m-001 · m-001 mechanical coversheet m-201 first floor mechanical plan m-201a alt. first floor...

20
PNEUMATIC - ELECTRIC SWITCH SIGHT GLASS AFS AFS PE PIPE GUIDE EXPANSION JOINT THERMOMETER PIPE ANCHOR AIR VENT W/COCK ORIFICE PLATE PRESSURE GAGE W/COCK FLEXIBLE CONNECTOR EQUIPMENT DESIGNATION EQUIPMENT SYMBOL (SEE SCHEDULE) SYSTEM NUMBER IF APPLICABLE EQUIPMENT REFERENCE NUMBER CONICAL TEE ROUND DUCTWORK LATERAL CONNECTION ROUND DUCTWORK SPIN COLLAR CONN SUPPLY BRANCH WITH XX XX XX XX EQUIPMENT REFERENCE NUMBER EQUIPMENT SYMBOL (SEE SCHEDULE) EQUIPMENT DESIGNATION XX FLEXIBLE DUCTWORK DESIGNATION - OMIT AND CONSTRUCTION IF DUCT MATERIALS AIR FLOW STATION DUCT PRESSURE CLASS SP SECURITY PENETRATION SCHEDULE IS USED SP 1/2"x1/2" WIRE MESH OED W/ WMS OED W/ WMS OPEN END DUCT W/ SCREEN CLOSURE & CONDENSATE PUMP CP SUPPLY REGISTER SR SLOT DIFFUSER SD HEAT EXCHANGER HE PORTABLE SMOKE COLLECTOR PSC REGISTER R SLOT DIFFUSER RETURN SDR VEHICLE FUME EXHAUST VARIABLE AIR VOLUME BOX VVR HEATING COIL HC H HUMIDIFIER GRILLE G D DIFFUSER FAN FILTER UNITS FFU FORCED FLOW HEATER FFH CABINET UNIT HEATER CUH MIXING BOX PUMP PRE-FILTER PREHEAT COIL MAKE-UP AIR HEATER OUTSIDE AIR INTAKE RELIEF VALVE UNIT HEATER PRESSURE REDUCING VALVE PACKAGED TERMINAL AIR CONDITIONER VARIABLE AIR VOLUME BOX-FAN POWERED WALL FIN RADIATION P CONDITIONING UNIT COOLING TOWER CRITICAL ROOM AIR CLEAN STEAM GENERATOR VF FAN DUCTLESS AIR CONDITIONER DUCT COIL DEHUMIDIFIER DUST COLLECTOR CABINET FAN COIL UNIT FLOW METER FUEL OIL PUMP FLASH TANK ELECTRIC UNIT HEATER CSG CT DAC DC DEH DCC EUH F FCU FM FT FOP CRAC VFE WF PRV PTAC RV UH MB MAH OAI PF PHC RELIEF HOOD RH SP T SDT SD HEATING & VENTILATING UNIT HV END OF MAIN DRIP EMD HIGH EFFICIENCY HEAT PUMP HIGH EFFICIENCY FILTER PARTICULATE AIR FILTER HEAT RECOVERY COIL HEAT RECOVERY UNIT HEAT TRANSFER PACKAGE V RS TRAP AIR COOLED CONDENSING UNIT AIR COOLED CONDENSER ACC ACCU BOILER AIR FLOW STATION AIR HANDLING UNIT BOILER FEED PUMP BOILER FEED SET CONVECTOR CHARCOAL FILTER CHILLER COOLING COIL AFS AHU BFP BFS C B CF CH CC PACKAGED AIR CONDITIONING UNIT AC HTP HRU HRC HP HEPA HEF BUCKET TRAP REFRIGERANT SUCTION CONCENTRIC REDUCER FLOAT AND THERMOSTATIC ECCENTRIC REDUCER ELBOW - DOWN BOTTOM TAKE-OFF TOP TAKE-OFF ELBOW - UP VENT LINE R RELAY THERMOSTAT T TEMPERATURE SENSOR STATIC PRESSURE SENSOR DUCT SMOKE DETECTOR SMOKE DAMPER TEMPERATURE SENSOR W/ REMOTE BULB T GAS SHUT OFF COCK GLOBE VALVE BALANCING VALVE BALL VALVE CHECK VALVE BUTTERFLY VALVE SOLENOID VALVE PRESSURE REDUCING VALVE THERMAL EXPANSION VALVE BUTTERFLY CONTROL VALVE 2-WAY CONTROL VALVE 3-WAY CONTROL VALVE BACK PRESSURE VALVE ANGLE GATE VALVE RELIEF OR SAFETY VALVE FLOW SETTER STRAINER W/BLOW-OFF STRAINER GATE VALVE 24x36 36x14Ø X T THERMOSTAT S H XX P L L PLENUM LIGHT PRESSURE SENSOR HUMIDISTAT SWITCH SHEET KEY NOTE NEW CONNECTION TO EXISTING AIR UP NEW WORK AIR DOWN OR DROP IN 36x14Ø UP DN 24x36 BRANCH CONNECTION 45°ELBOW (NO VANES) SUPPLY OR RETURN EXHAUST OR RETURN DUCT INCLINED RISE DIRECTION OF FLOW 90° ELBOW WITH TURNING VANES RECTANGULAR DUCT SIZE (FIRST FIGURE-SIDE SHOWN) (FIRST FIGURE-SIDE SHOWN) FLAT OVAL DUCT SIZE DIRECTION OF FLOW ROUND DUCT UP ROUND DUCT DOWN SUPPLY AIR DOWN EXHAUST OR RETURN SUPPLY AIR UP H T HUMIDITY SENSOR TEMPERATURE SENSOR S UNION T AD TYPE CFM AUTOMATIC DAMPER EXHAUST OR RETURN REGISTER GRILLE BDD FD SD FSD H T BACK DRAFT DAMPER SMOKE DAMPER WITH FIRE DAMPER WITH ACCESS DOOR ACCESS DOOR SENSOR DUCT TEMPERATURE COMBINATION FIRE & SMOKE DAMPER WITH ACCESS DOOR DUCT HUMIDITY SENSOR BALANCING DAMPER CFM TYPE AD V BDD FD SD FSD H T UP DN & CAP ADR SDT FLEXIBLE CONNECTION ACCESS DOOR DUCT SMOKE DETECTOR ADR SDT EXISTING TO REMAIN TYPE CFM DIFFUSER DIFFERENTIAL PRESSURE SWITCH DPS HL NC NO H DPT EP ES FZ FS HOA MS GLYCOL WATER RETURN GLYCOL WATER SUPPLY GWS GWR BBD CHWS CA CF BF D CHWR HG CWS CWR HPR HPS HWR LPR LPS LPCS HWS PCR MU MPS RL MPR MEDIUM PRESSURE CONDENSATE RETURN MEDIUM PRESSURE STEAM SUPPLY PUMPED CONDENSATE RETURN MAKE UP WATER REFRIGERANT LIQUID CONDENSATE DRAIN OR DRAIN CONDENSER WATER RETURN CONDENSER WATER SUPPLY HIGH PRESSURE CONDENSATE RETURN HIGH PRESSURE STEAM SUPPLY HEATING WATER RETURN HEATING WATER SUPPLY LOW PRESSURE CLEAN STEAM LOW PRESSURE CONDENSATE RETURN LOW PRESSURE STEAM SUPPLY CHILLED WATER RETURN HOT GAS BOILER BLOWDOWN CHILLED WATER SUPPLY DIRECTION OF FLOW BOILER FEED WATER COMPRESSED AIR CHEMICAL FEED DIRECTION OF SLOPE (DOWN) MS H HUMIDITY SENSOR W/ REMOTE BULB HIGH LIMIT SWITCH FLOW SWITCH HUMIDISTAT FREEZESTAT HUMIDITY SENSOR END SWITCH HAND-OFF-AUTOMATIC SWITCH MOTOR STARTER WITH DIFFERENTIAL PRESSURE TRANSMITTER ELECTRIC - PNEUMATIC SWITCH PRESSURE SENSOR NORMALLY CLOSED NORMALLY OPEN MOTOR STARTER MOTOR HAND-OFF-AUTOMATIC SWITCH H O A H M P CS DO AFS EXISTING TO BE REMOVED NEW WORK EXISTING TO REMAIN CURRENT SENSOR DAMPER OPERATOR AIRFLOW STATION DUCT WITH INTERNAL LINING SHEET NOTE (NUMBER), APPLIES ONLY ON THE SHEET IT APPEARS ON EXISTING TO BE REMOVED DIFFUSER W/TOP BOX TRANSITION CO2 CARBON DIOXIDE SENSOR MAKE UP AIR UNIT MAU VP DO FAN WITH AIRFLOW STATION FAN WITH INLET VANES VP VFD ATC ON-OFF SWITCH 3 POSITION SWITCH INDICATING LIGHT GAGE VARIABLE FREQUENCY DRIVE CRT DISPLAY PC WITH PRINTER AUTOMATIC TEMPERATURE CONTROL PANEL VELOCITY PRESSURE SENSOR REFERENCE STATIC PRESSURE BALANCING DAMPER BD POUNDS PER HOUR LBS/HR OPPOSABLE BLADE DAMPER OBD AUTOMATIC TEMPERATURE CONTROLS ATC CONNECTION POINT TO PACKAGED EQUIPMENT TOTAL STATIC PRESSURE TSP MISCELLANEOUS SYMBOLS SYMBOL DESCRIPTION DOUBLE LINE DESCRIPTION SINGLE LINE SYMBOL DESCRIPTION SYMBOL DESCRIPTION NOTE: NOT ALL SYMBOLS INDICATED MAY APPEAR ON THESE CONTRACT SHEETS DUCTWORK SYMBOLS DRAWING LEGEND PIPING SYMBOLS CONTROL DIAGRAM SYMBOLS SCHEDULED EQUIPMENT DESIGNATION DESCRIPTION GENERAL NOTES TECHNICAL TERMS DESIGNATION DESCRIPTION TYPE CFM NOTE: NOT ALL SYMBOLS INDICATED MAY APPEAR ON THESE CONTRACT SHEETS NOTE: NOT ALL SYMBOLS INDICATED MAY APPEAR ON THESE CONTRACT SHEETS NOTE: NOT ALL SYMBOLS INDICATED MAY APPEAR ON THESE CONTRACT SHEETS NOTE: NOT ALL SYMBOLS INDICATED MAY APPEAR ON THESE CONTRACT SHEETS NOTE: NOT ALL SYMBOLS INDICATED MAY APPEAR ON THESE CONTRACT SHEETS BLOWER COIL UNIT BCU UNIT VENTILATOR UV EXPANSION TANK XT EXHAUST LOUVER DRUM LOUVER EF DL REGISTER GRILLE RG RETURN EXHAUST REGISTER RR LINEAR SLOT LS REMOVABLE FRAME DEMOLITION ENDPOINT CEILING DIFFUSER CD PARALLEL BLADE DAMPER PBD FM FLOW METER IA INSTRUMENT AIR PRESSURE DIFFERENTIAL (STEAM TRAPS) PSID SMOKE EXHAUST FAN SEF RADIANT HEATING PANEL RHP ROOF TOP UNIT RTU DEDICATED OUTSIDE AIR SYSTEM DOAS DO PRESSURE CONTROL VALVE VAV BOX (COOLING ONLY) VAV BOX (WITH HW COIL) LAB EXHAUST FAN LEF BLAST GATE B/G BD CO2 CO2 SENSOR T CFM TRANSFER AIR V 1. DUCTWORK AND PIPING SHOWN INDICATES CONNECTION TO EQUIPMENT USED FOR BASIS OF DESIGN. COORDINATE DUCTWORK AND PIPING CONNECTIONS WITH ACTUAL EQUIPMENT PROVIDED. 2. STRUCTURAL SUPPORTS AND CONCRETE PADS SHOWN INDICATE SIZES REQUIRED FOR EQUIPMENT USED FOR BASIS OF DESIGN. COORDINATE SUPPORT AND PAD SIZES WITH ACTUAL EQUIPMENT PROVIDED. 3. CONTRACTOR SHALL INSTALL ALL AUTOMATIC CONTROL DEVICES (AUTOMATIC DAMPERS, CONTROL VALVES, FLOW METERS, TEMPERATURE SENSING WELLS ETC.) IN DUCTWORK AND PIPING AS INDICATED ON THESE DRAWINGS AND AS REQUIRED FOR A COMPLETE AND OPERATING SYSTEM. 4. ALL CONSTRUCTION MATERIALS & DEBRIS OF ANY KIND SHALL BE COMPLETELY REMOVED FROM ALL PLENUMS PRIOR TO SUBSTANTIAL COMPLETION OF PROJECT. CONSULTANTS PROJECT IDENTIFICATION ISSUE BLOCK PROJECT NO.: DESIGNED BY: DRAWN BY: CHECKED BY: APPROVED BY: COPYRIGHT: SHEET TITLE SEALS A B C 3019039 MARK DATE DESCRIPTION BY D E 3 2 4 5 6 1 PRPA VMF KITTY HAWK AVE. PHILADELPHIA, PA 3 2 4 5 6 1 STV 205 West Welsh Drive Douglassville, PA 19518 t 610.385.8200 f 610.385.8500 www.stvinc.com 0 02/23/18 FINAL BRIDGING DOCS KDB G. KAUR J. HELHOWSKI K. BOMBOY G. KAUR MECHANICAL COVERSHEET M-001 MECHANICAL SHEET LIST M-001 MECHANICAL COVERSHEET M-201 FIRST FLOOR MECHANICAL PLAN M-201A ALT. FIRST FLOOR MECHANICAL PLAN M-202 ENLARGED OFFICE MECHANICAL PLANS M-203A RADIANT FLOOR PLAN M-401 ENLARGED MECHANICAL ROOM PLAN M-501 MECHANICAL DETAILS M-502 MECHANICAL DETAILS M-503 MECHANICAL SCHEDULES M-504 MECHANICAL SCHEDULES M-505 MECHANICAL AIRFLOW RISER DIAGRAM M-505A ALT. MECHANICAL AIRFLOW RISER DIAGRAM M-506 HOT WATER DIAGRAMS M-507 ERU CONTROL DIAGRAM M-508 H&V UNIT CONTROL DIAGRAM M-509 AHU CONTROL DIAGRAM M-510 HEATING HOT WATER CONTROL DIAGRAMS M-511A RADIANT FLOOR CONTROL DIAGRAM M-512 VAV CONTROL DIAGRAMS M-513 MISCELLANEOUS MECHANICAL CONTROL DIAGRAMS FAN POWERED BOX FPB WIRE MESH SCREEN WMS

