    NOVUS PRODUTOS ELETRNICOS LTDA. 1/2

    XLe Model: HE-XE10512 Digital Inputs DC / 12 Digital DC Outputs / 2 Analog Inputs (High Resolution) / 2 Analog Outputs

    1 Specifications

    Digital Input DC

    Inputs per Module 12 (including 4 HSC inputs)

    Input Voltage Range 12 VDC / 24 VDC

    Absolute Max. Voltage 35 VDC Max.

    Input Impedance 10 k

    Input Current Positive Logic Negative Logic

    Lower / Upper Threshold 0.3 mA / 0.8 mA -2.1 mA / -1.6 mA

    Min / Max Upper Threshold 3 VDC / 8 VDC

    OFF to ON Response 1 ms

    ON to OFF Response 1 ms

    HSC Max. Switching Rate

    10 kHz Totalizer/Pulse, Edges

    5 kHz Frequency/Pulse, Width

    2.5 kHz Quadrature

    Digital DC Outputs

    Outputs per Module 12 (2 configurable PWM outputs)

    Commons per Module 1

    Output Type Sourcing / 10 K Pull-Down

    Absolute Max. Voltage 5 A continuous

    Output Protection Short Circuit

    Max. Output Current per point 0.5 A

    Max. Total Current 4 A Continuous

    Min / Max Output Supply Voltage 10 VDC / 30 VDC

    Max. Voltage Drop at RatedCurrent

    0.25 VDC

    Max. Inrush Current 650 mA per Channel

    Min. Load nome

    OFF to ON Response 1 ms

    ON to OFF Response 1 ms

    Output Characteristics Current Sourcing (Pos logic)

    Analog In put s, Hig h Reso lu tio n

    Number of Channels 2

    Input Ranges (Selectable)

    0 - 10 V / 020 mA / 420 mA / 100 mV

    RTD: Pt100

    T/C: J / K / T / N / E / R / S / B

    Safe input voltage range

    10 VDC: -0.5 V to +15 V

    mA: -0.5 V to +6 V

    RTD and T/C: +/- 24 V

    Input Impedance

    (Clamped @ -0.5 V to 12 VDC)

    Current Mode:

    100 / 35 mA max.

    Voltage Mode:

    500 k / 35 mA max.

    Nominal Resolution10 V / 20 mA / 100 mV: 14 Bits

    RTD and T/C: 16 Bits

    % AI full scale10 V / 20 mA / 100 mV: 32000 counts

    RTD and T/C: 20 counts / C

    Max. Over-Current 35 mA

    Open T/C Detect Current 50 nA

    Temperature range

    RTD -200~850 C / -328~1562 F

    J -210~750 C / -346~1382 F

    K / N -240~1370 C / -400~2498 F

    T -240~400C / -400~752 F

    E -200~900 C / -328~1652 F

    B / R / S 0~1600 C / 32~2912 F

    Max. Error at 25C

    (* excluding zero)

    (** After warm up time of onehour)

    mA / 10 V 0.1 %*

    RTD 1 C

    100 mV 0.05 %

    T/C 0.2 %**

    RTD Excitation Current 0.25 mA

    General Specifications

    Required Power (Steady State) 130 mA @ 24 VDC

    Required Power (Inrush) 30 A for 1 ms @ 24 VDC

    Primary Power Range 10 ~30 VDC

    Relative Humidity 5 to 95% Non-condensing

    Clock Accuracy +/- Seven Minutes/Month at 20 C

    Operating Temperature 0 C to +50 C

    Terminal Type Screw Type, 5 mm Removable

    Weight 354 g

    Note: Highest usable frequency for PWM output is 65 kHz

    2 Panel Cut-Out and Dimensions

    Refer to the XLe User Manual for panel box information and a handy checklist ofrequirements.Notes: The tolerance to meet NEMA standards is 0.005 (0.1 mm).

    Max. panel thickness: 5 mm.

    3 Ports / Connectors / Cables

    To Remove Back Cover unscrew 4 screws located on the back of the unit.

    I/O Jumpers: (Not Shown): I/O J umpers (JP) are located internally. To access,remove back cover of unit.

    Wiring Connectors (J1 / J2): I/O Jumpers (JP1 / JP2), and External Jumpers(RS-485) are described in theWiring and Jumperssection of this document.

    Memory Slot: Uses Removable Memory for data logging, screen captures,

    program loading and recipes. NovusPart No.: HE-MC1

    Serial Communic ations: MJ1: (RS-232 / RS-485) Use forCscape programmingand Application-Defined Communications. MJ2: (RS-232 / RS-485) Use forApplication-Defined Communications.

    Power Connector and Can Connector

    4 Serial Communications:

    MJ1: (RS-232 / RS-485) Use forCscape programming and Application-DefinedCommunications.

    MJ2: (RS-232 / RS-485) Use for Application-Defined Communications.

