ma6 ma6 grounding fittings all copper alloy ground connectors · 2014. 9. 4. · abg shown on page...

6
MA6 MA6 Effective December, 2007 Copyright 2007 800-621-1506 www.o-zgedney.com Grounding Fittings All Copper Alloy Ground Connectors Specification Grade Type ABG Use: For cable connection parallel or at right angles to pipe or rod. Features: • A high strength corrosion-resistant copper alloy ground connector connecting a ground wire either parallel or at right angles to a ground rod or pipe. • A positive ground is assured by the clamp- ing pressure that can be applied by the high strength silicon bronze U-bolt, nuts and lock washers. • Type ABG connectors are suitable for direct burial. • For ground pipe larger than 1 1 / 2” use Type CG Ground Connector shown on Page MA7. Third Party Certification: UL Listed: E-24264 CSA Certified: 015978 Applicable Third Party Standards: UL Standard: 467 CSA Standard: C22.2 No. 41 NEMA: FB-1 Driven (In.) Conductor Range Catalog Ground Ground AWG/kcmil Dimensions in Inches Number Rod Size Pipe Size Min. Max. L W U B ABG-0204 1 / 2 1 / 4 8 4 1 3 / 16 1 5 / 16 2 3 / 8 ABG-0222 1 / 2 1 / 4 4 2/0 1 3 / 16 1 1 / 2 2 1 / 4 3 / 8 ABG-0304 5 / 8 or 3 / 4 3 / 8 8 4 2 1 5 / 16 2 1 / 8 3 / 8 ABG-0322 5 / 8 or 3 / 4 3 / 8 4 2/0 2 1 1 / 2 2 3 / 8 3 / 8 ABG-0325 5 / 8 or 3 / 4 3 / 8 2/0 250 2 1 7 / 8 2 5 / 8 3 / 8 ABG-0350 5 / 8 or 3 / 4 3 / 8 300 500 2 1 / 2 2 3 / 8 3 1 / 8 1 / 2 ABG-0704 1 1 / 2 or 3 / 4 8 4 2 1 / 4 1 5 / 16 2 1 / 2 3 / 8 ABG-0722 1 1 / 2 or 3 / 4 4 2/0 2 1 / 4 1 1 / 2 2 3 / 4 3 / 8 ABG-0725 1 1 / 2 or 3 / 4 2/0 250 2 1 / 4 1 7 / 8 3 3 / 8 ABG-0750 1 1 / 2 or 3 / 4 300 500 2 3 / 4 2 3 / 8 3 1 / 2 1 / 2 ABG-1104 -- 1 8 4 2 9 / 16 1 5 / 16 2 3 / 4 3 / 8 ABG-1122 -- 1 4 2/0 2 9 / 16 1 1 / 2 3 3 / 8 ABG-1125 --- 1 2/0 250 2 9 / 16 1 7 / 8 3 3 / 8 3 / 8 ABG-1150 -- 1 300 500 3 2 3 / 8 3 3 / 4 1 / 2 ABG-1204 -- 1 1 / 4 8 4 3 1 5 / 16 3 1 / 4 3 / 8 ABG-1222 -- 1 1 / 4 4 2/0 3 1 1 / 2 3 1 / 4 3 / 8 ABG-1225 -- 1 1 / 4 2/0 250 3 1 7 / 8 3 1 / 2 3 / 8 ABG-1250 --- 1 1 / 4 300 500 3 3 / 8 2 3 / 8 4 1 / 8 1 / 2 ABG-1504 -- 1 1 / 2 8 4 3 1 / 8 1 5 / 16 3 1 / 2 3 / 8 ABG-1522 -- 1 1 / 2 4 2/0 3 1 / 8 1 1 / 2 3 7 / 8 3 / 8 ABG-1525 -- 1 1 / 2 2/0 250 3 1 / 8 1 7 / 8 3 3 / 4 3 / 8 ABG-1550 -- 1 1 / 2 300 500 3 9 / 16 2 7 / 16 4 1 / 4 1 / 2 Type ABG at Right Angles Type ABG Parallel Existing Conduit Existing Cable Existing Conduit