Upload: trinhbao

Post on 08-Jul-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

PNEUMATIC - ELECTRIC SWITCH

SIGHT GLASS

AFSAFS

PE

PIPE GUIDE

EXPANSION JOINT

THERMOMETER

PIPE ANCHOR

AIR VENT W/COCK

ORIFICE PLATE

PRESSURE GAGE W/COCK

FLEXIBLE CONNECTOR

EQUIPMENT DESIGNATION

EQUIPMENT SYMBOL (SEE SCHEDULE)

SYSTEM NUMBER IF APPLICABLE

EQUIPMENT REFERENCE NUMBER

CONICAL TEEROUND DUCTWORK

LATERAL CONNECTIONROUND DUCTWORK

SPIN COLLAR CONNSUPPLY BRANCH WITH

XX

XXXX

XX

EQUIPMENT REFERENCE NUMBER

EQUIPMENT SYMBOL (SEE SCHEDULE)

EQUIPMENT DESIGNATION

XX

FLEXIBLE DUCTWORK

DESIGNATION - OMIT

AND CONSTRUCTIONIF DUCT MATERIALS

AIR FLOW STATION

DUCT PRESSURE CLASS

SP

SECURITY PENETRATION

SCHEDULE IS USEDSP

1/2"x1/2" WIRE MESHOED W/ WMS OED W/ WMSOPEN END DUCT W/

SCREEN CLOSURE &

CONDENSATE PUMPCP

SUPPLY REGISTERSR

SLOT DIFFUSERSD

HEAT EXCHANGERHE

PORTABLE SMOKE COLLECTORPSC

REGISTERR

SLOT DIFFUSER RETURNSDR

VEHICLE FUME EXHAUST

VARIABLE AIR VOLUME BOXVVR

HEATING COILHCH HUMIDIFIER

GRILLEG

D DIFFUSER

FAN FILTER UNITSFFUFORCED FLOW HEATERFFH

CABINET UNIT HEATERCUH

MIXING BOX

PUMPPRE-FILTERPREHEAT COIL

MAKE-UP AIR HEATER

OUTSIDE AIR INTAKE

RELIEF VALVE

UNIT HEATER

PRESSURE REDUCING VALVE

PACKAGED TERMINAL AIR CONDITIONER

VARIABLE AIR VOLUME BOX-FAN POWERED

WALL FIN RADIATION

P

CONDITIONING UNIT

COOLING TOWER

CRITICAL ROOM AIR

CLEAN STEAM GENERATOR

VF

FAN

DUCTLESS AIR CONDITIONERDUCT COIL

DEHUMIDIFIERDUST COLLECTOR CABINET

FAN COIL UNITFLOW METER

FUEL OIL PUMPFLASH TANK

ELECTRIC UNIT HEATER

CSGCT

DACDC

DEHDCC

EUH

F

FCUFM

FTFOP

CRAC

VFE

WF

PRV

PTAC

RV

UH

MBMAH

OAI

PFPHC

RELIEF HOODRH

SP

T

SDT

SDHEATING & VENTILATING UNITHV

END OF MAIN DRIPEMD

HIGH EFFICIENCY

HEAT PUMP

HIGH EFFICIENCY FILTER

PARTICULATE AIR FILTER

HEAT RECOVERY COILHEAT RECOVERY UNITHEAT TRANSFER PACKAGE

V

RS

TRAP

AIR COOLED CONDENSING UNITAIR COOLED CONDENSERACC

ACCU

BOILER

AIR FLOW STATIONAIR HANDLING UNIT

BOILER FEED PUMPBOILER FEED SET

CONVECTOR

CHARCOAL FILTERCHILLER

COOLING COIL

AFSAHU

BFPBFS

C

B

CFCH

CC

PACKAGED AIR CONDITIONING UNITAC

HTPHRUHRCHP

HEPAHEF

BUCKET TRAP

REFRIGERANT SUCTION

CONCENTRIC REDUCER

FLOAT AND THERMOSTATIC

ECCENTRIC REDUCER

ELBOW - DOWN

BOTTOM TAKE-OFF

TOP TAKE-OFF

ELBOW - UP

VENT LINE

R RELAY

THERMOSTAT

T

TEMPERATURE SENSOR

STATIC PRESSURE SENSOR

DUCT SMOKE DETECTOR

SMOKE DAMPER

TEMPERATURE SENSOR W/ REMOTE BULB

T

GAS SHUT OFF COCK

GLOBE VALVE

BALANCING VALVE

BALL VALVE

CHECK VALVE

BUTTERFLY VALVE

SOLENOID VALVE

PRESSURE REDUCING VALVE

THERMAL EXPANSION VALVE

BUTTERFLY CONTROL VALVE

2-WAY CONTROL VALVE

3-WAY CONTROL VALVE

BACK PRESSURE VALVE

ANGLE GATE VALVE

RELIEF OR SAFETY VALVE

FLOW SETTER

STRAINER W/BLOW-OFF

STRAINER

GATE VALVE

24x36

36x14Ø

X

T THERMOSTAT

S

H

XX

P

LL PLENUM LIGHT

PRESSURE SENSOR

HUMIDISTAT

SWITCH

SHEET KEY NOTE

NEW CONNECTION TO EXISTING

AIR UP

NEW WORK

AIR DOWN

OR DROP IN

36x14Ø

UP DN

24x36

BRANCH CONNECTION

45°ELBOW (NO VANES)

