8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
1/28
MAN 2512 Rev: October 2005
ZoneSense
FI RE
ZONE 1
ZON E2
ZONE3
ZONE 4
ZO NE 5
ZONE 6
ZONE 7
ZONE 8
FAULT/ DISABLED/TEST
CANC EL
MENUIEN TER
SYSTEM STATUS
POWER
POWER FAULT
SYSTEM FAULT
EARTH FAULT
FAULTOUPUTSTATUS
ANCILLARYOUTPUTDISABLED
FIRE OUTPUTSTATUS
TEST
AMPAC
SYSTEM IS NORMAL
ALARMSDELAY
ACTIVEFIRE FAULT
FIRE OUTPUTONALARMS STATUS
DISABLED
NORMAL ENABLE
EVACUATERE S E TSILENCE
BUZZER
SILENCE
RE S OUNDOVERRIDE
FFFiiirrreee AAAlllaaarrrmmm CCCooonnntttrrrooolll PPPaaannneeelll
EEENNN555444 222 &&& 444 111999999777
Our aim is to provide Consistently Excellent Service in the eyes of our customers
Installation &Commissioning
of
Control & MonitoringAdd Ons
PLUS
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
2/28
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
3/28
Installation & Commissioning of Control & Monitoring Add Ons
Page 1
Table of Contents Page No.
1 About This Manual...............................................................................................21.1 Purpose ...............................................................................................................21.2 Scope...................................................................................................................21.3 References ..........................................................................................................21.4 PCB Removal / Replacement.............................................................................3
2 Wiring to the Main Card BRD25MCB ................................................................. 32.1 Communications ................................................................................................3
3 Adding Control and Monitoring Facilities ......................................................... 43.1 Internal Communications Connector (RS485).................................................43.2
Programming ......................................................................................................4
4 Installation and Wiring of Add On Cards and Boards...................................... 44.1 Address Setting and Terminating the Communications Bus ........................54.2 Input Board BRD25SIPB ....................................................................................64.3 Relay Board BRD25EWRB.................................................................................64.4 Fire Fan Module BRD25FCB..............................................................................74.5 Fan Termination Board BRD25FTB..................................................................84.6 General Indicator Card BRD25GIB -A...............................................................84.7 Switch and Indicator Card BRD25GIB - B ........................................................94.8 Zone Mimic Indicator Card ( Int. Pwr. ) BRD25GIB -C.....................................94.9 Zone Mimic Indicator Card ( Externally Powered. ) BRD25GIB -C ..............104.10 LED Annunciator Master ( LAM ) BRD25GIB - E ...........................................104.11 Sounder Board BRD25SOPB -A......................................................................11
5 Agent Release.................................................................................................... 115.1 Operation...........................................................................................................115.2 Agent Release Module BRD25ARB - A...........................................................145.3 Local Control Station BRD25ARB - B.............................................................155.4 Common Agent Release Module and Local Control Station Indicators.....165.5 Agent Release Termination Board BRD25ATB .............................................175.6 Interface Wiring ................................................................................................18
6 Appendix: Adding to the System Menu & Programming...............................207 Status and Programming Screens................................................................... 22
7.1 Level 1 to 3 Status Screens.............................................................................227.2 Level 3 System Programming .........................................................................237.3 Level 3 Programming Menu.............................................................................24
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
4/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 2
1 About This Manual
1.1 PurposeThis manual is an instructional tool for the installation and commissioning, of add on ancillary
cards, modules and boards that can be fitted to the ZoneSense PLUSFire Alarm Control Panel(FACP) and should be read in conjunction with the main Installation and Commissioning Manual.
1.2 ScopeThe information within this manual is only available to and for the use of personnel engaged in
the installation and operation of theZoneSense PLUSFACP.
ZoneSense PLUS has been designed to comply with major world standards. To ensure thesestandards are not compromised in any way installation staff and operators should;
1. be qualified and trained for the task/s they undertake;
2. be aware this manual should be read prior to the installation and commissioning of theZoneSense PLUSFACP;
3. observe anti-static pre-cautions at all times; and
4. if a problem is encountered or there is any doubt with respect to the operational parametersof the installation the supplier should be contacted.
1.3 References
ZoneSense PLUSTechnical ManualZoneSense PLUSOperation &Programming ManualZoneSense PLUSInstallation and Commissioning ManualApollo Detector / Device ManualsAmpac Product Data SheetsBritish Standard EN54 Parts 2 & 4European Standard BS 5839
FIRE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
Z ONE 6
ZONE 7
ZONE 8
FAULT / D ISABLED/TEST
CANCEL
MENU
IENTE R
SYSTEM STATUS
POWER
POWER FAULT
SYSTEM FAULT
EARTH FAULT FAULT OUPUTFAULT/DISABLED
ANCILLARYOUTPUTDIS ABLED
ALARMS/FAULTDISABLED
TESTAMPAC
SYSTEM IS NORMAL
ALARMSDELAY FIRE FAULT
FIR E OUTPUT O N FIR E PUTPUTFAULT/ DISABLED
DISABLED
NORMAL ENABLE
EVACUATERESETSILENCEBUZZER
SILENCERESOUNDOVERRIDE
Figure 1: Examples of the ABS, Metal Cabinet and Metal Cabinet with Battery Box
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
5/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 3
1.4 PCB Removal / Replacement
If the PCBs have to be removed the following precautions should be observed;
1. Removing the door will provide better access to the boards and ensure the hinges arenot accidentally stressed.
2. Personal anti- static procedures must be followed.
3. When disconnecting the telecom style connecting cable from the PCB, make sure thatthe cable remains connected to at least one board to prevent it being misplaced.
Note: Care should be taken when detaching this connector as it is necessary to depress thesmall locking tab to unlock the connector from itsbase. To reconnect the cable the connector must firstbe correctly aligned then pushed into the socket so itlocks into position.
4. Carefully remove the retaining screws at each
corner of the board taking care not to damageany of the components.
5. Place each board into anti- static storage once removed.
2 Wiring to the Main Card BRD25MCB
2.1 Communications
External Communications Terminals (RS485) TB2 1, 2 & 3The RS 485 output drives the remote cards and mimics up to a distance of 1.2km from the panelitself. The external cabling (2x2 shielded pair plus power) is wired to TB2 +, - and earth.
Note: If a fault occurs on the communications line the common FAULT and SYSTEM FAULTLEDS will be illuminated. The fault details can be displayed by selecting the Faults Menu.
Remote CardsThe number of cards that can be installed on the external communications bus are:
8 x Remote LED Mimics. 1 x 8 Way Remote Relay Output Board. This board provides 8 sets of normally open
(NO), normally closed ( NC ) and Common ( C ) voltage free contacts rated at 1A @30V.
Main Card Comms Link K1K1 MUST be inserted when only the front door panel cards and the Main Card are used as anFACP. If this is not the case and TB2 is cabled to LED mimics and / or 8 Way Remote Relay
Boards a link is inserted in the last board to complete the communication circuit orif boards aremounted on the back pan and communications are wired from the Main Card then the last boardin this chain MUST be terminated.
K1
Comms + -Comms Link
TB2
Top Left Hand Cornerof the Main Board
To LED Mimics and/orRemote Relay Boards
TB3
SP C/C ALT
Spare I/P
Class Change I/P
Alert I/P
Inputs
RS485 Com 1 2 3
Note:the shield iswired to
Shield
Figure 2: Wiring Detail
Push Tab Inwardsand Gently Pullthe ConnectorFrom the Socket
Connector
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
6/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 4
3 Adding Control and Monitoring Facilities
A combination ofone of each type of board / card, but not all of them, can be mounted on theback pan or the front panel of the FACP to provide additional features to a standard panel. Allboard inputs or outputs are programmable to any combination of zones.
