med gas vac system short

Upload: danilo-pretinho

Post on 07-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/3/2019 Med Gas Vac System Short

    1/8

    PSD

    1

    31

    Medical Gasand Vacuum

    Systems

    Continuing Education from Plumbing Systems & DesignKenneth G.Wentink, PE, CPD, and Robert D. Jackson

    JANUARY/FEBRUARY 2006

    PSDMAGAZINE.ORG

  • 8/3/2019 Med Gas Vac System Short

    2/8

    GENErAl

    Health care is in a constant state o change, which orces the

    plumbing engineer tokeep upwithnew technology toprovideinnovative approaches to thedesign o medical-gas systems. Indesigningmedical-gasandvacuumsystems,thegoalistoprovideasaeandsufcientowatrequiredpressurestothemedical-gasoutletorinletterminalsserved.Systemdesignandlayoutshouldallowconvenientaccessbythemedicalstatooutlet/inlettermi-nals,valves,andequipmentduringpatientcareoremergencies.

    Tis section ocuses on design parameters and current stan-dardsrequiredorthedesignononammablemedical-gasandvacuum systems used in therapeutic and anesthetic care. Teplumbingengineermustdeterminetheneedsothehealth-caresta.rytoworkcloselywiththemedicalstatoseekanswerstotheollowingundamentaldesignquestionsatthestartoaproj-ect:1. Howmanyoutlet/inletsarerequestedbysta?

    2. Howmanyoutlet/inletsarerequired?

    3. Basedoncurrentconditions,howotenistheoutlet/inletused?

    4. Basedoncurrentconditions,whatistheaveragedurationouseoreachoutlet/inlet?

    5. Whatistheproperusage(diversity)actortobeused?

    MEDICAl-GASSySTEMDESIGNChECklIST

    As any hospital acility mustbe specially designed to meet theapplicablelocalcoderequirementsandthehealth-careneedso

    thecommunityitserves,themedical-gasandvacuumpipingsys-temsmustalsobedesignedtomeetthespecicrequirementsoeachhospital.

    Followingaretheessentialstepstoawell-designedandunc-tionalmedical-gaspipedsystem,whicharerecommendedtotheplumbingengineer:1. Analyzeeachspecicareaothehealth-careacilitytodeter-

    minetheollowingitems:A. Whichpipedmedical-gassystemsarerequired?B. Howmanyoeachdierenttypeomedical-gasoutlet/inlet

    terminalarerequired?C. Whereshouldtheoutlet/inletterminalsbelocatedor

    maximumefciencyandconvenience?

    D. Whichtypeandstyleooutlet/inletterminalbestmeettheneedsothemedicalsta?

    2. Anticipateanybuildingexpansionandplaninwhichdirec-tiontheexpansionwilltakeplace(verticallyorhorizontally).Determinehowthemedical-gassystemshouldbesizedand

    valvedinordertoaccommodatetheutureexpansion.

    3. Determinelocationsorthevariousmedical-gassupplysources.

    A. Bulkoxygen(O2).B. High-pressurecylindermaniolds(O2,N2OorN2).

    C. Vacuumpumps(VAC).D. Medical-aircompressors(MA).

    4. Preparetheschematicpipinglayoutlocatingtheollowin

    A. Zonevalves.B. Isolationvalves.C. Masteralarms.D. Areaalarms.

    5. Calculatetheanticipatedpeakdemandsoreachmedicasystem.Appropriatelysizeeachparticularsectionsoastoavoidexceedingthemaximumpressuredropsallowed.

    6. Sizeandselectthevariousmedical-gasandvacuumsuppequipmentthatwillhandlethepeakdemandsoreach

    system,includingutureexpansions.Ithisprojectisanationtoanexistingacility,determinetheollowing:

    A. Whatmedicalgasesarecurrentlyprovidedandwhatathelocationsandnumberothestations?

    B. Canthecurrentgassupplier(orthehospitalspurchasdepartment)urnishtheconsumptionrecords?

    C. Arethecapacitiesotheexistingmedical-gassupplystemsadequatetohandletheadditionaldemand?

    D. Areanyexistingsystemsvalvedthatcouldbeusedorextension?Aretheexistingpipesizesadequatetohantheanticipatedadditionalloads?

    E. Whattypeoequipmentisinuseandwhoisthemanuturer?Isthisequipmentstate-o-the-art?

    F. IsiteasibletomanioldthenewandexistingequipmeG. WhatisthephysicalconditionotheexistingequipmeH. Isthereadequatespaceavailableorthenewmedical-

    supplysystemsandrelatedequipmentattheexistingtion?

    I. Isexistingequipmentscheduledtobereplaced?(Amatenancehistoryotheexistingequipmentmayhelpindetermination.)

    NuMBEroFSTATIoNS

    Terststepistolocateandcounttheoutlet/inlets,otencstations,oreachrespectivemedical-gassystem.Tisisusdonebyconsultingaprogrampreparedbytheacilityplann

    architect.Tisprogramisalistoalltheroomsandareasiacilityandtheservicesthatarerequiredineach.Iaprogramnotbeenprepared,theoorplansortheproposedacilitybeused.

