McQuay Air Cooled Mini ChillerModels: MAC065C MAC070C MAC080C MAC100C MAC120C MAC150C
Technique Manual
Engineered for flexibility and performance.TM
MiniChiller-2007-001(60Hz)
1
“McQuay”isaregisteredtrademarkofMcQuayInternational.Allrightsreservedthroughouttheworld.
©2007McQuayInternational
“BulletinillustrationscoverthegeneralappearanceofMcQuayInternationalproductsatthetimeofpublicationandwereservetherighttomakechangesindesignandconstructionatanytimewithoutnotice.”
Note:Installation and maintenance are to be performed only by qualified personnel who are familiarwithlocalcodesandregulations,andexperiencedwiththistypeofequipment.
Caution: Sharpedgesandcoilsurfacesareapotentialinjuryhazard.Avoidcontactwiththem.
Warning:Movingmachineryandelectricalpowerhazard.Maycauseseverepersonalinjuryordeath.Disconnectandlockoffpowerbeforeservicingequipment.
Contents
Nomenclature....................................................................................................................... 2
Features................................................................................................................................ 3
Specifications ...................................................................................................................... 5
Sound data ........................................................................................................................... 8
Performance Data ................................................................................................................ 9
Outlines and Dimensions ..................................................................................................11
Accessory Hydraulic Kit ................................................................................................... 13
Electric Data ....................................................................................................................... 14
Wiring Diagram .................................................................................................................. 15
Installation .......................................................................................................................... 19
Exposed View .................................................................................................................... 27
2
Nomenclature
M AC 080 C R – P AB - E
ExportU:SpecialForLatinMarketing
MainComponents
PowerSupply:P-208~230V/3Ph/60HzK-220V/1Ph/60Hz
HeatPumpBlank:CoolingOnly
DesignSeries
NomianlCoolingCapacity
AirCooledChiller
McQuay
3
Features
SuperiorPerformanceExtensive researchworkcoupledwithworld leadingmanufacturing technologyhas resulted thenewdesignwithsuperb performance and high efficiency.Stringentqualitycontrolandcomponentselectionensureperformanceandreliability.Majorcomponentsarerigorouslytested and qualified prior to usage in the machine.Everymachinedesignhaspassedmanyhoursofrigoroustestingtoensurethemachinereliability,durabilityandquality.Scroll compressor brings much higher energy efficiency. High efficiency heat exchanger ensures strenuous exertion ofequipmentcapacity.Waterpumpparticularlydesignedforairconditioningengineeringisoperatingsteadilywithminimumvibrationandnoise.
For MAC080C/CR To MAC150C/CRTheseunitsaredesignedwithdoubleindependentrefrigeratingsystem,greaterenergysavingisachievedbyonlyonecompressorondutyunderpartloadcondition.
Robust Construction With Slim OutlookDetailedengineeringworkcoupledwithextensivemarketresearchhasresultedthenewMACmodelcomeinnewmono-blockdesigntoyieldacompactandrobuststructurewhilemaintainingtheslimoutlook.ThesmallercapacitymodelsMAC030-070C(R)arehavingsidedischargedesign,whilethelargercapacitymodelsMAC080-150C(R)arehavingtopdischargedesign.
Simple To OperateThemachineiscompletewithintelligentmicroprocessorcontrollerandtemperaturesensortoautomaticallycontrolthe operation to its optimum condition, making it very simple to operate. All temperature settings are finished before shipment.TheonlythingforusertodoistostarttheunitbypressingtheON/OFFbuttonafterensuringunitproperfunction,theneveryoperationcanbeautomaticallyperformedbytheunititself.Eitherwireless remotecontrollerorwiredremotecontroller is ready forchoosing tomeetsatisfactory indoorunitcontrol,bothcompatiblewiththeunit.
Friendly InstallationThemachinehasbeendesignedwithfriendlyinstallationinmindsothatnorefrigerationchargingorcopperpipebrazingisrequiredonsite.Threaded fitting is provided for easy water piping connection on site.Waterinletandoutletareprovidedonbothsidesofthemachinesuchthatpipingcanbeconnectedoneithersideofthemachine.RustresistantPP-Rcompositewaterpipewithgoodinsulationpropertyandhighdurabilityisstandardpartsinthemachine.Stainless steel taper threaded fittings target convenient disassembly or assembly.For MAC080C/CR To MAC150C/CR, expansion chamber, water pump and water flow switch are already equipped inthiscompactpackagedunitwithtopairdischarge,inaddition,McQuayprovideaccessoryhydraulickitwithwaterstorage tank, auto water fill valve, auto air vent valve, auto pressure relief valve and strainer integrated in, aiming at ensuring high efficiency and safe operation. For MAC030C/CR To MAC070C/CR, expansion chamber is required in theaccessoryhydraulickitinsteadofbeingincorporatedinunit.