SUPPLY OR RETURN

EXHAUST OR RETURN

DUCT INCLINED RISE

DIRECTION OF FLOW

90° ELBOW WITHTURNING VANES

RECTANGULAR DUCT SIZE(FIRST FIGURE-SIDE SHOWN)

(FIRST FIGURE-SIDE SHOWN)FLAT OVAL DUCT SIZE

DIRECTION OF FLOW

ROUND DUCT UP

ROUND DUCT DOWN

SUPPLY AIR DOWN

EXHAUST OR RETURN

SUPPLY AIR UP

H

T

HUMIDITY SENSOR

TEMPERATURE SENSOR

S

UNION

T

AD

TYPECFM

AUTOMATIC DAMPER

EXHAUST OR RETURNREGISTERGRILLE

BDD

FD

SD

FSD

H

T

BACK DRAFT DAMPER

SMOKE DAMPER WITH

FIRE DAMPER WITHACCESS DOOR

ACCESS DOOR

SENSORDUCT TEMPERATURE

COMBINATION FIRE &SMOKE DAMPER WITHACCESS DOOR

DUCT HUMIDITY SENSOR

BALANCING DAMPER

CFMTYPE

AD

V

BDD

FD

SD

FSD

H

T

UP DN

& CAP

ADR

SDT

FLEXIBLE CONNECTION

ACCESS DOOR

DUCT SMOKE DETECTOR

ADR

SDT

EXISTING TO REMAIN

TYPECFM

DIFFUSER

DIFFERENTIAL PRESSURE SWITCHDPS

HL

NC

NO

H

DPT

EP

ES

FZ

FS

HOA

MS

GLYCOL WATER RETURN

GLYCOL WATER SUPPLYGWS

GWR

BBD

CHWS

CA

CF

BF

D

CHWR

HG

CWS

CWR

HPR

HPS

HWR

LPR

LPS

LPCS

HWS

PCR

MU

MPS

RL

MPR MEDIUM PRESSURE CONDENSATE RETURN

MEDIUM PRESSURE STEAM SUPPLY

PUMPED CONDENSATE RETURN

MAKE UP WATER

REFRIGERANT LIQUID

CONDENSATE DRAIN OR DRAIN

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

HIGH PRESSURE CONDENSATE RETURN

HIGH PRESSURE STEAM SUPPLY

HEATING WATER RETURN

HEATING WATER SUPPLY

LOW PRESSURE CLEAN STEAM

LOW PRESSURE CONDENSATE RETURN

LOW PRESSURE STEAM SUPPLY

CHILLED WATER RETURN

HOT GAS

BOILER BLOWDOWN

CHILLED WATER SUPPLY

DIRECTION OF FLOW

BOILER FEED WATER

COMPRESSED AIR

CHEMICAL FEED

DIRECTION OF SLOPE (DOWN)

MS

H HUMIDITY SENSOR W/ REMOTE BULB

HIGH LIMIT SWITCH

FLOW SWITCH

HUMIDISTAT

FREEZESTAT

HUMIDITY SENSOR

END SWITCH

HAND-OFF-AUTOMATIC SWITCH

MOTOR STARTER WITH

DIFFERENTIAL PRESSURE TRANSMITTER

ELECTRIC - PNEUMATIC SWITCH

PRESSURE SENSOR

NORMALLY CLOSED

NORMALLY OPEN

MOTOR STARTER

MOTOR

HAND-OFF-AUTOMATIC SWITCH

HOA

H

M

P

CS

DO

AFS

EXISTING TO BE REMOVED

NEW WORK

EXISTING TO REMAIN

CURRENT SENSOR

DAMPER OPERATOR

AIRFLOW STATION

DUCT WITH INTERNALLINING

SHEET NOTE (NUMBER), APPLIES ONLY ON THESHEET IT APPEARS ON

EXISTING TO BE REMOVED

DIFFUSER W/TOP BOXTRANSITION

CO2 CARBON DIOXIDE SENSOR

MAKE UP AIR UNITMAU

VP

DO

FAN WITH AIRFLOW STATION

FAN WITH INLET VANES

VP

VFD

ATC

ON-OFF SWITCH

3 POSITION SWITCH

INDICATING LIGHT

GAGE

VARIABLE FREQUENCY DRIVE

CRT DISPLAY

PC WITH PRINTER

AUTOMATIC TEMPERATURE CONTROL PANEL

VELOCITY PRESSURE SENSOR

REFERENCE STATIC PRESSURE

BALANCING DAMPERBDPOUNDS PER HOURLBS/HROPPOSABLE BLADE DAMPEROBD

AUTOMATIC TEMPERATURE CONTROLSATC

CONNECTION POINT TO PACKAGED EQUIPMENT

TOTAL STATIC PRESSURETSP

MISCELLANEOUS SYMBOLSSYMBOL DESCRIPTION DOUBLE LINE DESCRIPTION SINGLE LINE SYMBOL DESCRIPTION SYMBOL DESCRIPTION

NOTE: NOT ALL SYMBOLSINDICATED MAY APPEAR ONTHESE CONTRACT SHEETS

DUCTWORK SYMBOLSDRAWING LEGEND

PIPING SYMBOLS CONTROL DIAGRAM SYMBOLS SCHEDULED EQUIPMENTDESIGNATION DESCRIPTION

GENERAL NOTES

TECHNICAL TERMSDESIGNATION DESCRIPTION

TYPECFM

NOTE: NOT ALL SYMBOLSINDICATED MAY APPEAR ONTHESE CONTRACT SHEETS

NOTE: NOT ALL SYMBOLSINDICATED MAY APPEAR ONTHESE CONTRACT SHEETS

NOTE: NOT ALL SYMBOLSINDICATED MAY APPEAR ONTHESE CONTRACT SHEETS

NOTE: NOT ALL SYMBOLSINDICATED MAY APPEAR ONTHESE CONTRACT SHEETS

NOTE: NOT ALL SYMBOLSINDICATED MAY APPEAR ONTHESE CONTRACT SHEETS

BLOWER COIL UNITBCU

UNIT VENTILATORUV

EXPANSION TANKXT

EXHAUST LOUVER

DRUM LOUVER

EF

DL

REGISTER GRILLERG

RETURN EXHAUST REGISTERRR

LINEAR SLOTLS

REMOVABLE FRAME

DEMOLITION ENDPOINT

CEILING DIFFUSERCD

PARALLEL BLADE DAMPERPBD

FM FLOW METER

IA INSTRUMENT AIR

PRESSURE DIFFERENTIAL (STEAM TRAPS)PSID

SMOKE EXHAUST FANSEF

RADIANT HEATING PANELRHP

ROOF TOP UNITRTU

DEDICATED OUTSIDE AIR SYSTEMDOAS

DO PRESSURE CONTROL VALVE

VAV BOX (COOLING ONLY)

VAV BOX (WITH HW COIL)

LAB EXHAUST FANLEF

BLAST GATEB/G

BD

CO2 CO2 SENSOR

TCFM TRANSFER AIR

V

1. DUCTWORK AND PIPING SHOWN INDICATES CONNECTION TOEQUIPMENT USED FOR BASIS OF DESIGN. COORDINATE DUCTWORKAND PIPING CONNECTIONS WITH ACTUAL EQUIPMENT PROVIDED.

2. STRUCTURAL SUPPORTS AND CONCRETE PADS SHOWN INDICATESIZES REQUIRED FOR EQUIPMENT USED FOR BASIS OF DESIGN.COORDINATE SUPPORT AND PAD SIZES WITH ACTUAL EQUIPMENTPROVIDED.

3. CONTRACTOR SHALL INSTALL ALL AUTOMATIC CONTROL DEVICES(AUTOMATIC DAMPERS, CONTROL VALVES, FLOW METERS,TEMPERATURE SENSING WELLS ETC.) IN DUCTWORK AND PIPING ASINDICATED ON THESE DRAWINGS AND AS REQUIRED FOR ACOMPLETE AND OPERATING SYSTEM.

4. ALL CONSTRUCTION MATERIALS & DEBRIS OF ANY KIND SHALL BECOMPLETELY REMOVED FROM ALL PLENUMS PRIOR TO SUBSTANTIALCOMPLETION OF PROJECT.

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

MECHANICALCOVERSHEET

M-001

MECHANICAL SHEET LISTM-001 MECHANICAL COVERSHEETM-201 FIRST FLOOR MECHANICAL PLANM-201A ALT. FIRST FLOOR MECHANICAL PLANM-202 ENLARGED OFFICE MECHANICAL PLANSM-203A RADIANT FLOOR PLANM-401 ENLARGED MECHANICAL ROOM PLANM-501 MECHANICAL DETAILSM-502 MECHANICAL DETAILSM-503 MECHANICAL SCHEDULESM-504 MECHANICAL SCHEDULESM-505 MECHANICAL AIRFLOW RISER DIAGRAMM-505A ALT. MECHANICAL AIRFLOW RISER DIAGRAMM-506 HOT WATER DIAGRAMSM-507 ERU CONTROL DIAGRAMM-508 H&V UNIT CONTROL DIAGRAMM-509 AHU CONTROL DIAGRAMM-510 HEATING HOT WATER CONTROL DIAGRAMSM-511A RADIANT FLOOR CONTROL DIAGRAMM-512 VAV CONTROL DIAGRAMSM-513 MISCELLANEOUS MECHANICAL CONTROL DIAGRAMS

FAN POWERED BOXFPB

WIRE MESH SCREENWMS

UP

UP UP

A-2011

3

1 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18

AA

BB

CC

KK

F.6

G

F

E

D

HH

II

JJ

D.2

E.2

E.6

PARTS STOR

135

OFFICE

136OFFICE

137

CAR WASH

132

MECH / STOR

133

PARTS THROW-IN

130

BODY SHOP

122

STOR

129

OFFICE

128

DOUBLE PAINT

124

MECH

126STOR

127

DOUBLE PAINT

125

BATT MAINT

121

HEAVY PIO

120

10

OFFICE

134

23

E.5PIO

119

PAINT PREP

123

PRINT / SUPPLY

131

RM-2ARM-2B

RM-1A RM-1B

RM-2C

RM-3A

RM-3B

RM-3C

RM-6A

RM-6B

RM-6C

RM-4A

RM-4B

RM-4C

RM-5A

RM-5B

RM-7

RM-2D

RM-3D

RM-4D

RM-6D

HATCHED AREA

REPRESENT

RADIANT FLOOR

(TYP.)