    Tereisnocodethatspecicallymandatestheexactnumostationsthatmustbeprovidedinvariousareasorroomshealth-careacilities.Inact,thereisnoclearconsensusoopiamongmedicalauthoritiesordesignproessionalsastohowmstationsareactuallyrequiredintheacilityareas.Guidelines

    CONTINUING EDUCAT

    Medical Gas andVacuum Systems

    Reprinted fromAmerican Society of Plumbing Engineers Data Book Volume 3: Special Plumbing Systems, Chapter 2: Medical Gas and VacSystems. 2000, American Society of Plumbing Engineers.

    PlumbingSystems&Design JANUARY/FEBRUARY 2006 PSDMAGAZ

  • 8/3/2019 Med Gas Vac System Short

    3/8

    publishedby the American Institute o Architects(AIA),NationalFireProtectionAssociation(NFPA),andASPEthatrecommendtheminimumnumberostationsorvariousservicesinspecicareas.

    Te mostoten-usedrecommendations in deter-miningthenumberostationsorhospitalsarethosenecessarytobeaccreditedbytheJointCommissionor the Accreditation o Hospitals Organization(JCAHO).AccreditationisrequiredorMedicareandMedicaid compensation. Te JCAHO publishes a

    manualthatreerstotheAIAguidelinesorthemini-mum number o stations or oxygen, medical air,andvacuumthatmustbeinstalledinordertoobtainaccreditation.Ithisisaactorortheacility,theserequirements are mandatory. Other jurisdictions,suchasstateorlocalauthorities,mayrequireplanstobeapprovedbylocalhealthorbuildingofcials.Tese approvalsmay require adhering to the stateorlocalrequirementsand/orNFPA99,Health-CareFacilities.

    I accreditation or the approval o authorities isnotaactor,thenumberandarealocationsosta-tionsarenotmandated.Teactualcountthenwilldepend upon requirements determined by eachindividualacilityoranothermemberothedesignteam using both past experience and anticipateduture use, oten using the guideline recommenda-tionsasastartingpoint.

    MEDICAl-GASFlowrATES

    Eachstationmustprovideaminimumowrateortheproper unctioning o connected equipment underdesignandemergencyconditions.Teowratesanddiversity actors vary or individual stations in eachsystemdependingonthetotalnumberooutletsandthetypeocareprovided.

    Teowrateromthetotalnumberooutlets,with-outregardoranydiversity,iscalledthetotalcon-nectedload.Ithetotalconnectedloadwereusedorsizingpurposes,theresultwouldbeavastlyoversizedsystem,sincenotallo thestationsintheacilitywillbeusedatthesametime.Adiversity,orsimultane-ous-useactor,isusedtoallowortheactthatnotallothestationswillbeusedatonce.Itisusedtoreducethesystemowrateinconjunctionwiththetotalcon-nectedloadorsizingmainsandbranchpipingtoallpartsothedistributionsystem.Tisactorvariesordierentareasthroughoutanyacility.

    Teestimatedowrateanddiversityactorsorvarioussystems,areastations,andpiecesoequipmentareoundinable1.

    otaldemandormedical-gassystemsvariesasaunctionotimeoday,month,patient-carerequirements,andacilitytype.Tenumberostationsneededorpatientcareissubjectiveandcannotbequaliedbasedonphysicalmeasurements.Knowingthetypesopatientcareand/orauthorityrequirementswillallowplacementostationsinusagegroups.Tesegroupscanestablishdemand and simultaneous-use actors (diversities), which areusedinthecalculationorsizingaparticularsystem.Allmedical-gaspipingsystemsmustbeclearly identiedusinganapprovedcolor-codingsystemsimilartothatshowninable2.

    MEDICAl-GASSySTEMDISPENSINGEquIPMENT

    Medical-gas outlet/inlet terminals Most manuacture

    medical-gas system equipment oer various types o medgasoutlets.Tesemedical-gasoutletsareavailableinvariouorders(e.g.,O2-N2O-Air),center-linespacing,andorexposedconcealedmountings.OutlettypesandcongurationsmusttherequirementsothelocaljurisdictionalauthorityandN99.All outlets must be properly identiedandconrmed.shouldalsobetakentoaccuratelycoordinatethevariouspiecmedical-gasdispensingequipmentwiththearchitectandmedstainvolvedinthegivenproject.Itheprojectisarenovationoutlettypesshouldmatchexistingequipment.Withpreabripatientheadwallunits,themedical-gasoutletsaregenerallynishedbytheequipmentmanuacturer,anditis veryimpothatcoordinationbemaintainedbytheengineersothatunn

    table 1 Outlet Rating Chart or Medical-Vacuum Piping Systems

    Free-Air Allowance, cm(L/min) at 1 atmosphere

    Zone Allowances CorrRisers, Main Supply Li

    Valves

    Location o Medical-Surgical VacuumOutlets Per Room Per Outlet

    SimultaneousUsage Factor

    (%)