Safety ControlProtectiondevicessuchasdualpressureprotectionandoverloadprotectionetc.isprovidedtoensureunitoperatingwithin safety condition range. The microprocessor-based controller automatically directs system on or off byprocessingthewatertemperaturefeedback.Ifthewatertemperaturefallstounacceptablelowpoint,thecontrollerautomaticallyshutoffthesystemtopreventhydraulicsysteminternalfreezeforunitsafetyoperation.Meanwhile,
�
themicroprocessor-basedcontrollerautomaticallymonitorseverycomponentoperatingstatusandmalfunction,andfeedbackittoindoorcontrollertogreatlyeasetheworkofstatusmonitorandtroubleshooting.
All WeatherThecabinetismadeofelectrogalvanizedmildsteelsheet,coatedwithbakedpolyesterpowertoensuretheunitsextradurabilityinallclimatesagainstsun,rain,windcorrosion.Spacesaving (small footprint) designof themachineeliminates large installationarea requirement, noneed forequipmentroom.Themachineuseshighqualitypartstoensuredurabilityinvariousclimateconditions.
Simple To MaintainThesimpledesignofthemachineallowsformaximumserviceability.Allcomponentsarewithreachofthemaintenancepersonneluponopenupoftheservicingpanel.Ifemergencyshutoffoccurs,themicroprocessor-basedcontrollerwillindicatesthefaultcausetoquickenandeasetroubleshooting.
Three Color Appearance Available (For MAC030C/CR To MAC070C/CR)Therearethreeoptionalcolors-blue,greenandredavailabletobeeasilychosentomeetcustomers’requirements,sotheunitcanbeharmonicallyblendintobuildingoveralllook.
5
SpecificationsGeneral DataMODEL MAC065C MAC070C MAC080C MAC100C MAC120C MAC150C
NOMINAL COOLING CAPACITY Btu/h 57000 60000 76800 92200 112700 130000
SENSIBLE COOLING CAPACITY kW 16.7 17.5 22.5 27.0 33.0 38.0
NOMINAL TOTAL COOLING INPUT POWER kW 6.85 7.90 9.30 10.76 13.27 1�.98
POWER SOURCE V/Ph/Hz 208~230/1/60 208~230/3/60
REFRIGERANT TYPE R22
CASING
MATERIAL ELECTRO-GALVANIZEDMILDSTEEL
FINISH EPOXYPOLYSTERPOWER
THICKNESS mm/in 1.20/0.0�7
UNIT DIMENSION
HEIGHT mm/in 1700/67 1700/67 1260/50 1260/50 1260/50 1260/50
WIDTH mm/in 1212/�8 1212/�8 1150/�5 1150/�5 1150/�5 1150/�5
DEPTH mm/in 502/20 502/20 1800/71 1800/71 1800/71 1800/71
ACCESSORY HYDRAULIC KIT DIMENSION
HEIGHT mm/in 500/20
WIDTH mm/in 816/32
DEPTH mm/in �00/16
PACKING DIMENSION
HEIGHT mm/in 1930/76 1930/76 1�53/57 1�53/57 1�53/57 1�53/57
WIDTH mm/in 13�0/53 13�0/53 1732/68 1732/68 2032/80 2032/80
DEPTH mm/in 650/26 650/26 1032/�1 1032/�1 1032/�1 1282/50
NET WEIGHT kg/lb 220/�85 235/518 3�0/750 350/772 �70/1036 550/1213
GROSS WEIGHT kg/lb 270/595 285/628 �10/90� �20/926 580/1279 650/1�33
NOTES:1) ALLSPECIFICATIONSARESUBJECTEDTOCHANGEBYTHEMANUFACTURERWITHOUTPRIOR
NOTICE.2) ALLUNITSAREBEINGTESTEDANDCOMPLYTOISO5151.3) NOMINALCOOLINGCAPACITYAREBASEDONTHECONDITIONSBELOW:COOLING:27°CDB/19°C
WBINDOORAND35°CDB/24°CWBOUTDOOR.
