelaysforinstallationswithspacelimitations.Takingintoaccountthedifferingcasewidths-relayscanbecombinedwithorwithouttheuseofstandardblankingplatestoformacomplete19”mounting.Thissavesspaceandallowsforaneatinstallation.
Wiring
ExternalconnectionsaremadeviaringtypeterminalonallMiCOMrelayexceptonthecompactcase.Thesetakepintypeterminalsalongwiththe30seriesrelaysasanoption.
P439
CG
GTRIP
ALARM
HEALTHY
EDIT MODE
X6
OUT OF SERVICE
F1
F2
F3
F4
GC
B
E
A
A
A
A (in
cludi
ng b
rack
ets)
C
D
B
F
B
D
GE
FRO
NT
VIE
WSI
DE
VIE
W
103240
(inc. wiring)270
(inc. wiring)157.5
177
155139,8223
166,4249,6
155.2156
213.4
260.2 253.6 177.5
184.5
434.8227.9
481.6
260.2
481.6257.1 177.5
206
240(inc. wiring)
309.6 270(inc. wiring)
177
413.2
483
157.5 max
294.4
175.6
253310
88.5 162.5 294.4
Note: Maximum sizes for guidance only, for specific product information please check the relevant product documentation. (All dimensions in mm)
In addition 24TE case variant available for P132 1)
1)
A
Typical case dimensions Table B C D E F G
20TE
Px20
30TE
40TE
40TE rack
84TE
84TE rack
40TE surface
Px30
84TE surface
40TE
60TE
80TEPx40
80TE rack
compact
Px20
C/
Px30
C
Compact incl . brack.
Figure9,Typicalcasedimensions
07MiCOM Px20, Px30, Px40Protection Relays
TECHNICAL DATAPowersuppliesAwiderangeofpowersupplyoptionsareavailableattheorderingstage.
DigitalInputsAwiderangeofoptoinputvoltagesaresupportedthroughouttherange
Nominal VoltageVnom.
Operate Range (V) DC AC
Px20 Ph 2
24-60Vdc 19.2-76Vdc -48-250Vdc48-240Vac 38.4-300Vdc 38.4-264
Vac
Px20 Ph 1
24-60DC 19.2-72 -48-150DC 38.4-180 -130-250DC100-250AC
104-300DC-
-80-275
125-250DC100-250AC
100-300DC-
-80-275AC
Px30 24DC48-250DC
19-2938-300
-100-230
Px4024-48DC 19-65 -48-125DC 37-150 24-110110-250 87-300 80-265
Auxiliary Voltage Digital Operating range (V)Px20Ph 2
24-250Vdc 19.2-300Vdc24-240Vac 19.2-264Vac
Px20Ph 1
24-60DC 15.2-60DC48-150DC 25.6-180DC130-250DC/100-250AC 38.4-300DC/38.4-275AC
125-250DC/100-250AC 84-174DC
48-150DC130-250DC
25.6-180(ACimmune)38.4-300(ACimmune)
Px30
ThresholdsStandardVariant>18(Uaux.24-250VDC)FurtherOptions>73V(67%ofUaux.110VDC)>90V(60-70%ofUaux.125/150VDC)>146V(67%ofUaux.220VDC)>155V(60-70%ofUaux.220/250VDC)
Px40Vmin/Vmaxthresholds
24/27,30/34,48/54,110/125and220/250(softwareselectable)
General Series Data Px20 Px20C Px30 Px30C Px40 Frequency50/60Hz X X X X XDualrated1A/5A X X X X XCTthermalratingscontinuous:4Inomfor10s:30Inomfor1s:100Inom
X X X X X
OptoInputs max8 max7 max.34 max2 max.24OutputContacts max9. max8 max46 max8 max.46Carry:continuous 5A 5A 5A 5A 10AMakeandcarry 30Afor3s 30Afor3s 30Afor0.5s 30Afor0.5s 30Afor3sLEDIndication(freelyprogrammable) 8(4) 8(4) 23/18(forproductswith
textdisplay) 17(12) 12(8)
FunctionKeys/HotKeys No 4 6(forproductswithtextdisplay) 4 10functions/2hotkeys
(availableonsomemodels)SettingsGroups 1/2 2 4 4 4(2)FaultRecords 5/25* 5 8 8 5EventRecords 75/250* 75 200 100 250-512
DisturbanceRecords 5(15smax) 8(24smax) 8(16.4smax) 8(16.4smax) 75smax.