    Air toTranspocm (L/m

    Operating rooms:Major A (Radical, open heart; organtransplant; radical thoracic) 3.5 (100) 100 3.5 (1Major B (All other major ORs) 2.0 (60) 100 2.0 Minor 1.0 (30) 100 1.0

    Delivery rooms 1.0 (30) 100 1.0 Recovery room (post anesthesia) andintensive-care units (a minimum o 2outlets per bed in each such department):

    1st outlet at each bed 3 (85) 50 1.5 2nd outlet at each bed 1.0 (30) 50 0.5 3rd outlet at each bed 1.0 (30) 10 0.1 All others at each bed 1.0 (30) 10 0.1

    Emergency rooms 1.0 (30) 100 1.0 Patient rooms:

    Surgical 1.0 (30) 50 0.5 Medical 1.0 (30) 10 0.1 Nurseries 1.0 (30) 10 0.1

    Treatment & examining rooms 0.5 (15) 10 0.05 Autopsy 2.0 (60) 20 0.04

    Inhalation therapy, central supply &instructional areas 1.0 (30) 10 0.1 a Free air at 1 atmosphere.

    table 2 Color Coding or Piped Medical Gases

    Gas Intended or Medical Use United States Color Canada Color

    Oxygen Green Green on whitea

    Carbon dioxide Gray Black on gray

    Nitrous oxide Blue Silver on blue

    Cyclopropane Orange Silver on orange

    Helium Brown Silver on brown

    Nitrogen Black Silver on black

    Air Yellow* White and black on black and white

    Vacuum White Silver on yellowa

    Gas mixtures (other thanmixtures o oxygen and nitrogen)

    Color marking o mixtures shall be a combination o colorcorresponding to each component gas.

    Gas mixtures o oxygen andnitrogen

    19.5 to 23.5% oxygenAll other oxygen concentrations

    YellowaBlack and green

    Black and whitePink

    Source: Compressed Gas Association, Inc.a Historically, white has been used in the United S tates and yellow has been used in Canada to identiy vacuum systems.

    Thereore, it is recommended that white notbe used in the United States and yell ow notbe used in Canada as a marking

    to identiy containers or use with any medical gas. Other countries may have diering specifc requirements.

    JANUARY/FEBRUARY 2006 PlumbingSystems&Design

  • 8/3/2019 Med Gas Vac System Short

    4/8

    CONTINUING EDUCATION: Medical Gas and vacuum Syste

    saryduplicationoworkisavoided.Also,withregardtotheover-the-bed medical-gas service consoles, these consoles are otenspeciedintheelectricalorequipmentsectionothespecica-tionandmedical-gasserviceoutletsarespecied,urnished,andinstalledunderthemechanicalcontract.

    Gas-outlet sequence, center-line spacing, and multiple-gang-service outlets are some o the considerations to be taken intoaccountwhenrequestinginormationromthevariousequipmentmanuacturers.Itismorepractical,intermsoboththecostotheequipmentandtheinstallation,tospeciyandselectthemanuac-

    turersstandardoutlet(s).Detailsandspecicationsregardingtheindividualstandardoutletsareusuallyavailableromallmanuac-turersuponrequest.

    Teexistingoutletsarecompatiblewiththeadaptersoundonthehospitalsanesthesiamachines,owmeters,vacuumregula-tors,etc.Careshouldbetakentomakesureallutureexpansionsinthesameacilityhavecompatibleequipment.

    Patient head-wall systems A recent and growing trend inhospital construction is the requirement or patient head-wallsystems,whichincorporatemanyservicesor thepatientscare.Teseunitsmayincludetheollowing:1. Medical-gasoutlets.

    2. Electrical-serviceoutlets(includingemergencypower).3. Directandindirectlighting.

    4. Nurse-callsystem.

    5. Isolationtransormers.

    6. Groundingoutlets.

    7. Patient-monitoringreceptacles.

    8. VacuumslideandIVbrackets.

    9. Nightlights.

    10.Electricalswitches.

    Bed locator units are also available, which serve to providepowerorthemoreadvancedpatientbeds,telephone,nightlights,

    and standard power. Tese unitsalso unction to protect the wallsrom damage as beds are movedandadjusted.

    Head walls currently vary inshape, size, type, and cost rom asimple over-the-patient-bed stan-dard conguration to elaboratetotal-wallunits.Mostmanuactur-ersomedical-gasequipmentoermedical-gas outlets or all typeso patient consoles available intodays market. When speciying

    head-walls outlets, the plumbingengineer should consider the ol-lowing:1. Istheserviceoutletselected

    compatiblewiththeexistingoutletcomponent?