6
Components DataMODEL MAC065C MAC070C MAC080C MAC100C MAC120C MAC150C
EVAPORATOR
TYPE BRAZEDPLATEHEATEXCHANGE
PLATE MATERIAL STAINLESSSTEEL
MODEL NAME B3-052/�2 V25TH-38 20*20/ZL50V-��
B25-2�*2�/ZL50V-52
CB52-60/ZL50V-6�
CB52-72/ZL50V-76
NOMINAL WATER FLOW L/s(USGPM) 0.81/12.8� 0.92/1�.58 1.08/17.12 1.31/20.77 1.67/26.�7 2.00/31.70
WATER LINE
PUMP TYPE HORIZONTALMULTISTAGEENDSUCTION/PROPELLER/DIRECT
POWER SUPPLY V/Ph/Hz 208~230/1/60 208~230/3/60
RATED POWER INPUT KW 1.63 1.�0 1.53 1.53 1.85 1.85
RATED RUNNING CURRENT A 8.� �.9 3.5 3.5 7.8 7.8
INSTALLATION PIPE CONNECTION mm/in 3.175/Rc11/�
HEAD m 28 26 35 32 31 28
WATER PRESSURE DROP kPa(psi) 106/15 110/16 10�/16 110/16 107/16 103/15
EXPANSION TANK
MATERIAL STEEL
CAPACITY/VOLUME L 8
CONDENSER COIL
TYPE SEAMLESSCOPPERTUBE+CROSSALUMINIUMFIN
TUBE
MATERIAL COPPER
TYPE INNERGROOVE
WALL THICKNESS mm/in 0.30/0.012
OUTER DIAMETER mm/in 9.52/0.37
TUBE HEIGHT TH �1
FIN
MATERIAL ALUMINUM
THICKNESS mm/in 0.11/0.00�33
ROWS 2
FIN PER INCH 1�
TOTAL FACE AREA m2(ft2) 1.7�/18.7 1.7�/18.7 2.7�/29.5 2.7�/29.5 3.59/38.6 3.59/38.6
CONDENSER FAN
TYPE/DRIVE AXIALBIGVANEANDLOWNOISEBLOWER/DIRECT
QUANTITY 1 1 2 2 2 2
BLADE MATERIAL GALVANIZEDSTEEL
BLADE DIAMETER mm/in 710/28 710/28 600/2� 600/2� 660/26 660/26
POWER SUPPLY V/Ph/Hz 208~230/1/60 208~230/3/60
RATED INPUT POWER W 350 350 260*2 260*2 ��5*2 7�0*2
RATED RUNNING CURRENT A 1.6 1.5 0.9*2 0.9*2 1.1*2 1.5*2
MOTOR POLES 8
AIR VOLUME CMH/CFM 8000/�710 8000/�710 6500*2/3825*2
6500*2/3825*2
8500*2/5000*2
11000*2/6�75*2
7
MODEL MAC065C MAC070C MAC080C MAC100C MAC120C MAC150C
COMPRESSOR
TYPE SCROLL
QUANTITY 1 1 2 2 2 2
NOS OF CIRCUITS 1 1 2 2 2 2
POWER SUPPLY V/Ph/Hz 208~230/1/60 208~230/3/60
RATED INPUT POWER W 6.0� 6.3� 3.62 �.36*2 5.2�*2 5.80*2
RATED RUNNING CURRENT A 28.9 18.6 13.0*2 1�.5*2 17.5*2 18.5*2
MAXIMUM STARTING CURRENT A 36.0 25.2 20.0*2 25.0*2 26.0*2 25.2*2
PROTECTION DEVICES H/LPRESSURESWITCH/THERMALANDCURRENTOVERLOADPROTECTOR
STAGE OF CAPCITY CONTROL 0-100 0-100 0-50-100 0-50-100 0-50-100 0-50-100
INSULATION GRADE E
LOCKED ROTOR AMP. A 156 16� 91 128 156 16�
REFRIGERANT
TYPE R22
CONTROL CAPILLARY
REFRIGERANT CHARGE kg/lb 3.8/8.� �.3/9.5 3.5*2/7.7*2 �.0*2/8.8*2 5.8*2/12.8*2 5.7*2/12.6*2
NOTES:1) ALLSPECIFICATIONSARESUBJECTEDTOCHANGEBYTHEMANUFACTURERWITHOUTPRIOR
NOTICE.2) ALLUNITSAREBEINGTESTEDANDCOMPLYTOISO5151.3) NOMINALCOOLINGCAPACITYAREBASEDONTHECONDITIONSBELOW:COOLING:27°CDB/19°C
WBINDOORAND35°CDB/24°CWBOUTDOOR.