MANIFOLD

PANELS (TYP.)

Concrete Slab

Wire Tie

Base Material

Slab Insulation

Wire Mesh, Rebar or

Staple to Rigid Foam

Uponor Tubing

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

RADIANTFLOOR PLAN

M-203A

Scale: 3/32" - 1'-0"

RADIANT FLOOR PLAN

1

UNDERSLAB INSULATION

SLAB ON OR BELOW GRADE

2

8 9

IT

202MECH

220

ELEC

221

STORAGE

10

FIRE PUMP

222

22X12 EA M

12X1

2 EA

M500 CFM EAOPENINGw/WMS

72X24 SA

48X36 RA

24X18 EA54X34 RA DN

20X16 EA DN

52X35 OABELOW

108W X 100L X 24DOA INTAKE LOUVER

96W X 90L X 36DEXHAUST LOUVER

AHU1

ERU1

24X18 EA TOUNIT (ABOVE)

24X18 OA

UH1

UH1

UH1

UH1

UH1

CU3

RF1

100X18RA DN

72X22 SA DN

M

M

24X18 EA

24X18 EA

90X30 OA

24X18 SA TOUNIT (BELOW)

20X14 SA DN

CU4

60W X 40L X 24D OAINTAKE LOUVER

30X20 OA

24X16 OA

24X12 OA

12X12 OAM

M

M

1500 CFM OAOPENING w/WMS

2000 CFM OASUPPLY w/WMS

500 CFM OASUPPLY w/WMS

24X14 EA

M

2000CFM EA

24X1

6 EA

1500 CFM EAOPENINGw/WMS

EF1

4000 CFM EA

30X20 EA

2-14

6"Ø SA

SA

EA

54X34 SA DN

CU1

CU-4CU FOR ERU

MM

80X70 EA

72X24 RA

72X26 RA

VV

V

V

VV

V

V

MV

UH1

DN

7 8 9

IT

202MECH

220

ELEC

221

STORAGE

224

JC

201

10

FIRE PUMP

222

AHU1

ERU1

UH1

UH1

UH1

UH1

CU3

CU4

EF1

VVR04 2-14

SS1

CU1

CU-4CU FOR ERU

B2

B1

ET1

5 GAL. POTCHEMICALFEEDER

P2

4

BP1

BP2

AS1

P

ABOVE BELOW

P1

ABOVE BELOW

3

HWS/R TORADIANT FLOOR

HWS/R TO HOT WATERREHEAT SYSTEM

P

(ALT.) (ALT.)

VFD

VFD

VFD

VFD

VFD

VFD

VFD VFD

UH1

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

ENLARGEDMECHANICALROOM PLAN

M-401

Scale: 1/4" = 1'-0"

ENLARGED MECHANICAL ROOM DUCTWORK PLAN

1

Scale: 1/4" = 1'-0"

ENLARGED MECHANICAL ROOM PIPING PLAN

2

WOOD BLOCKING

RAIL

DUCT

SEE SPECIFICATION FORSPACING OF SUPPORTS

SUPPORT TO FASTEN TOCURB NAILER ONVERTICAL SIDE

DUCT MOUNTINGPEDESTALAS SPECIFIED

ROOFINGMATERIAL

ROOF DECKING

ROOF INSULATION

W

BRANCH

AIR

FLOWBRANCH

AIR

FLOW

SQUARE BRANCH TAKEOFF

1-1/2 W

RADIUS BRANCH TAKEOFF

TURN VANES

INSTALLATION NOTES

ALL DUCTS SHALL BE CONSTRUCTED AND ERECTED IN A NEATAND WORKMANLIKE MANNER.

DUCTS SHALL BE CONSTRUCTED OF THE WEIGHTS, GAUGES,AND MATERIAL SHOWN IN THE SCHEDULE ON THESE DRAWINGS.

THE DIMENSIONS SHOWN FOR ALL DUCTS SHOWN IN PLAN GIVETHE WIDTH FIRST AND THEN THE HEIGHT.

DUCT RISERS SHOULD BE SUPPORTED BY ANGLES AT EVERY FLOOR.

AIR TURN VANES SHALL BE INSTALLED IN ALL ABRUPT ELBOWSTO PREVENT TURBULANCE.

DUCTS SHALL BE SECURELY ATTACHED TO THE BUILDINGCONSTRUCTION IN AN APPROVED MANNER.

DIVERGING TRANSITION PIECES SHALL BE MADE AS GRADUALAS POSSIBLE.

INSTALL FIRE DAMPER AS REQUIRED BY N.F.P.A. PAMPHLET NO.90A OR THE LOCAL CODES.

ACCESS PANELS SHOULD BE PLACED BEFORE AND/OR AFTEREQUIPMENT INSTALLED IN THE DUCT.

DUCT AREA SHOULD NOT BE DECREASED MORE THAN 10PERCENT WHEN OBSTRUCTIONS CANNOT BE AVOIDED, ANDTHEN A STREAMLINED FITTING SHOULD BE USED.

FLEXIBLE CONNECTIONS SHOULD BE USED ON BOTH THE INLETAND OUTLET TO ALL FANS.

JOINTS AND SEAMS OF SUPPLY DUCTS SHALL BE FASTENED SECURELY AND MADE AIR TIGHT .

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

MAIN MAIN

EQUAL SIDES(TYPICAL)

TRANSITIONAS REQ'D.(TYPICAL)

TRANSITIONAS REQ'D.(TYPICAL)

R=W MIN.

VANES(TYPICAL)

DUCT SPLIT RATIO(SIZE FOR EQUAL VELOCITIES)

DUCT SPLIT RATIO(SIZE FOR EQUAL VELOCITIES)

EQUAL OR UNEQUAL RADIUS ELBOWSPLITTER VANES AS REQ'D.

R = W R = 1/3 W IF NEEDEDDUE TO SPACE LIMITATIONS(SPLITTER VANE R = 2/3 W)

DUCT SPLIT RATIO(SIZE FOR EQUALVELOCITIES)

SQUARE DIVERGING MAIN

SPLIT MAIN

RADIUS DIVERING MAIN

EQUALSIDES

EQUAL ORUNEQUALSIDES ASREQUIRED

R=AS SPECIFIED

REFER TO SMACNAMANUAL FOR VANESPACING

MITERED WITH VANES RADIUS NO VANES

MITERED NO VANES VANED RADIUS ELBOW

EQUAL

R = W

D D

R=D

RECTANGULAR DUCT

ROUND DUCT

AIR FLOW AIR FLOW

45° ROUNDTAP FITTING

R=W

RECTANGULAR DUCT

RECTANGULAROR SQUARE 45°TAP FITTINGRECTANGULAR ORSQUARE TO ROUND

RECTANGULARDUCT

ROUND DUCTCONICAL TEEFITTING WITHFLANGE

NOTE:HOLE IN RECTANGULAR DUCT SHALL BE CUT LARGE ENOUGH SOTHAT ROUGH METAL EDGE SHALL NOT PROJECT INTO AIR STREAM.

TYPICAL TAPOFF & TRANSITIONFROM SIDE OF DUCTROUND DUCT

AIR FLOW

RECTANGULAR TO ROUNDDUCT TRANSITION

15° MAXIMUM

15° MAXIMUM

6" 6"

6"

DOUBLE RADIUSTURNING VANES

DOUBLE RADIUSTURNING VANES

A

SECTION A-A

MAX.2'-0"

SMOKE BARRIER

SEALANT

CAULKINGACCESS DOOR

AIR FLOW

SMOKE DAMPER

OPERATOR(OUT OF THEAIRSTREAM)

NOTE:ACTIVATE SMOKE DAMPER FROM ONE OF THE FOLLOWING:1.2.3.

DUCT SMOKE DETECTOR.ROOM SMOKE DETECTOR.DOOR RELEASE DETECTOR/SMOKE BARRIER DOOR.COORDINATE DETECTOR AND WIRING WITH ELECTRICALCONTRACTOR

PROVIDE BREAKAWAY CONNECTIONSIN ACCORDANCE WITH SMACNA.

RETAINING ANGLES SHALL BE2" x 2" x 1/8" AND SHALL BESECURED TO 16 GA. SLEEVEIN ACCORDANCE WITH SMACNA.DO NOT SECURE ANGLES TOWALL OR FLOOR. PROVIDE ANGLESON ALL FOUR SIDES OF SLEEVEAND BOTH SIDES WALL OR FLOOR.

DUCTWORK

DUCT ACCESS DOOR LABELED"FIRE/SMOKE DAMPER ACCESS"

FIRE RATED WALL

16 GAUGE SLEEVE

APPLY SEALANT TO JOINT ALLAROUND ON BOTH SIDES OF WALL

PROVIDE CLEARANCE ON TOPAND SIDES FOR EXPANSION

FIRE RATED WALL

VERTICAL GUILLOTINE TYPEFIRE DAMPER WITH U.L.RATING AND STAMP

SUPPORT DUCTWORK TO STRUCTURESO WEIGHT DOES NOT REST ON FIREDAMPER

PROVIDE BREAKWAY CONNECTIONIN ACCORDANCE WITH SMACNA

RETAINING ANGLES SHALL BE2" x 2" x 1/8" AND SHALL BESECURED TO 16 GA. SLEEVEIN ACCORDANCE WITH SMACNA.DO NOT SECURE ANGLES TOWALL OR FLOOR. PROVIDE ANGLESON ALL FOUR SIDES OF SLEEVEAND BOTH SIDES WALL OR FLOOR.

