Page 1: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

Fire Alarm Control Panel (AS4428.1)

Installation & Commissioning

MAN 1563-4

ZoneSense PLUS

Page 2: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

TABLE OF CONTENTS Page No.

1 About This Manual .................................................................................................................... 1 1.1 Introduction .................................................................................................................... 1 1.2 General Requirements ................................................................................................... 1 1.3 References ..................................................................................................................... 1 1.4 Symbols ......................................................................................................................... 1

2 System Overview ...................................................................................................................... 2

3 ZoneSense PLUS Description ................................................................................................. 3

4 Placing the Basic System into Operation .............................................................................. 4 4.1 Unpacking ...................................................................................................................... 4 4.2 Anti-Static Precautions ................................................................................................... 4 4.3 Working On The System ................................................................................................ 4 4.4 The Cabinet .................................................................................................................... 4 4.5 Mounting The Cabinet .................................................................................................... 5

5 PCB Removal / Replacement ................................................................................................... 6 5.1 Power Supplies and AC Mains Installation .................................................................... 7

5.1.1 Primary Power Supply ....................................................................................... 7 5.1.2 Mains wiring ....................................................................................................... 7 5.1.3 Connecting the Panel ........................................................................................ 7 5.1.4 Connecting the Mains Earth .............................................................................. 7 5.1.5 Connecting the Mains Power to the Power Supply ........................................... 8

5.2 Battery Charger .............................................................................................................. 9 5.2.1 Connecting the Stand-By Batteries ................................................................... 9

6 Main Control Board ................................................................................................................ 10 6.1 Connector numbering .................................................................................................. 11 6.2 Terminal Block Numbering ........................................................................................... 12 6.3 Earth Monitoring ........................................................................................................... 14 6.4 Communications (TB2) ................................................................................................ 14

6.4.1 Main Card Comms Link (K1) ........................................................................... 14 6.5 Inputs – Monitored (TB3) ............................................................................................. 15

6.5.1 Common Terminal (TB3 Com) ........................................................................ 15 6.5.2 Door Switch Input (TB3 Com / 1) ..................................................................... 15 6.5.3 MCP (TB3 Com / 2) ......................................................................................... 15 6.5.4 Fault Input (TB3 Com / 3) ................................................................................ 15

6.6 Detector Zones (TB13 & TB14) ................................................................................... 16 6.6.1 Detector Configuration ..................................................................................... 16

6.7 Outputs - Monitored (TB4) ........................................................................................... 18 6.7.1 Alarm Outputs .................................................................................................. 18 6.7.2 External Bell Output (TB4 1 / 2) ....................................................................... 18 6.7.3 Warning System Output (TB4 3 / 4) ................................................................ 19 6.7.4 Ancillary Control Facility (ACF Output) (TB4 5 / 6) .......................................... 19 6.7.5 Alarm Signalling Equipment (ASE Output) (TB4 7 / 8) .................................... 19 6.7.6 Conventional Sounder Circuit Wiring (TB4) .................................................... 20 6.7.7 Sounder Loading and Distribution ................................................................... 20

6.8 Outputs – Monitored Open Collector (TB5) ................................................................. 21

Page 3: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

6.8.1 Alarm Output (TB5 1 / 2) ................................................................................. 21 6.8.2 Fault Output (TB5 3 / 4) ................................................................................... 21

6.9 Outputs – Volt Free Relay Programmable ................................................................... 21 6.9.1 Alarm Output (TB5 5 / 6 / 7) ............................................................................ 21

6.10 Outputs – Volt Free Relay Non-Programmable ........................................................... 21 6.10.1 Fault Output (TB5 8 / 9 / 10) .......................................................................... 21

6.11 Auxiliary Power Output (TB12 1 / 2) ............................................................................ 21 6.11.1 Reset Terminal / Buzzer Output. (TB12 / 3) .................................................. 22 6.11.2 Buzzer ............................................................................................................ 22

7 Expanding the FACP with compatible Ancilliary Board ..................................................... 23 7.1 Installation and Wiring of Add On Cards and Boards .................................................. 24 7.2 Internal Communications Connector (RS485) ............................................................. 25

8 Battery Capacity Calculation ................................................................................................. 26 8.1 Description ................................................................................................................... 26 8.2 Power Supply Rating ................................................................................................... 26 8.3 Power Supply & Battery Calculator .............................................................................. 27 8.4 Primary Power Source Calculations ............................................................................ 28

9 Battery Guidelines .................................................................................................................. 29

10 Trouble Shooting Chart ......................................................................................................... 30

11 Installation and Commissioning Report .............................................................................. 31 11.1 Procedure ..................................................................................................................... 32 11.2 System Information ...................................................................................................... 32

12 Statement of Installation Compliance .................................................................................. 35

13 Installation Details .................................................................................................................. 37

14 Certification Information ........................................................................................................ 38

15 Specifications ......................................................................................................................... 39

16 Glossary of Terms .................................................................................................................. 40

17 Definitions ............................................................................................................................... 41

18 Quick Reference Guides ........................................................................................................ 42

19 Front Panel Configuration Labelling .................................................................................... 45

Page 4: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

1

1 About This Manual

1.1 Introduction

This manual contains all the information required to install, commission and operate the ZoneSense PLUS Fire Alarm Control Panel (FACP) and is only available to and for the use of personnel engaged in its installation, commissioning and operation.

1.2 General Requirements

The ZoneSense PLUS FACP has been designed and manufactured from high quality commercial components so as to comply with major world standards. To ensure these standards are not compromised in any way installation staff and operators should;

Be qualified and trained for the task they undertake;

Be familiar with the contents of this manual prior to the installation, commissioning or operation of a ZoneSense PLUS control system;

Observe anti-static pre-cautions at all times; and

Be aware that if a problem is encountered or there is any doubt with respect to the operational parameters of the installation the supplier should be contacted.

1.3 References

ZoneSense PLUS Technical Manual

ZoneSense PLUS Operation and Programming

Australian Standards:

AS4428 - Fire Detection, Warning, Control and Intercom Systems – Control and Indicating Equipment. Part 1 and Part 5

1.4 Symbols

Important operational information

Note: Configuration considerations

Observe antistatic precautions

Mains supply earth

DANGER mains supply present

Page 5: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

2

2 System Overview The ZoneSense PLUS 4 and 8 zone FACP complies with the highest level of approval for any applicable code and can be connected to an appropriate Fire Service monitoring facility.

As a Minimum, the conventional panel meets the following Standards;

AS4428

AS4214

Only devices compatible with ZoneSense PLUS should be used in an installation. These are listed in this document.

Features

The front panel 8 x 2 line LCD, navigation keys and the Menu/Enter keys allow the ZoneSense PLUS to be programmed “on site”. The same LCD and keys are also used for panel operation and interrogation.

Four monitored conventional Alarm circuits.

Two optional auxiliary input connections.

Two open collector outputs (fire and fault).

Two relay outputs (ancillary and fault).

Optional external buzzer or reset output.

System expansion capabilities / options:

Password entry to a wide range of programming and diagnostic functions which include;

Zone configurations;

MCP Zone assignment;

Default display; and

Zone labels;

A wide range of secure user functions. This includes the ability to isolate / de-isolate a large number of system functions.

Flush or surface mountable enclosure. A surround is required for the metal cabinet

Controls have tactile and audible feedback of operation.

All terminals cater for 2.5mm cables.

Page 6: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

3

3 ZoneSense PLUS Description The ZoneSense PLUS Fire Alarm Control Panel (FACP) is approved to AS4428 and is available in ABS (BX1) or metal cabinets (BX20) with either four (4) or eight (8) zone conventional detection circuits.

The 2 line LCD display allows the user to view system status, faults/isolates, prompts for system commands; and guides the user during on-site programming.

Key features of the ZoneSense PLUS FACP include:

Multi-purpose expansion capabilities

Multi-level password access

Tactile-feedback controls

Selectable end-of-line

Keyed entry

Each zone can accommodate up to 40 conventional detectors that can be programmed to function in one of the following modes:

Normal (latching)

Alarm Verification Facility (AVF)

Non-latching

Self Reset

Dual selectable Agent Release

The standard ZoneSense PLUS FACP comprises of a main printed circuit board and a power supply unit.

The main board provides:

The visual indication and control

Two Relays with volt-free Alarm and Fault changeover contacts

Termination for zones

Monitored outputs

Power supply monitoring

RS485 communications port

The ZoneSense PLUS can be quickly converted to an AS4214 approved Agent Release System with the use of the Agent Release Module and if required a remote Local Control Station (LCS). Up to four LCS’s can be connected to the FACP via a dedicated RS485 communications port.

CN4CN3

CN2

CN1

0V+

27V

PO

WE

R

CN4CN3

CN2

CN1

0V+

27V

PO

WE

R

BRD25MCB

CN6CN10

CN8

CAB1905

CAB2117

CN9

CN5

CN1CN2 CN2 CN1

CAB1905

CAB1902

CAB1926TO BATTERIES

CAB2290

TB3 INPUTS

CO

M

MC

PD

S

FLT

10K EOL

NOTE CAB 2074:GREEN + BLACK TO 'COM'RED TO 'DS'

CAB2074

CAB2289

BLACKRED

AN

CAB1911TO EARTH OUTPUTOF 25PSU

EXTERNAL EARTHTO EARTH INPUTOF 25PSU

FRONT PANELADD ON 1

BACK PANELADD ON 1

TB4

KNOCKOUTS

BOTTOM MOUNTING HOLES

POWERSUPPLY

KEYHOLES MOUNTING HOLES

FRONT PANELADD ON 2

BACK PANELADD ON 2

Figure 1: Typical Example of LoopSense Plus – AR

Page 7: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

4

4 Placing the Basic System into Operation

4.1 Unpacking

Carefully unpack the ZoneSense PLUS

The package should include:

Main Card, with all controls and indicators mounted directly onto it;

a switch-mode power supply;

2 X 12 Volt batteries connected in series.

2 X 003 keys

4.2 Anti-Static Precautions

To prevent damage to components, modules and boards, anti-static precautions MUST be observed while performing any task within the FACP. The same applies to those situated in the field

4.3 Working On The System

Prior to unplugging any connector, connecting or disconnecting any wiring, removing or replacing any module or board, ensure that both the Mains and Batteries have been isolated to prevent damage to panel components.

4.4 The Cabinet

Features:

The cabinet is available in three different styles. Each style has the capability of being either surface or flush mounted. With flush mounting though a surround is required.