Relay Board, BRD25EWRB A or with a change of on board components it canalso be installed remotely on the external communications bus as a RemoteRelay Board BRD25EWRB -B
Input Board BRD25SIPB -. Sounder Board BRD25SOPB. Brigade Interface Board BRD25BBA. Fire Fan Module consists of a Termination Board ( BRD25FTB and front panel
card BRD25FCB -. Agent Release Module consists of a Termination Board ( BRD25ATB ), front
panel card ( BRD25ARBA ) and if required a remote local control station(BRD25ARBB).
General Indicator Card. BRD25GIB -A Switch and Indicator Card BRD25GIBA Zone Mimic Indicator Card ( Internal Power ) BRD25GIB -C Zone Mimic Indicator Card (External Power normally remote) BRD25GIB -D
Note: To add or remove Cards from the FACP programming go to the SYSTEM Menu.3.1 Internal Communications Connector (RS485)PCB mounted connectors provide serial communications to internal ancillary boards. CN9 on theMain Card cables to CN1 or 2 on the front panel boards and CN5 on the Main Card cables toCN1 or 2 on the back pan boards
3.2 ProgrammingRefer to the Operation and Programming Manual to program the above options into the FACP.
Note: The Configuration label should be updated once the panel has been upgraded.
4 Installation and Wiring of Add On Cards and Boards
CAB1925 to Batteries
CAB1902
CAB1905
CAB1911 TO MAINS EARTH
CN1CN2 CN2 CN1ALARM2
N/CCOMN/0BATTFAIL
N/CCOMN/0ISOLATE
N/CCOMN/0FAULT
N/CCOMN/0ALARM1
N/CCOMN/0
TB1-TB5
POWER
0V
+27V
0V
+27V
CN2
CN1
CN3CN4
POWER
+27V
0V
CN1
CN2
+27v Power fitted when Relay or Termination Boards are fitted
CN1
CN2
CN5
CN9
CN1CN2CN2 CN1
CAB2200 CAB2117
CAB1905
CAB2200
CN6
POWER
+27V
0V
CN1
CN2
POWER
+27V
0V
CN1
CN2
MAIN CONTROL CARD
OPTIONAL CARDSAGENT RELEASEFAN CONTROLGENERAL INDICATOR
OPTIONAL BOARDSAGENT TERMINATIONRELAYFAN TERMINATIONINPUTSOUNDER TERMINATION
A BATT BOX IS REQIF THESE BRDS ARE FITTED
OTIONALBRIGADE BOARD
CAB2200
CAB2200
BRD25ARB PCB0783 (AGENT RELEASE MODULE)BRD25ATB PCB0787 (AGENT TERMINATION BOARD)BRD25BBA PCB0779 (BRIGADE BOARD)BRD25EWRB PCB0770 (8 WAY RELAY BOARD)BRD25FCB PCB0783 (FIRE FAN MODULE )
BRD25FTB PCB0780 (FAN TERMINATION BOARD)
PSU1887
CN3
CN4
CN3 CN4
CN3
CN4
BRD25GIB PCB0781 (GENERAL INDICATOR CARD)BRD25MCB PCB0769 (MAIN CONTROL CARD)BRD25PSU PCB0813 (POWER SUPPLY UNIT)BRD25SIPB PCB0778 (SINGLE INPUT BOARD)BRD25SOPB PCB0772 (SOUNDER OUTPUT BOARD)
OPTIONAL CARDSAGENT RELEASEFAN CONTROLGENERAL INDICATOR
OPTIONAL BOARDSAGENT TERMINATIONRELAYFAN TERMINATIONINPUTSOUNDER TERMINATION
A BATT BOX IS REQIF THESE BRDS ARE FITTED
OPTIONAL BOARDSAGENT TERMINATIONRELAYFAN TERMINATIONINPUTSOUNDER TERMINATION
A BATT BOX IS REQIF THESE BRDS ARE FITTEDBUS 1
BUS 2
BUS 3
BOARDIDENTIFIERS:
CN8
CN10
Figure 3: Typical Wiring, Ancillary Card and Board Positioning Within the ABS FACP
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
7/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 5
4.1 Address Setting and Terminating the Communications Bus
Address Setting ( SW1 )
Except for the LED Mimics in ZoneSense PLUSFACPs there can only be one (1) Board / Card of
each type so the address on each board is set to 1.
Note: There can be up to 8 remote LED Mimics so the address of each is set from 1-8 dependingon the number Mimics in the system. The information displayed at each location will be identical.
DIL Switch: ON = 1, OFF = 0Address 1234 Address 123401 1000 05 101002 0100 06 011003 1100 07 111004 0010 08 0001
Figure 4:Address Table & Example of Switch ( SW1 ) Set to 1
Terminating the Communications BusLK1 is the EOL Link and must be inserted on the last board on each communications bus. If not,a communications fault can occur.
TB2
K1
Shield
CN 5
CN 9Front Panel
Card 1Front Panel
Card 2
BackpanBRD 1
BackpanBRD 2
INSERTLK1
RemoteCard 1
RemoteCard 2
LCS 1 LCS 2
INSERTLK1
INSERT
LK1
INSERTLK1
If Agent Release is fitted to the FACP there will be an Agent Termination Board mounted on the Backpan.Local Control Stations can then be fitted at some location remote from the FACP. These LCS's communicatewith the ATB via a second RS485 bus hence the last LCS in the chain will have to be terminated
Note: If Backpan boards AND remote facilitiesare fitted the front panel cards are not terminated
ToTB1 Agent Termination Board
Fit K1 if only theMain ControlCard is used asthe FACP or1 Bus is used
RS485 +-
BUS 1 ( B1 )
BUS 2 ( B2 )
BUS 3 ( B 3)
( Link 1 in Table below )
( Link 2 in Table below )
( Link 3 in Table below )
BUS 4 ( B 4)Fit LK1 to last LCS
Figure 5: RS485 Communication Bus Terminating
Linking TableLink Bus Configuration
B1 B1,2 B1,3 B1,2,3 B,2 B2,3 B31 X & K1 X X
2 X X X & K1 X
3 X X X X & K1
X = Insert LinkB1: Bus 1 to Front Panel CardsB2: Bus 2 to Backpan BoardsB3: Bus 3 to Remote facilitiesB4: Bus 4 Local Control Station cabled to the backpan Agent Release Board.
Note: Programming and the communication process allows the Main Card to identify the type ofboard it is communicating with.
1 2 3 4
On
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
8/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 6
4.2 Input Board BRD25SIPB
DescriptionThe Input Board makes provision for 16 voltage free contacts to be terminated to 16 opticallycoupled inputs. Its application is primarily for the monitoring of controlled ancillary equipment or toinitiate an action / event due to a change of state from what is accepted as the norm.
ConnectorsCN1 Is designated as the input Comms .CN2 Is designated as the output Comms to the next board.CN3 27 Volts into the Board. Quiescent Current:2.6mACN4 27 Volts to the next Board unless it is the last board in the chain then it is left empty.
Terminal BlocksTB 2 9 Taking note of the Common 0v terminals connect the voltage free contacts as shown
below. Note: only the first 8 are functionally programmable in ZoneSense PLUS
SW1 There can only be 1 Input Board so the address on each board is set to 1.
LK1 Is the EOL Link and is inserted should the board be the last in the chain. If notinserted on the last board the Main Card will initiate a communications fault.
SW1
LK1 EOL Termination Address SWSET to 1
INPUTS1 2 3 4 0V INPUTS5 6 7 8 0V INPUTS9 10 11 12 0V INPUTS13 14 15 16 0V0V
16 Inputs are Voltage Free Contacts
27 VIn
27V To CN3 of Next Board
TB9TB8TB7TB6TB5TB4TB3
RS485 Control In From CN2 of thePrevious Board or CN5 of the Main Card
RS485 Control Out to NextBoard or Link 1 EOL is Applied
CN2
CN1
CN3 CN4
TB2
1 2 3 4
ONON
Inputs
1 2 3 4
0V Inputs
5 6 7 8
0V Inputs
9 10 11 12
0V Inputs
13 14 15 16
0V0V
16 Inputs are Voltage Free Contacts
TB9TB8TB7TB6TB5TB4TB3TB2
8= 0 Volts = Input
+-
#1. 27 Volts In from CN10 on the Main Card or CN4 of the previous internal board.