PROVIDE CLEARANCE ON TOP ANDSIDES FOR EXPANSION

2" HIGH CURB ALL AROUNDHORIZONTAL GUILLOTINE TYPE FIREDAMPER WITH UL RATING AND STAMP

APPLY SEALANT TO JOINT ALLAROUND ON BOTH SIDES OF OPENING

FIRE RATED FLOOR. SEESTRUCTURAL DRAWINGS.

FIRE DAMPER ACCESS DOOR. LABEL"FIRE DAMPER ACCESS"

18"

18"A

A

18"

A

2" MINIMUM

LOCATE ACCESS DOORS IN DUCTWORK TO FACILITATE ACCESS TO DEVICESREQUIRING SERVICE AND INSPECTION.

(AUTOMATIC DAMPERS, THERMOSTATS, ETC.), FIRE DAMPERS, SMOKE DAMPERS,

20"-48"

12"(TYPICAL)

2"

18" AND LESS

18"

18"

A

2A 50" AND OVER

NOTES:PROVIDE DUCT ACCESS DOORS AS PER SPECIFICATION AT CONTROL DEVICES,

REHEAT COILS, HUMIDIFIERS, AIR FLOW SENSORS, AIR BOXES, AND WHEREREQUIRED FOR SERVICE ACCESS, AND AS SHOWN ON DRAWINGS.

1.

2.

STRUCTUREBUILDING

PARTITIONWALL OR

ON SCHEDULESIZE AS SHOWN

SHEET METAL DUCT

(TYP. 2)NOTED ON PLANS

9" MI

NIMU

M3"MIN

CFM RANGE DUCT SIZE

0-100 10x6

12x8105-200

405-600

205-400

20x12

16x8

805-1000

605-800

30x12

24x12

1005-1400 30x16

1" DUCT LINER

CEILING

PLAN INDICATION

AIR DEVICE SIZE AS

NOTE:

SHEETMETAL.1. ALL TRANSFER DUCTS SHALL BE CONSTRUCTED WITH MINIMUM 16 GAUGE

SEE SPECIFICATION FOR INSULATION THICKNESS AND TYPE.

EXTEND VOLUME DAMPER NECK PAST INSULATION.1.

2.

NOTE:

SEE NOTE 1

AS NOTED ON PLANSAIR DEVICE SIZE

AIR DEVICE NECK

CLAMP (TYPICAL)SCREW AND

DUCT, INSIDE DIAMETER

SUPPORT DETAIL TOSEE FLEXIBLE DUCT

MAXIMUM LENGTH 5'-0"AS NOTED ON PLANS.

INSULATED FLEXIBLE

MAXIMIZE FREE AREAAT 90° ELBOW

VD

CEILING

SEE NOTE 2INSULATION,

SCREW AND CLAMPW/STAINLESS STEELTO SPIN-IN FITTING

SUPPLY DUCT

FITTING w/DAMPERCONICAL SPIN-IN

SECURE FLEXIBLE DUCT

--M---

ON SCHEDULESIZE AS SHOWN

SHEET METAL DUCT

1" DUCT LINER

PARTITIONWALL OR

CEILING

STRUCTUREBUILDING

3"MIN 3"MIN

6"MIN

6"MIN

3"MIN

CFM RANGE DUCT SIZE

0-100 10x6

12x8105-200

405-600

205-400

20x12

16x8

805-1000

605-800

30x12

24x12

1005-1400 30x16

3"MIN

NOTE:

SHEETMETAL.1. ALL TRANSFER DUCTS SHALL BE CONSTRUCTED WITH MINIMUM 16 GAUGE

Not to ScaleM-501

10 TRANSFER DUCT (UP) DETAILNot to ScaleM-501

8 TRANSFER DUCT (THRU CEILING) DETAIL

Not to ScaleM-501

16 SMOKE DAMPER DETAIL

Not to ScaleM-501

11 DUCT ACCESS DOOR DETAIL

Not to ScaleM-501

7 FLEXIBLE DUCT DETAIL

Not to ScaleM-501

13 ROOF RAIL DETAIL

Not to ScaleM-501

3

ROUND AND SQUARE BRANCH TAKE OFFDETAILS

Not to ScaleM-501

1 SPLIT MAIN DETAIL

Not to ScaleM-501

12 ELBOW DETAILS

Not to ScaleM-501

6

TYPICAL TAKE-OFF FROM RECTANGULARDUCT TO ROUND DUCT DETAIL

Not to ScaleM-501

14 DUCT TRANSITIONS

Not to ScaleM-501

15 TYPICAL DUCT SPLITS

Not to ScaleM-501

5 STYLE 'A' WALL FIRE DAMPER DETAIL

Not to ScaleM-501

4 STYLE 'A' FLOOR FIRE DAMPER DETAIL

Not to ScaleM-501

2

SOUND BARRIER TREATMENT FORDUCTWORK

3" THICK2 - 4 LB. /CU. FT.DENSITY FIBERGLASSINSULATION APPLIEDTOOUTSIDE OF DUCT

TAPE & SPACKLEAS REQUIRED

LINE OF DUCTANGLE BRACING 12" A.C. ANDSCREW CONNECTIONS 12" A.C.

LINEDDUCTWORK

STRAPS TOSUPPORTDUCTWORK

TWO (2) LAYERS5/8"DRYWALLON 3-5/8 " METALSTUDS OUT OFCONTACT WITHDUCT

Not to ScaleM-501

9

DUCT SOUND PENETRATION DETAILTYPICAL

FOR BLOCKWORK/CONCRETEWALL, MORTOR TO SLEEVE ATFULL DEPTH OR PARTITION

SCHEDULED PARTITION

DUCT WITH INSULATIONAS SPECIFIED

STEEL SLEEVE

FIBERGLASS 2 PCF TO 3 PCF PACKEDAND COMPRESSED TO FULL DEPTHALTERNATE - EXPANDABLE FOAM

NON HARDENINGRESILIENT SEALANT

FOAM CYLINDER BACKERROD, AS REQUIRED

NON-HARDENINGRESILIENT SEALANT

1" M

AX

GENERAL NOTES:

1. DUCT SUPPORTS TO BE SPACED SUFFICIENTLY FROM PARTITIONLINE TO ALLOW ACCESS FOR INSULATION AND SEALING.

2. IN BLOCKWORK PARTITIONS, THICKNESS OF STEEL SLEEVE TO BESUFFICIENT TO SUPPORT MORTAR ABOVE. MINIMUM THICKNESS1/16 INCH.

3. USE SOUND PENETRATION DETAIL AT ALL SOUND WALLS.

MECHANICALDETAILS

M-501

LEVEL 10'-0"

VD

VD

PER SPECIFICATIONACCESS DOOR,

FLOW

PLAN VIEW

SECTION A-A

45° MAX.30° MAX.

FLANGED CONNECTION(TYPICAL)

A.D.

HEATING COILS

HEATING COILS

A A

NOTE:DUCT TRANSITIONS AT REHEAT COILS MAY OCCUR IN ONE DIRECTION, IFVELOCITY AND SPACE PERMIT.

1.

FLOW

WALK OFF MAT

PAN AREA

PROVIDE 6" WIDESHEET METALBLANK-OFF PANEL

12"x48

" SA

12"x48

" RA

SLAB

FAN COIL UNIT

1-1/4" DRAIN CONNECTIONWITH VALVE AND HOSECONNECTION FOREXTENSION TO FLOORDRAIN.

SLOPE BOTTOM OFDUCT PLENUM.

1-1/4" DRAIN CONNECTIONWITH VALVE AND HOSE

CONNECTION FOREXTENSION TO FLOORDRAIN.

SLOPE BOTTOM OFDUCT PLENUM.

WELDED ALUMINUM DUCTWORK(TYP.)

V V

FS FS

FLEXIBLE DUCTCONNECTION FLEXIBLE DUCT

CONNECTION

P

VENT TO ATMOSPHERE

REFER TO PRESSURERELIEF VALVE DETAIL.DISCHARGE TOATMOSPHERE.

LOW PRESSURE CONDENSATETO CONDENSATE RECEIVERTANK

TO DRAIN

DROP PAN ELBOW

TO ATMOSPHERE NOTES:1. CONSTRUCT FLASH TANK FOR 150 PSI STEAM2. MEDIUM PRESSURE CONDENSATE MUSTENTER CONDENSATE HEADER DOWNSTREAMOF ALL HIGH PRESSURE CONDENSATE.

CONDENSATEINLET HEADER FLASH TANK

MEDIUM PRESSURECONDENSATEHIGH PRESSURECONDENSATE

1/2" NPTFDISCHARGE/CONNECTION

50 GAL PREMIXEDGLYCOL FEEDERNEPTUNEMODEL G-50-1A OREQUAL

CONTROL PANEL

ROTARY GEAR PUMPW/ NEMA 48 FRAME MOTOR1.5 GPM VS. 100 PSI1/3 HP-1-60-115V-ODP

PRESSSWITCH

REFER TO PIPINGDIAGRAM FORCONTINUATION

Not to ScaleM-501

17 DUCT MOUNTED HEATING COIL DETAIL

1.

ROOF MOUNTEDEXHAUST FAN

2.

NOTESALL DUCTWORK SHALL BE CONSTRUCTED TO MEET THE DUCT CLASS

ALL DUCTWORK SHALL BE SEALED WITH CLASS A SEALER.

RELIEF DUCT

RETURN DUCT

RETURN FAN

VVR BOX

AIR HANDLING UNIT

2"WG 4"WG 1"WG

2"WG

2"WG 2"WG

2"WG

SHOWN ABOVE.