Normally painted Arch White Ripple. Other colours are available on request.

The inner and outer door hinges are mounted on the left-hand side of the cabinet which allow the doors open to an angle of 100º. Locking is normally keyless though keyed entry is available on request.

Knockouts are positioned at the top and rear of the cabinet to simplify cable entry.

Page 8: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

5

4.5 Mounting The Cabinet

Note: It is recommended the cabinet should be installed in a clean, dry, vibration-free area.

Open the front door. Use the keyhole mounting holes in the top corners and in the lower middle of the unit to mount it on the wall. Cables to connect the system to its external actuating devices are brought in through the knockouts on the top or bottom of the cabinet.

R 6mm.

12 mm

Tap lightly around therim of the knockout

3 mm

Figure 2: Example ZoneSense PLUS Mounting & Removing Knockouts

POWERSUPPLY

BRIDGEASSEMBLY

TO REMOVE FRONT DOORSLIDE THE DOOR UP ANDAWAY FROM THEHINGES

NOTE: BATTERY TRAY SITS HERE IN THE BOTTOM OF THE CABINET

REMOVINGKNOCKOUTS

ABS KEY SLOTS

Figure 3: Exploded and Assembled View of the Basic ABS Model FACP with 003 Key Entry

AMPACDOOR RELEASE PINS

DOOR RELEASE PINS

FRONT PANELADD ON CARDSURROUNDRELEASE CLIP

FRONT PANEL ADD ON CARD SURROUNDRELEASE CLIP BEHIND

Figure 4: ABS Door Key and Front Panel Add On Card Surround Release Clip

Page 9: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

6

5 PCB Removal / Replacement

If the PCB’s have to be removed the following precautions should be observed;

Removing the door will provide better access to the boards and ensure the hinges are not accidentally stressed.

Personal anti- static procedures must be followed.

When disconnecting the 20 way connecting cable from the PCB, make sure that the cable remains connected to at least one board to prevent it being misplaced.

Note: Care should be taken when detaching this connector as it is necessary to depress the small locking tab to unlock the connector from its base. To reconnect the cable the connector must first be correctly aligned then pushed into the socket so it locks into position.

Carefully remove the retaining screws at each corner of the board taking care not to damage any of the components.

Place each board into anti- static storage once removed.

Push Tab Inwardsand Gently Pullthe ConnectorFrom the Socket

Connector

Page 10: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

7

5.1 Power Supplies and AC Mains Installation

5.1.1 Primary Power Supply

The ZoneSense PLUS Supply PCB combines the functions of;

A mains to D.C. switched mode power supply unit that operates from a supply of; 204 - 264VAC @ 47 – 63Hz supplying the system while all zones are in alarm

A battery charging and monitoring unit

A mains fail is detected when the PSU voltage drops below 24V.

5.1.2 Mains wiring

The requirement for the Mains supply to the FACP is fixed wiring, using three core cable (no less than 0.75mm² and no more than 2.5mm²) or a suitable three conductor system, fed from an isolating switch fuse spur, fused at 3A. This should be secured from unauthorised operation and be marked 'FIRE ALARM: DO NOT SWITCH OFF. The Mains supply must be exclusive to the FACP.

5.1.3 Connecting the Panel

Connecting ZoneSense PLUS internal connections and boards is best undertaken immediately prior to Commissioning.

Before beginning ensure all devices on the circuits are correctly connected and that cable integrity is verified throughout the installation.

Important: DO NOT use an insulation tester ('Megger') with any electronic devices connected. Faults occurring in the wiring which are not picked up at this stage will almost certainly result in spurious and intermittent faults when the equipment is energised.

Important: Under no circumstances should the ZoneSense PLUS panel be operated without the Power Supply correctly mounted in the enclosure and the retaining screws securely tightened.

5.1.4 Connecting the Mains Earth

All earth cabling shall be terminated to the panel Chassis Earth Terminal in a star configuration.

The earth cable closest to the cabinet body shall have an M4 SPW beneath the lug then an M4 SPW and M4 nut.

Each additional earth cable shall be terminated with an M4 SPW and M4 nut.

An additional M4 nut and M4 SPW are fitted to the Chassis Earth Terminal for installers to connect their Mains Earth.

M4 Shake Proof Washer

M4 Shake Proof Washer

CHASSIS EARTH TERMINAL

M4 Nut

Earth Cable

Earth Cable

M4 Nut

M4 Shake Proof Washer *M4 Nut *

Note:

* Extra M4 Nut and M4 SPW are provided finger tight on the Earth bolt.

Figure 5: Panel Earthing

Page 11: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

8

5.1.5 Connecting the Mains Power to the Power Supply

CHASSIS EARTHTERMINAL

+BATT-

CAUTION:FOR CONTINUED PROTECTIONAGAINST RISK OF FIRE REPLACEONLY WITH SAME TYPE 2A FUSE

OFF

ON

METALCOVER

DC OUTPUT

ETH+27V 0V

1

1 2

68

4357

(AC IN)

CN5 TO THERMISTOREXTENSIONS OF PIN 1 (TEMPSENSE RTN) AND PIN 6(TEMPSENSE) OF RJ45

CN2: RJ45 PINOUT CONNECTIONS1.TEMP SENSE RTN2.SUPPLY SENSE3.PSU V ADJ4.CHARGER ON5.LOAD ON6.TEMPSENSE7.BATTERY V SENSE8.OVCABLED TO THE MAIN BOARD

Battery 2 12Volts

Battery 1 12 Volts

+--

+

2

PROTECTIVE PERSPEXCOVER

HIGH VOLTAGE PRESENTINDICATOR UNDER CAGE

COMBINED MAINS SWITCH& MAINS INDICATION

NEUTRAL (BLUE)EARTH (GREEN)ACTIVE (BROWN)

NOTE: MAINS CABLESHOULD BE NO LESSTHAN 0.75mm

1 2 3

CN5

CN2

TB2

TB1SW1

F1: 2AFuse

27V TO THE MAIN CARD(3 WAY PANDUIT)

A

LEDAC ON

DC ONLED

DANGER

N

MAINS CABLE

Figure 6: Power Supply Battery Charger Wiring (3A PSU SHOWN)

Page 12: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

9

5.2 Battery Charger

The battery charger is an integral part of the Power Supply and is capable of

Recharging standard sized system batteries within 24 hours

Detecting a missing, damaged or undercharged battery

Protecting the battery against reverse or a short circuit condition

Charging batteries in line with Sealed Lead Acid battery manufacturers circuit temperature compensation guidelines

The following table contains the thresholds for the corresponding battery faults:

Battery Voltage Battery Fault Condition VBATT < 23.5V BATTERY LOW

*VBATT < 22V BATTERY DAMAGED

VBATT < 20V BATTERY MISSING

Note: Battery disconnect has been incorporated to prevent the battery from discharging through the battery charger should the charging voltage be less than the battery voltage.

5.2.1 Connecting the Stand-By Batteries

The capacity of the batteries to be installed depends on the panel configuration and required stand-by time. To calculate the required AH capacity of the batteries, refer to the calculation guide located in the rear of this manual.

Two new, good quality and fully charged 12V Sealed Lead Acid batteries are required as the emergency stand-by power supply for the Panel. They are to be mounted in the bottom of the cabinet. In the ABS version a protective tray is supplied in the packaging.

The batteries should be connected in series using the series link wire provided and located within the panel enclosure. The red and black battery leads from the Power Supply (see Figures 4 & 5) should be run to the batteries in such a way that there is no risk of them being damaged, and then connect the red wire to the positive terminal and the black wire to the negative terminal.

The panel's sophisticated battery monitoring protects the batteries against deep discharge by activating a cut off circuit when the stand-by supply voltage reaches approx 21 volts. If batteries are not fitted, are discharged or in poor condition, the “FAULT" LED will be illuminated.

Page 13: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

10

6 Main Control Board The Main Control Card and its front display panel combined with the Power Supply / Battery Charger and batteries form the basis for the ZoneSense PLUS FACP.

DECAL

BRIDGE

PCB

SHIELD

ASSEMBLEDBRIDGE

Figure 7: Exploded view of the Control Panel

///

NO

NC

C

///

NO

NC

C

FUSE:5A.

OU

TP

UT

S

NO C NC

MO

N.

CO

MM

S

DCOUT

INP

UT

S

ZO

NE

S

OU

TP

UT

SK1

U12

U7

TB14TB13

SW12

SW11

SW10

SW9

SW8

SW7SW6

SW5SW4SW3SW2SW1

R22

CN2

D2 D3

D4 D5

D6 D7

D8 D9

D10

D11

D12

D13

D14

D16

D17

D18 D19

D20 D21

D22 D23

D24 D25

D26 D27D28

D29

D31

D38

TB2 TB3

CN7

TB4 TB12TB5

BZ1FS1

RL2 RL3

U2

U3

U6

U18

U20

U19

U1

X1

EXT RS485COMMS

INPUTS

DISABLEEARTH

ZONES 1 2 3 4

+ A -+2-+1-+ 2 +4-+3-+Z4-+Z2-3

OU

TP

UT

S

C 1 +Z7-- +Z8-+Z6-+Z1- +Z5-+Z3- + F -

MO

N.

TOP OVERLAY

ZONES5 6 7 8

MON O/Ps 1 - 4Ext WarnBell Sys ACF ASE ALM FLT

NO C NC

FLTALM

+ -

RSTor BZ

MONO/Ps

COM DS MCP FLT

LCD

Power

Power Fault

System Fault

Earth Fault

External Bell Fault

Warning System Fault

ACF / Isolate

ASE Fault

ExternalBell

Isolate

WarningSystemIsolate

Alarm

Acknowledge

Fault

Reset

Isolated

Isolate / De-isolate

Fault / Isolate

Alarm

ZONE 1 ZONE 2

ZONE 3 ZONE 4

ZONE 5 ZONE 6

ZONE 7 ZONE 8

ACFIsolate Cancel

MenuEnter

RELAYOUTPUTS

Figure 8: Main Control Card Front PCB View

CN5: Comms & 27VDC ( 400mA CurrentLimit ) To Backpan Boards. If the FACPBackpan Configuration Exceeds 400mAthe 27VDC MUST BE TAKEN FROM CN10

CN9: Comms & 27VDC To AnyCards Fitted To The Front Panel( 400mA Current Limit )Keyswitch

Link CN1

CN8CN10

TP61TP60 TP59 TP58

TP40

TP39TP37 TP36 TP35 TP34 TP33 TP32 TP31 TP30 TP29 TP28TP27 TP26 TP25TP24 TP23 TP22 TP21 TP20 TP19 TP18 TP17 TP1TP2TP3TP4TP5TP6TP7TP8TP9TP10TP11TP12TP13TP14TP15TP16

MO

N.