#2. Select an appropriate length cable from those supplied to connect Comms & 27V.
Note: Only the first 8 Voltage Free Contacts are functionally programable.The second 8 can be used to independently drive LEDs 8 to 16 on theGeneral Indicator Board.
Figure 6: Typical Input Wiring and Board Layout
4.3 Relay Board BRD25EWRB
Relay Board ( Internal ) BRD25EWRB -A
The Relay Board has provision for 8 X 1 Amp voltage free change over contacts for control ormonitoring purposes. Communication and control cabling is the same as all other internal boards.
Quiescent Current:2.4mA
LK1 EOL Termination
Address SWSET to 1
27 VIn
27V To CN3 of Next Board
RS485 Control In From CN2 of thePrevious Board or CN5 of the Main Card
RS485 Control Out to NextBoard or Link 1 EOL is Applied
CN2
CN 1
CN3 CN4 ON+-
#1. 27 Volts In from CN10 on the Main Card or CN4 of the previous internal board.
#2. Select an appropriate length cable from those supplied to connect Comms & 27V.
TB8TB7TB6TB5TB4TB3TB2TB1
SW 1
O/P 8N/CCOMN/0
O/P 7N/CCOMN/0
O/P 6N/CCOMN/0
O/P 5N/CCOMN/0
O/P 4N/CCOMN/0
O/P 3N/CCOMN/0
O/P 2N/CCOMN/0
O/P 1N/CCOMN/0
1 2 3 4
ON
TB8TB7TB6TB5TB4TB3TB2TB1
O/P 8N/CCOMN/0
O/P 7N/CCOMN/0
O/P 6N/CCOMN/0
O/P 5N/CCOMN/0
O/P 4N/CCOMN/0
O/P 3N/CCOMN/0
O/P 2N/CCOMN/0
O/P 1
N/C
COM
N/0
N/0 = Normally Open
COM = Common
N/C = Normally Closed
Figure 7: Board Layout
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
9/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 7
Relay Board ( Remote ) BRD25EWRB - B
In the remote version the Comms In and Out Terminal Block TB9 is cabled to the RS 485 Commsterminal block TB3 on the Main Card 302 7690 or LED Mimic and can be installed up to 1.2kmsfrom the FACP.
Note#1: This version can be powered from the panel or an external 27 volt source due to the onboard switched mode supply. Quiescent Current of both boards is 16mA
Note#2: In a system there can only be either a remote OR an internal board, not both.
Figure 8: Remote Relay Board Layout
4.4 Fire Fan Module BRD25FCB
The Fire Fan Module has four ( 4 ) separate fan controls each having an On, Auto and Offfunction switch and a set of three (3) monitoring LEDs. The LEDs indicate the status of theequipment eg. Run, Fault or Stop. The two ( 2 ) arrow head keys are used to step up and / ordown through the three ( 3 ) conditions. A slip in label can also be inserted into the hinged coverfor identification purposes.
Quiescent Current: 13.5mA
Slip In
Label
Card & PCB Securing Tabs( Top & Bottom )
PCB
ClearPlasticClipInLabel
Clip OnPlastic Surround( Push down here and pullout to remove and insert labels )
WINDOWS
WINDOWS
FOR SLIP
IN LABELS
Lettering on slip inlabels must be atleast 5mm in height.
K2 Termination Link
In Out
Address
SwitchSet to 1
1
2
3
4
ONCN1
CN2
CN1: Communications & 27V IN from CN2 off the previousFront Panel Card or CN9 on the Main Card
CN2: Communications & 27V OUT to Next Front Panel Card.If Unsed the Termination Link Must be Inserted.
Top Front Card &PCB Securing Clips
Bottom Front Card &PCB Securing Clips
Figure 9: Fire Fan Module Front Panel Figure 10: Fire Fan Module PCB Layout
U4
CN 3
CH4
RL8RL7RL6RL5RL4RL3RL2RL1
X1
U5
U3
U2
U1
TB8TB7TB6TB5
TB9
TB4TB 3TB2TB1
LK1
HY1 U6
SW1
M10
TB10
0V0V +27VDC+27VDC
EXTERNALPOWER
rev.1
EC3AW
A B COM
EOL Termination
///
N O N C
C
///
N O N C
CC
NCNO
///
C
NCNO
//////
N O N C
C
CN
C
NO
///
///
NO
NC
C///
NO
NC
C
O/P 8N/CCOMN/0
O/P 7N/CCOMN/0
O/P 6N/CCOMN/0
O/P 5N/CCOMN/0
O/P 4N/CCOMN/0
O/P 3N/CCOMN/0
O/P 2N/CCOMN/0
O/P 1N/CCOMN/0
TB1-TB8
A B COM
COMMS IN / OUT Address SW
To TB3 on the MainCard and/or LED MimicIn Out
27V
1 2 3 4
ON
Contact Legend:N/O = Normally OpenN/C = Normally ClosedC = Common
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
10/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 8
4.5 Fan Termination Board BRD25FTB
The Fan Termination Board interfaces between the Fire Fan Module and the plant/equipment itcontrols via the 24 volt 250mA Start, Stop, current limited, relay outputs and monitor inputs.Programmable monitoring of the field equipment is achieved using 0 volts as an input level toindicate run, fault and stop conditions of that equipment. Monitoring is programmed in theFunction Menu for a 3, 4 or 5 Wire Start / Stop, Run, Fault, Stop & Common functions. The inputsare protected by way of resetable transorbs and resistive / capacitive networks.
Quiescent Current: 6.5mA
ConnectorsCN1 RS485 Control IN from previous board or Main CardCN2 RS485 Control OUT to next board or LK1 EOL termination is appliedCN3 27 VDC IN from CN10 of the Main Card or CN4 of the previous boardCN4 27 VDC OUT
Terminal BlocksTB2 5 Are used to connect the fan control and monitoring wiring to the board.
SW1
TB4TB3TB2
LK1
TB5
EOL Termination
0V+27V
POWER
Address SW
FAN 1FAN 1STOP COMSTOPFLTRUN
FAN 2STOP COMSTOPFLTRUNSTART
FAN3FAN 3STOP COMSTOPFLTRUNSTART
FAN 4COMSTOPFLTRUNSTART
FAN4STOPSTART
FAN 2
CN1
CN2
CN3 CN4
RS485 Control in from CN2 of Previous Board or CN5 of the Main Card
RS485 Control Out to Next Board or Link 1 EOL is Applied
27V In from CN 10 on the Main Card or CN4 of the Previous Board
27V Out to Next Board if Applicable
1 2 3 4
ON
STOP
COM
STOP
FLT
RUN
START
TB 2, 3, 4 or 5
Cabling from FACPto Plant / Equipment
1 2 3 4 5 6
FAN CONTROLSOLID STATE ORRELAY INTERFACE
FAN MONITORING
0VINPUTS 1, 2 & 3+24V O/Ps
RUN
Figure 11: Fan Termination Board Layout and Typical I/O Wiring
4.6 General Indicator Card BRD25GIB -A
IMPORTANT
Note: The Cards BRD25GIB A, B, C and D all have a common PCB. What sets them apart fromeach other is not only the function they perform but how the componentry is loaded onto the cardto perform that function.
This Card indicates / displays the status of the inputs on the 16 Way Input Termination Board byway of Program selectable tri-coloured LEDs with its function being identified on the front panelby slip in labels.