ProgrammablelogicFlexiblelogic(availableonsomemodels)
Simple‘AND’logic Fullyprogrammable Fullyprogrammable Fullyprogrammable
IRIGB No No Option Option Option
LCDDisplay Alphanumeric Alphanumeric Alphanumeric/Graphical(somemodelsonly) Alphanumeric Alphanumeric
FrontPort(RS232) Yes(mostmodels) Yes Yes Yes Yes
RearPort Yes Yes Yes,2ndrearportoption Yes,2ndrearportoption Yes,2ndrearportoption
CourierEIA(RS)485(availableonsomemodels)
No EIA(RS)485orfiber EIA(RS)485orfiber K-Bus/EIA(RS)485orfiber(somemodelsonly)
Modbus EIA(RS)485 EIA(RS)485/Glassfiber EIA(RS)485orfiber EIA(RS)485orfiber EIA(RS)485orfiber(some
modelsonly)
IEC60870-5-103 EIA(RS)485 EIA(RS)485/Glassfiber EIA(RS)485orfiber EIA(RS)485orfiber EIA(RS)485orfiber(some
modelsonly)IEC60870-5-101 No No EIA(RS)485orfiber EIA(RS)485orfiber No
DNP3.0
EIA(RS)485(availableonsomemodelsonly)
No EIA(RS)485orfiber EIA(RS)485orfiber EIA(RS)485orfiber(somemodelsonly)
IEC61850 No No Availableonsomemodels No AvailableonsomemodelsOneBoxBayControlwithMimic No No Yes(availableonsome
models) No No
Terminals Ring Pin PinorRingType Pin Ring*AvailableonMiCOMphase2forP120,P122,P123,P125,P126,andP127
08MiCOM Px20, Px30, Px40Protection Relays
1 4 4 4 4 4 4 1 4 4 4 4 2 4 5 5 5
- - - - - - - 1 1 3 3 4/5 1 4/5 3 3 3/4
5
425
3/4
2 2 3 7 5 - 5 4 7 7 2 40 16 40 8 16 32
5 5 7 8 9 2 7 7 9 9 8 32 24 32 7 15 30
- - - - - 1 1 - - - - - - - - -
- - - - - X X - - - -
-
- - - - - -
16
15
-
-
32
32
-
-
- - -
- - -
- - -
- - -
- - -
- - -
X - -
- X X
- X X
- - -
- - -
- - -
- - - - - -
- - - - - -
X - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - X -
X X X X - X
X X X X X X
- - - - - -
- - - - X X
- - - - - - -
- - 10 1 10
- - 1/2 1/2 1/2
- X X - X
- - X - X
- - - - X
- - X - X
- - - X -
X X X - X
X X X X X
X X X X X
X X X X X
- - - -
- - -
- - -
X X X
- - -
- - -
X X X
- - -
X X X
X X X
X X X
X X X
X X X
-
-
-
X
-
-
-
-
-
-
-
-
-
-
-
X
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
- - - - - - - - - - X
- - - - - - X X X X X
- - -
-
- - - - - - -
-X X X - - X X X -
- - - - - - - - - -
- X X X - X - X X
X
X X
- X X X X X - X X X X
- X X X - - X X X X
- - - - - - - - X X X
- - - - - - X X X X X
- - - - - - - - - X X
- - - - - - - - XX X
- - - - - - - - - X X
- - - - - - - - - X X
- - - - - - - - - - -
X X X X X X X X X X X
- - - - - - - - XX X
- X X X - X - X X X X
- - - - - - - - - X X