Upload: others

Post on 20-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MA6 MA6 Grounding Fittings All Copper Alloy Ground Connectors · 2014. 9. 4. · ABG shown on page MA6. • Type CG connectors are suitable for direct burial. Third Party Certification:

MA6 MA6

Effective December, 2007Copyright 2007

800-621-1506www.o-zgedney.com

Grounding Fittings

All Copper Alloy Ground Connectors Specification Grade

Type ABG

Use:For cable connection parallel or at right angles to pipe or rod.

Features:• A high strength corrosion-resistant copper alloy ground connector connecting a ground wire either parallel or at right angles to a ground rod or pipe.• A positive ground is assured by the clamp-ing pressure that can be applied by the high strength silicon bronze U-bolt, nuts and lock washers.• Type ABG connectors are suitable for direct burial. • For ground pipe larger than 11⁄2” use Type CG Ground Connector shown on Page MA7.

Third Party Certification:UL Listed: E-24264

CSA Certified: 015978

Applicable Third Party Standards:UL Standard: 467CSA Standard: C22.2 No. 41NEMA: FB-1

Driven (In.) Conductor Range Catalog Ground Ground AWG/kcmil Dimensions in Inches Number Rod Size Pipe Size Min. Max. L W U B

ABG-0204 1⁄2 1⁄4 8 4 13⁄16 15⁄16 2 3⁄8 ABG-0222 1⁄2 1⁄4 4 2/0 13⁄16 11⁄2 21⁄4 3⁄8 ABG-0304 5⁄8 or 3⁄4 3⁄8 8 4 2 15⁄16 21⁄8 3⁄8 ABG-0322 5⁄8 or 3⁄4 3⁄8 4 2/0 2 11⁄2 23⁄8 3⁄8 ABG-0325 5⁄8 or 3⁄4 3⁄8 2/0 250 2 17⁄8 25⁄8 3⁄8 ABG-0350 5⁄8 or 3⁄4 3⁄8 300 500 21⁄2 23⁄8 31⁄8 1⁄2 ABG-0704 1 1⁄2 or 3⁄4 8 4 21⁄4 15⁄16 21⁄2 3⁄8 ABG-0722 1 1⁄2 or 3⁄4 4 2/0 21⁄4 11⁄2 23⁄4 3⁄8 ABG-0725 1 1⁄2 or 3⁄4 2/0 250 21⁄4 17⁄8 3 3⁄8 ABG-0750 1 1⁄2 or 3⁄4 300 500 23⁄4 23⁄8 31⁄2 1⁄2

ABG-1104 -- 1 8 4 29⁄16 15⁄16 23⁄4 3⁄8 ABG-1122 -- 1 4 2/0 29⁄16 11⁄2 3 3⁄8 ABG-1125 --- 1 2/0 250 29⁄16 17⁄8 33⁄8 3⁄8 ABG-1150 -- 1 300 500 3 23⁄8 33⁄4 1⁄2

ABG-1204 -- 11⁄4 8 4 3 15⁄16 31⁄4 3⁄8 ABG-1222 -- 11⁄4 4 2/0 3 11⁄2 31⁄4 3⁄8 ABG-1225 -- 11⁄4 2/0 250 3 17⁄8 31⁄2 3⁄8 ABG-1250 --- 11⁄4 300 500 33⁄8 23⁄8 41⁄8 1⁄2

ABG-1504 -- 11⁄2 8 4 31⁄8 15⁄16 31⁄2 3⁄8 ABG-1522 -- 11⁄2 4 2/0 31⁄8 11⁄2 37⁄8 3⁄8 ABG-1525 -- 11⁄2 2/0 250 31⁄8 17⁄8 33⁄4 3⁄8 ABG-1550 -- 11⁄2 300 500 39⁄16 27⁄16 41⁄4 1⁄2