Quiescent Current: 3 to 3.5mA depending on the application
Card & PCB Securing Tabs( Top & Bottom )
PCB
Clip OnPlastic Surround( Push down here and pull
out to remove and insert labels )
Lettering on slip inlabels must be atleast 5mm in height.
WindowsforSlip in Label
Slip In Label
K2 TerminationLink
In Out
AddressSwitchSet to 1
1
2
3
4
ON
CN1
CN2
CN1: Communications & 27V INfrom CN2 off the previous FrontPanel Card or CN9 on the Main Card
CN2: Communications & 27V OUT to Next Front Panel Card.If Unsed the Termination Link Must be Inserted.
Top Front Card &PCB Securing Clips
Bottom Front Card &PCB Securing Clips
Figure 12: Front Panel Card Layout Figure 13: Front Panel Card & PCB Layout
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
11/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 9
4.7 Switch and Indicator Card BRD25GIB - BThis Card can effectively perform 2 different functions. Firstly the indicators monitor the first 8inputs of the 16 Way Input Termination Board while secondly the switches can be programmed tomanually operate a specific relay in the system.
Quiescent Current:3.6mA
Card & PCB Securing Tabs( Top & Bottom )
PCBClearPlasticClipInLabel
Clip onPlastic Surround( Push down here and pull
out to remove and insert labels )
Note: As per AS 1668lettering on any of theslip in labels must beat least 5mm in height.
WindowsforSlip inLabel
Slip In Label
WINDOWS FORSLIP IN LABEL
K2 TerminationLink
In Out
AddressSwitch
Set to 1
1
2
3
4
ON
CN1
CN2
CN1: Communications & 27V INfrom CN2 off the previous FrontPanel Card or CN9 on the Main Card
CN2: Communications & 27V OUT to Next Front Panel Card.If Unsed the Termination Link Must be Inserted.
Top Front Panel Card &PCB Securing Clips
Bottom Front Panel Card &
PCB Securing Clips
Figure 14: Front Panel Card & PCB Layout
4.8 Zone Mimic Indicator Card ( Int. Pwr. ) BRD25GIB -C
The internally powered Zone Mimic Indicator Card connects to the FACP 27 volt power supplyand the internal communications bus for indication control. The card provides remote visualindication of any Zone in an Alarm and / or Fault / Isolate condition. A maximum of 8 of thesecards can be connected to, or daisy chained together, on any one system. Slip in labels identifythe monitored Zone. The Alarm LEDs flash for an un acknowledged alarm and are steady foracknowledged. The Fault / Isolate LEDs flash for a Fault condition and are steady if a Zone isIsolated.
Quiescent Current:14mA
Card & PCB Securing Tabs( Top & Bottom )
Clip OnPlastic Surround( Push down here and pullout to remove and insert labels )
Lettering on slip inlabels must be at
least 5mm in height.
Slip In Label
PCB
AlarmIsolateFault
Windows for
Slip in Label
K2 TerminationLink
In Out
AddressSwitchSet to 1
1
2
3
4
ON
CN1
CN2
CN1: Communications & 27V INfrom CN2 off the previous FrontPanel Card or CN9 on the Main Card
CN2: Communications & 27V OUT to Next Front Panel Card.If Unsed the Termination Link Must be Inserted.
Top Front Panel Card &PCB Securing Clips
Bottom Front Panel Card &PCB Securing Clips
Figure 15: Front Panel Card & PCB Layout
Note: Except for CN1 & 2 being fitted and TB1, HY1 the Buzzer and CN6 not being fitted theunderside of this card is the same as for the externally powered card.
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
12/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 10
4.9 Zone Mimic Indicator Card ( Externally Powered. ) BRD25GIB -C
The externally powered Zone Mimic Indicator Card operates in the same way as does theinternally powered version. The only difference is that the 27 volt power supply is independent ofthe FACP. This card would be used when the distance involved causes a significant voltage dropsuch that it may effect the reliable operation of the system or the costs involved in the cable is
offset by the availability of a remote 27 volt supply.
Quiescent Current:13mA ( This current applies to both cards )
Figure 16: PCB Front Layout Figure 17: Underside of PCB
4.10 LED Annunciator Master ( LAM ) BRD25GIB - E
The LAM provides remote stand alone FACP status, Alarm and Fault / Isolate Indication of 8zones. Two push buttons, Lamp Test and Silence Buzzer, provide for local testing of theindicators and buzzer while the buzzer duplicates that at the FACP. A maximum of 4 LAMs withaddresses of 1 to 4 may be cabled to an FACP.
Card & PCB Securing Tabs ( Top & Bottom )
Lettering on slip inlabel must be atleast 5mm in height.
Slip In Label
PCB
AlarmDisableFault
Windows for
Slip in LabelFIRE
FAULT
DISABLED
ALARMS STATUS
FIRE OUTPUT STATUS
TEST
DELAYACTIVE
POWER
LAMP
TEST
SILENCE
BUZZER
FIRE
FAULT/DISABLED
Release of the Clip On Surround( Metal Cabinet: Push down here and pull out to remove and insert label.ABS Cabinet: At the top RH cornner of the surround insert the surround removaltool between it and the front panel then slide along the surround to release)
PWR OUT
PWR IN
+
0V
+24V
CO M
-RS485 OUT TO NEXT LAM( IF APPLICABLE )
INPUTMUTE
BUZZER
LK1TERMINATION LINK
SWITCHADDRESS
CN 6
O
N
1
2
3
4
0V
+24V
+
CO M
- RS485 COMMS IN FROM FACP OR PREVIOUS LAM
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
LAM4
LAM3
LAM2
LAM1
LINK IS INSERTED ON THELAST CARD IN THE CHAIN
LAM 1 - 4ADDRESSSETTING
Figure 18: LAM Front Panel and PCB Layout
TB1
SW13
HY13V3 Supply Buzzer BZ1
CN6
0V
+
0V
+
BuzzerMuteInput
AddressSwitch
EC3AW
RS 485In
CO M
RS 485Out -
CO M
+
-
+
TerminationLink K2
27VIn
27VOut
1
2
3
4
ON
+
D17
D18
D19
D20
D1
D2
D3
D4
D5
D6
D7
D8
D9
D10
D11
D12
D13
D14
D15
D16
D21
D22
D23
D24
D25
D26
D27
D28
D29
D30
D31
D32
U1
U2
U3
U4U5
U6
U7
U8
X1
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
13/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 11
4.11 Sounder Board BRD25SOPB -A
The Sounder Board expands the number of sounders that can be used on an FACP to 8. Each
solid state output is rated at 24VDC / 500mA. and requires a 10K End of Line (EOL) resistorregardless whether or not a sounder is wired to the circuit.
Quiescent Current: 5.6mA Maximum Current per Output: 500mA
Figure 19: Wiring Detail & PCB Layout
Note: Sounder polarity MUST be observed.5 Agent Release
Control consists of the FACP Agent Release Module and Termination Board. Should control berequired at a point remote from the FACP an Agent Release Local Control Station can beincorporated .
5.1 Operation
IntroductionThe Agent Release Module and Termination Board communicate with the FACP via the RS485multi-drop bus.
The Agent Release Local Control Station communicates only with the Termination Board via aseparate RS485 bus. Up to 4 Agent Release Local Control Stations can be connected to onetermination board.
The Agent Release Module operates in three modes;1. Automatic/Manual;2. Manual Only; and3. Disable.
The mode is selected by operating the keyswitch switch on either or module.
The keyswitch at the Agent Release Module is the only keyswitch with a Disable selection andhas the highest priority. Hence when the keyswitch is in the Disable position all other keyswitches
are ignored and the agent control system is in the Disabled mode.
Next priority is Manual Only. If any keyswitch is in Manual Only (providing the keyswitch at theAgent Release Module is NOT in Disable), then the board is in the Manual Only mode.
