manual f inc aux dc.pdf

Upload: raj-chavan

Post on 14-Apr-2018

231 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 manual F inc aux DC.pdf

    1/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    Manual for VSIG with DEIF controller

    1.1 Block diagrams, schematic and wiring.

    Figure 1 Internal connection block diagram when enginegovernor is equipped with CANBUS connection

    GENSET

    POWER

    ELECTRONICS

    CANBUS

    3

    CANBUS2

    CANBUS4

    GENSET

    CONTROLLER

    ENGINE

    GOVERNOR

    CGT-DEIF

    PROTOCOL

    J1939 PROTOCOL

    WU ( wake up)

    CANBUS1

    B-B+

    +12V 0

  • 7/27/2019 manual F inc aux DC.pdf

    2/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    Figure 2 Internal connection block diagram when engine governor has not

    equipped with CANBUS connector.

    GENSET

    POWER

    ELECTRONICS

    CANBUS3

    CANBUS2

    GENSET

    CONTROLLER

    ENGINE

    GOVERNOR

    CGT-DEIF

    PROTOCOL

    SP (Analog speed signal 0V-5V)

    WU ( wake up)

    CANBUS1

    B-B+

    +12V 0

  • 7/27/2019 manual F inc aux DC.pdf

    3/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    Figure 3 Detailed wiring diagram

    WU

    4044

    CAN HCAN L

    120 ohm

    TO CANBUS 3

    CANBUS

    1

    CANBUS 2

    1 2 3

    CANL

    C

    ANH

    TO CANBUS 4

    GND

    GND42

  • 7/27/2019 manual F inc aux DC.pdf

    4/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    1.2 VSIG operation topologies

    Figure 4 Stand alone mode of operation.

    POWER

    ELECTRONICS

    4

    POWER ELECTRONICS BOX

    4LOAD

    EC1ENGINE

    CAN + WU

    CONT 1

    Generator volta es

    Mains volta es

  • 7/27/2019 manual F inc aux DC.pdf

    5/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    Figure 5 Parallel and grid with automatic synchronisation.

    POWER

    ELECTRONICS

    4

    POWER ELECTRONICS BOX

    MAINS

    4

    LOAD

    LOAD

    ENGINE

    CAN + WU

    CONT 1

    EC1

    Mains voltage sensing

    Generator volta es

    Mains volta es

  • 7/27/2019 manual F inc aux DC.pdf

    6/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    Figure 6 Parallel mode of operation with standard Genset or VSIGusing frequency (4%) and voltage (2%) droop

    4LOAD

    LOAD

    EC1

    EC1

    POWER

    ELECTRONICS

    4

    POWER ELECTRONICS BOX

    ENGINE

    ENGINE

    POWER

    ELECTRONICS

    4

    POWER ELECTRONICS BOX

    CAN + WU

    CAN + WU

    CONT 1

    CONT 1

    Common bus

    STANDARD

    GENERATOR

    ENGINE

    STANDARD GENSET

    Mains voltage sensing

    Mains voltage sensing

    Generator volta es

    Mains volta es

    Generator volta es

    Mains volta es

  • 7/27/2019 manual F inc aux DC.pdf

    7/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    1.2.1 Structure of the menu for VSIG part in DEIF EC1

  • 7/27/2019 manual F inc aux DC.pdf

    8/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    Figure 7 Structure of the menu for VSIG part in EC1

  • 7/27/2019 manual F inc aux DC.pdf

    9/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    1.2.2 Display Description.

    1. Window shows frequency of the mains and actual powerfactor

    2. Window shows Generator (before contactor) line voltagesL1,L2,L3. When contactor is closed Mains and Generatorvoltages are the same.

    3. Window shows line to line Generator voltages L1L2,L2l3,L3L1

    4. Window shows Mains line voltages (after contactor)L1,L2,L3. When contactor is closed Mains and Generatorvoltages are the same.

    5. Window shows Mains line to line voltages L1L2, L2L3,L3L16. Window displays Generator load RMS current for phase

    L1,L2,L37. Window displays active power in kW for each phase

    L1,L2,L38. Window shows Total Generator active power Ptot in kW,

    total reactive Qtot kVAR and total apparent power Stot in VA.9. Window displays produced power over the time since last

    start of the system (kWh since last start) and temperature ofthe internal Heat sink temp.