Type ABG at Right Angles Type ABG Parallel

Existing Conduit

Existing Cable

Existing Conduit

Page 2: MA6 MA6 Grounding Fittings All Copper Alloy Ground Connectors · 2014. 9. 4. · ABG shown on page MA6. • Type CG connectors are suitable for direct burial. Third Party Certification:

MA7 MA7

Effective December, 2007Copyright 2007

800-621-1506www.o-zgedney.com

Grounding Fittings

All Copper Alloy Ground Connectors Specification Grade

Type CG

Use:• For cable connection either parallel or at right angle to pipe. • A high strength corrosion-resistant copper alloy ground connector having a reversible contact plate which permits the ground wire to be connected either at right angles or parallel to a ground pipe. • The fitting is designed so that the saddle can be installed before the ground connection is made. • High strength silicon bronze hardware permits high clamping pressures to be applied.• For ground pipe smaller than 2” use Type ABG shown on page MA6.• Type CG connectors are suitable for direct burial.

Third Party Certification:UL Listed: E-24264

CSA Certified: 015978

Applicable Third Party Standards:UL Standard: 467CSA Standard: C22.2 No. 41Fed. Spec: W-F-406E

Ground Conductor Range Catalog Pipe Size AWG/kcmil Dimensions in Inches Number (Inches) Min. Max. L W U B

CG-2004 2 8 4 35⁄8 7⁄8 33⁄4 3⁄8 CG-2022 2 4 2/0 35⁄8 13⁄16 4 3⁄8 CG-2025 2 2/0 250 35⁄8 17⁄16 41⁄8 3⁄8 CG-2050 2 300 500 37⁄8 17⁄8 41⁄2 7⁄16

CG-2604 21⁄2 8 4 41⁄8 7⁄8 41⁄4 3⁄8 CG-2622 21⁄2 4 2/0 41⁄8 13⁄16 41⁄2 3⁄8 CG-2625 21⁄2 2/0 250 41⁄8 17⁄16 43⁄4 3⁄8 CG-2650 21⁄2 300 500 43⁄8 17⁄8 5 7⁄16

CG-3104 3 8 4 43⁄4 7⁄8 413⁄16 3⁄8 CG-3122 3 4 2/0 43⁄4 13⁄16 51⁄8 3⁄8 CG-3125 3 2/0 250 43⁄4 17⁄16 53⁄8 3⁄8 CG-3150 3 300 500 51⁄4 17⁄8 53⁄4 1⁄2 CG-3175 3 550 750

CG-3604 31⁄2 8 4 51⁄4 7⁄8 51⁄4 3⁄8 CG-3622 31⁄2 4 2/0 51⁄4 13⁄16 55⁄8 3⁄8 CG-3625 31⁄2 2/0 250 51⁄4 17⁄16 57⁄8 3⁄8 CG-3650 31⁄2 300 500 53⁄4 17⁄8 61⁄8 1⁄2 CG-3675 31⁄2 550 750

CG-4104 4 8 4 53⁄4 7⁄8 53⁄4 3⁄8 CG-4122 4 4 2/0 53⁄4 13⁄16 61⁄8 3⁄8 CG-4125 4 2/0 250 53⁄4 17⁄16 61⁄8 3⁄8 CG-4150 4 300 500 61⁄4 17⁄8 65⁄8 1⁄2 CG-4175 4 550 750

CG-4622 41⁄2 4 2/0 61⁄4 13⁄16 65⁄8 3⁄8 CG-4625 41⁄2 2/0 250 61⁄4 17⁄16 67⁄8 3⁄8 CG-4650 41⁄2 300 500 63⁄8 17⁄8 71⁄4 1⁄2

CG-5122 5 4 2/0 67⁄8 13⁄16 71⁄8 3⁄8 CG-5125 5 2/0 250 67⁄8 17⁄16 73⁄8 3⁄8 CG-5150 5 300 500 71⁄4 17⁄8 73⁄4 1⁄2 CG-5175 5 550 750