Finally, the system is in the Auto/Manual mode when all keyswitches are in Auto Manual.
The pressure switch input on the termination board (which is used to confirm that the agent hasbeen released) can be configured to accept a normally open contact, normally closed contact, orignored. This is selected via the FACP on-site programming.
TB3 TB2 TB1
SW 1
-VE+VESOUNDER 1
-VE+VESOUNDER 2
-VE+VESOUNDER 3
-VE+VESOUNDER 4
-VE+VESOUNDER 5
-VE+VESOUNDER 6
-VE+VESOUNDER 7
-VE+VESOUNDER 8DC IN
0V 27V
LK1 EOLTermination
Address SW
POWER
CN2
CN1
27V IN- +
To Sounders 1 to 4 + / - To Sounders 5 to 8 + / -
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
1 2 3 4
ON
TB3 TB2 TB1-VE+VE
SOUNDER 1-VE+VE
SOUNDER 2-VE+V E
SOUNDER 3-VE+V E
SOUNDER 4-VE+V E
SOUNDER 5-VE+VE
SOUNDER 6-VE+VE
SOUNDER 7-VE+V E
SOUNDER 80V 27V
To Sounders 1 to 4 + / - To Sounders 5 to 8 + / -
RS485 Control In From CN2 of thePrevious Board or CN5 of the Main Card
RS485 Control Out to NextBoard or Link 1 EOL is Applied
ONNote: Sounder polarity MUST be observed
27V IN- +
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
14/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 12
Disabled ModeDisabled mode is selected by placing the keyswitch at the Agent Release Module in the Disabledposition. This electrically isolates the activation circuit, and results in the following: Disabled indicators at the Agent Release Module and Local Control Station are lit. Agent Release Module and Local Control Station buzzers sound. No automatic releases can be commenced.
System inoperative output is activated.
Note:Disabled mode can not be overridden.Manual ModeWhen the board is in manual mode, then the Manual Only indicators at the Agent Release Module and Local Control Station are lit No automatic release sequences can be commenced. Does not interrupt a release sequence that has started System inoperative output is activatedTo manually discharge the agent, the Manual Release facility at the Agent Release Module or theLocal Control Station is activated.
The manual release sequence is: Manual Release Activated indicators are lit on the Agent Release Module and Local
Control Station Stage 1 outputs are switch to +24VDC. Stage 2 outputs are pulsed during the pre-release delay to +24VDC. Start optional pre-release delay. (Selected via FACP on-site programming). Upon expiration of the delay, activate the selected activation circuit and stage 2 outputs
becomes steady Light the agent released LED on the Agent Release Module and Local Control Station
when pressure switch input on the termination card is activated or immediately (dependson the pressure switch configuration).
FACP to activate the FIRE output and light the FIRE LED
The discharge sequence can be interrupted by the activation of the Hold input. Activation of theHold input prevents the release of the agent. When the Hold switch is released, the pre-releasedelay is restarted. While the Hold input is activated, the stage 2 output is switched off, and thebuzzer will sound.
Auto/Manual ModeIn this mode, automatic and manual discharge is possible. For manual discharge see above.
The automatic discharge sequence is initiated when one or two zones go into alarm.
With single zone alarm activation the following discharge sequence is executed. Auto Activation indicator is lit on the Agent Release Module and Local Control Station
Stage 1 outputs are switched to +24VDC Stage 2 outputs are pulsed during the pre-release delay to +24VDC Start optional pre-release delay (Selected via FACP on-site programming). Upon expiration of the delay, activate the selected activation circuit and stage 2 outputs
becomes steady. If configured light the agent released LED on the Agent Release Module and Local Control
Station when pressure switch input on the termination board is activated. FACP to activate the FIRE output and illuminate the FIRE LED. The operation of the Hold switch is as per the manual release
With dual zone activation, if the first zone goes into alarm, then the following steps are followed; Flash the auto release activated LED at the Agent Release Module and
Local Control Station
Stage 1 outputs are switched to +24VDC
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
15/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 13
When the second zone goes into alarm, then the following steps are followed Auto release activated LED on the Agent Release Module and Local Control Station goes
steady Stage 2 outputs are pulsed during the pre-release delay to +24VDC Start optional pre-release delay. (Selected via FACP on-site programming).
Upon expiration of the delay, activate the selected activation circuit and stage 2 outputsbecomes steady. Light the Agent Released LED on the Agent Release Module and Local Control Station
when the pressure switch input on the termination board is activated (depends on thepressure switch configuration).
FACP to activate the Fire output and illuminate the Fire LEDThe operation of the Hold switch is as per the Manual Release.
Released ConditionWhen the agent has been released, and the pressure switch input has been activated, then theboard is in the released condition. The condition is shown by: Agent Released indicator is lit at the Agent Release Module and Local Control Station FACP Fire output and associated indicator is On.
The condition remains until reset has been activated at the FACP.
It is possible, when the agent release module is in the released condition to de-activate the Stage1 and Stage 2 outputs. This is achieved by depressing the SILENCE/RESOUND button at theFACP. This action will also silence the alarm outputs at the FACP and the sounder outputs on the8 way sounder board (if fitted). If the SILENCE/RESOUND button is depressed again to instigatethe RESOUND facility, then the stage 1 and stage 2 outputs will be re-activated (as will theonboard alarm outputs and sounder outputs on the 8 way sounder board if fitted).
Lock-Off ValveWhen the lock-off valve is operated, the agent is blocked from reaching the release valve. Whenthe lock-off valve is operated, the following occurs: Light the Blocked Mode indicator at the Agent Release Module and Local Control Station
Operates the system inoperative output
Fault MonitoringThe sources of fault in the system are: Pressure switch monitoring circuit Low pressure switch monitoring circuit Lock-off valve monitoring circuit Activation circuit Stage 1 outputs Stage 2 outputs Fault in the trigger zones Fault with a Local Control Station
Note #1: The common fault indicator on the Agent Release Module and Local Control Station isilluminated for any Fault condition.
Note #2: For a pressure switch fault, low pressure switch fault, lock-off valve fault, stage 1output fault and stage 2 output fault the FACP will signal the brigade.
Note #3: When there is a fault in the activation circuit or in the trigger zones, in addition to theabove, the system inoperative output is operated.
Note #4: The FACP buzzer sounds for all faults and the LCD displays the type of fault.
Note #5: The FACP will report the type of fault on the LCD.
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
16/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 14
IsolationIf the trigger zones are isolated by the FACP, then the trigger zone isolated indicator at the AgentRelease Module and Local Control Station is illuminated, and the system inoperative output isoperated.
Disablement of the Trigger Zones
If the trigger zones are disabled by the FACP, then the isolate indicator at the FACP is illuminatedand the system inoperative output is operated.
5.2 Agent Release Module BRD25ARB - A
The Agent Release Module controls and monitors all the requirements for agent release andcarries the slide in label for identification of the agent and application area.
Keyswitch
PCB
Manual ReleaseSwitch
AUTO / MANUAL MANUAL ONLY
MANUAL HOLD
MANUAL RELEASEACTIVATED
AUTO RELEASEACTIVATED
RESERVE AGENT
TRIGGER ZONEDISABLED
INITIAL AGENT
AGENTRELEASED
BLOCKED MODE
COMMON FAULT
DISABLED
MANUAL
ELEASE
R
MANUALDISABLED
AUTO / MANUAL
HOLD
AGENT SELECT
MANUALONLY
Figure 20: Exploded View of Module and Front Panel Layout
Controlled AccessIt is a requirement that control be secured from unauthorised use. For this reason a key switchhas been included in the control process.
DISABLED
AUTO / MANUAL
MANUALONLY
Disabled, Manual Only, Auto/Manual Keyswitch In disabled mode theselected activation circuit is electrically isolated from the activation device, and the agent can notbe released. In manual only mode, the agent can only be released manually, and in Auto/Manualmode the agent can be released automatically or manually.
