Modbus Register Mapping

Controller

PCC 1301PowerCommand 1.1PowerCommand 1.2PowerCommand 2.2PowerCommand 2.3PowerCommand 3.3

English 2−2010 A029X159 (Issue 3)

Page 2: Mapa de Registros de Pcc
Page 3: Mapa de Registros de Pcc

i

Table of ContentsSECTION TITLE PAGE

SAFETY PRECAUTIONS II. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1. PCC 1301/POWERCOMMAND 1.X MODBUS REGISTER MAP 1. . . . . . . . . . . . . . . . . . . . .

2. POWERCOMMAND 2.X/3.X MODBUS REGISTER MAP 9. . . . . . . . . . . . . . . . . . . . . . . . . . . .

3. POWERCOMMAND 2.X/3.X MODBUS FAULT STATUS BITMAPS 297. . . . . . . . . . . . . . . . . . .

4. NFPA 110 & EXTENDED ANNUNCIATION BITMAP 340. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 4: Mapa de Registros de Pcc

ii

Safety Precautions

SAVE THESE INSTRUCTIONS − This manual contains important instructions that should be followed duringinstallation and maintenance of the generator set and batteries.

Before operating the generator set (genset), read the Operator’s Manual and become familiar with it andthe equipment. Safe and efficient operation can be achieved only if the equipment is properly operatedand maintained. Many accidents are caused by failure to follow fundamental rules and precautions.

The following symbols, found throughout this manual, alert you to potentially dangerous conditions to the op-erator, service personnel, or the equipment.

DANGER This symbol warns of immediate hazards which will result in severe personal injury ordeath.

WARNING This symbol refers to a hazard or unsafe practice which can result in severe personal in-jury or death.

CAUTION This symbol refers to a hazard or unsafe practice which can result in personal injury orproduct or property damage.

FUEL AND FUMES ARE FLAMMABLE

Fire, explosion, and personal injury or death can result from improper practices.

• DO NOT fill fuel tanks while engine is running, unless tanks are outside the engine compartment. Fuelcontact with hot engine or exhaust is a potential fire hazard.

• DO NOT permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source near thegenerator set or fuel tank.

• Fuel lines must be adequately secured and free of leaks. Fuel connection at the engine should be madewith an approved flexible line. Do not use zinc coated or copper fuel lines with diesel fuel.

• Natural gas is lighter than air, and will tend to gather under hoods. Propane is heavier than air, and willtend to gather in sumps or low areas. NFPA code requires all persons handling propane to be trained andqualified.

• Be sure all fuel supplies have a positive shutoff valve.

• Be sure battery area has been well-ventilated prior to servicing near it. Lead-acid batteries emit a highlyexplosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.

EXHAUST GASES ARE DEADLY

• Provide an adequate exhaust system to properly expel discharged gases away from enclosed or shel-tered areas and areas where individuals are likely to congregate. Visually and audibly inspect the exhaustfor leaks daily or per the maintenance schedule. Make sure that exhaust manifolds are secured and notwarped. Do not use exhaust gases to heat a compartment.

• The exhaust vent should be high enough to help clear gases, avoid accumulation of snow, and in accor-dance with local mechanical codes.

• Be sure the unit is well ventilated.

• Engine exhaust and some of its constituents are known to the state of California to cause cancer, birthdefects, and other reproductive harm.

MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH

• Keep your hands, clothing, and jewelry away from moving parts.

Page 5: Mapa de Registros de Pcc

iii

• Before starting work on the generator set, disconnect battery charger from its AC source, then disconnectstarting batteries, negative (−) cable first. In lean-burn natural gas (LBNG) gensets, also make sure thestarter’s air supply line is disconnected or completely vented until the generator set is ready to start. Thiswill prevent accidental starting.

• Make sure that fasteners on the generator set are secure. Tighten supports and clamps, keep guardsin position over fans, drive belts, etc.

• Do not wear loose clothing or jewelry in the vicinity of moving parts, or while working on electrical equip-ment. Loose clothing and jewelry can become caught in moving parts.

• If adjustment must be made while the unit is running, use extreme caution around hot manifolds, movingparts, etc.

DO NOT OPERATE IN FLAMMABLE AND EXPLOSIVE ENVIRONMENTS

Flammable vapor can cause an engine to overspeed and become difficult to stop, resulting in possible fire,explosion, severe personal injury and death. Do not operate a genset where a flammable vapor environmentcan be created by fuel spill, leak, etc., unless the genset is equipped with an automatic safety device to blockthe air intake and stop the engine. The owners and operators of the genset are solely responsible for operatingthe genset safely. Contact your authorized Cummins Power Generation distributor for more information.

ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH

• Remove electric power before removing protective shields or touching electrical equipment. Use rubberinsulative mats placed on dry wood platforms over floors that are metal or concrete when around electricalequipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp whenhandling electrical equipment. Do not wear jewelry. Jewelry can short out electrical contacts and causeshock or burning.

• Use extreme caution when working on electrical components. High voltages can cause injury or death.DO NOT tamper with interlocks.

• Follow all applicable state and local electrical codes. Have all electrical installations performed by a quali-fied licensed electrician. Tag and lock open switches to avoid accidental closure.

• DO NOT CONNECT GENERATOR SET DIRECTLY TO ANY BUILDING ELECTRICAL SYSTEM. Haz-ardous voltages can flow from the generator set into the utility line. This creates a potential for electrocu-tion or property damage. Connect only through an approved isolation switch or an approved parallelingdevice.

MEDIUM VOLTAGE GENERATOR SETS (601V to 15kV)

• Medium voltage acts differently than low voltage. Special equipment and training is required to work onor around medium voltage equipment. Operation and maintenance must be done only by persons trainedand qualified to work on such devices. Improper use or procedures will result in severe personal injuryor death.

• Do not work on energized equipment. Unauthorized personnel must not be permitted near energizedequipment. Due to the nature of medium voltage electrical equipment, induced voltage remains even af-ter the equipment is disconnected from the power source. Plan the time for maintenance with authorizedpersonnel so that the equipment can be de-energized and safely grounded.

GENERAL SAFETY PRECAUTIONS

• Coolants under pressure have a higher boiling point than water. DO NOT open a radiator or heat ex-changer pressure cap while the engine is running. To prevent severe scalding, let engine cool down be-fore removing coolant pressure cap. Turn cap slowly, and do not open it fully until the pressure has beenrelieved.

• Used engine oils have been identified by some state or federal agencies as causing cancer or reproduc-tive toxicity. When checking or changing engine oil, take care not to ingest, breathe the fumes, or contactused oil.

Page 6: Mapa de Registros de Pcc

iv

• Keep multi-class ABC fire extinguishers handy. Class A fires involve ordinary combustible materials suchas wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires,live electrical equipment. (ref. NFPA No. 10).

• Make sure that rags or combustible material are not left on or near the generator set.

• Make sure generator set is mounted in a manner to prevent combustible materials from accumulatingunder or near the unit.

• Remove all unnecessary grease and oil from the unit. Accumulated grease and oil can cause overheatingand engine damage which present a potential fire hazard.

• Keep the generator set and the surrounding area clean and free from obstructions. Remove any debrisfrom the set and keep the floor clean and dry.

• Do not work on this equipment when mentally or physically fatigued, or after consuming any alcohol ordrug that makes the operation of equipment unsafe.

• Substances in exhaust gases have been identified by some state or federal agencies as causing canceror reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.

• Do not store any flammable liquids, such as fuel, cleaners, oil, etc., near the generator set. A fire or explo-sion could result.

• Wear hearing protection when near an operating generator set.

• To prevent serious burns, avoid contact with hot metal parts such as radiator system, turbo charger sys-tem and exhaust system.

DISPOSE OF THIS UNIT PROPERLY

Page 7: Mapa de Registros de Pcc

v

THIS PAGE LEFT INTENTIONALLY BLANK

Page 8: Mapa de Registros de Pcc

1

1. PCC 1301/PowerCommand 1.x Modbus Register MapThe genset controller contains data that can be readby a remote device communicating via ModbusRTU protocol on a two−wire RS485 master/slavemulti−drop bus. In this arrangement the remote de-vice is the master and the genset controller is theslave.

For more information about the Modbus protocol,refer to Modbus Application Protocol v1.1a and

Modbus Serial Line Implementation Guide v1.0,both available at www.modbus.org.

Multi−Drop Network Mode Pins:

• Hi (+) TB2-3

• Lo (−) TB2-4

• Shield TB2-1

Note: If an address or bit is not listed in this table it isnot used.

Addr. Description Read / Write Scale Units Type Notes

40004 Save adjustments Read andWrite

− − Unsignedinteger

0=No action1=Save adjustmentsSave adjustments saves tonon volatile memory all thewrite parameters listed inthis table

40010 Genset control run/off/auto switch position

Read − Switchposition

Unsignedinteger

0=off1=Run/Manual2=Auto

40011 Genset operatingstate

Read − Operatingstate

Unsignedinteger

0=Stopped1=Start Pending2=Warm−up at Idle3=Running4=Cool down at Rated5=Cool down at Idle

40012 Fault Code Read − Event code Unsignedinteger

This register contains thefault code number of current-ly active fault. See servicemanual for list of supportedfault codes.

40013 Fault Type Read − Fault type Unsignedinteger

This register contains thefault type of currently activefault 0=Normal1=Warning2=Derate3=Shutdown with Cool down4=Shutdown

40016 NFPA 110 fault regis-ter

Read − bitmap See section 4.

40017 Extended Annunci-ation fault register

Read − bitmap See section 4.

40018 Alternator output volt-age line to neutral (a

phase)

Read 1.0 AC Volts Unsignedinteger

40019 Alternator output volt-age line to neutral (b

phase)

Read 1.0 AC Volts Unsignedinteger

Page 9: Mapa de Registros de Pcc

2

Addr. NotesTypeUnitsScaleRead / WriteDescription40020 Alternator output volt-

age line to neutral (cphase)

Read 1.0 AC Volts Unsignedinteger

40022 Alternator output volt-age line to line (a to b

phase)

Read 1.0 AC Volts Unsignedinteger

40023 Alternator output volt-age line to line (b to c

phase)

Read 1.0 AC Volts Unsignedinteger

40024 Alternator output volt-age line to line (c to a

phase)

Read 1.0 AC Volts Unsignedinteger

40025 Alternator output vol-tage (used for voltage

regulation)

Read 1.0 AC Volts Unsignedinteger

40026 Alternator output cur-rent (phase a)

Read 0.1 AC Amps Unsignedinteger

40027 Alternator output cur-rent (phase b)

Read 0.1 AC Amps Unsignedinteger

40028 Alternator output cur-rent (phase c)

Read 0.1 AC Amps Unsignedinteger

40029 Alternator output aver-age current

Read 0.1 AC Amps Unsignedinteger

40040 Alternator output volt−amperes (phase a)

Read 0.1 kVA Unsignedinteger

40041 Alternator output volt−amperes (phase b)

Read 0.1 kVA Unsignedinteger

40042 Alternator output volt−amperes (phase c)

Read 0.1 kVA Unsignedinteger

40043 Alternator output volt−amperes (total)

Read 0.1 kVA Unsignedinteger

40044 Alternator frequency Read 0.1 Hz Unsignedinteger

40058 Alternator output cur-rent (phase a)

Read 0.1 % of nominal Unsignedinteger

40059 Alternator output cur-rent (phase a)

Read 0.1 % of nominal Unsignedinteger

40060 Alternator output cur-rent (phase c)

Read 0.1 % of nominal Unsignedinteger

40061 Control battery volt-age

Read 0.1 DC Volts Unsignedinteger

40062 Engine oil pressure Read 1.0 kPa Unsignedinteger

40064 Engine coolant tem-perature

Read 0.1 Degrees Cel-sius

Unsignedinteger

40068 Engine speed Read 0.1 RPM Unsignedinteger

40069 Number of enginestarts

Read 1.0 Number ofstarts

Unsignedinteger

40070 Engine runtime (highbyte)

Read 1.0 Sec Unsignedinteger

Page 10: Mapa de Registros de Pcc

3

Addr. NotesTypeUnitsScaleRead / WriteDescription40071 Engine Runtime (Low

byte)Read 1.0 Sec Unsigned

integer

40300 Genset start stop con-trol via Modbus

Read andWrite

Unsignedinteger

0 − Stop1− Start

40302 Genset E−stop switchvia Modbus

Read andWrite

Unsignedinteger

0 − Estop not active1 − Estop active

43000 Nominal alternatorvoltage setting

Read andWrite

1.0 AC Volts Unsignedinteger

43001 Nominal alternator fre-quency setting

Read andWrite

Hz Unsignedinteger

0 = 601 = 50

43002 Alternator phase set-ting

Read andWrite

# of phases Unsignedinteger

0 = 11 =3

43003 Alternator connectionsetting

Read andWrite

Alternator Unsignedinteger

1=Wye

43004 Glow plug driver fea-ture enable

Read andWrite

Feature en-abled

Unsignedinteger

0 = No1 = Yes

43005 Battery charging alter-nator fault enable

Read andWrite

Feature en-abled

Unsignedinteger

0 = No1 = Yes

43006 Remote start timedelay

Read andWrite

1.0 Sec Unsignedinteger

43007 Remote stop timedelay

Read andWrite

1.0 Sec Unsignedinteger

43008 Engine starting −cycle crank attempts

setting

Read andWrite

1.0 Number of at-tempts

Unsignedinteger

43009 Engine starting −cycle crank time set-ting

Read andWrite

1.0 Sec Unsignedinteger

43010 Engine starting −cycle crank rest time

setting

Read andWrite

1.0 Sec Unsignedinteger

43011 Fault bypass (battleshort) feature enable

Read andWrite

Feature en-abled

Unsignedinteger

0 =Inactive1 = Active

43012 Fault bypass (battleshort) switch input as-

signment

Read andWrite

Switch as-signment

Unsignedinteger

0= None1=Customer Input 12=Customer Input 23=Operator Panel

43013 Automatic voltageregulator Enable

Read andWrite

Feature en-abled

Unsignedinteger

0 = No1 = Yes

43014 Automatic voltageregulator volts per

hertz roll off knee set-ting

Read andWrite

0.1 Hz Unsignedinteger

43015 Automatic voltageregulator volts perhertz roll off slope

setting

Read andWrite

0.1 %V/Hz Unsignedinteger

43016 Automatic voltageregulator gain setting

Read andWrite

1.0 % Unsignedinteger

Page 11: Mapa de Registros de Pcc

4

Addr. NotesTypeUnitsScaleRead / WriteDescription43017 Automatic voltage

regulator integral set-ting

Read andWrite

1.0 1.0 Unsignedinteger

43018 Automatic voltageregulator derivative

setting

Read andWrite

1.0 1.0 Unsignedinteger

43019 Electronic governingenable

Read andWrite

1.0 1.0 Unsignedinteger

0 = No1 = Yes

43020 Electronic governinginitial duty cycle set-

ting

Read andWrite

0.1 1.0 Unsignedinteger

43021 Electronic governinginitial duty cycle time

Read andWrite

0.1 Sec Unsignedinteger

43022 Electronic governingstart ramp duty cycle

setting

Read andWrite

0.1 % Unsignedinteger

43023 Electronic governingmaximum duty cycle

setting

Read andWrite

0.1 % Unsignedinteger

43024 Electronic governinggain setting

Read andWrite

1.0 % Unsignedinteger

43025 Electronic governingintegral setting

Read andWrite

1.0 % Unsignedinteger

43026 Electronic governingderivative setting

Read andWrite

1.0 % Unsignedinteger

43027 Electronic governingcrank exit fuel duty

cycle setting

Read andWrite

0.1 % Unsignedinteger

43028 Electronic governingdither factor setting

Read andWrite

1.0 % Unsignedinteger

43029 Electronic governingstart ramp time setting

Read andWrite

0.01 Sec Unsignedinteger

43030 Electronic governingenable engine speed

Read andWrite

1.0 RPM Unsignedinteger

43031 Electronic governingminimum duty cycle

setting

Read andWrite

1.0 % Unsignedinteger

43032 Electronic governingmaximum duty cycle

setting

Read andWrite

1.0 % Unsignedinteger

43033 Model number char-acter #1

Read andWrite

Character

43034 Model number char-acter #2

Read andWrite

Character

43035 Model number char-acter #3

Read andWrite

Character

43036 Model number char-acter #4

Read andWrite

Character

43037 Model number char-acter #5

Read andWrite

Character

Page 12: Mapa de Registros de Pcc

5

Addr. NotesTypeUnitsScaleRead / WriteDescription43038 Model number char-

acter #6Read and

WriteCharacter

43039 Model number char-acter #7

Read andWrite

Character

43040 Model number char-acter #8

Read andWrite

Character

43041 Model number char-acter #9

Read andWrite

Character

43042 Model number char-acter #10

Read andWrite

Character

43043 Model number char-acter #11

Read andWrite

Character

43044 Model number char-acter #12

Read andWrite

Character

43045 Model number char-acter #13

Read andWrite

Character

43046 Model number char-acter #14

Read andWrite

Character

43047 Model number char-acter #15

Read andWrite

Character

43048 Model number char-acter #16

Read andWrite

Character

43049 Serial number charac-ter #1

Read andWrite

Character

43050 Serial number charac-ter #2

Read andWrite

Character

43051 Serial number charac-ter #3

Read andWrite

Character

43052 Serial number charac-ter #4

Read andWrite

Character

43053 Serial number charac-ter #5

Read andWrite

Character

43054 Serial number charac-ter #6

Read andWrite

Character

43055 Serial number charac-ter #7

Read andWrite

Character

43056 Serial number charac-ter #8

Read andWrite

Character

43057 Serial number charac-ter #9

Read andWrite

Character

43058 Serial number charac-ter #10

Read andWrite

Character

43059 Serial number charac-ter #11

Read andWrite

Character

43060 Serial number charac-ter #12

Read andWrite

Character

43061 Serial number charac-ter #13

Read andWrite

Character

43062 Serial number charac-ter #14

Read andWrite

Character

Page 13: Mapa de Registros de Pcc

6

Addr. NotesTypeUnitsScaleRead / WriteDescription43063 Serial number charac-

ter #15Read and

WriteCharacter

43064 Serial number charac-ter #16

Read andWrite

Character

43065 Configurable input #1type

Read andWrite

Input type Unsignedinteger

0 = Event1 = Warning2 = Shutdown

43066 Configurable input #2type

Read andWrite

Input type Unsignedinteger

0 = Event1 = Warning2 = Shutdown

43067 Configurable output#1 event code number

Read andWrite

1.0 Event code Unsignedinteger

43068 Configurable output#2 fault event number

Read andWrite

1.0 Event code Unsignedinteger

43069 60 Hz alternator out-put voltage adjust %

Read andWrite

1.0 % Unsignedinteger

43070 50 Hz alternator out-put voltage adjust %

Read andWrite

0.1 % Unsignedinteger

43071 Alternator frequencyadjustment %

Read andWrite

0.1 0.1 Unsignedinteger

43072 60 Hz line 1 to neutralmetering voltage cal-

ibration

Read andWrite

0.0001 % Unsignedinteger

43073 60 Hz line 2 to neutralmetering voltage cal-

ibration

Read andWrite

0.0001 % Unsignedinteger

43075 50 Hz line 1 to neutralmetering voltage cal-

ibration

Read andWrite

0.0001 % Unsignedinteger

43076 50 Hz line 2 to neutralmetering voltage cal-

ibration

Read andWrite

0.0001 % Unsignedinteger

43077 50 Hz line 3 to neutralmetering voltage cal-

ibration

Read andWrite

0.0001 % Unsignedinteger

43078 60 Hz line 1 meteringcurrent calibration

Read andWrite

0.001 % Unsignedinteger

43079 60 Hz line 2 meteringcurrent calibration

Read andWrite

0.001 % Unsignedinteger

43080 60 Hz line 3 meteringcurrent calibration

Read andWrite

0.001 % Unsignedinteger

43081 50 Hz line 1 meteringcurrent calibration

Read andWrite

0.001 % Unsignedinteger

43082 50 Hz line 2 meteringcurrent calibration

Read andWrite

0.001 % Unsignedinteger

43083 50 Hz line 3 meteringcurrent calibration

Read andWrite

0.001 % Unsignedinteger

43084 Annunciator configur-able input #1 type

Read andWrite

Input type Unsignedinteger

0 = Event1 = Warning2 = Shutdown

Page 14: Mapa de Registros de Pcc

7

Addr. NotesTypeUnitsScaleRead / WriteDescription43085 Annunciator configur-

able input #2 typeRead and

WriteInput type Unsigned

integer0 = Event1 = Warning2 = Shutdown

43086 Annunciator configur-able input #3 type

Read andWrite

Input type Unsignedinteger

0 = Event1 = Warning2 = Shutdown

43087 Annunciator configur-able output #1 event

code number

Read andWrite

1.0 Event code Unsignedinteger

43088 Annunciator configur-able output #2 event

code number

Read andWrite

1.0 Event code Unsignedinteger

43089 Annunciator configur-able output #3 event

code number

Read andWrite

1.0 Event code Unsignedinteger

43090 Annunciator configur-able output #4 event

code number

Read andWrite

1.0 Event code Unsignedinteger

Page 15: Mapa de Registros de Pcc

8

THIS PAGE LEFT INTENTIONALLY BLANK

Page 16: Mapa de Registros de Pcc

9

2. PowerCommand 2.x/3.x Modbus Register Map

Note: If an address or bit is not listed in this table it is not used.

Addr. Name Parameter Access Description Control40010 GC / Start/

Stop Con-trol

ControlSwitch Posi-tion

ReadOnly

Current position of the genset switch panel Off−Run−Auto switch as seen by the genset control. Modbusmapping shall be in both addresses 40580 and40010. For Modbus Only: 0: Off 1: Auto 2: Manual

PC 2.x, PC3.x

0: Off1: Manual2: Auto

40011 GC / Start/Stop Con-trol

Genset RunSequenceState

ReadOnly

Current genset operating mode. Modbus mappingshall be in both addresses 43500 and 40011

PC 2.x, PC3.x

0: Off1: Time Delay to Start2: Warmup at Idle3: Rated Freq and Voltage4: Cooldown / Stop Delay5: Cooldown at Idle

40013 Modbus /Modbus

Modbus regis-ter 40013

ReadOnly

This register always returns the value 0. This is not as-sociated with any logical. It is made same as 1302 tomake it compatible with iWatch.

PC 2.x, PC3.x

0: None1: Warning2: Shutdown

40012 Modbus /Modbus

Most RecentFault or Warn-ing

ReadOnly

Multiplier:1

Unit: FaultCode

This Modbus Registerdisplays most recentFault or Warning. It is notmapped with any logical.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40014 ACM /GensetCurrentand Power− %

Genset %Standby TotalkW

ReadOnly

Multiplier:0.01

Unit: % Monitors the total gensetstandby KW percentageoutput.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40016 PCCNet /UniversalAnnuncia-tor

NFPA 110Logical Status

ReadOnly

Multiplier:1

Unit: 32−bit number to repre-sent the status of theNFPA 110 logical. Seesection 4.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 17: Mapa de Registros de Pcc

10

Addr. ControlDescriptionAccessParameterName40017 PCCNet /

UniversalAnnuncia-tor

NFPA 110Logical Status

ReadOnly

Multiplier:1

Unit: 32−bit number to repre-sent the status of theNFPA 110 logical. Seesection 4.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U40018 ACM /

VoltageGenset L1NVoltage

ReadOnly

Multiplier:1

Unit: Vac Genset L1N voltage PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40019 ACM /

VoltageGenset L2NVoltage

ReadOnly

Multiplier:1

Unit: Vac Genset L2N voltage PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40020 ACM /

VoltageGenset L3NVoltage

ReadOnly

Multiplier:1

Unit: Vac Genset L3N voltage PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40021 ACM /

VoltageGenset LNAverage Volt-age

ReadOnly

Multiplier:1

Unit: Vac Genset Line to Neutralaverage voltage

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40022 ACM /

VoltageGenset L1L2Voltage

ReadOnly

Multiplier:1

Unit: Vac Genset L1L2 voltage PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40023 ACM /

VoltageGenset L2L3Voltage

ReadOnly

Multiplier:1

Unit: Vac Genset L2L3 voltage PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 18: Mapa de Registros de Pcc

11

Addr. ControlDescriptionAccessParameterName40024 ACM /

VoltageGenset L3L1Voltage

ReadOnly

Multiplier:1

Unit: Vac Genset L3L1 voltage PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40025 ACM /Voltage

Genset LL Av-erage Voltage

ReadOnly

Multiplier:1

Unit: Vac Genset Line to Line aver-age voltage

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40026 ACM /Current

Genset L1Current

ReadOnly

Multiplier:1

Unit: Amps Monitors the genset L1current value.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40027 ACM /Current

Genset L2Current

ReadOnly

Multiplier:1

Unit: Amps Genset L2 current PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40028 ACM /Current

Genset L3Current

ReadOnly

Multiplier:1

Unit: Amps Genset L3 current PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40029 ACM /Current

Genset Aver-age Current

ReadOnly

Multiplier:1

Unit: Amps Genset average current PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40030 ACM /Current

Genset Neu-tral Current

ReadOnly

Multiplier:1

Unit: Amps Genset neutral current PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40031 ACM /Power

Genset L1 kW ReadOnly

Multiplier:1

Unit: kW Genset L1 kW PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 19: Mapa de Registros de Pcc

12

Addr. ControlDescriptionAccessParameterName40032 ACM /

PowerGenset L2 kW Read

OnlyMultiplier:1

Unit: kW Genset L2 kW PC 2.x, PC3.x

Offset: 0 Lower Limit: −32768Size (bits):16

Upper Limit: 32762

Sign: S

40033 ACM /Power

Genset L3 kW ReadOnly

Multiplier:1

Unit: kW Genset L3 kW PC 2.x, PC3.x

Offset: 0 Lower Limit: −32768Size (bits):16

Upper Limit: 32762

Sign: S

40034 ACM /Power

Genset TotalkW

ReadOnly

Multiplier:1

Unit: kW Genset total kW PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40035 ACM /Power

Genset L1kVAR

ReadOnly

Multiplier:1

Unit: kVAR Genset L1 KVAR PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40036 ACM /Power

Genset L2kVAR

ReadOnly

Multiplier:1

Unit: kVAR Genset L2 Kvar PC 2.x, PC3.x

Offset: 0 Lower Limit: −32768Size (bits):16

Upper Limit: 32762

Sign: S

40037 ACM /Power

Genset L3kVAR

ReadOnly

Multiplier:1

Unit: kVAR Genset L3 Kvar PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40038 ACM /Power

Genset TotalkVAR

ReadOnly

Multiplier:1

Unit: kVAR Genset total kVAR PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40039 ACM /Power

Genset TotalPower Factor

ReadOnly

Multiplier:0.01

Unit: PF Genset total power factor(L1+L2+L3)

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: S

Page 20: Mapa de Registros de Pcc

13

Addr. ControlDescriptionAccessParameterName40040 ACM /

PowerGenset L1kVA

ReadOnly

Multiplier:1

Unit: kVA Genset L1 kVA PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40041 ACM /

PowerGenset L2kVA

ReadOnly

Multiplier:1

Unit: kVA Genset L2 kVA PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40042 ACM /

PowerGenset L3kVA

ReadOnly

Multiplier:1

Unit: kVA Genset L3 kVA PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40043 ACM /

PowerGenset TotalkVA

ReadOnly

Multiplier:1

Unit: kVA Genset total kVA PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40044 PCCNet /

OperatorPanel

Genset Fre-quency OP

ReadOnly

Multiplier:0.01

Unit: Hz Genset Frequency OP.Modbus has differentmultiplier than PCCnet.For Modbus use only,Multiplier/Units = 0.1 Hz

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40046 ACM / En-

ergyGenset TotalNegative kWh

ReadOnly

Multiplier:1

Unit: kWh Genset total negativekWh accumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U40047 ACM / En-

ergyGenset TotalNegative kWh

ReadOnly

Multiplier:1

Unit: kWh Genset total negativekWh accumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 21: Mapa de Registros de Pcc

14

Addr. ControlDescriptionAccessParameterName40048 ACM / En-

ergyGenset TotalPositive kWh

ReadOnly

Multiplier:1

Unit: kWh Genset total positive kWhaccumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967290

Sign: U

40049 ACM / En-ergy

Genset TotalPositive kWh

ReadOnly

Multiplier:1

Unit: kWh Genset total positive kWhaccumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967290

Sign: U

40050 ACM / En-ergy

Genset TotalNet kWh

ReadOnly

Multiplier:1

Unit: kWh Genset total net kWh ac-cumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit: −2147483648Size (bits):32

Upper Limit: 2147483643

Sign: S

40051 ACM / En-ergy

Genset TotalNet kWh

ReadOnly

Multiplier:1

Unit: kWh Genset total net kWh ac-cumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit: −2147483648Size (bits):32

Upper Limit: 2147483643

Sign: S

40052 ACM / En-ergy

Genset TotalNegativekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset total negativekVARh accumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40053 ACM / En-ergy

Genset TotalNegativekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset total negativekVARh accumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40054 ACM / En-ergy

Genset TotalPositivekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset total positivekVARh accumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967290

Sign: U

40055 ACM / En-ergy

Genset TotalPositivekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset total positivekVARh accumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967290

Sign: U

Page 22: Mapa de Registros de Pcc

15

Addr. ControlDescriptionAccessParameterName40056 ACM / En-

ergyGenset TotalNet kVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset total net kVARhaccumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit: −2147483648Size (bits):32

Upper Limit: 2147483643

Sign: S40057 ACM / En-

ergyGenset TotalNet kVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset total net kVARhaccumulation

PC 2.x, PC3.x

Offset: 0 Lower Limit: −2147483648Size (bits):32

Upper Limit: 2147483643

Sign: S40058 ACM /

GensetCurrentand Power− %

Genset %Standby L1Current

ReadOnly

Multiplier:0.1

Unit: % Monitors the gensetstandby L1 current per-centage output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40059 ACM /

GensetCurrentand Power− %

Genset %Standby L2Current

ReadOnly

Multiplier:0.1

Unit: % Monitors the gensetstandby L2 current per-centage output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40060 ACM /

GensetCurrentand Power− %

Genset %Standby L3Current

ReadOnly

Multiplier:0.1

Unit: % Monitors the gensetstandby L3 current per-centage output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40061 ASI / Ana-

log InputsBattery Volt-age

ReadOnly

Multiplier:0.001

Unit: Vdc Battery voltage val-ue−−−−−> For Modbususe only multiplier/units =0.1 Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 23: Mapa de Registros de Pcc

16

Addr. ControlDescriptionAccessParameterName40062 CAN /

CAN InputMessages

Oil Pressure ReadOnly

Multiplier:0.1

Unit: psi Monitor point for the OilPressure. Modbus andPCCnet have differentmultiplier value. For mod-bus use only, Multiplier/Units = 1kPa

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40063 CAN /CAN InputMessages

Oil Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the OilTemperature

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40064 CAN /CAN InputMessages

Coolant Tem-perature

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for theCoolant Temperature.Modbus mapping shall beto both 46126 and 40064addresses. For Modbususe only, Multiplier/Units= 0.1C

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40065 CAN /CAN InputMessages

Intake Man-ifold Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF To monitor Intake Man-ifold Temperature. Thisparameter represents ”In-take Manifold Tempera-ture 1”.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −40Size (bits):16

Upper Limit: 410

Sign: S

40066 CAN /CAN InputMessages

Fuel Temper-ature

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the FuelTemperature

PC 2.x, PC3.x

Offset: 0 Lower Limit: −40Size (bits):16

Upper Limit: 410

Sign: S

40067 CAN /CAN InputMessages

Fuel Rate ReadOnly

Multiplier:0.05

Unit: gal/hr Monitor point for the FuelRate

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit:

Sign: U

Page 24: Mapa de Registros de Pcc

17

Addr. ControlDescriptionAccessParameterName40068 CAN /

CAN InputMessages

Average En-gine Speed

ReadOnly

Multiplier:0.125

Unit: rpm Monitor point for the Av-erage Engine Speed.Modbus and PCCnethave different multipliervalue. For modbus useonly, Multiplier/Units = 1RPM

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 4096

Sign: U

40069 PCCNet /OperatorPanel

Total Start At-tempts OP

ReadOnly

Multiplier:1

Unit: Total number of start at-tempts.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

40070 CAN /CAN InputMessages

Engine Run-ning Time

ReadOnly

Multiplier:0.05

Unit: hours Total engine run time.Modbus has differentmultiplier than PCCnet.For Modbus use only,multiplier/units = 1.0 Sec

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40071 CAN /CAN InputMessages

Engine Run-ning Time

ReadOnly

Multiplier:0.05

Unit: hours Total engine run time.Modbus has differentmultiplier than PCCnet.For Modbus use only,multiplier/units = 1.0 Sec

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40072 CAN /CAN InputMessages

Total FuelConsumption

ReadOnly

Multiplier:0.1

Unit: gal-lons

Total fuel consumptionsince start of engine.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40073 CAN /CAN InputMessages

Total FuelConsumption

ReadOnly

Multiplier:0.1

Unit: gal-lons

Total fuel consumptionsince start of engine.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 25: Mapa de Registros de Pcc

18

Addr. ControlDescriptionAccessParameterName40074 DR / Data

RecordingTotal Numberof Runs

ReadOnly

Multiplier:1

Unit: Total number of gensetruns.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967295

Sign: U40075 DR / Data

RecordingTotal Numberof Runs

ReadOnly

Multiplier:1

Unit: Total number of gensetruns.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967295

Sign: U40076 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40077 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 26: Mapa de Registros de Pcc

19

Addr. ControlDescriptionAccessParameterName40078 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40079 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40080 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 27: Mapa de Registros de Pcc

20

Addr. ControlDescriptionAccessParameterName40081 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40082 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40083 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 28: Mapa de Registros de Pcc

21

Addr. ControlDescriptionAccessParameterName40084 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40085 DR / Data

RecordingRuns ResetTime

Read/Write

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40086 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 29: Mapa de Registros de Pcc

22

Addr. ControlDescriptionAccessParameterName40087 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40088 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40089 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 30: Mapa de Registros de Pcc

23

Addr. ControlDescriptionAccessParameterName40090 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40091 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40092 DR / Data

RecordingRuns ResetTime

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theRun Attempts were reset.This parameter is READ/WRITE for Mon andPCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40076 − 40092 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 31: Mapa de Registros de Pcc

24

Addr. ControlDescriptionAccessParameterName40096 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40097 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40098 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 32: Mapa de Registros de Pcc

25

Addr. ControlDescriptionAccessParameterName40099 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40100 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40101 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 33: Mapa de Registros de Pcc

26

Addr. ControlDescriptionAccessParameterName40102 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40103 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40104 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 34: Mapa de Registros de Pcc

27

Addr. ControlDescriptionAccessParameterName40105 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40106 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40107 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 35: Mapa de Registros de Pcc

28

Addr. ControlDescriptionAccessParameterName40108 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40109 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C40110 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

Page 36: Mapa de Registros de Pcc

29

Addr. ControlDescriptionAccessParameterName40111 DR / Data

RecordingStart AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

40112 DR / DataRecording

Start AttemptsReset Time

ReadOnly

Multiplier:1

Unit: Real Time Clock stamprecord of the last time theStart Attempts were re-set. This parameter isREAD/WRITE for Monand PCCNet and READONLY for ModBus. Mod-bus implementation orthe Real time stamp willuse 40096 − 0112 for 17char of this string.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):144

Upper Limit:

Sign: C

40118 ACM /Voltage

Utility L1NVoltage

ReadOnly

Multiplier:1

Unit: Vac Utility L1N voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40119 ACM /Voltage

Utility L2NVoltage

ReadOnly

Multiplier:1

Unit: Vac Utility L2N voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40120 ACM /Voltage

Utility L3NVoltage

ReadOnly

Multiplier:1

Unit: Vac Utility L3N voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 37: Mapa de Registros de Pcc

30

Addr. ControlDescriptionAccessParameterName40121 ACM /

VoltageUtility LN Av-erage Voltage

ReadOnly

Multiplier:1

Unit: Vac Utility Line to Neutral av-erage voltage

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40122 ACM /Voltage

Utility L1L2Voltage

ReadOnly

Multiplier:1

Unit: Vac Utility L1L2 voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40123 ACM /Voltage

Utility L2L3Voltage

ReadOnly

Multiplier:1

Unit: Vac Utility L2L3 voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40124 ACM /Voltage

Utility L3L1Voltage

ReadOnly

Multiplier:1

Unit: Vac Utility L3L1 voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40125 ACM /Voltage

Utility LL Av-erage Voltage

ReadOnly

Multiplier:1

Unit: Vac Utility Line to Line aver-age voltage

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40126 ACM /Current

Utility L1 Cur-rent

ReadOnly

Multiplier:1

Unit: Amps Utility L1 current PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40127 ACM /Current

Utility L2 Cur-rent

ReadOnly

Multiplier:1

Unit: Amps Utility L2 current PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40128 ACM /Current

Utility L3 Cur-rent

ReadOnly

Multiplier:1

Unit: Amps Utility L3 current PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 38: Mapa de Registros de Pcc

31

Addr. ControlDescriptionAccessParameterName40129 ACM /

CurrentUtility AverageCurrent

ReadOnly

Multiplier:1

Unit: Amps Utility average current PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40131 ACM /Power

Utility L1 kW ReadOnly

Multiplier:1

Unit: kW Utility L1 kW PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40132 ACM /Power

Utility L2 kW ReadOnly

Multiplier:1

Unit: kW Utility L2 kW PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40133 ACM /Power

Utility L3 kW ReadOnly

Multiplier:1

Unit: kW Utility L3 kW PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40134 ACM /Power

Utility TotalkW

ReadOnly

Multiplier:1

Unit: kW Utility total kW PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40135 ACM /Power

Utility L1kVAR

ReadOnly

Multiplier:1

Unit: kVAR Utility L1 Kvar PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40136 ACM /Power

Utility L2kVAR

ReadOnly

Multiplier:1

Unit: kVAR Utility L2 Kvar PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40137 ACM /Power

Utility L3kVAR

ReadOnly

Multiplier:1

Unit: kVAR Utility L3 Kvar PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 39: Mapa de Registros de Pcc

32

Addr. ControlDescriptionAccessParameterName40138 ACM /

PowerUtility TotalkVAR

ReadOnly

Multiplier:1

Unit: kVAR Utility total kVAR PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40139 ACM /Power

Utility TotalPower Factor

ReadOnly

Multiplier:0.01

Unit: PF Utility total power factor PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: S

40140 ACM /Power

Utility L1 kVA ReadOnly

Multiplier:1

Unit: kVA Utility L1 kVA PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40141 ACM /Power

Utility L2 kVA ReadOnly

Multiplier:1

Unit: kVA Utility L2 kVA PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40142 ACM /Power

Utility L3 kVA ReadOnly

Multiplier:1

Unit: kVA Utility L3 kVA PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40143 ACM /Power

Utility TotalkVA

ReadOnly

Multiplier:1

Unit: kVA Utility total kVA PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40144 ACM / Fre-quency

Utility Fre-quency

ReadOnly

Multiplier:0.001

Unit: Hz Utility line frequency PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40145 ACM / Fre-quency

Utility Fre-quency

ReadOnly

Multiplier:0.001

Unit: Hz Utility line frequency PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 40: Mapa de Registros de Pcc

33

Addr. ControlDescriptionAccessParameterName40146 ACM / En-

ergyUtility TotalNegative kWh

ReadOnly

Multiplier:1

Unit: kWh Utility total negative kWhaccumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40147 ACM / En-ergy

Utility TotalNegative kWh

ReadOnly

Multiplier:1

Unit: kWh Utility total negative kWhaccumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40148 ACM / En-ergy

Utility TotalPositive kWh

ReadOnly

Multiplier:1

Unit: kWh Utility total positive kWhaccumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40149 ACM / En-ergy

Utility TotalPositive kWh

ReadOnly

Multiplier:1

Unit: kWh Utility total positive kWhaccumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40150 ACM / En-ergy

Utility TotalNet kWh

ReadOnly

Multiplier:1

Unit: kWh Utility total net kWh accu-mulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: S

40151 ACM / En-ergy

Utility TotalNet kWh

ReadOnly

Multiplier:1

Unit: kWh Utility total net kWh accu-mulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: S

40152 ACM / En-ergy

Utility TotalNegativekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Utility total negativekVARh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40153 ACM / En-ergy

Utility TotalNegativekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Utility total negativekVARh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 41: Mapa de Registros de Pcc

34

Addr. ControlDescriptionAccessParameterName40154 ACM / En-

ergyUtility TotalPositivekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Utility total positivekVARh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40155 ACM / En-ergy

Utility TotalPositivekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Utility total positivekVARh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40156 ACM / En-ergy

Utility TotalNet kVARh

ReadOnly

Multiplier:1

Unit:kVARh

Utility total net kVARh ac-cumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: S

40157 ACM / En-ergy

Utility TotalNet kVARh

ReadOnly

Multiplier:1

Unit:kVARh

Utility total net kVARh ac-cumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: S

40158 ACM /Voltage

Genset BusL1N Voltage

ReadOnly

Multiplier:1

Unit: Vac Genset Bus L1N voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40159 ACM /Voltage

Genset BusL2N Voltage

ReadOnly

Multiplier:1

Unit: Vac Genset Bus L2N voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40160 ACM /Voltage

Genset BusL3N Voltage

ReadOnly

Multiplier:1

Unit: Vac Genset Bus L3N voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40161 ACM /Voltage

Genset BusLN AverageVoltage

ReadOnly

Multiplier:1

Unit: Vac Genset Bus Line to Neu-tral average voltage

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 42: Mapa de Registros de Pcc

35

Addr. ControlDescriptionAccessParameterName40162 ACM /

VoltageGenset BusL1L2 Voltage

ReadOnly

Multiplier:1

Unit: Vac Genset Bus L1L2 voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40163 ACM /Voltage

Genset BusL2L3 Voltage

ReadOnly

Multiplier:1

Unit: Vac Genset Bus L2L3 voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40164 ACM /Voltage

Genset BusL3L1 Voltage

ReadOnly

Multiplier:1

Unit: Vac Genset Bus L3L1 voltage PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40165 ACM /Voltage

Genset BusLL AverageVoltage

ReadOnly

Multiplier:1

Unit: Vac Genset Bus Line to Lineaverage voltage

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40166 ACM /Current

Genset BusL1 Current

ReadOnly

Multiplier:1

Unit: Amps Genset Bus L1 current PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40167 ACM /Current

Genset BusL2 Current

ReadOnly

Multiplier:1

Unit: Amps Genset Bus L2 current PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40168 ACM /Current

Genset BusL3 Current

ReadOnly

Multiplier:1

Unit: Amps Genset Bus L3 current PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40169 ACM /Current

Genset BusAverage Cur-rent

ReadOnly

Multiplier:1

Unit: Amps Genset Bus Average cur-rent

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 43: Mapa de Registros de Pcc

36

Addr. ControlDescriptionAccessParameterName40171 ACM /

PowerGenset BusL1 kW

ReadOnly

Multiplier:1

Unit: kW Genset Bus L1 kW PC 3.x

Offset: 0 Lower Limit: −32768Size (bits):16

Upper Limit: 32762

Sign: S

40172 ACM /Power

Genset BusL2 kW

ReadOnly

Multiplier:1

Unit: kW Genset Bus L2 kW PC 3.x

Offset: 0 Lower Limit: −32768Size (bits):16

Upper Limit: 32762

Sign: S

40173 ACM /Power

Genset BusL3 kW

ReadOnly

Multiplier:1

Unit: kW Genset Bus L3 kW PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40174 ACM /Power

Genset BusTotal kW

ReadOnly

Multiplier:1

Unit: kW Genset Bus total kW PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40175 ACM /Power

Genset BusL1 kVAR

ReadOnly

Multiplier:1

Unit: kVAR Genset bus L1 Kvar PC 3.x

Offset: 0 Lower Limit: −32678Size (bits):16

Upper Limit: 32672

Sign: S

40176 ACM /Power

Genset BusL2 kVAR

ReadOnly

Multiplier:1

Unit: kVAR Genset bus L2 Kvar PC 3.x

Offset: 0 Lower Limit: −32768Size (bits):16

Upper Limit: 32762

Sign: S

40177 ACM /Power

Genset BusL3 kVAR

ReadOnly

Multiplier:1

Unit: kVAR Genset bus L3 Kvar PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40178 ACM /Power

Genset BusTotal kVAR

ReadOnly

Multiplier:1

Unit: kVAR Genset bus total kVAR PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 44: Mapa de Registros de Pcc

37

Addr. ControlDescriptionAccessParameterName40179 ACM /

PowerGenset BusTotal PowerFactor

ReadOnly

Multiplier:0.01

Unit: PF Genset Bus Total powerfactor

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: S

40180 ACM /Power

Genset BusL1 kVA

ReadOnly

Multiplier:1

Unit: kVA Genset Bus L1 kVA PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40181 ACM /Power

Genset BusL2 kVA

ReadOnly

Multiplier:1

Unit: kVA Genset Bus L2 kVA PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40182 ACM /Power

Genset BusL3 kVA

ReadOnly

Multiplier:1

Unit: kVA Genset Bus L3 kVA PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40183 ACM /Power

Genset BusTotal kVA

ReadOnly

Multiplier:1

Unit: kVA Genset bus total kVA PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

40184 ACM / Fre-quency

Genset BusFrequency

ReadOnly

Multiplier:0.001

Unit: Hz Genset bus line frequen-cy

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40185 ACM / Fre-quency

Genset BusFrequency

ReadOnly

Multiplier:0.001

Unit: Hz Genset bus line frequen-cy

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40186 ACM / En-ergy

Genset BusTotal NegativekWh

ReadOnly

Multiplier:1

Unit: kWh Genset bus total negativekWh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 45: Mapa de Registros de Pcc

38

Addr. ControlDescriptionAccessParameterName40187 ACM / En-

ergyGenset BusTotal NegativekWh

ReadOnly

Multiplier:1

Unit: kWh Genset bus total negativekWh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40188 ACM / En-ergy

Genset BusTotal PositivekWh

ReadOnly

Multiplier:1

Unit: kWh Genset bus total positivekWh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40189 ACM / En-ergy

Genset BusTotal PositivekWh

ReadOnly

Multiplier:1

Unit: kWh Genset bus total positivekWh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40190 ACM / En-ergy

Genset BusTotal Net kWh

ReadOnly

Multiplier:1

Unit: kWh Genset bus total net kWhaccumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: S

40191 ACM / En-ergy

Genset BusTotal Net kWh

ReadOnly

Multiplier:1

Unit: kWh Genset bus total net kWhaccumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: S

40192 ACM / En-ergy

Genset BusTotal NegativekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset bus total negativekVARh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40193 ACM / En-ergy

Genset BusTotal NegativekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset bus total negativekVARh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40194 ACM / En-ergy

Genset BusTotal PositivekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset bus total positivekVARh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 46: Mapa de Registros de Pcc

39

Addr. ControlDescriptionAccessParameterName40195 ACM / En-

ergyGenset BusTotal PositivekVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset bus total positivekVARh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U40196 ACM / En-

ergyGenset BusTotal NetkVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset Bus total netkVARh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: S40197 ACM / En-

ergyGenset BusTotal NetkVARh

ReadOnly

Multiplier:1

Unit:kVARh

Genset Bus total netkVARh accumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: S40198 ACM /

CurrentGround Cur-rent

ReadOnly

Multiplier:0.1

Unit: amps Ground current PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40199 ACM /

CurrentGenset Nega-tive SequenceCurrent %

ReadOnly

Multiplier:0.01

Unit: % Genset Negative Se-quence Current as Per-cent of Standby CurrentRating

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40207 ASI / Ana-

log InputsBattery Char-ger AlternatorFlash Voltage

ReadOnly

Multiplier:0.001

Unit: Vdc The Battery Charger Al-ternator Flash Voltage af-ter all scaling and validitychecks.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 35

Sign: U40201 ASI / Ana-

log Inputs/Outputs

Coolant Tem-peratureSender Type

Read/Write

Either Onan or Cummins sensor. Modbus Access:Read Only

PC 2.x, PC3.x

0: PGBU1: EBU

Page 47: Mapa de Registros de Pcc

40

Addr. ControlDescriptionAccessParameterName40210 ASI / Ana-

log InputsExternalSpeed BiasInput

ReadOnly

Multiplier:0.01

Unit: % Monitor point for the ex-ternal speed bias input.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −100Size (bits):16

Upper Limit: 100

Sign: S40211 ASI / Ana-

log InputsExternal Volt-age Bias Input

ReadOnly

Multiplier:0.01

Unit: % Monitor point for the ex-ternal voltage bias input.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −100Size (bits):16

Upper Limit: 100

Sign: S40214 ASI / Ana-

log InputskVAR LoadSetpoint

ReadOnly

Multiplier:0.01

Unit: % EU scaled value for thekVAR load setpoint

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit:

Sign: S40217 ASI / Ana-

log InputskVAR LoadShare Level

ReadOnly

Multiplier:0.01

Unit: % EU Scaled value for thekVAR load share levelanalog input

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S40219 ASI / Ana-

log InputskW Load Set-point

ReadOnly

Multiplier:0.01

Unit: % EU scaled value for thekW load setpoint

PC 3.x

Offset: 0 Lower Limit: −25.01Size (bits):16

Upper Limit: 125.01

Sign: S40222 ASI / Ana-

log InputskW LoadShare Level

ReadOnly

Multiplier:0.01

Unit: % EU Scaled value for thekW load share level ana-log input

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S40224 ASO /

AnalogOutputs

KVAR LoadShare OutputPredictor

ReadOnly

Multiplier:0.1

Unit: uA uA signal being injectedinto a 10K ohm resistornetwork

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 48: Mapa de Registros de Pcc

41

Addr. ControlDescriptionAccessParameterName40225 ASO /

AnalogOutputs

KW LoadShare OutputPredictor

ReadOnly

Multiplier:0.1

Unit: uA uA signal being injectedinto a 10K ohm resistornetwork

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40226 ASO /AnalogOutputs

Speed BiasOutput / Con-figurable Ana-log output #1Output Pre-dictor

ReadOnly

Multiplier:0.01

Unit: Vdc Configurable analog out-put voltage output value(predicted)

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40227 ASO /AnalogOutputs

Voltage BiasOutput / Con-figurable Ana-log output #2Output Pre-dictor

ReadOnly

Multiplier:0.01

Unit: Vdc Configurable analog out-put voltage output value(predicted)

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40228 CAN /CAN InputMessages

Amber Warn-ing Lamp Sta-tus

ReadOnly

Engine Control System indicates a warning condition. PC 2.x, PC3.x0: Inactive

1: Active

40229 CAN /CAN InputMessages

BarometricAbsolutePressure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for theBarometric AbsolutePressure. Displayed as”Ambient Pressure” in theHMI.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 37

Sign: U

40230 CAN /CAN InputMessages

Boost Pres-sure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for theBoost Absolute Pressure

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 148

Sign: U

40231 CAN /CANDatalink

CAN DatalinkStatus

ReadOnly

Indicates the status of the CAN datalink PC 2.x, PC3.x0: Inactive

1: Active2: Failed

40232 CAN /CAN InputMessages

CrankcasePressure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for theCrankcase Pressure.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −35.67Size (bits):16

Upper Limit: 38

Sign: S

Page 49: Mapa de Registros de Pcc

42

Addr. ControlDescriptionAccessParameterName40235 CAN /

CAN InputMessages

ECM DerateRequest

ReadOnly

Request made by the ECS for a reduction in load PC 2.x, PC3.x0: No Derate Request

1: Derate Request2: Error3: Don’t Care

4023640237

CAN /CAN InputMessages

Engine Ap-plication Type

ReadOnly

Monitor point for the output of the Engine applicationtype. Either ECM (CAN) or Hydro−Mechanical.