CG-6122 6 4 2/0 8 13⁄16 81⁄4 3⁄8 CG-6125 6 2/0 250 8 17⁄16 81⁄2 3⁄8 CG-6150 6 300 500 83⁄8 17⁄8 87⁄8 1⁄2 CG-6175 6 550 750 83⁄8 23⁄8 93⁄8 1⁄2 CG-6192 6 800 1000 83⁄8 23⁄8 93⁄8 1⁄2

CG-8125 8 2/0 250 10 17⁄16 101⁄2 3⁄8 CG-8150 8 300 500 103⁄8 17⁄8 107⁄8 1⁄2 CG-8175 8 550 750 CG-8192 8 800 1000

L

W

Type CG

Existing Ground

Pipe

Existing Cable

Page 3: MA6 MA6 Grounding Fittings All Copper Alloy Ground Connectors · 2014. 9. 4. · ABG shown on page MA6. • Type CG connectors are suitable for direct burial. Third Party Certification:

MA8 MA8

Effective December, 2007Copyright 2007

800-621-1506www.o-zgedney.com

Grounding Fittings

All Copper Alloy Ground Connectors Specification Grade

Type TG

Use:This ground connector is used for grounding “H” column fence posts. Its design eliminates the need for drilling the post.To attach, loosen the nut sufficiently to allow the end of the “J” bolt to slip over the flange, assemble the cable into the fitting and then tighten.

Material/Finish:The current carrying parts are of cast copper alloy. The “J” bolt, nut and washer are Hot Dip Galvanized steel.

Third Party Certification:CSA Certified: 015978

Applicable Third Party Standards:CSA Standard: C22.2 No. 41

Type RGFor braid or copper bar to pipe.

Use:This Ground Connector is designed to connect flat copper braid or copper bar to a pipe. A copper alloy body and silicon bronze bolt, nut and lock washers, combine strength and corrosion-resistance, insuring a positive mechanical and electrical connection.

Third Party Certification:UL Listed: E-24264

CSA Certified: 015978

Applicable Third Party Standards:UL Standard: 467CSA Standard: C22.2 No. 41Fed. Spec: W-F-406E

Notes:Sizes are for braid or copper bar 1” Max.Suitable for direct burial application.

Ground Catalog Pipe Size Dimensions in Inches Number (Inches) L W U B

RG-07 1⁄2 or 3⁄4 21⁄4 11⁄4 21⁄2 3⁄8 RG-11 1 25⁄8 13⁄8 213⁄16 3⁄8 RG-12 11⁄4 3 13⁄8 31⁄8 3⁄8 RG-15 11⁄2 31⁄8 13⁄8 31⁄2 3⁄8

RG-20 2 35⁄8 13⁄8 37⁄8 3⁄8 RG-26 21⁄2 41⁄8 13⁄8 43⁄8 3⁄8 RG-31 3 43⁄4 13⁄8 5 3⁄8 RG-36 31⁄2 51⁄4 13⁄8 51⁄2 3⁄8

RG-41 4 53⁄4 13⁄8 6 3⁄8 RG-51 5 73⁄16 15⁄8 71⁄4 3⁄8 RG-61 6 81⁄4 15⁄8 73⁄4 3⁄8

Conductor Range “H” Column Catalog Min. Max. Fence Post Dim. in Inches Number Solid Str. Min. Max. L W B

TG-24 4 4/0 1.31 1.95 41⁄8 1 3⁄8

Type TG

Type RG

Existing I-Beam

Existing Cable

Existing Ground

Pipe

Existing Braid

Page 4: MA6 MA6 Grounding Fittings All Copper Alloy Ground Connectors · 2014. 9. 4. · ABG shown on page MA6. • Type CG connectors are suitable for direct burial. Third Party Certification:

MA9 MA9

Effective December, 2007Copyright 2007

800-621-1506www.o-zgedney.com

Grounding Fittings

All Copper Alloy Ground Connectors Specification GradeType KGTwo-piece design

Use:This ground connector is designed to connect a ground wire to any flat surface. Copper alloy body and silicon bronze bolt, nut and lock washer, with the Interlocking clamp, combine strength and corrosion-resistance, insuring a positive ground connection. HEX-CUP construction of the fitting, simplifies installation by requiring only a single wrench for tightening.