Components Data
8
Sound data
NOTES:1) ALLSPECIFICATIONSARESUBJECTEDTOCHANGEBYTHEMANUFACTURERWITHOUTPRIOR
NOTICE.2) SOUNDPRESSURELEVELAREACCORDINGTOMICROPHONEPOSITIONOFTHEMEASUREMENT
POINTIS1mINFRONTAND1mBELOWTHEUNIT.
MODEL1/1 Octave Sound Pressure Level(dB,ref 20uPa)
dB(A)63HZ 125HZ 250HZ 500HZ 1000HZ 2000HZ �000HZ 8000HZ
MAC065C 28.8 39.0 �8.0 51.7 5�.9 51.� �6.6 �1.� 6�.0
MAC070C 39.2 �2.9 �9.8 53.6 53.8 �8.3 �5.1 �2.5 6�.0
MAC080C 27.8 �0.2 �7.6 50.8 52.6 51.7 �6.8 39.5 62.8
MAC100C 35.� �1.5 �8.0 51.7 5�.3 51.0 �6.3 �0.� 63.8
MAC120C 32.2 �3.8 ��.3 53.1 5�.8 52.8 �7.3 �1.� 6�.6
MAC150C 35.0 ��.8 �6.� 5�.3 58.5 53.2 �8.1 �3.1 66.9
9
Performance DataCooling Only Unit Performance Chart
Note:Thechartsaboveshowtheunitperformancechangingcharacteristicinrelationshipwithvariableambienttemperatureandsupplywatertemperature.Pleasenoticethattheremayexistssomelittledifferencebetweentheperformanceofactualmanufacturedunitandthatobtainedusingthesecharts.
MAC Cooling Performance Chart
56789
10
0.80
0.85
0.90
0.95
1.00
1.05
1.10
1.15
1.20
1.25
Ambient Temperature ( )
Per
form
ance
Cor
rect
ion
Fac
tor
MAC Cooling Power Input Chart
5
67
8
9
10℃
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
2032 445382
2032 445382
Ambient Temperature ( )
Pow
er In
put C
orre
ctio
n F
acto
10
Correction Factors With Glycol Use
GLYCOL% COOLING CAPACITY WATER FLOW PRESSURE DROP
10 0.99 1.015 1.06
20 0.98 1.0� 1.12
30 0.97 1.08 1.18
�0 0.965 1.135 1.2�
NOTE:ALLTHECORRECTIONFACTORSWITHGLYCOLUSEAREUNDER7℃LEAVINGWATERTEMPERATURE.
11
Outlines and DimensionsModel: MAC065C, 070C
MAC065C,070C
A B C D E
1212 502 1700 1135 1162
F G H I J
132 25� 235 80 60�.5
4-10X20
2-Rc1
UNIT:mm
12
Model: MAC080C, 100C, 120C, 150C
A
27 G
Cable Port(OUT)
Chilled Water Out
Cable Port (IN)
Rc 1 1/4Chilled Water In
Rc 1 1/4
253.