PC 2.x, PC3.x

0: ECM1: Hydro−MechanicalECS engine state indication1: Ventilation2: Start3: Run4: Normal Shutdown5: Emergency Shutdown6: Error7: Don’t Care

40242 CAN /CAN InputMessages

AftercoolerTemperature

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Af-tercooler Temperature.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −40Size (bits):16

Upper Limit: 410

Sign: S

40254 CAN /CAN InputMessages

Fuel SupplyPressure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for the FuelSupply Pressure. Dis-played as ”Fuel SupplyPressure” in the HMI.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 145

Sign: U

40257 CAN /CAN InputMessages

Intake Man-ifold 4 Tem-perature

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the In-take Manifold 4 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −40Size (bits):16

Upper Limit: 410

Sign: S

40258 CAN /CAN InputMessages

Fuel OutletPressure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for the FuelOutlet Pressure Pres-sure. Displayed as ”FuelRail Pressure” in theHMI.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 36404

Sign: U

Page 50: Mapa de Registros de Pcc

43

Addr. ControlDescriptionAccessParameterName40259 CAN /

CAN InputMessages

Fuel OutletPressure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for the FuelOutlet Pressure Pres-sure. Displayed as ”FuelRail Pressure” in theHMI.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 36404

Sign: U

40260 CAN /CAN InputMessages

Intake Man-ifold 2 Tem-perature

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the In-take Manifold 2 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −40Size (bits):16

Upper Limit: 410

Sign: S

40261 CAN /CAN InputMessages

Intake Man-ifold 3 Tem-perature

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the In-take Manifold 3 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −40Size (bits):16

Upper Limit: 410

Sign: S

40262 CAN /CAN Out-put Mes-sages

KeyswitchCommand

ReadOnly

Driver command that controls the output for thekeyswitch

PC 2.x, PC3.x

0: Inactive1: Active

40263 CAN /CAN InputMessages

Normal Shut-down Request

ReadOnly

Request made by the ECS for a normal shutdown withcooldown

PC 2.x, PC3.x

0: No Shutdown Request1: Normal Shutdown Request2: Error3: Don’t Care

40264 CAN /CAN InputMessages

Percent En-gine Torque/Duty Cycle

ReadOnly

Multiplier:1

Unit: % Monitor point for the per-cent engine torque outputand the governor percentduty cycle output whenused with the HM ECM

PC 2.x, PC3.x

Offset: 0 Lower Limit: −125Size (bits):16

Upper Limit: 125

Sign: S

40276 CAN /CAN InputMessages

Post−Filter OilPressure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for thePost−Filter Oil Pressure

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 145

Sign: U

Page 51: Mapa de Registros de Pcc

44

Addr. ControlDescriptionAccessParameterName40277 CAN /

CAN InputMessages

Pre−Filter OilPressure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for the Pre−Filter Oil Pressure

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 145

Sign: U

40278 DSI / Dis-crete In-puts

ConfigurableInput #14Switch

ReadOnly

Configurable Input #14 input software state status.Gives software Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

40279 CAN /CAN InputMessages

Turbocharger1 Speed

ReadOnly

Multiplier:1

Unit: rpm Monitor point for theTurbocharger 1 Speed

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 257000

Sign: U

40280 CAN /CAN InputMessages

Turbocharger1 Speed

ReadOnly

Multiplier:1

Unit: rpm Monitor point for theTurbocharger 1 Speed

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 257000

Sign: U

40281 CAN /CAN InputMessages

Turbocharger2 Boost Pres-sure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for theTurbocharger 2 BoostPressure

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 1160

Sign: U

40282 CAN /CAN InputMessages

Water in FuelIndicator

ReadOnly

Water in Fuel Indication PC 2.x, PC3.x0: No

1: Yes

40283 CM / Con-trollerModes

ControllerMode

ReadOnly

The controller mode PC 2.x, PC3.x0: Off

1: Ready3: Starting4: Idle5: Rated6: Stop Normal7: Stop Emergency8: Factory Test9: Wait to Power Down

40285 CM / Con-trollerModes

Power DownMode Timer

ReadOnly

Multiplier:1

Unit: sec-onds

Timer to count down thetime before the controlgoes to sleep

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 600

Sign: U

Page 52: Mapa de Registros de Pcc

45

Addr. ControlDescriptionAccessParameterName40286 CM / Con-

trollerModes

Setup ModeTimer

ReadOnly

Multiplier:1

Unit: Sec-onds

Time spent in SetupMode.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U40287 CM / Con-

trollerModes

Tool Wake−upCommand

ReadOnly

The control output to the common wake−up line towake up other devices

PC 2.x, PC3.x

0: Inactive1: Active

40289 DR / Exer-ciseScheduler

Active Sched-ule

ReadOnly

Indicates the currently active scheduler program orexception.

PC 2.x, PC3.x

0: None1: Program 12: Program 23: Program 34: Program 45: Program 56: Program 67: Program 78: Program 89: Program 910: Program 1011: Program 1112: Program 1213: Exception 114: Exception 215: Exception 316: Exception 417: Exception 518: Exception 6

40290 DR / DataRecording

Controller OnTime

Read/Write

Multiplier:1

Unit: Sec-onds

Controller ON time inseconds. Upper limit is136 years.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967291

Sign: U40291 DR / Data

RecordingController OnTime

Read/Write

Multiplier:1

Unit: Sec-onds

Controller ON time inseconds. Upper limit is136 years.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967291

Sign: U

Page 53: Mapa de Registros de Pcc

46

Addr. ControlDescriptionAccessParameterName40298 DR / Data

RecordingRuns SinceReset

Read/Write

Multiplier:1

Unit: Number of runs since thelast reset. Upper limit is2^32 − 1.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967290

Sign: U

40299 DR / DataRecording

Runs SinceReset

Read/Write

Multiplier:1

Unit: Number of runs since thelast reset. Upper limit is2^32 − 1.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967290

Sign: U

40300 Modbus /Modbus

Remote StartSwitch (Mod-bus)

Read/Write

Modbus Remote Start PC 2.x, PC3.x0: Inactive

1: Active

40301 Modbus /Modbus

Fault Reset(Modbus)

Read/Write

Modbus fault reset. PC 2.x, PC3.x0: Inactive

1: Active

40320 DSI / Dis-crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40321 DSI / Dis-crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40322 DSI / Dis-crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 54: Mapa de Registros de Pcc

47

Addr. ControlDescriptionAccessParameterName40323 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40324 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40325 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40326 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40327 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 55: Mapa de Registros de Pcc

48

Addr. ControlDescriptionAccessParameterName40328 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40329 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40330 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40331 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40332 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 56: Mapa de Registros de Pcc

49

Addr. ControlDescriptionAccessParameterName40333 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40334 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40335 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40336 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40337 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 57: Mapa de Registros de Pcc

50

Addr. ControlDescriptionAccessParameterName40338 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40339 DSI / Dis-

crete In-puts

Start InhibitNo1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the operator panelwhen this fault becomesactive

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40340 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40341 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40342 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 58: Mapa de Registros de Pcc

51

Addr. ControlDescriptionAccessParameterName40343 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40344 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40345 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40346 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40347 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 59: Mapa de Registros de Pcc

52

Addr. ControlDescriptionAccessParameterName40348 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40349 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40350 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40351 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40352 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 60: Mapa de Registros de Pcc

53

Addr. ControlDescriptionAccessParameterName40353 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40354 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40355 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40356 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40357 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 61: Mapa de Registros de Pcc

54

Addr. ControlDescriptionAccessParameterName40358 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40359 DSI / Dis-

crete In-puts

Start InhibitNo2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40360 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40361 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40362 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 62: Mapa de Registros de Pcc

55

Addr. ControlDescriptionAccessParameterName40363 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40364 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40365 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40366 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40367 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 63: Mapa de Registros de Pcc

56

Addr. ControlDescriptionAccessParameterName40368 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40369 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40370 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40371 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40372 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 64: Mapa de Registros de Pcc

57

Addr. ControlDescriptionAccessParameterName40373 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40374 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40375 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40376 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40377 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 65: Mapa de Registros de Pcc

58

Addr. ControlDescriptionAccessParameterName40378 DSI / Dis-

crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40379 DSI / Dis-crete In-puts

Start InhibitNo3 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 20character string for useby the Operator panelwhen this fault becomesactive.

PC 3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40400 Modbus /Modbus

Fault StatusBitmap 1

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40401 Modbus /Modbus

Fault StatusBitmap 2

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40402 Modbus /Modbus

Fault StatusBitmap 3

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40403 Modbus /Modbus

Fault StatusBitmap 4

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40404 Modbus /Modbus

Fault StatusBitmap 5

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

Page 66: Mapa de Registros de Pcc

59

Addr. ControlDescriptionAccessParameterName40405 Modbus /

ModbusFault StatusBitmap 6

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40406 Modbus /Modbus

Fault StatusBitmap 7

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40407 Modbus /Modbus

Fault StatusBitmap 8

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40408 Modbus /Modbus

Fault StatusBitmap 9

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40409 Modbus /Modbus

Fault StatusBitmap 10

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40410 Modbus /Modbus

Fault StatusBitmap 11

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40411 Modbus /Modbus

Fault StatusBitmap 12

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40412 Modbus /Modbus

Fault StatusBitmap 13

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

Page 67: Mapa de Registros de Pcc

60

Addr. ControlDescriptionAccessParameterName40413 Modbus /

ModbusFault StatusBitmap 14

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40414 Modbus /Modbus

Fault StatusBitmap 15

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40415 Modbus /Modbus

Fault StatusBitmap 16

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40416 Modbus /Modbus

Fault StatusBitmap 17

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40417 Modbus /Modbus

Fault StatusBitmap 18

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40418 Modbus /Modbus

Fault StatusBitmap 19

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40419 Modbus /Modbus

Fault StatusBitmap 20

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40420 Modbus /Modbus

Fault StatusBitmap 21

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

Page 68: Mapa de Registros de Pcc

61

Addr. ControlDescriptionAccessParameterName40421 Modbus /

ModbusFault StatusBitmap 22

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40422 Modbus /Modbus

Fault StatusBitmap 23

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: S

40430 Modbus /Modbus

Event StatusBitmap 1

ReadOnly

Multiplier:1

Unit: 16 bit fault bitmap for Mo-dus interface.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

40431 Modbus /Modbus

Fault StatusGas Bitmap 1

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40432 Modbus /Modbus

Fault StatusGas Bitmap 2

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40433 Modbus /Modbus

Fault StatusGas Bitmap 3

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40434 Modbus /Modbus

Fault StatusGas Bitmap 4

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40435 Modbus /Modbus

Fault StatusGas Bitmap 5

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 69: Mapa de Registros de Pcc

62

Addr. ControlDescriptionAccessParameterName40436 Modbus /

ModbusFault StatusGas Bitmap 6

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40437 Modbus /Modbus

Fault StatusGas Bitmap 7

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40438 Modbus /Modbus

Fault StatusGas Bitmap 8

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40439 Modbus /Modbus

Fault StatusGas Bitmap 9

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40440 Modbus /Modbus

Fault StatusGas Bitmap10

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40441 Modbus /Modbus

Fault StatusGas Bitmap11

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40442 Modbus /Modbus

Fault StatusGas Bitmap12

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40443 Modbus /Modbus

Fault StatusGas Bitmap13

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 70: Mapa de Registros de Pcc

63

Addr. ControlDescriptionAccessParameterName40444 Modbus /

ModbusFault StatusGas Bitmap14

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40445 Modbus /Modbus

Fault StatusGas Bitmap15

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40446 Modbus /Modbus

Fault StatusGas Bitmap16

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40447 Modbus /Modbus

Fault StatusGas Bitmap17

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40448 Modbus /Modbus

Fault StatusGas Bitmap18

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40449 Modbus /Modbus

Fault StatusGas Bitmap19

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40450 Modbus /Modbus

Fault StatusGas Bitmap20

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40451 Modbus /Modbus

Fault StatusGas Bitmap21

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 71: Mapa de Registros de Pcc

64

Addr. ControlDescriptionAccessParameterName40452 Modbus /

ModbusFault StatusGas Bitmap22

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40453 Modbus /Modbus

Fault StatusGas Bitmap23

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40454 Modbus /Modbus

Fault StatusGas Bitmap24

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40455 Modbus /Modbus

Fault StatusGas Bitmap25

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40456 Modbus /Modbus

Fault StatusGas Bitmap26

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40457 Modbus /Modbus

Fault StatusGas Bitmap27

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40458 Modbus /Modbus

Fault StatusGas Bitmap28

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40459 Modbus /Modbus

Fault StatusGas Bitmap29

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 72: Mapa de Registros de Pcc

65

Addr. ControlDescriptionAccessParameterName40460 Modbus /

ModbusFault StatusGas Bitmap30

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40461 Modbus /Modbus

Fault StatusGas Bitmap31

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40462 Modbus /Modbus

Fault StatusGas Bitmap32

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40463 Modbus /Modbus

Fault StatusGas Bitmap33

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40464 Modbus /Modbus

Fault StatusGas Bitmap34

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40465 Modbus /Modbus

Fault StatusGas Bitmap35

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40466 Modbus /Modbus

Fault StatusGas Bitmap36

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40467 Modbus /Modbus

Fault StatusGas Bitmap37

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 73: Mapa de Registros de Pcc

66

Addr. ControlDescriptionAccessParameterName40468 Modbus /

ModbusFault StatusGas Bitmap38

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40469 Modbus /Modbus

Fault StatusGas Bitmap39

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40470 Modbus /Modbus

Fault StatusGas Bitmap40

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40471 Modbus /Modbus

Fault StatusGas Bitmap41

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40472 Modbus /Modbus

Fault StatusGas Bitmap42

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40473 Modbus /Modbus

Fault StatusGas Bitmap43

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40474 Modbus /Modbus

Fault StatusGas Bitmap44

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40475 Modbus /Modbus

Fault StatusGas Bitmap45

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 74: Mapa de Registros de Pcc

67

Addr. ControlDescriptionAccessParameterName40476 Modbus /

ModbusFault StatusGas Bitmap46

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40477 Modbus /Modbus

Fault StatusGas Bitmap47

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40478 Modbus /Modbus

Fault StatusGas Bitmap48

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40479 Modbus /Modbus

Fault StatusGas Bitmap49

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40480 Modbus /Modbus

Fault StatusGas Bitmap50

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40481 Modbus /Modbus

Fault StatusGas Bitmap51

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40482 Modbus /Modbus

Fault StatusGas Bitmap52

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40483 Modbus /Modbus

Fault StatusGas Bitmap53

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 75: Mapa de Registros de Pcc

68

Addr. ControlDescriptionAccessParameterName40484 Modbus /

ModbusFault StatusGas Bitmap54

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40485 Modbus /Modbus

Fault StatusGas Bitmap55

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40486 Modbus /Modbus

Fault StatusGas Bitmap56

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40487 Modbus /Modbus

Fault StatusGas Bitmap57

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40488 Modbus /Modbus

Fault StatusGas Bitmap58

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40489 Modbus /Modbus

Fault StatusGas Bitmap59

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40490 Modbus /Modbus

Fault StatusGas Bitmap60

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40491 Modbus /Modbus

Fault StatusGas Bitmap61

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 76: Mapa de Registros de Pcc

69

Addr. ControlDescriptionAccessParameterName40492 Modbus /

ModbusFault StatusGas Bitmap62

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40493 Modbus /Modbus

Fault StatusGas Bitmap63

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40494 Modbus /Modbus

Fault StatusGas Bitmap64

ReadOnly

Multiplier:1

Unit: 16 bit Gas fault bitmapfor Modus interface.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

40500 DSI / Dis-crete In-puts

Low FuelSwitch

ReadOnly

Low Fuel input software state status. Gives softwareInactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

40501 DSI / Dis-crete In-puts

Low Fuel/ConfigurableInput #6Switch

ReadOnly

This is the status of the Configurable Input #6. PC 2.x, PC3.x0: Inactive

1: Active

40502 DSI / Safety WireLoop

ReadOnly

0: Inactive PC 3.x1: Active

40503 DSI / Dis-crete In-puts

DifferentialFault Trip

ReadOnly

Differential fault trip monitor point. PC 3.x0: Inactive1: Active

40504 DSI / Dis-crete In-puts

Master FirstStart Input A

ReadOnly

This is the status of the Master First Start A input. PC 3.x0: Inactive1: Active

40505 DSI / Dis-crete In-puts

Fire Trip ReadOnly

Fire trip monitor point. PC 3.x0: Inactive1: Active

40506 DSI / Dis-crete In-puts

Master FirstStart Input BSwitch

ReadOnly

Masterless Load Demand Enable Switch functionoutput status. Gives software Inactive/Active state

PC 3.x

0: Inactive1: Active

40507 DSI / Dis-crete In-puts

MasterlessLoad DemandEnable Switch

ReadOnly

Masterless Load Demand Enable Switch functionoutput status. Gives software Inactive/Active state

PC 3.x

0: Inactive1: Active

40508 DSI / Dis-crete In-puts

PredictiveLoad EnableSwitch

ReadOnly

Predictive Load Enable Switch function output sta-tus. Gives software Inactive/Active state

PC 3.x

0: Inactive1: Active

Page 77: Mapa de Registros de Pcc

70

Addr. ControlDescriptionAccessParameterName40509 DSI / Dis-

crete In-puts

PTC ModeSwitch

ReadOnly

PTC Mode Switch function output status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

40510 DSI / Dis-crete In-puts

Extended Par-allel/Configur-able Input #32Switch

ReadOnly

This is the status of the Configurable Input #32. PC 3.x

0: Inactive

1: Active

40511 DSI / Dis-crete In-puts

Ramp Load/Unload Switch

ReadOnly

Ramp Load/Unload input software state status. PC 3.x0: Load1: Unload

40512 DSI / Dis-crete In-puts

Remote E−stop Switch

ReadOnly

Remote E−stop input software state status. Givessoftware Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

40513 DSI / Dis-crete In-puts

Remote StartSwitch

ReadOnly

Remote Start input software state status. Givessoftware Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

40514 DSI / Dis-crete In-puts

Retransfer In-hibit Switch

ReadOnly

Retransfer Inhibit input software state status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

40515 DSI / Dis-crete In-puts

Retransfer In-hibit/Configur-able Input #21Switch

ReadOnly

This is the status of the Configurable Input #21. PC 3.x

0: Inactive

1: Active

40516 DSI / Dis-crete In-puts

Rupture BasinSwitch

ReadOnly

Rupture Basin input software state status. Givessoftware Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

40517 DSI / Dis-crete In-puts

Rupture Ba-sin/Configur-able Input #12Switch

ReadOnly

This is the status of the Configurable Input #12. PC 2.x, PC3.x0: Inactive

1: Active

40518 DSI / Dis-crete In-puts

Speed DroopEnable Switch

ReadOnly

Monitors the Speed Droop Enable Switch function;Inactive or Active state.

PC 2.x, PC3.x

0: Inactive1: Active

40519 DSI / Dis-crete In-puts

Start TypeSwitch

ReadOnly

Start Type input software state status. Gives soft-ware Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

40520 DSI / Dis-crete In-puts

Sync EnableSwitch

ReadOnly

Sync Enable input software state status. Gives soft-ware Inactive/Active state

PC 3.x

0: Inactive1: Active

Page 78: Mapa de Registros de Pcc

71

Addr. ControlDescriptionAccessParameterName40521 DSI / Dis-

crete In-puts

Sync Enable/ConfigurableInput #30Switch

ReadOnly

This is the status of the Configurable Input #30. PC 3.x

0: Inactive

1: Active

40522 DSI / Dis-crete In-puts

Tool Wake−upSwitch

ReadOnly

Tool Wake−up input software state status. Givessoftware Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

40523 DSI / Dis-crete In-puts

Transfer In-hibit Switch

ReadOnly

Transfer Inhibit input software state status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

40524 DSI / Dis-crete In-puts

Transfer In-hibit/Configur-able Input #20Switch

ReadOnly

This is the status of the Configurable Input #20. PC 3.x

0: Inactive

1: Active

40525 DSI / Dis-crete In-puts

Utility CB In-hibit/Configur-able Input #25Switch

ReadOnly

This is the status of the Configurable Input #25. PC 3.x

0: Inactive

1: Active

40526 DSI / Dis-crete In-puts

Utility CB PosB/Configur-able Input #23Switch

ReadOnly

This is the status of the Configurable Input #23. PC 3.x

0: Inactive

1: Active

40527 DSI / Dis-crete In-puts

Utility CBTripped/Confi-gurable Input#24 Switch

ReadOnly

This is the status of the Configurable Input #24. PC 3.x

0: Inactive

1: Active

40528 DSI / Dis-crete In-puts

Utility SingleMode Verify/ConfigurableInput #29Switch

ReadOnly

This is the status of the Configurable Input #29. PC 3.x

0: Inactive

1: Active

40529 DSI / Dis-crete In-puts

Utility CB In-hibit Switch

ReadOnly

Utility CB Inhibit input software state status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

40530 DSI / Dis-crete In-puts

Utility CB PosA Switch

ReadOnly

Utility CB Pos A input software state status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

40531 DSI / Dis-crete In-puts

Utility CB PosB Switch

ReadOnly

Utility CB Pos B input software state status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

40532 DSI / Dis-crete In-puts

Utility CBTrippedSwitch

ReadOnly

Utility CB Tripped input software state status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

Page 79: Mapa de Registros de Pcc

72

Addr. ControlDescriptionAccessParameterName40533 DSI / Dis-

crete In-puts

Utility SingleMode VerifySwitch

ReadOnly

Utility Single Mode Verify input software state sta-tus. Gives software Inactive/Active state

PC 3.x

0: Inactive1: Active

40534 DSI / Dis-crete In-puts

Voltage DroopEnable Switch

ReadOnly

Voltage Droop Enable Switch function output sta-tus. Gives software Inactive/Active state.

PC 2.x, PC3.x

0: Inactive1: Active

40535 DSO / Dis-crete Out-puts

ConfigurableOutput #1Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40536 DSO / Dis-crete Out-puts

ConfigurableOutput #2Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40537 DSO / Dis-crete Out-puts

ConfigurableOutput #20Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active

40538 DSO / Dis-crete Out-puts

ConfigurableOutput #21Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active

40539 DSO / Dis-crete Out-puts

ConfigurableOutput #22Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active

40540 DSO / Dis-crete Out-puts

ConfigurableOutput #3Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40541 DSO / Dis-crete Out-puts

ConfigurableOutput #4Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40542 DSO / Dis-crete Out-puts

Delayed Off /ConfigurableOutput #10

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40543 DSO / Dis-crete Out-puts

Fuel ShutoffStatus

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40545 DSO / Dis-crete Out-puts

Genset CBOpen Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active

40546 DSO / Dis-crete Out-puts

Hold PowerOn Driver Sta-tus

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40547 DSO / Dis-crete Out-puts

KeyswitchStatus

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40548 DSO / Dis-crete Out-puts

KW/KVARLoad ShareRelay Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active

Page 80: Mapa de Registros de Pcc

73

Addr. ControlDescriptionAccessParameterName40549 DSO / Dis-

crete Out-puts

Load Dump /ConfigurableOutput #11Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40550 DSO / Dis-crete Out-puts

Local Status /ConfigurableOutput #7Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40551 DSO / Dis-crete Out-puts

Master FirstStart OutputStatus

ReadOnly

Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active

40552 DSO / Dis-crete Out-puts

Oil PrimingPump / Confi-gurable Out-put #6 Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40553 DSO / Dis-crete Out-puts

Ready ToLoad /Confi-gurable Out-put #5 Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40554 DSO / Dis-crete Out-puts

Run Relay #1Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40555 DSO / Dis-crete Out-puts

Run Relay #2Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40556 DSO / Dis-crete Out-puts

Speed/Volt-age BiasRelay Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active

40557 DSO / Dis-crete Out-puts

Starter Status ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40558 DSO / Dis-crete Out-puts

Tool Wake−upDriver Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40559 DSO / Dis-crete Out-puts

Utility CBClose Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 2.x, PC3.x0: Inactive

1: Active

40560 DSO / Dis-crete Out-puts

Utility CBOpen Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active

40561 EH / EventHandler

CommonAlarm FaultStatus

ReadOnly

The status of the Common Alarm Fault PC 2.x, PC3.x0: Inactive

1: Active

40562 EH / EventHandler

CommonShutdownCommand

ReadOnly

The status of the common shutdown command PC 2.x, PC3.x0: Inactive

1: Active

40563 EH / EventHandler

CommonShutdownEvent Status

ReadOnly

The status of the Common Shutdown Event PC 2.x, PC3.x0: Inactive

1: Active

Page 81: Mapa de Registros de Pcc

74

Addr. ControlDescriptionAccessParameterName40564 EH / Event

HandlerCommonShutdown w/CooldownCommand

ReadOnly

The status of the common shutdown w/Cooldowncommand

PC 3.x

0: Inactive1: Active

40565 EH / EventHandler

CommonWarningEvent Status

ReadOnly

The status of the Common Warning Event PC 2.x, PC3.x0: Inactive

1: Active40566 EH / Event

HandlerDelayed Shut-down Flag

ReadOnly

Monitor point for the Delayed shutdown flag. PC 2.x, PC3.x0: Inactive

1: Active40567 EH / Event

HandlerDelayed Shut-down Timer

ReadOnly

Multiplier:0.1

Unit: sec-onds

Monitor point for theDelayed shutdown timer.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 3

Sign: U40568 EH / Event

HandlerDerate Re-quest

ReadOnly

Multiplier:1

Unit: % The requested % deratefrom the derate requestlogic

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 100

Sign: U40569 EH / Event

HandlerFault Detec-tion Reset

ReadOnly

The status of the Fault Detection Reset logic PC 2.x, PC3.x0: Inactive

1: Active40570 EH / Event

HandlerFault ResetCommand

ReadOnly

One shot due to fault reset switch being active. PC 2.x, PC3.x0: Inactive

1: Active40571 EH / Event

HandlerRemote Shut-down FaultReset Signal

ReadOnly

Becomes active when a remote fault reset signal hasbeen initiated.

PC 2.x, PC3.x

0: Inactive1: Active

40572 EH / EventHandler

ShutdownFault Reset

ReadOnly

The status of the Shutdown Fault reset logic. PC 2.x, PC3.x0: Inactive

1: Active40573 EH / Event

HandlerBattle ShortFlag

ReadOnly

Monitor point indicating the enabled/disabled statusof the battle short function

PC 2.x, PC3.x

0: Not Auto1: Auto

40574 GC / Start/Stop Con-trol

Auto Com-mand

ReadOnly

The output of the Auto Command OR logic PC 2.x, PC3.x0: Not Auto

1: Auto

Page 82: Mapa de Registros de Pcc

75

Addr. ControlDescriptionAccessParameterName40575 GC / Start/

Stop Con-trol

Auto Com-mand Inputs

ReadOnly

Multiplier:1

Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

40576 GC / Auto-matic Volt-age Regu-lator

AVR Regula-tion Mode

ReadOnly

The operational mode of the AVR as a voltage or acurrent regulator

PC 2.x, PC3.x

0: Voltage1: Current

40577 GC /SpeedReference

Base Fre-quency

ReadOnly

Multiplier:0.001

Unit: Hz Provides a point to moni-tor the base frequency

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40578 GC /SpeedReference

Base Fre-quency

ReadOnly

Multiplier:0.001

Unit: Hz Provides a point to moni-tor the base frequency

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

40579 GC /ChargingAlternatorProtection

BatteryChargingFault Integra-tor

ReadOnly

Multiplier:0.1

Unit: sec-onds

Time spent while thecharger is sensed asfailed

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 300

Sign: U

40581 GC / Con-trolledShutdownControl

ControlledShutdownStatus

ReadOnly

Indicates status of the controlled shutdown logic PC 3.x0: Inactive1: Pending2: Shutdown

40582 GC / Pre-lube

Crank Al-lowed

ReadOnly

Monitor Point indicates if Cranking is Allowed by thePrelube State Machine

PC 2.x, PC3.x

0: False1: True

40583 GC /CrankingControl

Dead BatteryPreventionCounter

ReadOnly

Multiplier:1

Unit: Tracks the number ofcrank attempts in order tolimit the attempts whenthe battery is so low thatthe control resets

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 250

Sign: U

Page 83: Mapa de Registros de Pcc

76

Addr. ControlDescriptionAccessParameterName40584 GC / Out-

putsDelayed OffCommand

ReadOnly

The status of the delayed run command off logic. PC 2.x, PC3.x0: Inactive

1: Active

40585 GC / Start/Stop Con-trol

EmergencyRemote Start

ReadOnly

The output of the Emergency Remote Start logic PC 2.x, PC3.x0: Stop

1: Start

40586 GC / Auto-matic Volt-age Regu-lator

ExcitationState

ReadOnly

Shows the enable status of the excitation enabled =regulator on.

PC 2.x, PC3.x

0: Disabled1: Enabled

40587 GC / Start/Stop Con-trol

ExerciseCommand

ReadOnly

The output of the Exercise Command OR logic PC 2.x, PC3.x0: Inactive

1: Active

40588 GC / Start/Stop Con-trol

ExerciseCommand In-puts

ReadOnly

Multiplier:1

Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 250

Sign: U

40589 GC / Start/Stop Con-trol

Exercise TimeRemaining

ReadOnly

Multiplier:0.1

Unit: hours Time remaining until ex-ercise stop sequence be-gins

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 25

Sign: U

40590 GC / Start/Stop Con-trol

Extended Par-allel SwitchCommand

ReadOnly

The output of the Extended Parallel Switch Com-mand OR logic

PC 3.x

0: Stop1: Start

40591 GC / Start/Stop Con-trol

Extended Par-allel SwitchCommand In-puts

ReadOnly

Multiplier:1

Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

40592 EH / EventHandler

Battle ShortCommand

ReadOnly

Indicates status of battle short inputs PC 2.x, PC3.x0: Inactive

1: Active

40593 EH / EventHandler

ShutdownFault Override

ReadOnly

Indicates whether or not the genset will ignore non−critical shutdown faults

PC 2.x, PC3.x

0: Inactive1: Active

Page 84: Mapa de Registros de Pcc

77

Addr. ControlDescriptionAccessParameterName40595 GC /

SpeedReference

Final Fre-quency Refer-ence

ReadOnly

Multiplier:0.001

Unit: Hz The frequency scaledversion of the final speedreference

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 100

Sign: U

40596 GC /SpeedReference

Final Fre-quency Refer-ence

ReadOnly

Multiplier:0.001

Unit: Hz The frequency scaledversion of the final speedreference

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 100

Sign: U

40598 GC / Out-puts

Fuel ShutoffCommand

ReadOnly

The result of the FSO driver output command logic PC 2.x, PC3.x0: Inactive

1: Active

40599 GC / Start/Stop Con-trol

Genset RunCommand

ReadOnly

Genset run / stop states PC 2.x, PC3.x0: Emergency Stop

1: Stop2: Load Demand Stop3: Run

40600 DSI / Dis-crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

40601 DSI / Dis-crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

40602 DSI / Dis-crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 85: Mapa de Registros de Pcc

78

Addr. ControlDescriptionAccessParameterName40603 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40604 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40605 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40606 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40607 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 86: Mapa de Registros de Pcc

79

Addr. ControlDescriptionAccessParameterName40608 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40609 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40610 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40611 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40612 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 87: Mapa de Registros de Pcc

80

Addr. ControlDescriptionAccessParameterName40613 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40614 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40615 DSI / Dis-

crete In-puts

ConfigurableInput #1 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40620 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40621 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 88: Mapa de Registros de Pcc

81

Addr. ControlDescriptionAccessParameterName40622 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40623 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40624 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40625 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40626 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 89: Mapa de Registros de Pcc

82

Addr. ControlDescriptionAccessParameterName40627 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40628 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40629 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40630 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40631 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 90: Mapa de Registros de Pcc

83

Addr. ControlDescriptionAccessParameterName40632 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40633 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40634 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40635 DSI / Dis-

crete In-puts

ConfigurableInput #2 FaultText

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40640 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 91: Mapa de Registros de Pcc

84

Addr. ControlDescriptionAccessParameterName40641 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40642 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40643 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40644 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40645 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 92: Mapa de Registros de Pcc

85

Addr. ControlDescriptionAccessParameterName40646 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40647 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40648 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40649 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40650 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 93: Mapa de Registros de Pcc

86

Addr. ControlDescriptionAccessParameterName40651 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40652 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40653 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40654 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40655 DSI / Dis-

crete In-puts

ConfigurableInput #13Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 94: Mapa de Registros de Pcc

87

Addr. ControlDescriptionAccessParameterName40660 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40661 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40662 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40663 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40664 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 95: Mapa de Registros de Pcc

88

Addr. ControlDescriptionAccessParameterName40665 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40666 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40667 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40668 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40669 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 96: Mapa de Registros de Pcc

89

Addr. ControlDescriptionAccessParameterName40670 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40671 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40672 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40673 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C40674 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 97: Mapa de Registros de Pcc

90

Addr. ControlDescriptionAccessParameterName40675 DSI / Dis-

crete In-puts

ConfigurableInput #14Fault Text

Read/Write

Multiplier:1

Unit: Trim to define the 16character string for useby the Operator panelwhen this fault becomesactive.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

40800 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40801 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40802 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40803 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40804 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 98: Mapa de Registros de Pcc

91

Addr. ControlDescriptionAccessParameterName40805 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40806 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40807 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40808 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40809 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40810 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 99: Mapa de Registros de Pcc

92

Addr. ControlDescriptionAccessParameterName40811 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40812 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40813 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40814 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40815 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40816 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 100: Mapa de Registros de Pcc

93

Addr. ControlDescriptionAccessParameterName40817 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40818 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40819 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40820 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40821 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40822 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 101: Mapa de Registros de Pcc

94

Addr. ControlDescriptionAccessParameterName40823 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40824 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40825 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40826 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40827 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40828 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 102: Mapa de Registros de Pcc

95

Addr. ControlDescriptionAccessParameterName40829 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40830 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40831 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40832 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40833 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40834 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 103: Mapa de Registros de Pcc

96

Addr. ControlDescriptionAccessParameterName40835 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40836 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40837 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40838 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40839 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40840 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 104: Mapa de Registros de Pcc

97

Addr. ControlDescriptionAccessParameterName40841 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40842 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40843 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40844 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40845 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40846 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 105: Mapa de Registros de Pcc

98

Addr. ControlDescriptionAccessParameterName40847 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40848 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40849 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40850 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40851 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40852 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 106: Mapa de Registros de Pcc

99

Addr. ControlDescriptionAccessParameterName40853 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40854 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40855 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40856 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40857 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40858 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 107: Mapa de Registros de Pcc

100

Addr. ControlDescriptionAccessParameterName40859 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40860 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40861 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40862 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40863 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40864 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 108: Mapa de Registros de Pcc

101

Addr. ControlDescriptionAccessParameterName40865 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40866 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40867 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40868 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40869 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40870 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 109: Mapa de Registros de Pcc

102

Addr. ControlDescriptionAccessParameterName40871 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40872 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40873 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40874 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40875 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40876 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 110: Mapa de Registros de Pcc

103

Addr. ControlDescriptionAccessParameterName40877 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40878 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40879 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40880 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40881 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40882 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 111: Mapa de Registros de Pcc

104

Addr. ControlDescriptionAccessParameterName40883 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40884 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40885 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40886 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40887 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40888 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 112: Mapa de Registros de Pcc

105

Addr. ControlDescriptionAccessParameterName40889 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40890 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40891 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40892 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40893 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40894 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 113: Mapa de Registros de Pcc

106

Addr. ControlDescriptionAccessParameterName40895 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40896 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40897 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40898 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40899 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40900 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 114: Mapa de Registros de Pcc

107

Addr. ControlDescriptionAccessParameterName40901 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40902 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40903 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40904 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40905 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40906 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 115: Mapa de Registros de Pcc

108

Addr. ControlDescriptionAccessParameterName40907 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40908 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40909 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40910 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40911 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40912 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 116: Mapa de Registros de Pcc

109

Addr. ControlDescriptionAccessParameterName40913 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40914 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40915 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40916 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40917 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40918 PCCNet /I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 117: Mapa de Registros de Pcc

110

Addr. ControlDescriptionAccessParameterName40919 PCCNet /

I/O Module0 Exp.Board

Aux102 0Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40920 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40921 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40922 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40923 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40924 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 118: Mapa de Registros de Pcc

111

Addr. ControlDescriptionAccessParameterName40925 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40926 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40927 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40928 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40929 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40930 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 119: Mapa de Registros de Pcc

112

Addr. ControlDescriptionAccessParameterName40931 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40932 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40933 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40934 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40935 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40936 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 120: Mapa de Registros de Pcc

113

Addr. ControlDescriptionAccessParameterName40937 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40938 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40939 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 9 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40940 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40941 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40942 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 121: Mapa de Registros de Pcc

114

Addr. ControlDescriptionAccessParameterName40943 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40944 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40945 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40946 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40947 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40948 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 122: Mapa de Registros de Pcc

115

Addr. ControlDescriptionAccessParameterName40949 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40950 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40951 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40952 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40953 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40954 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 123: Mapa de Registros de Pcc

116

Addr. ControlDescriptionAccessParameterName40955 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40956 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40957 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40958 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40959 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 10 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40960 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 124: Mapa de Registros de Pcc

117

Addr. ControlDescriptionAccessParameterName40961 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40962 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40963 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40964 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40965 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40966 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 125: Mapa de Registros de Pcc

118

Addr. ControlDescriptionAccessParameterName40967 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40968 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40969 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40970 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40971 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40972 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 126: Mapa de Registros de Pcc

119

Addr. ControlDescriptionAccessParameterName40973 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40974 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40975 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40976 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40977 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40978 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 127: Mapa de Registros de Pcc

120

Addr. ControlDescriptionAccessParameterName40979 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 11 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40980 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40981 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40982 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40983 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40984 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 128: Mapa de Registros de Pcc

121

Addr. ControlDescriptionAccessParameterName40985 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40986 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40987 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40988 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40989 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40990 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 129: Mapa de Registros de Pcc

122

Addr. ControlDescriptionAccessParameterName40991 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40992 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40993 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40994 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40995 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

40996 PCCNet /I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 130: Mapa de Registros de Pcc

123

Addr. ControlDescriptionAccessParameterName40997 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40998 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C40999 PCCNet /

I/O Module1 Exp.Board

Aux102 1Fault 12 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C43000 ACM /

GensetCurrentand Power− %

Genset % Ap-plication L1Current

ReadOnly

Multiplier:0.1

Unit: % Monitors the genset ap-plication L1 current per-centage output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43001 ACM /

GensetCurrentand Power− %

Genset % Ap-plication L2Current

ReadOnly

Multiplier:0.1

Unit: % Monitors the genset ap-plication L2 current per-centage output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43002 ACM /

GensetCurrentand Power− %

Genset % Ap-plication L1kVA

ReadOnly

Multiplier:0.1

Unit: % Monitors the genset ap-plication L1 KVA percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 131: Mapa de Registros de Pcc

124

Addr. ControlDescriptionAccessParameterName43003 ACM /

GensetCurrentand Power− %

Genset % Ap-plication L3Current

ReadOnly

Multiplier:0.1

Unit: % Monitors the genset ap-plication L3 current per-centage output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43004 ACM /GensetCurrentand Power− %

Genset % Ap-plication L2kVA

ReadOnly

Multiplier:0.1

Unit: % Monitors the genset ap-plication L2 KVA percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43005 ACM /GensetCurrentand Power− %

Genset % Ap-plication L3kVA

ReadOnly

Multiplier:0.1

Unit: % Monitors the genset ap-plication L3 KVA percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43006 ACM /GensetCurrentand Power− %

Genset % Ap-plication L1kW

ReadOnly

Multiplier:0.1

Unit: % Monitors the genset ap-plication L1 KW percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43007 ACM /GensetCurrentand Power− %

Genset % Ap-plication L2kW

ReadOnly

Multiplier:0.1

Unit: % Monitors the genset ap-plication L2 KW percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43008 ACM /GensetCurrentand Power− %

Genset % Ap-plication L3kW

ReadOnly

Multiplier:0.1

Unit: % Monitors the genset ap-plication L3 KW percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43009 ACM /GensetCurrentand Power− %

Genset % Ap-plication TotalkVA

ReadOnly

Multiplier:0.1

Unit: % Monitors the total gensetapplication KVA percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 132: Mapa de Registros de Pcc

125

Addr. ControlDescriptionAccessParameterName43010 ACM /

GensetCurrentand Power− %

Genset % Ap-plication TotalkW

ReadOnly

Multiplier:0.1

Unit: % Monitors the total gensetapplication KW percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43011 ACM /GensetCurrentand Power− %

Genset %Standby L1kVA

ReadOnly

Multiplier:0.1

Unit: % Monitors the gensetstandby L1 KVA percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43012 ACM /GensetCurrentand Power− %

Genset %Standby L3kVA

ReadOnly

Multiplier:0.1

Unit: % Monitors the gensetstandby L3 KVA percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43013 ACM /GensetCurrentand Power− %

Genset %Standby L2kVA

ReadOnly

Multiplier:0.1

Unit: % Monitors the gensetstandby L2 KVA percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43014 ACM /GensetCurrentand Power− %

Genset %Standby L1kW

ReadOnly

Multiplier:0.1

Unit: % Monitors the gensetstandby L1 KW percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43015 ACM /GensetCurrentand Power− %

Genset %Standby L2kW

ReadOnly

Multiplier:0.1

Unit: % Monitors the gensetstandby L2 KW percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43016 ACM /GensetCurrentand Power− %

Genset %Standby L3kW

ReadOnly

Multiplier:0.1

Unit: % Monitors the gensetstandby L3 KW percent-age output.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 133: Mapa de Registros de Pcc

126

Addr. ControlDescriptionAccessParameterName43017 ACM /

GensetCurrentand Power− %

Genset %Standby TotalkVA

ReadOnly

Multiplier:0.1

Unit: % Monitors the total gensetstandby KVA percentageoutput.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43018 ACM /

GensetRatingsScalars

Genset Ap-plication kVArating

ReadOnly

Multiplier:0.1

Unit: kVA The genset KVA rating. PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43019 ACM /

GensetRatingsScalars

Genset Ap-plication kWrating

ReadOnly

Multiplier:0.1

Unit: kW The genset KW rating. PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43020 ACM /

GensetRatingsScalars

Genset Ap-plication Nom-inal Current

ReadOnly

Multiplier:1

Unit: Amps The value of the gensetapplication nominal cur-rent. Displayed as ”Gen-set Application RatedCurrent” in HMI

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43021 ACM /

VoltageGenset Aver-age Voltage%

ReadOnly

Multiplier:0.01

Unit: % Genset average voltagepercentage.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43030 ACM /

PowerGenset L1Power Factor

ReadOnly

Multiplier:0.01

Unit: PF Genset L1 power factor PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: S43031 ACM /

PhaseGenset L1L2Phase Differ-ence

ReadOnly

Multiplier:0.01

Unit: De-grees

Genset L1L2 voltagephase angle

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 134: Mapa de Registros de Pcc

127

Addr. ControlDescriptionAccessParameterName43032 ACM /

VoltageGenset L1L2Voltage%

ReadOnly

Multiplier:0.01

Unit: % Genset L1L2 voltage% PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43033 ACM /Voltage

Genset L1NVoltage%

ReadOnly

Multiplier:0.01

Unit: % Genset L1N voltage% PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43044 ACM /Power

Genset L2Power Factor

ReadOnly

Multiplier:0.01

Unit: PF Genset L2 power factor PC 2.x, PC3.x

Offset: 0 Lower Limit: −1.28Size (bits):8

Upper Limit: 1.27

Sign: S

43045 ACM /Phase

Genset L2L3Phase Differ-ence

ReadOnly

Multiplier:0.01

Unit: De-grees

Genset L2L3 voltagephase angle

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 655.3

Sign: U

43046 ACM /Voltage

Genset L2L3Voltage%

ReadOnly

Multiplier:0.01

Unit: % Genset L2L3 voltage% PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43047 ACM /Voltage