- - - - - - - - - X X
- - - X - X - X X X X
- - - - - - - - - - X
- X X X - X - X X - -
- X X X
X X
- X - X X
X
X X
- - - - - - X X
- - - - - - X X X X
- X X X - X - X X -
- X X X - X - X X - X
- - - - - - - - - XX
- - - - - - - - - X X
- - - - - - - - - X X
- X - - -
- X X X X
X XXX X X
- - X X X
- - X X X
- X X X X
X X X X X
- X X X X
X X X X X
- X X X X
-
-
-
XX X X
X X X X X
- X X X X
- X - - -
- X - - -
X X X X X
- X - - -
X X X X X
- X - - -
- X - - -
- X - X X
- X - - X
- - X X X
- X X X X
- X - - -
X - X X X X
- XXX X X
- X X X X
X X - - -
- X - - -
- X - - -
-
-
X
-
-
X
-
X
X
X
X
X
-
X
X
X
X
X
X
X
X
X
X
X
X
-
-
X
-
X
-
-
X
-
X
X
-
X
X
X
-
-
-
-
-
X
-
-
X
-
X
X
X
X
X
-
X
X
X
X
X
X
X
X
X
X
X
X
-
-
X
-
X
-
-
X
X
X
-- - - - - - - - XX X - X X X X X X
-- - - - - - - - - X X - X X X X X X
X
-
X
X
X
-
-
-
CT Inputs
VT inputs
Opto Inputs ( max)1
Output Contacts (max)1
Output for Striker Triggering
Magnetic Flags
RTDs (max. option)
Analogue I/O (max. option)
Function Keys/Hotkeys
Bay Control & Monitoring
- with Mimic
Interlocking Logic
1 Phase or Earth overcurrent
3 Phase overcurrent
Ground fault
Phase directional
Ground Fault directional
Sensitive directional earthfault
Transient Ground Fault directionalWattmetric earthfault
Neutral admittance
Restricted earthfault
Voltage controlled overcurrent
Negative sequence overcurrent
Thermal overload
Undercurrent
Over/Under voltage
Residual over voltage
Negative sequence overvoltage
Over/Under frequency
Rate of change of frequency
Incomplete sequence relay
Master sequence device
Lock-out
Directional Power
Circuit breaker failure
Motor
Startup Monitoring
Autoreclose
Check synchronising
Broken conductor
Cold load pick-up
Inrush blocking
Switch on to fault
Circuit breaker monitoring
Trip Circuit Supervision
Limit value monitoring
Protective Signalling
InterMicom
Protection
Device P120 P121 P122 P122C P123P124Self
Power
P124Dual
PowerP125 P126 P127 P130C P132
P138Rail
P139 P141 P142 P143 P144 P145
50/51P/N
50/51P
50/51N
67P
67N
67N
67N
67W
YN
64
51V
46
49
37
27/59
59N
47
81O/U
87R
48
34
86
32
50BF
49LR
66
79
25
46BC
Voltage transformer supervision VTS
Current transformer supervision CTS
SOTF
TCS
85
MiCOM Series DataOVERCURRENT AND FEEDER MANAGEMENT RELAYS
•Pleasenotethatsomerelaysmayhavealimitonmax.I/Owhenusedasacombination.•3V0measuredinputandallowsveeconnectedVTs.