Not to ScaleM-501

18 DUCT PRESSURE CLASS DIAGRAM

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

AutoCAD SHX Text
PLAN INDICATION

NOTES:1.

2.

PROVIDE RETURN DUCT BOOT OVER ALL RETURN GRILLES, USED TO

PROVIDE PLENUM OVER RETURN LINEAR SLOT GRILLES USED TO TRANSFER

TRANSFER AIR INTO CEILING PLENUM. SEE DRAWING FOR SIZES.

AIR INTO CEILING PLEUM. PROVIDE 8" ROUND DUCTS EVERY 3 FEET ON

RETURN BOOT (SEE NOTE 1)

RETURN GRILLE

8" DUCT

LINEAR SLOT RETURN GRILLE

PLENUM

CEILING

2'-0"

2'-0"

CENTER.

DUCT LINER(TYP.)

(TYP.)DUCT LINER

Not to ScaleM-502

5

RETURN GRILLE/TRANSFERDUCT DETAIL

CONTROLS

VAV BOX

30° MAXIMUM

BRANCH DUCT

TRANSITION

FLR. PLANS.

MAIN DUCT

BRANCH INLET DUCTWORK

SEE TYPICAL BRANCHDUCT TAKE-OFF DETAIL

SHALL BE AS SHOWN ON

SUPP

LY M

AIN

AIR FLOW

INDEPENDENTLY

3 DIAMETERS OF BOX INLETOR MINIMUM OF 2 FEET

STRAIGHT ROUND DUCT

(WHERE SHOWN

ACCESS DOOR

TRANSITION

REHEAT COIL

TO BE SAME SIZE ASBOX INLET CONNECTION

BY MFGR.

BRANCH DUCT

AS REQUIRED BY CODE (MIN. 18")CLEAR ACCESS FOR CONTROLS

TERMINAL UNIT.

RIGHT SIDE, AS REQUIRED BY FIELD CONDITIONS.

INSTALLATION.MANUFACTURER AND SUBMIT TO ENGINEER FOR REVIEW PRIOR TO

DUCTS, ELBOWS AND FITTINGS.

EXCESSIVE TURBULENCE ON THE ENTERING SIDE OF EACH TERMINAL UNIT.

2.

1.

4.

3.

STRAIGHTENING VANES OR OTHER DEVICE AS RECOMMENDED BY THE

NOTES:

ARRANGE ACCESS TO PERMIT EASY FIELD BALANCE AND MAINTANANCE OF

MANUFACTURER OF TERMINAL UNOT SHALL PROVIDE CONTROLS ON LEFT OR

INDICATED ABOVE, CANNOT BE MAINTAINED, PROVIDE ORIFICE PLATE,WHEN MINIMUM UPSTREAM STRAIGHT DUCT CONNECTION TO TERMINALS, AS

THEREFORE, TERMINAL UNITS MUST NOT BE INSTALLED TOO CLOSE TO MAIN

THE OPERATION OF VARIABLE VOLUME TERMINAL UNITS ARE AFFECTED BY

SUPPORTED

PRESSURE CLASS4 1

WHERE REQUIRED

OR SPECIFIEDFOR SUPPLY AIR)

Not to ScaleM-502

1

VARIABLE AIR VOLUME BOX DUCTCONNECTION DETAIL

INSTALLATION NOTES

SHUT-OFF VALVE (TYP.)

UNION TYPE CONNECTION.PIPE SO PUMP CAN BEREMOVED FOR SERVICE

MOTOR

NIPPLE(TYP.)

PIPE FROM SYSTEMSEE PLANS FORCONTINUATION

PIPE TO SYSTEMSEE PLANS FORCONTINUATION

IN-LINE CIRCULATING PUMPSEE SCHEDULE FOR CAPACITY

BALANCE / SHUT-OFFVALVE

PRESSURE GAUGE

PROVIDE PUMP SUPPORT BRACKET W/VIBRATION ISOLATORS, AND HANG FROMSTRUCTURE ABOVE. INSTALL AS TO NOT CREATESTRESSES ON PUMP COMPONENTS. SUPPORTSSHALL NOT LIMIT THE PUMP'S ABILITY TO MOVEWITH PIPE EXPANSION.

CHECKVALVE FLEXIBLE

CONNECTION(TYP.)

BOLT PUMPTO SUPPORT

PUMP SUPPORTBRACKET

1.

2.

3.

SHUT OFF VALVES AND ACCESSORIES SHALL BE THE SAME SIZE AS SYSTEMPIPING.

THE BALANCE VALVE SHALL BE SIZED AT A PRESSURE DROP OF 3 PSI MAX ATFULL FLOW.

PROVIDE OPTIONAL SPACER COUPLING FOR FLUID TEMPERATURES OVER 100DEG. F.

1/4" SHUT-OFF COCK.(TYPICAL)

STRAINERWITHBLOW-OFFVALVE

1/2" FLUSHING BYPASSLOCATED ABOVE CEILING

PROVIDE ACCESS DOOR TOCONTROL VALVE

1/2" DRAIN

ENCLOSURE

HEATING ELEMENT HWS

HWR COIL

ACCESSDOOR

DUCT

TERMINALUNITACCESSDOOR BYMANUF.

NOTE:PROVIDE HALF THE TRU'S WITH 2-WAY VALVES AND HALF WITH 3-WAYVALVES. DISTRIBUTE THROUGHOUT THE BUILDING EVENLY.

PROVIDE MIN. OF 3 DUCTDIAMETERS OF STRAIGHT DUCTAT INLET TO TERMINAL BOX

DRAIN

N.C.

SWINGFITTINGS

SET VALVE EQUAL TOCOIL PRESSURE DROP

1/2" FLUSHINGLINEHW

SHW

R

Not to ScaleM-502

2 LARGE INLINE PUMP DETAIL (OVER 1 HP)

Not to ScaleM-502

4

CABINET/UNIT HEATERPIPING DETAIL Not to ScaleM-502

6

TERMINAL REHEAT UNIT WITH HOTWATER COIL DETAIL

Not to ScaleM-502

3

PIPE SOUND PENETRATION DETAILTYPICAL

FOR BLOCKWORK/CONCRETEWALL, MORTOR TO SLEEVE ATFULL DEPTH OR PARTITION

SCHEDULED PARTITION

PIPE WITH INSULATIONAS SPECIFIED

STEEL SLEEVE

FIBERGLASS 2 PCF TO 3 PCF PACKEDAND COMPRESSED TO FULL DEPTHALTERNATE - EXPANDABLE FOAM

NON HARDENINGRESILIENT SEALANT

FOAM CYLINDER BACKERROD, AS REQUIRED

NON-HARDENINGRESILIENT SEALANT

1" M

AX

NOTES:

1. PIPE SUPPORTS TO BE SPACED SUFFICIENTLY FROM PARTITION LINE TO ALLOWACCESS FOR INSULATION AND SEALING.

2. IN BLOCKWORK PARTITIONS, THICKNESS OF STEEL SLEEVE TO BE SUFFICIENT TOSUPPORT MORTAR ABOVE. MINIMUM THICKNESS 1/16 INCH.

3. USE SOUND PENETRATION DETAIL AT ALL SOUND WALLS.

F

A

INSTALL ONLY WHENBYPASS IS SPECIFIED

A

COIL

COIL

NOTES:1. PROVIDE BALANCING VALVES AND FLOW SENSORS AS

REQUIRED BY PIPE SIZE AND SPECIFICATION SECTION15510. INSTALL FLOW SENSOR PER MANUFACTURER'SREQUIREMENTS FOR STRAIGHT RUN OF PIPE DIAMETERS.

2.

3.

4.

IN LIEU OF TWO(2) GAUGES WHENEVER POSSIBLE OR

MOUNT CONTROL VALVE AND ACCESSORIES

COST EFFECTIVE.

PIPE SIZE AND SPECIFICATIONS.

BALANCE FLOW THRU COIL WITH CONTROL VALVE IN FULL

THERMOMETERS SHOWN FOR ALL DUCT MOUNTED COILS.

PRESSURE DROP.

PROVIDE PIPE UNIONS OR FLANGES AS REQUIRED BY

PROVIDE PRESSURE GAUGES AND THERMOMETERS ON ALL

WELLS IN LIEU OF THE PRESSURE GAUGES AND

POSITION. SET BYPASS BALANCING VALVE TO EQUAL

PROVIDE 6" FLANGED SPOOL PIECE MINIMUM AROUNDCONTROL VALVE WHEN REDUCERS ARE NOT PROVIDED.

AIR HANDLING UNIT COILS AS SHOWN. PROVIDE P/T

PROVIDE COMPOUND PRESSURE GAUGES WHEN SPECIFIED

5.

AREAS AND UNIT ACCESS.

DRAWINGS.

APPROXIMATELY 6'-0" A.F.F. IN MECHANICAL ROOMS, ANDIN A MANNER AS, NOT TO INTERFERE WITH COIL PULL

PROVIDE BYPASS AROUND CONTROL VALVE ASSEMBLY ATALL AIR HANDLING UNIT COILS. PROVIDE BYPASS AT DUCTMOUNTED COILS WHEN SPECIFIED OR SHOWN ON

COIL

BALANCE FOR

THRU EACHEQUAL FLOW

(TYPICAL)VALVE w/HOSE BIBB3/4" MINIMUM DRAIN

SEE NOTE 3

SUPPLY

RETURN

SEE NOTE 1

SEE NOTE 2

REDUCERS ASREQUIRED (TYPICAL)

BYPASS, FULL SIZEOF CONTROL VALVE.SEE NOTE 5

SHALL BE THE SAMEALL COIL PIPINGWHEN APPLICABLE.TO ADDITIONAL COILS

Not to ScaleM-502

7

MULTIPLE HOT WATER PREHEAT/REHEATCOIL PIPING WITH THREE-WAY VALVE DETAIL

A

INSTALL ONLY WHENBYPASS IS SPECIFIED

A

COIL

COIL

NOTES:1. PROVIDE BALANCING VALVES AND FLOW SENSORS AS

REQUIRED BY PIPE SIZE AND SPECIFICATION SECTION15510. INSTALL FLOW SENSOR PER MANUFACTURER'SREQUIREMENTS FOR STRAIGHT RUN OF PIPE DIAMETERS.