Genset L2NVoltage%

ReadOnly

Multiplier:0.01

Unit: % Genset L2N voltage% PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 655.3

Sign: U

43058 ACM /Power

Genset L3Power Factor

ReadOnly

Multiplier:0.01

Unit: PF Genset L3 power factor PC 2.x, PC3.x

Offset: 0 Lower Limit: −1.28Size (bits):8

Upper Limit: 1.22

Sign: S

43059 ACM /Phase

Genset L3L1Phase Differ-ence

ReadOnly

Multiplier:0.01

Unit: De-grees

Genset L3L1 voltagephase angle

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 655.3

Sign: U

Page 135: Mapa de Registros de Pcc

128

Addr. ControlDescriptionAccessParameterName43060 ACM /

VoltageGenset L3L1Voltage%

ReadOnly

Multiplier:0.01

Unit: % Genset L3L1 voltage% PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 655.3

Sign: U43061 ACM /

VoltageGenset L3NVoltage%

ReadOnly

Multiplier:0.01

Unit: % Genset L3N voltage% PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43062 ACM /

GensetRatingsScalars

GensetStandby kVArating

ReadOnly

Multiplier:0.1

Unit: kVA KVA rating for the gensetin Standby configuration.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43063 ACM /

GensetRatingsScalars

GensetStandby kWrating

ReadOnly

Multiplier:0.1

Unit: kW KW rating for the gensetin Standby configuration.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43064 ACM /

GensetRatingsScalars

GensetStandby Nom-inal Current

ReadOnly

Multiplier:1

Unit: Amps The value of the gensetstandby nominal current.Displayed as ”GensetStandby Rated Current”in HMI

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43065 ACM / En-

ergyGenset TotalkVAh

ReadOnly

Multiplier:1

Unit: kVAh Genset total kVAh accu-mulation

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U43066 ACM / En-

ergyGenset TotalkVAh

ReadOnly

Multiplier:1

Unit: kVAh Genset total kVAh accu-mulation

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 136: Mapa de Registros de Pcc

129

Addr. ControlDescriptionAccessParameterName43067 ACM /

GensetCurrentand Power− %

Genset TotalkVARs perStandby kVA

ReadOnly

Multiplier:0.01

Unit: % Total KVAR’s per StandbyKVA.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43100 ACM /Voltage

Genset BusAverage Volt-age%

ReadOnly

Multiplier:0.01

Unit: % Genset Bus average volt-age%

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43111 ACM /Power

Genset BusL1 PowerFactor

ReadOnly

Multiplier:0.01

Unit: PF Genset Bus L1 powerfactor

PC 3.x

Offset: 0 Lower Limit: −1.28Size (bits):8

Upper Limit: 1.22

Sign: S

43112 ACM /Phase

Genset BusL1L2 PhaseDifference

ReadOnly

Multiplier:0.01

Unit: De-grees

Genset bus L1L2 voltagephase angle

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43113 ACM /Voltage

Genset BusL1L2 Volt-age%

ReadOnly

Multiplier:0.01

Unit: % Genset Bus L1L2 volt-age%

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43114 ACM /Voltage

Genset BusL1N Voltage%

ReadOnly

Multiplier:0.01

Unit: % Genset Bus L1N volt-age%

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43125 ACM /Power

Genset BusL2 PowerFactor

ReadOnly

Multiplier:0.01

Unit: PF Genset Bus L2 powerfactor

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: S

43126 ACM /Phase

Genset BusL2L3 PhaseDifference

ReadOnly

Multiplier:0.01

Unit: De-grees

Genset bus L2L3 voltagephase angle

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 137: Mapa de Registros de Pcc

130

Addr. ControlDescriptionAccessParameterName43127 ACM /

VoltageGenset BusL2L3 Volt-age%

ReadOnly

Multiplier:0.01

Unit: % Genset Bus L2L3 volt-age%

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43128 ACM /Voltage

Genset BusL2N Voltage%

ReadOnly

Multiplier:0.01

Unit: % Genset Bus L2N volt-age%

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43139 ACM /Power

Genset BusL3 PowerFactor

ReadOnly

Multiplier:0.01

Unit: PF Genset Bus L3 powerfactor

PC 3.x

Offset: 0 Lower Limit: −1.28Size (bits):8

Upper Limit: 1.22

Sign: S

43140 ACM /Phase

Genset BusL3L1 PhaseDifference

ReadOnly

Multiplier:0.01

Unit: De-grees

Genset bus L3L1 voltagephase angle

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43141 ACM /Voltage

Genset BusL3L1 Volt-age%

ReadOnly

Multiplier:0.01

Unit: % Genset Bus L3L1 volt-age%

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43142 ACM /Voltage

Genset BusL3N Voltage%

ReadOnly

Multiplier:0.01

Unit: % Genset Bus L3N volt-age%

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43143 ACM / En-ergy

Genset BusTotal kVAh

ReadOnly

Multiplier:1

Unit: kVAh Genset bus total kVAhaccumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

43144 ACM / En-ergy

Genset BusTotal kVAh

ReadOnly

Multiplier:1

Unit: kVAh Genset bus total kVAhaccumulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 138: Mapa de Registros de Pcc

131

Addr. ControlDescriptionAccessParameterName43145 ACM /

PhaseSync PhaseDifference

ReadOnly

Multiplier:0.01

Unit: deg Other meter to gensetmeter L1 voltage phaseangle

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43146 ACM / Ap-plicationConfigura-tion

ParallelingApplication

Read/Write

Determines what the function of the Other Meter is. PC 3.x0: None1: Utility2: Genset Bus

43147 ACM /Power

System TotalkVA

ReadOnly

Multiplier:1

Unit: kVA Sum of genset bus andutility bus kVA

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43148 ACM /Power

System TotalkVAR

ReadOnly

Multiplier:1

Unit: kVAR Sum of genset bus andutility bus kVAR

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43149 ACM /Power

System TotalkW

ReadOnly

Multiplier:1

Unit: kW Sum of genset bus andutility bus kW

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43150 ACM /Power

System TotalPower Factor

ReadOnly

Multiplier:0.01

Unit: PF System total power factor(totalized value of utilitybus plus genset bus)

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: S

43151 ACM /Voltage

Utility AverageVoltage%

ReadOnly

Multiplier:0.01

Unit: % Utility average voltage% PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43162 ACM /Power

Utility L1 Pow-er Factor

ReadOnly

Multiplier:0.01

Unit: PF Utility L1 power factor PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: S

Page 139: Mapa de Registros de Pcc

132

Addr. ControlDescriptionAccessParameterName43163 ACM /

PhaseUtility L1L2Phase Differ-ence

ReadOnly

Multiplier:0.01

Unit: De-grees

Utility L1L2 voltagephase angle

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43164 ACM /Voltage

Utility L1L2Voltage%

ReadOnly

Multiplier:0.01

Unit: % Utility L1L2 voltage% PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43165 ACM /Voltage

Utility L1NVoltage%

ReadOnly

Multiplier:0.01

Unit: % Utility L1N voltage% PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43176 ACM /Power

Utility L2 Pow-er Factor

ReadOnly

Multiplier:0.01

Unit: PF Utility L2 power factor PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: S

43177 ACM /Phase

Utility L2L3Phase Differ-ence

ReadOnly

Multiplier:0.01

Unit: De-grees

Utility L2L3 voltagephase angle

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43178 ACM /Voltage

Utility L2L3Voltage%

ReadOnly

Multiplier:0.01

Unit: % Utility L2L3 voltage% PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43179 ACM /Voltage

Utility L2NVoltage%

ReadOnly

Multiplier:0.01

Unit: % Utility L2N voltage% PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43190 ACM /Power

Utility L3 Pow-er Factor

ReadOnly

Multiplier:0.01

Unit: PF Utility L3 power factor PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: S

Page 140: Mapa de Registros de Pcc

133

Addr. ControlDescriptionAccessParameterName43191 ACM /

PhaseUtility L3L1Phase Differ-ence

ReadOnly

Multiplier:0.01

Unit: De-grees

Utility L3L1 voltagephase angle

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43192 ACM /Voltage

Utility L3L1Voltage%

ReadOnly

Multiplier:0.01

Unit: % Utility L3L1 voltage% PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43193 ACM /Voltage

Utility L3NVoltage%

ReadOnly

Multiplier:0.01

Unit: % Utility L3N voltage% PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43194 ACM / En-ergy

Utility TotalkVAh

ReadOnly

Multiplier:1

Unit: kVAh Utility total kVAh accu-mulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

43195 ACM / En-ergy

Utility TotalkVAh

ReadOnly

Multiplier:1

Unit: kVAh Utility total kVAh accu-mulation

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

43200 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43201 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43202 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 141: Mapa de Registros de Pcc

134

Addr. ControlDescriptionAccessParameterName43203 DR / Data

RecordingGenset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43204 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43205 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43206 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43207 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43208 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43209 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43210 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 142: Mapa de Registros de Pcc

135

Addr. ControlDescriptionAccessParameterName43211 DR / Data

RecordingGenset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43212 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43213 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43214 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43215 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43216 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43217 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43218 DR / DataRecording

Genset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 143: Mapa de Registros de Pcc

136

Addr. ControlDescriptionAccessParameterName43219 DR / Data

RecordingGenset ModelNumber

Read/Write

Multiplier:1

Unit: Number identifying themodel of this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43220 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43221 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43222 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43223 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43224 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43225 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43226 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 144: Mapa de Registros de Pcc

137

Addr. ControlDescriptionAccessParameterName43227 DR / Data

RecordingGenset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43228 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43229 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43230 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43231 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43232 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43233 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43234 DR / DataRecording

Genset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 145: Mapa de Registros de Pcc

138

Addr. ControlDescriptionAccessParameterName43235 DR / Data

RecordingGenset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C43236 DR / Data

RecordingGenset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C43237 DR / Data

RecordingGenset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C43238 DR / Data

RecordingGenset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C43239 DR / Data

RecordingGenset SerialNumber

Read/Write

Multiplier:1

Unit: Serial number of identify-ing this genset.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C43240 DR / Data

RecordingAlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C43241 DR / Data

RecordingAlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 146: Mapa de Registros de Pcc

139

Addr. ControlDescriptionAccessParameterName43242 DR / Data

RecordingAlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43243 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43244 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43245 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43246 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43247 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43248 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 147: Mapa de Registros de Pcc

140

Addr. ControlDescriptionAccessParameterName43249 DR / Data

RecordingAlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43250 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43251 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43252 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43253 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43254 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43255 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 148: Mapa de Registros de Pcc

141

Addr. ControlDescriptionAccessParameterName43256 DR / Data

RecordingAlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43257 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43258 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43259 DR / DataRecording

AlternatorModel Num-ber

Read/Write

Multiplier:1

Unit: Number identifying thisgensets alternator modelnumber.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43260 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43261 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43262 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 149: Mapa de Registros de Pcc

142

Addr. ControlDescriptionAccessParameterName43263 DR / Data

RecordingAlternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43264 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43265 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43266 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43267 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43268 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43269 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 150: Mapa de Registros de Pcc

143

Addr. ControlDescriptionAccessParameterName43270 DR / Data

RecordingAlternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43271 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43272 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43273 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43274 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43275 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43276 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 151: Mapa de Registros de Pcc

144

Addr. ControlDescriptionAccessParameterName43277 DR / Data

RecordingAlternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43278 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43279 DR / DataRecording

Alternator Se-rial Number

Read/Write

Multiplier:1

Unit: Unique number identify-ing this gensets alterna-tor serial number.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43280 DSI / Dis-crete In-puts

Coolant LevelSwitch

ReadOnly

Coolant Level input software state status. Gives soft-ware Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43281 DSI / Dis-crete In-puts

Coolant Level/ConfigurableInput #5Switch

ReadOnly

This is the status of the Configurable Input #5. PC 2.x, PC3.x0: Inactive

1: Active

43283 DSI / Dis-crete In-puts

Fault ResetSwitch

ReadOnly

Fault Reset input software state status. Gives soft-ware Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43284 DSI / Dis-crete In-puts

Fault Reset/ConfigurableInput #10Switch

ReadOnly

This is the status of the Configurable Input #10. PC 2.x, PC3.x0: Inactive

1: Active

43285 DSI / Dis-crete In-puts

Genset CB In-hibit/Configur-able Input #28Switch

ReadOnly

This is the status of the Configurable Input #28. PC 3.x

0: Inactive

1: Active

43286 DSI / Dis-crete In-puts

Genset CBPos B/Confi-gurable Input#26 Switch

ReadOnly

This is the status of the Configurable Input #26. PC 3.x

0: Inactive

1: Active

43287 DSI / Dis-crete In-puts

Genset CBTripped/Confi-gurable Input#27 Switch

ReadOnly

This is the status of the Configurable Input #27. PC 3.x

0: Inactive

1: Active

Page 152: Mapa de Registros de Pcc

145

Addr. ControlDescriptionAccessParameterName43288 DSI / Dis-

crete In-puts

Genset CB In-hibit Switch

ReadOnly

Genset CB Inhibit input software state status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

43289 DSI / Dis-crete In-puts

Genset CBPos A Switch

ReadOnly

Genset CB Pos A input software state status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

43290 DSI / Dis-crete In-puts

Genset CBPos B Switch

ReadOnly

Genset CB Pos B input software state status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

43291 DSI / Dis-crete In-puts

Genset CBTrippedSwitch

ReadOnly

Genset CB Tripped input software state status. Givessoftware Inactive/Active state

PC 3.x

0: Inactive1: Active

43292 DSI / Dis-crete In-puts

Ground FaultSwitch

ReadOnly

Ground Fault Switch function output status. Givessoftware Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43293 DSI / Dis-crete In-puts

High Alt TempSwitch

ReadOnly

High Alt Temp Switch function output status. Givessoftware Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43295 DSI / Dis-crete In-puts

Load DemandStop/Confi-gurable Input#31 Switch

ReadOnly

This is the status of the Configurable Input #31. PC 3.x

0: Inactive

1: Active

43296 DSI / Dis-crete In-puts

Local E−stopSwitch

ReadOnly

Monitors the E−Stop switch. PC 2.x, PC3.x0: Inactive

1: Active

43297 DSI / Dis-crete In-puts

Low Coolant#2 Switch

ReadOnly

Low Coolant #2 Switch function output status. Givessoftware Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43298 DSI / Dis-crete In-puts

Low Fuel InDay TankSwitch

ReadOnly

Low Fuel In Day Tank Switch function output status.Gives software Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43299 DSI / Dis-crete In-puts

Low Fuel InDay TankSwitch

ReadOnly

Low Fuel In Day Tank Switch function output status.Gives software Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43300 ACM / Ap-plicationConfigura-tion

Genset BusDelta/WyeConnection

Read/Write

Delta or Wye for Utility connection PC 3.x

0: Delta

1: Wye

Page 153: Mapa de Registros de Pcc

146

Addr. ControlDescriptionAccessParameterName43301 ACM /

VoltageGenset BusNominal Volt-age

Read/Write

Multiplier:1

Unit: Vac Genset Bus nominal volt-age

PC 3.x

Offset: 0 Lower Limit: 110Size (bits):16

Upper Limit: 45000

Sign: U

43302 ACM / Ap-plicationConfigura-tion

Genset Delta/Wye Connec-tion

Read/Write

Delta or Wye for Genset connection PC 2.x, PC3.x0: Delta

1: Wye

43303 ACM /Voltage

Genset Nomi-nal Voltage

Read/Write

Multiplier:1

Unit: Vac Genset nominal line−linevoltage

PC 2.x, PC3.x

Offset: 0 Lower Limit: 110Size (bits):16

Upper Limit: 45000

Sign: U

43304 ACM / Ap-plicationConfigura-tion

Single/3Phase Con-nection

Read/Write

Setup mode interlocked. Genset’s single phase/3phase metering setup configuration.

PC 2.x, PC3.x

0: Single Phase1: Three Phase

43306 ACM / Ap-plicationConfigura-tion

Utility Delta/Wye Connec-tion

Read/Write

Delta or Wye for Utility connection PC 3.x

0: Delta

1: Wye

43307 ACM /Voltage

Utility NominalVoltage

Read/Write

Multiplier:1

Unit: Vac Utility nominal voltage PC 3.x

Offset: 0 Lower Limit: 110Size (bits):16

Upper Limit: 45000

Sign: U

43309 AP / Fre-quencyProtection

Overfrequen-cy Enable

Read/Write

Enables overfrequency diagnostic witness test. PC 2.x, PC3.x0: Disabled

1: Enabled

43310 AP / PowerFlow Moni-tor

OverloadWarning SetTime

Read/Write

Multiplier:1

Unit: sec-onds

The time delay until anoverload condition is re-ported as a fault

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 120

Sign: U

43311 AP / PowerFlow Moni-tor

OverloadWarningThreshold

Read/Write

Multiplier:0.01

Unit: % Sets the Overload Warn-ing fault trip threshold aspercentage of genset ap-plication kW rating.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 80Size (bits):16

Upper Limit: 140

Sign: U

Page 154: Mapa de Registros de Pcc

147

Addr. ControlDescriptionAccessParameterName43338 CAN /

CANDatalink

CAN FailureRetries

Read/Write

Multiplier:1

Unit: Sets the maximum num-ber of CAN communica-tion retries

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 10

Sign: U

43340 CM / Con-trollerModes

Max SetupMode Time

Read/Write

Multiplier:1

Unit: Sec-onds

Max time allowed in Set-up Mode.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 30Size (bits):16

Upper Limit: 3600

Sign: U

43341 CM / Con-trollerModes

Power DownMode Enable

Read/Write

Trim to enable sleep mode PC 2.x, PC3.x0: Disable

1: Enable

43342 CM / Con-trollerModes

Power DownMode TimeDelay

Read/Write

Multiplier:1

Unit: sec-onds

Timer setting for the Pow-er Down delay feature

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 600

Sign: U

43343 CM / Con-trollerModes

Setup ModeEnable

Read/Write

Volatile to allow entry into Setup Mode PC 2.x, PC3.x0: Disable

1: Enable

43344 DR / RealTime Clock

Clock Date Read/Write

Multiplier:1

Unit: Use to set or read thecurrent date.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 31

Sign: U

43345 DR / RealTime Clock

Clock Hour Read/Write

Multiplier:1

Unit: Use to set or read thecurrent hour.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 23

Sign: U

43346 DR / RealTime Clock

Clock Minute Read/Write

Multiplier:1

Unit: Use to set or read thecurrent minute.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 59

Sign: U

43347 DR / RealTime Clock

Clock Mode Read/Write

Use to set the real time clock and save settings.0: Normal PC 2.x, PC

3.x1: Set Clock2: Save Clock

Page 155: Mapa de Registros de Pcc

148

Addr. ControlDescriptionAccessParameterName43348 DR / Real

Time ClockClock Month Read/

WriteMultiplier:1

Unit: Use to set or read thecurrent month.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 12

Sign: U

43349 DR / RealTime Clock

Clock Second Read/Write

Multiplier:1

Unit: Use to set or read thecurrent second.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 59

Sign: U

43350 DR / RealTime Clock

Clock Year Read/Write

Multiplier:1

Unit: Use to set or read thecurrent year.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 99

Sign: U

43351 DR / RealTime Clock

Daylight Sav-ings End Hour

Read/Write

Multiplier:1

Unit: Use to set the hour of theday when daylight sav-ings time ends.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 2Size (bits):8

Upper Limit: 19

Sign: U

43352 DR / RealTime Clock

Daylight Sav-ings EndMonth

Read/Write

Multiplier:1

Unit: Use to set the monthwhen daylight savingstime ends.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 12

Sign: U

43353 DR / RealTime Clock

Daylight Sav-ings EndWeek Occur-rence inMonth

Read/Write

Use to set the week of the month when daylight sav-ings time ends.

PC 2.x, PC3.x

0: First Occurrence1: Second Occurrence2: Third Occurrence3: Fourth Occurrence4: Last Occurrence

43354 DR / RealTime Clock

Daylight Sav-ings Start Day

Read/Write

Use to set the day of the week when daylight savingstime starts.

PC 2.x, PC3.x

0: Sunday1: Monday2: Tuesday3: Wednesday4: Thursday5: Friday6: Saturday

Page 156: Mapa de Registros de Pcc

149

Addr. ControlDescriptionAccessParameterName43355 DR / Real

Time ClockDaylight Sav-ings StartHour

Read/Write

Multiplier:1

Unit: Use to set the hour of theday when daylight sav-ings time starts.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 2Size (bits):8

Upper Limit: 19

Sign: U

43356 DR / RealTime Clock

Daylight Sav-ings StartMonth

Read/Write

Multiplier:1

Unit: Use to set the monthwhen daylight savingstime starts.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 12

Sign: U

43357 DR / RealTime Clock

Daylight Sav-ings StartWeek Occur-rence inMonth

Read/Write

Use to set the week of the month when daylight sav-ings time starts.

PC 2.x, PC3.x

0: First Occurrence1: Second Occurrence2: Third Occurrence3: Fourth Occurrence4: Last Occurrence

43358 DR / RealTime Clock

Daylight Sav-ings Time Ad-justment

Read/Write

Multiplier:1

Unit: Min-utes

Use to set the amount ofdaylight savings time ad-justment applied.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 120

Sign: U

43359 DR / RealTime Clock

Daylight Sav-ings Time En-able

Read/Write

Use to enable the daylight savings time feature. PC 2.x, PC3.x0: Disabled

1: Enabled

43360 DR / Exer-ciseScheduler

ExerciseScheduler En-able

Read/Write

Enables the exercise scheduler. PC 2.x, PC3.x0: Disabled

1: Enabled

43361 DR / DataRecording

Reset FuelConsumption

Read/Write

The reset trip fuel consumption command. PC 2.x, PC3.x0: Inactive

1: Active

43362 DR / DataRecording

Reset Runs Read/Write

The reset runs command. PC 2.x, PC3.x0: Inactive

1: Active

43363 DR / DataRecording

Reset StartAttempts

Read/Write

The reset start attempts command. PC 2.x, PC3.x0: Inactive

1: Active

43364 DR / Exer-ciseScheduler

Scheduler Ex-ception Select

Read/Write

Multiplier:1

Unit: Used to select an excep-tion to adjust.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 6

Sign: U

Page 157: Mapa de Registros de Pcc

150

Addr. ControlDescriptionAccessParameterName43365 DR / Exer-

ciseScheduler

Scheduler Ex-ception x Date

Read/Write

Multiplier:1

Unit: Used to adjust the datefor the selected excep-tion.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 31

Sign: U43366 DR / Exer-

ciseScheduler

Scheduler Ex-ception xDuration Days

Read/Write

Multiplier:1

Unit: Used to adjust the lengthin days for the selectedexception.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 44

Sign: U43367 DR / Exer-

ciseScheduler

Scheduler Ex-ception xDurationHours

Read/Write

Multiplier:1

Unit: Used to adjust the lengthin hours for the selectedexception.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 23

Sign: U43368 DR / Exer-

ciseScheduler

Scheduler Ex-ception xDuration Min-utes

Read/Write

Multiplier:1

Unit: Used to adjust the lengthin minutes for the se-lected exception.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 59

Sign: U43369 DR / Exer-

ciseScheduler

Scheduler Ex-ception x En-able

Read/Write

Used to enable or disable the selected exception. PC 2.x, PC3.x0: Disable

1: Enable43370 DR / Exer-

ciseScheduler

Scheduler Ex-ception xHour

Read/Write

Multiplier:1

Unit: Used to adjust the start-ing hour for the selectedexception.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 23

Sign: U43371 DR / Exer-

ciseScheduler

Scheduler Ex-ception x Min-ute

Read/Write

Multiplier:1

Unit: Used to adjust the start-ing minute for the se-lected exception.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 59

Sign: U

Page 158: Mapa de Registros de Pcc

151

Addr. ControlDescriptionAccessParameterName43372 DR / Exer-

ciseScheduler

Scheduler Ex-ception xMonth

Read/Write

Multiplier:1

Unit: Used to adjust the start-ing month for the se-lected exception.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 12

Sign: U

43373 DR / Exer-ciseScheduler

Scheduler Ex-ception x Re-peat

Read/Write

Used to adjust the repeat interval for the selected ex-ception.

PC 2.x, PC3.x

0: Once Only1: Every Year

43374 DR / Exer-ciseScheduler

SchedulerProgram Se-lect

Read/Write

Multiplier:1

Unit: Used to select a programto adjust.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 12

Sign: U

43375 DR / Exer-ciseScheduler

SchedulerProgram xDurationHours

Read/Write

Multiplier:1

Unit: Used to adjust the lengthin hours for the selectedprogram.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 23

Sign: U

43376 DR / Exer-ciseScheduler

SchedulerProgram xDuration Min-utes

Read/Write

Multiplier:1

Unit: Used to adjust the lengthin minutes for the se-lected program.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 59

Sign: U

43377 DR / Exer-ciseScheduler

SchedulerProgram xEnable

Read/Write

Used to enable or disable the selected program. PC 2.x, PC3.x0: Disable

1: Enable

43378 DR / Exer-ciseScheduler

SchedulerProgram xRepeat Inter-val

Read/Write

Used to adjust the repeat interval for the selected pro-gram.

PC 2.x, PC3.x

0: Once1: Every Week2: Every 2 Weeks3: Every 3 Weeks4: Every 4 Weeks5: Every 5 Weeks6: First Week of Month7: Second Week of Month8: Third Week of Month9: Fourth Week of Month10: Last Week of Month

Page 159: Mapa de Registros de Pcc

152

Addr. ControlDescriptionAccessParameterName43379 DR / Exer-

ciseScheduler

SchedulerProgram xRun Mode

Read/Write

Used to adjust the run mode for the selected program. PC 2.x, PC3.x0: No Load

1: With Load2: Extended Parallel

43380 DR / Exer-ciseScheduler

SchedulerProgram xStart Day

Read/Write

Used to adjust the start day of the week for the se-lected program.

PC 2.x, PC3.x

0: Sunday1: Monday2: Tuesday3: Wednesday4: Thursday5: Friday6: Saturday

43381 DR / Exer-ciseScheduler

SchedulerProgram xStart Hour

Read/Write

Multiplier:1

Unit: Used to adjust the starthour for the selected pro-gram.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 23

Sign: U43382 DR / Exer-

ciseScheduler

SchedulerProgram xStart Minute

Read/Write

Multiplier:1

Unit: Used to adjust the startminute for the selectedprogram.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 59

Sign: U43383 DR / Real

Time ClockDaylight Sav-ings End Day

Read/Write

Use to set the day of the week when daylight savingstime ends.

PC 2.x, PC3.x

0: Sunday1: Monday2: Tuesday3: Wednesday4: Thursday5: Friday6: Saturday

43501 GC / Start/Stop Con-trol

Genset RunType

ReadOnly

Source or type of current genset run (if running) orprevious genset run (if stopped)

PC 2.x, PC3.x

0: Emergency Remote Start1: Non Emergency Remote Start2: Load Demand Start3: Manual Run4: Exercise

43502 GC / Start/Stop Con-trol

Idle RatedCommand

ReadOnly

The output command of the Idle/Rated Logic PC 2.x, PC3.x0: Idle

1: Rated

Page 160: Mapa de Registros de Pcc

153

Addr. ControlDescriptionAccessParameterName43503 GC / Start/

Stop Con-trol

Idle Request ReadOnly

Indicates a request to go to manual idle. Manual idleallowed if breaker is open or not controlled

PC 2.x, PC3.x

0: False1: True

43506 GC / Over-loadProtection

Load DumpCommand

ReadOnly

Monitors the software command to the load dumpdriver output

PC 2.x, PC3.x

0: Inactive1: Active

43507 GC / Over-loadProtection

Load DumpOverloadCondition

ReadOnly

Monitors the state of the load dump overload detec-tion algorithm

PC 2.x, PC3.x

0: Inactive1: Active

43508 GC / Over-loadProtection

Load DumpUnderfre-quency Con-dition

ReadOnly

The state of the load dump underfrequency detectionalgorithm

PC 2.x, PC3.x

0: Inactive1: Active

43509 GC / Bat-teryProtection

Low BatteryVoltage Run-ning Thresh-old

ReadOnly

Multiplier:0.1

Unit: Vdc The low battery voltagethreshold when the gen-set is in rated mode

PC 2.x, PC3.x

Offset: 0 Lower Limit: 12Size (bits):16

Upper Limit: 28

Sign: U

43510 GC / Bat-teryProtection

Low BatteryVoltageStoppedThreshold

ReadOnly

Multiplier:0.1

Unit: Vdc The low battery voltagethreshold when the gen-set is not in rated mode

PC 2.x, PC3.x

Offset: 0 Lower Limit: 11Size (bits):16

Upper Limit: 26

Sign: U

43511 GC / Bat-teryProtection

Low BatteryVoltageThreshold

ReadOnly

Multiplier:0.1

Unit: Vdc The selection of the run-ning or stopped threshold

PC 2.x, PC3.x

Offset: 0 Lower Limit: 11Size (bits):16

Upper Limit: 28

Sign: U

43512 GC / Start/Stop Con-trol

Manual Com-mand

ReadOnly

The output of the Manual Command OR logic PC 2.x, PC3.x0: Not Manual

1: Manual

43513 GC / Start/Stop Con-trol

Manual Com-mand Inputs

ReadOnly

Multiplier:1

Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

Page 161: Mapa de Registros de Pcc

154

Addr. ControlDescriptionAccessParameterName43515 GC / Pre-

lubeOil PrimingPump Com-mand

ReadOnly

The Prelube Driver Command. PC 2.x, PC3.x0: Inactive

1: Active

43516 GC / Pre-lube

Prelube Mode ReadOnly

Set to a required mode based on the type of startingrequirement

PC 2.x, PC3.x

0: Crank After Prelube1: Crank With Prelube2: Prelube Only

43517 GC / Pre-lube

Prelube State ReadOnly

The monitor point for the prelube state. PC 2.x, PC3.x0: Complete

1: Armed2: Prelube Output ON3: Prelube Output OFF4: Enable Crank

43518 GC / Start/Stop Con-trol

PTC GensetOperatingMode

ReadOnly

Current mode for the genset operation part of the PTCfunction

PC 3.x

0: Off1: Manual2: Normal3: Normal Override4: Test5: Exercise6: Utility Fail7: Extended Parallel

43519 GC / Start/Stop Con-trol

PTC ModeSwitch Com-mand

ReadOnly

The output of the PTC Mode Switch Command ORlogic

PC 3.x

0: Inactive1: Active

43520 GC / Start/Stop Con-trol

PTC ModeSwitch Com-mand Inputs

ReadOnly

Multiplier:1

Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on.

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

43521 GC / Start/Stop Con-trol

PTC Status ReadOnly

Indicates what the current state is of PTC control ac-tion

PC 3.x

0: Off/ Not Enabled1: Manual Mode2: Normal Utility3: Retransfer4: Retransfer Override5: Emergency Test6: Normal Test7: Exercise8: Utility Failure9: Extended Parallel

Page 162: Mapa de Registros de Pcc

155

Addr. ControlDescriptionAccessParameterName43522 GC / Start/

Stop Con-trol

PTC TransferPair Operat-ing Mode

ReadOnly

operation mode for the breaker pair portion of thePTC function

PC 3.x

0: Off1: Manual2: Normal3: Normal Override4: Test5: Exercise6: Utility Fail7: Extended Parallel

43523 GC / Out-puts

Ready toLoad Com-mand

ReadOnly

The state that the Ready to Load Driver output is be-ing commanded to

PC 2.x, PC3.x

0: Inactive1: Active

43524 GC / Start/Stop Con-trol

Remote StartCommand

ReadOnly

The output of the Remote Start Command OR logic PC 2.x, PC3.x0: Stop

1: Start

43525 GC / Start/Stop Con-trol

Remote StartCommand In-puts

ReadOnly

Multiplier:1

Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

43526 GC / Start/Stop Con-trol

Remote StartState

ReadOnly

Status of remote start and load demand stop inputs PC 2.x, PC3.x0: Off

1: Remote Start2: Load Demand Stop3: Load Demand Start

43527 GC / Auto-matic Volt-age Regu-lator

RMS Regula-tion Error

ReadOnly

Multiplier:0.01

Unit: % The RMS voltage (or cur-rent) error at the AVR

PC 2.x, PC3.x

Offset: 0 Lower Limit: −100Size (bits):16

Upper Limit: 100

Sign: S

43528 GC / Start/Stop Con-trol

Run Com-mand

ReadOnly

The signal that is commanding a change to the runmode

PC 2.x, PC3.x

0: Off1: Run

43529 GC / Start/Stop Con-trol

Run RelayCommand

ReadOnly

0: Inactive PC 2.x, PC3.x

1: Active

43530 GC / Out-puts

Speed andVoltage BiasRelay Com-mand

ReadOnly

Monitor point for the command which closes the on−board relay enabling the voltage and speed bias out-puts.

PC 3.x

0: Inactive1: Active

Page 163: Mapa de Registros de Pcc

156

Addr. ControlDescriptionAccessParameterName43531 GC /

SpeedReference

Speed BiasCommand

ReadOnly

Multiplier:0.01

Unit: % Indicates amount ofspeed bias offset GCS iscommanding to ECS gov-ernor or external gover-nor

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit:

Sign: S43533 GC / Start/

Stop Con-trol

Start Count-down

ReadOnly

Multiplier:1

Unit: sec-onds

Time remaining until startis initiated

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 300

Sign: U43534 GC /

CrankingControl

Start Discon-nect Logic

ReadOnly

Monitor point for the Start Disconnect logic. True =genset sensed above start disconnect speed.

PC 2.x, PC3.x

0: False1: True

43536 GC / Start/Stop Con-trol

Start TypeCommand

ReadOnly

The output of the Start Type Command OR logic PC 2.x, PC3.x0: Emergency

1: Non Emergency43537 GC / Start/

Stop Con-trol

Start TypeCommand In-puts

ReadOnly

Multiplier:1

Unit: Bitmask to show the in-puts to the Commandoutput which are current-ly on

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U43538 GC /

CrankingControl

Starter Com-mand

ReadOnly

The state the Starter Command output from thecranking algorithm is being commanded to

PC 2.x, PC3.x

0: Inactive1: Active

43539 GC / Start/Stop Con-trol

Stop Count-down

ReadOnly

Multiplier:1

Unit: sec-onds

Time remaining until gen-set stops

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 5000

Sign: U43540 GC / Start/

Stop Con-trol

Switch PanelRun Request

ReadOnly

Status of run and exercise commands from displaypanel

PC 2.x, PC3.x

0: None1: Manual2: Exercise

Page 164: Mapa de Registros de Pcc

157

Addr. ControlDescriptionAccessParameterName43542 GC / Volt-

age Set-point

Target Voltage ReadOnly

Multiplier:0.01

Unit: % The target voltage with-out ramping and torquematch voltage rolloff ef-fects

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 150

Sign: U

43543 GC / Start/Stop Con-trol

Time At NoLoad

ReadOnly

Multiplier:1

Unit: sec-onds

Amount of time the gen-set has run at no load

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 600

Sign: U

43544 GC / Start/Stop Con-trol

Time at RatedCooldown

ReadOnly

Multiplier:1

Unit: sec-onds

Amount of time spend inRated Cooldown

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 5000

Sign: U

43546 GC / Auto-matic Volt-age Regu-lator

Voltage BiasCommand

ReadOnly

Multiplier:0.01

Unit: % Indicates amount of volt-age bias offset GCS iscommanding to an exter-nal regulator

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit:

Sign: S

43547 GC / Volt-age Set-point

Voltage Set-point

ReadOnly

Multiplier:0.01

Unit: % The voltage setpointcommand

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 150

Sign: U

43550 GC / Bat-teryProtection

Weak BatteryThreshold

ReadOnly

Multiplier:0.1

Unit: Vdc Monitor point for theweak battery voltagethreshold

PC 2.x, PC3.x

Offset: 0 Lower Limit: 6Size (bits):16

Upper Limit: 16

Sign: U

43551 GC / Bat-teryProtection

Weak BatteryVoltage SetTime

Read/Write

Multiplier:1

Unit: sec-onds

The time delay until aweak battery condition isreported as a fault

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):16

Upper Limit: 5

Sign: U

Page 165: Mapa de Registros de Pcc

158

Addr. ControlDescriptionAccessParameterName43552 PARCTL /

Meteringand Refer-enceSelection

ParallelingVoltage RefOffset

ReadOnly

Multiplier:0.01

Unit: % voltage offset to voltageregulator for parallelingfunction

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43553 PARCTL /Synchro-nizer

SynchronizerStatus

ReadOnly

indicates whether synchronizer is on or off PC 3.x0: Synchronizer Off1: Synchronizer On

43554 PARST /PTC Tim-ers

Active Transi-tion Timer

ReadOnly

Multiplier:0.1

Unit: sec-onds

countdown value of theactive transition timer

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43555 PARST /PTC Tim-ers

Active Transi-tion Type

ReadOnly

indicates the active transition type for PTC PC 3.x0: None1: Programmed Transition2: Transfer3: Retransfer4: Max Parallel

43556 PARST /First Start

ArbitrationState

ReadOnly

indicates current arbitration state PC 3.x0: Off1: Arbitrate02: Winner3: Arbitrate14: Sleep

43557 PARST /First Start

ArbitrationTimer

ReadOnly

Multiplier:1

Unit: msec arbitration loop count-down timer

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43558 PARST /ParallelingControlMode

ES State ReadOnly

internal paralleling status variable PC 3.x0: Standby1: Dead Bus2: Synchronize3: Load Share4: Load Govern

43559 PARST /First Start

First StartState

ReadOnly

indicates status of the first start system PC 3.x0: First Start Not Allowed1: First Start Requested2: First Start Permitted

43560 PARST /CircuitBreaker

Genset CBClose Com-mand

ReadOnly

genset cb close command status PC 3.x0: Inactive1: Active

Page 166: Mapa de Registros de Pcc

159

Addr. ControlDescriptionAccessParameterName43561 PARST /

CircuitBreaker

Genset CBFail To CloseLockout

ReadOnly

status of gen fail to close lockout function PC 3.x0: Inactive1: Active

43562 PARST /CircuitBreaker

Genset CBPosition Sta-tus

ReadOnly

indicates genset breaker position PC 3.x0: Open1: Closed2: Not Available

43563 PARST /PTCSourceAvailability

Genset Avail-ability Status

ReadOnly

indicates status of the genset source PC 3.x0: Not Available1: Available2: Unknown

43564 PARST /Dead BusClose

Bus Status ReadOnly

indicates status of the bus PC 3.x0: Unavailable1: Dead2: Live

43565 PARST /CircuitBreaker

Genset CB In-hibit Com-mand

ReadOnly

genset cb inhibit command PC 3.x0: Inactive1: Active

43566 PARST /CircuitBreaker

Genset CBTripped Com-mand

ReadOnly

genset cb tripped command PC 3.x0: Inactive1: Active

43567 PARST /CircuitBreaker

Genset Cur-rent BasedBreaker Posi-tion

ReadOnly

indicates genset breaker position based on current PC 3.x

0: Unknown

1: Closed

43568 PARST /PTC Sen-sors

Genset Fre-quency LowerDrop−OutThreshold

ReadOnly

Multiplier:0.1

Unit: Hz indicates the lower drop−out threshold in Hz forgenset frequency sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43569 PARST /

PTC Sen-sors

Genset Fre-quency LowerPick−UpThreshold

ReadOnly

Multiplier:0.1

Unit: Hz indicates the lower pick−up threshold in Hz forgenset frequency sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43570 PARST /

PTC Sen-sors

Genset Fre-quency Sen-sor Status

ReadOnly

indicates genset frequency sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out

Page 167: Mapa de Registros de Pcc

160

Addr. ControlDescriptionAccessParameterName43571 PARST /

PTC Sen-sors

Genset Fre-quency UpperDrop−OutThreshold

ReadOnly

Multiplier:0.1

Unit: Hz indicates the upper drop−out threshold in Hz forgenset frequency sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43572 PARST /PTC Sen-sors

Genset Fre-quency UpperPick−UpThreshold

ReadOnly

Multiplier:0.1

Unit: Hz indicates the upper pick−up threshold in Hz forgenset frequency sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43573 PARST /PTC Sen-sors

Genset Lossof Phase Sen-sor Status

ReadOnly

indicates genset loss of phase sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out

43574 PARST /PTC Sen-sors

Genset Over-voltage Drop−Out Threshold

ReadOnly

Multiplier:1

Unit: Vac indicates the drop−outthreshold in volts for gen-set overvoltage sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43575 PARST /PTC Sen-sors

Genset Over-voltage Pick−Up Threshold

ReadOnly

Multiplier:1

Unit: Vac indicates the pick−upthreshold in volts for gen-set overvoltage sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43576 PARST /PTC Sen-sors

Genset Over-voltage Sen-sor Status

ReadOnly

indicates genset overvoltage sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out

43577 PARST /PTC Sen-sors

Genset PhaseRotation Sen-sor Status

ReadOnly

indicates genset phase rotation sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out

43578 PARST /PTC Sen-sors

Genset Un-dervoltageDrop−OutThreshold

ReadOnly

Multiplier:1

Unit: Vac indicates the drop−outthreshold in volts for gen-set undervoltage sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 168: Mapa de Registros de Pcc

161

Addr. ControlDescriptionAccessParameterName43579 PARST /

PTC Sen-sors

Genset Un-dervoltagePick−UpThreshold

ReadOnly

Multiplier:1

Unit: Vac indicates the pick−upthreshold in volts for gen-set undervoltage sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43580 PARST /PTC Sen-sors

Genset Un-dervoltageSensor Status

ReadOnly

indicates genset undervoltage sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out

43581 PARST /First Start

Master FirstStart OutputCommand

ReadOnly

status of the first start output command PC 3.x0: Inactive1: Active

43582 PARST /PTC Tim-ers

MaximumParallel Timer

ReadOnly

Multiplier:0.1

Unit: sec-onds

countdown value of themaximum parallel timer

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43583 PARST /PTC Tim-ers

MaximumParallel TimerStatus

ReadOnly

indicates status of the maximum parallel timer PC 3.x0: Not Timing1: Timing2: Expired

43584 PARST /ParallelingControlMode

ParallelingSpeed ControlMode

ReadOnly

indicates which speed control algorithm is in effect PC 2.x, PC3.x0: Isochronous

1: Droop2: Synchronize3: Load Share4: Load Govern

43585 PARST /ParallelingControlMode

ParallelingVoltage Con-trol Mode

ReadOnly

indicates which voltage control algorithm is in effect PC 2.x, PC3.x0: Isochronous

1: Droop2: Synchronize3: Load Share4: Load Govern

43586 PARST /PTC Tim-ers

ProgrammedTransitionTimer

ReadOnly

Multiplier:0.1

Unit: sec-onds

countdown value of theprogrammed transitiontimer

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43587 PARST /PTC Tim-ers

ProgrammedTransitionTimer Status

ReadOnly

indicates status of the programmed transition timer PC 3.x0: Not Timing1: Timing2: Expired

Page 169: Mapa de Registros de Pcc

162

Addr. ControlDescriptionAccessParameterName43588 PARST /

PTC En-ables

PTC EnableStatus

ReadOnly

indicates if PTC functions are running PC 3.x0: Disable1: Enable

43589 PARST /PTC StateMachine

PTC Operat-ing TransitionType

ReadOnly

indicates the transition type currently in effect PC 3.x0: Open Transition1: Hard Closed Transition2: Soft Closed Transition

43590 PARST /PTC StateMachine

PTC State ReadOnly

indicates the connected state of the Power TransferControl

PC 3.x

0: PTC Not Enabled1: No Source Connected2: Utility Connected3: Genset Connected4: Paralleled

43591 PARST /PTC Tim-ers

RetransferTimer

ReadOnly

Multiplier:0.1

Unit: sec-onds

countdown value of theretransfer timer

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43592 PARST /PTC Tim-ers

RetransferTimer Status

ReadOnly

indicates status of the retransfer timer PC 3.x0: Not Timing1: Timing2: Expired

43593 PARST /ParallelingControlMode

Speed DroopEnable Com-mand

ReadOnly

command value of speed droop enable PC 2.x, PC3.x0: Inactive

1: Active

43594 PARST /ParallelingControlMode

Speed DroopStatus

ReadOnly

indicates whether or not speed droop is in effect PC 2.x, PC3.x0: Droop Disabled

1: Droop Enabled

43595 PARST /PTC Tim-ers

Transfer Tim-er

ReadOnly

Multiplier:0.1

Unit: sec-onds

countdown value of thetransfer timer

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43596 PARST /PTC Tim-ers

Transfer Tim-er Status

ReadOnly

indicates status of the transfer timer PC 3.x0: Not Timing1: Timing2: Expired

43597 PARST /CircuitBreaker

Utility CBClose Com-mand

ReadOnly

utility cb close command status PC 3.x0: Inactive1: Active

43598 PARST /CircuitBreaker

Utility CBOpen Com-mand

ReadOnly

utility cb open command status PC 3.x0: Inactive1: Active

Page 170: Mapa de Registros de Pcc

163

Addr. ControlDescriptionAccessParameterName43599 PARST /

CircuitBreaker

Utility CBPosition Sta-tus

ReadOnly

indicates utility breaker position PC 3.x0: Open1: Closed2: Not Available

43600 PARCTL /Load Gov-ern

Load GovernkW Method

Read/Write

Use to select how genset kW output will be controlledwhen paralleled to utility.

PC 3.x

0: Genset kW1: Genset kW w/Utility Constraint2: Utility kW

43608 DSO / Dis-crete Out-puts

ConfigurableOutput #1Event Code

Read/Write

Multiplier:1

Unit: The event code for thisoutput.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43610 DSO / Dis-

crete Out-puts

ConfigurableOutput #2Event Code

Read/Write

Multiplier:1

Unit: The event code for thisoutput.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43613 DSO / Dis-

crete Out-puts

ConfigurableOutput #20Event Code

Read/Write

Multiplier:1

Unit: The event code for thisoutput.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43616 DSO / Dis-

crete Out-puts

ConfigurableOutput #21Event Code

Read/Write

Multiplier:1

Unit: The event code for thisoutput.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43619 DSO / Dis-

crete Out-puts

ConfigurableOutput #22Event Code

Read/Write

Multiplier:1

Unit: The event code for thisoutput.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43622 DSO / Dis-

crete Out-puts

ConfigurableOutput #3Event Code

Read/Write

Multiplier:1

Unit: The event code for thisoutput.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 171: Mapa de Registros de Pcc

164

Addr. ControlDescriptionAccessParameterName43625 DSO / Dis-

crete Out-puts

ConfigurableOutput #4Event Code

Read/Write

Multiplier:1

Unit: The event code for thisoutput.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

43641 EH / EventHandler

Delayed Shut-down Enable

Read/Write

Enables the Delayed Shutdown feature. PC 2.x, PC3.x0: Disabled

1: Enabled

43642 EH / EventHandler

Delayed Shut-down TimeDelay

Read/Write

Multiplier:0.1

Unit: sec-onds

Sets the shutdown faultdelayed time delay forthe Delayed Shutdownfeature.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 3

Sign: U

43643 EH / EventHandler

Remote FaultReset En-abled

Read/Write

Trim to enable Remote Fault Reset. Can only reset”Warning” Faults

PC 2.x, PC3.x

0: Disable1: Enable

43644 EH / FaultHandling

Fail To Shut-down Delay

Read/Write

Multiplier:1

Unit: sec-onds

Trim to set the time for ashutdown fault to be ac-tive and the genset notshutting down before theFail to Shutdown fault oc-curs.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 30

Sign: U

43645 EP / LowCoolantLevel

LCL DetectionResponse

Read/Write

Sets low coolant level fault response to None Warningor Shutdown.