    2. Doesthepatienthead-wallmanuacturerincludethetypeomedical-gasoutletsrequiredaspartotheproduct?

    Special types of ceiling-mounted, medical-gas out-

    lets In critical-care areas, which are generally consideremostindividualstobethoselocationsothehospitalprovidspecialtreatmentorserviceorthepatient(suchassurgery,reery,coronary,orintensive-careunits),thedesignersselectionplacementothemedical-gasserviceequipmentmustbed

    verycareullyinordertoprovideefcientworkcentersarounpatientorthemedicalsta.

    Manuacturers omedical-gasservice equipmentusuallyvideawiderangeoequipmentthatisavailableoruseinareas.Dependinguponthecustomerspreerenceandthea

    ablebudget,theequipmentisselectedtoprovidetheneceindividualgasservicesandaccessories.

    able3providesaquickreerenceguideortheengineertasabasisorselectingthecommonlyusedtypesooutletdispingequipment.

    Example 1Te ollowing illustrative example presentssomeo the

    importantcritical-careareaequipmentandoptionsorthestionotheequipment.

    Surgerymedical-gasservicestobepipedinclude:1. Oxygen.

    2. Nitrousoxide.

    3. Nitrogen.4. Medicalcompressedair.

    5. Vacuum.

    6. Wasteanesthetic-gasdisposal.

    Providingmedical-gasserviceoutletsinthesurgeryroombeaccomplishedinseveralways,suchastheollowing:1. Ceiling outletsIndividualmedical-gasoutletsmountedin

    ceilingwithhoseassembliesprovidingthemedicalstawconnectionsromtheoutletstotheadministeringappara

    Tismethodisconsideredbymosttobethemosteconomcalmeansoprovidinganadequategasservicetothesur

    table 3 Types o Dispensing Equipment or Specifc Areas

    Hospital Areas

    Medical Gas Outlet Dispensing Equipment

    Wall-MountedOutlets

    PatientCare Head

    Wall

    Ceiling-Mounted

    Outlets withHose Stops

    RigidCeiling

    Columns

    RetractableCeiling

    Columns

    Ceilingwith Gas

    Stacks

    NitrCon

    CabAutopsy rooms Delivery rooms Emergency examination and treatmentrooms

    Emergency operating rooms Induction rooms Labor rooms Major surgery rooms

    Minor surgery, cystoscopy Neonatal intensive care units Normal nursery rooms Nursery workrooms O.B. recovery rooms Patient rooms Pediatric and youth intensive care unit Post-operative recovery rooms Premature and pediatric nursery rooms Pre-op holding rooms Radiology rooms Respiratory care unit Specialized surgeries (cardiac and neuro)

    PlumbingSystems&Design JANUARY/FEBRUARY 2006 PSDMAGAZ

  • 8/3/2019 Med Gas Vac System Short

    5/8

    areas.Teceilinggas-serviceoutletsaregenerallylocatedatboththeheadandtheoototheoperatingtableinordertoprovidealternatepositioningotheoperatingtable.

    2. Surgical ceiling columns Surgicalceilingcolumnsareusu-allyavailableintwodesigns:rigid(apredeterminedlengthromtheceilingheightabovetheoor)andretractable.Bothsurgicalceilingcolumnsprovidemedical-gasserviceswithinanenclosurethatprojectsdownromtheceiling.Teceilingcolumnsareusuallylocatedatoppositeendsotheoperatingtableinordertoprovideconvenientaccesstothemedical-gasoutletsbytheanesthesiologist.Inadditiontothemedical-gasoutlets,theseceilingcolumnscanbeequippedwithelectri-caloutlets,groundingreceptacles,physiologicalmonitorreceptacles,andhooksorhangingintravenous-solutionbottles.

    Mostmanuacturersoeringsurgicalceilingcolumnsallowormanyvariationsinroomarrangementsomedical-gasservicesandrelatedaccessories,dependinguponthespeciccustomersneedsandtheengineersspecications.Whenspeciyingthistypeoequipment,itisnecessarytospeciycareullyallmedical-gasservicerequirementsandtheirdesiredarrangement(s).Also,theengineermustcoordinateallotherrequiredserviceswiththe

    electricalengineerandmedicalsta.3. Surgical gas tracks Surgicalgastracksareormsoceiling

    outletandhose-droparrangementsthatallowthemovementothehosedropsromoneendotheoperatingtabletotheotheronslidingtracksmountedontheceiling.Teseprod-uctsarecurrentlyavailableromvariousmanuacturersandallprovidethesamebasicservices.Teproperselectionandspecicationospecictypesarebasedonindividualcus-tomerpreerence.Manyvariationsinproductsandparticularproductapplicationsareavailableincritical(intensive)careareas.Consultationwithappropriatemanuacturersorrec-ommendationsisalwaysadvisable.