512
8
CD
HP Gauge (SYS2)
LP Gauge (SYS2)
FB
E
100
Model MAC080C MAC100C MAC120C MAC150C
A 1500.0 1500.0 1800.0 1800.0
B 900.0 900.0 1150.0 1150.0
C 1260.0 1260.0 1260.0 1260.0
D 1190.0 1190.0 1190.0 1190.0
E 297.5 297.5 3�7.5 3�7.5
F (Mounting hole) 307.5 307.5 307.5 307.5
G (Mounting hole) 1��6.0 1��6.0 15�6.0 15�6.0
UNIT:mm
13
Accessory Hydraulic Kit
Water Drainage Port DN25
Chilled Water Out R1
Dirt Drainage Port R1/2
4-10x20
Chilled Water In R1
UNIT:mm
1�
Electric DataMODEL MAC065C MAC070C MAC080C MAC100C MAC120C MAC150C
NOMINAL TOTAL INPUT POWER kW 6.85 7.90 9.30 10.76 13.27 1�.98
POWER SOURCE V/Ph/Hz 208~230/1/60 208~230/3/60
POW
ER S
OU
RC
E W
IRE
MAIN WIRE (R/S/T)
SECTION AREA mm2 � � 6 6 10 10
QTY 3 3 3 3 3 3
NETURAL WIRE
SECTION AREA mm2 � � � � � �
QTY 1 1 1 1 1 1
EARTH WIRESECTION AREA mm2 1 1 1 1 10 10
QTY 1 1 1 1 1 1
CONTROL WIRE SECTION AREA mm2 1 1 1 1 1 1
CO
MPR
ESSO
R
INSULATION GRADE E
POWER SOURCE V/Ph/Hz 208~230/1/60 208~230/3/60
RATED INPUT POWER kW 6.0� 6.3� 3.62*2 �.36*2 5.2�*2 5.80*2
RATED RUNNING CURRENT A 28.9 18.6 13.0*2 1�.5*2 17.5*2 18.6*2
LOCKED ROTOR AMP. A 128 16� 91 128 128 16�
WAT
ER P
UM
P
INSULATION GRADE F
IP 5�
POWER SOURCE V/Ph/Hz 208~230/1/60 208~230/3/60
RATED INPUT POWER kW 1.63 1.�0 1.53 1.53 1.85 1.85
RATED RUNNING CURRENT A 8.� �.9 3.5 3.5 7.8 7.8
MO
TOR
INSULATION GRADE F
IP ��
POWER SOURCE V/Ph/Hz 208~230/1/60 208~230/3/60
RATED INPUT POWER W 200 350 260*2 260*2 ��5*2 7�0*2
RATED RUNNING CURRENT A 1.6 1.5 0.9*2 0.9*2 1.1*2 1.5*2
15
Wiring DiagramEnsurethattheratedvoltageoftheunitcorrespondstothatofthenameplatebeforegeneralprecautions.Provideapoweroutlettobeusedexclusivelyforeachunit.Apowersupplydisconnectsandacircuitbreakerforover-currentprotectionshouldbeprovidedintheexclusiveline.Themodularair-cooledchillersmustbewellgrounded.Itabsolutelycannotbeconnectedwithgas-pipe,waterpipeandtelephoneline.
MAC065C
16
MAC070C
MAC080C
17
MAC100C
MAC120C
18
MAC150C
19
InstallationInstallation NoticeThis equipment must be installed by your dealer or authorized McQuay qualified personnel, and the installation must satisfyallthefollowingrequirements.
LocationIn order to achieve maximum capacity, the location selection should fulfill the following requirements: 1) The location must be well ventilated, so that air can be drawn in and discharge out efficiently.
2) Installtheunitinsuchawaythatthehotairdischargecannotbedrawninagainbyitselforotherunits.3) Ensure that there is no obstruction to air flow into or out of the unit. Remove obstacles which blocking intake or
dischargeairifexist.
Lifting Hook
Lifting Cable
Backing Angle
AirIntake
AirDischarge
AirI
ntak
e
AirDischarge
AirIntake
20
�) Ifgoodventilationcannotbeguaranteedwhenunitbeinginstalledindoors,itisadvisabletoinducedischargeairfromairoutlettooutdoorsbyinstallingductwhichisasshortaspossible.
Obstacles Blocking Servicing Access
Obstacles Blocking Air Intake
5) Supportunitbaseuptocreateaspaceabovefoundationforensuringfreewaterdrainage,andthestablefoundationwith level surface must be sufficiently durable against the unit weight.
Drain Ditch
Unit Supporter
Unit
21
6) Thelocationmustnotbesusceptibletodustoroiltoavoidcondensercoilbeingchokedbythecontaminant.Asthe general safety precaution, it is advised that no flammable danger gas should be located near to the unit.
7) It is advised to have sufficient clearance around the unit for proper condenser air flow and to facilitate access for maintenance.( see clearance shown in figure below)
Delivery and LiftingWhentransportingtheunit,itisadvisabletouseforkliftorcranetodothiswork.Onlythewoodenskidbaseisallowedtobeservedastheweight-supporter.
22
Lifting Hook
Lifting Cable
Backing Angle
Whenhoisting,pleasekeeptheunitstableandwithoutslope,meanwhile,besuretoavoidliftingropescontactwithsideheatexchanger,panelandunit’stoppart.