Note:The key is removable in all positions.
MANUAL HOLD
Manual Hold When activated, delays the discharge of the agent. When the switchis depressed during the pre-discharge delay, the delay is restarted when the switch is released. Ifdepressed at any other time a fault is registered after a 10 second debounce time out period.
AGENT SELECT
Agent Select When activated, causes the selected agent to toggle between Initialand Reserve.
MANUAL
ELEASE
R
Manual Release When activated causes a manual release of the agent, providing
the system is operative.
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
17/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 15
Agent Release Module PCB Layout
The PCB is fitted with two 2 x RJ45 connectors CN6 & 7 for power (27VDC) and communications(RS485) for communications between the Module and the FACP Main Card.
Quiescent Current:28.5mA
D10
D9
D14
D13
D12
D11
D6
D5
D4
D3
D8
D7
U4
U1
U2
U3
X1
Select
Manual ReleaseActivated
Initial Agent
Manual Hold
Auto / Manual
Auto ReleaseActivated
Reserve Agent
Trigger ZoneDisabled
Manual Only
AgentReleased
Blocked Mode
Common Fault
Disabled
Hold
CutoutCutout
SW 2
CN 2
TP9
Key Switch
AddressSwitch
RS485&
+/- 27vIn
RS485&
+/- 27vOut
1
2
3
4
O
NK1
TerminationLink
CN 8
Manual Release
CN 6 CN 7
Figure 21: Front Panel PCB Layout Figure 22: Underside of the Front Panel PCB
Note: If the keyswitch is not used CN2 will carry a link so as to activate the panel.5.3 Local Control Station BRD25ARB - BExcept for the agent select button, and the keyswitch only offering the Auto/Manual and ManualOnly selection the Local Control Station has the same indicators and controls as the AgentRelease Module.
AUTO / MANUAL MANUAL ONLY
MANUAL HOLD
MANUAL RELEASEACTIVATED
AUTO RELEASEACTIVATED
RESERVE AGENT
TRIGGER ZONEDISABLED
INITIAL AGENT
AGENTRELEASED
BLOCKED MODE
COMMON FAULT
DISABLED
MANUAL
ELEASE
RMANUAL
MANUAL ONLY
AUTO / MANUAL
HOLD
Keyswitch
PCB
Manual ReleaseSwitch
Figure 23: Local Control Station Layout
MANUAL
ELEASE
R
Manual Release Pressing the push button starts the manual agent releasesequence. This two action safety feature prevents any accidental operation of the control andshould not be disabled.
MANUAL
HOLD
Manual Hold When pressed places the system into manual mode and prevents theinitiation of the automatic discharge sequence.
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
18/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 16
5.4 Common Agent Release Module and Local Control Station Indicators
MANUAL RELEASEACTIVATED Manual Release Activated
Red in colour. Lit when a manual agent release sequence has commenced. This can beinstigated from the Agent Release Card and Local Control Station.
AUTO RELEASEACTIVATED Auto Release Activated
Red in colour. Lit when a automatic agent release sequence has commenced. This occurs whenthe zone(s) on the FACP have gone into alarm. For dual zones, the indicator should flash whenthe first zone goes into alarm, and steady when the second zone goes into alarm.
AGENTRELEASED Agent Released
Red in colour. Lit when the pressure switch indicates the agent has been discharged.
INITIAL AGENTInitial Agent
Yellow in colour. Lit when the initial agent activation circuit is selected.
RESERVE AGENTReserve Agent
Yellow in colour. Lit when the reserve agent activation circuit is selected.
BLOCKED MODEBlocked Mode
Yellow in colour. Lit when the lock-off valve has been activated.
MANUAL HOLDManual Hold
Yellow in colour. Lit when a Hold button is depressed on an LCS.
TRIGGER ZONE
DISABLED Trigger Zone DisabledYellow in colour. Lit when any of the trigger zones on the FACP are disabled.
COMMON FAULTCommon Fault
Yellow in colour. Lit under pressure switch, low pressure switch, lock-off valve, activation circuit,stage 1 output, stage 2 output, Local Control Station, trigger zone(s) fault conditions.
AUTO / MANUALAuto/Manual
Yellow in colour. Lit when a release sequence can be started automatically or manually.
MANUAL ONLY
Manual OnlyGreen in colour. Lit when a release sequence can be started manually only.
DISABLEDDisabled
Yellow in colour. Lit when the release sequence can not be started automatically or manually.
BuzzerBuzzer is activated under programmed control.
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
19/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 17
Local Control Station Terminal Blocks TB1 & TB2
TB2 Terminal Assignment TB1 Terminal Assignment1 RS485 + In 1 +27V In2 RS485 - In 2 0V In3 RS485 Common 3 +27V Out
4 RS485 + Out 4 0V Out5 RS485 - Out6 RS485 Common7 Interlock+8 Interlock-
Quiescent Current:18.5mA
Local Control Station Layout
The Comms line is RS485 between the Local Control Station and the Termination Board.
The Interlock is a monitored input with 10K EOL used to determine if air conditioning dampersand doors are closed. Typically the agent is not discharged until all dampers / doors are closed.
D10
D9
D14
D13
D12
D11
D6
D5
D4
D3
D8
D7
U4
U1
U2
U3
X1
Manual ReleaseActivated
Initial Agent
Manual Hold
Auto / Manual
Auto ReleaseActivated
Reserve Agent
Trigger ZoneDisabled
Manual Only
AgentReleased
Blocked Mode
Common Fault
Disabled
Hold
CutoutCutout
RS 485OUT
TB2
TB1
SW 2
K1
HY1
CN5
BUZZERBZ1
INTERLOCK
CO M TerminationLink
AddressSwitch
EC3AW3V3 POWERSUPPLY
+
CO M
+27V
Out 0V
+27VIn
0V
+_
+_
RS 485IN
+_
+
+
1
2
3
4
O
N
CN 8 CN 2
Key Switch
Manual ReleaseCutoutCutout
Figure 24: Top PCB Layout Figure 25: Bottom PCB Layout
5.5 Agent Release Termination Board BRD25ATB
Figure 26: Agent Termination Board PCB Layout
LK1
Q2
SW 1
U5
U9 U7
U1
RL6
RL4RL1 RL2 RL5 RL3
CN5
U3U4 U2
U10
RL7
+ LOCK-
+ L.PSW-
RELEASE
C
NC NO///
+L
COMM
NC
NO
-L
C
NC NO///
-+
SIG+
SIG-
LCP CABLE
+ PSW -
MonitoredINPUTS
N/0
STAGE2GASFIRED
+ - N/0 COMN/0 COM +
SYST.INOP.
SCRN+24VDC + -
C
NC NO///
C
NC NO///
-L
NO
NC
COMM
+L-L
NO
NC
COMM
+L
0VDC+ -
STAGE1
-COM
TB7TB6TB5TB4TB3TB2TB1
CN2
CN1
Address SettingCN 3 CN427V In
27V toNext Board
RS485 ControlIn From CN2 ofPrevious Board
RS485 ControlOut to NextBoard or Link 1EOL is Applied
MAIN RESV
+ - Outputs are Monitored
ContactRating
1A & 24V
ContactRating
1A & 24V
ContactRating
1A & 24V
ContactRating
1A & 24V
1 2 3 4
ON
EOLTermination
Quiescent Current:12mA
4K7
22KEOL
10KEOL
10KEOL
10KEOL
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
20/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 18
The Agent Release Termination Board interfaces to the;
1. The FACP via CN1, CN2 continuing the RS485 communications bus if required. LK1 isinserted if this is the last backpan board on the bus.