    4. Articulating ceiling-service centerArticulatedceiling-ser-vicecentersaremovedbypneumaticdrivesystemsandaredesignedortheconvenientdispensingomedical-gasandelectricalservicesinoperatingrooms.Temedical-gasandelectricalsystemsarecompleteorsingle-pointconnectiontoeachoutletatthemountingsupportplatorm.

    High-pressure nitrogen (N2) dispensing equipment Specialconsideration must be given by the plumbing engineer to theplacementothenitrogenoutlets.Teprimaryuseonitrogengasinhospitalsisordrivingturbo-surgicalinstruments.Variationsotheseturbo-surgicalinstruments,inboththeirmanuactureandtheirintendeduse,willrequirethatseveraldierentnitrogen-gaspressurelevelsbeavailable.Forthisreason,itisnecessarythat

    the engineer provide an adjustable pressure-regulating devicenearthenitrogengasoutlet.Anitrogencontrolpanelisusuallylocatedonthewall(inthesurgeryroom)oppositetheoperatingareasterileeld.Teinstallationshouldallowortheaccessandadjustmentopressuresettingsbyasurgicalnurse.

    Pipingromthenitrogencontrolpaneltoasurgicalceilingoutletwillprovideaconvenientsourceonitrogenorsurgicaltools.Tiswillpreventhosesrombeinglocatedontheoororbetweenthewalloutletandtheoperatingtable.Excesshosecanbeobstructivetothesurgicalteam.

    MEDICAl-GASSTorAGE

    Aterdecidingthemedical-gasservicestobeprovidedattheity, the engineer should determine thestorage capacity anpipe sizingrequiredandpossible locationsor thesource.codesandreerencesaswellastheadministrativeauthorityha

    jurisdictionshouldbeconsultedoreachmedical-gassystem.Because o the unique characteristics o each medica

    source, the gases aredescribed separately in thissection.anexplanationo thetechniquescurrentlyemployedto exhanestheticgasesisprovided.

    Oxygen (O2) Severalactorsmustbeknownwhenestimthe monthly consumption o oxygen in new or existing hecareacilities:1. ypeomedicalcareprovided.

    2. Numberooxygenoutletsor

    3. Numberopatientbeds.

    4. Futureexpansionoacility.

    5. Inexistingacilities,approximateconsumption.

    wo methods can beusedby the plumbing engineer tomatetheconsumptionooxygen.Temoreaccuratemethodobtainadetailedconsumptionrecordromthehealth-careacorobtainmonthlyoxygenshipmentinvoicesromthesupplinventoryrecordsarenotavailableromthehealth-careacilthesupplier,use consumptionrecords rom acomparablyacility,withgoodjudgment.

    Tesecondmethodistoapplytheollowingruleothumestimatethemonthlysupplyooxygen.Tisestimatingmeshouldbeusedwithgoodjudgment.Alwayscoordinateestimdemandwiththeoxygensupplierduringthedesignprocess1. Innon-acute-careareas,allow500t3(14m3)perbedper

    monthorsupplyandreserveoxygenstorage.

    2. Inacute-careareas,allow1000t3(28m3)perbedpermoorsupplyandreserveoxygenstorage.

    Oxygensupplysourcesaredividedintotwocategories:(1)

    oxygensystemsand(2)cylinder-maniold-supplysystems.Boxygen systems should be considered or health-care ac

    withanestimatedmonthlydemandabove35,000t3(991mequalto70oxygenoutlets.Manioldsystemsareusedinsmgeneralhospitalsorclinics.

    Bulk-oxygen systems Whenselectingandplacingbulk-oxsystems,thereareseveralactorstobeconsidered:Oxygentporttrucksize,truckaccesstobulk-storagetanks,andNFPStandard or Bulk Oxygen Systems at Consumer Sites.Bulk-oxequipment,construction,installation,andlocationmustco

    with NFPA 50 recommendations. I liquid oxygen is spillleaked,anextremereorexplosivehazardcouldoccur.NFPAdesignstandardstominimizereexposuretoandromsurrouingstructures.

    Bulk-storagesystemsconsistocryogenictanksthatstoreloxygenat lowpressures(225psi [1551.3kPa]orless).CryotanksareASMEunred,double-walled,vacuum-insulated,surevessels.Liquidoxygenhasa boilingpoint(nbp)o29(182.9C) and a liquid density o 71.27 lb/t3 (1141.8 kg/

    Whenvaporizedintogas,itproduces900timesitsliquidvolFurthermore,sincethetankischangedlessoten,processstityismaximizedandtheintroductionoatmosphericimpuisreduced.anksystemsareurnishedwithanintegralpresrelie valve vented to the atmosphere should the liquid oxconverttoagas.

