Download - Man Xle Hexe105
-
7/28/2019 Man Xle Hexe105
1/2
NOVUS PRODUTOS ELETRNICOS LTDA. 1/2
XLe Model: HE-XE10512 Digital Inputs DC / 12 Digital DC Outputs / 2 Analog Inputs (High Resolution) / 2 Analog Outputs
1 Specifications
Digital Input DC
Inputs per Module 12 (including 4 HSC inputs)
Input Voltage Range 12 VDC / 24 VDC
Absolute Max. Voltage 35 VDC Max.
Input Impedance 10 k
Input Current Positive Logic Negative Logic
Lower / Upper Threshold 0.3 mA / 0.8 mA -2.1 mA / -1.6 mA
Min / Max Upper Threshold 3 VDC / 8 VDC
OFF to ON Response 1 ms
ON to OFF Response 1 ms
HSC Max. Switching Rate
10 kHz Totalizer/Pulse, Edges
5 kHz Frequency/Pulse, Width
2.5 kHz Quadrature
Digital DC Outputs
Outputs per Module 12 (2 configurable PWM outputs)
Commons per Module 1
Output Type Sourcing / 10 K Pull-Down
Absolute Max. Voltage 5 A continuous
Output Protection Short Circuit
Max. Output Current per point 0.5 A
Max. Total Current 4 A Continuous
Min / Max Output Supply Voltage 10 VDC / 30 VDC
Max. Voltage Drop at RatedCurrent
0.25 VDC
Max. Inrush Current 650 mA per Channel
Min. Load nome
OFF to ON Response 1 ms
ON to OFF Response 1 ms
Output Characteristics Current Sourcing (Pos logic)
Analog In put s, Hig h Reso lu tio n
Number of Channels 2
Input Ranges (Selectable)
0 - 10 V / 020 mA / 420 mA / 100 mV
RTD: Pt100
T/C: J / K / T / N / E / R / S / B
Safe input voltage range
10 VDC: -0.5 V to +15 V
mA: -0.5 V to +6 V
RTD and T/C: +/- 24 V
Input Impedance
(Clamped @ -0.5 V to 12 VDC)
Current Mode:
100 / 35 mA max.
Voltage Mode:
500 k / 35 mA max.
Nominal Resolution10 V / 20 mA / 100 mV: 14 Bits
RTD and T/C: 16 Bits
% AI full scale10 V / 20 mA / 100 mV: 32000 counts
RTD and T/C: 20 counts / C
Max. Over-Current 35 mA
Open T/C Detect Current 50 nA
Temperature range
RTD -200~850 C / -328~1562 F
J -210~750 C / -346~1382 F
K / N -240~1370 C / -400~2498 F
T -240~400C / -400~752 F
E -200~900 C / -328~1652 F
B / R / S 0~1600 C / 32~2912 F
Max. Error at 25C
(* excluding zero)
(** After warm up time of onehour)
mA / 10 V 0.1 %*
RTD 1 C
100 mV 0.05 %
T/C 0.2 %**
RTD Excitation Current 0.25 mA
General Specifications
Required Power (Steady State) 130 mA @ 24 VDC
Required Power (Inrush) 30 A for 1 ms @ 24 VDC
Primary Power Range 10 ~30 VDC
Relative Humidity 5 to 95% Non-condensing
Clock Accuracy +/- Seven Minutes/Month at 20 C
Operating Temperature 0 C to +50 C
Terminal Type Screw Type, 5 mm Removable
Weight 354 g
Note: Highest usable frequency for PWM output is 65 kHz
2 Panel Cut-Out and Dimensions
Refer to the XLe User Manual for panel box information and a handy checklist ofrequirements.Notes: The tolerance to meet NEMA standards is 0.005 (0.1 mm).
Max. panel thickness: 5 mm.
3 Ports / Connectors / Cables
To Remove Back Cover unscrew 4 screws located on the back of the unit.
I/O Jumpers: (Not Shown): I/O J umpers (JP) are located internally. To access,remove back cover of unit.
Wiring Connectors (J1 / J2): I/O Jumpers (JP1 / JP2), and External Jumpers(RS-485) are described in theWiring and Jumperssection of this document.
Memory Slot: Uses Removable Memory for data logging, screen captures,
program loading and recipes. NovusPart No.: HE-MC1
Serial Communic ations: MJ1: (RS-232 / RS-485) Use forCscape programmingand Application-Defined Communications. MJ2: (RS-232 / RS-485) Use forApplication-Defined Communications.
Power Connector and Can Connector
4 Serial Communications:
MJ1: (RS-232 / RS-485) Use forCscape programming and Application-DefinedCommunications.
MJ2: (RS-232 / RS-485) Use for Application-Defined Communications.