2. LCSs ( up to 4 ) via TB1. LK1 is inserted in the last board in the RS485 Bus
3. Monitored Inputs: via TB2. ( EOL Resistance 22K, Series Resistance 4K7 )(a) Pressure Switch ( PSW ) agent released(b) Low Pressure Switch ( LPSW ) agent storage cylinder pressure has dropped to a pre-
determined level; and(c) Interlock, the manual lock-off valve has been operated.
4. Gas Fired: Output via RL2 N/O contacts rated at 1A @ 24VDC wired to TB3. Used toindicate to other monitoring devices the agent has been released.
5. System Inoperative: via RL1 N/O contacts rated at 1A @ 24VDC wired to TB4. Used towarn by way of signage / audible alarm and/or monitoring that the system is inoperative.
6. Stage 1: Output; initiates the visual and audible Fire Alarm and Evacuate warnings.
(a) Monitored; via RL4 C/O contacts wired to TB5 1 & 2 ( EOL required 10K ) and(b) un-monitored; via RL5 N/O contacts wired to TB5 3 & 4.
7. Stage 2: output; initiates the visual and audible Fire Alarm and Do No Enter warnings
(a) Monitored; via RL6 C/O contacts wired to TB6 1 &2; ( EOL required is 10K ) and(b) Un-monitored; via RL3 N/O contacts wired to TB6 3 & 4
8. Release: Main actuating circuit, monitored (10K EOL required) via TB7 1 & 2 ( 2A currentlimited ),Release: Reserve actuating circuit, monitored (10K EOL required) via TB7 3 & 4 ( 2Acurrent limited )(a) To Pyrogen Igniter ( max of 10 )
(b) Metron Igniters ( max of 10 a series 2watt 18 resister must be added to the circuit )(c) Solenoid valve ( max current of 2 amps & 27VDC )
5.6 Interface Wiring
Monitored Inputs TB2 1 & 2Pyrogen,
This input relies on a thermal fuse used in conjunction with 22K EOL and 4K7series resistors. The type of agent release mechanism has to be set in theProgramming Menu for the input to function as per the manufacturers specificationsand be in accordance with the relevant Standard.
1 2
PSW
TB2Termination Board
4K7 22KEOL
PyrogenCanister
+ -
PyrogenReleasePoint
FUSE
Pyrogen Release
Brd. 302-740 To TB7MAIN or
RESERVERelease
MAIN / RESERVERELEASE
TB1
-VE
+VE
17/10/00
D1
R1
C1
C2
R2
TB2
302-7400
Figure 27: Pyrogen Wiring
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
21/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 19
Solenoid & Metron
This input relies on N/O or N/C relay contacts used in conjunction with 22K EOL and 4K7series resistors. The type of agent release mechanism and contacts used has to be set in theProgramming Menu for the input to function as per the manufacturers specifications and be inaccordance with the relevant Standard.
Note: The PSW, LPSW & the Interlock Mechanisms are allmounted onto the top of the cylinder containing the Agent
TerminationBoard
+ -
4K722KEOL
AgentDistribution
4K7
22K EOL
LPSW LOCK
4K7
22K EOL
PSW
+ - + -
MAIN / RESERVERELEASE
To TB7MAIN or
RESERVERelease
Agent
Figure 28: Solenoid, Metron PSW, LPSW and LOCK Wiring
LPSW & LockThese inputs are also monitored and should be wired as shown above
1
2
To MonitoringInterface / Device
0V
RL2ATB3
= MOV35V
*
* *
To SysInop Mon
+
-System Inoperative
1
20V
RL1ATB4
+27V CurrentLimited to1A
Figure 29: Gas Fired Wiring Figure 30: System Inoperative Wiring
As can be seen from above the;
Gas Fired Output can be wired to any interfacing or 1A monitoring circuit that requires a closedrelay contact to indicate a change of state. This could be a relay or a solid state device.
System Inoperative Outputs 27V @ 1A to supply interfacing, signage and aural alarms toindicate the system has been taken out of service or has developed a fault.
Stage 1, Stage 2
- ( + )
+ ( - )
*
0VTB5 = Stage 1TB6 = Stage 2
= MOV35V
*
*
+ve
-ve 10KEOL
1 or 2 WaySignage
To audible / visual
device or interface
*
Stage 1 or Stage 2
RL3ARL5A
RL4B
RL4A RL6A
Agent Termination Board Relays
RL6B
1
2
3
4
The above circuitry applies to bothTB5 ( Stage 1 ) and TB6 ( Stage 2 )
TB5 / 6
MAIN RESV
+ -
10K EOL
Solenoid
+ -
TB7
Figure 31: Stage 1 and 2 Wiring Figure 32: Agent ReleaseSolenoid Wiring
Current Generation SignageStage 1 displays the warning sequence ie discharge of the agent is imminent while Stage 2communicates the discharge of the agent is or has occurred DO NOT ENTER.
2nd
Generation SignageIs able to display both phases of agent release.
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
22/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 20
6 Appendix: Adding to the System Menu & Programming
In this example 1 Input Board, 1 Relay Board and 1 Sounder Board will be added to the system. TheDisplay and Zone Labels will then be edited.
Step 1:Go to the SYSTEM MENU and then follow the procedure as set out below.
ALARMYES / NO
RESOUND
YES / NOBUZZERSYSTEM
EARTH MONYES / NO
BRIGADENO
FIRE FANNO
RELAYSYES
AGENTNO
SOUNDERSYES
SW INDICNO
INDICATENO
INPUTSYES
MIMIC0 TO 8
CODEAS4428
MENU
ENTER
LEGEND:
PRESS ENTER TO ACCESSMENU AND UPDATE PROGRAMOR CHANGE MENU
PRESS MOVE FORWARDTHROUGH THE MENU
PRESS: MOVE FORWARDOR BACKWARDTHROUGH THE MENU
CANCELPRESS CANCEL ATANY TIME TO BACKOUT OF THE MENU
MENU
ENTERMENU
ENTER
MENU
ENTER
CANCEL
MENU
ENTER
PRESS THESE KEYSTO SET YES / NO
YES
MENU
ENTERUPDATE PROGRAM
FACTORY SETCAN NOT BECHANGED
EXAMPLESET RESOUND TO YESTHEN MOVE TO ALARM
MOVE TO ALARMYES / NO
IF THESE 4OPTIONSARE NOT SETTO YES THEYWILL NOTAPPEARIN THETEST MENU
ENTERPASSWORD
FACTORY DEFAULTPASSWORD IS 3333
PASSWORD0000
MENU
ENTER
PASSWORD0100
PASSWORD0120
PASSWORD0123
MENU
ENTER
PASSWORDACCEPTED
EXAMPLESETTING
PASSWORD0123
SYSTEM
EXAMPLE OF SETTINGTHE SYSTEM MENU IF A
RELAY BOARD IS INSTALLED
YESMENU
ENTERUPDATE PROGRAM
EXAMPLE OF SETTINGTHE SYSTEM MENU IF A
SOUNDER BOARDIS INSTALLED
YESMENU
ENTERUPDATE PROGRAM
NO BRIGADE INTERFACE BOARD INSTALLED
NO FIRE FAN MODULE INSTALLED
NO AGENT RELEASE MODULE INSTALLED
NO SWITCH & INDICATOR CARD INSTALLED
NO INDICATOR CARD INSTALLED
NO MIMIC INSTALLED
EXAMPLE OF SETTINGTHE SYSTEM MENU IF AN
INPUT BOARD IS INSTALLED
YESMENU
ENTERUPDATE PROGRAM
Example of Adding Input, Relay and Sounder Boards in the SYSTEM MEU
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
23/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 21
Step 2
ZONES
CLOCK
OUTPUTS
FIRE FAN
AGENT
SOUNDERS
DISPLAY########
SET SNDRBRD O/P
.2..5..8
Z LABELS
MENU
ENTER
LEGEND:
PRESS ENTER TO GO TO SUB MENU, SET MENU OR UPDATE PROGRAM
PRESS MOVE FORWARD THROUGH THE MENU
PRESS MOVE FORWARD / BACKWARD THROUGH THE MENU
CANCEL PRESS CANCEL AT ANY TIME TO BACK OUT OF THE MENU
MENU
ENTER
CANCEL
MENU
ENTER
ACFISOALTE
ACF
ISOALTE PRESS ACF TO ISOL ATE CIRCUITS EXTERNAL TO FACP
MENU
ENTER
EDITTEXT
SET ZONETO
ACTIVATE1...5..8
MENU
ENTER
PROGRAM
MENU
ENTER
MCP ZONEZ#
1 TO 8
ON
OF F
1 TO 8
IN THIS EXAMPLE SNDR O/P 2,5&8ARE ACTIVATED BY ZONES 1,5&8
RELAYSR3 Z-ALRM
1..4...8
R3 SWITCH.......