09MiCOM Px20, Px30, Px40Protection Relays
Device P220 P225 P226C P241 P242 P243 P341 P342
CT Inputs
VT inputs
Opto Inputs (max)1
Output Contacts (max)1
RTDs/thermistors (option)
Analogue I/O (option)
Function Keys/Hotkeys
Interlocking Logic
Motor Protection
Short circuit 50/51
Motor Differential 87M
Locked Rotor 50S/51LR/51S
Reverse Power 32R
Reacceleration 27LV
Startup Monitoring/Excessive long start 66/48/51
Negative sequence overvoltage 47
Out of Step 55
Loss of load 37
Undercurrent 37P/37N
Unbalance/Lock-out 30/46/86
Speed switch inputs
Anti Backspin
14
100% Stator Earth Fault (Low Freq. Injection) 64S
Generator Protection
Generator Differential 87G
Interturn/split phase 50DT
Underimpedance 21
Pole Slipping 78
Directional Power 32L/O/R
Loss of Field 40
Restricted earthfault 64
100% Stator earth fault (3rd harmonic) 27TN
Overfluxing 24
Unintentional energisation at standstill 50/27
Voltage dependent O/C
Rotor Earth Fault
51V
64R
Ancillary Functions
Phase overcurrent 50/51P
Phase directional 67P
Ground fault 50N/51N
Ground Fault directional 67N
Negative sequence thermal 46T
Turbine abnormal frequency 81AB
Negative sequence overvoltage 47
Sensitive directional earthfault 67N
Wattmetric earthfault 64N/32N
Negative sequence overcurrent 460C
Thermal overload 38/49
Under/Over voltage 27/59
Residual over voltage 59N
Under frequency 81U
Over frequency 81O
Voltage vector shift dVq
Rate of change of frequency 81R
Circuit breaker failure 50BF
Circuit breaker monitoring
Trip Circuit Supervision TCS
P343 P344 P345
Protection
X
X
X
X
X
X
X
X
X
X
X
X
X
X
-
X
X
X
X
X
X
X
X
-
-
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
-
X
X
X
X
X
X
X
X
-
-
X
X
X
8
4
32
32
10/0
4/4
X
X
8
5
32
32
10/0
4/4
X
X
4 4 4 4 4 7 4 5
- 1 1 3 3 3 4 4
5 6 7 8 16 16 16 24
6 6 8 7 16 16 15 24
6/0 or 4/2 10/3 - 10/0 10/0 10/0 - 10/0
0/1 0/2 - 4/4 4/4 4/4 4/4 4/4
- - X X XXX X
- - - X X X X X
X
-
X
-
X
X
-
-
X
X
X
X
-
-
-
-
-
-
-
-
-
-
-
X
-
X
-
-
-
-
-
-
-
X
-
-
-
-
-
-
-
X
X X X X X
- - - - X - -
X X X X X - -
- - X X X
X X X
- -
X X - -
X X X X X - -
- - X X X - -
- - X X X - -
X X X X X - -
X X X X X - -
X X X X X - -
- -
- -
- -
- -
- -
- -
- -
- -
- -
- -
X X X X X
X X X X X
- - - - - - -
- - - - - - -
- - - - - - X
- - - - - - -
- - - - - X X
- - - XX XX
- - - - - X X
- - - - - - -
- - - - - - X
- - - - - - X
- - - - - - X
X X X X X X X
X- - - - - X
X X X X X X X
- - - - - X
- - - - - - X X X
- - - - - - X X X
- - - - - XX X X
X
X
X
X
X
X
X
X
X
X
X
X
X XX X
X
X
X
-
X
X
X
X
X
X
X
X
-
-
X
X
X
9
6
32
32
10/0
4/4
X
X
-
-
-
-
-
-
-
-
-
-
X
X
X
-
- - X X X - X
- - X X X X X
X X X X X - X
X X X X X X X
X X X X X X X
- - X X X X X
- - X X X X X
- - - - - X X
- - - - - X -
- - - - - X -
X X X X X X X
X X X X X X X
X X X X X X X X
MOTOR AND GENERATOR MANAGEMENT RELAYS
•Pleasenotethatsomerelaysmayhavealimitonmax.I/Owhenusedasacombination.