Afterdecidingthemountinglocation,removetheskidbasebyunfasteningthebolts.
MountingWhenmounting,pleaseusefoundationboltsorexpansionboltstofastentheunitwithfoundationsupportinglegs.When installing indoors, it is advisable to pad the unit bottom against foundation by using vibration absorptionrubber.
Chilled Water PipingChilledwaterpipingmustbeinsulatedandwaterprooftoavoidperformancelossandmoisturecondensingonit.Toguaranteethechilledwaterquality,thewaterstrainershippedwithunitmustbeinstalledonthechilledwaterinpipe.BothchilledwaterinletandoutletportareR1-1/�externaltaperthreadconnections.When performing water pipe connection, use gripping pliers to fix the unit connections to avoid the reserved connectionsonunitbeingdirectlysufferedfromrevolvingtorquewhenfastening.The accessory water pipe components shipped with unit include water pump and water flow switch. Please install themonpipeinaccordancewiththechilledwatersysteminstallationschematicdiagram.Airventvalveshouldbeinstalledathighestpointsonchilledwaterpipingsystem,seedetailedinformationin“chilledwater system installationschematicdiagram”.After completingchilledwaterpiping, carryout leakdetectionand0.4MPa pressure test to ensure having no fault, then fully fill water in system, open air vent valve, purge all the air trappedinthepipingsystem,afterthatshutofftheairventvalve.Waterdrainagevalveshouldbeinstalledatlowestpointsonchilledwaterpipingsystem.In order to achieve the unit long-life operation, it is recommended to give first priority to new type plastic water pipe suchasPP-R,PVC,neverusegalvanizedsteelpipewhenchoosingthematerialofwaterpipe.
Theaccessorystrainershippedwithunitmustbeinstalledonwaterinpipe,otherwisefailureoftheunitmaybecaused.Theunitshouldbeconnectedwiththewatersupplysystemthroughtheautomaticfeederthatistheunitaccessory.Thepressureofthewatersupplysystemmustbemorethan1.5barandlessthan6bar.
23
Thermometer
Unit
Accessory Hydraulic Kit (optional)
Y Strainer
Flex
ible
Joi
nt
Shut
off
Valv
e
Flex
ible
Joi
nt
Shut
off
Valv
e
Shut
off
Valv
e
Shut
off
Valv
e
Hea
ter
Shut
off
Valv
e
Wat
er G
auge
T
Dirt Drainage Valve
FCU
Check Valve
T
Water Fill Valve
Globe Valve
Flexible Joint
T
Two Way Valve
FCU
FCU
FCU
Two Way Valve
Two Way Valve
Air Vent ValveTwo Way Valve
Hydraulic system installation schematic diagramWheninstallingtheMACunit,usingclosedwatersystemisstronglyrecommendedbyMcQuay,andpleaserefertotheschematicdiagramabove.Inordertoensureenergysavingandsystemsafeoperation,McQuayhasprovidedhydraulicsystemaccessories,includinginsulatedstainlesssteelwaterstoragetank,safetyvalve,dirtdrainagevalve,autoairventvalve,Y-shapedstrainer and automatic water fill valve etc.Auxiliaryheaterinthediagramaboveisavailableforoption,pleasechooseeithertypeofauxiliaryelectricheaterandauxiliarygasheater.Ifyouhavethedemand,pleasecontactwithyourdealerordirectlywithMcQuayCompany,andinstallitaccordingtothediagramabove;ifyouhavenotheneedofthistype,thecomponentsindottedlineboxcanbeomitted.
Ifthechillerisoperatedwithveryoily,saltyoracidicwater,thesesubstancesmayleadtocapacity drop. Be sure to use clean water when filling in the water circuit to avoid heavy corrosionandchokingofthesystem.
Don tuse thewaterpumpequipped inunit tocleanpiping. Ifusing thepump toclean isrequired, you can fill clean water in system at water in side, meanwhile make the pump running,pleaseconduct30-minutepumpoperation,thencleanthestrainer.