    PINMJ1 Pins MJ2 Pins

    Signal Direction Signal Direction8 TXD OUT TXD OUT7 RXD IN RXD IN6 0 V GROUND 0 V GROUND5 +5 / 60 mA OUT +5 / 60 mA OUT4 RTS OUT TX- OUT3 CTS IN TX+ OUT2 RX- / TX- IN / OUT RX- IN1 RX+ / TX+ IN / OUT RX+ IN

    MJ2 Pinouts in Full and Half Duplex Modes

    PINMJ2 Full Duplex Mode MJ2 Half Duplex ModeSignal Direction Signal Direction

    8 TxD OUT TxD OUT7 RxD IN RxD IN

    6 0 V GROUND 0 V GROUND5 +5 V OUT +5 V OUT4 Tx- OUT Tx- OUT3 Tx+ OUT Tx+ OUT2 Rx- IN Tx- / Rx- IN/OUT

    1 Rx+ IN Tx+ / Rx+ IN/OUT

  • 7/28/2019 Man Xle Hexe105

    2/2

    NOVUS PRODUTOS ELETRNICOS LTDA. 2/2

    5 Wiring and Jumpers

    Wire according to the type of inputs / outputs used, and select the appropriatejumper option.

    Wiring Specifications

    For I/O wiring (discrete): 0.8 mm2(18 AWG) or larger.

    For shielded Analog I/O wiring: 0.8 mm2(18 AWG) or larger.

    For CAN wiring: 0.2 mm2(24 AWG) or larger.

    Use copper conductors in field wiring only, 60/75 C

    Orange Connector (J1)

    J1 OrangeConnector

    Name

    I1 IN 1I2 IN 2

    I3 IN 3

    I4 IN 4

    I5 IN 5

    I6 IN 6I7 IN 7

    I8 IN 8

    H1 HSC1 / IN9

    H2 HSC2 / IN10H3 HSC3 / IN11

    H4 HSC4 / IN12

    NC No connect

    NC No connect0V Ground

    Black Connector (J2)

    J2 BlackConnector

    Name

    0 V Ground

    V + V +NC No connect

    Q12 OUT 12Q11 OUT 11

    Q10 OUT 10Q9 OUT 9

    Q8 OUT 8Q7 OUT 7

    Q6 OUT 6Q5 OUT 5

    Q4 OUT 4Q3 OUT 3

    Q2 OUT 2 / PWM2

    Q1 OUT 1 / PWM 1

    Orange Connector (J3)

    J3 OrangeConnector

    Name

    T1 + IN1 +: T/C / RTD / 100 mV

    T1 - IN1 - : T/C / RTD / 100 mVT2 + IN2 +: T/C / RTD / 100 mV

    T2 - IN2 - : T/C / RTD / 100 mVAQ1 OUT1: 10 V / 4-20 mA

    AQ2 OUT2: 10 V / 4-20 mA0 V GROUND

    MA1 IN1: 0-20 mA / 4-20 mAV1 IN1: 0-10 V

    0 V GROUNDMA2 IN2: 0-20 mA / 4-20 mA

    V2 IN2: 0-10 V0 V GROUND

    Anal og i npu t and out put con nect ios (J3):

    I/O Jumpers Setti ngs (JP1, JP2, JP3 and JP4)

    The jumpers J P1, J P2, J P3 and J P4 are located in the connectors PCB internal tothe controller.

    JP1

    Digital DC Logic Positive Logic (*) Negative Logic

    JP2 JP3

    Analog Input Setting

    T/C 100 mV RTD (Pt100) V / mA (*)

    JP4

    Analog OutputSetting:

    Voltage or CurrentVOLTAGE (V) CURRENT (mA) (*)

    (*) Default

    Notes:

    When using JP2 / JP3 (inputs) or JP4 (output), each channel can beindependently configured. For example, J P2 can be configured for 10 V and J P3can be configuredas an RTD.

    External DIP Switch Settings (or Ju mpers Settings)

    Some XLes have jumpers to set RS-485 port termination, though most use DIPSwitches. The External J umpers or DIP Switches are used for termination of theRS-485 ports. The XLe is shipped un-terminated.

    To terminate, select one of the jumpers shipped with the product and insert itbased upon the option that is desired or, select the switch and configure basedupon the option that is desired.

    6 Safety

    When found on the product, the following symbols specify:

    This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardouslocations only

    WARNING EXPLOSION HAZARD Substitution of components may impair suitability for Class I ,Division 2

    WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has beenswitched off or the area is known to be non-hazardous.

    WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) groundbefore making any other connections.

    WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommendedto fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible.

    WARNING: Replace fuse with the same type and rating to provide protection against risk of fire andshock hazards.

    WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failureindicates a defective condition that will not clear by replacing the fuse.

    WARNING: Only qualified electrical personnel familiar with the construction and operation of thisequipment and the hazards involved should install, adjust, operate, or service this equipment. Readand understand this manual and other applicable manuals in their entirety before proceeding.Failure to observe this precaution could result in severe bodily injury or loss of life.

    7 Technical Support

    For assistance and manual updates, contact Technical Support at the followinglocations:

    e-mail: [email protected]

    You can find the complete documentation at www.novus.com.br.

    DIPSW3: FACTORY USE ONLY (tinybootloader firmware downloading). NOTTO BE USED FOR NORMAL OCSOPERATIN.

    DIPSW2: MJ2 Termination (Default none)DIPSW1: MJ1 Termination (Default none)

    001XLE037-R1

    arning: Consultuser documentation.