  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    1/28

    MAN 2512 Rev: October 2005

    ZoneSense

    FI RE

    ZONE 1

    ZON E2

    ZONE3

    ZONE 4

    ZO NE 5

    ZONE 6

    ZONE 7

    ZONE 8

    FAULT/ DISABLED/TEST

    CANC EL

    MENUIEN TER

    SYSTEM STATUS

    POWER

    POWER FAULT

    SYSTEM FAULT

    EARTH FAULT

    FAULTOUPUTSTATUS

    ANCILLARYOUTPUTDISABLED

    FIRE OUTPUTSTATUS

    TEST

    AMPAC

    SYSTEM IS NORMAL

    ALARMSDELAY

    ACTIVEFIRE FAULT

    FIRE OUTPUTONALARMS STATUS

    DISABLED

    NORMAL ENABLE

    EVACUATERE S E TSILENCE

    BUZZER

    SILENCE

    RE S OUNDOVERRIDE

    FFFiiirrreee AAAlllaaarrrmmm CCCooonnntttrrrooolll PPPaaannneeelll

    EEENNN555444 222 &&& 444 111999999777

    Our aim is to provide Consistently Excellent Service in the eyes of our customers

    Installation &Commissioning

    of

    Control & MonitoringAdd Ons

    PLUS

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    2/28

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    3/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page 1

    Table of Contents Page No.

    1 About This Manual...............................................................................................21.1 Purpose ...............................................................................................................21.2 Scope...................................................................................................................21.3 References ..........................................................................................................21.4 PCB Removal / Replacement.............................................................................3

    2 Wiring to the Main Card BRD25MCB ................................................................. 32.1 Communications ................................................................................................3

    3 Adding Control and Monitoring Facilities ......................................................... 43.1 Internal Communications Connector (RS485).................................................43.2

    Programming ......................................................................................................4

    4 Installation and Wiring of Add On Cards and Boards...................................... 44.1 Address Setting and Terminating the Communications Bus ........................54.2 Input Board BRD25SIPB ....................................................................................64.3 Relay Board BRD25EWRB.................................................................................64.4 Fire Fan Module BRD25FCB..............................................................................74.5 Fan Termination Board BRD25FTB..................................................................84.6 General Indicator Card BRD25GIB -A...............................................................84.7 Switch and Indicator Card BRD25GIB - B ........................................................94.8 Zone Mimic Indicator Card ( Int. Pwr. ) BRD25GIB -C.....................................94.9 Zone Mimic Indicator Card ( Externally Powered. ) BRD25GIB -C ..............104.10 LED Annunciator Master ( LAM ) BRD25GIB - E ...........................................104.11 Sounder Board BRD25SOPB -A......................................................................11

    5 Agent Release.................................................................................................... 115.1 Operation...........................................................................................................115.2 Agent Release Module BRD25ARB - A...........................................................145.3 Local Control Station BRD25ARB - B.............................................................155.4 Common Agent Release Module and Local Control Station Indicators.....165.5 Agent Release Termination Board BRD25ATB .............................................175.6 Interface Wiring ................................................................................................18

    6 Appendix: Adding to the System Menu & Programming...............................207 Status and Programming Screens................................................................... 22

    7.1 Level 1 to 3 Status Screens.............................................................................227.2 Level 3 System Programming .........................................................................237.3 Level 3 Programming Menu.............................................................................24

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    4/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 2

    1 About This Manual

    1.1 PurposeThis manual is an instructional tool for the installation and commissioning, of add on ancillary

    cards, modules and boards that can be fitted to the ZoneSense PLUSFire Alarm Control Panel(FACP) and should be read in conjunction with the main Installation and Commissioning Manual.

    1.2 ScopeThe information within this manual is only available to and for the use of personnel engaged in

    the installation and operation of theZoneSense PLUSFACP.

    ZoneSense PLUS has been designed to comply with major world standards. To ensure thesestandards are not compromised in any way installation staff and operators should;

    1. be qualified and trained for the task/s they undertake;

    2. be aware this manual should be read prior to the installation and commissioning of theZoneSense PLUSFACP;

    3. observe anti-static pre-cautions at all times; and

    4. if a problem is encountered or there is any doubt with respect to the operational parametersof the installation the supplier should be contacted.

    1.3 References

    ZoneSense PLUSTechnical ManualZoneSense PLUSOperation &Programming ManualZoneSense PLUSInstallation and Commissioning ManualApollo Detector / Device ManualsAmpac Product Data SheetsBritish Standard EN54 Parts 2 & 4European Standard BS 5839

    FIRE

    ZONE 1

    ZONE 2

    ZONE 3

    ZONE 4

    ZONE 5

    Z ONE 6

    ZONE 7

    ZONE 8

    FAULT / D ISABLED/TEST

    CANCEL

    MENU

    IENTE R

    SYSTEM STATUS

    POWER

    POWER FAULT

    SYSTEM FAULT

    EARTH FAULT FAULT OUPUTFAULT/DISABLED

    ANCILLARYOUTPUTDIS ABLED

    ALARMS/FAULTDISABLED

    TESTAMPAC

    SYSTEM IS NORMAL

    ALARMSDELAY FIRE FAULT

    FIR E OUTPUT O N FIR E PUTPUTFAULT/ DISABLED

    DISABLED

    NORMAL ENABLE

    EVACUATERESETSILENCEBUZZER

    SILENCERESOUNDOVERRIDE

    Figure 1: Examples of the ABS, Metal Cabinet and Metal Cabinet with Battery Box

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    5/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 3

    1.4 PCB Removal / Replacement

    If the PCBs have to be removed the following precautions should be observed;

    1. Removing the door will provide better access to the boards and ensure the hinges arenot accidentally stressed.

    2. Personal anti- static procedures must be followed.

    3. When disconnecting the telecom style connecting cable from the PCB, make sure thatthe cable remains connected to at least one board to prevent it being misplaced.

    Note: Care should be taken when detaching this connector as it is necessary to depress thesmall locking tab to unlock the connector from itsbase. To reconnect the cable the connector must firstbe correctly aligned then pushed into the socket so itlocks into position.

    4. Carefully remove the retaining screws at each

    corner of the board taking care not to damageany of the components.

    5. Place each board into anti- static storage once removed.

    2 Wiring to the Main Card BRD25MCB

    2.1 Communications

    External Communications Terminals (RS485) TB2 1, 2 & 3The RS 485 output drives the remote cards and mimics up to a distance of 1.2km from the panelitself. The external cabling (2x2 shielded pair plus power) is wired to TB2 +, - and earth.

    Note: If a fault occurs on the communications line the common FAULT and SYSTEM FAULTLEDS will be illuminated. The fault details can be displayed by selecting the Faults Menu.

    Remote CardsThe number of cards that can be installed on the external communications bus are:

    8 x Remote LED Mimics. 1 x 8 Way Remote Relay Output Board. This board provides 8 sets of normally open

    (NO), normally closed ( NC ) and Common ( C ) voltage free contacts rated at 1A @30V.

    Main Card Comms Link K1K1 MUST be inserted when only the front door panel cards and the Main Card are used as anFACP. If this is not the case and TB2 is cabled to LED mimics and / or 8 Way Remote Relay

    Boards a link is inserted in the last board to complete the communication circuit orif boards aremounted on the back pan and communications are wired from the Main Card then the last boardin this chain MUST be terminated.

    K1

    Comms + -Comms Link

    TB2

    Top Left Hand Cornerof the Main Board

    To LED Mimics and/orRemote Relay Boards

    TB3

    SP C/C ALT

    Spare I/P

    Class Change I/P

    Alert I/P

    Inputs

    RS485 Com 1 2 3

    Note:the shield iswired to

    Shield

    Figure 2: Wiring Detail

    Push Tab Inwardsand Gently Pullthe ConnectorFrom the Socket

    Connector

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    6/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 4

    3 Adding Control and Monitoring Facilities

    A combination ofone of each type of board / card, but not all of them, can be mounted on theback pan or the front panel of the FACP to provide additional features to a standard panel. Allboard inputs or outputs are programmable to any combination of zones.