Third Party Certification:CSA Certified: 015978

Applicable Third Party Standards:CSA Standard: C22.2 No. 41

Note:Bolts furnished will fasten connector to plate up to 1⁄4” thick. Longer bolts will be furnished when nec-essary if plate thickness is specified. Contact your local representative.

Conductor Range Catalog AWG/kcmil Dimensions in Inches Number Min. Max. L W H B

KG-04 8 4 11⁄8 11⁄8 13⁄8 3⁄8 KG-22 4 2/0 15⁄8 11⁄4 13⁄4 3⁄8 KG-25 2/0 250 2 13⁄8 21⁄16 7⁄16

KG-50 300 500 23⁄8 11⁄2 29⁄16 1⁄2 KG-75 550 750 27⁄8 13⁄4 27⁄8 5⁄8 KG-92 800 1000 33⁄8 2 31⁄8 5⁄8

Type KGMOne-piece design

Use:An economical ground connector for connecting a ground wire to any flat surface. Copper alloy body and silicon bronze bolt, nut and lock washer combine strength and corrosion-resistance to insure a positive ground connection. HEX-CUP construction of the fitting simplifies installation by requiring only a single wrench for tightening

Note:Bolts furnished will fasten connector to plate up to 1⁄4” thick. Longer bolts will be furnished when necessary if plate thickness is specified. Contact your local representative.

Conductor Range Catalog AWG/kcmil Dimensions in Inches Number Min. Max. L W H B

KGM-04 8 4 11⁄8 11⁄8 13⁄8 3⁄8 KGM-22 4 2/0 15⁄8 11⁄4 15⁄8 3⁄8 KGM-25 2/0 250 2 13⁄8 113⁄16 7⁄16

KGM-50 300 500 23⁄8 11⁄2 25⁄16 1⁄2 KGM-75 550 750 27⁄8 13⁄4 25⁄8 5⁄8 KGM-92 800 1000 33⁄8 2 27⁄8 5⁄8

Type KG

Type KGM

Existing Cable

Existing Cable

Page 5: MA6 MA6 Grounding Fittings All Copper Alloy Ground Connectors · 2014. 9. 4. · ABG shown on page MA6. • Type CG connectors are suitable for direct burial. Third Party Certification:

MA10 MA10

Effective December, 2007Copyright 2007

800-621-1506www.o-zgedney.com

Grounding Fittings

All Copper Alloy Ground ConnectorsSpecification Grade Type LGOne bolt

Type MGTwo bolts

Use:For connecting two parallel cables of the same or varying sizes to any flat surface. Installation of connectors is simplified by HEX-CUP construction. Cables are gripped by the interlocking clamp, used throughout the line of ground devices. Copper alloy body and silicon bronze bolts, nuts and lock washers make a completely corrosion resistant fitting and permit high pressure to be applied - insuring a positive ground con-nection. The two Types LG and MG differ only in the number of fastening bolts as shown.

Third Party Certification:Type MGUL Listed: E-24264 Type MG & Type LGCSA Certified: 015978

Applicable Third Party Standards:UL Standard: 467CSA Standard: C22.2 No. 41

Note:Bolts furnished will fasten connector to plate up to 1⁄4” thick. Longer bolts will be furnished when necessary if plate thickness is specified. Contact your local representative.

Suitable for direct burial.