    JANUARY/FEBRUARY 2006 PlumbingSystems&Design

  • 8/3/2019 Med Gas Vac System Short

    6/8

    CONTINUING EDUCATION: Medical Gas and vacuum Syste

    Most bulk-oxygen storage systems are urnished with vapor-izers. Vaporizersarebanks o nned-tube heatexchangers thatconverttheliquidtoitsgaseousstate.Tevaporizerscomeinsev-eral stylesincluding atmospheric, powered (orced-air, steam,and electric), waste-heat, and hybridand sizes. Te selec-tion ovaporizers should bebased on demand, intermittent orcontinuous usage, energy costs,and temperature zones. Poorlyventilated sites or undersizedheat exchangers cancause ice toormonvaporizersduringtheconversionprocess.Excessiveiceormations can clog and damage the vaporizer. Also, ice couldallowextremelycoldgasorthecryogenicliquidtoenterthepipedsystem; damage the valves, alarms, and medical components;andeveninjurepatients.Figure1illustratesatypicalbulk-oxygensystemschematic.

    Automaticcontrolsurnishedwiththetanksregulatetheowoliquidthroughthevaporizers.Whenthereisademandoroxygen,thesupplysystemdrawsliquidromthebottomothecryogenicstoragetankthroughthevaporizers.Tegasmovesthroughanal

    line regulator. Tus, a constant supply o oxygen at a regulatedpressureisprovided.Incaseomechanicaldifcultyorthedepletionotheliquid-

    oxygensupply,thereservesupplywillbegintoeedintothedistri-butionsystemautomatically.

    An alarm signal should alert appropriate hospital personnelwhenthe liquid inthe oxygenstorage tank reachesa predeter-minedlevel.Te alarmsignalsshouldindicatelowliquidlevels,reserveinuse,andreservelow.

    Cylinder-manifold supply systems Compressed-oxygensystems are comprised o cylinder maniolds that allow a pri-marysupplysourceooxygencylinderstobeinuseandanequalnumberooxygencylinderstobeconnectedasareservesupply.

    Tecontrolsothecylindermanioldwillautomaticallyshiowotheoxygengasromtheservicesidetothereserve

    whentheservicesideisdepleted.Maniold systems can be located indoors or outdoors. W

    manioldsarelocatedindoors,theengineershouldobservollowing: Location Preerably,themanioldshouldbeinadedicat

    roomonanoutsidewallnearaloadingdockandhaveadquateventilationandserviceconvenience.

    Adjacent areas Tereshouldbenodoors,vents,orotherdirectcommunicationsbetweentheanesthetizinglocatiothestoragelocationandanycombustibleagents.Ilocatinearoradjacenttoanelevatedtemperatureareaisunavoable,theengineershouldspeciysufcientinsulationtop

    ventcylinderoverheating;

    Fire rating Tere-resistanceratingotheroomshouldbleast1h.

    Ventilation Outsideventilationisrequired.

    Security Teroom(orarea)mustbeprovidedwithadoogatethatcanbelockedandlabeled.

    Oxygenmanioldsaresizedtakingintoconsiderationthelowing:1. Tesizeothecylinders,244t3(6909L)H-cylinder(see

    4orasizingchart).

    2. Tehospitalsusageooxygen,int3(L)permonth.

    Figure 1 Typical Bulk Supply System (Schematic)

    PlumbingSystems&Design JANUARY/FEBRUARY 2006 PSDMAGAZ

  • 8/3/2019 Med Gas Vac System Short

    7/8

    table 4 Selection Chart or Oxygen Maniolds

    Hospital Usage Duplex Maniold Size

    Cu. Ft. (103 L) per month Total Cylinders Cylinders per Side

    5,856 (165.8) 6 3

    9,760 (276.4) 10 5

    13,664 (386.9) 14 7

    17,568 (497.5) 18 9

    21,472 (608.0) 22 11

    25,376 (718.6) 26 1329,280 (829.1) 30 15

    33,154 (938.8) 34 17

    Note: Based on use o 244 t3 (6909.35 L) H-cylinders.

    Nitrous oxide(N2O) Tecommonsourceonitrousoxideisacylinder-manioldsystem.High-pressuremanioldsystemscon-sistotwobanksocylinders,primaryandreserve.(Seediscus-sionunderOxygen,above.)

    Systemdemandsornitrousoxidecanbemoredifculttodeter-minethantheyareorothermedicalgases.Tenumberosurger-iesscheduled,thetypesandlengthsosurgery,andtheadmin-isteringtechniques usedbytheanesthesiologistscause extremevariations in theamount o nitrousoxideused. Becauseo thisvariation,considerationsmustbegiventothesizeandselectionothenitrous-oxidemanioldsystem.

    Avoid locating the nitrous-oxide maniold system outdoors inareaswithextremelycoldclimates.Nitrousoxideissuppliedlique-edatitsvaporpressure o745psi(5136.6kPa)at70F(21.1C).At extremely cold temperatures, the cylinder pressure will dropdramatically,reducingthecylinderpressuretoapointwhereitisimpossibletomaintainanadequatelinepressure.Tisisduetoalackoheatorvaporization.