PC 2.x, PC3.x

0: None1: Warning2: Shutdown

43646 EP / LowCoolantTemp

LCT WarningClear Time

Read/Write

Multiplier:1

Unit: Min-utes

Sets time to clear the lowcoolant temp fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 30

Sign: U

43647 EP / LowCoolantTemp

LCT WarningSet Time

Read/Write

Multiplier:1

Unit: Min-utes

Sets time to set the lowcoolant temp fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 30

Sign: U

Page 172: Mapa de Registros de Pcc

165

Addr. ControlDescriptionAccessParameterName43648 EP / Low

CoolantTemp

LCT WarningThreshold

Read/Write

Multiplier:1

Unit: degF Sets threshold for the lowcoolant temp fault warn-ing.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −20Size (bits):16

Upper Limit: 100

Sign: S43649 GC / Volt-

age Set-point

V/Hz KneeFrequency

Read/Write

Multiplier:0.1

Unit: Hz The voltage will roll off(decrease) proportionallyto the V/Hz setup oncethe frequency drops be-low the set point in theV/Hz Knee Frequency.This allows the genset torecover faster when thefrequency drops.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: U43650 GC / Volt-

age Set-point

V/Hz RolloffSlope

Read/Write

Multiplier:0.1

Unit: % /Hz

The amount of voltageroll off when the frequen-cy is below the knee fre-quency

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: U43651 GC / Bat-

teryProtection

12 V HighBattery Volt-age Threshold

Read/Write

Multiplier:0.1

Unit: Vdc Sets 12V high batteryvoltage fault threshold.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 14Size (bits):16

Upper Limit: 17

Sign: U43652 GC / Bat-

teryProtection

12 V Low Bat-tery VoltageRunningThreshold

Read/Write

Multiplier:0.1

Unit: Vdc Sets 12V low battery volt-age fault threshold forgenset operation while inrated mode

PC 2.x, PC3.x

Offset: 0 Lower Limit: 12Size (bits):16

Upper Limit: 16

Sign: U43653 GC / Bat-

teryProtection

12 V Low Bat-tery VoltageStoppedThreshold

Read/Write

Multiplier:0.1

Unit: Vdc Sets 12V low battery volt-age fault threshold forgenset operation in allmodes except rated

PC 2.x, PC3.x

Offset: 0 Lower Limit: 11Size (bits):16

Upper Limit: 13

Sign: U

Page 173: Mapa de Registros de Pcc

166

Addr. ControlDescriptionAccessParameterName43654 GC / Bat-

teryProtection

12 V WeakBattery Volt-age Threshold

Read/Write

Multiplier:0.1

Unit: Vdc Sets 12V weak batteryvoltage fault threshold

PC 2.x, PC3.x

Offset: 0 Lower Limit: 6Size (bits):16

Upper Limit: 10

Sign: U43655 GC / Bat-

teryProtection

24 V HighBattery Volt-age Threshold

Read/Write

Multiplier:0.1

Unit: Vdc Sets 24V high batteryvoltage fault threshold

PC 2.x, PC3.x

Offset: 0 Lower Limit: 28Size (bits):16

Upper Limit: 34

Sign: U43656 GC / Bat-

teryProtection

24 V Low Bat-tery VoltageRunningThreshold

Read/Write

Multiplier:0.1

Unit: Vdc Sets 24V low battery volt-age fault threshold forgenset operation while inrated mode

PC 2.x, PC3.x

Offset: 0 Lower Limit: 24Size (bits):16

Upper Limit: 28

Sign: U43657 GC / Bat-

teryProtection

24 V Low Bat-tery VoltageStoppedThreshold

Read/Write

Multiplier:0.1

Unit: Vdc Sets 24V low battery volt-age fault threshold forgenset operation in allmodes except rated

PC 2.x, PC3.x

Offset: 0 Lower Limit: 22Size (bits):16

Upper Limit: 26

Sign: U43658 GC / Bat-

teryProtection

24 V WeakBattery Volt-age Threshold

Read/Write

Multiplier:0.1

Unit: Vdc Sets 24V weak batteryvoltage fault threshold

PC 2.x, PC3.x

Offset: 0 Lower Limit: 12Size (bits):16

Upper Limit: 16

Sign: U43659 GC /

SpeedReference

AdjustableFreq/SpeedGain

Read/Write

Multiplier:0.01

Unit: rpm/Hz

Sets the rpm/Hz conver-sion factor when the Freqto Speed Gain Select trimis set to this trim

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 240

Sign: U43660 GC /

SpeedReference

Alternate Fre-quencySwitch

Read/Write

Sets the genset nominal frequency. PC 2.x, PC3.x0: 50 Hz

1: 60 Hz

Page 174: Mapa de Registros de Pcc

167

Addr. ControlDescriptionAccessParameterName43661 GC / Auto-

matic Volt-age Regu-lator

AVR Gain Ad-just Trim

Read/Write

Multiplier:0.01

Unit: A trim that allows theuser to modify the overallgains of the AVR.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0.05Size (bits):16

Upper Limit: 10

Sign: U43662 GC /

ChargingAlternatorProtection

Charging Al-ternator FaultTime Delay

Read/Write

Multiplier:0.1

Unit: sec-onds

Sets the time delay forthe charging alt failurefault

PC 2.x, PC3.x

Offset: 0 Lower Limit: 2Size (bits):16

Upper Limit: 300

Sign: U43663 GC /

CrankingControl

ContinuousCrank EngageTime

Read/Write

Multiplier:1

Unit: sec-onds

Sets the maximumamount of time to engagethe starter when usingthe continuous crankingmethod

PC 2.x, PC3.x

Offset: 0 Lower Limit: 40Size (bits):16

Upper Limit: 100

Sign: U43664 GC / Con-

trolledShutdownControl

ControlledShutdown Ad-vance NoticeDelay

Read/Write

Multiplier:1

Unit: sec-onds

Delay allowed for a shut-down with cooldown faultprior to shutting down thegenset

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 300

Sign: U43665 GC /

CrankingControl

Crank At-tempts

Read/Write

Multiplier:1

Unit: Sets the maximum num-ber of times to engagethe starter when attempt-ing to start engine usingthe cycle cranking meth-od

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):16

Upper Limit: 7

Sign: U43666 GC /

CrankingControl

Cycle / ContCrank Select

Read/Write

Selects whether to use continuous cranking or cyclecranking when attempting to start engine

PC 2.x, PC3.x

0: Cycle1: Continuous

Page 175: Mapa de Registros de Pcc

168

Addr. ControlDescriptionAccessParameterName43667 GC /

CrankingControl

Cycle CrankEngage Time

Read/Write

Multiplier:1

Unit: sec-onds

Sets the maximumamount of time to engagethe starter during a singlecrank attempt when usingthe cycle cranking meth-od

PC 2.x, PC3.x

Offset: 0 Lower Limit: 2Size (bits):16

Upper Limit: 20

Sign: U43668 GC /

CrankingControl

Cycle CrankRest Time

Read/Write

Multiplier:1

Unit: sec-onds

Sets the amount of timeto wait between crank at-tempts

PC 2.x, PC3.x

Offset: 0 Lower Limit: 7Size (bits):16

Upper Limit: 40

Sign: U43669 GC / Out-

putsDelayed OffFSO RelayTime

Read/Write

Multiplier:0.1

Unit: sec-onds

Time delay betweenwhen the Delayed OffCommand turns off andRun Command turns off

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 120

Sign: U43670 GC / Volt-

age Set-point

External AVRKnee Fre-quency

Read/Write

Multiplier:0.1

Unit: Hz Sets the knee frequencyfor the fixed knee freqlogic.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: U43671 GC / Volt-

age Set-point

External BiasCommandsEnable

Read/Write

Enables the external bias (speed and voltage com-mands) to the hardware outputs.

PC 3.x

0: Disabled1: Enabled

43672 GC /SpeedReference

FrequencyAdjust

Read/Write

Multiplier:0.01

Unit: Hz A method of adding in afrequency offset to thebase frequency subject tohigh and low limit calibra-tions

PC 2.x, PC3.x

Offset: 0 Lower Limit: −6Size (bits):16

Upper Limit: 6

Sign: S

Page 176: Mapa de Registros de Pcc

169

Addr. ControlDescriptionAccessParameterName43673 GC / Start/

Stop Con-trol

Genset Exer-cise Time

Read/Write

Multiplier:0.1

Unit: hours Sets the total exercisetime not including war-mup at idle or idle cool-down time

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 25

Sign: U43674 GC / Gov-

ernorGovernorGain Adjust

Read/Write

Multiplier:0.01

Unit: A trim that allows theuser to modify the overallgain of the governor

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0.05Size (bits):16

Upper Limit: 10

Sign: U43675 GC / Bat-

teryProtection

High BatteryVoltage SetTime

Read/Write

Multiplier:1

Unit: sec-onds

The time delay until ahigh battery voltage con-dition is reported as afault.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 2Size (bits):16

Upper Limit: 60

Sign: U43676 GC / Bat-

teryProtection

High BatteryVoltageThreshold

ReadOnly

Multiplier:0.1

Unit: Vdc The high battery voltagethreshold

PC 2.x, PC3.x

Offset: 0 Lower Limit: 14Size (bits):16

Upper Limit: 34

Sign: U43677 GC / Start/

Stop Con-trol

Idle CooldownTime

Read/Write

Multiplier:0.25

Unit: min-utes

Sets time to run at idlebefore shutting downgenset on normal stops

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 60

Sign: U43678 GC /

SpeedReference

Idle Speed Read/Write

Multiplier:1

Unit: rpm Sets the speed at whichthe engine will idle sub-ject to high and low limitcalibrations

PC 2.x, PC3.x

Offset: 0 Lower Limit: 700Size (bits):16

Upper Limit: 1100

Sign: U

Page 177: Mapa de Registros de Pcc

170

Addr. ControlDescriptionAccessParameterName43679 GC /

SpeedReference

Idle to RatedRamp Time

Read/Write

Multiplier:0.1

Unit: sec-onds

The time over which thespeed reference is toramp from idle speed torated speed

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 30

Sign: U43680 GC / Start/

Stop Con-trol

Idle WarmupCoolant Temp

Read/Write

Multiplier:1

Unit: degF Coolant temperaturethreshold to end idle war-mup time

PC 2.x, PC3.x

Offset: 0 Lower Limit: −40Size (bits):16

Upper Limit: 300

Sign: S43681 GC / Start/

Stop Con-trol

Idle WarmupTime

Read/Write

Multiplier:1

Unit: sec-onds

Sets maximum idle war-mup time. Warmup timemay be less if coolanttemperature exceedsthreshold

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 3600

Sign: U43682 GC / Over-

loadProtection

Load DumpActivationMethod

Read/Write

Enables the load dump output as a function of theoverload and underfrequency conditions

PC 2.x, PC3.x

0: Overload1: Underfrequency2: Overload or Underfrequency3: Disabled

43683 GC / Over-loadProtection

Load DumpOverload SetTime

Read/Write

Multiplier:1

Unit: sec-onds

The time delay until theload dump overload con-dition is set active

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 120

Sign: U43684 GC / Over-

loadProtection

Load DumpOverloadThreshold

Read/Write

Multiplier:1

Unit: % The load dump overloadthreshold as a percent-age of the genset ap-plication rating

PC 2.x, PC3.x

Offset: 0 Lower Limit: 80Size (bits):16

Upper Limit: 140

Sign: U

Page 178: Mapa de Registros de Pcc

171

Addr. ControlDescriptionAccessParameterName43685 GC / Over-

loadProtection

Load DumpUnderfre-quency Offset

Read/Write

Multiplier:1

Unit: Hz The frequency amountwhich the load dump un-derfrequency threshold isbelow the final frequencyreference

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: S

43686 GC / Over-loadProtection

Load DumpUnderfre-quency SetTime

Read/Write

Multiplier:1

Unit: sec-onds

The time delay until theload dump underfrequen-cy condition is set active

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 20

Sign: U

43687 GC / Over-loadProtection

Load DumpUnderfre-quencyThreshold

ReadOnly

Multiplier:0.1

Unit: Hz The frequency tripthreshold for the loaddump underfrequencycondition

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 90

Sign: U

43688 GC / Bat-teryProtection

Low BatteryVoltage SetTime

Read/Write

Multiplier:1

Unit: sec-onds

The time delay until a lowbattery voltage conditionis reported as a fault

PC 2.x, PC3.x

Offset: 0 Lower Limit: 2Size (bits):16

Upper Limit: 60

Sign: U

43689 GC / Out-puts

Low Fuel inDay TankTime

Read/Write

Multiplier:1

Unit: sec-onds

Low Fuel in Day TankFault time delay fromswitch input.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 20

Sign: U

43690 GC / Out-puts

Low Fuel Set/Clear Time

Read/Write

Multiplier:1

Unit: sec-onds

A trim that sets the delaytime for generating the in-active and active faults.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 2Size (bits):16

Upper Limit: 60

Sign: U

43691 GC / Start/Stop Con-trol

Manual War-mup Bypass

Read/Write

Use to command idle speed or to bypass idle warmupduring a manual run

PC 2.x, PC3.x

0: Normal1: Bypass Warmup

Page 179: Mapa de Registros de Pcc

172

Addr. ControlDescriptionAccessParameterName43692 GC / Start/

Stop Con-trol

Max Idle Time Read/Write

Multiplier:0.1

Unit: min-utes

Sets the fault time for theToo Long in Idle fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 20

Sign: U43693 GC / Bat-

teryProtection

Nominal Bat-tery Voltage

Read/Write

Selects the genset_s nominal battery operating volt-age

PC 2.x, PC3.x

0: 12V1: 24V

43694 GC / Pre-lube

Prelube CycleEnable

Read/Write

Enables Or Disables the cyclic mode of prelube op-eration

PC 2.x, PC3.x

0: Disabled1: Enabled

43695 GC / Pre-lube

Prelube CycleTime

Read/Write

Multiplier:0.1

Unit: hours Sets the period of thePrelube Cycle Iteration

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):16

Upper Limit: 1000

Sign: U43696 GC / Pre-

lubePrelube Func-tion Enable

Read/Write

Selects whether the Prelube function is enabled ordisabled. This is Setup mode interlocked

PC 2.x, PC3.x

0: Disabled1: Enabled

43697 GC / Pre-lube

Prelube OilPressureThreshold

Read/Write

Multiplier:0.1

Unit: psig The oil pressure valuewhich when reached theprelube driver will turn off

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: U43698 GC / Pre-

lubePrelube Time-out Period

Read/Write

Multiplier:0.1

Unit: sec-onds

Sets the maximum timefor which the PrelubeDriver will Remain ON

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 30

Sign: U43699 GC /

SpeedReference

Rated to IdleRamp Time

Read/Write

Multiplier:0.1

Unit: sec-onds

The time over which thespeed reference is toramp from rated speed toidle speed

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 30

Sign: U

Page 180: Mapa de Registros de Pcc

173

Addr. ControlDescriptionAccessParameterName43700 PARST /

PTCSourceAvailability

Utility Avail-ability Status

ReadOnly

indicates status of the utility source PC 3.x0: Not Available1: Available2: Unknown

43701 PARST /CircuitBreaker

Utility CB In-hibit Com-mand

ReadOnly

utility cb inhibit command PC 3.x0: Inactive1: Active

43702 PARST /CircuitBreaker

Utility CBTripped Com-mand

ReadOnly

utility cb tripped command PC 3.x0: Inactive1: Active

43703 PARST /CircuitBreaker

Utility CurrentBased Break-er Position

ReadOnly

indicates utility breaker position based on current PC 3.x0: Unknown1: Closed

43704 PARST /PTC Sen-sors

Utility Fre-quency LowerDrop−OutThreshold

ReadOnly

Multiplier:0.1

Unit: Hz indicates the lower drop−out threshold in Hz forutility frequency sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43705 PARST /PTC Sen-sors

Utility Fre-quency LowerPick−UpThreshold

ReadOnly

Multiplier:0.1

Unit: Hz indicates the lower pick−up threshold in Hz for util-ity frequency sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43706 PARST /PTC Sen-sors

Utility Fre-quency Sen-sor Status

ReadOnly

indicates utility frequency sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out

43707 PARST /PTC Sen-sors

Utility Fre-quency UpperDrop−OutThreshold

ReadOnly

Multiplier:0.1

Unit: Hz indicates the upper drop−out threshold in Hz forutility frequency sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43708 PARST /PTC Sen-sors

Utility Fre-quency UpperPick−UpThreshold

ReadOnly

Multiplier:0.1

Unit: Hz indicates the upper pick−up threshold in Hz for util-ity frequency sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43709 PARST /PTC Sen-sors

Utility Loss ofPhase SensorStatus

ReadOnly

indicates utility loss of phase sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out

Page 181: Mapa de Registros de Pcc

174

Addr. ControlDescriptionAccessParameterName43710 PARST /

PTC Sen-sors

Utility Over-voltage Drop−Out Threshold

ReadOnly

Multiplier:1

Unit: Vac indicates the drop−outthreshold in volts for util-ity overvoltage sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43711 PARST /PTC Sen-sors

Utility Over-voltage Pick−Up Threshold

ReadOnly

Multiplier:1

Unit: Vac indicates the pick−upthreshold in volts for util-ity overvoltage sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43712 PARST /PTC Sen-sors

Utility Over-voltage Sen-sor Status

ReadOnly

indicates utility overvoltage sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out

43713 PARST /PTC Sen-sors

Utility PhaseRotation Sen-sor Status

ReadOnly

indicates utility phase rotation sensor status PC 3.x0: Un-known1: Picked Up2: Dropped Out

43714 PARST /PTC Sen-sors

Utility Under-voltage Drop−Out Threshold

ReadOnly

Multiplier:1

Unit: Vac indicates the drop−outthreshold in volts for util-ity undervoltage sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43715 PARST /PTC Sen-sors

Utility Under-voltage Pick−Up Threshold

ReadOnly

Multiplier:1

Unit: Vac indicates the pick−upthreshold in volts for util-ity undervoltage sensor

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

43716 PARST /PTC Sen-sors

Utility Under-voltage Sen-sor Status

ReadOnly

indicates utility undervoltage sensor status PC 3.x0: Unknown1: Picked Up2: Dropped Out

43717 PARST /ParallelingControlMode

Voltage DroopEnable Com-mand

ReadOnly

Command value of voltage droop enable PC 2.x, PC3.x0: Inactive

1: Active

43718 PARST /ParallelingControlMode

Voltage DroopStatus

ReadOnly

indicates whether or not voltage droop is in effect PC 2.x, PC3.x0: Droop Disabled

1: Droop Enabled

Page 182: Mapa de Registros de Pcc

175

Addr. ControlDescriptionAccessParameterName43719 PCCNet /

I/O Module0 MainBoard

AlternatorTemperature1 (Aux101)

ReadOnly

Multiplier:1

Unit: degF Monitor point for the Al-ternator Temp 1 inputfrom the Aux 101 I/OModule.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −32767Size (bits):16

Upper Limit: 32762

Sign: S43720 PCCNet /

I/O Module0 MainBoard

AlternatorTemperature2 (Aux101)

ReadOnly

Multiplier:1

Unit: degF Monitor point for the Al-ternator Temp 2 inputfrom the Aux 101 I/OModule.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −32767Size (bits):16

Upper Limit: 32762

Sign: S43721 PCCNet /

I/O Module0 MainBoard

AlternatorTemperature3 (Aux101)

ReadOnly

Multiplier:1

Unit: degF Monitor point for the Al-ternator Temp 3 inputfrom the Aux 101 I/OModule.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −32767Size (bits):16

Upper Limit: 32762

Sign: S43722 PCCNet /

I/O Module0 MainBoard

Ambient Tem-perature(Aux101)

ReadOnly

Multiplier:1

Unit: degF Monitor point for the Am-bient Temp input from theAux 101 I/O Module.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −32767Size (bits):16

Upper Limit: 32762

Sign: S43723 PCCNet /

I/O Module0 MainBoard

Aux101 0Analog Input1 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 0 analog input 1in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit: −500Size (bits):16

Upper Limit: 500

Sign: S43724 PCCNet /

I/O Module0 MainBoard

Aux101 0Analog Input2 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 0 analog input 2in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit: −500Size (bits):16

Upper Limit: 500

Sign: S

Page 183: Mapa de Registros de Pcc

176

Addr. ControlDescriptionAccessParameterName43725 PCCNet /

I/O Module0 MainBoard

Aux101 0Analog Input3 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 0 analog input 3in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43726 PCCNet /I/O Module0 MainBoard

Aux101 0Analog Input4 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 0 analog input 4in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43727 PCCNet /I/O Module0 MainBoard

Aux101 0Analog Input5 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 0 analog input 5in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43728 PCCNet /I/O Module0 MainBoard

Aux101 0Analog Input6 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 0 analog input 6in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43729 PCCNet /I/O Module0 MainBoard

Aux101 0Analog Input7 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 0 analog input 7in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43730 PCCNet /I/O Module0 MainBoard

Aux101 0Analog Input8 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 0 analog input 8in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43731 PCCNet /I/O Module1 MainBoard

Aux101 1Analog Input1 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 1 analog input 1in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit: −500Size (bits):16

Upper Limit: 500

Sign: S

Page 184: Mapa de Registros de Pcc

177

Addr. ControlDescriptionAccessParameterName43732 PCCNet /

I/O Module1 MainBoard

Aux101 1Analog Input2 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 1 analog input 2in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit: −500Size (bits):16

Upper Limit: 500

Sign: S

43733 PCCNet /I/O Module1 MainBoard

Aux101 1Analog Input3 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 1 analog input 3in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43734 PCCNet /I/O Module1 MainBoard

Aux101 1Analog Input4 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 1 analog input 4in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43735 PCCNet /I/O Module1 MainBoard

Aux101 1Analog Input5 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 1 analog input 5in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43736 PCCNet /I/O Module1 MainBoard

Aux101 1Analog Input6 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 1 analog input 6in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43737 PCCNet /I/O Module1 MainBoard

Aux101 1Analog Input7 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 1 analog input 7in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43738 PCCNet /I/O Module1 MainBoard

Aux101 1Analog Input8 Voltage

ReadOnly

Multiplier:0.01

Unit: Vdc Monitor point for themodule 1 analog input 8in Volts

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 185: Mapa de Registros de Pcc

178

Addr. ControlDescriptionAccessParameterName43739 PCCNet /

UniversalAnnuncia-tor

Battery Char-ger AC Failu-re (HMI113)

ReadOnly

Monitor point for the battery charger failure input fromthe PCCNet Annunciator.

PC 2.x, PC3.x

0: Inactive1: Active

43740 PCCNet /I/O Module0 MainBoard

Drive EndBearing Tem-perature(Aux101)

ReadOnly

Multiplier:1

Unit: degF Monitor point for theDrive End Bearing Tempinput from the I/O Mod-ule.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −32767Size (bits):16

Upper Limit: 32762

Sign: S

43741 PCCNet /I/O Module0 MainBoard

Exhaust StackTemperature1 (Aux101)

ReadOnly

Multiplier:1

Unit: degF Monitor point for the Ex-haust Stack Temp1 inputfrom the I/O Module.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −32767Size (bits):16

Upper Limit: 32762

Sign: S

43742 PCCNet /I/O Module0 MainBoard

Exhaust StackTemperature2 (Aux101)

ReadOnly

Multiplier:1

Unit: degF Monitor point for the Ex-haust Stack Temp2 inputfrom the I/O Module.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −32768Size (bits):16

Upper Limit: 32762

Sign: S

43743 PCCNet /I/O Module0 MainBoard

ExternalSpeed BiasInput(PCCNet)

ReadOnly

Multiplier:0.01

Unit: % Monitor point for theSpeed Bias input fromthe I/O Module.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −100Size (bits):16

Upper Limit: 100

Sign: U

43744 PCCNet /I/O Module0 MainBoard

External Volt-age Bias Input(PCCNet)

ReadOnly

Multiplier:0.01

Unit: % Monitor point for the Volt-age Bias input from theI/O Module.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −100Size (bits):16

Upper Limit: 100

Sign: U

43745 PCCNet /I/O Module0 MainBoard

Fuel Level %(PCCNet)

ReadOnly

Multiplier:0.1

Unit: % Monitor point for the %fuel level input from theI/O Module.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 186: Mapa de Registros de Pcc

179

Addr. ControlDescriptionAccessParameterName43746 PCCNet /

I/O Module0 MainBoard

Fuel Level(PCCNet)

ReadOnly

Multiplier:1

Unit: Monitor point for the fuellevel (in gallons) inputfrom the I/O Module.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43747 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Status

ReadOnly

Monitor point for input #1 from the Annunciator. PC 2.x, PC3.x0: Inactive

1: Active

43748 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Status

ReadOnly

Monitor point for input #2 from the Annunciator. PC 2.x, PC3.x0: Inactive

1: Active

43749 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Status

ReadOnly

Monitor point for the input #3 from the Annunciator. PC 2.x, PC3.x0: Inactive

1: Active

43750 PCCNet /I/O Module0 MainBoard

Intake Man-ifold Tempera-ture 1(Aux101)

ReadOnly

Multiplier:1

Unit: degF Monitor point for the In-take Manifold Temp 1 in-put from the I/O Module.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −32768Size (bits):16

Upper Limit: 32762

Sign: S

43751 PCCNet /UniversalAnnuncia-tor

Low CoolantLevel(HMI113)

ReadOnly

Monitor point for the Low Coolant Level input from thePCCNet Annunciator.

PC 2.x, PC3.x

0: Inactive1: Active

43752 PCCNet /UniversalAnnuncia-tor

Low Fuel Le-vel (HMI113)

ReadOnly

Monitor point for the Low Fuel Level input from thePCCNet Annunciator.

PC 2.x, PC3.x

0: Inactive1: Active

43755 PCCNet /I/O Module0 MainBoard

Non−DriveEnd BearingTemperature(Aux101)

ReadOnly

Multiplier:1

Unit: degF Monitor point for theNon−Drive End BearingTemp input from the I/OModule.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −65534Size (bits):16

Upper Limit: 65535

Sign: S

43756 PCCNet /Monitoringand Diag-nostics

Number ofConnectedBargraphModules

ReadOnly

Multiplier:1

Unit: Used to monitor theamount of connectedBargraph modules.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 255

Sign: U

Page 187: Mapa de Registros de Pcc

180

Addr. ControlDescriptionAccessParameterName43757 PCCNet /

I/O Module0 MainBoard

Oil Tempera-ture (Aux101)

ReadOnly

Multiplier:1

Unit: degF Monitor point for the OilTemp input from the I/OModule.

PC 2.x, PC3.x

Offset: 0 Lower Limit: −65534Size (bits):16

Upper Limit: 65535

Sign: S43758 Modbus /

ModbusModbus BusMessageCount

ReadOnly

Multiplier:1

Unit: Modbus bus messagecount

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43759 Modbus /

ModbusModbus CRCErrors Count

ReadOnly

Multiplier:1

Unit: Modbus CRC errorscount

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43760 Modbus /

ModbusModbus Ex-ception Count

ReadOnly

Multiplier:1

Unit: Modbus exception count PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43761 Modbus /

ModbusModbus NoResponseCount

ReadOnly

Multiplier:1

Unit: Modbus no responsecount

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43762 Modbus /

ModbusModbus SlaveMessageCount

ReadOnly

Multiplier:1

Unit: Modbus slave messagecount

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U43763 PARCTL /

Synchro-nizer

FrequencyMatch Error

ReadOnly

Multiplier:0.001

Unit: Hz frequency match errorvalue used by frequencymatch PI loop

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 188: Mapa de Registros de Pcc

181

Addr. ControlDescriptionAccessParameterName43764 PARCTL /

Synchro-nizer

FrequencyMatch Offset

ReadOnly

Multiplier:0.001

Unit: Hz offset to the frequencymatch error calculation

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43765 PARCTL /Derate

Load DumpRequest

ReadOnly

indicates a load dump is desired due to load exceed-ing derate level.

PC 2.x, PC3.x

0: Inactive1: Active

43766 PARCTL /Load Gov-ern

Load GovernkVAR RampState

ReadOnly

indicates status of load govern kVAR ramping control PC 3.x0: Not Applicable1: Ramp Load2: Track Target3: Ramp Unload4: Ramp Unload Complete

43767 PARCTL /Load Gov-ern

Load GovernkVAR Target

ReadOnly

Multiplier:0.01

Unit: % indicates the final targetsetpoint for genset kVARoutput when paralleled toutility

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43768 PARCTL /Load Gov-ern

Load GovernkW RampState

ReadOnly

indicates status of load govern kW ramping control PC 3.x0: Not Applicable1: Ramp Load2: Track Target3: Ramp Unload4: Ramp Unload Complete

43769 PARCTL /Load Gov-ern

Load GovernkW Target

ReadOnly

Multiplier:0.01

Unit: % indicates the final targetsetpoint for genset kWoutput when paralleled toutility

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

43770 PARCTL /Synchro-nizer

PermissiveClose Allowed

ReadOnly

indicates when permissive sync check conditionshave been met

PC 3.x

0: Not Allowed1: Allowed

43772 PARCTL /Synchro-nizer

PermissivePhase MatchError

ReadOnly

Multiplier:0.01

Unit: deg phase error signal for thepermissive sync check al-gorithm

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 189: Mapa de Registros de Pcc

182

Addr. ControlDescriptionAccessParameterName43773 PARCTL /

Synchro-nizer

Phase MatchError

ReadOnly

Multiplier:0.01

Unit: deg phase error signal for thesynchronizer control al-gorithm

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S43774 PARCTL /

LoadShare

Ramp Load/Unload Com-mand

ReadOnly

indicates overall status of ramp load unload inputs PC 3.x0: Load1: Unload

43775 PARCTL /Load Gov-ern

Utility Un-loaded Status

ReadOnly

indicates unloaded status of the utility source PC 3.x0: Not Available1: Not Unloaded2: Unloaded

43776 DSO / Dis-crete Out-puts

Genset CBClose Status

ReadOnly

Indicates if the output_s status is Inactive or Active PC 3.x0: Inactive1: Active

43777 DSI / Dis-crete In-puts

Start Type/ConfigurableInput #11Switch

ReadOnly

This is the status of the Configurable Input #11. PC 2.x, PC3.x0: Inactive

1: Active

43778 DR / Exer-ciseScheduler

SchedulerRun Com-mand

ReadOnly

Indicates the current run command coming from thescheduler.

PC 2.x, PC3.x

0: Off1: No Load2: With Load3: Extended Parallel

43789 DSI / Dis-crete In-puts

Backup StartDisconnect/ConfigurableInput #33Switch

ReadOnly

This is the status of the Configurable Input #33. PC 3.x

0: Inactive

1: Active

43790 DSI / Dis-crete In-puts

Backup StartDisconnectSwitch

ReadOnly

Status of the Backup Start Disconnect Switch Input PC 3.x0: Inactive1: Active

43791 DSI / Dis-crete In-puts

Battery Char-ger FailedSwitch

ReadOnly

Battery Charger Failed Switch function output status;gives software Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43785 DR / DataRecording

Start AttemptsSince Reset

Read/Write

Multiplier:1

Unit: Number of start attemptssince the last reset.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967290

Sign: U

Page 190: Mapa de Registros de Pcc

183

Addr. ControlDescriptionAccessParameterName43786 DR / Data

RecordingStart AttemptsSince Reset

Read/Write

Multiplier:1

Unit: Number of start attemptssince the last reset.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967290

Sign: U43787 DR / Data

RecordingTotal Start At-tempts

Read/Write

Multiplier:1

Unit: Total number of start at-tempts.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967295

Sign: U43788 DR / Data

RecordingTotal Start At-tempts

Read/Write

Multiplier:1

Unit: Total number of start at-tempts.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4294967295

Sign: U43792 DSI / Dis-

crete In-puts

Battle ShortSwitch

ReadOnly

Battle Short Switch function output status (Active orInactive).

PC 2.x, PC3.x

0: Inactive1: Active

43793 DSI / Dis-crete In-puts

ConfigurableInput #1Switch

ReadOnly

Configurable Input #1 input software state status.Gives software Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43794 DSI / Dis-crete In-puts

ConfigurableInput #2Switch

ReadOnly

Configurable Input #2 input software state status.Gives software Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43795 DSI / Dis-crete In-puts

ConfigurableInput #13Switch

ReadOnly

Configurable Input #13 input software state status.Gives software Inactive/Active state

PC 2.x, PC3.x

0: Inactive1: Active

43796 PARST /CircuitBreaker

Genset CBOpen Com-mand

ReadOnly

genset cb open command status PC 3.x0: Inactive1: Active

43797 PCCNet /Monitoringand Diag-nostics

Number ofConnectedBattery Char-gers

ReadOnly

Multiplier:1

Unit: Used to monitor theamount of connectedBattery Chargers.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 255

Sign: U

Page 191: Mapa de Registros de Pcc

184

Addr. ControlDescriptionAccessParameterName43800 GC / Start/

Stop Con-trol

Rated Cool-down Time

Read/Write

Multiplier:1

Unit: sec-onds

Minimum time to spendat rated speed less than10% load before normalshutdown is allowed

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 600

Sign: U43801 GC / Start/

Stop Con-trol

Rated to IdleTransitionDelay

Read/Write

Multiplier:0.1

Unit: sec-onds

Sets the delay time fortransitioning from Ratedto Idle speed. 0 seconds= feature is disabled.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: U43802 GC / Out-

putsRupture BasinTime

Read/Write

Multiplier:0.1

Unit: sec-onds

Rupture Basin fault timedelay

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 20

Sign: U43803 GC / Start/

Stop Con-trol

Start TimeDelay

Read/Write

Multiplier:1

Unit: sec-onds

Sets the time to wait fromreceiving a valid remotestart signal until startingthe genset

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 300

Sign: U43804 GC /

SpeedReference

Starting toRated RampTime

Read/Write

Multiplier:0.1

Unit: sec-onds

The time over which thespeed reference is toramp from starting speedto rated speed

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 30

Sign: U43805 GC / Start/

Stop Con-trol

Time Delay toStop

Read/Write

Multiplier:1

Unit: sec-onds

Sets time to run at ratedspeed before going tocooldown at idle. Doesnot apply to manual runs

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 600

Sign: U

Page 192: Mapa de Registros de Pcc

185

Addr. ControlDescriptionAccessParameterName43806 GC / Volt-

age Set-point

Voltage Adjust Read/Write

Multiplier:0.01

Unit: % A trim that allows theuser to add/subtract anoffset to the nominal volt-age when calculating thevoltage setpoint

PC 2.x, PC3.x

Offset: 0 Lower Limit: −5Size (bits):16

Upper Limit: 5

Sign: S

43807 GC / Volt-age Set-point

Voltage RampTime

Read/Write

Multiplier:0.01

Unit: sec-onds

The time period overwhich the voltage set-point command shouldrise from 0% to the targetvoltage

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 5

Sign: U

43810 Modbus /Modbus

Battle ShortSwitch (Mod-bus)

Read/Write

Trim to enable Battle Short via Modbus. PC 2.x, PC3.x0: Inactive

1: Active

43811 Modbus /Modbus

ExerciseSwitch (Mod-bus)

Read/Write

Modbus exercise switch PC 2.x, PC3.x0: Inactive

1: Active

43813 Modbus /Modbus

Extended Par-allel Switch(Modbus)

Read/Write

Modbus extended parallel switch PC 2.x, PC3.x0: Inactive

1: Active

43814 Modbus /Modbus

PTC ModeSwitch (Mod-bus)

Read/Write

Modbus PTC Mode switch PC 3.x0: Inactive1: Active

43815 Modbus /Modbus

Start Type(Modbus)

Read/Write

Modbus start type switch PC 2.x, PC3.x0: Emergency

1: Non Emergency

43816 PARCTL /Synchro-nizer

Sync Disable Read/Write

use to turn off synchronizer for testing purposes PC 3.x0: Inactive1: Active

43817 PARST /CircuitBreaker

Genset CB In-hibit Switch(Modbus)

Read/Write

genset cb inhibit from Modbus PC 3.x0: Inactive1: Active

43818 PARST /ParallelingControlMode

Isolated BusSpeed ControlMethod

Read/Write

Sets the speed control method for isolated bus paral-leling. Parameter is also known as Load Share SpeedDroop Control Method

PC 2.x, PC3.x

0: Constant1: Droop

43819 PARST /ParallelingControlMode

Isolated BusVoltage Con-trol Method

Read/Write

Sets the voltage control method for isolated bus par-alleling.

PC 2.x, PC3.x

0: Constant1: Droop

Page 193: Mapa de Registros de Pcc

186

Addr. ControlDescriptionAccessParameterName43820 PARST /

PTC Tim-ers

MaximumParallel Time(TDMP)

Read/Write

Multiplier:0.1

Unit: sec-onds

Sets the maximum timethat the genset can re-main paralleled to theutility during closed tran-sition transfers.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 1800

Sign: U

43821 PARST /PTC Tim-ers

ProgrammedTransition De-lay (TDPT)

Read/Write

Multiplier:0.1

Unit: sec-onds

Sets the time delay fromwhen one source opensuntil the other closes dur-ing open transition trans-fers.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 60

Sign: U

43822 PARST /PTC Tim-ers

RetransferDelay (TDEN)

Read/Write

Multiplier:0.1

Unit: sec-onds

Sets the amount of timethat the utility sourcemust be available beforethe control will retransferto that source.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 1800

Sign: U

43823 PARST /ParallelingControlMode

SynchronizerSpeed ControlMethod

Read/Write

Sets the speed control method for synchronizing. PC 3.x0: Phase Match1: Slip Frequency2: External

43824 PARST /ParallelingControlMode

SynchronizerVoltage Con-trol Method

Read/Write

Sets the voltage control method for synchronizing. PC 3.x

0: Voltage Match

1: External

43825 PARST /PTC Tim-ers

Transfer De-lay (TDNE)

Read/Write

Multiplier:0.1

Unit: sec-onds

Sets the amount of timethat the genset sourcemust be available beforethe control will transfer tothat source.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 120

Sign: U

43826 PARST /PTC StateMachine

TransitionType

Read/Write

Sets the load transfer transition type for use whenGenset Application Type = Power Transfer Control.

PC 3.x

0: Open Transition1: Hard Closed Transition2: Soft Closed Transition

Page 194: Mapa de Registros de Pcc

187

Addr. ControlDescriptionAccessParameterName43827 PARST /

PTC Inhib-its

Retransfer In-hibit Switch(Modbus)

Read/Write

retransfer inhibit switch input status from Modbus PC 3.x0: Inactive1: Active

43828 PARST /CircuitBreaker

Utility CB In-hibit Switch(Modbus)

Read/Write

utility cb inhibit from Modbus PC 3.x0: Inactive1: Active

43829 PARST /ParallelingControlMode

Utility ParallelSpeed ControlMethod

Read/Write

Sets the speed control method for utility paralleling. PC 3.x

0: Load Govern

1: Droop

43830 PARST /ParallelingControlMode

Utility ParallelVoltage Con-trol Method

Read/Write

Sets the voltage control method for utility paralleling. PC 3.x0: Load Govern1: Droop2: Load Govern with Droop Feed Forward

43831 PCCNet /I/O Module0 MainBoard

Aux101 De-vice 0PCCNet Fail-ure ResponseType

Read/Write

Selects the genset reaction to a loss of a Device 0 I/OModule as critical (Shutdown) or non−critical (Warn-ing).

PC 2.x, PC3.x

0: Critical Device Response1: Non−Critical Device Response

43832 PCCNet /I/O Module1 MainBoard

Aux101 De-vice 1PCCNet Fail-ure ResponseType

Read/Write

Selects the genset reaction to a loss of a Device 1 I/OModule as critical (Shutdown) or non−critical (Warn-ing).

PC 2.x, PC3.x

0: Critical Device Response1: Non−Critical Device Response

43834 PCCNet /UniversalAnnuncia-tor

HMI113 An-nunciatorPCCNet Fail-ure ResponseType

Read/Write

Selects the genset reaction to a loss of an Annuncia-tor as critical or non−critical. Selecting Critical willcause a shutdown when the Annunciator looses com-munication.

PC 2.x, PC3.x

0: Critical Device Response1: Non−Critical Device Response

43835 PCCNet /OperatorPanel

HMI1xxPCCNet Fail-ure ResponseType

Read/Write

Selects the genset reaction to a loss of an HMI1xx Op-erator Panel as critical or non−critical. A critical re-sponse will shutdown the genset when PCCNet com-munication is lost.

PC 2.x, PC3.x

0: Critical Device Response1: Non−Critical Device Response

43836 PCCNet /OperatorPanel

HMI220PCCNet Fail-ure ResponseType

Read/Write

Selects the genset reaction to a loss of an HMI220Operator Panel as critical or non−critical.. A critical re-sponse will shutdown the genset when PCCNet com-munication is lost.

PC 2.x, PC3.x

0: Critical Device Response1: Non−Critical Device Response

43837 PCCNet /OperatorPanel

HMI320PCCNet Fail-ure ResponseType

Read/Write

Selects the genset reaction to a loss of an HMI320Operator Panel as critical or non−critical.. A critical re-sponse will shutdown the genset when PCCNet com-munication is lost.

PC 2.x, PC3.x

0: Critical Device Response1: Non−Critical Device Response

Page 195: Mapa de Registros de Pcc

188

Addr. ControlDescriptionAccessParameterName43838 PCCNet /

OperatorPanel

HMI4xxPCCNet Fail-ure ResponseType

Read/Write

Selects the genset reaction to a loss of an HMI4xx Op-erator Panel as critical or non−critical.. A critical re-sponse will shutdown the genset when PCCNet com-munication is lost.

PC 2.x, PC3.x

0: Critical Device Response1: Non−Critical Device Response

43839 PCCNet /Monitoringand Diag-nostics

PCCNet De-vice FailureTime Delay

Read/Write

Multiplier:1

Unit: sec-onds

Selects the time allowedfor arbitration to occurbefore a PCCNet failurefault is generated.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):8

Upper Limit: 250

Sign: U43840 PARST /

PTC En-ables

Test WithLoad Enable

Read/Write

Use to choose whether a test is with load or withoutload.

PC 3.x

0: Disabled1: Enabled

43841 PARST /PTC Inhib-its

Transfer In-hibit Switch(Modbus)

Read/Write

transfer inhibit switch input status from Modbus PC 3.x0: Inactive1: Active

43845 Modbus /Modbus

Modbus Fail-ure TimeDelay

Read/Write

Multiplier:1

Unit: sec-onds

Time delay before thecontrol activates the Mo-dus failure fault after themaster is sensed as nolonger present.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: U43846 Modbus /

ModbusModbus Com-municationsLost Re-sponse Meth-od

Read/Write

When set to Reset Commands will reset the Moduscontrol logics to an inactive state when Modbus com-munications are lost

PC 2.x, PC3.x

0: Do Nothing1: Reset Commands

43847 Modbus /Modbus

Modbus ClearCounters

Read/Write

Resets all Modus counters including J14 if applicable. PC 2.x, PC3.x0: Do Nothing

1: Clear Counters43848 PARCTL /

Load Gov-ern

ControlledShutdownMax RampUnload Time

Read/Write

Multiplier:1

Unit: sec-onds

maximum ramp unloadtime during a shutdownwith cooldown

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 300

Sign: U

Page 196: Mapa de Registros de Pcc

189

Addr. ControlDescriptionAccessParameterName43849 PARCTL /

Load Gov-ern

Genset kVARSetpoint

Read/Write

Multiplier:1

Unit: kVAR Sets the genset load gov-ern kVAR base load inter-nal operating setpoint inunits of kVAR. Requiresthat Load Govern kVARSetpoint Source = Inter-nal and Load GovernkVAR Method = GensetkVAR.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 20000

Sign: S

43850 PARCTL /Load Gov-ern

Genset kVARSetpoint Per-cent

Read/Write

Multiplier:0.01

Unit: % Sets the genset load gov-ern kVAR base load inter-nal operating setpoint in% of standby kVA rating.Requires that Load Gov-ern kVAR SetpointSource = Internal andLoad Govern kVAR Meth-od = Genset kVAR.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 60

Sign: S

43851 PARCTL /Load Gov-ern

Genset kWSetpoint

Read/Write

Multiplier:1

Unit: kW Sets the genset load gov-ern kW base load internaloperating setpoint in unitsof kW. Requires thatLoad Govern kW Set-point Source = Internaland Load Govern kWMethod = Genset kW.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 20000

Sign: S

43852 PARCTL /Load Gov-ern

Genset kWSetpoint Per-cent

Read/Write

Multiplier:0.01

Unit: % Sets the genset load gov-ern kW base load internaloperating setpoint in % ofstandby rating. Requiresthat Load Govern kWSetpoint Source = Inter-nal and Load Govern kWMethod = Genset kW.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 100

Sign: S

Page 197: Mapa de Registros de Pcc

190

Addr. ControlDescriptionAccessParameterName43853 PARCTL /

Load Gov-ern

Genset PowerFactor Set-point

Read/Write

Multiplier:0.01

Unit: PF Sets the load govern set-point for genset powerfactor control. Requiresthat Load Govern kVARSetpoint Source = Inter-nal and Load GovernkVAR Method = GensetPower Factor.

PC 3.x

Offset: 0 Lower Limit: 0.7Size (bits):8

Upper Limit: 1

Sign: S43854 PARCTL /

Load De-mand

Load DemandStop (Mod-bus)

Read/Write

Modbus input for activating load demand stop on thegenset

PC 3.x

0: Inactive1: Active

43855 PARCTL /Load Gov-ern

Load GovernkVAR Method

Read/Write

Use to select how genset kVAR output will be con-trolled when paralleled to utility.

PC 3.x

0: Genset kVAR1: Genset Power Factor2: Utility kVAR3: Utility Power Factor

43856 PARCTL /Load Gov-ern

Load GovernkVAR RampLoad Time

Read/Write

Multiplier:1

Unit: sec-onds

Sets load govern kVARramp load rate = GensetStandby kVA * 0.6/ thistime.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 900

Sign: U43857 PARCTL /

Load Gov-ern

Load GovernkVAR RampUnload Time

Read/Write

Multiplier:1

Unit: sec-onds

Sets load govern kVARramp unload rate = Gen-set Standby KVA * 0.6/this time.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 900

Sign: U43859 PARCTL /

Load Gov-ern

Load GovernkW RampLoad Time

Read/Write

Multiplier:1

Unit: sec-onds

Sets load govern kWramp load rate = GensetStandby kW rating/ thistime.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 900

Sign: U

Page 198: Mapa de Registros de Pcc

191

Addr. ControlDescriptionAccessParameterName43860 PARCTL /

Load Gov-ern

Load GovernkW Ramp Un-load Time

Read/Write

Multiplier:1

Unit: sec-onds

Sets load govern kWramp unload rate = Gen-set Standby kW rating/this time.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 900

Sign: U43861 PARCTL /

LoadShare

Ramp Load/Unload (Mod-bus)

Read/Write

use to control ramp load and unload via Modbus PC 3.x0: Load1: Unload

43862 PARCTL /Synchro-nizer

Slip Frequen-cy

Read/Write

Multiplier:0.001

Unit: Hz Sets the synchronizer slipfrequency. Requires thatSync Speed ControlMethod = Slip Frequency.

PC 3.x

Offset: 0 Lower Limit: −3Size (bits):16

Upper Limit: 3

Sign: S43863 PARCTL /

Load Gov-ern

Utility kVARSetpoint

Read/Write

Multiplier:1

Unit: kVAR Sets the utility kVAR peakshave internal operatingsetpoint in units of kVAR.Requires that Load Gov-ern kVAR SetpointSource = Internal andLoad Govern kVAR Meth-od = Utility kVAR

PC 3.x

Offset: 0 Lower Limit: −20000Size (bits):16

Upper Limit: 20000

Sign: S43864 PARCTL /

Load Gov-ern

Utility kVARSetpoint Per-cent

Read/Write

Multiplier:0.01

Unit: % Sets the utility kVAR peakshave internal operatingsetpoint in % of gensetstandby kVA rating. Re-quires that Load GovernkVAR Setpoint Source =Internal and Load GovernkVAR Method = UtilitykVAR.