2�
Power ConnectionLawsandregulationsconcerningelectricalwiringworkvarybycountry.Therefore,workshouldbasicallybeperformedaccordingtotheregulationsofeachcountry.Beforepowerconnection,makesurethatyourlocalpowersupplytypeaccordswiththeunitnameplate.Pleaseusesuitablesizededicatedwiretopowerthisunit.Theconnectionsmustbemadesecuredwithouttensiontheterminals.Allelectricworkmustbeperformedbylicensedtechnicianaccordingtolocalregulationsandtheinstructionsgiveninthiscatalogue.Theunitmustbeproperlyearthconnected.Donotconnecttheearthwiretogaspipe,citywaterpipeortelephonewire,improperearthconnectionmaycauseelectricalshock.Pleasemountelectricleakprotectionbreakertoavoidelectricshock.Pleaseensurecorrectphasesequence,makeL1,L2,L3correspondwithR,S,Tonterminalblockrespectively,otherwisethesystemcannotbestartedandthecontrollerhasnodisplay.Every wire should be firmly connected without tension to the cables and terminals.Allcablesshouldnotcontactwithrefrigeratingpipingandmoveablecomponentssuchascompressorandfanmotoretc.
Servicing and Maintenance
ServicingService and maintenance are to be performed only by qualified personnel who are well trained with refrigeration engineering.Beforerestarttheunit,doathoroughcheckandanalysisoftheunitsafetycontrolcomponents.Theoptimumdesignoftherefrigeratingsystemeliminatesthepossibilityofproblemsbeingoccurredduringnormaloperation.Thereisnoneedtoconductanymaintenancetorefrigerantpipingiftheunitisundernormalrunning.McQuaydesignershavegivenfullconsiderationtomakeservicingconvenientduringunitdevelopment.Afteropeningservicepanel,bothservicingandmaintenancecanbeeasilycarriedout.Undernormalenvironment,theonlyworkneededischeckingthereturnairwayandcleaningtheheatexchangesurfaceregularlyatmonthorseasonintervaldecidedonoperatingcondition.If the surrounding is very dirty or oily, for maintaining superior performance and sufficient capacity, please ask specializedpersonneltodoregularcleaningofheatexchanger.
MaintenanceForkeepingconsistentperformanceanddurabilitywithsafe,effectiveandlong-lifeoperation,alwaysconductproperandregularmaintenancetotheunit.Forlongperiodofoperationtime,theheatexchangerwillbecomedirtyimpairingitseffectivenessandreducingtheperformanceoftheairconditioner.Consultyourlocaldealeronthecleaningoftheheatexchanger.Nomainmaintenanceorservicingneededfortheinternalwatercircuitexceptthewaterpumpfailure.Itisadvisedthatregularcheckonthestrainershouldbeconductedandreplacethewaterstrainerifthestrainerisdirtyorclogged.Alwayscheckthewaterlevelinthesystem,forthetargetofprotectingthemovingcomponentsinthehydraulickitfromoverheating,excessivewearingandwaterfreeze.Allthechilledwaterinthehydraulicsystemmustbedrainedoutcompletelyduringunitshutdowninwinter,toavoidwaterpipingdamageduetofreeze.
Atemergency(ifyousmellsomethingburning),stopoperationandturnthepowersourceswitchoff,askforyourdealer
25
Common Failure
Whenanymalfunctionisoccurred,immediatelyturntheswitchoffandshutdownoperation,thencontactwithyourdealerforresolution.Forsomefrequentlyoccurredfailure,youcanconductsomehandlingreferringtothesimpletroubleshootingtipsgivenbelow.
SYMPTOMS POSSIBLE CAUSES REMEDIAL ACTION
1.Compressor doesnot start
·Nopowersupply. ·Checkpowersupply.
·Fusesblownorautomaticcircuitbreakdownopen.
·Lookforshortcircuitorgroundedwiresinmotorwindings.Replacefusesandresetcircuitbreakerswhenthefaulthasbeencorrected.Checktightnessandsoundnessofallelectricalconnections.
·Unitisstoppedbecauseasafetyhastripped. ·Determine the typeofsafetyshutdownandcorrect thedefaultbeforetheunitisrestarted.
·Loosewires. ·Checkwireconnectionsandtightenterminalscrews.
·Compressorfaulty. ·Contactlocaldealer.
2.Fan does not work
·Nopowersupply. ·Checkpowersupply.
·Fanmotorfaulty. ·Contactlocaldealer.
3.Air conditioner does work, but insufficient cooling.
·Thermostatsettingtoohigh. ·Resetthermostat
·Condensercoildirty. ·Contactlocaldealer.
·Obstacleblockingairinletoroutletoftheunit. ·Removetheobstacle.