    Fornitrous-oxidemanioldslocatedindoors,thesameprecau-tionspreviouslylistedoroxygensystemsmustbeobserved.

    Teollowingshouldbeconsideredwhenselectingandsizing

    nitrous-oxidemanioldsanddeterminingthenumberocylindersrequired:1. Tesizeothecylinders:489t3(13847L)K-cylinders(see

    able5).

    2. Tenumberoanesthetizinglocationsoroperatingrooms.

    3. Provideo1cylinderperoperatingroomorin-serviceandreservesupplies.

    table 5 Sizing Chart or Nitrous Oxide Cylinder Maniolds

    Number oOperating

    Rooms

    Duplex Maniold Size

    Indoor Outdoor

    Total CylindersCylinders per

    Side Total CylindersCylinders per

    Side

    4 4 2 4 28 8 4 10 5

    10 10 5 12 5

    12 12 6 14 7

    16 16 8 20 10Note: Based on use o 489 t3 (13.85 103 L) K-cylinders.

    Medical compressed air Medical compressed air may besupplied by two types o system: (1) a high-pressure cylinder-manioldsystem;and(2)amedicalair-compressorsystem.

    Temanioldsystemsorcompressedairaresimilarincongu-rationtothoseoroxygenandnitrousoxide(seediscussionunderOxygen, above). Air supplied romcylinders or that hasbeen

    reconstitutedromoxygenU.S.P.andnitrogenN.F.mustcomasaminimum,withGradeDinANSIZE86.I, Commodity Spcation or Air.

    Medical compressed air can be produced on site rom aspheric air using air compressors designed or medical apptions.Terearethreemajortypesoaircompressorinthemaplacetoday: thecentriugal,reciprocating,and rotaryscrewreciprocating and rotary screw are positive-displacementunits,whilethecentriugalcompressorisadynamictypecpressor.Temedicalaircompressorshallbedesignedtopre

    theintroductionocontaminantsorliquidintothepipelinebyotwomethods:ype1aircompressorseliminateoilanywhethecompressor.ype2aircompressorsseparatetheoil-contasectionromthecompressionchamber.Examplesoatype1cpressoraretheliquidring,rotaryscrew,andpermanentlysebearingcompressor.ype2compressorshaveextendedhead

    Apositive-displacementcompressorisnormallyratedinacubiceetperminute(acm).Tisistheamountoairtakenatmosphericconditionsthattheunitwilldeliveratitsdischa

    Withinabroadrange,changesininletairtemperature,presandhumiditydonotchangetheacmratingoeitherthereccatingor therotaryscrewcompressor.Te centriugalcomsorscapacity,however,isaectedslightlybytheinletaircotionsduetothenatureothecompressionprocess.Forexamas the air temperature decreases, the capacity o the dyncompressorwillincrease.Tecapacityo acentriugalcomsorisnormallydenedininletcubiceetperminute(icm).eorttoobtainanapplestoapplescomparisonovariouspressors,manymanuacturersspeciytheircapacityrequireminstandardcubiceetperminute(scm).Tissometimescamuch conusionbecausemany people do not ully undershowtoconvertromacmoricmtoscm.Tedesignenginspeciying scm must dene a typical inlet air condition abuildingsiteandtheirsetostandardconditions(normallypsia[101.4kPa],60F[15.6C],and0%relativehumidity).

    cally,thewarmestnormalconditionisspeciedbecauseatemperaturegoesupscmwillgodown.oconvertromacmtoscm,theollowingequationisus

    Equation 1

    scm =acmPi(Ppi%RH) std

    Pstd(Ppstd%RHstd) iwhere Pi=Initialpressure Ppi=Partialinitialpressureowatervaporin100%humid

    thetemperatureinquestion RH=Relativehumidity Pstd=Pressureunderstandardconditions Ppstd=Partialstandardpressureowatervaporin100%hum

    airatthetemperatureinquestionRHstd=Relativehumidityatstandardconditions std=emperatureatstandardconditions,F(C) i=Inlettemperature,F(C)

    JANUARY/FEBRUARY 2006 PlumbingSystems&Design

  • 8/3/2019 Med Gas Vac System Short

    8/8

    CONTINUING EDUCATION: Medical Gas and vacuum Syste

    Equation 1aTisequationisderivedromthePerectGaslaw,whichis:

    P1V1 =P2V2

    1 2or:

    V2=V1P1 2P2 1

    whereP1=InitialpressureV1=Initialvolume1=Initialtemperature

    P2=FinalpressureV2=Finalvolume2=Finaltemperature

    Forareciprocatingorrotary-screwcompressor,theconversionromacmtoscmissimple.Teinletairconditionsandstandardconditions are inserted into the above ormula and multipliedbytheacmcapacityotheunit.Itmakesnodierencewhatthedesignconditionsareorthatcompressor,asthesedonotgureintotheormula.Inthecaseoadynamiccompressor,theicmairowatthegiveninletconditionsisinsertedinplaceotheacmintheormula.Anotherdesignissuethattheengineershouldbeawareo ishowaltitudeaectstheoutputo thecompressor.At

    altitudes above sea level, all medical-air systems have reducedow.Inthesecases,therequiredsizingwillneedtobeadjustedtocompensate.odothis,multiplythescmrequirementsbythecorrectionactorinable6.