2.

3.

4.

IN LIEU OF TWO(2) GAUGES WHENEVER POSSIBLE OR

MOUNT CONTROL VALVE AND ACCESSORIES

COST EFFECTIVE.

PIPE SIZE AND SPECIFICATIONS.

BALANCE FLOW THRU COIL WITH CONTROL VALVE IN FULL

THERMOMETERS SHOWN FOR ALL DUCT MOUNTED COILS.

PRESSURE DROP.

PROVIDE PIPE UNIONS OR FLANGES AS REQUIRED BY

PROVIDE PRESSURE GAUGES AND THERMOMETERS ON ALL

WELLS IN LIEU OF THE PRESSURE GAUGES AND

POSITION. SET BYPASS BALANCING VALVE TO EQUAL

PROVIDE 6" FLANGED SPOOL PIECE MINIMUM AROUNDCONTROL VALVE WHEN REDUCERS ARE NOT PROVIDED.

AIR HANDLING UNIT COILS AS SHOWN. PROVIDE P/T

PROVIDE COMPOUND PRESSURE GAUGES WHEN SPECIFIED

5.

AREAS AND UNIT ACCESS.

DRAWINGS.

APPROXIMATELY 6'-0" A.F.F. IN MECHANICAL ROOMS, ANDIN A MANNER AS, NOT TO INTERFERE WITH COIL PULL

PROVIDE BYPASS AROUND CONTROL VALVE ASSEMBLY ATALL AIR HANDLING UNIT COILS. PROVIDE BYPASS AT DUCTMOUNTED COILS WHEN SPECIFIED OR SHOWN ON

COIL

BALANCE FOR

THRU EACHEQUAL FLOW

(TYPICAL)VALVE w/HOSE BIBB3/4" MINIMUM DRAIN

SEE NOTE 3

SUPPLY

RETURN

SEE NOTE 1

SEE NOTE 2

REDUCERS ASREQUIRED (TYPICAL)

BYPASS, FULL SIZEOF CONTROL VALVE.SEE NOTE 5

SHALL BE THE SAMEALL COIL PIPINGWHEN APPLICABLE.TO ADDITIONAL COILS

F

Not to ScaleM-502

8

MULTIPLE HOT WATER PREHEAT/REHEATCOIL PIPING WITH TWO-WAY VALVE DETAIL MECHANICAL

DETAILS

M-502

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

MECHANICALSCHEDULES

M-503

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

MECHANICALSCHEDULES

M-504

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

MECHANICALAIRFLOW RISER

DIAGRAM

M-505

ROOF

2ND FLOOR OFFICES

VPC SOUTH

VPC NORTHFIRST FLOOR OFFICES

AHU1

8,055 CFM RA

SA

8,055 CFM TOSECOND FLOOR

OFFICES

VAV- TYP

SA

11,660 CFM TOFIRST FLOOR

OFFICES

11,660 CFM RA

OA7,795 TO

22,410 CFM

FPB- TYP

VAV- TYP

FPB-

ERU1

ELECTRICALROOM

PUMPROOM

MECHANICALROOM

EA17,310 TO

22,410 CFM

700 CFM EA

TYP

700 CFM EA

SA1,690 CFM TO

SECOND FLOORRESTROOMS/JC

SA460 CFM TO FIRST

FLOORRESTROOMS/JC

4,000 CFM

EF1

RF1

M

M

M

M

OA4,000 CFM

M

1,500OA

M

500OA

M

2,000OA

M

1,500EA

M

500EA

M

2,000EA

ROOF

FIRST FLOOR OFFICES

HV1

OA50,000 CFM

EA

PIOPROCESSING

50,000 CFM

50,000 CFM RA

50,000 CFM SA

HV1

OA

EA

HV1

OA15,000 CFM

EA

BODY SHOP

15,000 CFM

15,000 CFM RA

15,000 CFM SA

HV2

OA30,000 CFM

EA30,000 CFM

30,000 CFM RA

30,000 CFM SA

PARTSTHROW IN

HV3

OA

EA

STORAGE

5,000 CFM RA

5,000 CFM SA

5,000 CFM

5,000 CFM

Scale: NTS

OFFICE AREA AIRFLOW DIAGRAM

1

Scale: NTS

PROCESSING FLOOR AIRFLOW DIAGRAM

1

50,000 CFM

50,000 CFM

50,000 CFM RA

50,000 CFM SA

HV1

OA50,000 CFM

EA50,000 CFM

50,000 CFM RA

50,000 CFM SA

HV1

OA50,000 CFM

EA50,000 CFM

50,000 CFM RA

50,000 CFM SA

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

ALT.MECHANICAL

AIRFLOW RISERDIAGRAM

M-505A

ROOF

2ND FLOOR OFFICES

VPC SOUTH

VPC NORTH

FIRST FLOOR OFFICES

AHU1

8,055 CFM RA

SA

8,055 CFM TOSECOND FLOOR

OFFICES

VAV- TYP

SA

11,660 CFM TOFIRST FLOOR

OFFICES

11,660 CFM RA

OA7,795 TO

22,410 CFM

FPB- TYP

VAV- TYP

FPB-

ERU1

ELECTRICALROOM

PUMPROOM

MECHANICALROOM

EA17,310 TO

22,410 CFM

700 CFM EA

TYP

700 CFM EA

SA1,690 CFM TO

SECOND FLOORRESTROOMS/JC

SA460 CFM TO FIRST

FLOORRESTROOMS/JC

4,000 CFM

EF1

RF1

M

M

M

M

OA4,000 CFM

M

1,500OA

M

500OA

M

2,000OA

M

1,500EA

M

500EA

M

2,000EA

ROOF

FIRST FLOOR OFFICES

HV1

OA17,000 CFM

EA

PIOPROCESSING

17,000 CFM

17,000 CFM RA

17,000 CFM SA

HV1

OA17,000 CFM

EA17,000 CFM

17,000 CFM RA

17,000 CFM SA

HV2

OA15,000 CFM

EA

BODY SHOP

15,000 CFM

15,000 CFM RA

15,000 CFM SA

HV3

OA5,000 CFM

EA5,000 CFM

5,000 CFM RA

5,000 CFM SA

PARTSTHROW IN

HV3

OA

EA

STORAGE

5,000 CFM RA

5,000 CFM SA

5,000 CFM

5,000 CFM

Scale: NTS

OFFICE AREA AIRFLOW DIAGRAM

1

Scale: NTS

PROCESSING FLOOR AIRFLOW DIAGRAM

1

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

HOT WATERDIAGRAMS

M-506

P3

P4

STANDBYINLINE PUMPWITH VFD

P1

P2

STANDBY

HWS(P)

HWR(P)

AS1

ET1

AUTOMATICAIR VENT

TO F.D.P

TOF.D.

SYSTEM FILLONLY (N.C.)

HOT WATER REHEATSYSTEM 140°F TO 120°F

ALTERNATE - HOT WATERRADIANT FLOOR SYSTEM100°F TO 90°F

BYPASSCHEMICALFEEDER B

2

BP2

B1

BP1

CHECKVALVE

CHECKVALVE

HWRHEADER

HWSHEADER

NOTES:1. SEE FLOOR PLANS FOR QUANTITY OF VAV COILS AND CABINET UNIT HEATERS.2. SEE FLOOR PLANS FOR ADDITIONAL SERVICE VALVES.

HWS

HWR

3-WAY MIXINGVALVE

RELIEF50 PSIG

RELIEF50 PSIG

Scale: NTS

HEATING HOT WATER FLOW DIAGRAM

1

MECHANICAL ROOM

HWR(RAD)

HWS(RAD)

HWR(180°F)HWS(180°F)

HWR(

RAD)HW

S(RA

D)

HWS(RAD)

HWR(RAD)

HEADERSTYP.

MANIFOLDPANEL TYP.

M

RADIANT HEATING WATER(100°F TO 90°F)

BALANCINGVALVE

DIFF. BYPASSVALVE

NO

HWS(RAD)

HWR(RAD)

SUPPLY

RETURN SERVICE VALVE ABOVECEILING (TYP.)

MANIFOLD PANEL WITHACCESS DOOR (TYP.)

RETURN HEADER

SUPPLY HEADER

RETURN SERVICE VALVEPER LOOP (TYP.)

BALANCING VALVE PERLOOP (TYP.)

SUPPLY SERVICE VALVEPER LOOP (TYP.)

BALANCING VALVE(TYP.)

METAL TOPEX (TYP.)

PANEL SLEEVE (TYP.)