    10. Window shows Number of starts of the generating set and

    running hours since last start.11. Window shows power electronics power (PE rating) ratingin VA, software version SW and power electronics serialnumber (PE serial nb)

    12. Window shows required engine speed from powerelectronics box (demanded speed) and actual engine speed.DC-link voltage it is internal system voltage should bedepending of the output voltage setting 600V or 800V.

    13. Genset controller software version14. Menu, which leads to Power Electronics box system

    setting. To access settings press ENTER key.15. Setting output voltage to change setting press enter put

    password of 2000 and set required voltage with arrows.Warning not all voltages have been implemented.

    16. PE Volt dip sets maximum allowed voltage dip of thegenerator voltages during full step load. Warning: Minimum

  • 7/27/2019 manual F inc aux DC.pdf

    10/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    engine speed much be set accordingly to fulfil thisrequirement. This is can be determined by test on theengine.

    17. In this menu operator can adjust output voltage of thegenerator. Waning this feature does work only in StandAlone mode.

    18. In this menu operator can set required mode of operation.Stand Alone, Grid operation , Parallel operation accordingwith the Figure 4 to Figure 6.

    19. In this menu operator can set required output voltagefrequency.

    20. In this menu operator can set minimum engine speed toachieve required voltage dip during step load.

    21. Demanded reactive power in Grid operation Mode.

    Operator can set required demanded reactive powerdelivered to the grid. Only in Grid operation mode.

    22. Operator can set required demanded active powerdelivered to the grid. Only in Grid operation mode.

    23. If system is equipped with Aux DC supply operator canchange modes of operation. OFF, 12V, 24V, 42V

    24. Operator can adjust voltage of the Aux DC supplyFor 12V mode ( from 10V-15V step 1V)For 24V mode ( from 19V-30V step 1V)For 42 mode (from 32V-52V step 1V)25. This menu display actual Aux DC voltage and Aux DC

    current.

  • 7/27/2019 manual F inc aux DC.pdf

    11/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    1.3 Configuration and operation.

    1.3.1 Configuration mode (common for all modes)

    Turn power ON to the DEIF controller.When engine is not running, set in DEIF controller parameters like

    Voltage, frequencyOperation mode type:1. Stand alone2. Parallel with grid3. Parallel with Genset (droop method)

    To make changes go to Parameter menu and press ENTER.Password for accessing Parameter menu is 2000.Go to required option and press ENTER to edit parameter.Change value of parameter by arrows and accept it by pressingENTER.

    Warning: PE controller will not accept new settings of mode ofoperation, output voltage and frequency when engine isrunning. Changing those parameters during when system is in

    GENERATING MODE will cause system to stop.

    1.3.2 Start-up and shut down.

    To start Genset and system press green start button( I ) on theGenset controller front panel.If engine has successfully stared after few seconds Green LEDover the generator symbol (sine wave in a circle) should come on.

    There is one minute engine warming time when engine will beworking with speed greater than 1500 rpm. After one minuteengine will settle at the minimum set speed.This means that Generator is working correctly. After 20-30seconds (depends of set mode of operation) contactor 1 will be

  • 7/27/2019 manual F inc aux DC.pdf

    12/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    closed which will put set voltage on VSIG terminals. This isindicated by green LED situated over switch symbol.

    To stop press red button ( O ).Green LED over switch symbol will immediately switch OFF andcontactor 1 open. When engine stops Green LED over generatorsymbol will start blinking. This means that system is shutting down.When LED will go off this means that system has shut down fullyand is ready to start again.Warning: Do not press start button before system has fully shutdown (while LED is blinking).

    Figure 8 Front panel of EC1

  • 7/27/2019 manual F inc aux DC.pdf

    13/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    1.3.3 Setting output voltage

    To make changes go to Parameter menu and press ENTER.Password for accessing Parameter menu is 2000.Go to PE volt mode (15) option and press ENTER to edit

    parameter. Set required output voltage using arrows and acceptit by pressing ENTER. Change will have effect on the next startof the system.

    1.3.4 Setting output frequency

    To make changes go to Parameter menu and press ENTER.Password for accessing Parameter menu is 2000.Go to Freq mode (19) option and press ENTER to editparameter. Set required frequency using arrows and accept it

    by pressing ENTER. Change will have effect on the next start ofthe system.