PC 3.x

Offset: 0 Lower Limit: −320Size (bits):16

Upper Limit: 320

Sign: S

Page 199: Mapa de Registros de Pcc

192

Addr. ControlDescriptionAccessParameterName43865 PARCTL /

Load Gov-ern

Utility kWConstraint

Read/Write

Multiplier:1

Unit: kW Sets the utility kW mini-mum load level forconstrained base loadmode of operation. Re-quires that Load GovernkW Setpoint Source = In-ternal and Load GovernkW Method = Genset kWw/Utility Constraint.

PC 3.x

Offset: 0 Lower Limit: −20000Size (bits):16

Upper Limit: 20000

Sign: S

43866 PARCTL /Load Gov-ern

Utility kWConstraintPercent

Read/Write

Multiplier:0.01

Unit: % Sets utility kW minimumload level for constrainedbase load mode in % ofgenset standby rating.Requires that Load Gov-ern kW Setpoint Source =Internal and Load GovernkW Method = Genset kWw/Utility Constraint.

PC 3.x

Offset: 0 Lower Limit: −320Size (bits):16

Upper Limit: 320

Sign: S

43867 PARCTL /Load Gov-ern

Utility kW Set-point

Read/Write

Multiplier:1

Unit: kW Sets the utility kW peakshave internal operatingsetpoint in units of kW.Requires that Load Gov-ern kW Setpoint Source =Internal and Load GovernkW Method = Utility kW.

PC 3.x

Offset: 0 Lower Limit: −20000Size (bits):16

Upper Limit: 20000

Sign: S

43868 PARCTL /Load Gov-ern

Utility kW Set-point Percent

Read/Write

Multiplier:0.01

Unit: % Sets the utility kW peakshave internal operatingsetpoint in % of gensetstandby rating. Requiresthat Load Govern kWSetpoint Source = Inter-nal and Load Govern kWMethod = Utility kW.

PC 3.x

Offset: 0 Lower Limit: −320Size (bits):16

Upper Limit: 320

Sign: S

Page 200: Mapa de Registros de Pcc

193

Addr. ControlDescriptionAccessParameterName43869 PARCTL /

Load Gov-ern

Utility PowerFactor Set-point

Read/Write

Multiplier:0.01

Unit: PF Sets the internal setpointfor utility power factorcontrol mode when paral-leled to utility. Requiresthat Load Govern kVARSetpoint Source = Inter-nal and Load GovernkVAR Method = UtilityPower Factor.

PC 3.x

Offset: 0 Lower Limit: 0.7Size (bits):8

Upper Limit: 1

Sign: S

43870 PCCNet /I/O Module0 MainBoard

Aux101 0Output 2Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

43871 PCCNet /I/O Module0 MainBoard

Aux101 0Output 4Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

43872 PCCNet /I/O Module0 MainBoard

Aux101 0Output 5Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

43873 PCCNet /I/O Module0 MainBoard

Aux101 0Output 6Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 201: Mapa de Registros de Pcc

194

Addr. ControlDescriptionAccessParameterName43874 PCCNet /

I/O Module0 MainBoard

Aux101 0Output 7Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U43875 PCCNet /

I/O Module1 MainBoard

Aux101 1Output 1Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43876 PCCNet /

I/O Module1 MainBoard

Aux101 1Output 2Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43877 PCCNet /

I/O Module1 MainBoard

Aux101 1Output 3Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43878 PCCNet /

I/O Module1 MainBoard

Aux101 1Output 4Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 202: Mapa de Registros de Pcc

195

Addr. ControlDescriptionAccessParameterName43879 PCCNet /

I/O Module1 MainBoard

Aux101 1Output 5Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43880 PCCNet /

I/O Module1 MainBoard

Aux101 1Output 6Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43881 PCCNet /

I/O Module1 MainBoard

Aux101 1Output 7Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43882 PCCNet /

I/O Module1 MainBoard

Aux101 1Output 8Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43883 PCCNet /

I/O Module0 Exp.Board

Aux102 0Output 10Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 203: Mapa de Registros de Pcc

196

Addr. ControlDescriptionAccessParameterName43884 PCCNet /

I/O Module0 Exp.Board

Aux102 0Output 11Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43885 PCCNet /

I/O Module0 Exp.Board

Aux102 0Output 12Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43886 PCCNet /

I/O Module0 Exp.Board

Aux102 0Output 13Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43887 PCCNet /

I/O Module0 Exp.Board

Aux102 0Output 14Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43888 PCCNet /

I/O Module0 Exp.Board

Aux102 0Output 15Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 204: Mapa de Registros de Pcc

197

Addr. ControlDescriptionAccessParameterName43889 PCCNet /

I/O Module0 Exp.Board

Aux102 0Output 16Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43890 PCCNet /

I/O Module0 Exp.Board

Aux102 0Output 9Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43891 PCCNet /

I/O Module1 Exp.Board

Aux102 1Output 10Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43892 PCCNet /

I/O Module1 Exp.Board

Aux102 1Output 11Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43893 PCCNet /

I/O Module1 Exp.Board

Aux102 1Output 12Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 205: Mapa de Registros de Pcc

198

Addr. ControlDescriptionAccessParameterName43894 PCCNet /

I/O Module1 Exp.Board

Aux102 1Output 13Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43895 PCCNet /

I/O Module1 Exp.Board

Aux102 1Output 14Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43896 PCCNet /

I/O Module1 Exp.Board

Aux102 1Output 15Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43897 PCCNet /

I/O Module1 Exp.Board

Aux102 1Output 16Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43898 PCCNet /

I/O Module1 Exp.Board

Aux102 1Output 9Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 206: Mapa de Registros de Pcc

199

Addr. ControlDescriptionAccessParameterName43900 PCCNet /

UniversalAnnuncia-tor

HMI113 Out-put 1 Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

43901 PCCNet /UniversalAnnuncia-tor

HMI113 Out-put 2 Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

43902 PCCNet /UniversalAnnuncia-tor

HMI113 Out-put 3 Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

43903 PCCNet /UniversalAnnuncia-tor

HMI113 Out-put 4 Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

43906 PARST /ParallelingControlMode

Speed DroopEnable Switch(Modbus)

Read/Write

speed droop enable switch input status from Modbus PC 2.x, PC3.x0: Inactive

1: Active

43907 PARST /ParallelingControlMode

Voltage DroopEnable Switch(Modbus)

Read/Write

Voltage droop enable switch input status from Mod-bus

PC 2.x, PC3.x

0: Inactive1: Active

43908 PARST /CircuitBreaker

Genset CBTrippedSwitch (Mod-bus)

Read/Write

genset cb tripped from Modbus PC 3.x

0: Inactive

1: Active

Page 207: Mapa de Registros de Pcc

200

Addr. ControlDescriptionAccessParameterName43909 PARST /

CircuitBreaker

Utility CBTrippedSwitch (Mod-bus)

Read/Write

utility cb tripped switch input from Modbus PC 3.x

0: Inactive

1: Active

43910 PC Tool /Non−View-able

Save Trims Read/Write

The save trims command. PC 2.x, PC3.x0: Do Nothing

1: Save Trims43911 PCCNet /

I/O Module0 MainBoard

Aux101 0Output 3Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43912 PCCNet /

I/O Module0 MainBoard

Aux101 0Output 1Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U43913 PCCNet /

I/O Module0 MainBoard

Aux101 0Output 8Fault/Event

Read/Write

Multiplier:1

Unit: Parameter to allow forthe entry of the fault/event code which will turnthe output relay on andoff.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U43915 GC / Start/

Stop Con-trol

Extended Par-allel Enable

Read/Write

use to enable the extended paralleling mode of PTC PC 3.x0: Disabled1: Enabled

Page 208: Mapa de Registros de Pcc

201

Addr. ControlDescriptionAccessParameterName43916 GC / Volt-

age Set-point

V/Hz KneeFrequency50Hz

Read/Write

Multiplier:0.1

Unit: Hz The voltage will roll off(decrease) proportionallyto the V/Hz setup oncethe frequency drops be-low the set point in theV/Hz Knee Frequency.This allows the genset torecover faster when thefrequency drops. This isfor 50Hz frequency.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: U

43917 GC / Volt-age Set-point

V/Hz KneeFrequency60Hz

Read/Write

Multiplier:0.1

Unit: Hz The voltage will roll off(decrease) proportionallyto the V/Hz setup oncethe frequency drops be-low the set point in theV/Hz Knee Frequency.This allows the genset torecover faster when thefrequency drops. This isfor 60Hz frequency.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: U

43918 GC / Volt-age Set-point

V/Hz RolloffSlope 50Hz

Read/Write

Multiplier:0.1

Unit: % /Hz

The amount of voltageroll off when the frequen-cy is below the knee fre-quency

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: U

43919 GC / Volt-age Set-point

V/Hz RolloffSlope 60Hz

Read/Write

Multiplier:0.1

Unit: % /Hz

The amount of voltageroll off when the frequen-cy is below the knee fre-quency

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 10

Sign: U

43920 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 209: Mapa de Registros de Pcc

202

Addr. ControlDescriptionAccessParameterName43921 ACM / Ap-

plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43922 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43923 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43924 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43925 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43926 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43927 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43928 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 210: Mapa de Registros de Pcc

203

Addr. ControlDescriptionAccessParameterName43929 ACM / Ap-

plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43930 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43931 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43932 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43933 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43934 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43935 ACM / Ap-plicationConfigura-tion

GensetSource Name

Read/Write

Multiplier:1

Unit: Name for the gensetsource.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43936 ACM / Ap-plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 211: Mapa de Registros de Pcc

204

Addr. ControlDescriptionAccessParameterName43937 ACM / Ap-

plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43938 ACM / Ap-plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43939 ACM / Ap-plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43940 ACM / Ap-plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43941 ACM / Ap-plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43942 ACM / Ap-plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43943 ACM / Ap-plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

43944 ACM / Ap-plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 212: Mapa de Registros de Pcc

205

Addr. ControlDescriptionAccessParameterName43945 ACM / Ap-

plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C43946 ACM / Ap-

plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C43947 ACM / Ap-

plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C43948 ACM / Ap-

plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C43949 ACM / Ap-

plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C43950 ACM / Ap-

plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C43951 ACM / Ap-

plicationConfigura-tion

Utility SourceName

Read/Write

Multiplier:1

Unit: Name for the Utilitysource

PC 3.x

Offset: 0 Lower Limit:Size (bits):136

Upper Limit:

Sign: C

Page 213: Mapa de Registros de Pcc

206

Addr. ControlDescriptionAccessParameterName43952 GC /

SpeedReference

Speed/Fre-quency Delay

Read/Write

Multiplier:0.1

Unit: sec-onds

Sets the delay time forgenerating the Speed/Frequency mismatchfault

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0.5Size (bits):16

Upper Limit: 10

Sign: U

43953 GC /SpeedReference

Speed/Fre-quencyThreshold

Read/Write

Multiplier:0.1

Unit: Hz Sets the threshold forgenerating the Speed/Frequency mismatchfault

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0.5Size (bits):16

Upper Limit: 20

Sign: U

43954 PARCTL /Synchro-nizer

Sync Enable(Modbus)

Read/Write

Modbus input for enabling the synchronizer PC 3.x0: Inactive1: Active

43955 GC / Start/Stop Con-trol

Genset IdleEnable

Read/Write

Enables or Disable idling of genset with external gov-ernor.

PC 2.x, PC3.x

0: Disabled1: Enabled

43956 PARCTL /Synchro-nizer

PermissiveFrequencyMatch Error

ReadOnly

Multiplier:0.001

Unit: Hz frequency match errorvalue used by permissivesync check

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

43957 PARCTL /Synchro-nizer

PermissiveFrequencyMatch Error

ReadOnly

Multiplier:0.001

Unit: Hz frequency match errorvalue used by permissivesync check

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

43958 PARCTL /Synchro-nizer

Sync EnableCommand

ReadOnly

indicates overall status of sync enable inputs PC 3.x0: Inactive1: Active

43959 PARCTL /Load Gov-ern

Utility Un-loaded Level

Read/Write

Multiplier:1

Unit: kW Sets threshold at whichutility source is consid-ered as unloaded.

PC 3.x

Offset: 0 Lower Limit: −32768Size (bits):16

Upper Limit: 32767

Sign: S

Page 214: Mapa de Registros de Pcc

207

Addr. ControlDescriptionAccessParameterName43960 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43961 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43962 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43963 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43964 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43965 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 215: Mapa de Registros de Pcc

208

Addr. ControlDescriptionAccessParameterName43966 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43967 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43968 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43969 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43970 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43971 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 216: Mapa de Registros de Pcc

209

Addr. ControlDescriptionAccessParameterName43972 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43973 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43974 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43975 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43976 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43977 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 217: Mapa de Registros de Pcc

210

Addr. ControlDescriptionAccessParameterName43978 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43979 PCCNet /UniversalAnnuncia-tor

HMI113 Fault1 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43980 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43981 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43982 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43983 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 218: Mapa de Registros de Pcc

211

Addr. ControlDescriptionAccessParameterName43984 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43985 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43986 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43987 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43988 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43989 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 219: Mapa de Registros de Pcc

212

Addr. ControlDescriptionAccessParameterName43990 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43991 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43992 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43993 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43994 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43995 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 220: Mapa de Registros de Pcc

213

Addr. ControlDescriptionAccessParameterName43996 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43997 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43998 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

43999 PCCNet /UniversalAnnuncia-tor

HMI113 Fault2 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

45999 CAN /CANDatalink

UnrecognizedSPN/FMI Sta-tus

ReadOnly

Indicates whether or not all pairs in current DM1 arerecognized

PC 2.x, PC3.x

0: All Pairs Recognized1: Pair Not Recognized

46000 ACM /Phase

Genset PhaseRotation

ReadOnly

Genset phase rotation PC 2.x, PC3.x0: L1−L2−L3

1: L1−L3−L22: Not Available

46001 ACM /Phase

Utility PhaseRotation

ReadOnly

Utility phase rotation PC 3.x0: L1−L2−L31: L1−L3−L22: Not Available

46002 ACM /Phase

Genset BusPhase Rota-tion

ReadOnly

Genset bus phase rotation PC 3.x0: L1−L2−L31: L1−L3−L22: Not Available

Page 221: Mapa de Registros de Pcc

214

Addr. ControlDescriptionAccessParameterName46003 GC /

SpeedReference

Base Speed ReadOnly

Multiplier:0.0625

Unit: rpm Provides a point to moni-tor the base speed

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U46004 GC /

SpeedReference

Base Speed ReadOnly

Multiplier:0.0625

Unit: rpm Provides a point to moni-tor the base speed

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U46005 GC /

SpeedReference

Final SpeedReference

ReadOnly

Multiplier:0.0625

Unit: rpm Provides a point to moni-tor the final speed refer-ence

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U46006 GC /

SpeedReference

Final SpeedReference

ReadOnly

Multiplier:0.0625

Unit: rpm Provides a point to moni-tor the final speed refer-ence

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U46008 CAN /

CAN InputMessages

Exhaust Port1 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 1 Temperature

PC 2.x, PC3.x

Offset: 0 Lower Limit: −459Size (bits):16

Upper Limit: 3155

Sign: S46009 CAN /

CAN InputMessages

Exhaust Port2 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 2 Temperature

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S46010 CAN /

CAN InputMessages

Exhaust Port3 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 3 Temperature

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S

Page 222: Mapa de Registros de Pcc

215

Addr. ControlDescriptionAccessParameterName46011 CAN /

CAN InputMessages

Exhaust Port4 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 4 Temperature

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S46012 CAN /

CAN InputMessages

Exhaust Port5 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 5 Temperature

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S46013 CAN /

CAN InputMessages

Exhaust Port6 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 6 Temperature

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S46014 CAN /

CAN InputMessages

Exhaust Port7 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 7 Temperature

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S46015 CAN /

CAN InputMessages

Exhaust Port8 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 8 Temperature

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S46016 CAN /

CAN InputMessages

Exhaust Port9 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 9 Temperature

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S46017 CAN /

CAN InputMessages

Exhaust Port10 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 10 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S

Page 223: Mapa de Registros de Pcc

216

Addr. ControlDescriptionAccessParameterName46018 CAN /

CAN InputMessages

Exhaust Port11 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 11 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S

46019 CAN /CAN InputMessages

Exhaust Port12 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 12 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S

46020 CAN /CAN InputMessages

Exhaust Port13 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 13 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S

46021 CAN /CAN InputMessages

Exhaust Port14 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 14 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S

46022 CAN /CAN InputMessages

Exhaust Port15 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 15 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S

46023 CAN /CAN InputMessages

Exhaust Port16 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 16 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S

46024 CAN /CAN InputMessages

Exhaust Port17 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 17 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S

Page 224: Mapa de Registros de Pcc

217

Addr. ControlDescriptionAccessParameterName46025 CAN /

CAN InputMessages

Exhaust Port18 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 18 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S46026 CAN /

CAN InputMessages

Exhaust Port19 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 19 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S46027 CAN /

CAN InputMessages

Exhaust Port20 Tempera-ture

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the Ex-haust Port 20 Tempera-ture

PC 2.x, PC3.x

Offset: 0 Lower Limit: −460Size (bits):16

Upper Limit: 3155

Sign: S46028 CAN_LBN

G / CANGas InputMessages

Knock LevelCylinder 1

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder1

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U46029 CAN_LBN

G / CANGas InputMessages

Knock LevelCylinder 2

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder2

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U46030 CAN_LBN

G / CANGas InputMessages

Knock LevelCylinder 3

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder3

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U46031 CAN_LBN

G / CANGas InputMessages

Knock LevelCylinder 4

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder4

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

Page 225: Mapa de Registros de Pcc

218

Addr. ControlDescriptionAccessParameterName46032 CAN_LBN

G / CANGas InputMessages

Knock LevelCylinder 5

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder5

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46033 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 6

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder6

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46034 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 7

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder7

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46035 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 8

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder8

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46036 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 9

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder9

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46037 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 10

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder10

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46038 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 11

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder11

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46039 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 12

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder12

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

Page 226: Mapa de Registros de Pcc

219

Addr. ControlDescriptionAccessParameterName46040 CAN_LBN

G / CANGas InputMessages

Knock LevelCylinder 13

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder13

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46041 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 14

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder14

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46042 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 15

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder15

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46043 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 16

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder16

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46044 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 17

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder17

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46045 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 18

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder18

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46046 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 19

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder19

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

46047 CAN_LBNG / CANGas InputMessages

Knock LevelCylinder 20

ReadOnly

Multiplier:1

Unit: % Knock Level for cylinder20

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

Page 227: Mapa de Registros de Pcc

220

Addr. ControlDescriptionAccessParameterName46048 CAN_LBN

G / CANGas InputMessages

Knock CountCyl 1

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 1

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46049 CAN_LBNG / CANGas InputMessages

Knock CountCyl 2

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 2

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46050 CAN_LBNG / CANGas InputMessages

Knock CountCyl 3

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 3

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46051 CAN_LBNG / CANGas InputMessages

Knock CountCyl 4

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 4

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46052 CAN_LBNG / CANGas InputMessages

Knock CountCyl 5

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 5

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46053 CAN_LBNG / CANGas InputMessages

Knock CountCyl 6

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 6

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46054 CAN_LBNG / CANGas InputMessages

Knock CountCyl 7

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 7

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46055 CAN_LBNG / CANGas InputMessages

Knock CountCyl 8

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 8

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 228: Mapa de Registros de Pcc

221

Addr. ControlDescriptionAccessParameterName46056 CAN_LBN

G / CANGas InputMessages

Knock CountCyl 9

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 9

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46057 CAN_LBNG / CANGas InputMessages

Knock CountCyl 10

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 10

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46058 CAN_LBNG / CANGas InputMessages

Knock CountCyl 11

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 11

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46059 CAN_LBNG / CANGas InputMessages

Knock CountCyl 12

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 12

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46060 CAN_LBNG / CANGas InputMessages

Knock CountCyl 13

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 13

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46061 CAN_LBNG / CANGas InputMessages

Knock CountCyl 14

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 14

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46062 CAN_LBNG / CANGas InputMessages

Knock CountCyl 15

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 15

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46063 CAN_LBNG / CANGas InputMessages

Knock CountCyl 16

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 16

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

Page 229: Mapa de Registros de Pcc

222

Addr. ControlDescriptionAccessParameterName46064 CAN_LBN

G / CANGas InputMessages

Knock CountCyl 17

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 17

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46065 CAN_LBNG / CANGas InputMessages

Knock CountCyl 18

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 18

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46066 CAN_LBNG / CANGas InputMessages

Knock CountCyl 19

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 19

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46067 CAN_LBNG / CANGas InputMessages

Knock CountCyl 20

ReadOnly

Multiplier:1

Unit: Knock count value forCylinder 20

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65530

Sign: U

46068 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 1

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 1

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46069 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 2

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 2

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46070 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 3

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 3

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46071 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 4

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 4

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 230: Mapa de Registros de Pcc

223

Addr. ControlDescriptionAccessParameterName46072 CAN_LBN

G / CANGas InputMessages

Spark TimingCyl 5

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 5

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46073 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 6

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 6

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46074 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 7

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 7

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46075 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 8

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 8

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46076 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 9

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 9

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46077 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 10

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 10

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46078 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 11

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 11

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46079 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 12

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 12

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 231: Mapa de Registros de Pcc

224

Addr. ControlDescriptionAccessParameterName46080 CAN_LBN

G / CANGas InputMessages

Spark TimingCyl 13

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 13

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46081 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 14

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 14

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46082 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 15

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 15

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46083 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 16

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 16

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46084 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 17

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 17

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46085 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 18

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 18

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46086 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 19

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 19

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46087 CAN_LBNG / CANGas InputMessages

Spark TimingCyl 20

ReadOnly

Multiplier:0.1

Unit: De-grees

Spark timing degrees forcylinder 20

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

Page 232: Mapa de Registros de Pcc

225

Addr. ControlDescriptionAccessParameterName46088 CAN_LBN

G / CANGas InputMessages

InternalSSM558 1Temperature

ReadOnly

Multiplier:0.1

Unit: degF Temperature of the en-gine electronic controlunit SSM558 1

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S46089 CAN_LBN

G / CANGas InputMessages

InternalSSM558 2Temperature

ReadOnly

Multiplier:0.1

Unit: degF Temperature of the en-gine electronic controlunit SSM558 2

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S46090 CAN_LBN

G / CANGas InputMessages

InternalMCM700Temperature

ReadOnly

Multiplier:0.1

Unit: degF Temperature of the en-gine electronic controlunit MCM700

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S46091 CAN_LBN

G / CANGas InputMessages

Derate Autho-rization

ReadOnly

Derate authorization request from customer. PC 3.x0: NO1: YES2: Reserved3: N/A

46092 CAN_LBNG / CANGas InputMessages

Start SystemStatus

ReadOnly

Start system status monitor point. PC 3.x0: Not Tripped1: Tripped2: Reserved3: N/A

46093 CAN_LBNG / CANGas InputMessages

Ventilator FanStatus

ReadOnly

Vent Fan status monitor point. PC 3.x0: OFF1: ON2: TRIPPED3: N/A

46094 CAN_LBNG / CANGas InputMessages

Louvres Sta-tus

ReadOnly

Louvres Closed monitor point. PC 3.x0: Open1: Closed2: Reserved3: N/A

46095 CAN_LBNG / CANGas InputMessages

Radiator FanStatus

ReadOnly

Radiator Fan status monitor point. PC 3.x0: OFF1: ON2: TRIPPED3: N/A

Page 233: Mapa de Registros de Pcc

226

Addr. ControlDescriptionAccessParameterName46096 CAN_LBN

G / CANGas InputMessages

GIB IsolatorOpen(Aux101)

ReadOnly

GIB Isolator Open monitor point. PC 3.x0: Close1: Open2: Reserved3: N/A

46097 AD_LBNG/ LBNGAuxiliaryDevices

AlternatorHeater Status

ReadOnly

Alternator Heater status monitor point. PC 3.x0: OFF1: ON2: TRIPPED3: N/A

46099 CAN_LBNG / CANGas InputMessages

Gearbox OilPressure(Aux101)

ReadOnly

Gearbox Oil Pressure monitor point. PC 3.x

0: No

1: Yes

46100 CAN_LBNG / CANGas InputMessages

Gearbox OilTemperature(Aux101)

ReadOnly

Gearbox Oil Temperature monitor point. PC 3.x

0: No

1: Yes

46101 CAN_LBNG / CANGas InputMessages

Start InhibitNo1 (Aux101)

ReadOnly

Start Inhibit No1 monitor point. PC 3.x0: Inactive1: Active2: Reserved3: N/A

46102 CAN_LBNG / CANGas InputMessages

Start InhibitNo2 (Aux101)

ReadOnly

Start Inhibit No2 monitor point. PC 3.x0: Inactive1: Active2: Reserved3: N/A

46103 CAN_LBNG / CANGas InputMessages

Start InhibitNo3 (Aux101)

ReadOnly

Start Inhibit No3 monitor point. PC 3.x0: Inactive1: Active2: Reserved3: N/A

46104 CAN_LBNG / CANGas InputMessages

DC PSU Un-available(Aux101)

ReadOnly

Engine PSU Not Available monitor point. PC 3.x

0: No

1: Yes

46105 CAN_LBNG / CANGas InputMessages

Ventilator FanTrip (Aux101)

ReadOnly

Ventilator Fan Trip monitor point. PC 3.x

0: No

1: Yes

46106 CAN_LBNG / CANGas InputMessages

Aux101−3Software Ver-sion

ReadOnly

Multiplier:0.01

Unit: Software version of thefirmware for theAux101−3

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 234: Mapa de Registros de Pcc

227

Addr. ControlDescriptionAccessParameterName46107 CAN_LBN

G /Aux101−4Software Ver-sion

ReadOnly

Multiplier:0.01

Unit: Software version of thefirmware for theAux101−4

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46108 CAN_LBN

G /Aux101−5Software Ver-sion

ReadOnly

Multiplier:0.01

Unit: Software version of thefirmware for theAux101−5

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46109 CAN_LBN

G / CANGas InputMessages

Engine Oper-ating State

ReadOnly

Indicate current state or mode of operation by the en-gine

PC 3.x

0: Engine Stopped1: Pre−Start2: Starting3: Warm−Up4: Running5: Cool−Down6: Engine Stopping7: Post−Run

46110 CAN_LBNG / CANGas InputMessages

Fuel PumpControl Status

ReadOnly

Fuel pump state PC 3.x

0: Inactive

1: Active

46111 CAN_LBNG / CANGas InputMessages

Time Remain-ing in EngineOperatingState

ReadOnly

Multiplier:1

Unit: sec-onds

Indicate time remaining inthe current engine state

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46112 CAN_LBN

G / CANGas InputMessages

Fuel ShutoffVent Valvestatus

ReadOnly

Fuel shutoff valve status PC 3.x

0: Closed

1: Open

46113 CAN_LBNG / CANGas InputMessages

DownstreamValve Com-mand Status

ReadOnly

The result of the FSO driver output command logic forfuel shutoff valve 1

PC 3.x

0: Closed1: Open2: Reserved3: N/A

46114 CAN_LBNG / CANGas InputMessages

UpstreamValve Com-mand Status

ReadOnly

The result of the FSO driver output command logic forfuel shutoff valve 2

PC 3.x

0: Closed1: Open2: Reserved3: N/A

Page 235: Mapa de Registros de Pcc

228

Addr. ControlDescriptionAccessParameterName46115 CAN_LBN

G / CANGas InputMessages

VPS Status ReadOnly

Control setting for fuel shutoff valve proving systemtest

PC 3.x

0: Not Tested1: Pass2: Reserved3: FAIL

46116 CAN_LBNG / CANGas InputMessages

Gas SupplyPressure

ReadOnly

Multiplier:0.1

Unit: psi Gage Pressure of gassupply to fuel meteringdevice.

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46117 CAN_LBNG / CANGas InputMessages

Engine OilPreHeater CtrlStatus

ReadOnly

Engine Oil pre heater command status PC 3.x0: OFF1: ON2: Reserved3: N/A

46118 CAN_LBNG / CANGas InputMessages

Engine PowerConservationCtrl Status

ReadOnly

Control setting for cutting power to various deviceswhen the engine is not in use

PC 3.x

0: OFF1: ON

46119 CAN_LBNG / CANGas InputMessages

Engine Cool-ant PreHeaterCtrl Status

ReadOnly

Engine coolant PreHeater states PC 3.x0: OFF1: ON2: Reserved3: N/A

46120 CAN_LBNG / CANGas InputMessages

Engine Cool-ant Pump CtrlStatus

ReadOnly

Engine coolant circulating pump status PC 3.x0: OFF1: ON2: Reserved3: N/A

46121 CAN_LBNG / CANGas InputMessages

Engine Con-trolled Shut-down Request

ReadOnly

Active when the engine control request a controlledshutdown (shutdown with cooldown)

PC 3.x

0: Inactive1: Active

46122 CAN_LBNG / CANGas InputMessages

EmergencyShutdown Re-quest

ReadOnly

Active when the engine control request an emergen-cy shutdown (immediate shutdown)

PC 3.x

0: Inactive1: Active

46123 CAN_LBNG / CANGas InputMessages

Engine DerateRequest

ReadOnly

Multiplier:0.4

Unit: Per-cent

Derate request in percentmade by the engine con-trol

PC 3.x

Offset: 0 Lower Limit:Size (bits):8

Upper Limit:

Sign: U

Page 236: Mapa de Registros de Pcc

229

Addr. ControlDescriptionAccessParameterName46124 CAN /

CAN InputMessages

Coolant Pres-sure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for theCoolant Pressure.

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 145

Sign: U46125 CAN_LBN

G / CANGas InputMessages

Coolant 2Pressure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for theCoolant 2 Pressure.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 145

Sign: U46127 CAN_LBN

G / CANGas InputMessages

Coolant 2Temperature

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for theCoolant 2 Temperature

PC 3.x

Offset: 0 Lower Limit: −40Size (bits):16

Upper Limit: 260

Sign: S46128 CAN_LBN

G / CANGas InputMessages

CompressorBypass Posi-tion

ReadOnly

Multiplier:0.1

Unit: % Engine turbochargercompressor bypass ac-tuator position

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46129 CAN_LBN

G / CANGas InputMessages

Engine Oil Fil-ter OutletPressure

ReadOnly

Multiplier:0.1

Unit: psi Engine oil pressure at theoutlet of the filter

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46130 CAN_LBN

G / CANGas InputMessages

Oil PrimingPump ControlStatus

ReadOnly

Status for the priming pump (ON or OFF) PC 3.x0: OFF1: ON2: Reserved3: N/A

46131 CAN_LBNG / CANGas InputMessages

Oil PrimingState

ReadOnly

Status of the engine before start (Pre−Lubed or Not) PC 3.x0: Low1: Optimum2: Reserved3: N/A

46132 CAN_LBNG / CANGas InputMessages

Oil Pre−Heated State

ReadOnly

Status of the engine oil before start (Pre−Heated orNot)

PC 3.x

0: Heated1: Cold2: Not Available

Page 237: Mapa de Registros de Pcc

230

Addr. ControlDescriptionAccessParameterName46133 CAN_LBN

G / CANGas InputMessages

Coolant Pre−Heated State

ReadOnly

Status of the engine coolant before start (Pre−Heatedor Not)

PC 3.x

0: Heated1: Cold2: Not Available

46134 CAN_LBNG / CANGas InputMessages

VentilationStatus

ReadOnly

Engine Ventilation Status (Vented or Not) PC 3.x0: Vented1: Not Vented2: Ventilation Delay3: Currently Venting4: Not Able To Determine5: Not Available

46135 CAN_LBNG / CANGas InputMessages

Intake Man-ifold Pressure1

ReadOnly

Multiplier:0.1

Unit: psi Intake Manifold Pressure1

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46136 CAN_LBN

G / CANGas InputMessages

CompressorOutlet Pres-sure

ReadOnly

Multiplier:0.1

Unit: kPa Absolute Pressure at theoutlet of the compressor.

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46137 CAN_LBN

G / CANGas InputMessages

Turbocharger1 Boost Pres-sure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for theTurbocharger 1 BoostPressure

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 1160

Sign: U46138 CAN_LBN

G / CANGas InputMessages

Genset AvgAC Frequency

ReadOnly

Multiplier:0.1

Unit: Hz Average Genset AC fre-quency

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46139 CAN_LBN

G / CANGas InputMessages

Fuel Valve 1Inlet AbsolutePressure

ReadOnly

Multiplier:0.1

Unit: psi Absolute Pressure of Gason the inlet side of thefirst system control valve

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 238: Mapa de Registros de Pcc

231

Addr. ControlDescriptionAccessParameterName46140 CAN_LBN

G / CANGas InputMessages

Fuel Valve 1Outlet Abso-lute Pressure

ReadOnly

Multiplier:0.1

Unit: psi Absolute Pressure of Gason the outlet side of thefirst system control valve

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46141 CAN_LBNG / CANGas InputMessages

Fuel Valve 1Position

ReadOnly

Multiplier:0.1

Unit: % PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46142 CAN_LBNG / CANGas InputMessages

Fuel Valve 2Inlet AbsolutePressure

ReadOnly

Multiplier:0.1

Unit: psi Absolute Pressure of Gason the inlet side of thesecond system controlvalve

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46143 CAN_LBNG / CANGas InputMessages

Fuel Valve 2Outlet Abso-lute Pressure

ReadOnly

Multiplier:0.1

Unit: psi Absolute Pressure of Gason the outlet side of thesecond system controlvalve

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46144 CAN_LBNG / CANGas InputMessages

Fuel Valve 2Position

ReadOnly

Multiplier:0.1

Unit: % PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46145 CAN_LBNG / CANGas InputMessages

Gas MassFlow

ReadOnly

Multiplier:0.1

Unit:Poundsper hour

Gas Mass Flow value ofthe engine.

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

46146 CAN_LBNG / CANGas InputMessages

Gas MassFlow

ReadOnly

Multiplier:0.1

Unit:Poundsper hour

Gas Mass Flow value ofthe engine.

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 239: Mapa de Registros de Pcc

232

Addr. ControlDescriptionAccessParameterName46147 CAN_LBN

G / CANGas InputMessages

Throttle 1Position

ReadOnly

Multiplier:0.1

Unit: % Position of the throttle 1. PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46148 CAN_LBNG / CANGas InputMessages

Throttle 2Position

ReadOnly

Multiplier:0.1

Unit: % Position of the throttle 2. PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46149 CAN_LBNG / CANGas InputMessages

Raw Value DERTD Bearing

ReadOnly

Multiplier:1

Unit:Count

Raw Value for the DERTD Bearing from theAux101

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46150 CAN_LBNG / CANGas InputMessages

Raw Value Al-ternator RTDL1

ReadOnly

Multiplier:1

Unit:Count

Raw Value AlternatorRTD L1 from Aux101 (10bits raw data)

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46151 CAN_LBNG / CANGas InputMessages

Raw Value Al-ternator RTDL2

ReadOnly

Multiplier:1

Unit:Count

Raw Value AlternatorRTD L2 from Aux101 (10bits raw data)

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46152 CAN_LBNG / CANGas InputMessages

Raw Value Al-ternator RTDL3

ReadOnly

Multiplier:1

Unit:Count

Raw Value AlternatorRTD L3 from Aux101 (10bits raw data)

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46153 CAN_LBNG / CANGas InputMessages

Raw ValueNDE RTDBearing

ReadOnly

Multiplier:1

Unit:Count

Raw Value NDE RTDBearing from Aux101 (10bits raw data)

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 240: Mapa de Registros de Pcc

233

Addr. ControlDescriptionAccessParameterName46154 CAN_LBN

G / CANGas InputMessages

LBNG Key-switch Com-mand

ReadOnly

Driver command that controls the output for the key-switch

PC 3.x

0: Inactive1: Active

46155 CAN_LBNG / CANGas InputMessages

MCM700 Bat-tery Voltage

ReadOnly

Multiplier:0.1

Unit: Vdc Engine Control ModuleBattery Voltage.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

46156 CAN_LBNG / CANGas InputMessages

MCM700 Iso-lated BatteryVoltage

ReadOnly

Multiplier:0.1

Unit: Vdc Engine Control ModuleIsolated Battery Voltage.

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46157 CAN_LBNG / CANGas InputMessages

CM700 Sen-sor Voltage A

ReadOnly

Multiplier:0.1

Unit: Vdc Engine Control ModuleCM700 Sensor Voltage A

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46158 CAN_LBNG / CANGas InputMessages

CM700 Sen-sor Voltage B

ReadOnly

Multiplier:0.1

Unit: Vdc Engine Control ModuleCM700 Sensor Voltage B

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46159 CAN_LBNG / CANGas InputMessages

CM700 Sen-sor Voltage C

ReadOnly

Multiplier:0.1

Unit: Vdc Engine Control ModuleCM700 Sensor Voltage C

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46160 CAN_LBNG / CANGas InputMessages

SSM558 1Battery Volt-age

ReadOnly

Multiplier:0.1

Unit: Vdc SSM558 1 Engine Con-trol Module Battery Volt-age.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

46161 CAN_LBNG / CANGas InputMessages

SSM558 1Isolated Bat-tery Voltage

ReadOnly

Multiplier:0.1

Unit: Vdc SSM558 1 Engine Con-trol Module Isolated Bat-tery Voltage.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

Page 241: Mapa de Registros de Pcc

234

Addr. ControlDescriptionAccessParameterName46162 CAN_LBN

G / CANGas InputMessages

SSM558 2Battery Volt-age

ReadOnly

Multiplier:0.1

Unit: Vdc SSM558 2 Engine Con-trol Module Battery Volt-age.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U46163 CAN_LBN

G / CANGas InputMessages

SSM558 2Isolated Bat-tery Voltage

ReadOnly

Multiplier:0.1

Unit: Vdc SSM558 2 Engine Con-trol Module Isolated Bat-tery Voltage.

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U46164 CAN_LBN

G / CANGas InputMessages

Intake Man-ifold Pressure2

ReadOnly

Multiplier:0.1

Unit: psi Intake Manifold Pressure2

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46165 CAN_LBN

G / CANGas InputMessages

Intake Man-ifold Tempera-ture 2

ReadOnly

Multiplier:0.1

Unit: degF Monitor point for the In-take Manifold Tempera-ture 2

PC 3.x

Offset: 0 Lower Limit: −40Size (bits):16

Upper Limit: 410

Sign: S46166 CAN_LBN

G / CANGas InputMessages

Exhaust BackPressure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for exhaustback pressure value

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46168 CAN_LBN

G / CANGas InputMessages

Air Filter Dif-ferential Pres-sure

ReadOnly

Multiplier:0.1

Unit: psi Monitor point for air filterdifferential pressure value

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S46170 CAN_LBN

G / CANGas InputMessages

Gas MassFlow 2

ReadOnly

Multiplier:0.1

Unit:Poundsper hour

Gas Mass Flow 2 valueof the engine.

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

Page 242: Mapa de Registros de Pcc

235

Addr. ControlDescriptionAccessParameterName46171 CAN_LBN

G / CANGas InputMessages

Gas MassFlow 2

ReadOnly

Multiplier:0.1

Unit:Poundsper hour

Gas Mass Flow 2 valueof the engine.

PC 3.x

Offset: 0 Lower Limit:Size (bits):32

Upper Limit:

Sign: U

46272 CAN_LBNG / CANGas InputMessages

Engine ECMInternal Tem-perature

ReadOnly

Multiplier:0.1

Unit: degF Temperature of the en-gine electronic controlunit

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: S

46175 AD_LBNG/ Gearbox

Gearbox OilPressure Low

ReadOnly

Occurs when Gearbox Low Oil Pressure switch be-comes active.

PC 3.x

0: Inactive1: Active

46176 AD_LBNG/ Gearbox

GearboxPresent

Read/Write

Enables gearbox protection. PC 3.x0: No1: Yes

46180 AD_LBNG/ DiscreteInputs

E−Stops dis-engaged

ReadOnly

Monitors the E−Stops switches. PC 3.x0: Inactive1: Active

46182 AD_LBNG/ LBNGAuxiliaryDevices

Radiator Fancontrol

ReadOnly

Radiator fan control command PC 3.x

0: Inactive

1: Active

46183 AD_LBNG/ LBNGAuxiliaryDevices

Ventilator Fanmode

Read/Write

Vent fan control mode limited or continuous PC 3.x

0: Limited

1: Continuous

46184 AD_LBNG/ LBNGAuxiliaryDevices

Louvre Con-trol

ReadOnly

Louvre control PC 3.x

0: Inactive

1: Active

46191 AD_LBNG/ LBNGAuxiliaryDevices

Ventilator Fancontrol

ReadOnly

Ventilator fan control command PC 3.x

0: Inactive

1: Active

46273 CAN_LBNG / CANGas InputMessages

AlternatorHeater ON(Aux101)

ReadOnly

Alternator Heater monitor point. PC 3.x

0: No

1: Yes

46288 CAN_LBNG / CANGas InputMessages

DE/NDE Cyl-inder View-point Refer-ence

Read/Write

Gives reference point for engine cylinder numbering PC 3.x0: Drive End1: Non−Drive End2: Reserved3: N/A

Page 243: Mapa de Registros de Pcc

236

Addr. ControlDescriptionAccessParameterName46289 CAN_LBN

G / CANGas InputMessages

Start SystemTrip (Aux 101)

ReadOnly

Start system trip monitor point. PC 3.x0: Not Tripped1: Tripped2: Reserved3: N/A

46290 CAN_LBNG / CANGas InputMessages

LouvresClosed (Aux101)

ReadOnly

Louvres Closed monitor point. PC 3.x0: Open1: Closed2: Reserved3: N/A

46291 CAN_LBNG / CANGas InputMessages

Radiator FanTrip (Aux 101)

ReadOnly

Radiator Fan Trip monitor point. PC 3.x0: Not Tripped1: Tripped2: Reserved3: N/A

46300 CAN_LBNG / Con-trollerModes

LBNG GensetEnable

Read/Write

Switch to enable or disable the gas specific featuresand parameters

PC 3.x

0: Disable1: Enable

46301 CAN_LBNG / CANGas InputMessages

Aux101−3 En-able

Read/Write

Enable the processing for Aux101−3 messages PC 3.x

0: Disable

1: Enable

46302 CAN_LBNG / CANGas InputMessages

Aux101−4 En-able

Read/Write

Enable the processing for Aux101−4 messages PC 3.x

0: Disable

1: Enable

46303 CAN_LBNG / CANGas InputMessages

Aux101−5 En-able

Read/Write

Enable the processing for Aux101−5 messages PC 3.x

0: Disable

1: Enable

46304 CAN_LBNG / CANGas InputMessages

Aux101−6 En-able

Read/Write

Enable the processing for Aux101−6 messages PC 3.x

0: Disable

1: Enable

46308 CAN_LBNG / CANGas InputMessages

Aux101−3 In-put Port Con-fig

Read/Write

Multiplier:1

Unit: Input Port configurationbye for the Aux101−3

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 255

Sign: U

46309 CAN_LBNG / CANGas InputMessages

Aux101−4 In-put Port Con-fig

Read/Write

Multiplier:1

Unit: Input Port configurationbye for the Aux101−4

PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 255

Sign: U

Page 244: Mapa de Registros de Pcc

237

Addr. ControlDescriptionAccessParameterName46310 CAN_LBN

G / CANGas InputMessages

Aux101−5 In-put Port Con-fig

Read/Write

Multiplier:1

Unit: Input Port configurationbye for the Aux101−5

PC 3.x

Offset: 0 Lower Limit: 0

Size (bits):16

Upper Limit: 255

Sign: U

46311 CAN_LBNG / CANGas InputMessages

Aux101−3 DIActive High/Low Selection

Read/Write

Multiplier:1

Unit: Digital Input Port configu-ration active High or ac-tive low for the Aux101−3

PC 3.x

Offset: 0 Lower Limit: 0

Size (bits):16

Upper Limit: 255

Sign: U

46312 CAN_LBNG / CANGas InputMessages

Aux101−4 DIActive High/Low Selection

Read/Write

Multiplier:1

Unit: Digital Input Port configu-ration active High or ac-tive low for the Aux101−4

PC 3.x

Offset: 0 Lower Limit: 0

Size (bits):16

Upper Limit: 255

Sign: U

46313 CAN_LBNG / CANGas InputMessages

Aux101−5 DIActive High/Low Selection

Read/Write

Multiplier:1

Unit: Digital Input Port configu-ration active High or ac-tive low for the Aux101−5

PC 3.x

Offset: 0 Lower Limit: 0

Size (bits):16

Upper Limit: 255

Sign: U

46314 CAN_LBNG / CANGas InputMessages

Aux101−3 DIConfig Mask

Read/Write

Multiplier:1

Unit: Discrete Input configura-tion bit mask for theAux101−3

PC 3.x

Offset: 0 Lower Limit: 0

Size (bits):16

Upper Limit: 255

Sign: U

46315 CAN_LBNG / CANGas InputMessages

Aux101−4 DIConfig Mask

Read/Write

Multiplier:1

Unit: Discrete Input configura-tion bit mask for theAux101−4

PC 3.x

Offset: 0 Lower Limit: 0

Size (bits):16

Upper Limit: 255

Sign: U

Page 245: Mapa de Registros de Pcc

238

Addr. ControlDescriptionAccessParameterName46316 CAN_LBN

G / CANGas InputMessages

Aux101−5 DIConfig Mask

Read/Write

Multiplier:1

Unit: Discrete Input configura-tion bit mask for theAux101−5

PC 3.x

Offset: 0 Lower Limit: 0

Size (bits):16

Upper Limit: 255

Sign: U

46317 CAN_LBNG / CANGas InputMessages

Rated OilTemperatureThreshold

Read/Write

Multiplier:0.015625

Unit: degF Oil temperature thresholdfor the engine to be ableto run at rated speed

PC 3.x

Offset: 0 Lower Limit: 0

Size (bits):16

Upper Limit: 60

Sign: S

46318 CAN_LBNG / CANGas InputMessages

Alternator Effi-ciency

Read/Write

Multiplier:0.0025

Unit: % Alternator efficiency PC 3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 1

Sign: U

46323 CAN_LBNG / CANGas InputMessages

Vehicle Elec-trical Power 2PGN65165Enable

Read/Write

A trim that enables the Vehicle Electrical Power 2message

PC 3.x

0: Disabled1: Enabled

46326 CAN_LBNG / CANGas InputMessages

Gaseous FuelPressurePGN65163Enable

Read/Write

A trim that enables the Gaseous Fuel Pressure mes-sage

PC 3.x

0: Disabled1: Enabled

46327 CAN_LBNG / CANGas InputMessages

Fuel Informa-tion 3 − Gas-eousPGN64930Enable

Read/Write

A trim that enables the Fuel Information 3 − Gaseousmessage

PC 3.x

0: Disabled

1: Enabled

46328 CAN_LBNG / CANGas InputMessages

Fuel Informa-tion 2 − Gas-eousPGN65153Enable

Read/Write

A trim that enables the Fuel Information 2 − Gaseousmessage

PC 3.x

0: Disabled

1: Enabled

46332 CAN_LBNG / CANGas InputMessages

Inlet/ExhaustConditionsPGN65270Enable

Read/Write

A trim that enables the Inlet/Exhaust Conditions mes-sage

PC 3.x

0: Disabled1: Enabled

46333 CAN_LBNG / CANGas InputMessages

Knock Count1 PGN65336Enable

Read/Write

A trim that enables Knock Count 1 message PC 3.x

0: Disabled

1: Enabled

Page 246: Mapa de Registros de Pcc

239

Addr. ControlDescriptionAccessParameterName46334 CAN_LBN

G / CANGas InputMessages

Knock Count2 PGN65337Enable

Read/Write

A trim that enables Knock Count 2 message PC 3.x

0: Disabled

1: Enabled

46335 CAN_LBNG / CANGas InputMessages

Knock Count3 PGN65338Enable

Read/Write

A trim that enables Knock Count 3 message PC 3.x

0: Disabled

1: Enabled

46336 CAN_LBNG / CANGas InputMessages

Knock Count4 PGN65339Enable

Read/Write

A trim that enables Knock Count 4 message PC 3.x

0: Disabled

1: Enabled

46337 CAN_LBNG / CANGas InputMessages

Knock Count5 PGN65340Enable

Read/Write

A trim that enables Knock Count 5 message PC 3.x

0: Disabled

1: Enabled

46338 CAN_LBNG / CANGas InputMessages

Ignition Tim-ing 1PGN65154Enable

Read/Write

A trim that enables the Ignition Timing 1 message PC 3.x

0: Disabled

1: Enabled

46339 CAN_LBNG / CANGas InputMessages

Ignition Tim-ing 2PGN65155Enable

Read/Write

A trim that enables the Ignition Timing 2 message PC 3.x

0: Disabled

1: Enabled

46340 CAN_LBNG / CANGas InputMessages

Ignition Tim-ing 3PGN65156Enable

Read/Write

A trim that enables the Ignition Timing 3 message PC 3.x

0: Disabled

1: Enabled

46341 CAN_LBNG / CANGas InputMessages

Ignition Tim-ing 4PGN65157Enable

Read/Write

A trim that enables the Ignition Timing 4 message PC 3.x

0: Disabled

1: Enabled

46342 CAN_LBNG / CANGas InputMessages

Ignition Tim-ing 5PGN65158Enable

Read/Write

A trim that enables the Ignition Timing 5 message PC 3.x

0: Disabled

1: Enabled

46344 GC /LBNGStart−En-able Func-tion

Start−Enable(MODBUS In-put)

Read/Write

Remote MODBUS Start−Enable input. PC 3.x

0: Disable

1: Enable

46346 CAN_LBNG / CANGas InputMessages

Cylinder Iden-tification Start-ing Point

Read/Write

Parameter to define on which end is the numbering ofthe cylinder starting on the HMI (NDE or DE)

PC 3.x

0: Drive End1: Non Drive End2: N/A

Page 247: Mapa de Registros de Pcc

240

Addr. ControlDescriptionAccessParameterName46348 GC /

SpeedReference

Target Speed ReadOnly

Multiplier:0.0625

Unit: rpm The speed referencefunction desired speedbefore ramping

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4000

Sign: U46349 GC /

SpeedReference

Target Speed ReadOnly

Multiplier:0.0625

Unit: rpm The speed referencefunction desired speedbefore ramping

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):32

Upper Limit: 4000

Sign: U46367 Modbus /

ModbusModbus BusMessageCount (J14)

ReadOnly

Multiplier:1

Unit: The number of Modusmessages with no re-sponse for J14 port only

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46366 Modbus /

ModbusModbus StopBits (J14)

Read/Write

Sets the Modus number of stop bits for this node Lim-ited to 1 bit if parity = Odd or Even

PC 3.x

0: 011: 02

46368 Modbus /Modbus

Modbus CRCError Count(J14)

ReadOnly

Multiplier:1

Unit: The number of ModusCRC errors for J14 only.