MiCOM Px20, Px30, Px40Protection Relays 10
Broken Conductor 46BC
Stub Bus Protection 50ST
Voltage/Current transformer supervision VTS/CTS
Capacitive voltage transformer supervision CVTS
P444 P445 P847Device P430C P432 P433 P435 P436Rail
P437 P438Rail
P439 P441 P442 P443
CT Inputs
VT inputs
Opto Inputs(max)1
Output Contacts(max)1
RTDs (option)
Analogue I/O (option)
Function Key/Hotkeys
Bay Control & Monitoring with Mimic
Interlocking Logic
Distance Protection
Distance 21/21N
3 pole Autoreclose 79
1/3 pole
Power Swing Blocking 78
Out of step tripping 68
Check synchronising 25
Directional Power 32
Switch on-to fault 50/27
Mutual Compensation
Rail Catenary Protection HZ
PMU
Defrost Protection
Train startups
Phasor Measurement
Phase overcurrent 50/51P
Phase directional 67P
Ground fault 50/51N
Ground Fault directional 67N
Transient Ground Fault directional 67N
Neutral admittance YN
Delta directional comparison
Wattmetric earthfault 67W
Negative sequence overcurrent 46
Directional negative sequence 46/67
Thermal overload 49
Under/Over voltage 27/59
Residual over voltage 59N
Over/Under frequency 81U
Rate of change of frequency 81R
Circuit breaker failure 50BF
Channel Aided Scheme Logic 85
Trip Circuit Supervision TCS
InterMicom
Protection
-
X
X
-
4
3
2
8
-
30
-
X X X X
-
X
X
X
-
X
-
X
X
-
-
-
-
X
X
X
X
- -
-
X
X
X
X
X
X
X
X
X
X
X
-
X
X
-
4/5
4/5
52
38
1
1/2
-
X
X
X
-
X
X
XX
X
X
X
X
-
-
-
X
X
X
X
-
-
-
X
X
X
X
X
X
X
X
X
X
-
X
X
X
-
4
20
1
1/2
-
-
X
X
-
X
X
X
X
-
-
-
-
X
X
X
X
X
-
X
X
X
X
X
X
X
X
X
X
X
X
X
X
-
4
4/54/5
32
46
1
1/2
-
-
X
-
X
X
X
XX
X
X
-
-
-
-
X
X
X
X
X
-
X
X
X
X
X
X
X
X
X
X
X
- X -
X X -
X X X
- - -
2 4/5 3
1 4/5 2
28 32 28
46 46 46
1 1 1
1/2 1/2 1/2
- -
- - -
- - -
X X X
- - -
- X -
- X -
- X -
- X -
- -
X X X
- X -
16 2/3 - 25/50/60
- - X
X - X
X X X
- X X
- X -
- X -
- - -
- - -
- - -
- - -
- X -
- X -
X X X
X X X
- X -
- X -
- X -
X X X
- X -
X X X
XX -
X X X X
X X X X
X X X X
- X X - -
X
X
X
X
4
4
24
46
-
-
X
-
X
-
X
X
-
X
-
X
X
-
-
-
X
X
X
X
-
-
-
X
X
X
-
-
-
-
X
X
X
X
4
4
24
32 32
-
-
X
-
-
-
X
X
-
X
-
X
-
-
-
-
X
X
X
X
-
-
-
-
X
X
X
X
X
-
-
X
X
X
X
X
X
X
-
12
12
32
X
-
X
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X
X
X
X
X
-
-
-
-
X
X
X
X
X
X
X
X
X
X
X
-
X
-
4 4 4 4
4/5 4 4 4
40 8 16 24
26 14 21 32
1 - - -
1/2 - - -
- X X X
X - - -
- -- - -X
X X X X
X X - -
- - X X
X X X
- - -
X X X X
X
X
X
X - - -
X X X X
- X X X
- - - -
- - - -
- - - -
- - - - -- - --- - - -
X X X X
X X X X
X X X X
X X X X
X - - -
XX X X
- - - X
- -
- -
-
XX X X - -
X X X X
X X X X
X X X X
X X X X
X - - X
X - - -
X - - -
X X X X
X X X X
X X X X
X - X X
di/dt,dv/dt,dΦ/dt
ΔI/ΔV
DISTANCE RELAYS AND PHASOR MEASUREMENT UNIT
•Pleasenotethatsomerelaysmayhavealimitonmax.I/Owhenusedasacombination.