    Relay Board, BRD25EWRB A or with a change of on board components it canalso be installed remotely on the external communications bus as a RemoteRelay Board BRD25EWRB -B

    Input Board BRD25SIPB -. Sounder Board BRD25SOPB. Brigade Interface Board BRD25BBA. Fire Fan Module consists of a Termination Board ( BRD25FTB and front panel

    card BRD25FCB -. Agent Release Module consists of a Termination Board ( BRD25ATB ), front

    panel card ( BRD25ARBA ) and if required a remote local control station(BRD25ARBB).

    General Indicator Card. BRD25GIB -A Switch and Indicator Card BRD25GIBA Zone Mimic Indicator Card ( Internal Power ) BRD25GIB -C Zone Mimic Indicator Card (External Power normally remote) BRD25GIB -D

    Note: To add or remove Cards from the FACP programming go to the SYSTEM Menu.3.1 Internal Communications Connector (RS485)PCB mounted connectors provide serial communications to internal ancillary boards. CN9 on theMain Card cables to CN1 or 2 on the front panel boards and CN5 on the Main Card cables toCN1 or 2 on the back pan boards

    3.2 ProgrammingRefer to the Operation and Programming Manual to program the above options into the FACP.

    Note: The Configuration label should be updated once the panel has been upgraded.

    4 Installation and Wiring of Add On Cards and Boards

    CAB1925 to Batteries

    CAB1902

    CAB1905

    CAB1911 TO MAINS EARTH

    CN1CN2 CN2 CN1ALARM2

    N/CCOMN/0BATTFAIL

    N/CCOMN/0ISOLATE

    N/CCOMN/0FAULT

    N/CCOMN/0ALARM1

    N/CCOMN/0

    TB1-TB5

    POWER

    0V

    +27V

    0V

    +27V

    CN2

    CN1

    CN3CN4

    POWER

    +27V

    0V

    CN1

    CN2

    +27v Power fitted when Relay or Termination Boards are fitted

    CN1

    CN2

    CN5

    CN9

    CN1CN2CN2 CN1

    CAB2200 CAB2117

    CAB1905

    CAB2200

    CN6

    POWER

    +27V

    0V

    CN1

    CN2

    POWER

    +27V

    0V

    CN1

    CN2

    MAIN CONTROL CARD

    OPTIONAL CARDSAGENT RELEASEFAN CONTROLGENERAL INDICATOR

    OPTIONAL BOARDSAGENT TERMINATIONRELAYFAN TERMINATIONINPUTSOUNDER TERMINATION

    A BATT BOX IS REQIF THESE BRDS ARE FITTED

    OTIONALBRIGADE BOARD

    CAB2200

    CAB2200

    BRD25ARB PCB0783 (AGENT RELEASE MODULE)BRD25ATB PCB0787 (AGENT TERMINATION BOARD)BRD25BBA PCB0779 (BRIGADE BOARD)BRD25EWRB PCB0770 (8 WAY RELAY BOARD)BRD25FCB PCB0783 (FIRE FAN MODULE )

    BRD25FTB PCB0780 (FAN TERMINATION BOARD)

    PSU1887

    CN3

    CN4

    CN3 CN4

    CN3

    CN4

    BRD25GIB PCB0781 (GENERAL INDICATOR CARD)BRD25MCB PCB0769 (MAIN CONTROL CARD)BRD25PSU PCB0813 (POWER SUPPLY UNIT)BRD25SIPB PCB0778 (SINGLE INPUT BOARD)BRD25SOPB PCB0772 (SOUNDER OUTPUT BOARD)

    OPTIONAL CARDSAGENT RELEASEFAN CONTROLGENERAL INDICATOR

    OPTIONAL BOARDSAGENT TERMINATIONRELAYFAN TERMINATIONINPUTSOUNDER TERMINATION

    A BATT BOX IS REQIF THESE BRDS ARE FITTED

    OPTIONAL BOARDSAGENT TERMINATIONRELAYFAN TERMINATIONINPUTSOUNDER TERMINATION

    A BATT BOX IS REQIF THESE BRDS ARE FITTEDBUS 1

    BUS 2

    BUS 3

    BOARDIDENTIFIERS:

    CN8

    CN10

    Figure 3: Typical Wiring, Ancillary Card and Board Positioning Within the ABS FACP

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    7/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 5

    4.1 Address Setting and Terminating the Communications Bus

    Address Setting ( SW1 )

    Except for the LED Mimics in ZoneSense PLUSFACPs there can only be one (1) Board / Card of

    each type so the address on each board is set to 1.

    Note: There can be up to 8 remote LED Mimics so the address of each is set from 1-8 dependingon the number Mimics in the system. The information displayed at each location will be identical.

    DIL Switch: ON = 1, OFF = 0Address 1234 Address 123401 1000 05 101002 0100 06 011003 1100 07 111004 0010 08 0001

    Figure 4:Address Table & Example of Switch ( SW1 ) Set to 1

    Terminating the Communications BusLK1 is the EOL Link and must be inserted on the last board on each communications bus. If not,a communications fault can occur.

    TB2

    K1

    Shield

    CN 5

    CN 9Front Panel

    Card 1Front Panel

    Card 2

    BackpanBRD 1

    BackpanBRD 2

    INSERTLK1

    RemoteCard 1

    RemoteCard 2

    LCS 1 LCS 2

    INSERTLK1

    INSERT

    LK1

    INSERTLK1

    If Agent Release is fitted to the FACP there will be an Agent Termination Board mounted on the Backpan.Local Control Stations can then be fitted at some location remote from the FACP. These LCS's communicatewith the ATB via a second RS485 bus hence the last LCS in the chain will have to be terminated

    Note: If Backpan boards AND remote facilitiesare fitted the front panel cards are not terminated

    ToTB1 Agent Termination Board

    Fit K1 if only theMain ControlCard is used asthe FACP or1 Bus is used

    RS485 +-

    BUS 1 ( B1 )

    BUS 2 ( B2 )

    BUS 3 ( B 3)

    ( Link 1 in Table below )

    ( Link 2 in Table below )

    ( Link 3 in Table below )

    BUS 4 ( B 4)Fit LK1 to last LCS

    Figure 5: RS485 Communication Bus Terminating

    Linking TableLink Bus Configuration

    B1 B1,2 B1,3 B1,2,3 B,2 B2,3 B31 X & K1 X X

    2 X X X & K1 X

    3 X X X X & K1

    X = Insert LinkB1: Bus 1 to Front Panel CardsB2: Bus 2 to Backpan BoardsB3: Bus 3 to Remote facilitiesB4: Bus 4 Local Control Station cabled to the backpan Agent Release Board.

    Note: Programming and the communication process allows the Main Card to identify the type ofboard it is communicating with.

    1 2 3 4

    On

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    8/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 6

    4.2 Input Board BRD25SIPB

    DescriptionThe Input Board makes provision for 16 voltage free contacts to be terminated to 16 opticallycoupled inputs. Its application is primarily for the monitoring of controlled ancillary equipment or toinitiate an action / event due to a change of state from what is accepted as the norm.

    ConnectorsCN1 Is designated as the input Comms .CN2 Is designated as the output Comms to the next board.CN3 27 Volts into the Board. Quiescent Current:2.6mACN4 27 Volts to the next Board unless it is the last board in the chain then it is left empty.

    Terminal BlocksTB 2 9 Taking note of the Common 0v terminals connect the voltage free contacts as shown

    below. Note: only the first 8 are functionally programmable in ZoneSense PLUS

    SW1 There can only be 1 Input Board so the address on each board is set to 1.

    LK1 Is the EOL Link and is inserted should the board be the last in the chain. If notinserted on the last board the Main Card will initiate a communications fault.

    SW1

    LK1 EOL Termination Address SWSET to 1

    INPUTS1 2 3 4 0V INPUTS5 6 7 8 0V INPUTS9 10 11 12 0V INPUTS13 14 15 16 0V0V

    16 Inputs are Voltage Free Contacts

    27 VIn

    27V To CN3 of Next Board

    TB9TB8TB7TB6TB5TB4TB3

    RS485 Control In From CN2 of thePrevious Board or CN5 of the Main Card

    RS485 Control Out to NextBoard or Link 1 EOL is Applied

    CN2

    CN1

    CN3 CN4

    TB2

    1 2 3 4

    ONON

    Inputs

    1 2 3 4

    0V Inputs

    5 6 7 8

    0V Inputs

    9 10 11 12

    0V Inputs

    13 14 15 16

    0V0V

    16 Inputs are Voltage Free Contacts

    TB9TB8TB7TB6TB5TB4TB3TB2

    8= 0 Volts = Input

    +-

    #1. 27 Volts In from CN10 on the Main Card or CN4 of the previous internal board.