+ - +Z3-+Z5- +Z1-+Z6-+Z8- -+Z7- 1 C

OU

TP

UT

S

3+Z2-+Z4-+3-+4- 2 ++1-+2-+ -

RE

V._

1

ZO

NE

S

+- +- - + - +

EARTHDISABLEIN

PU

TS

CO

MM

S

BOTTOM OVERLAY

CN1: The Link is inserted when the Front Panel Keyswitch is not used

CN8: 27VDC In From the Power Supply

CN10: 27VDC ( P/S Current Limit ) to the Backpan Boards

CN6: Monitoring Comms from the Power Supply

TP 1 to 44 ( See the Terminal Block Quick Reference for Detail )

Cutout

Figure 9: Main Control Card Rear PCB View

Page 14: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

11

Note: When connecting to the Brigade PSU Monitor board transient and “Flyback” (Back EMF) protection methodologies MUST be applied.

6.1 Connector numbering Connector Purpose /Pins

CN1 Link pins & when the front panel keyswitch is NOT used.

CN2 LCD Driver

CN3 & 4 LCD Back Lighting

CN5 Comms and +/- 27V and earth to the backpan boards. (Imax = 400mA)

Pins & 0V & +27V, & RS 485 Bus, Tx. Enable

CN6 Monitoring / Comms from the Power Supply.

Pins & 0V PSU Sense PSU Adjust Charger ON

Batt Load Temp sense Batt V Sense.

CN7 Factory Use Only

CN8 +/- 27V and earth from the Power Supply / Charger.

Pins 0V +27V Earth

CN9 Comms to the internal front panel cards. (Imax = 400mA)

Pins Pin connections are the same as CN5

CN10 +27V and 0V to the Sounder, Agent Release and Fan Termination back plan boards (Imax = P/S limit). All other backpan boards, 27VDC supply is via the RJ45 Comms cable.

Page 15: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

12

6.2 Terminal Block Numbering Terminal Block TP Number AS4428

COMMUNICATIONS EXTERNAL

TB2/1 RS485 +

2 28 RS485 -

3 29 Shield

INPUTS

TB3/1 Common

2 25 Door Switch (monitored)

3 26 Manual Call Point (monitored)

4 27 Fault Input (monitored)

ZONES ( 25mA / Zone )

TB13/1 1 + Zone 1

2 2 - Zone 1

3 3 + Zone 2

4 4 - Zone 2

5 5 + Zone 3

6 6 - Zone 3

7 7 + Zone 4

8 8 - Zone 4

TB14/1 9 + Zone 5

2 10 - Zone 5

3 11 + Zone 6

4 12 - Zone 6

5 13 + Zone 7

6 14 - Zone 7

7 15 + Zone 8

8 16 - Zone 8

MONITORED OUTPUTS ( 500mA / O/p )

TB4/1 17 External Bell +

2 18 External Bell -

3 19 Warning System +

4 20 Warning System -

5 21 ACF + Aux Control Function

6 22 ACF -

7 23 ASE + Alarm Signaling Equipment

8 24 ASE -

OPEN COLLECTOR OUTPUTS ( 30 mA /O/P )

TB5/1 25 Alarm +

2 26 Alarm -

3 27 Fault +

4 28 Fault -

OUTPUTS VOLT FREE RELAY ( 1A @ 30V )

5 29 NO Alarm

6 30 C Alarm

7 31 NC Alarm

8 32 NO Fault

9 33 C Fault

10 34 NC Fault

AUX, RESET / BUZZER

TB12/1 35 Aux 24VDC + (Mon 500mA)

2 36 Aux 24VDC –

3 37 Reset/Buzzer 100mA max

Page 16: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

13

+

-

RS

485

MO

NIT

OR

ED

INP

UT

S

CO

M D

S M

CP

FLT

+ Z

1 -

+

Z2

-

+ Z

3 -

+ Z

4 -

+

Z5

- +

Z6

- +

Z7

- +

Z8

-

DE

TE

CT

OR

ZO

NE

S

+1

-

+2

-

+3

-

+4

-

+

-A

LA

RM

+

-FA

ULT

N/O

C N

/CA

LAR

MFA

ULT

N/O

C N

/C

AU

X 2

4VD

C

+

-R

ST BZE

AR

TH

DIS

AB

LE

LAM

8

Way

Rem

ote

Rel

ay B

oard

EO

L 3K

3

Max

imum

of 4

0D

evic

es p

er Z

one

AL

L U

n-u

sed

Zo

nes

MU

ST

be

Ind

ivid

ual

lyTe

rmin

ated

wit

h an

EO

L

ALA

RM

OU

TP

UT

S

Com

ms

Link

3 S

ecR

eset

Pul

se

Not

e: C

omm

s Li

nkis

req

uire

d w

hen

only

one

Sys

tem

sC

omm

s bo

ard

is u

sed

EO

LR

esi

stor

EO

LR

esis

tor

EO

LR

esis

tors

EO

L Te

rmin

atio

n V

alue

sZ

one

=

1

0uf,

3K3,

4K

7, 6

K8,

10K

Mon

itore

d O

/P's

=

1

0Koh

ms

CN

8:27

V In

from

CN

4 of

the

P/S

CN

10:

27V

Out

to

Bac

kpan

Ter

min

atio

n B

oard

s

CN

6 P

SU

Con

trol

from

CN

2 of

the

P/S

Cur

rent

Lim

ited

to 2

5mA

. and

Det

ecto

r R

emov

al F

acili

ty A

vaila

ble

Max

imum

500

mA

/ 24

VM

onito

red

Ope

nC

olle

ctor

30

mA

O/P

's

Vol

tage

Fre

eC

onta

cts

1A/3

0V50

0mA

O/P

+24

v / 1

00m

A

0v

12v

Bat

t12

v B

att

+

--

+

-BAT

T+

DC

OU

TP

UT

OV+2

7VGN

D1

2

1268 4

357

TO

TH

ER

MIS

TO

RE

XT

EN

SIO

NS

OF

PIN

1

(TE

MP

SE

NS

E R

TN

) AN

D P

IN 6

(TE

MP

SE

NS

E)

OF

RJ4

5

RJ

45

PIN

OU

T C

ON

NE

CT

ION

S1

.TE

MP

SE

NS

E R

TN

2.S

UP

PLY

SE

NS

E3

.PS

U V

AD

J4

.CH

AR

GE

R O

N5

.LO

AD

ON

6.T

EM

PS

EN

SE

7.B

AT

TE

RY

V S

EN

SE

8.O

V

1

2 3

CN

2

CN

5

CN

5CN

2

LE

D

CN

4

CN

3

Po

wer

Su

pp

ly U

nit

( P

SU

)

Rea

r o

f M

ain

Car

d

Fro

nt o

f M

ain

Car

d Ill

ustr

ated

Ext

erna

l Cab

ling

Po

wer

Su

pp

ly /

Mai

n B

oar

d In

tern

al W

irin

g

Pro

gra

mm

abl

eU

n-p

rog

ram

ma

bleR

ST

/ B

Z O

/P is

Pro

gram

mab

leas

a R

ese

t or

Bu

zze

r bu

t not

bot

h

Fau

lt In

put

Doo

r S

witc

h

Fire

MC

P

AC

FW

arn

Sys

Bel

l

TB

2T

B3

TB

13T

B4

TB

5T

B1

2

EO

LR

esis

tor

Sh

ield

No

te:

Bas

es a

re f

itte

d w

ith

dio

des

ifth

e d

etec

tor

rem

ova

l fac

ilty

is u

sed

EO

LR

esis

tor

AS

E

Term

inat

e al

l 3 O

ptio

nal

I/P's

with

EO

L R

esis

tor

TB

14

Note: If a diode is NOT fittedinternally to the Bell / Sounder adiode MUST be fitted asshown - fit 1N4004 or similar

Bell

EOL10KOhms

Warn Sys

EOL10KOhms

Figure 10: General Wiring Diagram ZoneSense PLUS

Page 17: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

14

6.3 Earth Monitoring

The earth monitoring disable/enable feature is accessible via the SYSTEM menu at access level 3. Disabling the earth monitoring does not illuminate the Earth Fault LED on the control panel.

Note: If ZoneSense PLUS is connected to a third party system which has earth monitoring and it’s earth monitoring is being affected by ZoneSense PLUS even after being disabled through programming the resistor R22 on the Main Card in ZoneSense PLUS can be removed.

6.4 Communications (TB2)

External Communications Terminals (RS485) TB2 1, 2 & 3

The RS 485 output drives the remote cards and mimics up to a distance of 1.2km from the FACP. The external cabling (1 pair twisted shielded cable plus power) is wired to TB2 +, - and earth.

Note: If a fault occurs on the communications line the common FAULT and SYSTEM FAULT LED’S will be illuminated. Selecting the Faults Menu will display the fault details on the LCD.

6.4.1 Main Card Comms Link (K1)

K1 MUST be inserted when;

Front door panel cards and the Main Card are used as an FACP; or

Backpan boards and the Main Card are used as an FACP; or

Remote boards and the Main Card are used as an FACP.

K1

Co

mm

s + -Comms Link

TB2Earth Disable

Top Left HandCorner of theMain Card

To LAMs and/orRemote Relay Boards

TB3

D/SW MCP FLT

Manual Call Point

Door SwitchFault

Inpu

ts

RS485 Com 1 2 3

Note: Terminate the 3 I/P's in 10K EOL

Figure 11: Comms Wiring Details

Page 18: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

15

6.5 Inputs – Monitored (TB3)

6.5.1 Common Terminal (TB3 Com)

The COM terminal is used as the common for the following three 0v potential inputs.

6.5.2 Door Switch Input (TB3 Com / 1)

This optional input is used for connecting the FACP’s door switch. Connection is to TB3 COM & 1

6.5.3 MCP (TB3 Com / 2)

The optional external MCP I/P is monitored for normal operation and must be mapped to a particular zone.

To test the input insert the test key provided into the MCP. Removal of the key resets the MCP.