    1.3.5 Adjusting output voltage (17)

    -10% -10% around previously selected valueValue of the output voltage can be adjusted from -10% to +10% with 0.1% minimum step.To make changes go to Parameter menu and press ENTER.

    Password for accessing Parameter menu is 2000.Go to Volt adj (17) option and press ENTER to edit parameter.Set adjust voltage using arrows and accept it by pressingENTER. Change will have effect on the output voltage.

    Note: This function works only in stand alone operating mode.

    1.3.6 Setting voltage dip parameter (16).

    Voltage dip parameter sets allowable transient voltage dipduring full step load. Lower the voltage dip -> higher theminimum speed.To make changes go to Parameter menu and press ENTER.Password for accessing Parameter menu is 2000.

  • 7/27/2019 manual F inc aux DC.pdf

    14/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    Go to PE Volt dip (16) option and press ENTER to editparameter. Set required voltage dip using arrows and accept itby pressing ENTER. Change will have immediate effect on thevoltage dip parameter.

    Note: Voltage dip during step load is depended of minimumengine speed. If voltage dip during step load (from no loadcondition to full load condition) is higher than set in the menu,minimum speed (20) of the engine must be increasedaccordingly.

    1.3.7 Min RPM (minimum engine speed) (20)

    To make changes go to Parameter menu and press ENTER.

    Password for accessing Parameter menu is 2000.Go to Min RPM (20) option and press ENTER to editparameter. Set required minimum engine speed using arrowsand accept it by pressing ENTER. Change will have immediateeffect on the minimum engine speed.

    Minimum engine speed parameter is to set idle speed of theengine at no load condition. Lower engine speed means lovernoise and fuel consumption of the whole Genset at small loadless than 30% of the total Genset power. Unfortunately itimpacts voltage dip during the full step load (0-100%). If voltagedip is not within set voltage dip parameter(16) this means thatminimum engine speed must be increased. Operator has todetermine optimal engine speed needed to fulfil requirement bytest. If full step load will never be applied to the Gensetminimum engine speed can be significantly decreased.Depends of the engine but typically 1200 rpm can be sufficientto achieve 30%-50% step load with 10% voltage dip.

    1.4 Modes of operation description

  • 7/27/2019 manual F inc aux DC.pdf

    15/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    1.4.1 Stand Alone mode.

    This mode can be used only when Genset will be operating asa single unit as it is shown on Figure 4.

    1.4.2 Grid connection with back synchronisation.

    After start-up PE will go into synchronisation mode. Insynchronisation mode, system checks mains parameters asphase sequence, voltage, frequency and compares them withsettings send in configuration mode.

    When grid parameters are correct with internal settings, PEoutput voltages will be synchronised with grid voltages.

    When synchronisation is finished and PE controller will closecontactor1 and indicate it by green diode over switch symbolon EC1.Amount of power (active and reactive) injected to the grid is setby DEIF Genset controller.It can be changed in Parameter \ DEPMAND P for active powerand Parameter \ DEPMAND Q for reactive power.When grid parameters are not correct, PE controller will reportappropriate error message and system will shut down.

    Messages can be:f not ack frequency of the bus varies from set frequencyTerm volt not ack voltage of the bus varies from set voltagePhase sych not ack wrong phase sequence

    When grid is lost, PE controller will open contactor1 and waitfor two minute for the grid voltages reappear.If grid voltages reappear during two minute period system willsynchronise back to the grid and will start producing power with

    the recently set values.If grid voltage will not reappear after two minutes, system willshut down with the appropriate error.

  • 7/27/2019 manual F inc aux DC.pdf

    16/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    1.4.3 Parallel operation of two Gensets any type (synchronous orVSIG)

    After start-up PE will go into synchronisation mode. In

    synchronisation mode, system checks mains parameters asphase sequence, voltage, frequency and compares them withsettings send in configuration mode.

    When bus parameters are correct with internal settings, PEoutput voltages will be synchronised with line voltages.When synchronisation is finished, PE controller will close outputcontactor1 and systems will start sharing load using droopmethod 4% speed droop and 2% voltage droop.

    Note:In all modes system will report faults of its internalcomponents, overloads, short circuits.

    1.4.4 Aux DC charger. (23)

    If system is equipped with Aux DC supply, operator can selectone of required output modes (OFF,12V,24V,42V).If set output mode is not available from the supplied unit orsystem is not equipped with Aux DC supply system will issueinitialisation error.