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46369 Modbus /

ModbusModbus Ex-ception Count(J14)

ReadOnly

Multiplier:1

Unit: Modbus exception countfor J14 only.

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46370 Modbus /

ModbusModbus NoResponseCount (J14)

ReadOnly

Multiplier:1

Unit: Modbus no responsecount for J14 only.

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

Page 248: Mapa de Registros de Pcc

241

Addr. ControlDescriptionAccessParameterName46371 Modbus /

ModbusModbus SlaveMessageCount (J14)

ReadOnly

Multiplier:1

Unit: The number of Modbusslave messages for J14only.

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U46372 Modbus /

ModbusModbus NodeAddress (J14)

Read/Write

Multiplier:1

Unit: Sets the Modus addressfor this node for J14 only.

PC 3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 247

Sign: U46373 Modbus /

ModbusModbus BaudRate (J14)

Read/Write

Sets the baud rate for Modus communications for J14only.

PC 3.x

1.666666663.3756.753: 19200

46374 Modbus /Modbus

Modbus Parity(J14)

Read/Write

Sets the Modus parity for this node for J14 only. PC 3.x0: Even1: Odd2: None

46376 Modbus /Modbus

Modbus BaudRate

Read/Write

Sets the Modus baud rate. PC 2.x, PC3.x0: 2400 Baud

1: 4800 Baud2: 9600 Baud3: 19200 Baud4: 38400 Baud

46377 Modbus /Modbus

Modbus Parity Read/Write

Sets the Modus parity for this node PC 2.x, PC3.x0: Even

1: Odd2: None

46378 Modbus /Modbus

Modbus NodeAddress

Read/Write

Multiplier:1

Unit: Sets the Modus addressfor this node

PC 2.x, PC3.x

Offset: 0 Lower Limit: 1Size (bits):8

Upper Limit: 247

Sign: U46379 Modbus /

ModbusModbus StopBits

Read/Write

Sets the Modus number of stop bits for this node Lim-ited to 1 bit if parity = Odd or Even

PC 2.x, PC3.x

0: 011: 02

Page 249: Mapa de Registros de Pcc

242

Addr. ControlDescriptionAccessParameterName46380 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46381 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46382 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46383 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46384 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46385 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 250: Mapa de Registros de Pcc

243

Addr. ControlDescriptionAccessParameterName46386 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46387 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46388 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46389 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46390 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46391 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 251: Mapa de Registros de Pcc

244

Addr. ControlDescriptionAccessParameterName46392 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46393 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46394 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46395 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46396 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46397 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 252: Mapa de Registros de Pcc

245

Addr. ControlDescriptionAccessParameterName46398 PCCNet /

UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46399 PCCNet /UniversalAnnuncia-tor

HMI113 Fault3 Text

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext string to enter theconfigurable fault text forthis fault.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46561 PCCNet /OperatorPanel

Operator Pan-el Status

ReadOnly

Multiplier:1

Unit: 16−bit number to repre-sent the status of opera-tor panel indications.

PC 3.x

Offset: 0 Lower Limit:Size (bits):16

Upper Limit:

Sign: U

46600 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46601 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46602 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 253: Mapa de Registros de Pcc

246

Addr. ControlDescriptionAccessParameterName46603 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46604 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46605 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46606 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46607 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46608 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 254: Mapa de Registros de Pcc

247

Addr. ControlDescriptionAccessParameterName46609 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46610 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46611 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46612 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46613 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46614 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 255: Mapa de Registros de Pcc

248

Addr. ControlDescriptionAccessParameterName46615 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46616 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46617 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46618 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46619 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46620 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 256: Mapa de Registros de Pcc

249

Addr. ControlDescriptionAccessParameterName46621 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46622 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46623 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46624 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46625 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46626 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 257: Mapa de Registros de Pcc

250

Addr. ControlDescriptionAccessParameterName46627 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46628 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46629 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46630 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46631 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46632 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 258: Mapa de Registros de Pcc

251

Addr. ControlDescriptionAccessParameterName46633 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46634 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46635 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46636 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46637 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46638 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 259: Mapa de Registros de Pcc

252

Addr. ControlDescriptionAccessParameterName46639 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46640 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46641 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46642 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46643 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46644 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 260: Mapa de Registros de Pcc

253

Addr. ControlDescriptionAccessParameterName46645 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46646 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46647 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46648 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46649 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46650 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 261: Mapa de Registros de Pcc

254

Addr. ControlDescriptionAccessParameterName46651 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46652 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46653 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46654 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46655 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46656 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 262: Mapa de Registros de Pcc

255

Addr. ControlDescriptionAccessParameterName46657 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46658 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46659 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 1 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46660 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46661 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46662 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 263: Mapa de Registros de Pcc

256

Addr. ControlDescriptionAccessParameterName46663 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46664 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46665 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46666 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46667 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46668 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 264: Mapa de Registros de Pcc

257

Addr. ControlDescriptionAccessParameterName46669 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46670 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46671 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46672 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46673 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46674 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 265: Mapa de Registros de Pcc

258

Addr. ControlDescriptionAccessParameterName46675 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46676 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46677 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46678 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46679 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 2 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46800 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 266: Mapa de Registros de Pcc

259

Addr. ControlDescriptionAccessParameterName46801 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46802 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46803 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46804 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46805 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46806 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 267: Mapa de Registros de Pcc

260

Addr. ControlDescriptionAccessParameterName46807 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46808 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46809 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46810 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46811 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46812 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 268: Mapa de Registros de Pcc

261

Addr. ControlDescriptionAccessParameterName46813 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46814 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46815 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46816 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46817 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46818 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 269: Mapa de Registros de Pcc

262

Addr. ControlDescriptionAccessParameterName46819 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46820 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46821 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46822 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46823 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46824 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 270: Mapa de Registros de Pcc

263

Addr. ControlDescriptionAccessParameterName46825 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46826 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46827 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46828 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46829 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46830 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 271: Mapa de Registros de Pcc

264

Addr. ControlDescriptionAccessParameterName46831 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46832 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46833 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46834 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46835 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46836 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 272: Mapa de Registros de Pcc

265

Addr. ControlDescriptionAccessParameterName46837 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46838 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46839 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46840 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46841 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46842 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 273: Mapa de Registros de Pcc

266

Addr. ControlDescriptionAccessParameterName46843 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46844 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46845 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46846 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46847 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46848 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 274: Mapa de Registros de Pcc

267

Addr. ControlDescriptionAccessParameterName46849 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46850 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46851 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46852 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46853 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46854 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 275: Mapa de Registros de Pcc

268

Addr. ControlDescriptionAccessParameterName46855 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46856 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46857 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46858 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46859 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46860 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 276: Mapa de Registros de Pcc

269

Addr. ControlDescriptionAccessParameterName46861 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46862 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46863 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46864 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46865 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46866 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 277: Mapa de Registros de Pcc

270

Addr. ControlDescriptionAccessParameterName46867 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46868 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46869 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46870 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46871 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46872 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 278: Mapa de Registros de Pcc

271

Addr. ControlDescriptionAccessParameterName46873 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46874 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46875 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46876 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46877 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46878 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 279: Mapa de Registros de Pcc

272

Addr. ControlDescriptionAccessParameterName46879 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46880 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46881 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46882 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46883 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46884 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 280: Mapa de Registros de Pcc

273

Addr. ControlDescriptionAccessParameterName46885 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46886 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46887 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46888 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46889 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46890 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 281: Mapa de Registros de Pcc

274

Addr. ControlDescriptionAccessParameterName46891 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46892 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46893 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46894 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46895 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46896 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 282: Mapa de Registros de Pcc

275

Addr. ControlDescriptionAccessParameterName46897 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46898 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46899 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 3 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46900 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46901 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46902 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 283: Mapa de Registros de Pcc

276

Addr. ControlDescriptionAccessParameterName46903 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46904 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46905 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46906 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46907 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46908 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 284: Mapa de Registros de Pcc

277

Addr. ControlDescriptionAccessParameterName46909 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46910 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46911 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46912 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46913 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46914 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 285: Mapa de Registros de Pcc

278

Addr. ControlDescriptionAccessParameterName46915 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46916 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46917 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46918 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46919 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 4 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46920 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 286: Mapa de Registros de Pcc

279

Addr. ControlDescriptionAccessParameterName46921 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46922 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46923 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46924 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46925 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46926 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 287: Mapa de Registros de Pcc

280

Addr. ControlDescriptionAccessParameterName46927 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46928 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46929 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46930 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46931 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46932 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 288: Mapa de Registros de Pcc

281

Addr. ControlDescriptionAccessParameterName46933 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46934 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46935 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46936 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46937 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46938 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 289: Mapa de Registros de Pcc

282

Addr. ControlDescriptionAccessParameterName46939 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 5 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46940 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46941 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46942 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46943 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46944 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 290: Mapa de Registros de Pcc

283

Addr. ControlDescriptionAccessParameterName46945 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46946 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46947 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46948 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46949 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46950 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 291: Mapa de Registros de Pcc

284

Addr. ControlDescriptionAccessParameterName46951 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46952 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46953 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46954 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46955 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46956 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 292: Mapa de Registros de Pcc

285

Addr. ControlDescriptionAccessParameterName46957 PCCNet /

I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46958 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46959 PCCNet /I/O Module1 MainBoard

Aux101 1 In-put 6 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46960 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46961 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46962 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 293: Mapa de Registros de Pcc

286

Addr. ControlDescriptionAccessParameterName46963 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46964 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46965 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46966 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46967 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46968 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 294: Mapa de Registros de Pcc

287

Addr. ControlDescriptionAccessParameterName46969 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46970 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46971 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46972 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46973 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46974 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 295: Mapa de Registros de Pcc

288

Addr. ControlDescriptionAccessParameterName46975 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46976 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46977 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46978 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46979 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 7 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46980 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 296: Mapa de Registros de Pcc

289

Addr. ControlDescriptionAccessParameterName46981 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46982 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46983 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46984 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46985 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46986 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 297: Mapa de Registros de Pcc

290

Addr. ControlDescriptionAccessParameterName46987 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46988 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46989 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46990 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46991 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46992 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 298: Mapa de Registros de Pcc

291

Addr. ControlDescriptionAccessParameterName46993 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46994 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46995 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46996 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46997 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

46998 PCCNet /I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

Page 299: Mapa de Registros de Pcc

292

Addr. ControlDescriptionAccessParameterName46999 PCCNet /

I/O Module0 MainBoard

Aux101 0 In-put 8 FaultText

Read/Write

Multiplier:1

Unit: Twenty (20) charactertext field to allow for theentry of the displayedconfigurable fault text.

PC 2.x, PC3.x

Offset: 0 Lower Limit:Size (bits):168

Upper Limit:

Sign: C

47001 GC / Gov-ernor

ElectronicGovernor En-able

Read/Write

Disable for mechanical governed genset. MODBUSAccess: Ready Only

PC 2.x, PC3.x

0: Disable1: Enable

47002 GC / Gov-ernor

GK1 (60Hz) Read/Write

Multiplier:1

Unit: The governor 60Hz K1gain adjust. MODBUSAccess: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

47003 GC / Gov-ernor

GK2 (60Hz) Read/Write

Multiplier:1

Unit: The governor 60Hz inte-gral gain adjust. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

47004 GC / Gov-ernor

GK3 (60Hz) Read/Write

Multiplier:1

Unit: The governor 60Hz K3gain adjust. MODBUSAccess: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 32768

Sign: U

47005 GC / Gov-ernor

GovernorDamping Ef-fect (60Hz)

Read/Write

Multiplier:1.52587890625E−05

Unit: The governor 60Hzdamping adjust. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0.6Size (bits):16

Upper Limit: 0.95

Sign: U

47006 GC / Gov-ernor

GK1 (50Hz) Read/Write

Multiplier:1

Unit: The governor 50Hz K1gain adjust. MODBUSAccess: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

Page 300: Mapa de Registros de Pcc

293

Addr. ControlDescriptionAccessParameterName47007 GC / Gov-

ernorGK2 (50Hz) Read/

WriteMultiplier:1

Unit: The governor 50Hz inte-gral gain adjust. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U47008 GC / Gov-

ernorGK3 (50Hz) Read/

WriteMultiplier:1

Unit: The governor 50Hz K3gain adjust. MODBUSAccess: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 32768

Sign: U47009 GC / Gov-

ernorGovernorDamping Ef-fect (50Hz)

Read/Write

Multiplier:1.52587890625E−05

Unit: The governor 50Hzdamping adjust. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0.6Size (bits):16

Upper Limit: 0.95

Sign: U47010 GC / Gov-

ernorGK1 (Idle) Read/

WriteMultiplier:1

Unit: This trim is used to adjustgk1 in idle mode. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U47011 GC / Gov-

ernorGK2 (Idle) Read/

WriteMultiplier:1

Unit: This trim is used to adjustgk2 in idle mode. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U47012 GC / Gov-

ernorGK3 (Idle) Read/

WriteMultiplier:1

Unit: This trim is used to adjustgk3 in idle mode. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 32768

Sign: U

Page 301: Mapa de Registros de Pcc

294

Addr. ControlDescriptionAccessParameterName47013 GC / Gov-

ernorGov DampingEffect (Idle)

Read/Write

Multiplier:1.52587890625E−05

Unit: The governor dampingadjust for idle rating.MODBUS Access: ReadOnly

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0.6Size (bits):16

Upper Limit: 0.95

Sign: U

47014 GC / Gov-ernor

Gain Window-ing Enable

Read/Write

Either enables or disables Gain Windowing feature.MODBUS Access: Read Only

PC 2.x, PC3.x

0: Disable1: Enable

47015 GC / Gov-ernor

GK1 Low(50Hz)

Read/Write

Multiplier:1

Unit: The governor 50Hz K1low gain adjust. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

47016 GC / Gov-ernor

GK1 Low(60Hz)

Read/Write

Multiplier:1

Unit: The governor 60Hz K1low gain adjust. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

47017 GC / Gov-ernor

GK1 High(50Hz)

Read/Write

Multiplier:1

Unit: The governor 50Hz K1high gain adjust. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

47018 GC / Gov-ernor

GK1 High(60Hz)

Read/Write

Multiplier:1

Unit: The governor 60Hz K1high gain adjust. MOD-BUS Access: Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 65535

Sign: U

47019 GC / Gov-ernor

GovernorSpeed DeltaHigh

Read/Write

Multiplier:1

Unit: The speed error higherlimit. MODBUS Access:Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 50Size (bits):16

Upper Limit: 1000

Sign: U

Page 302: Mapa de Registros de Pcc

295

Addr. ControlDescriptionAccessParameterName47020 GC / Gov-

ernorGovernorSpeed DeltaLow

Read/Write

Multiplier:1

Unit: The speed error lowerlimit. MODBUS Access:Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 50Size (bits):16

Upper Limit: 1000

Sign: U47021 ASI / Ana-

log Inputs/Outputs

Intake Man-ifold Tempera-ture SenderType

Read/Write

Either Onan or Cummins sensor. MODBUS Access:Read Only

PC 2.x, PC3.x

0: PGBU1: EBU

47022 ASI / Ana-log Inputs/Outputs

Intake Man-ifold Tempera-ture SensorEnable

Read/Write

Intake Manifold Temp Sensor available or not. MOD-BUS Access: Read Only

PC 2.x, PC3.x

0: Disable1: Enable

47023 ASI / Ana-log Inputs/Outputs

Oil Tempera-ture SenderType

Read/Write

Either Onan or Cummins sensor. PC 2.x, PC3.x0: PGBU

1: EBU47024 ASI / Ana-

log Inputs/Outputs

Oil Tempera-ture SensorEnable

Read/Write

High Oil Temperature Sensor available or not. PC 2.x, PC3.x0: Disable

1: Enable47025 GC / Auto-

matic Volt-age Regu-lator

AVR PWMCommand

ReadOnly

Multiplier:0.01

Unit: % The AVR PWM softwarecommand. Linear rela-tionship between countsand % duty cycle with10000 counts=100% dutycycle. MODBUS Access:Read Only

PC 2.x, PC3.x

Offset: 0 Lower Limit: 0Size (bits):16

Upper Limit: 100

Sign: U

Page 303: Mapa de Registros de Pcc

296

THIS PAGE LEFT INTENTIONALLY BLANK

Page 304: Mapa de Registros de Pcc

297

3. PowerCommand 2.x/3.x Modbus Fault Status BitmapsNote: If an address or bit is not listed in this table it is not used.