R3 Z-FLT.......
R3 Z-ISOL.......
R3 I/P1.3...7.
MENU
ENTERRELAY 3 MENU
ENTER
SELECT RELAY 3
ON
OF F
MENU
ENTER UPDATE MENUMENU
ENTER
IN THIS EXAMPLE RELAY 3 IS ACTIVATED BY ZONES 1,4 OR 8WHEN IN ALARM OR I/P's 1,3 OR 7 OF THE I/P BOARD ARE ON
TURN OFF2,3,5,6,7
TURN ON1,3&7
ON
OFF
MENU
ENTER UPDATE MENUMENU
ENTER
TO EDIT DISPLAYTEXT USE
SELECTZONEMENU
ENTER
TO MOVE THROUGH THE
ALPHABET / NUMBERS
TO MOVE THROUGH
THE WORD
MENU
ENTER
EDITTEXT
UPDATE MENUMENU
ENTER
Programming the Relays and Sounders to be Activated by Zones and Editing Text
CN 5
CN10
CN 1
CN 3
CN 2
CN 4
Address SW
1 2 3 4
ON
Set to 1
EOL Not Used
RELAY BOARDMAIN CARD
CN 1
CN 3
CN 2
CN 4
Address SW
1 2 3 4
ON
Set to 1
EOL Not Used
INPUT BOARD
CN 1
CN 2
TB3
Address SW
1 2 3 4
ON
Set to 1
EOL LINKINSERTEDIN LASTBOARD OFTHE CHAIN
SOUNDERBOARD
+-
+++++-----
RS485 and 27V Cabling for the Installation of a Relay, Input and Sounder Board as in the SYSTEM and
PROGRAMMING Menu Structures Above
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
24/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 22
7 Status and Programming Screens
The following shows all the screens that are possible in the FACP and how to navigate throughthem. I f a screen is not available it means that option has not been installed or is not available tothe model in use.
Operating Main Menu
LEVEL 1 LEVEL 2 LEVEL 3
STATUS FAULTS TEST DISABLE SYSTEM PROGRAMMING
7.1 Level 1 to 3 Status Screens
SOFTWAREVER E1.2
STATUS
OUTPUTS BRIGADE RELAYS FIRE FAN AGENT SOUNDERS INPUT VOLTAGE
ALARM 1OFF/NORM
ALARM 2OFF/NORM
ALARM 3OFF/NORM
ALARM 4OFF/NORM
FIREOFF/NORM
FAULTOFF/NORM
ANC OUTOFF/NORM
ALARM 1OFF / ON
FAULTOFF / ON
DISABLEOFF / ON
BATT FAILOFF / ON
ALARM 2OFF / ON
RELAY 1OFF / ON
RELAY 2OFF / ON
RELAY 3OFF / ON
RELAY 4OFF / ON
RELAY 5OFF / ON
RELAY 6OFF / ON
RELAY 7OFF / ON
RELAY 8OFF / ON
FAN 1OFF / ON
FAN 2OFF / ON
FAN 3OFF / ON
FAN 4OFF / ON
AGENTOFF/NORM
SNDR 1OFF/NORM
SNDR 2OFF/NORM
SNDR 3OFF/NORM
SNDR 4OFF/NORM
SNDR 5OFF/NORM
SNDR 6OFF/NORM
SNDR 7OFF/NORM
SNDR 8OFF/NORM
INPUT 1OFF / ON
INPUT 2OFF / ON
INPUT 3OFF / ON
INPUT 4OFF / ON
INPUT 5OFF / ON
INPUT 6OFF / ON
INPUT 7OFF / ON
INPUT 8OFF / ON
BATT V26.8V
CHRGR V27.0V
SYSTEM V27.0V
MENU
ENTER
MENU
ENTER
MENU
ENTER
MENU
ENTER
MENU
ENTERMENU
ENTERMENU
ENTER
MENU
ENTERMENU
ENTER
MENU
ENTER
LEGEND:PRESS ENTER
PRESS MOVE FORWARDTHROUGH THE MENU
PRESS: MOVE FORWARDOR BACKWARDTHROUGH THE MENU
CANCELPRESS CANCEL ATANY TIME TO BACKOUT OF THE MENU
CANCEL
MENU
ENTER
PRESS THESE KEYSTO SET YES / NO, OFF / ON,OFF NORMAL
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
25/28
Installation & Commissioning of Control & Monitoring Add Ons
Page: 23
7.2 Level 3 System Programming
ALARMYES / NO
RESOUND
YES / NOBUZZERSYSTEM
EARTH MONYES / NO
BRIGADEYES / NO
FIRE FANYES / NO
RELAYSYES/ NO
AGENTYES / NO
SOUNDERSYES / NO
SW INDICYES / NO
INDICATEYES / NO
INPUTSYES / NO
MIMIC0 TO 8
CODEEN54
MENU
ENTER
LEGEND:
PRESS ENTER TO ACCESSMENU AND UPDATE PROGRAMOR CHANGE MENU
PRESS MOVE FORWARDTHROUGH THE MENU
PRESS: MOVE FORWARDOR BACKWARDTHROUGH THE MENU
CANCELPRESS CANCEL ATANY TIME TO BACKOUT OF THE MENU
MENU
ENTERMENU
ENTER
MENU
ENTER
CANCEL
MENU
ENTER
PRESS THESE KEYSTO SET YES / NO
YES
MENU
ENTERUPDATE PROGRAM
FACTORY SETCAN NOT BECHANGED
EXAMPLESET RESOUND TO YESTHEN MOVE TO ALARM
MOVE TO ALARMYES / NO
NOTES:TO ADD OR DELTEFROM THE SYSTEM SETTO YES OR NO AND THEN
GO TO THE PROGRAMMENU TO SET THEOPERATIONALPARAMETERSIF THESE OPTIONSARE NOT SET TO YESTHEY WILL NOT APPEARIN THE TEST, STATUS ORPROGRAM MENU
ENTERPASSWORD
FACTORY DEFAULTPASSWORD IS 3333
PASSWORD0000
MENU
ENTER
PASSWORD0100
PASSWORD0120
PASSWORD0123
MENU
ENTER
PASSWORDACCEPTED
EXAMPLE OFSETTING
PASSWORD0123
SYSTEM
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
26/28
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
27/28
-
8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm
28/28
Installation & Commissioning of Control & Monitoring Add Ons
UNCONTROLLED DOCUMENT
NOTE: Due to Ampacs commitment to continuous improvement specifications may change without notice.
AUSTRALIAAMPAC TECHNOLOGIES PTY LTD
97 Walters DriveOsborne Park 6017Western Australia
Tel: 61 8 9242 3333Fax: 61 8 9242 3334
Email: [email protected]
EUROPEAMPAC EUROPE LTD.
Unit 1, Norden Court,Alan Ramsbottom Way
Great Harwood, BlackburnEngland BB6 7UR
Tel: 44 (0) 1254 880 201Fax: 44 (0) 1254 880 202Email: [email protected]