PINMJ1 Pins MJ2 Pins
Signal Direction Signal Direction8 TXD OUT TXD OUT7 RXD IN RXD IN6 0 V GROUND 0 V GROUND5 +5 / 60 mA OUT +5 / 60 mA OUT4 RTS OUT TX- OUT3 CTS IN TX+ OUT2 RX- / TX- IN / OUT RX- IN1 RX+ / TX+ IN / OUT RX+ IN
MJ2 Pinouts in Full and Half Duplex Modes
PINMJ2 Full Duplex Mode MJ2 Half Duplex ModeSignal Direction Signal Direction
8 TxD OUT TxD OUT7 RxD IN RxD IN
6 0 V GROUND 0 V GROUND5 +5 V OUT +5 V OUT4 Tx- OUT Tx- OUT3 Tx+ OUT Tx+ OUT2 Rx- IN Tx- / Rx- IN/OUT
1 Rx+ IN Tx+ / Rx+ IN/OUT
-
7/28/2019 Man Xle Hexe105
2/2
NOVUS PRODUTOS ELETRNICOS LTDA. 2/2
5 Wiring and Jumpers
Wire according to the type of inputs / outputs used, and select the appropriatejumper option.
Wiring Specifications
For I/O wiring (discrete): 0.8 mm2(18 AWG) or larger.
For shielded Analog I/O wiring: 0.8 mm2(18 AWG) or larger.
For CAN wiring: 0.2 mm2(24 AWG) or larger.
Use copper conductors in field wiring only, 60/75 C
Orange Connector (J1)
J1 OrangeConnector
Name
I1 IN 1I2 IN 2
I3 IN 3
I4 IN 4
I5 IN 5
I6 IN 6I7 IN 7
I8 IN 8
H1 HSC1 / IN9
H2 HSC2 / IN10H3 HSC3 / IN11
H4 HSC4 / IN12
NC No connect
NC No connect0V Ground
Black Connector (J2)
J2 BlackConnector
Name
0 V Ground
V + V +NC No connect
Q12 OUT 12Q11 OUT 11
Q10 OUT 10Q9 OUT 9
Q8 OUT 8Q7 OUT 7
Q6 OUT 6Q5 OUT 5
Q4 OUT 4Q3 OUT 3
Q2 OUT 2 / PWM2
Q1 OUT 1 / PWM 1
Orange Connector (J3)
J3 OrangeConnector
Name
T1 + IN1 +: T/C / RTD / 100 mV
T1 - IN1 - : T/C / RTD / 100 mVT2 + IN2 +: T/C / RTD / 100 mV
T2 - IN2 - : T/C / RTD / 100 mVAQ1 OUT1: 10 V / 4-20 mA
AQ2 OUT2: 10 V / 4-20 mA0 V GROUND
MA1 IN1: 0-20 mA / 4-20 mAV1 IN1: 0-10 V
0 V GROUNDMA2 IN2: 0-20 mA / 4-20 mA
V2 IN2: 0-10 V0 V GROUND
Anal og i npu t and out put con nect ios (J3):
I/O Jumpers Setti ngs (JP1, JP2, JP3 and JP4)
The jumpers J P1, J P2, J P3 and J P4 are located in the connectors PCB internal tothe controller.
JP1
Digital DC Logic Positive Logic (*) Negative Logic
JP2 JP3
Analog Input Setting
T/C 100 mV RTD (Pt100) V / mA (*)
JP4
Analog OutputSetting:
Voltage or CurrentVOLTAGE (V) CURRENT (mA) (*)
(*) Default
Notes:
When using JP2 / JP3 (inputs) or JP4 (output), each channel can beindependently configured. For example, J P2 can be configured for 10 V and J P3can be configuredas an RTD.
External DIP Switch Settings (or Ju mpers Settings)
Some XLes have jumpers to set RS-485 port termination, though most use DIPSwitches. The External J umpers or DIP Switches are used for termination of theRS-485 ports. The XLe is shipped un-terminated.
To terminate, select one of the jumpers shipped with the product and insert itbased upon the option that is desired or, select the switch and configure basedupon the option that is desired.
6 Safety
When found on the product, the following symbols specify:
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardouslocations only
WARNING EXPLOSION HAZARD Substitution of components may impair suitability for Class I ,Division 2
WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has beenswitched off or the area is known to be non-hazardous.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) groundbefore making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommendedto fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire andshock hazards.
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failureindicates a defective condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with the construction and operation of thisequipment and the hazards involved should install, adjust, operate, or service this equipment. Readand understand this manual and other applicable manuals in their entirety before proceeding.Failure to observe this precaution could result in severe bodily injury or loss of life.
7 Technical Support
For assistance and manual updates, contact Technical Support at the followinglocations:
e-mail: [email protected]
You can find the complete documentation at www.novus.com.br.
DIPSW3: FACTORY USE ONLY (tinybootloader firmware downloading). NOTTO BE USED FOR NORMAL OCSOPERATIN.
DIPSW2: MJ2 Termination (Default none)DIPSW1: MJ1 Termination (Default none)
001XLE037-R1
arning: Consultuser documentation.
arning: ElectricalShock Hazard.
mailto:[email protected]:[email protected]:[email protected]