Conductor Range Catalog AWG/kcmil Dimensions in Inches Number Min. Max. L W H B

LG-04 8 4 11⁄8 11⁄8 13⁄8 3⁄8 LG-22 4 2/0 13⁄4 11⁄4 13⁄4 3⁄8 LG-25 2/0 250 21⁄8 11⁄2 21⁄16 7⁄16

LG-50 300 500 27⁄8 13⁄4 29⁄16 1⁄2

LG-75 550 750 31⁄2 2 27⁄8 5⁄8 LG-92 800 1000 37⁄8 21⁄4 31⁄8 5⁄8

Conductor Range Catalog Either Side Dimensions in Inches Number Min. Max. L W H B C

MG-04 8 4 11⁄8 11⁄2 13⁄8 5⁄16 7⁄8

MG-22 4 2/0 13⁄4 13⁄4 13⁄4 3⁄8 1 MG-25 2/0 250 21⁄8 13⁄4 21⁄16 3⁄8 1 MG-50 300 500 27⁄8 21⁄8 29⁄16 7⁄16 11⁄4

MG-75 550 750 31⁄2 23⁄8 27⁄8 1⁄2 13⁄8 MG-92 800 1000 37⁄8 3 31⁄8 5⁄8 15⁄8

Type MG are suitable for direct burial.

WC

LB

W H

LB

Type LG Type MG

Existing Cable

Page 6: MA6 MA6 Grounding Fittings All Copper Alloy Ground Connectors · 2014. 9. 4. · ABG shown on page MA6. • Type CG connectors are suitable for direct burial. Third Party Certification:

MA11 MA11

Effective December, 2007Copyright 2007

800-621-1506www.o-zgedney.com

Grounding Fittings

All Copper Alloy Ground Connectors Specification Grade

Type QG

Use:This Ground Connector affords a means of connecting a cable to a flat surface. The ground conductor is looped in the groove of the fitting and clamped securely by the pressure plate. The high copper content of this fitting insures high conductivity and the silicon bronze bolt, nut and lock washer complete the corrosion-resistant fitting.

Third Party Certification:UL Listed: E-24264

CSA Certified: 015978

Applicable Third Party Standards:UL Standard: 467CSA Standard: C22.2 No. 41

Note:Bolts furnished will fasten connector to plate up to 1⁄4” thick. Longer bolts will be furnished when necessary if plate thickness is specified. Contact your local representative.

Suitable for direct burial.

Conductor Range Catalog AWG/kcmil Dimensions in Inches Number Min. Max. B L W H

QG-01 8 1 3⁄8 13⁄8 13⁄8 11⁄8 QG-21 6 1/0 3⁄8 19⁄16 19⁄16 11⁄4 QG-24 1 4/0 1⁄2 2 2 11⁄2 QG-30 1/0 300 1⁄2 23⁄8 23⁄8 13⁄4

Type VG

Use:These ground connectors are attached to a ground cable in the floor or wall base, and after the concrete is poured a 2” x 2” flat plate is left exposed flush with the surface. The connectors may be located at pre-determined locations, or if set at intervals throughout the floor or wall base, a ground pad id always readily available for grounding electrical equipment.

Third Party Certification:UL Listed: E-24264

Applicable Third Party Standards:UL Standard 467

Note:Suitable for direct burial.

Conductor Range Catalog AWG/kcmil Dimensions in Inches Number Min. Max. A B C E

*VG-21-2 4 1/0 2 211⁄16 21⁄8 13⁄8 *VG-24-2 2/0 4/0 2 211⁄16 21⁄8 13⁄8 *VG-50-2 250 500 2 213⁄16 21⁄4 2 *VG-92-2 750 1000 2 3 25⁄8 2

**VG-21-4 4 1/0 2 211⁄16 21⁄8 13⁄8 **VG-24-4 2/0 4/0 2 211⁄16 21⁄8 13⁄8 **VG-50-4 250 500 2 213⁄16 21⁄4 2 **VG-92-4 750 1000 2 3 25⁄8 2

*Two Tapped Holes**Four Tapped Holes

H

B

Type QG

Type VG

Existing Cable