10K ohms

TerminationResistor

12

3

Wiring to an MCP

K1

Co

mm

s + -Comms Link

TB2Earth Disable

Front Door

TB3

D/SW MCP FLT

Manual Call PointDoor Switch Fault

Inpu

ts

RS485 Com 1 2 3

Note: Terminate the 3 I/P's in 10K EOL

Top Left HandCorner of theMain Card

Figure 12: Typical MCP Wiring

6.5.4 Fault Input (TB3 Com / 3)

This optional input is used to bring a fault into the system from an external source. Requirements for the input are an open collector or 0 volt, voltage free contact to initiate a fault. Connection is to TB3 COM & 3

Page 19: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

16

6.6 Detector Zones (TB13 & TB14)

Zone circuit connections are made directly to TB13 & TB14 on the Main Card and if screened cabling is used the screen is terminated at the panel's chassis earth terminal. All zones can be programmed to operate in one of the 5 different configuration modes each with a reset time in the order of > 1 second < 2 seconds.

D/SW MCP FLT

Com 1 2 3 5 6 7 8

TB3 TB13 TB14

+ Z2 - + Z3 - + Z4 -

Detector Zones

L1 In

+

L2

-R

APOLLO SERIES 60 STANDARD BASE WIRING

EOL

Earth

L1 Out

L1 In

+L1 In

+

L1 Out L1 Out

- L2 - L2 -

-R

Earth

-R

Earth

+ Z1 -

1 2 3 4

Selectable EOL Values:10uF Capacitor3K3 (Factory default)4K76K810K

EOL EOL EOL

Figure 13: Typical Detector Wiring

6.6.1 Detector Configuration

The operating configuration modes are:

Operating Configuration LCD

Normal Normal

Alarm Verification Facility AVF

Non Latching No Latch

Self Reset Self Reset

Agent Trigger Zone 1, 2, 3, & 4 T1, 2, 3, & 4

Note: AS1670 SECTION 8.6 ALARM VERIFICATION FACILITY states that alarm zone facilities used for the following shall not be subject to alarm verification:

Manual call points.

Detectors used to activate fire suppression systems.

Detectors installed in hazardous areas.

Fire suppression systems.

Beam detectors where a beam-interrupt fault overrides the alarm state.

AZF’s containing fixed temperature detectors only.

Detectors that have integral alarm confirmation delays such as some multipoint aspirated smoke detector systems.

Since the provision of alarm verification delays transmission of a signal to the monitoring service, it is desirable that it only be provided where other efforts to eliminate unwanted alarm signals have been unsuccessful.

Note: EOL type (capacitive / resistive) and value are set in the Programming Menu

Note: A maximum of 40 ZoneSense PLUS compatible Optical / Heat and Ionisation Detectors or Manual Call Points can be fitted to each circuit and mixed in any order.

Page 20: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

17

Note: An End of Line EOL (Factory set default = 3K3) device must be connected across the terminals of the last device on each zone circuit to allow the circuit to be monitored. Zones that are not used must also have an EOL fitted to the zone terminals on the Main Control Board.

Page 21: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

18

6.7 Outputs - Monitored (TB4)

6.7.1 Alarm Outputs

The panel has 4 dedicated individually monitored outputs which are;

rated at 500mA @ 24VDC nominal;

protected against short circuits;

Monitored for open and short circuit conditions even when an output is active. The monitoring operates on a reverse voltage principal and will indicate a fault within 60 seconds.

Programming which zones will operate any of the outputs is done via the front Panel.

6.7.2 External Bell Output (TB4 1 / 2)

Switched 24VDC.

Operated by an alarm from a non-isolated zone.

Is controlled by the “External Bell Isolate” switch. When pushed the “External Bell” output is inhibited and the LED is illuminated. If pushed again the output is toggled back to the normal state.

Operates the audible fault indication if the output is still in fault and left isolated for longer than 8 hours.

Bell

Note: If a diode is NOT fittedinternally to the Bell / Sounder adiode MUST be fitted asshown - fit 1N4004 or similar

EOL10KOhms

5 6 7 8

TB14 TB4

+ 2 - + 3 - + 4 -

Alarm Outputs

+ 1 -

1 2 3 4+ Z7 - + Z8 -

5 6 7 8

Figure 14: Typical Bell Wiring

Note: If a diode is NOT fitted internally to the Bell a diode MUST be fitted as shown above

Page 22: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

19

6.7.3 Warning System Output (TB4 3 / 4)

Switched 24VDC.

Operated by an alarm from a non-isolated zone.

The “Warning System Isolate” switch controls this output. When pushed the “Warning System” output is inhibited and the LED is illuminated. If pushed again the output is toggled back to the normal state.

Re-activates the audible fault indication if the output is still in fault and left isolated for longer than 8 hours.

Sounder

EOL10KOhms

5 6 7 8

TB14 TB4

+ 2 - + 3 - + 4 -

Alarm Outputs

+ 1 -

1 2 3 4+ Z7 - + Z8 -

5 6 7 8

Note: If a diode is NOT fittedinternally to the Bell / Sounder adiode MUST be fitted asshown - fit 1N4004 or similar

Figure 15: Typical Warning System Wiring

Note: If a diode is NOT fitted internally to the Sounder a diode MUST be fitted as shown above

6.7.4 Ancillary Control Facility (ACF Output) (TB4 5 / 6)

Switched 24VDC.

Operated by an alarm from a non-isolated zone

The “ACF Isolate” switch controls this output. When pushed the “ACF” output is inhibited and the LED is illuminated. If pushed again the output is toggled back to the normal state.

Re-activates the audible fault indication if the output is still in fault and left isolated for longer than 8 hours.

6.7.5 Alarm Signalling Equipment (ASE Output) (TB4 7 / 8)

Is a dedicated switched 24VDC output controlled via programming through the menu structure and operated by an alarm from a non- isolated zone.

Re-activates the audible fault indication if the output is still in fault and left isolated for longer than 8 hours.

Page 23: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

20

6.7.6 Conventional Sounder Circuit Wiring (TB4)

Each of the four alarm outputs can also be configured to drive a conventional sounder circuit.

Sounder

EOL10KOhms

5 6 7 8

TB14 TB4

+ 2 - + 3 - + 4 -

Alarm Outputs

+ 1 -

1 2 3 4+ Z7 - + Z8 -

5 6 7 8

Sounder

EOL10KOhms

Sounder

EOL10KOhms

Sounder

EOL10KOhms

Figure 16: Typical Sounder Wiring

An end of line resistor (10kΩ) must be connected at the end of each circuit to allow the wiring to be monitored.

The wiring for each circuit is connected to the relevant 2.5mm connector block on the Main Control Card and the screens terminated to the chassis earth terminal.

Note: All Sounders must be polarised.

Note: If a diode is NOT fitted internally to the Bell / Sounder a diode MUST be fitted as shown.

Note: No Spurs off the main line as EOL monitoring will be compromised

6.7.7 Sounder Loading and Distribution

The FACP's power supply is designed to give a maximum output current of 1.8A. In addition to powering the sounders, this current is also used for handling short circuit faults, supplying the FACP’s battery charging circuit and any output relays that may be fitted. As a safe margin and to allow for these other loads, the total sounder loading for the panel should not exceed a maximum of 1.5A.

Each output and or sounder circuit is current limited to a maximum alarm current of 500mA. The Sounders should be distributed throughout the building according to the sound levels required, and the load distributed as equally as possible across each circuit.

Page 24: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

21

6.8 Outputs – Monitored Open Collector (TB5)

Definition: A monitored open collector output for user connections.

Via the front panel it is possible to program which zones will operate any of the outputs.

6.8.1 Alarm Output (TB5 1 / 2)

The output operates in parallel to the Alarm Output relay and energises if a zone is not isolated and is in the alarm condition.

The output is current limited to 30mA.

If a zone is configured as non-latching it will not operate this output.

6.8.2 Fault Output (TB5 3 / 4)

The output operates in parallel to the Fault Output relay and de-energises in any fault condition.

The output is current limited to 30mA.

All faults automatically cancel on clearance (buzzer and indication).

6.9 Outputs – Volt Free Relay Programmable

Definition: A relay with voltage free change over contacts for user connections.

Programming which zones will operate any of the outputs is done via the front panel.

6.9.1 Alarm Output (TB5 5 / 6 / 7)

The relay is energised in the alarm condition of a zone that is not isolated.

The contacts are to rated at 1A 30VDC.

This output is not monitored.

6.10 Outputs – Volt Free Relay Non-Programmable

Definition: A relay with voltage free change over contacts for user connections.

6.10.1 Fault Output (TB5 8 / 9 / 10)

The relay is de-energised in any fault condition.

All faults automatically cancel on clearance (buzzer and indication).

The contacts are rated at 1A 30VDC.

This output is not monitored.

6.11 Auxiliary Power Output (TB12 1 / 2)

An output supplying power, with both the + TB12/1 and – TB12/2 legs fused is provided for ancillary devices.

The output is rated at 500mA @ 24VDC.

The output is protected against short circuit conditions.

In the event of the protection device operating a fault shall be signalled.

The monitoring is only up to the terminal block and does not extend to the field.

Current drawn from this output reduces that available to the sounders.

A fault on this output is indicated by the common FAULT LED illuminating steady and indication on the LCD.

External bell isolated

When fitted Ancillary control functions have been isolated.

Page 25: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

22

6.11.1 Reset Terminal / Buzzer Output. (TB12 / 3)

An output rated at 24VDC @ 100mA that can be configured to the user’s requirement to provide either of the following 2 functions:

Reset.

Reset is used to reset field devices such as beam detectors that is Reset switches negative for a period of 1.2 seconds on operation of the “Reset” button.

Buzzer.

Buzzer is connected to an external Buzzer which will sound at the same time as the internal panel buzzer. The output is protected against transient voltages.

6.11.2 Buzzer

The buzzer is required to operate on any alarm, fault or isolate condition. If the buzzer has been muted there is provision for the buzzer to resound again after an 8 hour period has elapsed if a new condition has not occurred. This provision is provided for;

Zone isolated

Warning system isolated

Page 26: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

23

7 Expanding the FACP with compatible Ancilliary Board The addition of or a combination of the modules / boards / cards listed below and mounted on the back pan or the front panel of the FACP provide additional control and monitoring facilities to a standard panel. All board inputs or outputs are programmable to any combination of zones.

Note: Only one of each board type can be installed in any one panel. The board types are:

Backpan

Relay Board, BRD25EWRB –A (Panel mounted)

Input Board BRD25SIPB.