· Insufficient refrigerant in the system. ·Contactlocaldealer.
· Improper water flow rate. ·Contactlocaldealer.
·Waterinthesystemiscontaminated. ·Contactlocaldealer.
Trouble Shooting
Whenothercodeisdisplayed,pleaseconsultspecializedpersonnel.Seedetailedindoorcontrolleroperationincorrespondinginstructionmanual.
Error Code Possible Causes SolutionsE1 Returnwatersensorcontactloose/short Contactwiththedealer,checkandrewireitE2 Supplywatersensorcontactloose/short Contactwiththedealer,checkandrewireitE3 Returnairsensorcontactloose/short Contactwiththedealer,checkandrewireitE� System1defrostingsensorcontactloose/short Contactwiththedealer,checkandrewireitE7 Insufficient water flow Adjust water flow rate, check and clean strainerE8 Waterpumpoverload ContactwiththedealerEA Compressor1overload ContactwiththedealerEC Compressor1highpressurecutout ContactwiththedealerED Compressor1lowpressurecutout ContactwiththedealerEE RAMaccessfailure ContactwiththedealerEF Toolowsupplywatertemperaturewhencooling Contactwiththedealer
26
Notice
InspectionAssoonastheunitisreceived,itshouldbeinspectedforanydamagethatmayhaveoccurredintransit.Ifdamageisevident,itshouldbenotedonthecarrier’sfreightbill.Aseparaterequestforinspectionbythecarrier’sagentshouldbemadeinwritingatonce.Concealed damage must be reported within 15 days of receipt of shipment. Check shipment against the bill oflading to verify that all items were delivered. Any shortages should be noted on the delivery receipt, and a claim filed immediately.
Instruction for use1) Suitableroomtemperaturesetting
Itisadvisabletocomforteveryoneintheconditionedspace,sothetemperaturesettingshouldn’tbetoohighortoolow.Itisrecommendedthatthesettingshouldbewithintherangeoffrom26℃to28℃whencooling,from18℃to23℃whenheating.
2) WinterantifreezeofchilledwatercirculatinginthehydraulicsystemAllthechilledwater inthehydraulicsystemmustbedrainedoutcompletelyduringunitshutdowninwinter,toavoidwaterpipingdamageduetofreeze.
3) Don’tblockairintakeandairdischargewayThese obstacles may cause performance deficiency or shutdown of the air conditioner.
�) AntirustPleasetakeantirustmeasuresandregularlyremoverustwhenusingwaterpipevulnerabletorust toconnectchilledwatersystem
5) Conducting regular chilled water maintenance, this contributes to ensure safe, high efficiency and consistent operation.
6) Only clean water is suitable to fill in system, in addition, install the high efficiency water strainer, which is provided byMcQuay,ontheupstreampipetounitwaterinlet
7) SpecialattentiontowinterantifreezeDuringlongperiodshutdowninwinter,thewaterinsystemmustbecompletelydrainedout.Pleaserefertothediagrambelowandthelabelsstuckonunit.Addproperquantityantifreezersuchasethyleneglycolintothehydraulicsystemiftheunitisnotondutyforshorttime.
27
Exposed View
No. Parts No. Parts
1 Airoutletguard 15 Fan
2 Orifice plate 16 Fanmotor
3 Frontplatesupport 17 Fanmotorsupport
4 Left/rightheatexchangerguard 18 Heatexchangerguard(rear)
5 Leftheatexchangercomponents 19 Left/rightpost
6 Partitioncomponents 20 Rightheatexchangercomponents
7 Left/rightsideplatecomponents 21 Vapor-liquidseparator
8 Frontplatecomponents 22 Plateheatexchanger
9 Controlboxsupport 23 Compressor
10 Controlboxcomponents 24 Pipingfrompumptoheatexchanger
11 Returnpipecomponents 25 Liquidtank
12 Inflow pipe components 26 Pump
13 Leftdoorcomponents 27 Chassiscomponents
14 Rightdoorcomponents
©2007McQuayInternational+1(800)�32-13�2www.mcquay.com
Whileutmostcareistakeninensuringthatalldetailsinthepublicationarecorrectatthetimeofgoingtopress,weareconstantlystrivingforimprovementandthereforereservetherighttoaltermodelspecifications and equipment without notice.Details of specifications and equipment are also subject to change to suit local conditions and requirements andnotallmodelsareavailableineverymarket.