    1.4.5 Aux DC voltage adjustment (24)

    Operator can adjust output voltage around previously selectedoutput mode.For 12V supply adjustments are 10V-15V with step of 1V.For 24V supply adjustments are 19V-30V with step of 1V.For 42V supply adjustments are 32V-52V with step of 1V.Actual output voltage and load current is displayed on screen25.

    If Aux DC charger is overloaded it will issue Aux DC overloaderror. For internal transistor failure Aux DC driver errormessage will be issued.

  • 7/27/2019 manual F inc aux DC.pdf

    17/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

  • 7/27/2019 manual F inc aux DC.pdf

    18/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    1.5 ERROR messages.

    Inv U drv UnAckInv V drv UnAckInv W drv UnAckBoost top drv UnAckBoost bot drv UnAck

    Break chop drv UnAck

    This is low level hardwareerror from IGBT drivers andshould never occur innormal condition. If thiserror occurs every timesystem is started thismeans that PE must beserviced.Possible causes for thiserror are

    transistor failure,driver failure,short circuit inside the PEbox.

    Break chopper driver errorDC-link over V UnAck This error is caused when

    there is big regenerativeload. ( to much power

    flowing into the system)

    Heat sink trip UnAck Heat sink temperature is tohigh. Usually it means thatthere is something wrongwith cooling system notsufficient water flow.

    FPGA UnAck Internal error of the main

    controller. Should neverappear during normaloperation. If this erroroccurs every time system isstarted PE box must beserviced.

  • 7/27/2019 manual F inc aux DC.pdf

    19/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    Overload UnAck Inverter was overloadedGov fail UnAck Engine speed is not

    achieving demandedspeed. It means problem

    with the engine or governoror wiring.DC-link asym UnAck Internal error can be

    caused by regenerativeload or failure of internalcomponents. If this erroroccurs every time system isstarted PE box must beserviced.

    Term U pres UnAck When system is set to

    stand alone mode and thereare voltages present on theterminals it will issue thiserror.

    Term U NOK UnAck If system is set to parallelmode or grid mode andvoltage settings of thesystem do not match to theactual voltages measured

    on the terminals this errorwill be issued. Customershould check settings.

    Term f NOK UnAck If system is set to parallelmode or grid mode andfrequency settings of thesystem do not match to theactual frequency measuredon the terminals this errorwill be issued. Customer

    should check settings.Phase seq UnAck If system is set to parallel

    mode or grid mode andphase sequence on theterminals do not much to

  • 7/27/2019 manual F inc aux DC.pdf

    20/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date:

    05/03/08

    Drawn:

    ArturKrasnodebski

    Approved: Cummins Generator

    Technologies (CGT)

    Stamford UK

    Issue:

    F

    the phase sequence of thesystem this error will beissued. Customer shouldcheck terminal phase

    sequence.Init error UnAck This error will occur whensystem havent receivedcorrect settings before start.This is usually problembetween DEIF andCummins. This error shouldnever occur in normaloperation.

    PMG temp UnAck If PMG temp will be higher

    than max specified thiserror will be issued andsystem will be stopped

    PCB temp UnAck If PCB temp (Printed CircuitBoard inside PE box) will behigher than max specifiedthis error will be issued andsystem will be stopped

    Choke temp UnAck If choke will be higher than

    max specified this error willbe issued and system willbe stopped

    Heat sink temp UnAck If IGBT heatsink temp willbe higher than maxspecified this error will beissued and system will bestopped

    Over voltage UnAck If voltage is higher thannominal for more than 3 s

    this error will be issued andsystem will be stopped

    Under voltage UnAck If voltage is lower thannominal for more than 8 sthis error will be issued and

  • 7/27/2019 manual F inc aux DC.pdf

    21/21

    A: B: C: D: E: F:

    G: H: J: K: L: M:

    Date: Drawn: Approved: Cummins Generator Issue:

    system will be stoppedAux DC overload If Aux DC supply is

    overloaded this error will beissued and Aux DC will be

    turned OFFAux DC driver error This is low level hardwareerror from IGBT drivers andshould never occur innormal condition. If thiserror occurs every timesystem is started thismeans that PE must beserviced.Possible causes for this

    error aretransistor failure,driver failure,short circuit inside the PEbox.