Sounder Board BRD25SOPB.

Brigade Interface Board BRD25BBA.

Emergency Warning System ( EV20 or EV40 - metal cabinet only )

Front Panel

Fire Fan Module consists of a Termination Board (BRD25FTB) and front panel card BRD25FCB -.

General Indicator Card. BRD25GIB -A

Switch and Indicator Card BRD25GIBA

Emergency Warning System control panel (EV20 or EV40 - metal cabinet only)

Remote

Zone Mimic Indicator Card (External Power normally remote) BRD25GIB – D

LED Annunciator Master BRD25 GIB – E

Remote Relay Board BRD25EWRB – B

Note: To add or remove Add-On’s from the FACP go to the SYSTEM and PROGRAM Menus.

Note: Refer to manual MAN1565 “ZoneSense Plus Add-On’s” for full installation details.

Page 27: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

24

7.1 Installation and Wiring of Add On Cards and Boards

CA

B19

25 to

Bat

terie

s

CA

B19

02

CA

B19

05

CA

B19

11 T

O M

AIN

S E

AR

TH

CN

1C

N2

CN

2C

N1

AL

AR

M 2

N/C

CO

MN

/0B

ATT

FA

ILN

/CC

OM

N/0

ISO

LA

TEN

/CC

OM

N/0

FA

ULT

N/C

CO

MN

/0A

LA

RM

1N/C

CO

MN

/0

TB

1-T

B5

PO

WE

R

0V+27V

0V+27VCN2CN1

CN

3C

N4

POWER

+27V 0V

CN

1

CN

2

+27

v P

ower

fitte

d w

hen

Age

nt R

elea

se, S

ound

er,

Fan

Ter

min

atio

n B

oard

s ar

e fit

ted

to B

ackp

an

CN

1

CN

2

CN

5

CN

9

CN

1C

N2

CN

2C

N1

CA

B22

00C

AB

2117

CA

B19

05 CA

B22

00

CN

6

POWER

+27V 0V

CN

1

CN

2

POWER

+27V 0V

CN

1

CN

2

MA

IN C

ON

TR

OL

CA

RD

OP

TIO

NA

L C

AR

DS

AG

EN

T R

ELE

AS

EF

AN

CO

NT

RO

LG

EN

ER

AL

IND

ICA

TO

R

OP

TIO

NA

L B

OA

RD

SA

GE

NT

TE

RM

INA

TIO

NR

ELA

YF

AN

TE

RM

INA

TIO

NIN

PU

TS

OU

ND

ER

TE

RM

INA

TIO

N

A B

AT

T B

OX

IS

RE

QIF

TH

ES

E B

RD

S A

RE

FIT

TE

D

OT

ION

AL

BR

IGA

DE

BO

AR

DC

AB

2200

CA

B22

00

BR

D25

AR

B P

CB

0783

(

AG

EN

T R

ELE

AS

E M

OD

ULE

)B

RD

25A

TB

PC

B07

87

(A

GE

NT

TE

RM

INA

TIO

N B

OA

RD

)B

RD

25B

BA

PC

B07

79

(B

RIG

AD

E B

OA

RD

)B

RD

25E

WR

B P

CB

0770

(8

WA

Y R

ELA

Y B

OA

RD

)B

RD

25F

CB

PC

B07

83

(F

IRE

FA

N M

OD

ULE

)B

RD

25F

TB

PC

B07

80

(

FAN

TE

RM

INA

TIO

N B

OA

RD

)

PSU

1887

CN

3

CN

4

CN

3C

N4

CN

3C

N4

BR

D25

GIB

PC

B07

81

(

GE

NE

RA

L IN

DIC

AT

OR

CA

RD

)B

RD

25M

CB

PC

B07

69

(M

AIN

CO

NT

RO

L C

AR

D)

BR

D25

PS

U P

CB

0813

(P

OW

ER

SU

PP

LY U

NIT

)B

RD

25S

IPB

PC

B07

78

(S

ING

LE IN

PU

T B

OA

RD

)B

RD

25S

OP

B P

CB

0772

(

SO

UN

DE

R O

UT

PU

T B

OA

RD

)

OP

TIO

NA

L C

AR

DS

AG

EN

T R

ELE

AS

EF

AN

CO

NT

RO

LG

EN

ER

AL

IND

ICA

TO

R

OP

TIO

NA

L B

OA

RD

SA

GE

NT

TE

RM

INA

TIO

NR

ELA

YFA

N T

ER

MIN

AT

ION

INP

UT

SO

UN

DE

R T

ER

MIN

AT

ION

A B

AT

T B

OX

IS

RE

QIF

TH

ES

E B

RD

S A

RE

FIT

TE

D

OP

TIO

NA

L B

OA

RD

SA

GE

NT

TE

RM

INA

TIO

NR

ELA

YF

AN

TE

RM

INA

TIO

NIN

PU

TS

OU

ND

ER

TE

RM

INA

TIO

N

A B

AT

T B

OX

IS R

EQ

IF T

HE

SE

BR

DS

AR

E F

ITT

ED

BU

S 1

BU

S 2

BU

S 3

: Ext

erna

l Car

ds &

Boa

rds

BO

AR

DID

EN

TIF

IER

S:

CN

8

CN

10

Figure 17: Add On Card and Board Positioning Within the ABS FACP

Page 28: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

25

7.2 Internal Communications Connector (RS485)

PCB mounted connectors provide serial communications to internal ancillary boards. CN9 on the Main Card cables to CN5 or 6 on the Agent Release Card or CN1 or 2 on the “Add on” front panel cards and CN5 on the Main Card cables to CN1 or 2 on the back pan boards

TB2

K1

Shield

CN5

CN9 Front PanelCard 1

Front PanelCard 2

BackpanBRD 1

BackpanBRD 2

INSERTLK1

RemoteCard 1

RemoteCard 2

LCS 1 LCS 2

INSERTLK1

INSERTLK1

INSERTLK1

With Agent Release fitted to the FACP there will be an Agent Termination Board mounted on the Backpan. Local Control Stations can then be fitted at some location remote from the FACP. These LCS's communicate with the ATB via a second RS485 bus hence the last LCS in the chain will have to be terminated

Note: If Backpan boards AND remote facilitiesare fitted the front panel cards are not terminated

ToTB1 Agent Termination Board

Fit K1 if only theMain ControlCard is used asthe FACP or only1 Bus is used

RS485 +-

BUS 1 ( B1 )

BUS 2 ( B2 )

BUS 3 ( B 3)

( Link 1 in Table below )

( Link 2 in Table below )

( Link 3 in Table below )

BUS 4 ( B 4) Fit to last LCS

Figure 18: RS485 Communication Bus Terminating

Linking Table

K1 is fitted as standard on the Main Control Board. It is removed when more than one Bus is used as defined in the Linking Table below.

Link Bus Configuration

B1 B1,2 B1,3 B1,2,3 B,2 B2,3 B3

1 X & K1 X X

2 X X X & K1 X

3 X X X X & K1

X = Insert Link

B1: Bus 1 Front Panel Cards

B2: Bus 2 Backpan Boards

B3: Bus 3 Remote facilities

B4: Bus 4 Local Control Station fitted to the backpan Agent Release Board.

Page 29: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

26

8 Battery Capacity Calculation The standby power source capacity, or battery capacity, determines how long the system will continue to operate in the event of the loss of the primary power source. It therefore becomes necessary to calculate the battery and hence power supply / battery charger capacity required for each installation.

The following calculator has been designed to determine the required capacity to meet the required standard. Should an existing panel be expanded the required battery and power supply capacity should be recalculated to ensure the panel continues to operate within the standard.

The standards considered in this document are AS1670.1 2004

8.1 Description

Enter the number of units listed in the left hand column which go to make up the panel, complete the multiplication to obtain the quiescent current then multiply by the standby and alarm hours required by the standard.

8.2 Power Supply Rating

The minimum Power Supply Rating ( 4 ) is obtained by calculating the manufacturers recommended battery charge current and [ see Note ] ( 1 ) then adding the quiescent current of the entire system ( 2 ) and the alarm current ( 3 ).

1. Battery Capacity (AH) (determined from Calculator) = Amps

24 x 0.8

2. Add Quiescent Current of the System (Iq) = Amps

3. Add the extra current that is drawn when in alarm (Ia) = Amps

4. Minimum Current Rating of Power Supply is = Amps

Note #1: The capacity of the battery shall be such that in the event of failure of the primary power source the batteries shall be capable of maintaining the system in normal working (quiescent) condition for at least 24 hours, after which sufficient capacity shall remain to operate two worst case AZF’s and associated ACF’s for 30 min.

Note #2: Where the fire control station will not receive the system's total power supply failure signal the battery shall have sufficient capacity to maintain normal system operation for 72 hours plus 30min. in alarm.

Note #2: Where the fire control station will not receive the system's total power supply failure signal and Agent Release is incorporated in the FACP, the battery shall have sufficient capacity to maintain normal system operation for 96 hours plus 30min. in alarm.

Note #3: When calculating battery capacity, allowance shall be made for the expected loss of capacity over the useful life of the battery. A new battery shall be at least 125% of the calculated capacity requirements, based on a loss of 20% of its capacity over the useful life of the battery.

Page 30: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

27

8.3 Power Supply & Battery Calculator Criteria Example

Iq Calculation Iq Iq Calculation Iq Panel Configuration No Off X mA = Iq No Off X mA = Iq Basic 4 zone gas panel 60 0 Basic 8 zone gas panel 90 1 90 90

Interface Cards/Boards 0

Sounder Board 6 0 Brigade Board 23 1 23 23 Input Board 5 0 Fire Fan Module 16.5 1 16.5 16.5 General Indicator Card 3 0 Relay Board (Internal) 0.5 1 0.5 0.5 Switch & Indicator Card 3.5 0 EV20SZEWS 41 0 EV40SZEWS 58 0 LED Annunciator Master (LAM) 11.5 1 11.5 11.5 Local Control Station 18.5 0 Relay Board (Remote) 16 0

Zone Devices Total 0

Orbis range (average) 0.107 21 0.107 2.3 Apollo range (average) 0.048 32 0.048 1.5 0 Fireray 2000 Beam Det. 13 0

Iq = Iq = 145.3

Devices activating when the system is in alarm 2 Gas Zones in Alarm 215 1 215 215 Sounder Board 152 1 152 152 Brigade Board 41 1 41 41 Input Board 5 0 Fire Fan Module 87 1 87 87 General Indicator Card 3 0 Relay Board (Internal) 67 0 Switch & Indicator Card 3.5 0 EV20SZEWS 650 0 EV40SZEWS max 30Watt Load 3400 0 Relay Board (Remote) 102 1 102 102 Local Control Station 21 0 Relay Board (Remote) 102 0 Warning Signs (2 Stage) 140 2 280 280 Bells 100 1 100 100 Strobe 125 2 125 250 Other 0 Ida= Ida= 1227

Devices de-activating when the system goes into alarm Aircon Relays 20 2 20 40 Electric locks 100 2 100 200 Other Idd= Idd= 240

I Alarm ( Ia = Iq + Ida – Idd ) = mA Ia = 145 +1227 – 240 = 1132 rounded for calculation

Page 31: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

28

Criteria Example Battery capacity at end of battery life

NOTE:

= ( Iq x 24 ) + ( Ia x 0.5 ) Note: the figure of 24 above should be 96 if Brigade unmonitored Agent Release is used.