MiCOM Px20, Px30, Px40Protection Relays 11
LINE DIFFERENTIAL, TRANSFORMER AND BUSBAR PROTECTION RELAYS
•Pleasenotethatsomerelaysmayhavealimitonmax.I/Owhenusedasacombination.
4 4 5 9 5 9 4 6 6 8 12 15 4 4 4
- - - 4 3 4 3 - - - 1 1 1 - - -
5 8 16 16 16 24 24
8 7 14 14 14 32 32
- - - - - - -
- - - - - - -
- X X X X X X
- X X X X X X
8 2 4 34 40 34 8
8 8 14 22 30 22 8
- - - 1/2 1/2 1/2 -
- - - 1 1 1 -
X X - - - - -
X X - - - - -
16 24
8 21
- -
- -
- -
- -
87P X
X
-
X
X
X
-
X
X
X
-
X
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X X X X X X X X X X X X X - X X
- - X X X X - - - - - - - - -
X X X X X X X
- - X X X X -
- - X X X XX X X X
-
- - X X X X -
- - X X X X -
- X X X X -
- X - X
X X X
X X X
- - -
X X X X X - - - - - - - -
- - - - - - - - - - - - - -
X X X X X - - - - - - - - -
X X X X X - - - - - - - -
- - - - - - - - - - - - -
- - - - - - - - - - - -
- X XX X - - - - - - - - -
X X - - - - - - - - - - -
X X - - - - - - - - - - -
X
X
X
X
X- - - - - - - - - - -
X - X - - - - - - - - -
- - - - -
X -
-
X
X -
- -
- - -
-
X X
- - -
X X X X X X - - - -
- - - - - - X - - - - - - - -
X - - - - - - - -
- X X X X X - - -
- 2 2 2 3 4 - - -
- - 2 3 3 - - -
- X X X X X - - -
- - - X X X - - -
- X X X X X - - -
- - - X X X
-
-
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - -
- - - - - - - -
- - - - - - - - - - - - X - -
- - - - - - - - - - - - - X X
- - - - - - - - - - - X - -
- - - - - - - - - - - - X - -
- - - - - - - - - - - - X - -
- - - - - - - - - - - - X X X
- - - - - - - - - - - - - X X
- - - - - - - - - - - X X X
-
-
X X X X X X -
- - - - - - - - -
-X X X X X X X
- - - - - - - -
- - - - - - - -
- - - - - -
- - - - - -
- - - - - - - - - -
X - - X X X X X X -
X X X X
X
X X X X X X -
X - - - - - - - - - - - - -
- - - - X X X -
- -
X X
-
- - -
- - - -
- -
- -
- -
- -
- -
X
- - - - -
X X X X X X X X - -
- - 3 pole3 pole 1/3 pole
1/3 pole
- - - - -
- - - - - - X
X X
4
3
2
8
-
-
X
X
-
X
X
X
-
X
-
X
-
X
X
X
-
X
X
-
-
-
X
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
X
X
-
-
X
X
- X X X X X
X X X X
X X X X
-
- - - X X X
- - - - - -
X X - - -
X X X X X
CT Inputs
VT inputs
Opto Inputs(max) 1
Output Contacts(max) 1
Analogue I/O (opti
RTDs (option)
Function Keys/Hotkeys
Interlocking Logic
Protection
Line Differential
2 terminal
2/3 terminal
FO signalling
Metallic signalling
Transient Bias (CT saturation)
SDH/Sonet ne
In Zone transformer
2 harmonic restraint
Vector Compensation
2 breaker configuration
Direct/Permissive Intertripping
Phase Comparison
PLC signalling
Transformer Differential
windings
Restricted earth fault
overfluxing/5 harmonic
overexcitation
2 harmonic restraint
Busbar Protection