    #2. Select an appropriate length cable from those supplied to connect Comms & 27V.

    Note: Only the first 8 Voltage Free Contacts are functionally programable.The second 8 can be used to independently drive LEDs 8 to 16 on theGeneral Indicator Board.

    Figure 6: Typical Input Wiring and Board Layout

    4.3 Relay Board BRD25EWRB

    Relay Board ( Internal ) BRD25EWRB -A

    The Relay Board has provision for 8 X 1 Amp voltage free change over contacts for control ormonitoring purposes. Communication and control cabling is the same as all other internal boards.

    Quiescent Current:2.4mA

    LK1 EOL Termination

    Address SWSET to 1

    27 VIn

    27V To CN3 of Next Board

    RS485 Control In From CN2 of thePrevious Board or CN5 of the Main Card

    RS485 Control Out to NextBoard or Link 1 EOL is Applied

    CN2

    CN 1

    CN3 CN4 ON+-

    #1. 27 Volts In from CN10 on the Main Card or CN4 of the previous internal board.

    #2. Select an appropriate length cable from those supplied to connect Comms & 27V.

    TB8TB7TB6TB5TB4TB3TB2TB1

    SW 1

    O/P 8N/CCOMN/0

    O/P 7N/CCOMN/0

    O/P 6N/CCOMN/0

    O/P 5N/CCOMN/0

    O/P 4N/CCOMN/0

    O/P 3N/CCOMN/0

    O/P 2N/CCOMN/0

    O/P 1N/CCOMN/0

    1 2 3 4

    ON

    TB8TB7TB6TB5TB4TB3TB2TB1

    O/P 8N/CCOMN/0

    O/P 7N/CCOMN/0

    O/P 6N/CCOMN/0

    O/P 5N/CCOMN/0

    O/P 4N/CCOMN/0

    O/P 3N/CCOMN/0

    O/P 2N/CCOMN/0

    O/P 1

    N/C

    COM

    N/0

    N/0 = Normally Open

    COM = Common

    N/C = Normally Closed

    Figure 7: Board Layout

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    9/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 7

    Relay Board ( Remote ) BRD25EWRB - B

    In the remote version the Comms In and Out Terminal Block TB9 is cabled to the RS 485 Commsterminal block TB3 on the Main Card 302 7690 or LED Mimic and can be installed up to 1.2kmsfrom the FACP.

    Note#1: This version can be powered from the panel or an external 27 volt source due to the onboard switched mode supply. Quiescent Current of both boards is 16mA

    Note#2: In a system there can only be either a remote OR an internal board, not both.

    Figure 8: Remote Relay Board Layout

    4.4 Fire Fan Module BRD25FCB

    The Fire Fan Module has four ( 4 ) separate fan controls each having an On, Auto and Offfunction switch and a set of three (3) monitoring LEDs. The LEDs indicate the status of theequipment eg. Run, Fault or Stop. The two ( 2 ) arrow head keys are used to step up and / ordown through the three ( 3 ) conditions. A slip in label can also be inserted into the hinged coverfor identification purposes.

    Quiescent Current: 13.5mA

    Slip In

    Label

    Card & PCB Securing Tabs( Top & Bottom )

    PCB

    ClearPlasticClipInLabel

    Clip OnPlastic Surround( Push down here and pullout to remove and insert labels )

    WINDOWS

    WINDOWS

    FOR SLIP

    IN LABELS

    Lettering on slip inlabels must be atleast 5mm in height.

    K2 Termination Link

    In Out

    Address

    SwitchSet to 1

    1

    2

    3

    4

    ONCN1

    CN2

    CN1: Communications & 27V IN from CN2 off the previousFront Panel Card or CN9 on the Main Card

    CN2: Communications & 27V OUT to Next Front Panel Card.If Unsed the Termination Link Must be Inserted.

    Top Front Card &PCB Securing Clips

    Bottom Front Card &PCB Securing Clips

    Figure 9: Fire Fan Module Front Panel Figure 10: Fire Fan Module PCB Layout

    U4

    CN 3

    CH4

    RL8RL7RL6RL5RL4RL3RL2RL1

    X1

    U5

    U3

    U2

    U1

    TB8TB7TB6TB5

    TB9

    TB4TB 3TB2TB1

    LK1

    HY1 U6

    SW1

    M10

    TB10

    0V0V +27VDC+27VDC

    EXTERNALPOWER

    rev.1

    EC3AW

    A B COM

    EOL Termination

    ///

    N O N C

    C

    ///

    N O N C

    CC

    NCNO

    ///

    C

    NCNO

    //////

    N O N C

    C

    CN

    C

    NO

    ///

    ///

    NO

    NC

    C///

    NO

    NC

    C

    O/P 8N/CCOMN/0

    O/P 7N/CCOMN/0

    O/P 6N/CCOMN/0

    O/P 5N/CCOMN/0

    O/P 4N/CCOMN/0

    O/P 3N/CCOMN/0

    O/P 2N/CCOMN/0

    O/P 1N/CCOMN/0

    TB1-TB8

    A B COM

    COMMS IN / OUT Address SW

    To TB3 on the MainCard and/or LED MimicIn Out

    27V

    1 2 3 4

    ON

    Contact Legend:N/O = Normally OpenN/C = Normally ClosedC = Common

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    10/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 8

    4.5 Fan Termination Board BRD25FTB

    The Fan Termination Board interfaces between the Fire Fan Module and the plant/equipment itcontrols via the 24 volt 250mA Start, Stop, current limited, relay outputs and monitor inputs.Programmable monitoring of the field equipment is achieved using 0 volts as an input level toindicate run, fault and stop conditions of that equipment. Monitoring is programmed in theFunction Menu for a 3, 4 or 5 Wire Start / Stop, Run, Fault, Stop & Common functions. The inputsare protected by way of resetable transorbs and resistive / capacitive networks.

    Quiescent Current: 6.5mA

    ConnectorsCN1 RS485 Control IN from previous board or Main CardCN2 RS485 Control OUT to next board or LK1 EOL termination is appliedCN3 27 VDC IN from CN10 of the Main Card or CN4 of the previous boardCN4 27 VDC OUT

    Terminal BlocksTB2 5 Are used to connect the fan control and monitoring wiring to the board.

    SW1

    TB4TB3TB2

    LK1

    TB5

    EOL Termination

    0V+27V

    POWER

    Address SW

    FAN 1FAN 1STOP COMSTOPFLTRUN

    FAN 2STOP COMSTOPFLTRUNSTART

    FAN3FAN 3STOP COMSTOPFLTRUNSTART

    FAN 4COMSTOPFLTRUNSTART

    FAN4STOPSTART

    FAN 2

    CN1

    CN2

    CN3 CN4

    RS485 Control in from CN2 of Previous Board or CN5 of the Main Card

    RS485 Control Out to Next Board or Link 1 EOL is Applied

    27V In from CN 10 on the Main Card or CN4 of the Previous Board

    27V Out to Next Board if Applicable

    1 2 3 4

    ON

    STOP

    COM

    STOP

    FLT

    RUN

    START

    TB 2, 3, 4 or 5

    Cabling from FACPto Plant / Equipment

    1 2 3 4 5 6

    FAN CONTROLSOLID STATE ORRELAY INTERFACE

    FAN MONITORING

    0VINPUTS 1, 2 & 3+24V O/Ps

    RUN

    Figure 11: Fan Termination Board Layout and Typical I/O Wiring

    4.6 General Indicator Card BRD25GIB -A

    IMPORTANT

    Note: The Cards BRD25GIB A, B, C and D all have a common PCB. What sets them apart fromeach other is not only the function they perform but how the componentry is loaded onto the cardto perform that function.

    This Card indicates / displays the status of the inputs on the 16 Way Input Termination Board byway of Program selectable tri-coloured LEDs with its function being identified on the front panelby slip in labels.

    Quiescent Current: 3 to 3.5mA depending on the application

    Card & PCB Securing Tabs( Top & Bottom )

    PCB

    Clip OnPlastic Surround( Push down here and pull

    out to remove and insert labels )

    Lettering on slip inlabels must be atleast 5mm in height.