Addr. Bit # Name FaultCode

Event Name Response Control

40400 0 Fault Status Bit-map 1

115 Engine Magnetic Crankshaft Speed/Position

Shutdown PC 2.x, PC3.x

40400 1 Fault Status Bit-map 1

122 Intake Manifold 1 Pressure: Vtg AboveNormal

Warning PC 2.x, PC3.x

40400 2 Fault Status Bit-map 1

123 Intake Manifold 1 Pressure: Vtg BelowNormal

Warning PC 2.x, PC3.x

40400 3 Fault Status Bit-map 1

124 Intake Manifold 1 Pressure: Moderate-ly Severe

Warning PC 2.x, PC3.x

40400 4 Fault Status Bit-map 1

135 Engine Oil Rifle Pressure 1: Vtg AboveNormal

Warning PC 2.x, PC3.x

40400 5 Fault Status Bit-map 1

141 Engine Oil Rifle Pressure 1: Vtg BelowNormal

Warning PC 2.x, PC3.x

40400 6 Fault Status Bit-map 1

143 Engine Oil Rifle Pressure −ModeratelySevere

Warning PC 2.x, PC3.x

40400 7 Fault Status Bit-map 1

144 Engine Coolant Temp 1: Vtg AboveNormal

Warning PC 2.x, PC3.x

40400 8 Fault Status Bit-map 1

145 Engine Coolant Temp 1: Vtg BelowNormal

Warning PC 2.x, PC3.x

40400 9 Fault Status Bit-map 1

146 Engine Coolant Temp: ModeratelyAbove Normal

Derate PC 2.x, PC3.x

40400 10 Fault Status Bit-map 1

151 Engine Coolant Temp: Severely AboveNormal

Shutdown PC 2.x, PC3.x

40400 11 Fault Status Bit-map 1

153 Intake Manifold 1 Temp: Vtg AboveNormal

Warning PC 2.x, PC3.x

40400 12 Fault Status Bit-map 1

154 Intake Manifold 1 Temp: Vtg BelowNormal

Warning PC 2.x, PC3.x

40400 13 Fault Status Bit-map 1

155 Intake Manifold 1 Temp: SeverelyAbove Normal

Shutdown PC 2.x, PC3.x

40400 14 Fault Status Bit-map 1

187 Sensor Supply 2: Vtg Below Normal Warning PC 2.x, PC3.x

40400 15 Fault Status Bit-map 1

195 Coolant Level Sensor 1: Vtg AboveNormal

Warning PC 2.x, PC3.x

40401 0 Fault Status Bit-map 2

196 Coolant Level Sensor 1: Vtg BelowNormal

Warning PC 2.x, PC3.x

40401 1 Fault Status Bit-map 2

197 Coolant Level: Below Normal − Moder-ately Severe

Warning PC 2.x, PC3.x

40401 2 Fault Status Bit-map 2

212 Engine Oil Temp Sensor 1: Vtg AboveNormal

Warning PC 2.x, PC3.x

40401 3 Fault Status Bit-map 2

213 Engine Oil Temp Sensor 1: Vtg belowNormal

Warning PC 2.x, PC3.x

40401 4 Fault Status Bit-map 2

214 Engine Oil Temp: Above Normal −Most severe

Shutdown PC 2.x, PC3.x

40401 5 Fault Status Bit-map 2

221 Barometric Pressure: Vtg Above Nor-mal

Warning PC 2.x, PC3.x

40401 6 Fault Status Bit-map 2

222 Barometric Pressure Sensor: Vtg Be-low Normal

Warning PC 2.x, PC3.x

40401 7 Fault Status Bit-map 2

223 Eng Oil Burn Valve Solenoid: Vtg Be-low Normal

Warning PC 2.x, PC3.x

Page 305: Mapa de Registros de Pcc

298

Addr. ControlResponseEvent NameFaultCode

NameBit #

40401 8 Fault Status Bit-map 2

224 Engine Oil Burn Valve Solenoid: VtgAbove Normal

Warning PC 2.x, PC3.x

40401 9 Fault Status Bit-map 2

227 Sensor Supply 2: Vtg Above Normal Warning PC 2.x, PC3.x

40401 10 Fault Status Bit-map 2

228 Coolant Pressure: Below Normal−Most Severe

Shutdown PC 2.x, PC3.x

40401 11 Fault Status Bit-map 2

231 Coolant Pressure Sensor: Vtg AboveNormal

Warning PC 2.x, PC3.x

40401 12 Fault Status Bit-map 2

232 Coolant Pressure Sensor: Vtg BelowNormal

Warning PC 2.x, PC3.x

40401 13 Fault Status Bit-map 2

234 Engine Crankshaft Speed/Posn:Above Normal

Shutdown PC 2.x, PC3.x

40401 14 Fault Status Bit-map 2

235 Coolant Level: Below Normal−MostSevere

Shutdown PC 2.x, PC3.x

40401 15 Fault Status Bit-map 2

238 Sensor Supply 3: Vtg Below Normal Warning PC 2.x, PC3.x

40402 0 Fault Status Bit-map 3

239 Voltage Supply C High Error Warning PC 2.x, PC3.x

40402 1 Fault Status Bit-map 3

245 Radiator Fan Control Driver Low Error Warning PC 2.x, PC3.x

40402 2 Fault Status Bit-map 3

261 Engine Fuel Temp: Above Normal−Moderately Severe

Warning PC 2.x, PC3.x

40402 3 Fault Status Bit-map 3

263 Engine Fuel Temp Sensor 1: VtgAbove Normal

Warning PC 2.x, PC3.x

40402 4 Fault Status Bit-map 3

265 Engine Fuel Temp Sensor 1: Vtg Be-low Normal

Warning PC 2.x, PC3.x

40402 5 Fault Status Bit-map 3

266 Engine Fuel Temp: Above Normal−Most severe

Shutdown PC 2.x, PC3.x

40402 6 Fault Status Bit-map 3

271 Fuel Pump Pressurizing Assembly 1:Vtg Below Normal

Warning PC 2.x, PC3.x

40402 7 Fault Status Bit-map 3

272 Fuel Pump Pressurizing Assembly 1:Vtg Above Normal

Warning PC 2.x, PC3.x

40402 8 Fault Status Bit-map 3

281 APC_DIESEL_CYL_PRS_IMBAL_ER-ROR

Warning PC 2.x, PC3.x

40402 9 Fault Status Bit-map 3

285 SAE J1939 Muxing PGN Timeout: Ab-normal Update Rate

Warning PC 2.x, PC3.x

40402 10 Fault Status Bit-map 3

286 SAE J1939 Muxing Config: Out of Cal-ibration

Warning PC 2.x, PC3.x

40402 13 Fault Status Bit-map 3

295 AMBIENT_AIR_PRESS_KEYON_ER-ROR

Warning PC 2.x, PC3.x

40402 14 Fault Status Bit-map 3

319 RTC PWR Intr: Data Erratic Intermit-tent or Wrong

Warning PC 2.x, PC3.x

40402 15 Fault Status Bit-map 3

322 Injector Solenoid Driver Cylinder 1:UnderCurrent

Warning PC 2.x, PC3.x

40403 0 Fault Status Bit-map 4

323 Injector Solenoid Driver Cylinder 5:UnderCurrent

Warning PC 2.x, PC3.x

40403 1 Fault Status Bit-map 4

324 Injector Solenoid Driver Cylinder 3:UnderCurrent

Warning PC 2.x, PC3.x

40403 2 Fault Status Bit-map 4

325 Injector Solenoid Driver Cylinder 6:UnderCurrent

Warning PC 2.x, PC3.x

Page 306: Mapa de Registros de Pcc

299

Addr. ControlResponseEvent NameFaultCode

NameBit #

40403 3 Fault Status Bit-map 4

331 Injector Solenoid Driver Cylinder 2:UnderCurrent

Warning PC 2.x, PC3.x

40403 4 Fault Status Bit-map 4

332 Injector Solenoid Driver Cylinder 4:UnderCurrent

Warning PC 2.x, PC3.x

40403 6 Fault Status Bit-map 4

342 Electronic Calibration Code: Out ofCalibration

Shutdown PC 2.x, PC3.x

40403 7 Fault Status Bit-map 4

343 Eng Ctrl: internal h/w failure−Bad De-vice/Component

Warning PC 2.x, PC3.x

40403 8 Fault Status Bit-map 4

351 Injector Power Supply: Bad Device/Component

Warning PC 2.x, PC3.x

40403 9 Fault Status Bit-map 4

352 Sensor Supply 1: Vtg Below Normal Warning PC 2.x, PC3.x

40403 10 Fault Status Bit-map 4

359 Fail To Start Fault Shutdown PC 2.x, PC3.x

40403 11 Fault Status Bit-map 4

386 Sensor Supply 1: Vtg Above Normal Warning PC 2.x, PC3.x

40403 12 Fault Status Bit-map 4

415 Eng Oil Rifle Pressure: Below Normal−Most Severe

Shutdown PC 2.x, PC3.x

40403 13 Fault Status Bit-map 4

418 Water in Fuel Indicator: Above Nor-mal−Least Severe

Warning PC 2.x, PC3.x

40403 14 Fault Status Bit-map 4

421 Eng Oil Temp: Above Normal−Moder-ately Severe

Warning PC 2.x, PC3.x

40403 15 Fault Status Bit-map 4

422 COOLANT_LEVEL_READING_IN-CORRECT

Warning PC 2.x, PC3.x

40404 0 Fault Status Bit-map 5

425 OIL_TEMPERA-TURE_IN_RANGE_ERROR

Warning PC 2.x, PC3.x

40404 1 Fault Status Bit-map 5

426 J1939 Datalink: Data Erratic/Intermit-tent/Wrong

NONE PC 2.x, PC3.x

40404 2 Fault Status Bit-map 5

427 CAN Datalink Degraded Warning PC 2.x, PC3.x

40404 3 Fault Status Bit-map 5

435 OIL_PRESSURE_SWITCH_ERROR Warning PC 2.x, PC3.x

40404 4 Fault Status Bit-map 5

441 Low Battery Voltage Warning PC 2.x, PC3.x

40404 5 Fault Status Bit-map 5

442 High Battery Voltage Warning PC 2.x, PC3.x

40404 6 Fault Status Bit-map 5

449 Injector Metering Rail 1 Pressure:Above Normal

Shutdown PC 2.x, PC3.x

40404 7 Fault Status Bit-map 5

451 Injector Metering Rail 1 Pressure: VtgAbove Normal

Warning PC 2.x, PC3.x

40404 8 Fault Status Bit-map 5

452 Injector Metering Rail 1 Pressure: VtgBelow Normal

Warning PC 2.x, PC3.x

40404 9 Fault Status Bit-map 5

488 Intake Manifold 1 Temp: Above Nor-mal−Moderate

Derate PC 2.x, PC3.x

40404 10 Fault Status Bit-map 5

546 Fuel Delivery Pressure: Vtg AboveNormal

Warning PC 2.x, PC3.x

40404 11 Fault Status Bit-map 5

547 Fuel Delivery Pressure: Vtg BelowNormal

Warning PC 2.x, PC3.x

40404 12 Fault Status Bit-map 5

553 APC_DIESEL_HIGH_PRS_ERROR Warning PC 2.x, PC3.x

Page 307: Mapa de Registros de Pcc

300

Addr. ControlResponseEvent NameFaultCode

NameBit #

40404 13 Fault Status Bit-map 5

554 APC_DIESEL_PRS_SIR_ERROR Warning PC 2.x, PC3.x

40404 14 Fault Status Bit-map 5

556 Crankcase Pressure: Above Normal−Most Severe

Shutdown PC 2.x, PC3.x

40404 15 Fault Status Bit-map 5

559 Injector Metering Rail 1 Pressure: Be-low Normal

Warning PC 2.x, PC3.x

40405 1 Fault Status Bit-map 6

611 Engine Shut Down Hot Condition Ex-ists

Warning PC 2.x, PC3.x

40405 3 Fault Status Bit-map 6

689 Eng Crankshaft Speed/Pos Warning Warning PC 2.x, PC3.x

40405 4 Fault Status Bit-map 6

731 Eng Speed: Cam/Crankshaft Misalign-ment

Warning PC 2.x, PC3.x

40405 7 Fault Status Bit-map 6

1117 Power Lost With Ignition On Warning PC 2.x, PC3.x

40405 8 Fault Status Bit-map 6

1122 Rated to Idle Transition NONE PC 2.x, PC3.x

40405 9 Fault Status Bit-map 6

1124 Delayed Shutdown Fault Warning PC 2.x, PC3.x

40405 10 Fault Status Bit-map 6

1131 Battle Short Mode Active Warning PC 2.x, PC3.x

40405 11 Fault Status Bit-map 6

1132 Controlled Shutdown In Process Warning PC 3.x

40405 13 Fault Status Bit-map 6

1243 Engine Derate Derate PC 2.x, PC3.x

40405 14 Fault Status Bit-map 6

1244 Engine Normal Shutdown Shutdownw/Cool-down

PC 2.x, PC3.x

40405 15 Fault Status Bit-map 6

1245 Engine Shutdown Shutdown PC 2.x, PC3.x

40406 0 Fault Status Bit-map 7

1246 Unrecognized Engine Fault Warning PC 2.x, PC3.x

40406 1 Fault Status Bit-map 7

1247 Engine Shutdown _ Unannounced Shutdown PC 2.x, PC3.x

40406 2 Fault Status Bit-map 7

1248 Engine Warning Warning PC 3.x

40406 3 Fault Status Bit-map 7

1256 Ctrl Module ID Input State Warning Er-ror

Warning PC 2.x, PC3.x

40406 4 Fault Status Bit-map 7

1257 Ctrl Module ID I/P State shutdown Er-ror

Shutdown PC 2.x, PC3.x

40406 5 Fault Status Bit-map 7

1322 kW Load Setpoint OOR High Warning PC 3.x

40406 6 Fault Status Bit-map 7

1323 kW Load Setpoint OOR Low Warning PC 3.x

40406 7 Fault Status Bit-map 7

1324 kVAR Load Setpoint OOR High Warning PC 3.x

40406 8 Fault Status Bit-map 7

1325 kVAR Load Setpoint OOR Low Warning PC 3.x

40406 9 Fault Status Bit-map 7

1336 Cooldown Completed Fault Shutdown PC 2.x, PC3.x

Page 308: Mapa de Registros de Pcc

301

Addr. ControlResponseEvent NameFaultCode

NameBit #

40406 10 Fault Status Bit-map 7

1357 Eng Oil Lvl Remote Reservoir: BelowNormal

Warning PC 2.x, PC3.x

40407 0 Fault Status Bit-map 8

1376 Eng Camshaft Speed/Pos Warning Warning PC 2.x, PC3.x

40407 1 Fault Status Bit-map 8

3611 Custom Overcurrent Fault Warning PC 3.x

40407 2 Fault Status Bit-map 8

3513 Negative Sequence Overcurrent Warning PC 3.x

40407 3 Fault Status Bit-map 8

1416 Fail to Shutdown Warning PC 2.x, PC3.x

40407 4 Fault Status Bit-map 8

1417 Power Down Failure Warning PC 2.x, PC3.x

40407 5 Fault Status Bit-map 8

1433 Local E−Stop Shutdown PC 2.x, PC3.x

40407 6 Fault Status Bit-map 8

1434 Remote E−Stop Shutdown PC 2.x, PC3.x

40407 7 Fault Status Bit-map 8

1435 Low Coolant Temperature Warning PC 2.x, PC3.x

40407 8 Fault Status Bit-map 8

1438 Fail To Crank Fault Shutdown PC 2.x, PC3.x

40407 9 Fault Status Bit-map 8

1439 Low Fuel in Day Tank Warning PC 2.x, PC3.x

40407 10 Fault Status Bit-map 8

1441 Low Fuel Level Warning PC 2.x, PC3.x

40407 11 Fault Status Bit-map 8

1442 Weak Battery Warning PC 2.x, PC3.x

40407 12 Fault Status Bit-map 8

1443 Dead Battery Shutdown PC 2.x, PC3.x

40407 13 Fault Status Bit-map 8

1444 Overload Warning PC 2.x, PC3.x

40407 14 Fault Status Bit-map 8

1445 Short Circuit Shutdown PC 2.x, PC3.x

40407 15 Fault Status Bit-map 8

1446 High AC Voltage Shutdown PC 2.x, PC3.x

40408 0 Fault Status Bit-map 9

1447 Low AC Voltage Shutdown PC 2.x, PC3.x

40408 1 Fault Status Bit-map 9

1448 Underfrequency Shutdown PC 2.x, PC3.x

40408 2 Fault Status Bit-map 9

1449 Overfrequency Warning PC 2.x, PC3.x

40408 3 Fault Status Bit-map 9

1459 Reverse kW Shutdown PC 2.x, PC3.x

40408 4 Fault Status Bit-map 9

1461 Loss of Field Shutdown PC 2.x, PC3.x

40408 5 Fault Status Bit-map 9

1463 Not In Auto NONE PC 2.x, PC3.x

40408 6 Fault Status Bit-map 9

1464 Load Dump Warning PC 2.x, PC3.x

40408 7 Fault Status Bit-map 9

1465 Ready To Load NONE PC 2.x, PC3.x

Page 309: Mapa de Registros de Pcc

302

Addr. ControlResponseEvent NameFaultCode

NameBit #

40408 8 Fault Status Bit-map 9

1469 Speed/Frequency Mismatch Fault Warning PC 2.x, PC3.x

40408 9 Fault Status Bit-map 9

1471 High Current Warning Warning PC 2.x, PC3.x

40408 10 Fault Status Bit-map 9

1472 Overcurrent Shutdown Shutdown PC 2.x, PC3.x

40408 11 Fault Status Bit-map 9

1483 Common Alarm None PC 2.x, PC3.x

40408 12 Fault Status Bit-map 9

1548 Injector Solenoid Driver Cylinder 7:UnderCurrent

Warning PC 2.x, PC3.x

40408 13 Fault Status Bit-map 9

1549 Injector Solenoid Driver Cylinder 8:UnderCurrent

Warning PC 2.x, PC3.x

40408 14 Fault Status Bit-map 9

1551 Injector Solenoid Driver Cylinder 10:UnderCurrent

Warning PC 2.x, PC3.x

40408 15 Fault Status Bit-map 9

1552 Injector Solenoid Driver Cylinder 11:UnderCurrent

Warning PC 2.x, PC3.x

40409 0 Fault Status Bit-map 10

1553 Injector Solenoid Driver Cylinder 12:UnderCurrent

Warning PC 2.x, PC3.x

40409 1 Fault Status Bit-map 10

1554 Injector Solenoid Driver Cylinder 13:UnderCurrent

Warning PC 2.x, PC3.x

40409 2 Fault Status Bit-map 10

1555 Injector Solenoid Driver Cylinder 14:UnderCurrent

Warning PC 2.x, PC3.x

40409 3 Fault Status Bit-map 10

1556 Injector Solenoid Driver Cylinder 15:UnderCurrent

Warning PC 2.x, PC3.x

40409 4 Fault Status Bit-map 10

1557 Injector Solenoid Driver Cylinder 16:UnderCurrent

Warning PC 2.x, PC3.x

40409 7 Fault Status Bit-map 10

1622 Injector Solenoid Driver Cylinder 9:UnderCurrent

Warning PC 2.x, PC3.x

40409 8 Fault Status Bit-map 10

1689 Real Time Clock Power Interrupt Fault Warning PC 2.x, PC3.x

40409 9 Fault Status Bit-map 10

1695 SENSOR_SUPPLY_5_VOLT-AGE_HIGH_ERROR

Warning PC 2.x, PC3.x

40409 10 Fault Status Bit-map 10

1696 SENSOR_SUPPLY_5_VOLT-AGE_LOW_ERROR

Warning PC 2.x, PC3.x

40409 11 Fault Status Bit-map 10

1843 Crankcase Pressure: Vtg Above Nor-mal

Warning PC 2.x, PC3.x

40409 12 Fault Status Bit-map 10

1844 Crankcase Pressure: Vtg Below Nor-mal

Warning PC 2.x, PC3.x

40409 13 Fault Status Bit-map 10

1845 Water in Fuel Indicator: Vtg AboveNormal

Warning PC 2.x, PC3.x

40409 14 Fault Status Bit-map 10

1846 Water in Fuel Indicator: Vtg BelowNormal

Warning PC 2.x, PC3.x

40409 15 Fault Status Bit-map 10

1847 Eng Coolant Temp − Shutdown w/Cool Shutdownw/Cool-down

PC 2.x, PC3.x

40410 0 Fault Status Bit-map 11

1852 Water in Fuel Indicator: Above Nor-mal−Moderate

Warning PC 2.x, PC3.x

40410 1 Fault Status Bit-map 11

1853 HMI113 Fault 1 NONE PC 2.x, PC3.x

Page 310: Mapa de Registros de Pcc

303

Addr. ControlResponseEvent NameFaultCode

NameBit #

40410 2 Fault Status Bit-map 11

1854 HMI113 Fault 2 NONE PC 2.x, PC3.x

40410 3 Fault Status Bit-map 11

1855 HMI113 Fault 3 NONE PC 2.x, PC3.x

40410 5 Fault Status Bit-map 11

1891 Eng Oil Change Interval Warning PC 2.x, PC3.x

40410 6 Fault Status Bit-map 11

1893 J39_EGR_VALVE_COMM_TIME-OUT_ERROR

Warning PC 2.x, PC3.x

40410 7 Fault Status Bit-map 11

1894 J39_VGT_COMM_TIMEOUT_ERROR Warning PC 2.x, PC3.x

40410 8 Fault Status Bit-map 11

1896 EGR_DL_VALVE_STUCK_ERROR Warning PC 2.x, PC3.x

40410 9 Fault Status Bit-map 11

1899 EGR_DELTA_P_IR_LOW_ERROR Warning PC 2.x, PC3.x

40410 11 Fault Status Bit-map 11

1912 Utility Loss Of Phase Warning PC 3.x

40410 12 Fault Status Bit-map 11

1913 Genset Loss Of Phase Warning PC 3.x

40410 13 Fault Status Bit-map 11

1914 Utility Phase Rotation Warning PC 3.x

40410 14 Fault Status Bit-map 11

1915 Genset Phase Rotation Warning PC 3.x

40410 15 Fault Status Bit-map 11

1916 Sync Check OK NONE PC 3.x

40411 0 Fault Status Bit-map 12

1917 High Fuel Level Warning PC 2.x, PC3.x

40411 1 Fault Status Bit-map 12

1918 Very Low Fuel Level Shutdown PC 2.x, PC3.x

40411 2 Fault Status Bit-map 12

1933 EGR_DL_VOLTAGE_HIGH_ERROR Warning PC 2.x, PC3.x

40411 3 Fault Status Bit-map 12

1934 EGR_DL_VOLTAGE_LOW_ERROR Warning PC 2.x, PC3.x

40411 4 Fault Status Bit-map 12

1935 EGR_DL_COMMAND_SOURCE_ER-ROR

Warning PC 2.x, PC3.x

40411 5 Fault Status Bit-map 12

1942 BEYOND_THD_AZ_ERROR Warning PC 2.x, PC3.x

40411 6 Fault Status Bit-map 12

1943 CBR_DENSITY_DERATE_ER-ROR_ID

NONE PC 2.x, PC3.x

40411 7 Fault Status Bit-map 12

1944 HMI113 Output Configuration Fault Warning PC 2.x, PC3.x

40411 8 Fault Status Bit-map 12

1961 EGR_DL_EDU_TMPTR_HIGH_ER-ROR

Warning PC 2.x, PC3.x

40411 9 Fault Status Bit-map 12

1974 CRANKCASE_PRES-SURE_LEAST_SEV_HIGH

Warning PC 2.x, PC3.x

40411 10 Fault Status Bit-map 12

1992 Eng Crankshaft Speed/Posn: AboveNormal

Shutdown PC 2.x, PC3.x

40411 11 Fault Status Bit-map 12

1999 Maximum Parallel Time Warning PC 3.x

40411 12 Fault Status Bit-map 12

2185 Sensor Supply 4: Vtg Above Normal Warning PC 2.x, PC3.x

Page 311: Mapa de Registros de Pcc

304

Addr. ControlResponseEvent NameFaultCode

NameBit #

40411 13 Fault Status Bit-map 12

2186 Sensor Supply 4: Vtg Below Normal Warning PC 2.x, PC3.x

40411 14 Fault Status Bit-map 12

2215 Fuel Pump Delivery Pressure: BelowNormal

Warning PC 2.x, PC3.x

40411 15 Fault Status Bit-map 12

2249 APC_DIESEL_LOW2_PRS_ERROR Warning PC 2.x, PC3.x

40412 0 Fault Status Bit-map 13

2261 Fuel Pump Delivery Pressure: AboveNormal

Warning PC 2.x, PC3.x

40412 1 Fault Status Bit-map 13

2262 Fuel Pump Delivery−Below Normal Warning PC 2.x, PC3.x

40412 2 Fault Status Bit-map 13

2265 Electric Lift Pump for Eng Fuel: VtgAbove Normal

Warning PC 2.x, PC3.x

40412 3 Fault Status Bit-map 13

2266 Electric Lift Pump for Eng Fuel: VtgBelow Normal

Warning PC 2.x, PC3.x

40412 4 Fault Status Bit-map 13

2292 APC_DIESEL_FLOW_HIGH_ERROR Warning PC 2.x, PC3.x

40412 5 Fault Status Bit-map 13

2293 APC_DIESEL_FLOW_LOW_ERROR Warning PC 2.x, PC3.x

40412 6 Fault Status Bit-map 13

2311 Electronic Fuel Injection Control Valve Warning PC 2.x, PC3.x

40412 7 Fault Status Bit-map 13

2328 Utility Available NONE PC 3.x

40412 8 Fault Status Bit-map 13

2331 Utility Undervoltage Warning PC 3.x

40412 9 Fault Status Bit-map 13

2332 Utility Connected NONE PC 3.x

40412 10 Fault Status Bit-map 13

2333 Genset Connected NONE PC 3.x

40412 11 Fault Status Bit-map 13

2335 Excitation/Loss of AC Voltage Sensing Shutdown PC 2.x, PC3.x

40412 12 Fault Status Bit-map 13

2336 Checksum Fault Shutdown PC 2.x, PC3.x

40412 13 Fault Status Bit-map 13

2342 Too Long in Idle Warning PC 2.x, PC3.x

40412 14 Fault Status Bit-map 13

2358 Utility Overvoltage Warning PC 3.x

40412 15 Fault Status Bit-map 13

2377 Fan Control: Vtg Above Normal Warning PC 2.x, PC3.x

40413 0 Fault Status Bit-map 14

2396 Utility Breaker Fail To Close Warning PC 3.x

40413 1 Fault Status Bit-map 14

2397 Utility Breaker Fail To Open Warning PC 3.x

40413 2 Fault Status Bit-map 14

3226 Base Load NONE PC 3.x

40413 3 Fault Status Bit-map 14

3227 Peak Shave NONE PC 3.x

40413 4 Fault Status Bit-map 14

2555 GHC_LOW_VOLTAGE_ERROR_1 Warning PC 2.x, PC3.x

40413 5 Fault Status Bit-map 14

2556 GHC_HIGH_VOLTAGE_ERROR_1 Warning PC 2.x, PC3.x

Page 312: Mapa de Registros de Pcc

305

Addr. ControlResponseEvent NameFaultCode

NameBit #

40413 6 Fault Status Bit-map 14

2678 Charging Alternator Failure Fault Warning PC 2.x, PC3.x

40413 7 Fault Status Bit-map 14

2965 Genset Available NONE PC 3.x

40413 8 Fault Status Bit-map 14

2971 Test/Exercise is Active Fault NONE PC 2.x, PC3.x

40413 9 Fault Status Bit-map 14

2972 Field Overload Shutdown PC 2.x, PC3.x

40413 10 Fault Status Bit-map 14

2973 CHARGE_PRESS_IR_ERROR Warning PC 2.x, PC3.x

40413 11 Fault Status Bit-map 14

2943 Manual Switch Configuration Fault Warning PC 2.x, PC3.x

40413 12 Fault Status Bit-map 14

2944 Auto Switch Configuration Fault Warning PC 2.x, PC3.x

40413 13 Fault Status Bit-map 14

2914 Genset AC Meter Failed Shutdown PC 2.x, PC3.x

40413 14 Fault Status Bit-map 14

2915 Genset Bus AC Meter Failed Warning PC 3.x

40413 15 Fault Status Bit-map 14

2916 Utility AC Meter Failed Warning PC 3.x

40414 0 Fault Status Bit-map 15

2814 Genset CT Ratio Too Small Shutdown PC 2.x, PC3.x

40414 1 Fault Status Bit-map 15

2815 Genset CT Ratio Too Large Warning PC 2.x, PC3.x

40414 2 Fault Status Bit-map 15

2816 Genset PT Ratio Too Small Shutdown PC 2.x, PC3.x

40414 3 Fault Status Bit-map 15

2817 Genset PT Ratio Too Large Warning PC 2.x, PC3.x

40414 4 Fault Status Bit-map 15

2818 Genset Bus PT Ratio Too Small Shutdown PC 3.x

40414 5 Fault Status Bit-map 15

2819 Genset Bus PT Ratio Too Large Warning PC 3.x

40414 6 Fault Status Bit-map 15

2821 Utility PT Ratio Too Small Shutdown PC 3.x

40414 7 Fault Status Bit-map 15

2822 Utility PT Ratio Too Large Warning PC 3.x

40414 8 Fault Status Bit-map 15

2619 Aux101 0 Input 1 Fault Warning PC 2.x, PC3.x

40414 9 Fault Status Bit-map 15

2621 Aux101 0 Input 2 Fault Warning PC 2.x, PC3.x

40414 10 Fault Status Bit-map 15

2622 Aux101 0 Input 3 Fault Warning PC 2.x, PC3.x

40414 11 Fault Status Bit-map 15

2623 Aux101 0 Input 4 Fault Warning PC 2.x, PC3.x

40414 12 Fault Status Bit-map 15

2624 Aux101 0 Input 5 Fault Warning PC 2.x, PC3.x

40414 13 Fault Status Bit-map 15

2625 Aux101 0 Input 6 Fault Warning PC 2.x, PC3.x

40414 14 Fault Status Bit-map 15

2626 Aux101 0 Input 7 Fault Warning PC 2.x, PC3.x

Page 313: Mapa de Registros de Pcc

306

Addr. ControlResponseEvent NameFaultCode

NameBit #

40414 15 Fault Status Bit-map 15

2627 Aux101 0 Input 8 Fault Warning PC 2.x, PC3.x

40415 0 Fault Status Bit-map 16

2882 Aux101 1 Input 1 Fault Warning PC 2.x, PC3.x

40415 1 Fault Status Bit-map 16

2883 Aux101 1 Input 2 Fault Warning PC 2.x, PC3.x

40415 2 Fault Status Bit-map 16

2884 Aux101 1 Input 3 Fault Warning PC 2.x, PC3.x

40415 3 Fault Status Bit-map 16

2885 Aux101 1 Input 4 Fault Warning PC 2.x, PC3.x

40415 4 Fault Status Bit-map 16

2886 Aux101 1 Input 5 Fault Warning PC 2.x, PC3.x

40415 5 Fault Status Bit-map 16

2887 Aux101 1 Input 6 Fault Warning PC 2.x, PC3.x

40415 6 Fault Status Bit-map 16

2888 Aux101 1 Input 7 Fault Warning PC 2.x, PC3.x

40415 7 Fault Status Bit-map 16

2889 Aux101 1 Input 8 Fault Warning PC 2.x, PC3.x

40415 8 Fault Status Bit-map 16

2628 Aux102 0 Expansion Input 9 Fault Warning PC 2.x, PC3.x

40415 9 Fault Status Bit-map 16

2629 Aux102 0 Expansion Input 10 Fault Warning PC 2.x, PC3.x

40415 10 Fault Status Bit-map 16

2631 Aux102 0 Expansion Input 11 Fault Warning PC 2.x, PC3.x

40415 11 Fault Status Bit-map 16

2632 Aux102 0 Expansion Input 12 Fault Warning PC 2.x, PC3.x

40415 12 Fault Status Bit-map 16

2891 Aux102 1 Expansion Input 9 Fault Warning PC 2.x, PC3.x

40415 13 Fault Status Bit-map 16

2892 Aux102 1 Expansion Input 10 Fault Warning PC 2.x, PC3.x

40415 14 Fault Status Bit-map 16

2893 Aux102 1 Expansion Input 11 Fault Warning PC 2.x, PC3.x

40415 15 Fault Status Bit-map 16

2894 Aux102 1 Expansion Input 12 Fault Warning PC 2.x, PC3.x

40416 0 Fault Status Bit-map 17

2895 PCCnet Device Failed Warning Warning PC 2.x, PC3.x

40416 1 Fault Status Bit-map 17

2896 PCCnet Device Failed Shutdown Shutdown PC 2.x, PC3.x

40416 2 Fault Status Bit-map 17

2917 Genset Bus Voltage OOR Warning Warning PC 3.x

40416 3 Fault Status Bit-map 17

2918 Utility Voltage OOR Warning Warning PC 3.x

40416 4 Fault Status Bit-map 17

2919 Utility Current OOR Warning Warning PC 3.x

40416 5 Fault Status Bit-map 17

2921 Genset Bus Current OOR Warning Warning PC 3.x

40416 6 Fault Status Bit-map 17

2922 Genset Neutral Current OOR Warning Warning PC 3.x

40416 7 Fault Status Bit-map 17

2923 Genset Bus kW OOR Warning Warning PC 3.x

Page 314: Mapa de Registros de Pcc

307

Addr. ControlResponseEvent NameFaultCode

NameBit #

40416 8 Fault Status Bit-map 17

2924 Genset Bus kVAR OOR Warning Warning PC 3.x

40416 9 Fault Status Bit-map 17

2925 Genset Bus kVA OOR Warning Warning PC 3.x

40416 10 Fault Status Bit-map 17

2926 Utility kW OOR Warning Warning PC 3.x

40416 11 Fault Status Bit-map 17

2927 Utility kVAR OOR Warning Warning PC 3.x

40416 12 Fault Status Bit-map 17

2928 Utility kVA OOR Warning Warning PC 3.x

40416 13 Fault Status Bit-map 17

3599 Ground Current OOR Warning Warning PC 3.x

40416 14 Fault Status Bit-map 17

2931 AUX101 Device ID Fault Shutdown PC 2.x, PC3.x

40416 15 Fault Status Bit-map 17

2779 Utility Unloaded Event NONE PC 3.x

40417 3 Fault Status Bit-map 18

2932 AUX101 Oil Temp OOR Hi Warning PC 2.x, PC3.x

40417 4 Fault Status Bit-map 18

2933 AUX101 Oil Temp OOR Low Warning PC 2.x, PC3.x

40417 5 Fault Status Bit-map 18

2657 Exhaust Stack Temp 1 OOR High Warning PC 2.x, PC3.x

40417 6 Fault Status Bit-map 18

2947 Exhaust Stack Temp 1 OOR Low Warning PC 2.x, PC3.x

40417 7 Fault Status Bit-map 18

2949 High Exhaust Stack Temperature 1 Warning PC 2.x, PC3.x

40417 8 Fault Status Bit-map 18

2653 Exhaust Stack Temp 2 OOR High Warning PC 2.x, PC3.x

40417 9 Fault Status Bit-map 18

2946 Exhaust Stack Temp 2 OOR Low Warning PC 2.x, PC3.x

40417 10 Fault Status Bit-map 18

2948 High Exhaust Stack Temperature 2 Warning PC 2.x, PC3.x

40417 11 Fault Status Bit-map 18

2934 Ambient Temp OOR High Warning PC 2.x, PC3.x

40417 12 Fault Status Bit-map 18

2935 Ambient Temp OOR Low Warning PC 2.x, PC3.x

40417 13 Fault Status Bit-map 18

2936 Fuel Level OOR High Warning PC 2.x, PC3.x

40417 14 Fault Status Bit-map 18

2937 Fuel Level OOR Low Warning PC 2.x, PC3.x

40417 15 Fault Status Bit-map 18

2951 Alternator Temp 1 OOR High Warning PC 2.x, PC3.x

40418 0 Fault Status Bit-map 19

2952 Alternator Temp 1 OOR Low Warning PC 2.x, PC3.x

40418 1 Fault Status Bit-map 19

2953 High Alternator Temp 1 Warning PC 2.x, PC3.x

40418 2 Fault Status Bit-map 19

2954 Alternator Temp 2 OOR High Warning PC 2.x, PC3.x

40418 3 Fault Status Bit-map 19

2955 Alternator Temp 2 OOR Low Warning PC 2.x, PC3.x

Page 315: Mapa de Registros de Pcc

308

Addr. ControlResponseEvent NameFaultCode

NameBit #

40418 4 Fault Status Bit-map 19

2956 High Alternator Temp 2 Warning PC 2.x, PC3.x

40418 5 Fault Status Bit-map 19

2957 Alternator Temp 3 OOR High Warning PC 2.x, PC3.x

40418 6 Fault Status Bit-map 19

2958 Alternator Temp 3 OOR Low Warning PC 2.x, PC3.x

40418 7 Fault Status Bit-map 19

2959 High Alternator Temp 3 Warning PC 2.x, PC3.x

40418 8 Fault Status Bit-map 19

2992 Intake Manifold Temp 1 OOR High Warning PC 2.x, PC3.x

40418 9 Fault Status Bit-map 19

2978 Intake Manifold Temp 1 OOR Low Warning PC 2.x, PC3.x

40418 10 Fault Status Bit-map 19

2981 Drive End Bearing Temp OOR High Warning PC 2.x, PC3.x

40418 11 Fault Status Bit-map 19

2982 Drive End Bearing Temp OOR Low Warning PC 2.x, PC3.x

40418 12 Fault Status Bit-map 19

2983 High Drive End Bearing Temperature Warning PC 2.x, PC3.x

40418 13 Fault Status Bit-map 19

2984 Non−Drive End Bearing Temp OORHigh

Warning PC 2.x, PC3.x

40418 14 Fault Status Bit-map 19

2985 Non−Drive End Bearing Temp OORLow

Warning PC 2.x, PC3.x

40418 15 Fault Status Bit-map 19

2986 High Non−Drive End Bearing Temper-ature

Warning PC 2.x, PC3.x

40419 0 Fault Status Bit-map 20

2945 Rupture Basin Warning PC 2.x, PC3.x

40419 1 Fault Status Bit-map 20

2979 High Alternator Temp Switch fault Warning PC 2.x, PC3.x

40419 2 Fault Status Bit-map 20

2993 Battery Charger Failed Fault Warning PC 2.x, PC3.x

40419 3 Fault Status Bit-map 20

2938 Earth/Ground Fault Warning PC 2.x, PC3.x

40419 4 Fault Status Bit-map 20

2939 Modbus Failure Fault Warning PC 2.x, PC3.x

40419 5 Fault Status Bit-map 20

2977 Low Coolant Level #2 Warning PC 2.x, PC3.x

40419 6 Fault Status Bit-map 20

1978 Speed Bias OOR High Warning PC 2.x, PC3.x

40419 7 Fault Status Bit-map 20

2541 Voltage Bias OOR Low Warning PC 2.x, PC3.x

40419 8 Fault Status Bit-map 20

2539 Voltage Bias OOR High Warning PC 2.x, PC3.x

40419 9 Fault Status Bit-map 20

1573 Configurable Input #1 NONE PC 2.x, PC3.x

40419 10 Fault Status Bit-map 20

1312 Configurable Input #2 NONE PC 2.x, PC3.x

40419 11 Fault Status Bit-map 20

1317 Configurable Input #13 NONE PC 2.x, PC3.x

40419 12 Fault Status Bit-map 20

1318 Configurable Input #14 NONE PC 2.x, PC3.x

Page 316: Mapa de Registros de Pcc

309

Addr. ControlResponseEvent NameFaultCode

NameBit #

40419 13 Fault Status Bit-map 20

1979 Speed Bias OOR Low Warning PC 2.x, PC3.x

40419 14 Fault Status Bit-map 20

236 Both Engine Speed Signals Lost: MostSevere Level

Shutdown PC 2.x, PC3.x

40419 15 Fault Status Bit-map 20

3629 Less Severe Response−Warning Warning PC 3.x

40420 0 Fault Status Bit-map 21

3631 Most Severe−Shutdown Shutdown PC 3.x

40430 0 Event Status Bit-map 1

1540 Common Warning NONE PC 2.x, PC3.x

40430 1 Event Status Bit-map 1

1541 Common Shutdown NONE PC 2.x, PC3.x

40431 0 Fault Status GasBitmap 1

121 EPS Main Channel Lost Error Warning PC 3.x

40431 1 Fault Status GasBitmap 1

136 Oil Inlet Pressure High Error Warning PC 3.x

40431 2 Fault Status GasBitmap 1

137 Oil Inlet Pressure Low Error Warning PC 3.x

40431 3 Fault Status GasBitmap 1

142 Oil Overpressure Error Warning PC 3.x

40431 4 Fault Status GasBitmap 1

156 Intake Manifold Temp 2 OORH Warning PC 3.x

40431 5 Fault Status GasBitmap 1

157 Intake Manifold Temp 2 OORL Warning PC 3.x

40431 6 Fault Status GasBitmap 1

158 Intake Manifold Temp 2 High Shutdown PC 3.x

40431 7 Fault Status GasBitmap 1

159 Intake Manifold 3 Temp OORH Warning PC 3.x

40431 8 Fault Status GasBitmap 1

161 Intake Manifold 3 Temp OORL Warning PC 3.x

40431 9 Fault Status GasBitmap 1

162 Intake Manifold 3 Temp High Shutdown PC 3.x

40431 10 Fault Status GasBitmap 1

163 Intake Manifold 4 Temp OORH Warning PC 3.x

40431 11 Fault Status GasBitmap 1

164 Intake Manifold 4 Temp OORL Warning PC 3.x

40431 12 Fault Status GasBitmap 1

165 Intake Manifold 4 Temp High Shutdown PC 3.x

40431 13 Fault Status GasBitmap 1

175 Throttle_Driver_Feedback_High_Error Shutdownw/Cool-down

PC 3.x

40431 14 Fault Status GasBitmap 1

176 Throttle_Driver_Feedback_Low_Error Shutdownw/Cool-down

PC 3.x

40431 15 Fault Status GasBitmap 1

177 Throttle_Actuator_Error Shutdownw/Cool-down

PC 3.x

40432 0 Fault Status GasBitmap 2

219 Eng Oil Level Remote Reservoir:Least Severe Level

Warning PC 2.x, PC3.x

Page 317: Mapa de Registros de Pcc

310

Addr. ControlResponseEvent NameFaultCode

NameBit #

40432 1 Fault Status GasBitmap 2

233 HT Coolant Pressure Moderate Low Warning PC 2.x, PC3.x

40432 2 Fault Status GasBitmap 2

244 Red Stop Lamp Driver OORL Warning PC 3.x

40432 3 Fault Status GasBitmap 2

246 Exhaust Gas Temp Sensor 1 OORH Warning PC 3.x

40432 4 Fault Status GasBitmap 2

247 Exhaust Gas Temp Sensor 1 OORL Warning PC 3.x

40432 5 Fault Status GasBitmap 2

248 Exhaust Gas Temp Sensor 1 High Warning PC 3.x

40432 6 Fault Status GasBitmap 2

253 Oil Level Low Error Shutdownw/Cool-down

PC 3.x

40432 7 Fault Status GasBitmap 2

254 FSO NON Low Control Error Shutdown PC 2.x, PC3.x

40432 8 Fault Status GasBitmap 2

277 Fuel Control Valve Out of Adj Warning PC 3.x

40432 9 Fault Status GasBitmap 2

346 Powerdown Data Lost Error Warning PC 3.x

40432 10 Fault Status GasBitmap 2

354 Manifold_Absolute_Pres-sure_1_High_Error

Warning PC 3.x

40432 11 Fault Status GasBitmap 2

355 Manifold_Absolute_Pres-sure_1_Low_Error

Warning PC 3.x

40432 12 Fault Status GasBitmap 2

412 J1708 Link Cannot Transmit Error NONE PC 3.x

40432 13 Fault Status GasBitmap 2

414 J1708 Link Not Fast Enough Error NONE PC 3.x

40432 14 Fault Status GasBitmap 2

453 Gas_Mass_Flow_High_Error Warning PC 3.x

40432 15 Fault Status GasBitmap 2

454 Gas_Mass_Flow_Low_Error Warning PC 3.x

40433 0 Fault Status GasBitmap 3

458 Spark_Timing_B_Error Shutdownw/Cool-down

PC 3.x

40433 1 Fault Status GasBitmap 3

459 Spark_Timing_A_Error Shutdownw/Cool-down

PC 3.x

40433 2 Fault Status GasBitmap 3

461 Spark_Reference_B_Error Shutdownw/Cool-down

PC 3.x

40433 3 Fault Status GasBitmap 3

462 Spark_Reference_A_Error Shutdownw/Cool-down

PC 3.x

40433 4 Fault Status GasBitmap 3

477 Isolated Battery Voltage Low Error Warning PC 3.x

40433 5 Fault Status GasBitmap 3

478 Isolated Battery Voltage High Error Warning PC 3.x

40433 6 Fault Status GasBitmap 3

512 Throttle Pos 1 Feedback OOR High Warning PC 3.x

Page 318: Mapa de Registros de Pcc

311

Addr. ControlResponseEvent NameFaultCode

NameBit #

40433 7 Fault Status GasBitmap 3

513 Throttle Pos 1 Feedback OOR Low Warning PC 3.x

40433 8 Fault Status GasBitmap 3

557 Fuel Control Valve 2 OORH Shutdownw/Cool-down

PC 3.x

40433 9 Fault Status GasBitmap 3

558 Fuel Control Valve 2 OORL Warning PC 3.x

40433 10 Fault Status GasBitmap 3

561 Heavy_Knock_Error_1_(A1) Shutdownw/Cool-down

PC 3.x

40433 11 Fault Status GasBitmap 3

562 Heavy_Knock_Error_2_(B1) Shutdownw/Cool-down

PC 3.x

40433 12 Fault Status GasBitmap 3

563 Heavy_Knock_Error_3_(A2) Shutdownw/Cool-down

PC 3.x

40433 13 Fault Status GasBitmap 3

564 Heavy_Knock_Error_4_(B2) Shutdownw/Cool-down

PC 3.x

40433 14 Fault Status GasBitmap 3

565 Heavy_Knock_Error_5_(A3) Shutdownw/Cool-down

PC 3.x

40433 15 Fault Status GasBitmap 3

566 Heavy_Knock_Error_6_(B3) Shutdownw/Cool-down

PC 3.x

40434 0 Fault Status GasBitmap 4

567 Heavy_Knock_Error_7_(A4) Shutdownw/Cool-down

PC 3.x

40434 1 Fault Status GasBitmap 4

568 Heavy_Knock_Error_8_(B4) Shutdownw/Cool-down

PC 3.x

40434 2 Fault Status GasBitmap 4

569 Heavy_Knock_Error_9_(A5) Shutdownw/Cool-down

PC 3.x

40434 3 Fault Status GasBitmap 4

571 Knock Cyl 1 (A1) OORL Warning PC 3.x

40434 4 Fault Status GasBitmap 4

572 Knock Cyl 2 (B1) OORL Warning PC 3.x

40434 5 Fault Status GasBitmap 4

573 Knock Cyl 3 (A2) OORL Warning PC 3.x

40434 6 Fault Status GasBitmap 4

574 Knock Cyl 4 (B2) OORL Warning PC 3.x

40434 7 Fault Status GasBitmap 4

575 Knock Cyl 5 (A3) OORL Warning PC 3.x

40434 8 Fault Status GasBitmap 4

576 Knock Cyl 6 (B3) OORL Warning PC 3.x

40434 9 Fault Status GasBitmap 4

577 Knock Cyl 7 (A4) OORL Warning PC 3.x

40434 10 Fault Status GasBitmap 4

578 Knock Cyl 8 (B4) OORL Warning PC 3.x

Page 319: Mapa de Registros de Pcc

312

Addr. ControlResponseEvent NameFaultCode

NameBit #

40434 11 Fault Status GasBitmap 4

579 Knock Cyl 9 (A5) OORL Warning PC 3.x

40434 12 Fault Status GasBitmap 4

584 High Side DRV3 High Control Error Warning PC 3.x

40434 13 Fault Status GasBitmap 4

585 High Side DRV3 Low Control Error Warning PC 3.x

40434 14 Fault Status GasBitmap 4

591 Exhaust_Backpressure_High_Error Warning PC 3.x

40434 15 Fault Status GasBitmap 4

592 Exhaust_Backpressure_Low_Error Warning PC 3.x

40435 0 Fault Status GasBitmap 5

595 Turbo 1 Overspeed Warning Error Warning PC 3.x

40435 1 Fault Status GasBitmap 5

618 Turbo 1 Inlet Pressure High Warning PC 3.x

40435 2 Fault Status GasBitmap 5

619 Turbo 2 Inlet Press High Warning PC 3.x

40435 3 Fault Status GasBitmap 5

641 Exhaust Temp 1 (A1) High Serious Er-ror

Shutdownw/Cool-down

PC 3.x

40435 4 Fault Status GasBitmap 5

642 Exhaust Temp 3 (A2) High Serious Er-ror

Shutdownw/Cool-down

PC 3.x

40435 5 Fault Status GasBitmap 5

643 Exhaust Temp 5 (A3) High Serious Er-ror

Shutdownw/Cool-down

PC 3.x

40435 6 Fault Status GasBitmap 5

644 Exhaust Temp 7 (A4) High Serious Er-ror

Shutdownw/Cool-down

PC 3.x

40435 7 Fault Status GasBitmap 5

645 Exhaust Temp 9 (A5) High Serious Er-ror

Shutdownw/Cool-down

PC 3.x

40435 8 Fault Status GasBitmap 5

646 Exhaust Temp 11 (A6) High SeriousError

Shutdownw/Cool-down

PC 3.x

40435 9 Fault Status GasBitmap 5

647 Exhaust Temp 13 (A7) High SeriousError

Shutdownw/Cool-down

PC 3.x

40435 10 Fault Status GasBitmap 5

648 Exhaust Temp 15 (A8) High SeriousError

Shutdownw/Cool-down

PC 3.x

40435 11 Fault Status GasBitmap 5

651 Exhaust Temp 17 (A9) High SeriousError

Shutdownw/Cool-down

PC 3.x

40435 12 Fault Status GasBitmap 5

652 Exhaust Temp 2 (B1) High Serious Er-ror

Shutdownw/Cool-down

PC 3.x

40435 13 Fault Status GasBitmap 5

653 Exhaust Temp 4 (B2) High Serious Er-ror

Shutdownw/Cool-down

PC 3.x

Page 320: Mapa de Registros de Pcc

313

Addr. ControlResponseEvent NameFaultCode

NameBit #

40435 14 Fault Status GasBitmap 5

654 Exhaust Temp 6 (B3) High Serious Er-ror

Shutdownw/Cool-down

PC 3.x

40435 15 Fault Status GasBitmap 5

655 Exhaust Temp 8 (B4) High Serious Er-ror

Shutdownw/Cool-down

PC 3.x

40436 0 Fault Status GasBitmap 6

656 Exhaust Temp 10 (B5) High SeriousError

Shutdownw/Cool-down

PC 3.x

40436 1 Fault Status GasBitmap 6

657 Exhaust Temp 12 (B6) High SeriousError

Shutdownw/Cool-down

PC 3.x

40436 2 Fault Status GasBitmap 6

658 Exhaust Temp 14 (B7) High SeriousError

Shutdownw/Cool-down

PC 3.x

40436 3 Fault Status GasBitmap 6

671 Exhaust Gas Temp Cyl 1 (A1) OORL Warning PC 3.x

40436 4 Fault Status GasBitmap 6

672 Exhaust Gas Temp Cyl 3 (A2) OORL Warning PC 3.x

40436 5 Fault Status GasBitmap 6

673 Exhaust Gas Temp Cyl 5 (A3) OORL Warning PC 3.x

40436 6 Fault Status GasBitmap 6

674 Exhaust Gas Temp Cyl 7 (A4) OORL Warning PC 3.x

40436 7 Fault Status GasBitmap 6

675 Exhaust Gas Temp Cyl 9 (A5) OORL Warning PC 3.x

40436 8 Fault Status GasBitmap 6

676 Exhaust Gas Temp Cyl 11 (A6) OORL Warning PC 3.x

40436 9 Fault Status GasBitmap 6

677 Exhaust Gas Temp Cyl 13 (A7) OORL Warning PC 3.x

40436 10 Fault Status GasBitmap 6

678 Exhaust Gas Temp Cyl 15 (A8) OORL Warning PC 3.x

40436 11 Fault Status GasBitmap 6

683 Turbo 2 Speed Moderate High Warning PC 3.x

40436 12 Fault Status GasBitmap 6

684 Turbo 2 Speed Moderate Low Warning PC 3.x

40436 13 Fault Status GasBitmap 6

685 Turbo 2 Speed Incorrect Warning PC 3.x

40436 14 Fault Status GasBitmap 6

686 Turbo 1 Speed Incorrect Warning PC 2.x, PC3.x

40436 15 Fault Status GasBitmap 6

687 Turbo 1 Speed Low Warning PC 3.x

40437 0 Fault Status GasBitmap 7

697 ECM Internal Temperature High Error Warning PC 2.x, PC3.x

40437 1 Fault Status GasBitmap 7

698 ECM Internal Temperature Low Error Warning PC 2.x, PC3.x

40437 2 Fault Status GasBitmap 7

721 Exhaust Gas Temp 2 (B1) OORL Warning PC 3.x

40437 3 Fault Status GasBitmap 7

722 Exhaust Gas Temp 4 (B2) OORL Warning PC 3.x

Page 321: Mapa de Registros de Pcc

314

Addr. ControlResponseEvent NameFaultCode

NameBit #

40437 4 Fault Status GasBitmap 7

723 Exhaust Gas Temp 6 (B3) OORL Warning PC 3.x

40437 5 Fault Status GasBitmap 7

724 Exhaust Gas Temp 8 (B4) OORL Warning PC 3.x

40437 6 Fault Status GasBitmap 7

725 Exhaust Gas Temp 10 (B5) OORL Warning PC 3.x

40437 7 Fault Status GasBitmap 7

726 Exhaust Gas Temp 12 (B6) OORL Warning PC 3.x

40437 8 Fault Status GasBitmap 7

727 Exhaust Gas Temp 14 (B7) OORL Warning PC 3.x

40437 9 Fault Status GasBitmap 7

728 Exhaust Gas Temp 16 (B8) OORL Warning PC 3.x

40437 10 Fault Status GasBitmap 7

736 Starter Air Pressure OORL Warning PC 3.x

40437 11 Fault Status GasBitmap 7

737 Starter Air Pressure OORH Warning PC 3.x

40437 12 Fault Status GasBitmap 7

738 Starter Air Press Underpressure Error Warning PC 3.x

40437 13 Fault Status GasBitmap 7

741 Air Filter Restriction Pressure High Er-ror

Warning PC 3.x

40437 14 Fault Status GasBitmap 7

742 Air Filter Restriction Pressure Low Er-ror

Warning PC 3.x

40437 15 Fault Status GasBitmap 7

751 Gas_Mass_Flow_In_Range_Error Warning PC 3.x

40438 0 Fault Status GasBitmap 8

752 Exhaust_Gas_Oxygen_In_Range_Er-ror

Warning PC 3.x

40438 1 Fault Status GasBitmap 8

783 Intake Manifold 1 Temp Abnormal Shutdownw/Cool-down

PC 3.x

40438 2 Fault Status GasBitmap 8

1213 COP_Overboost_Error Shutdownw/Cool-down

PC 3.x

40438 3 Fault Status GasBitmap 8

1274 Heavy_Knock_Error_10_(B5) Shutdownw/Cool-down

PC 3.x

40438 4 Fault Status GasBitmap 8

1281 Heavy_Knock_Error_12_(B6) Shutdownw/Cool-down

PC 3.x

40438 5 Fault Status GasBitmap 8

1285 Continuous_Light_Knock_Er-ror_13_(A7)

Shutdownw/Cool-down

PC 3.x

40438 6 Fault Status GasBitmap 8

1286 Heavy_Knock_Error_13_(A7) Shutdownw/Cool-down

PC 3.x

40438 7 Fault Status GasBitmap 8

1291 Heavy_Knock_Error_14_(B7) Shutdownw/Cool-down

PC 3.x

40438 8 Fault Status GasBitmap 8

1295 Continuous_Light_Knock_Er-ror_15_(A8)

Shutdownw/Cool-down

PC 3.x

Page 322: Mapa de Registros de Pcc

315

Addr. ControlResponseEvent NameFaultCode

NameBit #

40438 9 Fault Status GasBitmap 8

1296 Heavy_Knock_Error_15_(A8) Shutdownw/Cool-down

PC 3.x

40438 10 Fault Status GasBitmap 8

1311 Heavy_Knock_Error_18_(B9) Shutdownw/Cool-down

PC 3.x

40438 11 Fault Status GasBitmap 8

1362 Oil Filter Restriction Error Warning PC 3.x

40438 12 Fault Status GasBitmap 8

1452 Genset Breaker Fail To Close Shutdown PC 3.x

40438 13 Fault Status GasBitmap 8

1457 Fail To Synchronize Warning PC 3.x

40438 14 Fault Status GasBitmap 8

1458 Sync Phase Rotation Mismatch Warning PC 3.x

40438 15 Fault Status GasBitmap 8

1474 ECM Software mismatch Shutdownw/Cool-down

PC 3.x

40439 0 Fault Status GasBitmap 9

1521 Exhaust Gas Temp 3 (A2) OORH Warning PC 3.x

40439 1 Fault Status GasBitmap 9

1522 Exhaust Gas Temp 5 (A3) OORH Warning PC 3.x

40439 2 Fault Status GasBitmap 9

1523 Exhaust Gas Temp 7 (A4) OORH Warning PC 3.x

40439 3 Fault Status GasBitmap 9

1524 Exhaust Gas Temp 9 (A5) OORH Warning PC 3.x

40439 4 Fault Status GasBitmap 9

1525 Exhaust Gas Temp 11 (A6) OORH Warning PC 3.x

40439 5 Fault Status GasBitmap 9

1526 Exhaust Gas Temp 13 (A7) OORH Warning PC 3.x

40439 6 Fault Status GasBitmap 9

1527 Exhaust Gas Temp 15 (A8) OORH Warning PC 3.x

40439 7 Fault Status GasBitmap 9

1528 Exhaust Gas Temp 17 (A9) OORH Warning PC 3.x

40439 8 Fault Status GasBitmap 9

1529 Exhaust Gas Temp 2 (B1) OORH Warning PC 3.x

40439 9 Fault Status GasBitmap 9

1531 Exhaust Gas Temp 6 (B3) OORH Warning PC 3.x

40439 10 Fault Status GasBitmap 9

1532 Exhaust Gas Temp 8 (B4) OORH Warning PC 3.x

40439 11 Fault Status GasBitmap 9

1533 Exhaust Gas Temp 10 (B5) OORH Warning PC 3.x

40439 12 Fault Status GasBitmap 9

1534 Exhaust Gas Temp 12 (B6) OORH Warning PC 3.x

40439 13 Fault Status GasBitmap 9

1535 Exhaust Gas Temp 14 (B7) OORH Warning PC 3.x

40439 14 Fault Status GasBitmap 9

1536 Exhaust Gas Temp 16 (B8) OORH Warning PC 3.x

40439 15 Fault Status GasBitmap 9

1537 Exhaust Gas Temp 18 (B9) OORH Warning PC 3.x

Page 323: Mapa de Registros de Pcc

316

Addr. ControlResponseEvent NameFaultCode

NameBit #

40440 0 Fault Status GasBitmap 10

1545 EPS Backup Channel Lost Warning PC 3.x

40440 1 Fault Status GasBitmap 10

1546 EPS Main Channel Lost Warning PC 3.x

40440 2 Fault Status GasBitmap 10

1579 Continuous_Light_Knock_Er-ror_12_(B6)

Shutdownw/Cool-down

PC 3.x

40440 3 Fault Status GasBitmap 10

1581 Continuous_Light_Knock_Er-ror_14_(B7)

Shutdownw/Cool-down

PC 3.x

40440 4 Fault Status GasBitmap 10

1582 Continuous_Light_Knock_Er-ror_16_(B8)

Shutdownw/Cool-down

PC 3.x

40440 5 Fault Status GasBitmap 10

1583 Heavy_Knock_Error_16_(B8) Shutdownw/Cool-down

PC 3.x

40440 6 Fault Status GasBitmap 10

1587 Continuous_Light_Knock_Er-ror_17_(A9)

Shutdownw/Cool-down

PC 3.x

40440 7 Fault Status GasBitmap 10

1588 Heavy_Knock_Error_17_(A9) Shutdownw/Cool-down

PC 3.x

40440 8 Fault Status GasBitmap 10

1593 Continuous_Light_Knock_Er-ror_18_(B9)

Shutdownw/Cool-down

PC 3.x

40440 9 Fault Status GasBitmap 10

1618 Exhaust Gas Temp Cyl 1 (A1) OORH Warning PC 3.x

40440 10 Fault Status GasBitmap 10

1619 Exhaust Gas Temp Cyl 4 (B2) OORH Warning PC 3.x

40440 11 Fault Status GasBitmap 10

1636 Intake Manif Press 2 OORH Warning PC 3.x

40440 12 Fault Status GasBitmap 10

1637 Intake Manif Press 2 OORL Warning PC 3.x

40440 13 Fault Status GasBitmap 10

1737 CAN_Throttle_Internal_Failure_Error Shutdownw/Cool-down

PC 3.x

40440 14 Fault Status GasBitmap 10

1738 CAN_Throttle_Internal_Fault_Error Warning PC 3.x

40440 15 Fault Status GasBitmap 10

1739 Engine Throttle Control Condition Ex-ists

Warning PC 3.x

40441 0 Fault Status GasBitmap 11

1741 CAN_Throttle_High_Temp_Warn-ing_Error

Warning PC 3.x

40441 1 Fault Status GasBitmap 11

1742 CAN_Throttle_Temp_Limiting_Error Warning PC 3.x

40441 2 Fault Status GasBitmap 11

1743 Throttle Ctrl 2 OOR High Shutdownw/Cool-down

PC 3.x

40441 3 Fault Status GasBitmap 11

1744 Throttle Ctrl 2 OOR Low Shutdownw/Cool-down

PC 3.x

Page 324: Mapa de Registros de Pcc

317

Addr. ControlResponseEvent NameFaultCode

NameBit #

40441 4 Fault Status GasBitmap 11

1745 Throttle Ctrl 2 Incorrect Shutdownw/Cool-down

PC 3.x

40441 5 Fault Status GasBitmap 11

1746 Throttle Ctrl 2 Out of Adjustment Shutdownw/Cool-down

PC 3.x

40441 6 Fault Status GasBitmap 11

1747 Throttle Ctrl 2 Bad Device Shutdownw/Cool-down

PC 3.x

40441 7 Fault Status GasBitmap 11