Central unit up to 28 feeders
Peripheral units 8 zones
regated differential 8 zones
Sensitive earth fault differential 6 zones
Check Zone 8 zones
CT supervision
CT Saturation Detection
Fibre optic signalling
Ancillary Functions
Phase overcurrent
se directional
Ground fault
Ground Fault directional
Sensitive directional earthfault
Wattmetric earth
Distance Protection
Power Swing Blocking
Check Sync
Negative sequence overcurrent
Thermal overload
Loss of load/Undercurrent
Under/Over frequency
Circuit breaker failure
Autoreclose
Over/Under voltage
Trip Circuit Supervision
CT supervision
Device P521 P541P530C P542 P543 P544 P545 P546 P547 P630C P631 P632 P633 P634 P741 P742 P743
4
on)
tworks
-nd
th
nd
-
-
Phase seg
–
Pha
fault
81U/O
50BF
79
27/59
TCS
87PC
87P
87G/64
24
87BB
87P
87N
87CZ
CTS
50/51P
67P
50/51N
67N
CTS
67N
64W
21
78
25
46
49
37
EnergyAutomation-DS-PROTRange-1827-EN
©2010SchneiderElectric-Allrightsreserved
Asstandards,specificationsanddesignschangefromtimetotime,pleaseaskforconfirmationoftheinformationgiveninthispublication.
Publishing:SchneiderElectricDesign:SchneiderElectricPrinting:
This document has been printed on ecological paper
10-2010
Schneider Electric35,rueJosephMonierCS3032392506Rueil-MalmaisonCedex,FranceTel:+33(0)141297000
RCSNanterre954503439Capitalsocial896313776€www.schneider-electric.com
MiCOM Px20, Px30, Px40Protection Relays 12
4 - 6 - - - - -
- 4 3 4 4 4 3 3
5 48 16 2 5 5 16 32
9 32 24 4 8 8 15 30
X - - - - - - -
X - - - - - - -
X - - - - - - -
X - - - - - - -
- X - - - - - -
- X - - - - - -
- X - - - - - -
- X - - - - - -
- - X - - - - -
- - X - - - - -
- - X - - - - -
- - X - - - - -
- - - X X X X X
- - - X X X X X
- - - X X X - -
- - - - X X - -
- - - - X X X X
- - - - - X X X
- - - - - X X
- - - - - - X X
- - - - - - X X
- - - - - - X X
X X X - X X X X
yes by
logic
Device P821 P842 P846 P921 P922 P923 P941 P943
CT Inputs
VT inputs
Opto Inputs(max)
Output Contacts(max)
Protection
Breaker Failure Protection 50BF
2 Stage
Pole Discrepancy
Dead Zone Function
Autoreclose 79
Mesh Corner/Single Switch
Check Sync 25
Ferroresonance Suppression
Open Line Detector DLO
High Speed Breaker Fail 50BF
Fast Hybrid Output contacts
3 pole tripping
Voltage and Frequency Protection
Undervoltage 27
Overvoltage 59
Residual Overvoltage 59N
Phase Sequence Voltage 47/27D
Under/Over frequency 81U/O
Rate of change of Frequency (df/dt+t)
81R
Frequency supervised Rate of change of Frequency (f+df/dt)
81RF
Frequency supervised average Rate of change of Frequency (f+Δf/Δt)
81RAV
Generator Abnormal Frequency 81AB
Load Restoration logic
Trip Circuit Supervision TCS
VOLTAGE, FREQUENCY AND ANCILLARY PROTECTION RELAYS