    WindowsforSlip in Label

    Slip In Label

    K2 TerminationLink

    In Out

    AddressSwitchSet to 1

    1

    2

    3

    4

    ON

    CN1

    CN2

    CN1: Communications & 27V INfrom CN2 off the previous FrontPanel Card or CN9 on the Main Card

    CN2: Communications & 27V OUT to Next Front Panel Card.If Unsed the Termination Link Must be Inserted.

    Top Front Card &PCB Securing Clips

    Bottom Front Card &PCB Securing Clips

    Figure 12: Front Panel Card Layout Figure 13: Front Panel Card & PCB Layout

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    11/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 9

    4.7 Switch and Indicator Card BRD25GIB - BThis Card can effectively perform 2 different functions. Firstly the indicators monitor the first 8inputs of the 16 Way Input Termination Board while secondly the switches can be programmed tomanually operate a specific relay in the system.

    Quiescent Current:3.6mA

    Card & PCB Securing Tabs( Top & Bottom )

    PCBClearPlasticClipInLabel

    Clip onPlastic Surround( Push down here and pull

    out to remove and insert labels )

    Note: As per AS 1668lettering on any of theslip in labels must beat least 5mm in height.

    WindowsforSlip inLabel

    Slip In Label

    WINDOWS FORSLIP IN LABEL

    K2 TerminationLink

    In Out

    AddressSwitch

    Set to 1

    1

    2

    3

    4

    ON

    CN1

    CN2

    CN1: Communications & 27V INfrom CN2 off the previous FrontPanel Card or CN9 on the Main Card

    CN2: Communications & 27V OUT to Next Front Panel Card.If Unsed the Termination Link Must be Inserted.

    Top Front Panel Card &PCB Securing Clips

    Bottom Front Panel Card &

    PCB Securing Clips

    Figure 14: Front Panel Card & PCB Layout

    4.8 Zone Mimic Indicator Card ( Int. Pwr. ) BRD25GIB -C

    The internally powered Zone Mimic Indicator Card connects to the FACP 27 volt power supplyand the internal communications bus for indication control. The card provides remote visualindication of any Zone in an Alarm and / or Fault / Isolate condition. A maximum of 8 of thesecards can be connected to, or daisy chained together, on any one system. Slip in labels identifythe monitored Zone. The Alarm LEDs flash for an un acknowledged alarm and are steady foracknowledged. The Fault / Isolate LEDs flash for a Fault condition and are steady if a Zone isIsolated.

    Quiescent Current:14mA

    Card & PCB Securing Tabs( Top & Bottom )

    Clip OnPlastic Surround( Push down here and pullout to remove and insert labels )

    Lettering on slip inlabels must be at

    least 5mm in height.

    Slip In Label

    PCB

    AlarmIsolateFault

    Windows for

    Slip in Label

    K2 TerminationLink

    In Out

    AddressSwitchSet to 1

    1

    2

    3

    4

    ON

    CN1

    CN2

    CN1: Communications & 27V INfrom CN2 off the previous FrontPanel Card or CN9 on the Main Card

    CN2: Communications & 27V OUT to Next Front Panel Card.If Unsed the Termination Link Must be Inserted.

    Top Front Panel Card &PCB Securing Clips

    Bottom Front Panel Card &PCB Securing Clips

    Figure 15: Front Panel Card & PCB Layout

    Note: Except for CN1 & 2 being fitted and TB1, HY1 the Buzzer and CN6 not being fitted theunderside of this card is the same as for the externally powered card.

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    12/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 10

    4.9 Zone Mimic Indicator Card ( Externally Powered. ) BRD25GIB -C

    The externally powered Zone Mimic Indicator Card operates in the same way as does theinternally powered version. The only difference is that the 27 volt power supply is independent ofthe FACP. This card would be used when the distance involved causes a significant voltage dropsuch that it may effect the reliable operation of the system or the costs involved in the cable is

    offset by the availability of a remote 27 volt supply.

    Quiescent Current:13mA ( This current applies to both cards )

    Figure 16: PCB Front Layout Figure 17: Underside of PCB

    4.10 LED Annunciator Master ( LAM ) BRD25GIB - E

    The LAM provides remote stand alone FACP status, Alarm and Fault / Isolate Indication of 8zones. Two push buttons, Lamp Test and Silence Buzzer, provide for local testing of theindicators and buzzer while the buzzer duplicates that at the FACP. A maximum of 4 LAMs withaddresses of 1 to 4 may be cabled to an FACP.

    Card & PCB Securing Tabs ( Top & Bottom )

    Lettering on slip inlabel must be atleast 5mm in height.

    Slip In Label

    PCB

    AlarmDisableFault

    Windows for

    Slip in LabelFIRE

    FAULT

    DISABLED

    ALARMS STATUS

    FIRE OUTPUT STATUS

    TEST

    DELAYACTIVE

    POWER

    LAMP

    TEST

    SILENCE

    BUZZER

    FIRE

    FAULT/DISABLED

    Release of the Clip On Surround( Metal Cabinet: Push down here and pull out to remove and insert label.ABS Cabinet: At the top RH cornner of the surround insert the surround removaltool between it and the front panel then slide along the surround to release)

    PWR OUT

    PWR IN

    +

    0V

    +24V

    CO M

    -RS485 OUT TO NEXT LAM( IF APPLICABLE )

    INPUTMUTE

    BUZZER

    LK1TERMINATION LINK

    SWITCHADDRESS

    CN 6

    O

    N

    1

    2

    3

    4

    0V

    +24V

    +

    CO M

    - RS485 COMMS IN FROM FACP OR PREVIOUS LAM

    ON

    1

    2

    3

    4

    ON

    1

    2

    3

    4

    ON

    1

    2

    3

    4

    ON

    1

    2

    3

    4

    LAM4

    LAM3

    LAM2

    LAM1

    LINK IS INSERTED ON THELAST CARD IN THE CHAIN

    LAM 1 - 4ADDRESSSETTING

    Figure 18: LAM Front Panel and PCB Layout

    TB1

    SW13

    HY13V3 Supply Buzzer BZ1

    CN6

    0V

    +

    0V

    +

    BuzzerMuteInput

    AddressSwitch

    EC3AW

    RS 485In

    CO M

    RS 485Out -

    CO M

    +

    -

    +

    TerminationLink K2

    27VIn

    27VOut

    1

    2

    3

    4

    ON

    +

    D17

    D18

    D19

    D20

    D1

    D2

    D3

    D4

    D5

    D6

    D7

    D8

    D9

    D10

    D11

    D12

    D13

    D14

    D15

    D16

    D21

    D22

    D23

    D24

    D25

    D26

    D27

    D28

    D29

    D30

    D31

    D32

    U1

    U2

    U3

    U4U5

    U6

    U7

    U8

    X1

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    13/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 11

    4.11 Sounder Board BRD25SOPB -A

    The Sounder Board expands the number of sounders that can be used on an FACP to 8. Each

    solid state output is rated at 24VDC / 500mA. and requires a 10K End of Line (EOL) resistorregardless whether or not a sounder is wired to the circuit.

    Quiescent Current: 5.6mA Maximum Current per Output: 500mA

    Figure 19: Wiring Detail & PCB Layout

    Note: Sounder polarity MUST be observed.5 Agent Release

    Control consists of the FACP Agent Release Module and Termination Board. Should control berequired at a point remote from the FACP an Agent Release Local Control Station can beincorporated .

    5.1 Operation

    IntroductionThe Agent Release Module and Termination Board communicate with the FACP via the RS485multi-drop bus.

    The Agent Release Local Control Station communicates only with the Termination Board via aseparate RS485 bus. Up to 4 Agent Release Local Control Stations can be connected to onetermination board.

    The Agent Release Module operates in three modes;1. Automatic/Manual;2. Manual Only; and3. Disable.

    The mode is selected by operating the keyswitch switch on either or module.

    The keyswitch at the Agent Release Module is the only keyswitch with a Disable selection andhas the highest priority. Hence when the keyswitch is in the Disable position all other keyswitches

    are ignored and the agent control system is in the Disabled mode.

    Next priority is Manual Only. If any keyswitch is in Manual Only (providing the keyswitch at theAgent Release Module is NOT in Disable), then the board is in the Manual Only mode.

    Finally, the system is in the Auto/Manual mode when all keyswitches are in Auto Manual.