    table 6 Altitude Correction Factors or Medical-Air Systems

    Altitude, t (m)Normal Barometric

    Pressure, in. Hg (mm Hg)

    CorrectionFactor or SCFM

    (L/min)

    Sea level 29.92 (759.97) 1.0 (28.31)

    1,000 (304.8) 28.86 (733.04) 1.01 (28.6)

    2,000 (609.6) 27.82 (706.63) 1.03 (29.16)

    3,000 (914.4) 26.82 (681.23) 1.05 (29.73)

    4,000 (1219.2) 25.84 (656.33) 1.06 (30.01)5,000 (1524) 24.90 (632.46) 1.08 (30.58)

    6,000 (1828.8) 23.98 (609.09) 1.10 (31.14)

    7,000 (2133.6) 23.09 (586.48) 1.12 (31.71)

    8,000 (2438.4) 22.23 (564.64) 1.15 (32.56)

    9,000 (2743.2) 21.39 (543.3) 1.17 (33.13)

    10,000 (3048) 20.58 (522.7) 1.19 (33.69)

    In other words, to correctly size the medical-air system, youwouldapplythecorrectionactorlistedinthechartabovetothepeak-calculatedload(scm)atsealevel.

    Example 2Aacilityislocatedat5000t(1524m)abovesealevelandthesystemdemandis29.4SCFM.akethe29.4scmandmultiplyitby1.08(correctionactorromable5)togettheadjustedscmrequire-mento31.8scmat5000tabovesealevel.Tereore,amedical-airsystemogreatercapacityisneededathigheraltitudes.

    Anotherhandyormulaorcompressed-airsystemsistheol-lowing:toconvertscmtoL/minmultiplyby28.31685.

    Each compressor must becapableomaintaining 100% othemedical-airpeakdemandregardlessothestandbycompressorsoperating status. Tebasiccompressor package consistsolterintakes, duplex compressors, ater-coolers, receiving tanks, air

    dryers,in-linelters,regulators,dew-pointmonitors,andvaTecompressorcomponentsareconnectedbypipingthataequipmentisolation, provides pressure relie,and removesdensateromreceivers.Medical-aircompressorsmustdrawsideairromabovetheroolevel,remoteromanydoors,windandexhaustorventopenings.Wheretheoutsideatmosphericpolluted,speciallterscanbeattachedtothecompressorsinto remove carbon monoxide and other contaminants. ReNFPA99orproperlocationomedical-airintakes.MedicalpressedairmustcomplywithNFPA99and/orCanadianStan

    Associations(CSAs)denitionoair-qualitystandards.Wheremorethantwounitsareprovidedortheacility,an

    unitsmustbecapableosupplyingthepeakcalculateddemProvide automatic alternators (duty-cycling controls) to enevenwearinnormalusage.Alternatorcontrolsincorporateaptivemeansoautomaticallyactivatingtheadditionalunit(orushouldthein-servicepumpailtomaintaintheminimumreqpressure.

    Medical compressed air produced by compressors madenedasoutsideatmospheretowhichnocontaminants(iormoparticulatematter,odors,oilvapors,orothergases)beenaddedbythecompressorsystem.Noteverycompresssuitableoruseasasourceormedicalcompressedairinhecareacilities.Onlythosecompressorunitsspecicallydesigandmanuacturedormedicalpurposesshouldbeconsiderareliablesourceooil-ree,moisture-ree,andlow-tempercompressedair.Acceptablecompressortypesincludeoil-reeless,and liquid-ringcompressors.Separationo theoil-coningsectionromthecompressionchamberbyatleasttwoserequiredbythecompressormanuacturers.

    Aircompressedormedical-breathingpurposesaretobeorthispurposeonlyandshouldnotbeusedorotherapptionsorcross-connectedwithothercompressedairsystems

    table 7 Minimum Pipe Sizes or Medical Air-Compressor Intake Risers

    Pipe size, in.

    (mm)

    Flow rate, cm

    (L/min)2.5 (63.5) 50 (1416)

    3 (76.2) 70 (1985)

    4 (101.6) 210 (5950)

    5 (127.0) 400 (11330)

    able7providestheminimumpipesizesormedicalair-cpressorintakerisers.Consultwiththecompressormanuacton intake recommendations and allowable riction loss ointakeriserbeorenalizingthepipesizeequipmentselectio

    0 Pl bi S t & D i JANUARY/FEBRUARY 2006 PSDMAGAZ