1748 Throttle Ctrl 2 Root Unknown Warning PC 3.x

40441 8 Fault Status GasBitmap 11

1749 Throttle Ctrl 2 Condition Exists Warning PC 3.x

40441 9 Fault Status GasBitmap 11

1751 Throttle Ctrl 2 Warning High Warning PC 3.x

40441 10 Fault Status GasBitmap 11

1752 Throttle Ctrl 2 Moderate High Warning PC 3.x

40441 11 Fault Status GasBitmap 11

1753 Fuel Shutoff 2 OOR High Warning PC 3.x

40441 12 Fault Status GasBitmap 11

1754 Fuel Tmp 2 OOR High Warning PC 3.x

40441 13 Fault Status GasBitmap 11

1755 Fuel Tmp 2 OOR Low Warning PC 3.x

40441 14 Fault Status GasBitmap 11

1756 Gas Flow 2 OOR High Warning PC 3.x

40441 15 Fault Status GasBitmap 11

1757 Gas Flow 2 OOR Low Warning PC 3.x

40442 0 Fault Status GasBitmap 12

1758 Gas Flow 2 Incorrect Data Warning PC 3.x

40442 1 Fault Status GasBitmap 12

1759 FCV 2 Pos Feedback Incorrect Shutdownw/Cool-down

PC 3.x

40442 2 Fault Status GasBitmap 12

1761 FCV_Actuator_Error_1761 Shutdownw/Cool-down

PC 3.x

40442 3 Fault Status GasBitmap 12

1984 Int Man 2 Tmp Moderate High Warning PC 3.x

40442 4 Fault Status GasBitmap 12

1765 FCV 2 In Pr OOR High Warning PC 3.x

40442 5 Fault Status GasBitmap 12

1766 FCV 2 In Pr OOR Low Warning PC 3.x

40442 6 Fault Status GasBitmap 12

1767 FCV 2 Out Pr OOR High Warning PC 3.x

40442 7 Fault Status GasBitmap 12

1768 FCV 2 Out Pr OOR Low Warning PC 3.x

40442 8 Fault Status GasBitmap 12

1769 E_Shutd Indication OORH Warning PC 3.x

40442 9 Fault Status GasBitmap 12

1771 E_Shutd Indication OORL Warning PC 3.x

Page 325: Mapa de Registros de Pcc

318

Addr. ControlResponseEvent NameFaultCode

NameBit #

40442 10 Fault Status GasBitmap 12

1772 Eng Derate Request OORH Warning PC 3.x

40442 11 Fault Status GasBitmap 12

1773 Eng Derate Request OORL Warning PC 3.x

40442 12 Fault Status GasBitmap 12

1774 Oil Priming Pump OORH Warning PC 3.x

40442 13 Fault Status GasBitmap 12

1775 Oil Priming Pump OORL Warning PC 3.x

40442 14 Fault Status GasBitmap 12

3362 Power Conservation Control OORH Warning PC 3.x

40442 15 Fault Status GasBitmap 12

3363 Power Conservation Control OORL Warning PC 3.x

40443 0 Fault Status GasBitmap 13

1778 Engine_Heater_Control_Driv-er_High_Error

Warning PC 3.x

40443 1 Fault Status GasBitmap 13

1779 Engine_Heater_Control_Driv-er_Low_Error

Warning PC 3.x

40443 2 Fault Status GasBitmap 13

1781 Shutd Request OOR High Warning PC 3.x

40443 3 Fault Status GasBitmap 13

1782 Shutd Request OOR Low Warning PC 3.x

40443 4 Fault Status GasBitmap 13

1783 Coolant_Pump_Control_Driv-er_High_Error

Warning PC 3.x

40443 5 Fault Status GasBitmap 13

1784 Coolant_Pump_Control_Driv-er_Low_Error

Warning PC 3.x

40443 6 Fault Status GasBitmap 13

1785 Oil_Priming_Pump_Manual_Over-ride_Input_On

Warning PC 3.x

40443 7 Fault Status GasBitmap 13

1786 Oil_Priming_Pump_Stuck_On_Error Warning PC 3.x

40443 8 Fault Status GasBitmap 13

1787 Post_Lube_Oil_Priming_Error Warning PC 3.x

40443 9 Fault Status GasBitmap 13

1788 Maintenance_Lube_Oil_Priming_Error Warning PC 3.x

40443 10 Fault Status GasBitmap 13

1789 Pre_Start_Lube_Oil_Priming_Error Shutdownw/Cool-down

PC 3.x

40443 11 Fault Status GasBitmap 13

1791 Failure_To_Meet_Load_Speed_Error Shutdownw/Cool-down

PC 3.x

40443 12 Fault Status GasBitmap 13

1792 Idle when CB Closed Warning PC 3.x

40443 13 Fault Status GasBitmap 13

1793 Speed/Posit sensor out of Adj Warning PC 3.x

40443 14 Fault Status GasBitmap 13

1794 Fire Detected Shutdownw/Cool-down

PC 3.x

40443 15 Fault Status GasBitmap 13

1795 Compressor_Bypass_Posi-tion_High_Error

Warning PC 3.x

40444 0 Fault Status GasBitmap 14

1796 Compressor_Bypass_Posi-tion_Low_Error

Warning PC 3.x

Page 326: Mapa de Registros de Pcc

319

Addr. ControlResponseEvent NameFaultCode

NameBit #

40444 1 Fault Status GasBitmap 14

1797 Compressor Bypass ctrl OORH Warning PC 3.x

40444 2 Fault Status GasBitmap 14

1798 Compressor Bypass ctrl OORL Warning PC 3.x

40444 3 Fault Status GasBitmap 14

1799 CB_Position_Err_Status Warning PC 3.x

40444 4 Fault Status GasBitmap 14

1811 HIGH_SIDE_DRV2_High_Control_Er-ror (VPS)

Warning PC 3.x

40444 5 Fault Status GasBitmap 14

1812 HIGH_SIDE_DRV2_Low_Control_Er-ror (VPS)

Warning PC 3.x

40444 6 Fault Status GasBitmap 14

1813 Valve_Proving_Sys-tem_Test_Failed_Warning_Error

Warning PC 3.x

40444 7 Fault Status GasBitmap 14

1814 Valve_Proving_Sys-tem_Test_Failed_Shutdown_Error

Shutdownw/Cool-down

PC 3.x

40444 8 Fault Status GasBitmap 14

1815 RLY14_High_Control_Error Warning PC 3.x

40444 9 Fault Status GasBitmap 14

1816 Oil PreHtr Ctrl OOR Low Warning PC 3.x

40444 10 Fault Status GasBitmap 14

1817 Oil_Pre−Heater_Tripped_Error Warning PC 3.x

40444 11 Fault Status GasBitmap 14

1818 Oil_Pre−Heater_Not_Warming_Error Warning PC 3.x

40444 12 Fault Status GasBitmap 14

1819 Common AC Aux CB tripped Warning PC 3.x

40444 13 Fault Status GasBitmap 14

1821 Min_FSO_Speed_Error Shutdownw/Cool-down

PC 3.x

40444 14 Fault Status GasBitmap 14

1822 LT Coolant Level Low Shutdown Error Shutdownw/Cool-down

PC 3.x

40444 15 Fault Status GasBitmap 14

1823 LT Coolant Level Low Warning Error Warning PC 3.x

40445 0 Fault Status GasBitmap 15

1824 Idle_Rated_Trans_Oil_Temp_Low_Er-ror

Warning PC 3.x

40445 1 Fault Status GasBitmap 15

1825 Dirty_Oil_Level_Error Warning PC 3.x

40445 2 Fault Status GasBitmap 15

1826 ECM Software incompatible Shutdownw/Cool-down

PC 3.x

40445 3 Fault Status GasBitmap 15

1827 Fuel_Inlet_Pressure_High_Error Warning PC 3.x

40445 4 Fault Status GasBitmap 15

1828 Fuel_Inlet_Pressure_Low_Error Warning PC 3.x

40445 5 Fault Status GasBitmap 15

1829 Vent_Gas_Valve_Error Shutdownw/Cool-down

PC 3.x

40445 6 Fault Status GasBitmap 15

1831 Upstream_FSO_Valve_Error Shutdownw/Cool-down

PC 3.x

Page 327: Mapa de Registros de Pcc

320

Addr. ControlResponseEvent NameFaultCode

NameBit #

40445 7 Fault Status GasBitmap 15

1832 Downstream_FSO_Valve_Error Shutdownw/Cool-down

PC 3.x

40445 8 Fault Status GasBitmap 15

1833 Engine_Heater_Trip_Error Warning PC 3.x

40445 9 Fault Status GasBitmap 15

1834 Coolant_Pump_Trip_Error Warning PC 3.x

40445 10 Fault Status GasBitmap 15

1835 Oil_Priming_Pump_Tripped_Error Warning PC 3.x

40445 11 Fault Status GasBitmap 15

1836 LCP_(LT)_Low_Serious_Error Shutdownw/Cool-down

PC 3.x

40445 12 Fault Status GasBitmap 15

1837 Permanent_FS_Cam_Sync_Lost_Er-ror

Shutdownw/Cool-down

PC 3.x

40445 13 Fault Status GasBitmap 15

1838 Partial_Engine_Overload_Shut-down_Error

Shutdownw/Cool-down

PC 3.x

40445 14 Fault Status GasBitmap 15

1839 Fuel_Supply_Pressure_High_Error Warning PC 3.x

40445 15 Fault Status GasBitmap 15

1841 Fuel_Supply_Pressure_Low_Error Warning PC 3.x

40446 0 Fault Status GasBitmap 16

1842 Radiator_Fan_Trip_Error Warning PC 3.x

40446 1 Fault Status GasBitmap 16

1858 Exhaust Aft Inlet O2 OOR High Warning PC 3.x

40446 2 Fault Status GasBitmap 16

1859 Exhaust Aft Inlet O2 OOR Low Warning PC 3.x

40446 3 Fault Status GasBitmap 16

1861 Exhaust Aft Inlet O2 Incorrect Warning PC 3.x

40446 4 Fault Status GasBitmap 16

1862 Exhaust Aft Out O2 OOR High Warning PC 3.x

40446 5 Fault Status GasBitmap 16

1863 Exhaust Aft Outlet O2 OOR Low Warning PC 3.x

40446 6 Fault Status GasBitmap 16

1864 Exhaust Aft Outlet O2 Incorrect Warning PC 3.x

40446 7 Fault Status GasBitmap 16

1985 Int Man 3 Tmp Moderate High Warning PC 3.x

40446 8 Fault Status GasBitmap 16

1986 Int Man 4 Tmp Moderate High Warning PC 3.x

40446 9 Fault Status GasBitmap 16

2111 Coolant_Inlet_Temperatu-re_(LT)_High_Error

Warning PC 3.x

40446 10 Fault Status GasBitmap 16

2112 Coolant_Inlet_Temperatu-re_(LT)_Low_Error

Warning PC 3.x

40446 11 Fault Status GasBitmap 16

2113 CIT_(LT)_High_Warning_Error Warning PC 3.x

40446 12 Fault Status GasBitmap 16

2114 CIT_(LT)_High_Serious_Error Shutdownw/Cool-down

PC 3.x

Page 328: Mapa de Registros de Pcc

321

Addr. ControlResponseEvent NameFaultCode

NameBit #

40446 13 Fault Status GasBitmap 16

2115 LT_Coolant_Pressure_High_Error Warning PC 3.x

40446 14 Fault Status GasBitmap 16

2116 LT_Coolant_Pressure_Low_Error Warning PC 3.x

40446 15 Fault Status GasBitmap 16

2117 LCP_(LT)_Low_Warning_Error Warning PC 3.x

40447 0 Fault Status GasBitmap 17

2121 Exhaust_Temp_1_(A1)_High_Warn-ing_Error

Warning PC 3.x

40447 1 Fault Status GasBitmap 17

2122 Exhaust_Temp_3_(A2)_High_Warn-ing_Error

Warning PC 3.x

40447 2 Fault Status GasBitmap 17

2123 Exhaust_Temp_5_(A3)_High_Warn-ing_Error

Warning PC 3.x

40447 3 Fault Status GasBitmap 17

2124 Exhaust_Temp_7_(A4)_High_Warn-ing_Error

Warning PC 3.x

40447 4 Fault Status GasBitmap 17

2125 Exhaust_Temp_9_(A5)_High_Warn-ing_Error

Warning PC 3.x

40447 5 Fault Status GasBitmap 17

2126 Exhaust_Temp_11_(A6)_High_Warn-ing_Error

Warning PC 3.x

40447 6 Fault Status GasBitmap 17

2127 Exhaust_Temp_13_(A7)_High_Warn-ing_Error

Warning PC 3.x

40447 7 Fault Status GasBitmap 17

2128 Exhaust_Temp_15_(A8)_High_Warn-ing_Error

Warning PC 3.x

40447 8 Fault Status GasBitmap 17

2129 Exhaust_Temp_17_(A9)_High_Warn-ing_Error

Warning PC 3.x

40447 9 Fault Status GasBitmap 17

2131 Exhaust_Temp_2_(B1)_High_Warn-ing_Error

Warning PC 3.x

40447 10 Fault Status GasBitmap 17

2132 Exhaust_Temp_4_(B2)_High_Warn-ing_Error

Warning PC 3.x

40447 11 Fault Status GasBitmap 17

2133 Exhaust_Temp_6_(B3)_High_Warn-ing_Error

Warning PC 3.x

40447 12 Fault Status GasBitmap 17

2134 Exhaust_Temp_8_(B4)_High_Warn-ing_Error

Warning PC 3.x

40447 13 Fault Status GasBitmap 17

2135 Exhaust_Temp_10_(B5)_High_Warn-ing_Error

Warning PC 3.x

40447 14 Fault Status GasBitmap 17

2136 Exhaust_Temp_12_(B6)_High_Warn-ing_Error

Warning PC 3.x

40447 15 Fault Status GasBitmap 17

2137 Exhaust_Temp_14_(B7)_High_Warn-ing_Error

Warning PC 3.x

40448 0 Fault Status GasBitmap 18

2138 Exhaust_Temp_16_(B8)_High_Warn-ing_Error

Warning PC 3.x

40448 1 Fault Status GasBitmap 18

2139 Exhaust_Temp_18_(B9)_High_Warn-ing_Error

Warning PC 3.x

40448 2 Fault Status GasBitmap 18

2141 Start_Air_Pressure_High_Error Warning PC 3.x

40448 3 Fault Status GasBitmap 18

2142 Start_Air_Pressure_Low_Error Warning PC 3.x

40448 4 Fault Status GasBitmap 18

2143 SAP_Overpressure_Error Warning PC 3.x

Page 329: Mapa de Registros de Pcc

322

Addr. ControlResponseEvent NameFaultCode

NameBit #

40448 5 Fault Status GasBitmap 18

2144 Exhaust Temp 16 (B8) High SeriousError

Shutdownw/Cool-down

PC 3.x

40448 6 Fault Status GasBitmap 18

2145 Exhaust Temp 18 (B9) High SeriousError

Shutdownw/Cool-down

PC 3.x

40448 7 Fault Status GasBitmap 18

2146 EGT 17 (A9) OOR Low Warning PC 3.x

40448 8 Fault Status GasBitmap 18

2147 EGT 18 (B9) OOR Low Warning PC 3.x

40448 9 Fault Status GasBitmap 18

2154 Oil_Filter_Outlet_Pressure_High_Error Warning PC 3.x

40448 10 Fault Status GasBitmap 18

2155 Oil_Filter_Outlet_Pressure_Low_Error Warning PC 3.x

40448 11 Fault Status GasBitmap 18

2157 Int Man 2 Tmp Abnormal Rate Shutdownw/Cool-down

PC 3.x

40448 12 Fault Status GasBitmap 18

2158 Int Man 3 Tmp Abnormal Rate Shutdownw/Cool-down

PC 3.x

40448 13 Fault Status GasBitmap 18

2159 Int Man 4 Tmp Abnormal Rate Shutdownw/Cool-down

PC 3.x

40448 14 Fault Status GasBitmap 18

2188 Exhaust O2 OOR High Warning PC 3.x

40448 15 Fault Status GasBitmap 18

2191 ST_Throttle_Press_Err_Status Warning PC 3.x

40449 0 Fault Status GasBitmap 19

2192 Exhaust O2 OOR Low Warning PC 3.x

40449 1 Fault Status GasBitmap 19

2217 RAM_Image_Word_Error Warning PC 3.x

40449 2 Fault Status GasBitmap 19

2219 Exhaust O2 Moderate High Warning PC 3.x

40449 3 Fault Status GasBitmap 19

2221 Exhaust O2 Moderate Low Warning PC 3.x

40449 4 Fault Status GasBitmap 19

2281 Knock 11 (A6) Moderate High Shutdownw/Cool-down

PC 3.x

40449 5 Fault Status GasBitmap 19

2282 Knock 11 (A6) Critical High Shutdownw/Cool-down

PC 3.x

40449 6 Fault Status GasBitmap 19

2298 Fuel Shutoff 2 OOR Low Warning PC 3.x

40449 7 Fault Status GasBitmap 19

2315 Red Lamp OOR High Warning PC 3.x

40449 8 Fault Status GasBitmap 19

2316 Amber Lamp OOR High Warning PC 3.x

40449 9 Fault Status GasBitmap 19

2317 Amber Lamp OOR Low Warning PC 3.x

Page 330: Mapa de Registros de Pcc

323

Addr. ControlResponseEvent NameFaultCode

NameBit #

40449 10 Fault Status GasBitmap 19

2427 Fuel_Outlet_Pressure_High_Error Warning PC 3.x

40449 11 Fault Status GasBitmap 19

2428 Fuel_Outlet_Pressure_Low_Error Warning PC 3.x

40449 12 Fault Status GasBitmap 19

2453 Total Real Power Circuit OORH Warning PC 3.x

40449 13 Fault Status GasBitmap 19

2454 Total Real Power Circuit OORL Warning PC 3.x

40449 14 Fault Status GasBitmap 19

2455 Speed_Bias_Low_Error Warning PC 3.x

40449 15 Fault Status GasBitmap 19

2456 Speed_Bias_High_Error Warning PC 3.x

40450 0 Fault Status GasBitmap 20

2457 Max_Total_Misfire_Error Shutdownw/Cool-down

PC 3.x

40450 1 Fault Status GasBitmap 20

2458 Cylinder_2_(B1)_Total_Misfire_Error Warning PC 3.x

40450 2 Fault Status GasBitmap 20

2459 Cylinder_4_(B2)_Total_Misfire_Error Warning PC 3.x

40450 3 Fault Status GasBitmap 20

2461 Cylinder_6_(B3)_Total_Misfire_Error Warning PC 3.x

40450 4 Fault Status GasBitmap 20

2462 Cylinder_8_(B4)_Total_Misfire_Error Warning PC 3.x

40450 5 Fault Status GasBitmap 20

2463 Cylinder_10_(B5)_Total_Misfire_Error Warning PC 3.x

40450 6 Fault Status GasBitmap 20

2464 Cylinder_12_(B6)_Total_Misfire_Error Warning PC 3.x

40450 7 Fault Status GasBitmap 20

2465 Cylinder_14_(B7)_Total_Misfire_Error Warning PC 3.x

40450 8 Fault Status GasBitmap 20

2466 Cylinder_16_(B8)_Total_Misfire_Error Warning PC 3.x

40450 9 Fault Status GasBitmap 20

2467 Cylinder_18_(B9)_Total_Misfire_Error Warning PC 3.x

40450 10 Fault Status GasBitmap 20

2469 Cylinder_1_(A1)_Total_Misfire_Error Warning PC 3.x

40450 11 Fault Status GasBitmap 20

2471 Cylinder_3_(A2)_Total_Misfire_Error Warning PC 3.x

40450 12 Fault Status GasBitmap 20

2472 Cylinder_5_(A3)_Total_Misfire_Error Warning PC 3.x

40450 13 Fault Status GasBitmap 20

2473 Cylinder_7_(A4)_Total_Misfire_Error Warning PC 3.x

40450 14 Fault Status GasBitmap 20

2475 Cylinder_9_(A5)_Total_Misfire_Error Warning PC 3.x

40450 15 Fault Status GasBitmap 20

2476 Cylinder_11_(A6)_Total_Misfire_Error Warning PC 3.x

40451 0 Fault Status GasBitmap 21

2477 Cylinder_13_(A7)_Total_Misfire_Error Warning PC 3.x

40451 1 Fault Status GasBitmap 21

2478 Cylinder_15_(A8)_Total_Misfire_Error Warning PC 3.x

Page 331: Mapa de Registros de Pcc

324

Addr. ControlResponseEvent NameFaultCode

NameBit #

40451 2 Fault Status GasBitmap 21

2479 Cylinder_17_(A9)_Total_Misfire_Error Warning PC 3.x

40451 3 Fault Status GasBitmap 21

2482 Start_Before_Ready_Error Shutdownw/Cool-down

PC 3.x

40451 4 Fault Status GasBitmap 21

2483 Continuous_Starter_Failure_Error Shutdownw/Cool-down

PC 3.x

40451 5 Fault Status GasBitmap 21

2484 Exhaust Temperature 1 (A1) AbnormalRate

Shutdownw/Cool-down

PC 3.x

40451 6 Fault Status GasBitmap 21

2485 Exhaust Temperature 3 (A2) AbnormalRate

Shutdownw/Cool-down

PC 3.x

40451 7 Fault Status GasBitmap 21

2486 Exhaust Temperature 5 (A3) AbnormalRate

Shutdownw/Cool-down

PC 3.x

40451 8 Fault Status GasBitmap 21

2487 Exhaust Temperature 7 (A4) AbnormalRate

Shutdownw/Cool-down

PC 3.x

40451 9 Fault Status GasBitmap 21

2488 Exhaust Temperature 9 (A5) AbnormalRate

Shutdownw/Cool-down

PC 3.x

40451 10 Fault Status GasBitmap 21

2489 Exhaust Temperature 11 (A6) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

40451 11 Fault Status GasBitmap 21

2491 Exhaust Temperature 13 (A7) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

40451 12 Fault Status GasBitmap 21

2492 Exhaust Temperature 15 (A8) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

40451 13 Fault Status GasBitmap 21

2493 Exhaust Temperature 17 (A9) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

40451 14 Fault Status GasBitmap 21

2494 Exhaust Temperature 2 (B1) AbnormalRate

Shutdownw/Cool-down

PC 3.x

40451 15 Fault Status GasBitmap 21

2495 Exhaust Temperature 4 (B2) AbnormalRate

Shutdownw/Cool-down

PC 3.x

40452 0 Fault Status GasBitmap 22

2496 Exhaust Temperature 6 (B3) AbnormalRate

Shutdownw/Cool-down

PC 3.x

40452 1 Fault Status GasBitmap 22

2497 Exhaust Temperature 8 (B4) AbnormalRate

Shutdownw/Cool-down

PC 3.x

40452 2 Fault Status GasBitmap 22

2498 Exhaust Temperature 10 (B5) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

Page 332: Mapa de Registros de Pcc

325

Addr. ControlResponseEvent NameFaultCode

NameBit #

40452 3 Fault Status GasBitmap 22

2499 Exhaust Temperature 12 (B6) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

40452 4 Fault Status GasBitmap 22

2511 Exhaust Temperature 14 (B7) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

40452 5 Fault Status GasBitmap 22

2512 Exhaust Temperature 16 (B8) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

40452 6 Fault Status GasBitmap 22

2513 Exhaust Temperature 18 (B9) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

40452 7 Fault Status GasBitmap 22

2517 Compressor_Outlet_Pres-sure_High_Error

Warning PC 3.x

40452 8 Fault Status GasBitmap 22

2518 Compressor_Outlet_Pres-sure_Low_Error

Warning PC 3.x

40452 9 Fault Status GasBitmap 22

2521 Bank_Id_Error Shutdownw/Cool-down

PC 3.x

40452 10 Fault Status GasBitmap 22

2522 Continuous_Light_Knock_Er-ror_1_(A1)

Shutdownw/Cool-down

PC 3.x

40452 11 Fault Status GasBitmap 22

2523 Continuous_Light_Knock_Er-ror_2_(B1)

Shutdownw/Cool-down

PC 3.x

40452 12 Fault Status GasBitmap 22

2524 Continuous_Light_Knock_Er-ror_3_(A2)

Shutdownw/Cool-down

PC 3.x

40452 13 Fault Status GasBitmap 22

2525 Continuous_Light_Knock_Er-ror_4_(B2)

Shutdownw/Cool-down

PC 3.x

40452 14 Fault Status GasBitmap 22

2526 Continuous_Light_Knock_Er-ror_5_(A3)

Shutdownw/Cool-down

PC 3.x

40452 15 Fault Status GasBitmap 22

2527 Continuous_Light_Knock_Er-ror_6_(B3)

Shutdownw/Cool-down

PC 3.x

40453 0 Fault Status GasBitmap 23

2528 Continuous_Light_Knock_Er-ror_7_(A4)

Shutdownw/Cool-down

PC 3.x

40453 1 Fault Status GasBitmap 23

2529 Continuous_Light_Knock_Er-ror_8_(B4)

Shutdownw/Cool-down

PC 3.x

40453 2 Fault Status GasBitmap 23

2531 Continuous_Light_Knock_Er-ror_9_(A5)

Shutdownw/Cool-down

PC 3.x

40453 3 Fault Status GasBitmap 23

2532 Continuous_Light_Knock_Er-ror_10_(B5)

Shutdownw/Cool-down

PC 3.x

Page 333: Mapa de Registros de Pcc

326

Addr. ControlResponseEvent NameFaultCode

NameBit #

40453 4 Fault Status GasBitmap 23

2544 ECM_Overtemp_Error Shutdownw/Cool-down

PC 3.x

40453 5 Fault Status GasBitmap 23

2567 DG_Air_Compressor_Trip_Error Warning PC 3.x

40453 6 Fault Status GasBitmap 23

2643 Throttle Pos 2 Feedback OOR High Warning PC 3.x

40453 7 Fault Status GasBitmap 23

2644 Throttle Pos 2 Feedback OOR Low Warning PC 3.x

40453 8 Fault Status GasBitmap 23

2661 At Least One ACK: Most Severe Fault Shutdown PC 2.x, PC3.x

40453 9 Fault Status GasBitmap 23

2724 Gas Supply Pr Moderate High Warning PC 3.x

40453 10 Fault Status GasBitmap 23

2725 Gas Supply Pr Moderate Low Warning PC 3.x

40453 11 Fault Status GasBitmap 23

2737 Exh Gas Tmp Critical High Shutdownw/Cool-down

PC 3.x

40453 12 Fault Status GasBitmap 23

2766 Bank_A_CCD_Failed_Error Shutdownw/Cool-down

PC 3.x

40453 13 Fault Status GasBitmap 23

2767 Bank_B_CCD_Failed_Error Shutdownw/Cool-down

PC 3.x

40453 14 Fault Status GasBitmap 23

2768 CAN Parent Communication Incorrect Shutdownw/Cool-down

PC 3.x

40453 15 Fault Status GasBitmap 23

2769 CAN Child Com Incorrect Shutdownw/Cool-down

PC 3.x

40454 0 Fault Status GasBitmap 24

2789 COT_Low_Error Warning PC 3.x

40454 1 Fault Status GasBitmap 24

2793 COT_Low_Serious_Error Shutdownw/Cool-down

PC 3.x

40454 2 Fault Status GasBitmap 24

2794 Ign Shutd Relay OOR High Warning PC 3.x

40454 3 Fault Status GasBitmap 24

2795 Ign Shutd Relay OOR Low Warning PC 3.x

40454 4 Fault Status GasBitmap 24

2796 Partial_Engine_Overload_Warn-ing_Error

Warning PC 3.x

40454 5 Fault Status GasBitmap 24

2797 Inlet Gas Diff Pressure OOR High Warning PC 3.x

40454 6 Fault Status GasBitmap 24

2798 Inlet Gas Diff Pressure OOR Low Warning PC 3.x

40454 7 Fault Status GasBitmap 24

2799 IMOP_Compressor_Outlet_Pres-ure_Delta_Error

Shutdownw/Cool-down

PC 3.x

Page 334: Mapa de Registros de Pcc

327

Addr. ControlResponseEvent NameFaultCode

NameBit #

40454 8 Fault Status GasBitmap 24

2811 IMOP_Compressor_Outlet_Pres-sure_Maximum_Error

Shutdownw/Cool-down

PC 3.x

40454 9 Fault Status GasBitmap 24

2837 Exhaust_Temp_1_(A1)_Deviation_Er-ror

Warning PC 3.x

40454 10 Fault Status GasBitmap 24

2838 Exhaust_Temp_3_(A2)_Deviation_Er-ror

Warning PC 3.x

40454 11 Fault Status GasBitmap 24

2839 Exhaust_Temp_5_(A3)_Deviation_Er-ror

Warning PC 3.x

40454 12 Fault Status GasBitmap 24

2841 Exhaust_Temp_7_(A4)_Deviation_Er-ror

Warning PC 3.x

40454 13 Fault Status GasBitmap 24

2842 Exhaust_Temp_9_(A5)_Deviation_Er-ror

Warning PC 3.x

40454 14 Fault Status GasBitmap 24

2843 Exhaust_Temp_11_(A6)_Devi-ation_Error

Warning PC 3.x

40454 15 Fault Status GasBitmap 24

2844 Exhaust_Temp_13_(A7)_Devi-ation_Error

Warning PC 3.x

40455 0 Fault Status GasBitmap 25

2845 Exhaust_Temp_15_(A8)_Devi-ation_Error

Warning PC 3.x

40455 1 Fault Status GasBitmap 25

2846 Exhaust_Temp_17_(A9)_Devi-ation_Error

Warning PC 3.x

40455 2 Fault Status GasBitmap 25

2847 Exhaust_Temp_2_(B1)_Deviation_Er-ror

Warning PC 3.x

40455 3 Fault Status GasBitmap 25

2848 Exhaust_Temp_4_(B2)_Deviation_Er-ror

Warning PC 3.x

40455 4 Fault Status GasBitmap 25

2849 Exhaust_Temp_6_(B3)_Deviation_Er-ror

Warning PC 3.x

40455 5 Fault Status GasBitmap 25

2851 Exhaust_Temp_8_(B4)_Deviation_Er-ror

Warning PC 3.x

40455 6 Fault Status GasBitmap 25

2852 Exhaust_Temp_10_(B5)_Devi-ation_Error

Warning PC 3.x

40455 7 Fault Status GasBitmap 25

2853 Exhaust_Temp_12_(B6)_Devi-ation_Error

Warning PC 3.x

40455 8 Fault Status GasBitmap 25

2854 Exhaust_Temp_14_(B7)_Devi-ation_Error

Warning PC 3.x

40455 9 Fault Status GasBitmap 25

2855 Exhaust_Temp_16_(B8)_Devi-ation_Error

Warning PC 3.x

40455 10 Fault Status GasBitmap 25

2856 Exhaust_Temp_18_(B9)_Devi-ation_Error

Warning PC 3.x

40455 11 Fault Status GasBitmap 25

2857 Turbo_1_Overspeed_Critical_Error Shutdownw/Cool-down

PC 3.x

40455 12 Fault Status GasBitmap 25

2858 Turbo_2_Overspeed_Critical_Error Shutdownw/Cool-down

PC 3.x

40455 13 Fault Status GasBitmap 25

2859 Alt Heater Ctrl OOR High Warning PC 3.x

40455 14 Fault Status GasBitmap 25

2861 Alt Heater Ctrl OOR Low Warning PC 3.x

Page 335: Mapa de Registros de Pcc

328

Addr. ControlResponseEvent NameFaultCode

NameBit #

40455 15 Fault Status GasBitmap 25

2862 Gen Alternator 1st Start Cond Exists Warning PC 3.x

40456 0 Fault Status GasBitmap 26

2863 Genset to Engine Com Incorrect Shutdownw/Cool-down

PC 3.x

40456 1 Fault Status GasBitmap 26

2864 FSO_NON_High_Control_Error Shutdownw/Cool-down

PC 3.x

40456 2 Fault Status GasBitmap 26

3364 Power Conservation Control Cond Ex-ists

Warning PC 3.x

40456 3 Fault Status GasBitmap 26

2866 FCV_Position_High_Error Warning PC 3.x

40456 4 Fault Status GasBitmap 26

2867 FCV_Position_Low_Error Warning PC 3.x

40456 5 Fault Status GasBitmap 26

2868 Engine_Heater_Over−Tempera-ture_Alarm_Error

Warning PC 3.x

40456 6 Fault Status GasBitmap 26

2869 HT Cool Temp Driver OOR High Warning PC 3.x

40456 7 Fault Status GasBitmap 26

2871 HT Cool Temp Driver OOR Low Warning PC 3.x

40456 8 Fault Status GasBitmap 26

2872 HT Cool Temp Driver Cond Exists Warning PC 3.x

40456 9 Fault Status GasBitmap 26

2873 LT Cool Temp Driver OOR High Warning PC 3.x

40456 10 Fault Status GasBitmap 26

2874 LT Cool Temp Driver OOR Low Warning PC 3.x

40456 11 Fault Status GasBitmap 26

2875 LT Cool Temp Driver Cond Exists Warning PC 3.x

40456 12 Fault Status GasBitmap 26

2876 Comp_Surge_Shutdown_Error Shutdownw/Cool-down

PC 3.x

40456 13 Fault Status GasBitmap 26

2877 Comp_Surge_Derate_Error Warning PC 3.x

40456 14 Fault Status GasBitmap 26

2994 MC68302_Error Warning PC 3.x

40456 15 Fault Status GasBitmap 26

2995 Int Man Pressure 1 Critical High Shutdownw/Cool-down

PC 3.x

40457 0 Fault Status GasBitmap 27

2996 Int Man Pressure 1 Moderate High Warning PC 3.x

40457 1 Fault Status GasBitmap 27

2997 Exhaust O2 Critical Low Shutdownw/Cool-down

PC 3.x

40457 2 Fault Status GasBitmap 27

3111 Excessive_Mech_Vibration_1_(A1) Shutdownw/Cool-down

PC 3.x

40457 3 Fault Status GasBitmap 27

3112 Excessive_Mech_Vibration_2_(B1) Shutdownw/Cool-down

PC 3.x

Page 336: Mapa de Registros de Pcc

329

Addr. ControlResponseEvent NameFaultCode

NameBit #

40457 4 Fault Status GasBitmap 27

3113 Excessive_Mech_Vibration_3_(A2) Shutdownw/Cool-down

PC 3.x

40457 5 Fault Status GasBitmap 27

3114 Excessive_Mech_Vibration_4_(B2) Shutdownw/Cool-down

PC 3.x

40457 6 Fault Status GasBitmap 27

3115 Excessive_Mech_Vibration_5_(A3) Shutdownw/Cool-down

PC 3.x

40457 7 Fault Status GasBitmap 27

3116 Excessive_Mech_Vibration_6_(B3) Shutdownw/Cool-down

PC 3.x

40457 8 Fault Status GasBitmap 27

3117 Excessive_Mech_Vibration_7_(A4) Shutdownw/Cool-down

PC 3.x

40457 9 Fault Status GasBitmap 27

3118 Excessive_Mech_Vibration_8_(B4) Shutdownw/Cool-down

PC 3.x

40457 10 Fault Status GasBitmap 27

3119 Excessive_Mech_Vibration_9_(A5) Shutdownw/Cool-down

PC 3.x

40457 11 Fault Status GasBitmap 27

3121 Excessive_Mech_Vibration_10_(B5) Shutdownw/Cool-down

PC 3.x

40457 12 Fault Status GasBitmap 27

3122 Excessive_Mech_Vibration_11_(A6) Shutdownw/Cool-down

PC 3.x

40457 13 Fault Status GasBitmap 27

3123 Excessive_Mech_Vibration_12_(B6) Shutdownw/Cool-down

PC 3.x

40457 14 Fault Status GasBitmap 27

3124 Excessive_Mech_Vibration_13_(A7) Shutdownw/Cool-down

PC 3.x

40457 15 Fault Status GasBitmap 27

3125 Excessive_Mech_Vibration_14_(B7) Shutdownw/Cool-down

PC 3.x

40458 0 Fault Status GasBitmap 28

3126 Excessive_Mech_Vibration_15_(A8) Shutdownw/Cool-down

PC 3.x

40458 1 Fault Status GasBitmap 28

3127 Excessive_Mech_Vibration_16_(B8) Shutdownw/Cool-down

PC 3.x

40458 2 Fault Status GasBitmap 28

3128 Excessive_Mech_Vibration_17_(A9) Shutdownw/Cool-down

PC 3.x

40458 3 Fault Status GasBitmap 28

3129 Excessive_Mech_Vibration_18_(B9) Shutdownw/Cool-down

PC 3.x

40458 4 Fault Status GasBitmap 28

1275 Knock Cyl 10 (B5) OORL Warning PC 3.x

Page 337: Mapa de Registros de Pcc

330

Addr. ControlResponseEvent NameFaultCode

NameBit #

40458 5 Fault Status GasBitmap 28

1277 Knock Cyl 11 (A6) OORL Warning PC 3.x

40458 6 Fault Status GasBitmap 28

1282 Knock Cyl 12 (B6) OORL Warning PC 3.x

40458 7 Fault Status GasBitmap 28

1287 Knock Cyl 13 (A7) OORL Warning PC 3.x

40458 8 Fault Status GasBitmap 28

1292 Knock Cyl 14 (B7) OORL Warning PC 3.x

40458 9 Fault Status GasBitmap 28

1297 Knock Cyl 15 (A8) OORL Warning PC 3.x

40458 10 Fault Status GasBitmap 28

1584 Knock Cyl 16 (B8) OORL Warning PC 3.x

40458 11 Fault Status GasBitmap 28

1589 Knock Cyl 17 (A9) OORL Warning PC 3.x

40458 12 Fault Status GasBitmap 28

1338 Knock Cyl 18 (B9) OORL Warning PC 3.x

40459 0 Fault Status GasBitmap 29

189 HT Coolant Temperature Root CauseUnknown

Shutdownw/Cool-down

PC 3.x

40459 1 Fault Status GasBitmap 29

229 HT Coolant Pressure Incorrect Warning PC 3.x

40459 2 Fault Status GasBitmap 29

334 HT Coolant Temperature Incorrect Warning PC 3.x

40459 4 Fault Status GasBitmap 29

831 Spark Plug 1 (A1) OORL Warning PC 3.x

40459 5 Fault Status GasBitmap 29

832 Spark Plug 2 (B1) OORL Warning PC 3.x

40459 6 Fault Status GasBitmap 29

833 Spark Plug 3 (A2) OORL Warning PC 3.x

40459 7 Fault Status GasBitmap 29

834 Spark Plug 4 (B2) OORL Warning PC 3.x

40459 8 Fault Status GasBitmap 29

835 Spark Plug 5 (A3) OORL Warning PC 3.x

40459 9 Fault Status GasBitmap 29

836 Spark Plug 6 (B3) OORL Warning PC 3.x

40459 10 Fault Status GasBitmap 29

837 Spark Plug 7 (A4) OORL Warning PC 3.x

40459 11 Fault Status GasBitmap 29

838 Spark Plug 8 (B4) OORL Warning PC 3.x

40459 12 Fault Status GasBitmap 29

839 Spark Plug 9 (A5) OORL Warning PC 3.x

40459 13 Fault Status GasBitmap 29

841 Spark Plug 10 (B5) OORL Warning PC 3.x

40459 14 Fault Status GasBitmap 29

842 Spark Plug 11 (A6) OORL Warning PC 3.x

40459 15 Fault Status GasBitmap 29

843 Spark Plug 12 (B6) OORL Warning PC 3.x

40460 0 Fault Status GasBitmap 30

844 Spark Plug 13 (A7) OORL Warning PC 3.x

Page 338: Mapa de Registros de Pcc

331

Addr. ControlResponseEvent NameFaultCode

NameBit #

40460 1 Fault Status GasBitmap 30

845 Spark Plug 14 (B7) OORL Warning PC 3.x

40460 2 Fault Status GasBitmap 30

846 Spark Plug 15 (A8) OORL Warning PC 3.x

40460 3 Fault Status GasBitmap 30

847 Spark Plug 16 (B8) OORL Warning PC 3.x

40460 4 Fault Status GasBitmap 30

848 Spark Plug 17 (A9) OORL Warning PC 3.x

40460 5 Fault Status GasBitmap 30

849 Spark Plug 18 (B9) OORL Warning PC 3.x

40460 7 Fault Status GasBitmap 30

891 Spark Plug 1 (A1) Root Cause Un-known

Warning PC 3.x

40460 8 Fault Status GasBitmap 30

892 Spark Plug 2 (B1) Root Cause Un-known

Warning PC 3.x

40460 9 Fault Status GasBitmap 30

893 Spark Plug 3 (A2) Root Cause Un-known

Warning PC 3.x

40460 10 Fault Status GasBitmap 30

894 Spark Plug 4 (B2) Root Cause Un-known

Warning PC 3.x

40460 11 Fault Status GasBitmap 30

895 Spark Plug 5 (A3) Root Cause Un-known

Warning PC 3.x

40460 12 Fault Status GasBitmap 30

896 Spark Plug 6 (B3) Root Cause Un-known

Warning PC 3.x

40460 13 Fault Status GasBitmap 30

897 Spark Plug 7 (A4) Root Cause Un-known

Warning PC 3.x

40460 14 Fault Status GasBitmap 30

898 Spark Plug 8 (B4) Root Cause Un-known

Warning PC 3.x

40460 15 Fault Status GasBitmap 30

899 Spark Plug 9 (A5) Root Cause Un-known

Warning PC 3.x

40461 0 Fault Status GasBitmap 31

911 Spark Plug 10 (B5) Root Cause Un-known

Warning PC 3.x

40461 1 Fault Status GasBitmap 31

912 Spark Plug 11 (A6) Root Cause Un-known

Warning PC 3.x

40461 2 Fault Status GasBitmap 31

913 Spark Plug 12 (B6) Root Cause Un-known

Warning PC 3.x

40461 3 Fault Status GasBitmap 31

914 Spark Plug 13 (A7) Root Cause Un-known

Warning PC 3.x

40461 4 Fault Status GasBitmap 31

915 Spark Plug 14 (B7) Root Cause Un-known

Warning PC 3.x

40461 5 Fault Status GasBitmap 31

916 Spark Plug 15 (A8) Root Cause Un-known

Warning PC 3.x

40461 6 Fault Status GasBitmap 31

917 Spark Plug 16 (B8) Root Cause Un-known

Warning PC 3.x

40461 7 Fault Status GasBitmap 31

918 Spark Plug 17 (A9) Root Cause Un-known

Warning PC 3.x

40461 8 Fault Status GasBitmap 31

919 Spark Plug 18 (B9) Root Cause Un-known

Warning PC 3.x

40461 10 Fault Status GasBitmap 31

1276 Knock Cyl 10 (B5) OORH Warning PC 3.x

40461 11 Fault Status GasBitmap 31

1278 Knock Cyl 11 (A6) OORH Warning PC 3.x

Page 339: Mapa de Registros de Pcc

332

Addr. ControlResponseEvent NameFaultCode

NameBit #

40461 12 Fault Status GasBitmap 31

1279 Knock 12 (B6) High Warning Warning PC 3.x

40461 13 Fault Status GasBitmap 31

1283 Knock Cyl 12 (B6) OORH Warning PC 3.x

40461 14 Fault Status GasBitmap 31

1284 Knock 13 (A7) High Warning Warning PC 3.x

40461 15 Fault Status GasBitmap 31

1288 Knock Cyl 13 (A7) OORH Warning PC 3.x

40462 0 Fault Status GasBitmap 32

1289 Knock 14 (B7) High Warning Warning PC 3.x

40462 1 Fault Status GasBitmap 32

1293 Knock Cyl 14 (B7) OORH Warning PC 3.x

40462 2 Fault Status GasBitmap 32

1294 Knock 15 (A8) High Warning Warning PC 3.x

40462 3 Fault Status GasBitmap 32

1298 Knock Cyl 15 (A8) OORH Warning PC 3.x

40462 4 Fault Status GasBitmap 32

1299 Knock 16 (B8) High Warning Warning PC 3.x

40462 6 Fault Status GasBitmap 32

1339 Knock Cyl 18 (B9) OORH Warning PC 3.x

40462 7 Fault Status GasBitmap 32

1352 Knock 20 (B10) High Warning Warning PC 3.x

40462 8 Fault Status GasBitmap 32

1353 Continuous_Light_Knock_Er-ror_20_(B10)

Shutdownw/Cool-down

PC 3.x

40462 9 Fault Status GasBitmap 32

1354 Heavy_Knock_Error_20_(B10) Shutdownw/Cool-down

PC 3.x

40462 10 Fault Status GasBitmap 32

1355 Knock Cyl 20 (B10) OORL Warning PC 3.x

40462 11 Fault Status GasBitmap 32

1356 Knock Cyl 20 (B10) OORH Warning PC 3.x

40462 12 Fault Status GasBitmap 32

1572 Continuous_Light_Knock_Er-ror_19_(A10)

Shutdownw/Cool-down

PC 3.x

40462 13 Fault Status GasBitmap 32

1574 Heavy_Knock_Error_19_(A10) Shutdownw/Cool-down

PC 3.x

40462 14 Fault Status GasBitmap 32

1575 Knock Cyl 19 (A10) OORL Warning PC 3.x

40462 15 Fault Status GasBitmap 32

1576 Knock Cyl 19 (A10) OORH Warning PC 3.x

40463 0 Fault Status GasBitmap 33

1585 Knock Cyl 16 (B8) OORH Warning PC 3.x

40463 1 Fault Status GasBitmap 33

1586 Knock 17 (A9) High Warning Warning PC 3.x

40463 2 Fault Status GasBitmap 33

1591 Knock Cyl 17 (A9) OORH Warning PC 3.x

40463 3 Fault Status GasBitmap 33

1592 Knock 18 (B9) High Warning Warning PC 3.x

Page 340: Mapa de Registros de Pcc

333

Addr. ControlResponseEvent NameFaultCode

NameBit #

40463 4 Fault Status GasBitmap 33

1594 Knock 19 (A10) High Warning Warning PC 3.x

40463 6 Fault Status GasBitmap 33

2193 HT Coolant Level Moderate High Warning PC 3.x

40463 7 Fault Status GasBitmap 33

2231 Knock Cyl 1 (A1) OORH Warning PC 3.x

40463 8 Fault Status GasBitmap 33

2232 Knock Cyl 2 (B1) OORH Warning PC 3.x

40463 9 Fault Status GasBitmap 33

2233 Knock Cyl 3 (A2) OORH Warning PC 3.x

40463 10 Fault Status GasBitmap 33

2234 Knock Cyl 4 (B2) OORH Warning PC 3.x

40463 11 Fault Status GasBitmap 33

2235 Knock Cyl 5 (A3) OORH Warning PC 3.x

40463 12 Fault Status GasBitmap 33

2236 Knock Cyl 6 (B3) OORH Warning PC 3.x

40463 13 Fault Status GasBitmap 33

2237 Knock Cyl 7 (A4) OORH Warning PC 3.x

40463 14 Fault Status GasBitmap 33

2238 Knock Cyl 8 (B4) OORH Warning PC 3.x

40463 15 Fault Status GasBitmap 33

2239 Knock Cyl 9 (A5) OORH Warning PC 3.x

40464 0 Fault Status GasBitmap 34

2279 Knock 11 (A6) High Warning Warning PC 3.x

40464 1 Fault Status GasBitmap 34

2431 Knock 1 (A1) High Warning Warning PC 3.x

40464 2 Fault Status GasBitmap 34

2432 Knock 2 (B1) High Warning Warning PC 3.x

40464 3 Fault Status GasBitmap 34

2433 Knock 3 (A2) High Warning Warning PC 3.x

40464 4 Fault Status GasBitmap 34

2434 Knock 4 (B2) High Warning Warning PC 3.x

40464 5 Fault Status GasBitmap 34

2435 Knock 5 (A3) High Warning Warning PC 3.x

40464 6 Fault Status GasBitmap 34

2436 Knock 6 (B3) High Warning Warning PC 3.x

40464 7 Fault Status GasBitmap 34

2437 Knock 7 (A4) High Warning Warning PC 3.x

40464 8 Fault Status GasBitmap 34

2438 Knock 8 (B4) High Warning Warning PC 3.x

40464 9 Fault Status GasBitmap 34

2439 Knock 9 (A5) High Warning Warning PC 3.x

40464 10 Fault Status GasBitmap 34

2441 Knock 10 (B5) High Warning Warning PC 3.x

40464 11 Fault Status GasBitmap 34

2514 Exhaust Temperature 19 (A10) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

40464 12 Fault Status GasBitmap 34

2515 Exhaust Temperature 20 (B10) Abnor-mal Rate

Shutdownw/Cool-down

PC 3.x

Page 341: Mapa de Registros de Pcc

334

Addr. ControlResponseEvent NameFaultCode

NameBit #

40464 13 Fault Status GasBitmap 34

2553 Engine Oil Level Low Warning Error Warning PC 3.x

40464 14 Fault Status GasBitmap 34

2568 Gas Supply Pressure Critical High Shutdownw/Cool-down

PC 3.x

40464 15 Fault Status GasBitmap 34

2569 Gas Supply Pressure Critical Low Shutdownw/Cool-down

PC 3.x

40465 0 Fault Status GasBitmap 35

2586 Spark Plug 1 (A1) High Warning NONE PC 3.x

40465 1 Fault Status GasBitmap 35

2587 Spark Plug 2 (B1) High Warning NONE PC 3.x

40465 2 Fault Status GasBitmap 35

2588 Spark Plug 3 (A2) High Warning NONE PC 3.x

40465 3 Fault Status GasBitmap 35

2589 Spark Plug 4 (B2) High Warning NONE PC 3.x

40465 4 Fault Status GasBitmap 35

2591 Spark Plug 5 (A3) High Warning NONE PC 3.x

40465 5 Fault Status GasBitmap 35

2592 Spark Plug 6 (B3) High Warning NONE PC 3.x

40465 6 Fault Status GasBitmap 35

2593 Spark Plug 1 (A1) Low Warning NONE PC 3.x

40465 7 Fault Status GasBitmap 35

2594 Spark Plug 2 (B1) Low Warning NONE PC 3.x

40465 8 Fault Status GasBitmap 35

2595 Spark Plug 3 (A2) Low Warning NONE PC 3.x

40465 9 Fault Status GasBitmap 35

2596 Spark Plug 4 (B2) Low Warning NONE PC 3.x

40465 10 Fault Status GasBitmap 35

2597 Spark Plug 5 (A3) Low Warning NONE PC 3.x

40465 11 Fault Status GasBitmap 35

2598 Spark Plug 6 (B3) Low Warning NONE PC 3.x

40465 12 Fault Status GasBitmap 35

2646 HT Coolant Temperature ConditionExists

Warning PC 3.x

40465 13 Fault Status GasBitmap 35

2963 HT Coolant Temperature WarningHigh

NONE PC 2.x, PC3.x

40466 0 Fault Status GasBitmap 36

3262 Spark Plug 7 (A4) High Warning NONE PC 3.x

40466 1 Fault Status GasBitmap 36

3263 Spark Plug 7 (A4) Low Warning NONE PC 3.x

40466 2 Fault Status GasBitmap 36

3264 Spark Plug 8 (B4) High Warning NONE PC 3.x

40466 3 Fault Status GasBitmap 36

3265 Spark Plug 8 (B4) Low Warning NONE PC 3.x

40466 4 Fault Status GasBitmap 36

3266 Spark Plug 9 (A5) High Warning NONE PC 3.x

40466 5 Fault Status GasBitmap 36

3267 Spark Plug 9 (A5) Low Warning NONE PC 3.x

40466 6 Fault Status GasBitmap 36

3268 Spark Plug 10 (B5) High Warning NONE PC 3.x

Page 342: Mapa de Registros de Pcc

335

Addr. ControlResponseEvent NameFaultCode

NameBit #

40466 7 Fault Status GasBitmap 36

3269 Spark Plug 10 (B5) Low Warning NONE PC 3.x

40466 8 Fault Status GasBitmap 36

3271 Spark Plug 11 (A6) High Warning NONE PC 3.x

40466 9 Fault Status GasBitmap 36

3272 Spark Plug 11 (A6) Low Warning NONE PC 3.x

40466 10 Fault Status GasBitmap 36

3273 Spark Plug 12 (B6) High Warning NONE PC 3.x

40466 11 Fault Status GasBitmap 36

3274 Spark Plug 12 (B6) Low Warning NONE PC 3.x

40466 12 Fault Status GasBitmap 36

3275 Spark Plug 13 (A7) High Warning NONE PC 3.x

40466 13 Fault Status GasBitmap 36

3276 Spark Plug 13 (A7) Low Warning NONE PC 3.x

40466 14 Fault Status GasBitmap 36

3277 Spark Plug 14 (B7) High Warning NONE PC 3.x

40466 15 Fault Status GasBitmap 36

3278 Spark Plug 14 (B7) Low Warning NONE PC 3.x

40467 0 Fault Status GasBitmap 37

3279 Spark Plug 15 (A8) High Warning NONE PC 3.x

40467 1 Fault Status GasBitmap 37

3281 Spark Plug 15 (A8) Low Warning NONE PC 3.x

40467 2 Fault Status GasBitmap 37

3282 Spark Plug 16 (B8) High Warning NONE PC 3.x

40467 3 Fault Status GasBitmap 37

3283 Spark Plug 16 (B8) Low Warning NONE PC 3.x

40467 4 Fault Status GasBitmap 37

3284 Spark Plug 17 (A9) High Warning NONE PC 3.x

40467 5 Fault Status GasBitmap 37

3285 Spark Plug 17 (A9) Low Warning NONE PC 3.x

40467 6 Fault Status GasBitmap 37

3286 Spark Plug 18 (B9) High Warning NONE PC 3.x

40467 7 Fault Status GasBitmap 37

3287 Spark Plug 18 (B9) Low Warning NONE PC 3.x

40467 8 Fault Status GasBitmap 37

3288 Exhaust Aft Outlet Oxygen RelayOORH

Warning PC 3.x

40467 9 Fault Status GasBitmap 37

3289 Exhaust Aft Outlet Oxygen RelayOORL

Warning PC 3.x

40467 10 Fault Status GasBitmap 37

3291 Exhaust Aft Inlet Oxygen Relay OORH Warning PC 3.x

40467 11 Fault Status GasBitmap 37

3292 Exhaust Aft Inlet Oxygen Relay OORL Warning PC 3.x

40467 12 Fault Status GasBitmap 37

3293 Exhaust Oxygen Relay OORH Warning PC 3.x

40467 13 Fault Status GasBitmap 37

3294 Exhaust Oxygen Relay OORL Warning PC 3.x

40468 3 Fault Status GasBitmap 38

3365 External Air Pressure Low Warning Er-ror

Warning PC 3.x

40468 4 Fault Status GasBitmap 38

3384 Manifold_Absolute_Pres-sure_2_High_Error

Warning PC 3.x

Page 343: Mapa de Registros de Pcc

336

Addr. ControlResponseEvent NameFaultCode

NameBit #

40468 5 Fault Status GasBitmap 38

3391 Manifold_Absolute_Pres-sure_2_Low_Error

Warning PC 3.x

40468 6 Fault Status GasBitmap 38

3392 Int Man Pressure 2 Critical High Shutdownw/Cool-down

PC 3.x

40468 7 Fault Status GasBitmap 38

3393 Int Man Pressure 2 Moderate High Warning PC 3.x

40468 9 Fault Status GasBitmap 38

3397 Low Gearbox Oil Pressure − ConditionExists

Shutdownw/Cool-down

PC 3.x

40468 10 Fault Status GasBitmap 38

3398 High Gearbox Oil Temperature − Con-dition Exists

Shutdownw/Cool-down

PC 3.x

40468 11 Fault Status GasBitmap 38

3399 Differential Fault − Condition Exists Shutdownw/Cool-down

PC 3.x

40468 12 Fault Status GasBitmap 38

3411 DC Power Supply Fault − ConditionExists

Warning PC 3.x

40468 13 Fault Status GasBitmap 38

3412 GIB Isolator Open Fault − ConditionExists

Warning PC 3.x

40468 14 Fault Status GasBitmap 38

3413 Radiator Fan Trip Fault − ConditionExists

Warning PC 3.x

40468 15 Fault Status GasBitmap 38

3414 Ventilator Fan Trip Fault − ConditionExists

Warning PC 3.x

40469 0 Fault Status GasBitmap 39

3415 Louvres Closed Fault − Condition Ex-ists

Warning PC 3.x

40469 1 Fault Status GasBitmap 39

3416 Start System Fault − Condition Exists Warning PC 3.x

40469 2 Fault Status GasBitmap 39

3417 Alternator Heater Trip Fault − Condi-tion Exists

Warning PC 3.x

40469 4 Fault Status GasBitmap 39

9971 ECM Derate Fault NONE PC 3.x

40469 5 Fault Status GasBitmap 39

3479 Start−Inhibit Shutdown Fault Shutdown PC 3.x

40469 6 Fault Status GasBitmap 39

3481 Start−Inhibit Warning Fault Event Warning PC 3.x

40469 7 Fault Status GasBitmap 39

3483 High Alternator Temperature 1 Shut-down Fault

Shutdown PC 2.x, PC3.x

40469 8 Fault Status GasBitmap 39

3484 High Alternator Temperature 2 Shut-down Fault

Shutdown PC 2.x, PC3.x

40469 9 Fault Status GasBitmap 39

3485 High Alternator Temperature 3 Shut-down Fault

Shutdown PC 2.x, PC3.x

40469 10 Fault Status GasBitmap 39

3486 High Drive End Bearing TemperatureShutdown Fault

Shutdown PC 2.x, PC3.x

40469 11 Fault Status GasBitmap 39

3487 High Non−Drive End Bearing TempShutdown Fault

Shutdown PC 2.x, PC3.x

40469 12 Fault Status GasBitmap 39

3482 Off Load Running Fault Shutdown PC 3.x

40469 14 Fault Status GasBitmap 39

463 Exhaust_Gas_Oxygen_High_Error Warning PC 3.x

Page 344: Mapa de Registros de Pcc

337

Addr. ControlResponseEvent NameFaultCode

NameBit #

40469 15 Fault Status GasBitmap 39

464 Exhaust_Gas_Oxygen_Low_Error Warning PC 3.x

40470 0 Fault Status GasBitmap 40

3491 Oil Filter Restriction High Shutdownw/Cool-down

PC 3.x

40470 1 Fault Status GasBitmap 40

2313 Fuel Control Valve Error Warning PC 3.x

40470 2 Fault Status GasBitmap 40

3475 Engine Electronic Fuel Valve #2OORH

Warning PC 3.x

40470 3 Fault Status GasBitmap 40

3476 Engine Electronic Fuel Valve #2 OORL Warning PC 3.x

40470 4 Fault Status GasBitmap 40

2812 Throttle Control Actuator Error Shutdownw/Cool-down

PC 3.x

40470 5 Fault Status GasBitmap 40

3489 Compressor Bypass Actuator Error Warning PC 3.x

40470 6 Fault Status GasBitmap 40

3458 Knock Engine Derate Warning PC 3.x

40470 7 Fault Status GasBitmap 40

781 CAN Datalink Failed Shutdown PC 2.x, PC3.x

40470 8 Fault Status GasBitmap 40

3499 Throttle Actuator 2− Special Instruc-tion

Shutdownw/Cool-down

PC 3.x

40470 9 Fault Status GasBitmap 40

3511 Throttle Actuator 2− Shorted High Shutdownw/Cool-down

PC 3.x

40470 10 Fault Status GasBitmap 40

3512 Throttle Actuator 2− Shorted Low Shutdownw/Cool-down

PC 3.x

40470 11 Fault Status GasBitmap 40

2752 Throttle Actuator − Shorted High Shutdownw/Cool-down

PC 3.x

40470 12 Fault Status GasBitmap 40

3514 Throttle Actuator − Shorted Low Shutdownw/Cool-down

PC 3.x

40470 13 Fault Status GasBitmap 40

3515 Throttle Actuator − Special instruction Shutdownw/Cool-down

PC 3.x

40470 14 Fault Status GasBitmap 40

3521 Throttle Actuator − Temperature low Warning PC 3.x

40470 15 Fault Status GasBitmap 40

3522 Throttle Actuator 2− Temp low Warning PC 3.x

Page 345: Mapa de Registros de Pcc

338

THIS PAGE LEFT INTENTIONALLY BLANK

Page 346: Mapa de Registros de Pcc

339

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

Page 347: Mapa de Registros de Pcc

340

4. NFPA 110 & Extended Annunciation BitmapNFPA110 bitmap (Register 40016)

BIT DESCRIPTION0 (MSB) Common Alarm

1 Genset Supplying Load

2 Genset Running

3 Not in Auto

4 High Battery Voltage

5 Low Battery Voltage

6 Charger AC Failure

7 Fail to Start

8 Low Coolant Temperature

9 Pre-high Engine Temperature

10 High Engine Temperature

11 Pre-low Oil Pressure

12 Low Oil Pressure

13 Overspeed

14 Low Coolant Level

15 (LSB) Low Fuel Level

Extended Annunciation Bitmap (Register 40017)

BIT DESCRIPTION0 (MSB) Check Genset

1 Ground Fault

2 High AC Voltage

3 Low AC Voltage

4 Under Frequency

5 Overload

6 Overcurrent

7 Short Circuit

8 Reverse KW

9 Reverse KVAR

10 Fail to Sync

11 Fail to Close

12 Load Demand

13 Genset Circuit Breaker Tripped

14 Utility Circuit Breaker Tripped

15 (LSB) Emergency Stop