    The pressure switch input on the termination board (which is used to confirm that the agent hasbeen released) can be configured to accept a normally open contact, normally closed contact, orignored. This is selected via the FACP on-site programming.

    TB3 TB2 TB1

    SW 1

    -VE+VESOUNDER 1

    -VE+VESOUNDER 2

    -VE+VESOUNDER 3

    -VE+VESOUNDER 4

    -VE+VESOUNDER 5

    -VE+VESOUNDER 6

    -VE+VESOUNDER 7

    -VE+VESOUNDER 8DC IN

    0V 27V

    LK1 EOLTermination

    Address SW

    POWER

    CN2

    CN1

    27V IN- +

    To Sounders 1 to 4 + / - To Sounders 5 to 8 + / -

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    :

    1 2 3 4

    ON

    TB3 TB2 TB1-VE+VE

    SOUNDER 1-VE+VE

    SOUNDER 2-VE+V E

    SOUNDER 3-VE+V E

    SOUNDER 4-VE+V E

    SOUNDER 5-VE+VE

    SOUNDER 6-VE+VE

    SOUNDER 7-VE+V E

    SOUNDER 80V 27V

    To Sounders 1 to 4 + / - To Sounders 5 to 8 + / -

    RS485 Control In From CN2 of thePrevious Board or CN5 of the Main Card

    RS485 Control Out to NextBoard or Link 1 EOL is Applied

    ONNote: Sounder polarity MUST be observed

    27V IN- +

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    14/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 12

    Disabled ModeDisabled mode is selected by placing the keyswitch at the Agent Release Module in the Disabledposition. This electrically isolates the activation circuit, and results in the following: Disabled indicators at the Agent Release Module and Local Control Station are lit. Agent Release Module and Local Control Station buzzers sound. No automatic releases can be commenced.

    System inoperative output is activated.

    Note:Disabled mode can not be overridden.Manual ModeWhen the board is in manual mode, then the Manual Only indicators at the Agent Release Module and Local Control Station are lit No automatic release sequences can be commenced. Does not interrupt a release sequence that has started System inoperative output is activatedTo manually discharge the agent, the Manual Release facility at the Agent Release Module or theLocal Control Station is activated.

    The manual release sequence is: Manual Release Activated indicators are lit on the Agent Release Module and Local

    Control Station Stage 1 outputs are switch to +24VDC. Stage 2 outputs are pulsed during the pre-release delay to +24VDC. Start optional pre-release delay. (Selected via FACP on-site programming). Upon expiration of the delay, activate the selected activation circuit and stage 2 outputs

    becomes steady Light the agent released LED on the Agent Release Module and Local Control Station

    when pressure switch input on the termination card is activated or immediately (dependson the pressure switch configuration).

    FACP to activate the FIRE output and light the FIRE LED

    The discharge sequence can be interrupted by the activation of the Hold input. Activation of theHold input prevents the release of the agent. When the Hold switch is released, the pre-releasedelay is restarted. While the Hold input is activated, the stage 2 output is switched off, and thebuzzer will sound.

    Auto/Manual ModeIn this mode, automatic and manual discharge is possible. For manual discharge see above.

    The automatic discharge sequence is initiated when one or two zones go into alarm.

    With single zone alarm activation the following discharge sequence is executed. Auto Activation indicator is lit on the Agent Release Module and Local Control Station

    Stage 1 outputs are switched to +24VDC Stage 2 outputs are pulsed during the pre-release delay to +24VDC Start optional pre-release delay (Selected via FACP on-site programming). Upon expiration of the delay, activate the selected activation circuit and stage 2 outputs

    becomes steady. If configured light the agent released LED on the Agent Release Module and Local Control

    Station when pressure switch input on the termination board is activated. FACP to activate the FIRE output and illuminate the FIRE LED. The operation of the Hold switch is as per the manual release

    With dual zone activation, if the first zone goes into alarm, then the following steps are followed; Flash the auto release activated LED at the Agent Release Module and

    Local Control Station

    Stage 1 outputs are switched to +24VDC

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    15/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 13

    When the second zone goes into alarm, then the following steps are followed Auto release activated LED on the Agent Release Module and Local Control Station goes

    steady Stage 2 outputs are pulsed during the pre-release delay to +24VDC Start optional pre-release delay. (Selected via FACP on-site programming).

    Upon expiration of the delay, activate the selected activation circuit and stage 2 outputsbecomes steady. Light the Agent Released LED on the Agent Release Module and Local Control Station

    when the pressure switch input on the termination board is activated (depends on thepressure switch configuration).

    FACP to activate the Fire output and illuminate the Fire LEDThe operation of the Hold switch is as per the Manual Release.

    Released ConditionWhen the agent has been released, and the pressure switch input has been activated, then theboard is in the released condition. The condition is shown by: Agent Released indicator is lit at the Agent Release Module and Local Control Station FACP Fire output and associated indicator is On.

    The condition remains until reset has been activated at the FACP.

    It is possible, when the agent release module is in the released condition to de-activate the Stage1 and Stage 2 outputs. This is achieved by depressing the SILENCE/RESOUND button at theFACP. This action will also silence the alarm outputs at the FACP and the sounder outputs on the8 way sounder board (if fitted). If the SILENCE/RESOUND button is depressed again to instigatethe RESOUND facility, then the stage 1 and stage 2 outputs will be re-activated (as will theonboard alarm outputs and sounder outputs on the 8 way sounder board if fitted).

    Lock-Off ValveWhen the lock-off valve is operated, the agent is blocked from reaching the release valve. Whenthe lock-off valve is operated, the following occurs: Light the Blocked Mode indicator at the Agent Release Module and Local Control Station

    Operates the system inoperative output

    Fault MonitoringThe sources of fault in the system are: Pressure switch monitoring circuit Low pressure switch monitoring circuit Lock-off valve monitoring circuit Activation circuit Stage 1 outputs Stage 2 outputs Fault in the trigger zones Fault with a Local Control Station

    Note #1: The common fault indicator on the Agent Release Module and Local Control Station isilluminated for any Fault condition.

    Note #2: For a pressure switch fault, low pressure switch fault, lock-off valve fault, stage 1output fault and stage 2 output fault the FACP will signal the brigade.

    Note #3: When there is a fault in the activation circuit or in the trigger zones, in addition to theabove, the system inoperative output is operated.

    Note #4: The FACP buzzer sounds for all faults and the LCD displays the type of fault.

    Note #5: The FACP will report the type of fault on the LCD.

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    16/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 14

    IsolationIf the trigger zones are isolated by the FACP, then the trigger zone isolated indicator at the AgentRelease Module and Local Control Station is illuminated, and the system inoperative output isoperated.

    Disablement of the Trigger Zones

    If the trigger zones are disabled by the FACP, then the isolate indicator at the FACP is illuminatedand the system inoperative output is operated.

    5.2 Agent Release Module BRD25ARB - A

    The Agent Release Module controls and monitors all the requirements for agent release andcarries the slide in label for identification of the agent and application area.

    Keyswitch

    PCB

    Manual ReleaseSwitch

    AUTO / MANUAL MANUAL ONLY

    MANUAL HOLD

    MANUAL RELEASEACTIVATED

    AUTO RELEASEACTIVATED

    RESERVE AGENT

    TRIGGER ZONEDISABLED

    INITIAL AGENT

    AGENTRELEASED

    BLOCKED MODE

    COMMON FAULT

    DISABLED

    MANUAL

    ELEASE

    R

    MANUALDISABLED

    AUTO / MANUAL

    HOLD

    AGENT SELECT

    MANUALONLY

    Figure 20: Exploded View of Module and Front Panel Layout

    Controlled AccessIt is a requirement that control be secured from unauthorised use. For this reason a key switchhas been included in the control process.

    DISABLED

    AUTO / MANUAL

    MANUALONLY

    Disabled, Manual Only, Auto/Manual Keyswitch In disabled mode theselected activation circuit is electrically isolated from the activation device, and the agent can notbe released. In manual only mode, the agent can only be released manually, and in Auto/Manualmode the agent can be released automatically or manually.

    Note:The key is removable in all positions.

    MANUAL HOLD

    Manual Hold When activated, delays the discharge of the agent. When the switchis depressed during the pre-discharge delay, the delay is restarted when the switch is released. Ifdepressed at any other time a fault is registered after a 10 second debounce time out period.