= ( Iq x 24 ) + Fc( Ia x 0.5 ) Fc – capacity de-rating factor. AS1670.1 states a factor of is deemed to satisfy the criteria. (using rounded figures)

= ( 145mA x 24 )+ 2(1227mA x 0.5 ) = 3480mA + 1227mA = 4707mA Note: 1,000ma = 1 Amp = Ah = 4.7Ah( rounded ) New battery capacity requirement

= Ah x 1.25 = 4 x 1.25

= 5.875 Ah Rounded up to nearest available battery rating

= 6 or 7Ah

8.4 Primary Power Source Calculations Battery Charger Current Requirement: Battery is charged for 24 hrs. to provide 5Iq + 0.5Ia

=

( 5x Iq ) + Fc( 0.5 x Ia )

=

( 5x Iq ) + Fc( 0.5 x Ia )

= ( 5 x 145 ) + 2( 0.5 x 1227 ) = 725 + 1227 Ah Requirement = 1952 Ah

Battery Charging Current Required

=

Ah above

=

1952

24 x e 24 x e ( = 19.2 ) e is the battery efficiency, 0.8 = 0.101A

Power Supply Requirement Select the greater of 1 or 2 1. Ia + non battery backed ancillary alarm loads 2. Iq + non battery backed quiescent loads If the power supply is used as the charger the current rating of the supply shall be [( 1 or 2 ) + battery charger current ].

Note: Remember to take into account ALL outputs that will be switched on when calculating Ida.

Page 32: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

29

9 Battery Guidelines (Tested by SSL to comply with AS 1603.4-1987 Appendix G).

Note #1: afp number is the SSL Listing Number.

Note #2: Types are the Manufacturers and not the suppliers.

Note #3: Those listed below in small Italic are not generally used by Ampac.

Note #4: Automotive type batteries are not normally suitable for stationary use.

afp - 791 afp - 792 afp - 1220 afp - 1221 afp - 1222 afp - 1228

Yuasa NP Series

Power-Sonic PS Series

Matsushita LCR Series

Matsushita LCL Series

Matsushita LCX Series

B & B BP Series

NPH1.3-6 NPH3.2-6 NPH1.3-12 NPH2-12 NPH3.2-12 NPH5-12 NPH16-12 NP1-6 NP1.2-6 NP2.6-6 NP3-6 NP4-6 NP4-6W NP4.2-6H NP7-6 NP8-6 NP10-6 NP0.8-12 NP1.2-12 NP1.9-12 NP2.3-12 NP2-12 NP2.6-12 NP4-12 NP7-12 NP12-12 NP24-12 NP24-12B

PS-605 PS-610 PS-630 PS-632 PS-640 PS-650L PS-670 PS-6100 PS-1208 PS-1212 PS-1219 PS-1232 PS-1240 PS-1270 PS-12120 PS-12180 PS-12240 PS-12330 PS-12400 PS-12650

LC-R065P LCR12V4BP LC-R125P LC-RC1217P LC-R064R2P LC-R067P LC-RO011P LC-R127P LC-R127R2P

LC-LA12V33P

LC-X1224P9(AP) LC-X1228P(AP) LC-X1238P(AP) LC-X1242P(AP)

BP 1.2-6 BP 4.0-6 BP 4.5-6 BP 6 –6 BP 7 –6 BP 8 -6 BP 10-6 BP 1.2-12 BP 1.9-12 BP 4 –12 BP 7 –12 BP 12-12 BP 17-12 BP 24-12 BP 40-12

Page 33: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

30

10 Trouble Shooting Chart Problem Solution

No Mains Power Check mains Fuse

Supply fault LED illuminated

Check output voltage it should be set to 27.2VDC. Low = (less than 26.5VDC ) High = (greater than 28VDC ) Check the battery has been connected properly

Earth Fault LED illuminated Check all input and output cabling and wiring assemblies for short to ground

System Fault LED illuminated Ensure correct panel configuration Check all connections for loose wiring

Warning System Fault LED illuminated Check correct E.O.L is fitted Check wiring is connected correctly

RS485 Communication Bus not working Refer LCD. This may identify where there is a break in the communication line

Can not access a menu Incorrect Password entered

Forgotten Password Ring AMPAC and directions will be given to provide you with a temporary code

Bell / Sounder Fault Make sure you have a 10K Ω EOL resistor fitted and a diode (1N4004) in series with the bell / sounder

Page 34: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

31

11 Installation and Commissioning Report This ZoneSense PLUS Fire Alarm Control Panel is installed at:

Company Name

Street

Suburb

State / Country

(Company Name & Installation Address) Postcode

Owner or Owners' Authorised Representative:

Company Name

Street

Suburb

State / Country

(Company Name & Installation Address) Postcode

Type of Installation: NEW MODIFIED ADDITION UPGRADE

(Please Circle)

Date of commissioning tests: / /

Name and address of commissioning company, (in 'BLOCK LETTERS')

Company Name

Street

Suburb

State / Country

(Company Name & Installation Address) Postcode

Commissioning Representative Name: (Print)

Signature:

Page 35: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

32

11.1 Procedure

The following tests are the minimum that shall be performed when commissioning a system using the ZoneSense PLUS Fire Alarm Control Panel. Supplements to these tests may be added by way of attachments or notation (using waterproof ink) to this documentation. If supplements or tests are added reference to them shall be made at an appropriate point on this document.

This Commissioning Record is to be completed in conjunction with the -

operator's manual;

installer's statement(s);

'as-installed' drawings; and

detector test records,

The Record provides a complete description of the installed system and its tested performance at the time of being commissioned.

11.2 System Information

Tick relevant box

1. Ensure that all detectors used in the system:

i. Are listed in the operator's manual; ii. Are compatible with the installed AZF, iii.

Do not exceed the permitted number of detectors on each circuit; and

iv. Are installed in an environment for which they are suitable.

2. Check that the primary power source for the system has been provided in accordance with AS 3000, and that the isolating switch disconnects the active conductors.

3. Check that the detector and the FACP locations are in accordance with the appropriate clauses of, AS 1670.

4. Alarm Zone Circuit:

i. Measure each alarm zone circuit voltage, and ensure each is within the equipment manufacturer's specifications.

ii. Insulation resistance of all installation wiring measured in accordance with AS 3000 or similar approved method and record the worst case result in the logbook.

5.

Open circuit and short circuit the end of line device on each alarm zone circuit, or conduct other appropriate tests to ensure that fault and alarm conditions are operating correctly on all alarm zone facilities on other sections of the control and indicating equipment.

Not

Applicable

No

Yes

Page 36: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

33

6. FACP test to be carried out as follows:

i. Operate each alarm test, fault test, isolate and reset facility provided for each alarm zone facility to determine correct operation.

ii. Operate the primary power source switch on and off at least five times to check the system will not cause a false alarm from primary power source interruptions.

7. Detector testing to be carried out as follows:

i.

Test each installed detector or sampling point with an approved in-situ tester, and ensure that each detector has operated in the correct range, and the alarm has indicated on the control and indicating equipment and, if applicable, at the detector tested.

ii.

Confirm that response of the system does not exceed 6 s from the time the detector operates until the master alarm facility registers the alarm (while in normal mode) on each zone, or 32 s when AVF is fitted.

iii. Record tests on detector test record as required by AS 1851.8 and attach to the report.

8. Check the operation of each manual call point and all other actuating devices.

9. For flame detectors, perform the following:

i. Check that the number and type of detectors provide adequate protection of the area.

ii. Check that there are no 'blind' spots in areas protected. iii. Check that detectors are rigidly fixed. iv.

Check that detectors are properly connected to compatible control and indicating equipment.

v. Check that detector lenses are clean and adequately protected from dust and extraneous radiation sources where these are present.

vi. Test the detection response to a flame source or simulated flame.

10. For smoke detection sampling systems, perform the following:

i. Measure the response time of all sampling points using smoke placed at each sampling point.

ii. Check the back-up power supply capacity. iii. Check the operation of alarm settings and indicators. iv. Check operation of remote indication of alarm and fault signals. v. Check the operation of airflow failure indicators.

Page 37: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

34

vi. Check the operation of the system (signal) failure indicators. vii. Check the isolate/reset functions. viii. Check the fault and alarm test facilities.

11. Test each ancillary function by operating the alarm zone facility(ies), associated with the ancillary function.

12. Alarm signaling:

i. Check that the master alarm facility is able to receive the alarm signal by operating each alarm zone facility.

ii. Check that the master alarm facility initiates an alarm to the fire control station equipment.

13. Battery supply:

i. Check that both the primary and secondary power sources are of a suitable type and capacity complying with Clause 8.2.

ii. Perform a float voltage check according to the battery manufacturer's recommendation to ensure that the charger type and setting is correct.

Type of battery. Float voltage/ required.

Charger type. Charger set at.

14. Check that all alarm zone facilities have been correctly labeled and that the alarm zone is immediately apparent from the labeling.

15. Check the 'as-installed' drawings are marked up, are consistent with the installation and the operator's manual is relevant to the installation.