    AGENT SELECT

    Agent Select When activated, causes the selected agent to toggle between Initialand Reserve.

    MANUAL

    ELEASE

    R

    Manual Release When activated causes a manual release of the agent, providing

    the system is operative.

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    17/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 15

    Agent Release Module PCB Layout

    The PCB is fitted with two 2 x RJ45 connectors CN6 & 7 for power (27VDC) and communications(RS485) for communications between the Module and the FACP Main Card.

    Quiescent Current:28.5mA

    D10

    D9

    D14

    D13

    D12

    D11

    D6

    D5

    D4

    D3

    D8

    D7

    U4

    U1

    U2

    U3

    X1

    Select

    Manual ReleaseActivated

    Initial Agent

    Manual Hold

    Auto / Manual

    Auto ReleaseActivated

    Reserve Agent

    Trigger ZoneDisabled

    Manual Only

    AgentReleased

    Blocked Mode

    Common Fault

    Disabled

    Hold

    CutoutCutout

    SW 2

    CN 2

    TP9

    Key Switch

    AddressSwitch

    RS485&

    +/- 27vIn

    RS485&

    +/- 27vOut

    1

    2

    3

    4

    O

    NK1

    TerminationLink

    CN 8

    Manual Release

    CN 6 CN 7

    Figure 21: Front Panel PCB Layout Figure 22: Underside of the Front Panel PCB

    Note: If the keyswitch is not used CN2 will carry a link so as to activate the panel.5.3 Local Control Station BRD25ARB - BExcept for the agent select button, and the keyswitch only offering the Auto/Manual and ManualOnly selection the Local Control Station has the same indicators and controls as the AgentRelease Module.

    AUTO / MANUAL MANUAL ONLY

    MANUAL HOLD

    MANUAL RELEASEACTIVATED

    AUTO RELEASEACTIVATED

    RESERVE AGENT

    TRIGGER ZONEDISABLED

    INITIAL AGENT

    AGENTRELEASED

    BLOCKED MODE

    COMMON FAULT

    DISABLED

    MANUAL

    ELEASE

    RMANUAL

    MANUAL ONLY

    AUTO / MANUAL

    HOLD

    Keyswitch

    PCB

    Manual ReleaseSwitch

    Figure 23: Local Control Station Layout

    MANUAL

    ELEASE

    R

    Manual Release Pressing the push button starts the manual agent releasesequence. This two action safety feature prevents any accidental operation of the control andshould not be disabled.

    MANUAL

    HOLD

    Manual Hold When pressed places the system into manual mode and prevents theinitiation of the automatic discharge sequence.

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    18/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 16

    5.4 Common Agent Release Module and Local Control Station Indicators

    MANUAL RELEASEACTIVATED Manual Release Activated

    Red in colour. Lit when a manual agent release sequence has commenced. This can beinstigated from the Agent Release Card and Local Control Station.

    AUTO RELEASEACTIVATED Auto Release Activated

    Red in colour. Lit when a automatic agent release sequence has commenced. This occurs whenthe zone(s) on the FACP have gone into alarm. For dual zones, the indicator should flash whenthe first zone goes into alarm, and steady when the second zone goes into alarm.

    AGENTRELEASED Agent Released

    Red in colour. Lit when the pressure switch indicates the agent has been discharged.

    INITIAL AGENTInitial Agent

    Yellow in colour. Lit when the initial agent activation circuit is selected.

    RESERVE AGENTReserve Agent

    Yellow in colour. Lit when the reserve agent activation circuit is selected.

    BLOCKED MODEBlocked Mode

    Yellow in colour. Lit when the lock-off valve has been activated.

    MANUAL HOLDManual Hold

    Yellow in colour. Lit when a Hold button is depressed on an LCS.

    TRIGGER ZONE

    DISABLED Trigger Zone DisabledYellow in colour. Lit when any of the trigger zones on the FACP are disabled.

    COMMON FAULTCommon Fault

    Yellow in colour. Lit under pressure switch, low pressure switch, lock-off valve, activation circuit,stage 1 output, stage 2 output, Local Control Station, trigger zone(s) fault conditions.

    AUTO / MANUALAuto/Manual

    Yellow in colour. Lit when a release sequence can be started automatically or manually.

    MANUAL ONLY

    Manual OnlyGreen in colour. Lit when a release sequence can be started manually only.

    DISABLEDDisabled

    Yellow in colour. Lit when the release sequence can not be started automatically or manually.

    BuzzerBuzzer is activated under programmed control.

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    19/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 17

    Local Control Station Terminal Blocks TB1 & TB2

    TB2 Terminal Assignment TB1 Terminal Assignment1 RS485 + In 1 +27V In2 RS485 - In 2 0V In3 RS485 Common 3 +27V Out

    4 RS485 + Out 4 0V Out5 RS485 - Out6 RS485 Common7 Interlock+8 Interlock-

    Quiescent Current:18.5mA

    Local Control Station Layout

    The Comms line is RS485 between the Local Control Station and the Termination Board.

    The Interlock is a monitored input with 10K EOL used to determine if air conditioning dampersand doors are closed. Typically the agent is not discharged until all dampers / doors are closed.

    D10

    D9

    D14

    D13

    D12

    D11

    D6

    D5

    D4

    D3

    D8

    D7

    U4

    U1

    U2

    U3

    X1

    Manual ReleaseActivated

    Initial Agent

    Manual Hold

    Auto / Manual

    Auto ReleaseActivated

    Reserve Agent

    Trigger ZoneDisabled

    Manual Only

    AgentReleased

    Blocked Mode

    Common Fault

    Disabled

    Hold

    CutoutCutout

    RS 485OUT

    TB2

    TB1

    SW 2

    K1

    HY1

    CN5

    BUZZERBZ1

    INTERLOCK

    CO M TerminationLink

    AddressSwitch

    EC3AW3V3 POWERSUPPLY

    +

    CO M

    +27V

    Out 0V

    +27VIn

    0V

    +_

    +_

    RS 485IN

    +_

    +

    +

    1

    2

    3

    4

    O

    N

    CN 8 CN 2

    Key Switch

    Manual ReleaseCutoutCutout

    Figure 24: Top PCB Layout Figure 25: Bottom PCB Layout

    5.5 Agent Release Termination Board BRD25ATB

    Figure 26: Agent Termination Board PCB Layout

    LK1

    Q2

    SW 1

    U5

    U9 U7

    U1

    RL6

    RL4RL1 RL2 RL5 RL3

    CN5

    U3U4 U2

    U10

    RL7

    + LOCK-

    + L.PSW-

    RELEASE

    C

    NC NO///

    +L

    COMM

    NC

    NO

    -L

    C

    NC NO///

    -+

    SIG+

    SIG-

    LCP CABLE

    + PSW -

    MonitoredINPUTS

    N/0

    STAGE2GASFIRED

    + - N/0 COMN/0 COM +

    SYST.INOP.

    SCRN+24VDC + -

    C

    NC NO///

    C

    NC NO///

    -L

    NO

    NC

    COMM

    +L-L

    NO

    NC

    COMM

    +L

    0VDC+ -

    STAGE1

    -COM

    TB7TB6TB5TB4TB3TB2TB1

    CN2

    CN1

    Address SettingCN 3 CN427V In

    27V toNext Board

    RS485 ControlIn From CN2 ofPrevious Board

    RS485 ControlOut to NextBoard or Link 1EOL is Applied

    MAIN RESV

    + - Outputs are Monitored

    ContactRating

    1A & 24V

    ContactRating

    1A & 24V

    ContactRating

    1A & 24V

    ContactRating

    1A & 24V

    1 2 3 4

    ON

    EOLTermination

    Quiescent Current:12mA

    4K7

    22KEOL

    10KEOL

    10KEOL

    10KEOL

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    20/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 18

    The Agent Release Termination Board interfaces to the;

    1. The FACP via CN1, CN2 continuing the RS485 communications bus if required. LK1 isinserted if this is the last backpan board on the bus.

    2. LCSs ( up to 4 ) via TB1. LK1 is inserted in the last board in the RS485 Bus

    3. Monitored Inputs: via TB2. ( EOL Resistance 22K, Series Resistance 4K7 )(a) Pressure Switch ( PSW ) agent released(b) Low Pressure Switch ( LPSW ) agent storage cylinder pressure has dropped to a pre-

    determined level; and(c) Interlock, the manual lock-off valve has been operated.

    4. Gas Fired: Output via RL2 N/O contacts rated at 1A @ 24VDC wired to TB3. Used toindicate to other monitoring devices the agent has been released.

    5. System Inoperative: via RL1 N/O contacts rated at 1A @ 24VDC wired to TB4. Used towarn by way of signage / audible alarm and/or monitoring that the system is inoperative.

    6. Stage 1: Output; initiates the visual and audible Fire Alarm and Evacuate warnings.

    (a) Monitored; via RL4 C/O contacts wired to TB5 1 & 2 ( EOL required 10K ) and(b) un-monitored; via RL5 N/O contacts wired to TB5 3 & 4.

    7. Stage 2: output; initiates the visual and audible Fire Alarm and Do No Enter warnings

    (a) Monitored; via RL6 C/O contacts wired to TB6 1 &2; ( EOL required is 10K ) and(b) Un-monitored; via RL3 N/O contacts wired to TB6 3 & 4

    8. Release: Main actuating circuit, monitored (10K EOL required) via TB7 1 & 2 ( 2A currentlimited ),Release: Reserve actuating circuit, monitored (10K EOL required) via TB7 3 & 4 ( 2Acurrent limited )(a) To Pyrogen Igniter ( max of 10 )

    (b) Metron Igniters ( max of 10 a series 2watt 18 resister must be added to the circuit )(c) Solenoid valve ( max current of 2 amps & 27VDC )

    5.6 Interface Wiring

    Monitored Inputs TB2 1 & 2Pyrogen,

    This input relies on a thermal fuse used in conjunction with 22K EOL and 4K7series resistors. The type of agent release mechanism has to be set in theProgramming Menu for the input to function as per the manufacturers specificationsand be in accordance with the relevant Standard.

    1 2

    PSW

    TB2Termination Board

    4K7 22KEOL

    PyrogenCanister

    + -

    PyrogenReleasePoint

    FUSE

    Pyrogen Release

    Brd. 302-740 To TB7MAIN or

    RESERVERelease

    MAIN / RESERVERELEASE

    TB1

    -VE

    +VE

    17/10/00

    D1

    R1

    C1

    C2

    R2

    TB2

    302-7400

    Figure 27: Pyrogen Wiring

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    21/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 19

    Solenoid & Metron

    This input relies on N/O or N/C relay contacts used in conjunction with 22K EOL and 4K7series resistors. The type of agent release mechanism and contacts used has to be set in theProgramming Menu for the input to function as per the manufacturers specifications and be inaccordance with the relevant Standard.

    Note: The PSW, LPSW & the Interlock Mechanisms are allmounted onto the top of the cylinder containing the Agent

    TerminationBoard

    + -

    4K722KEOL

    AgentDistribution

    4K7

    22K EOL

    LPSW LOCK

    4K7

    22K EOL

    PSW

    + - + -

    MAIN / RESERVERELEASE

    To TB7MAIN or

    RESERVERelease

    Agent

    Figure 28: Solenoid, Metron PSW, LPSW and LOCK Wiring

    LPSW & LockThese inputs are also monitored and should be wired as shown above

    1

    2

    To MonitoringInterface / Device

    0V

    RL2ATB3

    = MOV35V

    *

    * *

    To SysInop Mon

    +

    -System Inoperative

    1

    20V

    RL1ATB4

    +27V CurrentLimited to1A

    Figure 29: Gas Fired Wiring Figure 30: System Inoperative Wiring

    As can be seen from above the;

    Gas Fired Output can be wired to any interfacing or 1A monitoring circuit that requires a closedrelay contact to indicate a change of state. This could be a relay or a solid state device.

    System Inoperative Outputs 27V @ 1A to supply interfacing, signage and aural alarms toindicate the system has been taken out of service or has developed a fault.

    Stage 1, Stage 2

    - ( + )

    + ( - )

    *

    0VTB5 = Stage 1TB6 = Stage 2

    = MOV35V

    *

    *

    +ve

    -ve 10KEOL

    1 or 2 WaySignage

    To audible / visual

    device or interface

    *

    Stage 1 or Stage 2

    RL3ARL5A

    RL4B

    RL4A RL6A

    Agent Termination Board Relays

    RL6B

    1

    2

    3

    4

    The above circuitry applies to bothTB5 ( Stage 1 ) and TB6 ( Stage 2 )

    TB5 / 6

    MAIN RESV

    + -

    10K EOL

    Solenoid

    + -

    TB7

    Figure 31: Stage 1 and 2 Wiring Figure 32: Agent ReleaseSolenoid Wiring

    Current Generation SignageStage 1 displays the warning sequence ie discharge of the agent is imminent while Stage 2communicates the discharge of the agent is or has occurred DO NOT ENTER.

    2nd

    Generation SignageIs able to display both phases of agent release.

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    22/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 20

    6 Appendix: Adding to the System Menu & Programming

    In this example 1 Input Board, 1 Relay Board and 1 Sounder Board will be added to the system. TheDisplay and Zone Labels will then be edited.

    Step 1:Go to the SYSTEM MENU and then follow the procedure as set out below.

    ALARMYES / NO

    RESOUND

    YES / NOBUZZERSYSTEM

    EARTH MONYES / NO

    BRIGADENO

    FIRE FANNO

    RELAYSYES

    AGENTNO

    SOUNDERSYES

    SW INDICNO

    INDICATENO

    INPUTSYES

    MIMIC0 TO 8

    CODEAS4428

    MENU

    ENTER

    LEGEND:

    PRESS ENTER TO ACCESSMENU AND UPDATE PROGRAMOR CHANGE MENU

    PRESS MOVE FORWARDTHROUGH THE MENU

    PRESS: MOVE FORWARDOR BACKWARDTHROUGH THE MENU

    CANCELPRESS CANCEL ATANY TIME TO BACKOUT OF THE MENU

    MENU

    ENTERMENU

    ENTER

    MENU

    ENTER

    CANCEL

    MENU

    ENTER

    PRESS THESE KEYSTO SET YES / NO

    YES

    MENU

    ENTERUPDATE PROGRAM

    FACTORY SETCAN NOT BECHANGED

    EXAMPLESET RESOUND TO YESTHEN MOVE TO ALARM

    MOVE TO ALARMYES / NO

    IF THESE 4OPTIONSARE NOT SETTO YES THEYWILL NOTAPPEARIN THETEST MENU

    ENTERPASSWORD

    FACTORY DEFAULTPASSWORD IS 3333

    PASSWORD0000

    MENU

    ENTER

    PASSWORD0100

    PASSWORD0120

    PASSWORD0123

    MENU

    ENTER

    PASSWORDACCEPTED

    EXAMPLESETTING

    PASSWORD0123

    SYSTEM

    EXAMPLE OF SETTINGTHE SYSTEM MENU IF A

    RELAY BOARD IS INSTALLED

    YESMENU

    ENTERUPDATE PROGRAM

    EXAMPLE OF SETTINGTHE SYSTEM MENU IF A

    SOUNDER BOARDIS INSTALLED

    YESMENU

    ENTERUPDATE PROGRAM

    NO BRIGADE INTERFACE BOARD INSTALLED

    NO FIRE FAN MODULE INSTALLED

    NO AGENT RELEASE MODULE INSTALLED

    NO SWITCH & INDICATOR CARD INSTALLED

    NO INDICATOR CARD INSTALLED

    NO MIMIC INSTALLED

    EXAMPLE OF SETTINGTHE SYSTEM MENU IF AN

    INPUT BOARD IS INSTALLED

    YESMENU

    ENTERUPDATE PROGRAM

    Example of Adding Input, Relay and Sounder Boards in the SYSTEM MEU

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    23/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 21

    Step 2

    ZONES

    CLOCK

    OUTPUTS

    FIRE FAN

    AGENT

    SOUNDERS

    DISPLAY########

    SET SNDRBRD O/P

    .2..5..8

    Z LABELS

    MENU

    ENTER

    LEGEND:

    PRESS ENTER TO GO TO SUB MENU, SET MENU OR UPDATE PROGRAM

    PRESS MOVE FORWARD THROUGH THE MENU

    PRESS MOVE FORWARD / BACKWARD THROUGH THE MENU

    CANCEL PRESS CANCEL AT ANY TIME TO BACK OUT OF THE MENU

    MENU

    ENTER

    CANCEL

    MENU

    ENTER

    ACFISOALTE

    ACF

    ISOALTE PRESS ACF TO ISOL ATE CIRCUITS EXTERNAL TO FACP

    MENU

    ENTER

    EDITTEXT

    SET ZONETO

    ACTIVATE1...5..8

    MENU

    ENTER

    PROGRAM

    MENU

    ENTER

    MCP ZONEZ#

    1 TO 8

    ON

    OF F

    1 TO 8

    IN THIS EXAMPLE SNDR O/P 2,5&8ARE ACTIVATED BY ZONES 1,5&8

    RELAYSR3 Z-ALRM

    1..4...8

    R3 SWITCH.......