16. Ensure the results of these tests are recorded in the system logbook.

Page 38: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

35

12 Statement of Installation Compliance Please PRINT 1. Name of Building: 2. Address: 3. I/We have installed in the above building an alteration to the system manufactured by, OR a system

manufactured by. (Name of Service Provider)

4. The system is connected to monitoring service provider by a Permanent , Non-Permanent connection

5. Date of connection / / 6. Ancillary equipment installed / connected to the control and indicating equipment.

(See Commissioning Of Cards and Boards) Yes No 7. Current drain of ancillary loads powered from the FACP power supply 8. Primary power source voltage 9. Battery type and capacity Manufacturer AH

10. Is maintenance agreement held for the system? Yes No

11. Operator's handbook supplied? Yes No

12. Logbook supplied? Yes No

13. 'As-installed' drawings supplied? Yes No 14. Portions of the building not protected by this system are; (Please PRINT)

1 6

2 7

3 8

4 9

5 10

Page 39: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

36

15. I/We 1. 2. 3. Print Name/s Hereby certify that the installation has been thoroughly tested from each actuating device and that a test of the transmission of the alarm signal to the monitoring service provider has been satisfactorily carried out. I/We further certify that the whole system and all components called up in Clause 1.3 in connection therewith are installed entirely in accordance with the current requirements of AS 1670.l, - Except with regard to the following details which have already been approved, approval attached. Strike out the bolded sentence if there have not been any exceptions. Signature Date / / Installing Company Please PRINT or Stamp

Page 40: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

37

13 Installation Details

# Indicate with a number in brackets the number of actuating devices in concealed spaces.

* Add addressable loop number in brackets where applicable.

Number and Type of Actuating Devices

Alarm Zone

#

* Number of Actuating Devices per Zone

Thermal A B C D E

Smoke Ion Photo

Flame IR UV

Manual Call Point

Other

Page 41: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

38

14 Certification Information The ZoneSense PLUS is designed and manufactured by:

AMPAC TECHNOLOGIES PTY LTD

7 Ledgar Rd

Balcatta

WA 6021

Western Australia

PH: 61-8-9201 6100

FAX: 61-8-9201 6101

Manufactured to:

Certificate of Compliance Number:

Equipment Serial Number:

Date of Manufacture:

HEAD OFFICE

Page 42: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

39

15 Specifications Mechanical

Dimensions Metal Cabinet: (mm) 500H x 405W x 145D

Note: A battery box is available should either model be optioned to capacity.

Environmental

Temperature: -5ºC to + 55ºC

Humidity: 25% to 75% Non condensing

Power Supply

Input Voltage: 180 - 264VAC ( 47-63Hz )

Protection (Quick Acting Fuse): 1.25 Amp M205

Minimum Cable Requirements: Not less than 0.75mm

Voltage: 27.2VDC +/- 0.1VDC

Power Supply Ripple Voltage: <100mV

Power Supply Regulation: 2%

Power Supply Fault Indication Volts High 28VDC

(at room temperature) Volts Low 26.5VDC

Power Supply Output Current: 2Amps

Protection: Current Limiting

Charger O/P Voltage: (@ 25˚C) 27.3 +/- 0.1VDC

Battery Type: Sealed Lead Acid: 2 x 12V Sealed Lead Acid

Maximum Battery Capacity: 7AH - 12AH for metal cabinet

Maximum Charger Current Limited: 400mA

Battery Supply Current Limited: 3A (PTC)

Battery Discharged Cut-off Voltage: 21VDC

Main Card

Quiescent Current (Iq) (Add 8mA / zone for 3K3 EOL) 25mA

Iq plus Zone 1 in Alarm 90mA

Maximum Current Draw per Output (Current Limited) 500mA

Maximum Number of Devices per Conventional Zone: 40 max

Cabling Requirements: 2 core 1.5 to 2.5mm²

Fault monitoring: O/C, S/C, (EOL default = 3K3)

Outputs

Alarm (Current Limited) 24VDC @ 500mA Max

Alarm / Fault Monitored Open Collector (Current Limited) 24VDC @ 30mA Max

Alarm Fault Relay Contacts 24VDC @ 1A

Auxiliary VDC 24VDC 500mA Monitored

Inputs

MCP, Door Switch and Fault 0VDC Closing Contact

Communications

Internal to FACP RS485

External to FACP RS485

Page 43: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

40

16 Glossary of Terms ACF: ANCILLARY CONTROL FACILITY

ACKD: ACKNOWLEDGED

AHU: AIR HANDLING UNIT

ALM: ALARM

AVF: ALARM VERIFICATION FACILITY

AZF: ALARM ZONE FACILITY

AZC: ALARM ZONE CIRCUIT

C: RELAY COMMON CONTACT (WIPER)

CIC: CONTROLLER INTERFACE CARD

CN: CONNECTOR

CPU: COMMON PROCESSOR UNIT

DGP: DATA GATHERING POINT

EARTH: BUILDING EARTH

EOL: END OF LINE

FDS: FIRE DETECTION SYSTEM

FACP: FIRE ALARM CONTROL PANEL

FLT: FAULT

GND: GROUND (0 VOLTS) NOT EARTH

I/O: INPUT/OUTPUT

LCD: LIQUID CRYSTAL DISPLAY

MAF: MASTER ALARM FACILITY

MCP: MANUAL CALL POINT

MOV: METAL OXIDE VARISTOR (TRANSIENT PROTECTION)

NIC: NETWORK INTERFACE CARD

N/C: NORMALLY CLOSED RELAY CONTACTS

N/O: NORMALLY OPEN RELAY CONTACTS

N/W: NETWORK

PCB: PRINTED CIRCUIT BOARDS

P/S: POWER SUPPLY

PSM: POWER SUPPLY MODULE

REM: REMOTE

SPOT: SINGLE PERSON OPERATING TEST

TB: TERMINAL BLOCK

VDC: DIRECT CURRENT VOLTS

Page 44: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

41

17 Definitions Addressable system - a fire alarm and detection system that contains addressable alarm zone facilities or addressable control devices.

Alarm Verification Facility (AVF) - that part of the FACP, which provides an automatic resetting function for spurious alarm signals so that they will not inadvertently initiate Master Alarm Facility (MAF), or ACF functions. Using ConfigManager prior to downloading to the FireFinder™ sets this option

Alarm zone - the specific portion of a building or complex identified by a particular alarm zone facility.

Alarm Zone Circuit (AZC) - the link or path that carries signals from an actuating device(s) to an alarm zone facility(s).

Alarm Zone Facility (AZF) - that part of the control and indicating equipment that registers and indicates signals (alarm and fault) received from its alarm zone circuit. It also transmits appropriate signals to other control and indicating facilities.

Alert signal - an audible signal or combination of audible and visible signals, from the occupant warning system to alert wardens and other nominated personnel as necessary to commence prescribed actions.

Ancillary Control Facility (ACF) - that portion of the control and indicating equipment that on receipt of a signal initiates predetermined actions in external ancillary devices.

Ancillary equipment - remote equipment connected to FACP.

Ancillary relay - relay within FACP to operate ancillary equipment.

Ancillary output - output for driving ancillary equipment.

Approved and approval - approved by, or the approval of, the Regulatory Authority concerned.

Card-detect link - a link on a module connector to indicate the disconnection of the module.

Conventional System - is a fire detection system using a dedicated circuit for each alarm zone.

Distributed system - a fire alarm and detection system where sections of the control and indicating equipment are remotely located from the FACP or where sub-indicator panel(s) communicate with a main FACP.

Field connections - are connections made to FACP or ancillary equipment during installation.

Fire alarm system - an arrangement of components and apparatus for giving an audible, visible, or other perceptible alarm of fire, and which may also initiate other action.

Fire detection system - an arrangement of detectors and control and indicating equipment employed for automatically detecting fire and initiating other action as arranged.

Fire Alarm Control Panel (FACP) - a panel on which is mounted an indicator or indicators together with associated equipment for the fire alarm or sprinkler system.

Fire resisting - an element of construction, component or structure which, by requirement of the Regulatory Authority, has a specified fire resistance.

Indicating equipment - the part of a fire detection and or alarm system, which provides indication of any warning signals (alarm and fault), received by the control equipment.

Interface - The interconnection between equipment that permits the transfer of data.

Main equipment - equipment essential to the operation of the system including, control equipment, amplification equipment and power supply modules.

Master Alarm Facility (MAF) - that part of the equipment which receives alarm and fault signals from any alarm zone facility and initiates the common signal (alarm and/or fault) for transmission to the fire control station. Bells and other ancillary functions may be initiated from this facility.

Power Supply - that portion of the FACP which supplies all voltages necessary for its operation.

Regulatory Authority - an authority administering Acts of Parliament or Regulations under such Acts.

Page 45: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

42

18 Quick Reference Guides

SOFTWAREVER E1.2

STATUS

OUTPUTS VOLTAGE

BELLOFF/NORM

WARN SYSOFF/NORM

ACFOFF/NORM

ASEOFF/NORM

ALARMOFF/NORM

FAULTOFF/NORM

BATT V26.8V

CHRGR V27.0V

SYSTEM V27.0V

MENUENTER

MENUENTER

MENUENTER

MENUENTER

PRESS ENTER TO GO TO SUB MENU,SET MENU OR UPDATE PROGRAM

PRESS: MOVE FORWARD ORBACKWARD THROUGH THE MENU

CANCELPRESS CANCEL ATANY TIME TO BACKOUT OF THE MENU

CANCEL

MENUENTER

PRESS THESE KEYSTO SET YES / NO, OFF / ON,OFF NORMAL

LEGEND

FAULTS2 Flt/s

F 1 / 2FIRE FAN

FIRE FANMISSING

FAN CTRLMISSING

MENUENTER

LEGEND:

PRESS ENTERTO GO TO MENU

PRESS TO VIEW DETAILSOF EACH FAULT

CANCELPRESS CANCEL AT ANYTIME TO BACK OUT OFTHE MENU OR STOP TEST

MENUENTER

MENUENTER

F 2 / 2FIRE CTRL

MENUENTER

MENUENTER

1

FAULTS

2

ALARMTEST

ZONE 1TEST

FAULTTEST

WALKTEST

LAMPTEST

ZONE 2TEST

ZONE 3TEST

ZONE 4TEST

ZONE 5TEST

ZONE 6ACTIVE

ZONE 7ACTIVE

ZONE 8ACTIVE

ZONE 1TEST

ZONE 2TEST

ZONE 3TEST

ZONE 4TEST

ZONE 5TEST

ZONE 6TEST

ZONE 7TEST

ZONE 1TEST

ZONE 2TEST

ZONE 3TEST

ZONE 4TEST

ZONE 5TEST

ZONE 6TEST

ZONE 7TEST

ZONE 8TEST

LEGEND:

PRESS TO INCREMENT UP DOWN ZONE NUMBER TO BE TESTED

CANCELPRESS CANCEL AT ANY TIME TO BACK OUT OF THE MENU OR STOP TEST

MENUENTER

MENUENTER

MENUENTER

MENUENTER

MENUENTER

BATTERYTEST

MENUENTER

ZONE 8TEST

PRESS ENTER TO START TEST ( TEST PERFORMED FOR TIMEOUT ) MENUENTER

LAMP>>>>TEST>>>>

MENUENTER

TEST....COMPLETE

WALK TSTZONE 4

CANCELTO END

TEST END5MIN SEC

EXAMPLE OF TESTING ZONE 4

BATT 60s26.8 V

BATT TSTPASS

TEST

3

Page 46: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

43

ALARMYES / NO

RESOUNDYES / NOBUZZER

EARTH MONYES / NO

SW INDICYES / NO

INDICATEYES / NO

INPUTSYES / NO

LAM0 TO 8

CODEAS4428

MENUENTER

LEGEND:

PRESS ENTER TO ACCESS MENU AND UPDATE PROGRAMOR CHANGE MENU

PRESS MOVE FORWARDTHROUGH THE MENU

PRESS: MOVE FORWARDOR BACKWARDTHROUGH THE MENU

CANCELPRESS CANCEL ATANY TIME TO BACKOUT OF THE MENU

MENUENTER

MENUENTER

PRESS THESE KEYSTO SET YES / NO

YES

MENUENTER

UPDATE PROGRAM

FACTORY SETCAN NOT BECHANGED

EXAMPLESET RESOUND TO YESTHEN MOVE TO ALARM

MOVE TO ALARMYES / NO

SYSTEMENTERPASSWORD

MENUENTER

5FACTORY DEFAULTPASSWORD IS 3333

PASSWORD0000

MENUENTER

PASSWORD3000

PASSWORD3300

PASSWORD3330

MENUENTER

PASSWORDACCEPTED

EXAMPLE OFENTERING

PASSWORD3333

SYSTEM

BRIGADEYES / NO

FIRE FANYES / NO

RELAYSYES/ NO

AGENTYES / NO

SOUNDERSYES / NO

IF THESE 4 OPTIONSARE NOT SET TO YESTHEY WILL NOT APPEARIN THE TEST, STATUS ORPROGRAM MENU

PASSWORD3333

Page 47: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

44

AGENT T2AGENT T1SREST 60AVFSELECT

ZONE 1 - 8NORMAL

ZONES

SELECTDAYTIME

CLOCK

OUTPUTS

RELAYS

FIRE FAN

AGENT

SOUNDERS

DISPLAY########

SELECTBELL

ZN 1 TO 8

R# Z-ALRM1 TO 8

ALARMZN 1 TO 8

SETSNDR #

12345678

SELECTWARN

SYSZN 1 TO 8

RELEASESOLENOID

FUNCTION3,4,5 WIRE

SELECTALM OUTZN 1 TO 8

R# SWITCH1 TO 8

MAN DELAY30

RELEASEPYROGEN

SELECTBGD ALM 1ZN 1 TO 8

LCS1

RELEASEMETRON

TO EDIT DISPLAYTEXT USE

Z LABELS

R# Z-FLT1 TO 8

INHIBITZN 1 TO 8

SELECTACF

ZN 1 TO 8

SELECTASE

ZN 1 TO 8

SELECTBGD ALM 2ZN 1 TO 8

RESETBUZZER

R# Z-ISOL1 TO 8

R# I/P1 TO 8

LATCHYES / NO

ACF ISOLYES / NO

PRESS S/WN/O

AUTO DELAY30

EOL10uf

EOLRES 3K3

EOLRES4K7

MENUENTER

LEGEND:

PRESS ENTER TO GO TO SUB MENU, SET MENU OR UPDATE PROGRAM

PRESS MOVE FORWARD THROUGH THE MENU

PRESS MOVE FORWARD / BACKWARD THROUGH THE MENU

CANCEL PRESS CANCEL AT ANY TIME TO BACK OUT OF THE MENU

MENUENTER

MENUENTER

MENUENTER

MENUENTER

MENUENTER

MENUENTER

MENUENTER

MENUENTER

CANCEL

MENUENTER

ACF ISOL

ZONES/C

ZONEALARM

MENUENTER

ZONEFAULT

EOLRES 6K8

EOLRES 10K

PRESS SWN/C

SELECTZONEMENU

ENTER

MENUENTER

ACFISOALTE

ACFISOALTE PRESS ACF TO ISOLATE CIRCUITS EXTERNAL TO FACP

SET0 - 60 SEC

SET0 - 60 SEC

SET1 TO 4

RELEASECONSTANT

TO MOVE THROUGH THEALPHABET / NUMBERS

TO MOVE THROUGHTHE WORD

MENUENTER

EDITTEXT

PRESS SWNONE

MENUENTER

SETZONE #

12345678

MENUENTER

MENUENTER

EDITTEXT

SELECTFAN

1,2,3,4

MENUENTER

LATCH

SELECTRELAY1 TO 8

MENUENTER RESET

MENUENTER

YES

N O

RESET

BUZZER

PROGRAM

MENUENTER

MCP ZONEZ#

MCP ZONEZ#

MENUENTER

8

1

MOVETHROUGHDAY TIME

CHANGEDAY TIME

ASSIGN MCPTO A ZONE

O N

OFF

MENUENTER

1 TO 8

1 TO 8

1 TO 4

MENUENTER UPDATE MENU

O N

OFF

MENUENTER UPDATE MENU CANCEL BACKOUT OF MENU

O N

OFF

MENUENTER UPDATE MENU MENU

ENTER

345

MENUENTER

NOTE:

THESE MENUS ARE ONLYAVAILABLEIF RELAYS, FIRE

FAN, SOUNDERS HAVEBEEN CHANGED TO YES IN

THE SYSTEM MENU

EXAMPLE OF ACTIVATING ZONE TO TURN ON/OFF SELECTED OUTPUT

EXAMPLE OF SELECTING FUNCTION WIRE TO BE USED

NON LATCH

1 TO 8

MENUENTERINDICATE

STYLESELECT

STYLE #X

SET STYLE FROM1 TO MAX AVAILABLE INMODULE

MAX

1

PRESS SWN/O & MECH

AS FACTORYDEFAULT

Agent Notes: If only one trigger zone is allocated a zone then the system will be activated by one zone only.Any trigger zone may be allocated to any zone. However when a trigger zone has been allocatedeg T1 to zone 1 then only the remaining trigger zones T2, T3 or T4 are each available to beallocated one of the remaining detector zones.

If multiple trigger zones are allocated eg T1 - Z1, T2 - Z2, T3 - Z3 then any one zone in alarm willoperate the first stage and any other zone in alarm will operate the second stage.

AGENT T4AGENT T3

INHIBIT LCSBUZZER

NORMALSILENT

Page 48: MAN1563-4 ZoneSense Plus 2008 AS Inst Comm...4 4 Placing the Basic System into Operation 4.1 Unpacking Carefully unpack the ZoneSense PLUS The package should include: Main Card, with

45

19 Front Panel Configuration Labelling ZONE

1

CONFIGURATION

NORM / AVF / NON / SELF / AT1 / AT2

BELL WARN ACF ASE ALARM B ALARM 2 RELAY 1 RELAY 2 RELAY 3 RELAY 4 RELAY 5 RELAY 6 RELAY 7 RELAY 8

NORM / AVF / NON / SELF / AT1 / AT22NORM / AVF / NON / SELF / AT1 / AT23NORM / AVF / NON / SELF / AT1 / AT24NORM / AVF / NON / SELF / AT1 / AT25NORM / AVF / NON / SELF / AT1 / AT26NORM / AVF / NON / SELF / AT1 / AT27NORM / AVF / NON / SELF / AT1 / AT28

SWITCHINPUT

ACF ISOLRESETLATCHING

FUNCTIONINHIBIT ZONES

LATCHINGACF ISOLATE

FAN 1 FAN 2 FAN 3 FAN 4

A / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / I

A / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / I

A / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / I

A / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / I

A / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / I

A / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / I

A / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / I

A / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / IA / F / I

Y / NY / NY / N Y / N

Y / NY / N

Y / NY / NY / N

Y / NY / NY / N

Y / NY / NY / N

Y / NY / NY / N

Y / NY / NY / N

Y / NY / NY / N Y / N

Y / N

3 / 4 / 5 3 / 4 / 5 Y / NY / N

3 / 4 / 5 Y / NY / N

3 / 4 / 5 Y / NY / N

B ALARM 1

AGENT RELEASEAUTO DELAY - SECSMANUAL DELAY - SECSPRESSURE SWITCHNo OF LCS'S

SOLENOID / PYROGEN / METRON0 / 15 / 30 / 60 /

NO / NC / NA1 / 2 / 3 / 4

0 / 15 / 30 / 60 /

SYSSOUNDER

1SOUNDER

2SOUNDER

3SOUNDER

4SOUNDER

5SOUNDER

6SOUNDER

7SOUNDER

8

EOL VALUEMCP ZONE 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 No LAMS 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8

3K3 / 4K7 / 6K8 / 10K / CAP

A

B

CD

E

F

GH

Instructions to Installer A, B, D, F & H Using a permanent marking pen cross out the conditions that do not apply. C, E, & G Using a permanent marking pen cross (X) the box for the option that is set for the Zone.

A Indicates the configuration of each Zone Normal (NORM), AVF, Non-latching (NON), Self latching

(SELF) Agent Trigger 1 (AT1), Agent Trigger 2 (AT2).

B Indicates what EOL value has been selected, what Zone has the FACP MCP been mapped to, and the

number of Mimics controlled by the FACP.

C Indicates what Zones controls what Main Card Outputs.

D Indicates if Zone Alarm ( A ), Fault ( F ) or Isolate ( I ) controls the designated relay, as well as any 16

input or Card input or, any switch / indicator switches and if the ACF Isolate, Reset function or Latching is set.

E Indicates what Zones control what Sounders.

F Indicates the type of Agent Release fitted, the type and duration of delay and the number of Local

Control Stations fitted.

G Indicates what Zone/s activates what Fan/s.

H Indicates what Zone/s Inhibit what Fan/s and the type of wire Function and whether or not latching and /

or ACF Isolate i