    R3 Z-FLT.......

    R3 Z-ISOL.......

    R3 I/P1.3...7.

    MENU

    ENTERRELAY 3 MENU

    ENTER

    SELECT RELAY 3

    ON

    OF F

    MENU

    ENTER UPDATE MENUMENU

    ENTER

    IN THIS EXAMPLE RELAY 3 IS ACTIVATED BY ZONES 1,4 OR 8WHEN IN ALARM OR I/P's 1,3 OR 7 OF THE I/P BOARD ARE ON

    TURN OFF2,3,5,6,7

    TURN ON1,3&7

    ON

    OFF

    MENU

    ENTER UPDATE MENUMENU

    ENTER

    TO EDIT DISPLAYTEXT USE

    SELECTZONEMENU

    ENTER

    TO MOVE THROUGH THE

    ALPHABET / NUMBERS

    TO MOVE THROUGH

    THE WORD

    MENU

    ENTER

    EDITTEXT

    UPDATE MENUMENU

    ENTER

    Programming the Relays and Sounders to be Activated by Zones and Editing Text

    CN 5

    CN10

    CN 1

    CN 3

    CN 2

    CN 4

    Address SW

    1 2 3 4

    ON

    Set to 1

    EOL Not Used

    RELAY BOARDMAIN CARD

    CN 1

    CN 3

    CN 2

    CN 4

    Address SW

    1 2 3 4

    ON

    Set to 1

    EOL Not Used

    INPUT BOARD

    CN 1

    CN 2

    TB3

    Address SW

    1 2 3 4

    ON

    Set to 1

    EOL LINKINSERTEDIN LASTBOARD OFTHE CHAIN

    SOUNDERBOARD

    +-

    +++++-----

    RS485 and 27V Cabling for the Installation of a Relay, Input and Sounder Board as in the SYSTEM and

    PROGRAMMING Menu Structures Above

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    24/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 22

    7 Status and Programming Screens

    The following shows all the screens that are possible in the FACP and how to navigate throughthem. I f a screen is not available it means that option has not been installed or is not available tothe model in use.

    Operating Main Menu

    LEVEL 1 LEVEL 2 LEVEL 3

    STATUS FAULTS TEST DISABLE SYSTEM PROGRAMMING

    7.1 Level 1 to 3 Status Screens

    SOFTWAREVER E1.2

    STATUS

    OUTPUTS BRIGADE RELAYS FIRE FAN AGENT SOUNDERS INPUT VOLTAGE

    ALARM 1OFF/NORM

    ALARM 2OFF/NORM

    ALARM 3OFF/NORM

    ALARM 4OFF/NORM

    FIREOFF/NORM

    FAULTOFF/NORM

    ANC OUTOFF/NORM

    ALARM 1OFF / ON

    FAULTOFF / ON

    DISABLEOFF / ON

    BATT FAILOFF / ON

    ALARM 2OFF / ON

    RELAY 1OFF / ON

    RELAY 2OFF / ON

    RELAY 3OFF / ON

    RELAY 4OFF / ON

    RELAY 5OFF / ON

    RELAY 6OFF / ON

    RELAY 7OFF / ON

    RELAY 8OFF / ON

    FAN 1OFF / ON

    FAN 2OFF / ON

    FAN 3OFF / ON

    FAN 4OFF / ON

    AGENTOFF/NORM

    SNDR 1OFF/NORM

    SNDR 2OFF/NORM

    SNDR 3OFF/NORM

    SNDR 4OFF/NORM

    SNDR 5OFF/NORM

    SNDR 6OFF/NORM

    SNDR 7OFF/NORM

    SNDR 8OFF/NORM

    INPUT 1OFF / ON

    INPUT 2OFF / ON

    INPUT 3OFF / ON

    INPUT 4OFF / ON

    INPUT 5OFF / ON

    INPUT 6OFF / ON

    INPUT 7OFF / ON

    INPUT 8OFF / ON

    BATT V26.8V

    CHRGR V27.0V

    SYSTEM V27.0V

    MENU

    ENTER

    MENU

    ENTER

    MENU

    ENTER

    MENU

    ENTER

    MENU

    ENTERMENU

    ENTERMENU

    ENTER

    MENU

    ENTERMENU

    ENTER

    MENU

    ENTER

    LEGEND:PRESS ENTER

    PRESS MOVE FORWARDTHROUGH THE MENU

    PRESS: MOVE FORWARDOR BACKWARDTHROUGH THE MENU

    CANCELPRESS CANCEL ATANY TIME TO BACKOUT OF THE MENU

    CANCEL

    MENU

    ENTER

    PRESS THESE KEYSTO SET YES / NO, OFF / ON,OFF NORMAL

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    25/28

    Installation & Commissioning of Control & Monitoring Add Ons

    Page: 23

    7.2 Level 3 System Programming

    ALARMYES / NO

    RESOUND

    YES / NOBUZZERSYSTEM

    EARTH MONYES / NO

    BRIGADEYES / NO

    FIRE FANYES / NO

    RELAYSYES/ NO

    AGENTYES / NO

    SOUNDERSYES / NO

    SW INDICYES / NO

    INDICATEYES / NO

    INPUTSYES / NO

    MIMIC0 TO 8

    CODEEN54

    MENU

    ENTER

    LEGEND:

    PRESS ENTER TO ACCESSMENU AND UPDATE PROGRAMOR CHANGE MENU

    PRESS MOVE FORWARDTHROUGH THE MENU

    PRESS: MOVE FORWARDOR BACKWARDTHROUGH THE MENU

    CANCELPRESS CANCEL ATANY TIME TO BACKOUT OF THE MENU

    MENU

    ENTERMENU

    ENTER

    MENU

    ENTER

    CANCEL

    MENU

    ENTER

    PRESS THESE KEYSTO SET YES / NO

    YES

    MENU

    ENTERUPDATE PROGRAM

    FACTORY SETCAN NOT BECHANGED

    EXAMPLESET RESOUND TO YESTHEN MOVE TO ALARM

    MOVE TO ALARMYES / NO

    NOTES:TO ADD OR DELTEFROM THE SYSTEM SETTO YES OR NO AND THEN

    GO TO THE PROGRAMMENU TO SET THEOPERATIONALPARAMETERSIF THESE OPTIONSARE NOT SET TO YESTHEY WILL NOT APPEARIN THE TEST, STATUS ORPROGRAM MENU

    ENTERPASSWORD

    FACTORY DEFAULTPASSWORD IS 3333

    PASSWORD0000

    MENU

    ENTER

    PASSWORD0100

    PASSWORD0120

    PASSWORD0123

    MENU

    ENTER

    PASSWORDACCEPTED

    EXAMPLE OFSETTING

    PASSWORD0123

    SYSTEM

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    26/28

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    27/28

  • 8/9/2019 MAN2512 ZoneSense Plus en Add Ons Inst Comm

    28/28

    Installation & Commissioning of Control & Monitoring Add Ons

    UNCONTROLLED DOCUMENT

    NOTE: Due to Ampacs commitment to continuous improvement specifications may change without notice.

    AUSTRALIAAMPAC TECHNOLOGIES PTY LTD

    97 Walters DriveOsborne Park 6017Western Australia

    Tel: 61 8 9242 3333Fax: 61 8 9242 3334

    Email: [email protected]

    EUROPEAMPAC EUROPE LTD.

    Unit 1, Norden Court,Alan Ramsbottom Way

    Great Harwood, BlackburnEngland BB6 7UR

    Tel: 44 (0) 1254 880 201Fax: 44 (0) 1254 880 202Email: [email protected]