VPC MAIN FLOOR

Scale: NTS

MANIFOLD PIPING DETAIL

2

Scale: NTS

RADIANT HEATING FLOW DIAGRAM FOR ALTERNATE

3

NO

INLINE PUMPWITH VFD

INLINE PUMPWITH VFD

INLINE PUMPWITH VFD

P1

P2

STANDBY

INLINE PUMPWITH VFD

INLINE PUMPWITH VFD

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

ERU CONTROLDIAGRAM

M-507

-COLO

R GR

APHI

CS

EMER

GENC

Y PO

WER

PRO

GRAM

COIL

RESE

T PR

OGRA

M

ECON

OMIZ

ER P

ROGR

AM

NIGH

T SE

TBAC

K PR

OGRA

M

OPTI

MUM

STAR

T / S

TOP

PROG

RAM

TIME

SCH

EDUL

ING

EVEN

T PR

OGRA

M

FAN

SPEE

D

BTU

-LOW

LIMI

T

HIGH

LIMI

T

ANALOGAL

ARMS

PROO

F FA

ILURE

-

OUTPUTS

POST

ITIO

NING

SPEE

D CO

NTRO

L

-

ANALOG

OPEN

/CLO

SE

BYPA

SS S

TART

ER

STAR

T/ST

OP

ALAR

M

MOTO

R SP

EED

CURR

ENT

SENS

ING

DIIF

EREN

TIAL

PRE

SSUR

E

PRES

SURE

STAT

US -

OPEN

/CLO

SE

ENERGY MANAGEMENTAPPLICATIONS

APPLICATION SOFTWARE

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

DIGITAL DIGITAL

ALARMS

TYPE

STAT

US -

ON/O

FF

ERU SYSTEM DDC INPUT / OUTPUT SUMMARY

DIFF

EREN

TIAL

PRE

SSUR

E

TEMP

ERAT

URE

RELA

TIVE

HUM

IDIT

Y

FLOW

RAT

E, C

FM

DETE

CTOR

TRI

PPED

HIGH

LIMI

T

LOW

LIMI

T

CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

SCHE

DULE

- OC

CUPI

ED/U

NOCC

UPIE

D

RUN

TIME

TREN

D

SUPPLY AIR TEMPERATURE SENSOR

RETURN AIR TEMPERATURE SENSOR

SUPPLY FAN (VFD)

DIRTY FILTER SWITCH

OUTSIDE AIR DAMPER & END SWITCH

HEATING DISCHARGE TEMPERATURE SENSOR

EXHAUST AIR DAMPER & END SWITCH

SAFETIES AND ALARMS

1. ERU FILTER PRESSURE DROP - THE PRESSURE DROP ACROSS THE FILTER SHALL BE MONITORED BY THE BASSYSTEM ON THE ERU AS INDICATED. AN ALARM SHALL BE INDICATED AT THE WORKSTATION UPON CLOSURE OFANY DIFFERENTIAL PRESSURE SWITCH.

2. SMOKE DETECTORS LOCATED IN THE SUPPLY AND RETURN DUCTWORK SHALL ALARM THE FIRE ALARM CONTROLPANEL IF A SMOKE CONDITION EXISTS. IN TURN THE FIRE ALARM CONTROL PANEL SHALL DE-ENERGIZE THESUPPLY FAN AND EXHAUST FAN.

3. LOW PRESSURE AND HIGH PRESSURE SENSOR SHALL ALARM THE OPERATOR AND SHUT-DOWN THEASSOCIATED FAN.

4. TEMPERATURE ALARMSa. MONITOR SUPPLY AIR TEMPERATURE. PROVIDE LOW TEMPERATURE ALARM IF TEMPERATURE DROPS

BELOW 55° F.

ERU CONTROL SEQUENCE

SPECIFIC CONTROL

1. START-UP OCCUPIED MODEa. NORMALLY CLOSED OUTDOOR AIR DAMPER AND EXHAUST FAN DAMPER SHALL OPEN. ONCE THE DAMPER

POSITION IS PROVEN, THE SUPPLY FAN SHALL START AND RAMP TO 50% AIRFLOW. WHENEVER THE SYSTEMIS IN OPERATION IN THE OCCUPIED MODE THE SUPPLY FAN SHALL OPERATE CONTINUOUSLY.

b. ONCE THE TEMPERATURE WITHIN THE BUILDING IS HEATED TO 65° F, THE BAS SHALL MONITOR THE ROOMTEMPERATURE SENSORS.

2. FAN SPEED CONTROLa. IN THE NORMAL OCCUPIED MODE THE SUPPLY FAN SPEED CONTROLS SHALL BE VIA THE DUCT MOUNTED

STATIC PRESSURE SENSOR TO MAINTAIN 100% OF SUPPLY CFM BASED ON DUCT STATIC.

3. GAS FURNACE CONTROLa. THE GAS FURNACE SHALL MODULATE IN ORDER TO MAINTAIN IT'S DISCHARGE TEMPERATURE SETPOINT AT

AN ADJUSTABLE SETPOINT OF 60° F.

4. SMOKE CONTROLa. UPON AN INDICATION OF SMOKE SENSED BY THE SUPPLY OR EXHAUST DUCT DETECTOR, THE FIRE ALARM

SYSTEM PROVIDE SIGNAL TO BAS SYSTEM TO SHUTDOWN SUPPLY FAN AND EXHAUST FAN, AND CLOSEOUTSIDE AIR DAMPER AND EXHAUST AIR DAMPER.

b. FIRE SMOKE CONTROL PANEL SHALL PROVIDE SIGNAL TO BAS SYSTEM TO RESTART UNIT IN NORMAL MODE.

5. COOLING COIL CONTROLa. THE COOLING COIL SHALL ALTERNATE IF SUPPLY AIR TEMPERATURE EXCEEDS 85° F. COOLING COIL AND GAS

FIRED DUCT FURNACE SHALL NOT BE ACTIVATED CONCURRENTLY.

6. EXHAUST FAN CONTROLa. EXHAUST FAN SHALL BE ENERGIZED WHEN HV IS OPERATING IN NORMAL MODE.b. BEFORE STARTING EXHAUST FAN OPEN NORMALLY CLOSED AIR DAMPER. VERIFY DAMPER IS OPEN WITH

DAMPER END SWITCH.c. LOW PRESSURE SENSOR SHALL SHUTDOWN EXHAUST FAN AND PROVIDE ALARM TO THE OPERATOR.d. IN NORMAL OCCUPIED MODE THE EXHAUST FAN SPEED CONTROLS SHALL BE VIA THE DUCT MOUNTED STATIC

PRESSURE SENSOR TO MAINTAIN 100% OF EXHAUST FAN BASED ON DUCT STATIC.

SUPPLY AIR HIGH PRESSURE

EXHAUST FAN (VFD)

EXHAUST AIR STATIC PRESSURE SENSOR

OA (NC)

AO

OUTSIDEAIR DAMPER

M

ENDSWITCH

ESDI

RA

H L

DI

FILTER

DX COOLINGCOIL

VFDLAN

AI CURRENT SENSINGAO SPEEDTO FIRE ALARM

DO START/STOP

SF

GAS FURNACE

HEATEXCHANGERPLATE

SUPPLY AIRTEMPERATURESENSOR

AI

TO FIREALARM

SMOKEDETECTOR

STATICPRESSURESENSOR

HL

AI

ENDSWITCH

ES

AO

DI

M

(NC)

AO

EXHAUSTAIR DAMPER (NC)

MENDSWITCH

ESDI

VFDLAN

AI CURRENT SENSINGAO SPEEDTO FIRE ALARM

DO START/STOP

EF

STATICPRESSURESENSOR

HL

AI

Scale: NTS

ERU CONTROL SEQUENCE

1

RETURN AIRTEMPERATURESENSOR

AI

H L

DI

EA

SA

DI

DWYER 1900HIGH PRESSURELIMIT WITH MANUALRESET

HL

DI DWYER 1900HIGH PRESSURELIMIT WITH MANUALRESET

HL

SUPPLY AIR HIGH PRESSURE

EXHAUST AIR HIGH PRESSURE

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

TO FIREALARM

SMOKEDETECTOR

SUPPLY/RETURN SMOKE DETECTORS

H&V UNITCONTROLDIAGRAM

M-508

-COLO

R GR

APHI

CS

EMER

GENC

Y PO

WER

PRO

GRAM

COIL

RESE

T PR

OGRA

M

ECON

OMIZ

ER P

ROGR

AM

NIGH

T SE

TBAC

K PR

OGRA

M

OPTI

MUM

STAR

T / S

TOP

PROG

RAM

TIME

SCH

EDUL

ING

EVEN

T PR

OGRA

M

FAN

SPEE

D

BTU

-LOW

LIMI

T

HIGH

LIMI

T

ANALOGAL

ARMS

PROO

F FA

ILURE

-

OUTPUTS

POST

ITIO

NING

SPEE

D CO

NTRO

L

-

ANALOG

OPEN

/CLO

SE

BYPA

SS S

TART

ER

STAR

T/ST

OP

ALAR

M

MOTO

R SP

EED

CURR

ENT

SENS

ING

DIIF

EREN

TIAL

PRE

SSUR

E

PRES

SURE

STAT

US -

OPEN

/CLO

SE

ENERGY MANAGEMENTAPPLICATIONS

APPLICATION SOFTWARE

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

DIGITAL DIGITAL

ALARMS

TYPE

STAT

US -

ON/O

FF

HV SYSTEM DDC INPUT / OUTPUT SUMMARY

DIFF

EREN

TIAL

PRE

SSUR

E

TEMP

ERAT

URE

RELA

TIVE

HUM

IDIT

Y

FLOW

RAT

E, C

FM

HIGH

LIMI

T

LOW

LIMI

T

CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

SCHE

DULE

- OC

CUPI

ED/U

NOCC

UPIE

D

RUN

TIME

TREN

D

SUPPLY AIR TEMPERATURE SENSOR

RETURN AIR TEMPERATURE SENSOR

SUPPLY FAN (VFD)

DIRTY FILTER SWITCH

OUTSIDE AIR DAMPER & END SWITCH

EXHAUST AIR DAMPER & END SWITCH

SAFETIES AND ALARMS

1. HV FILTER PRESSURE DROP - THE PRESSURE DROP ACROSS THE FILTER SHALL BE MONITORED BY THE BASSYSTEM ON THE H & V UNIT AS INDICATED. AN ALARM SHALL BE INDICATED AT THE WORKSTATION UPONCLOSURE OF ANY DIFFERENTIAL PRESSURE SWITCH.

2. SMOKE DETECTORS LOCATED IN THE SUPPLY AND RETURN DUCTWORK SHALL ALARM THE FIRE ALARM CONTROLPANEL IF A SMOKE CONDITION EXISTS. IN TURN THE FIRE ALARM CONTROL PANEL SHALL DE-ENERGIZE THESUPPLY FAN.

3. LOW PRESSURE AND HIGH PRESSURE SENSOR SHALL ALARM THE OPERATOR AND SHUT-DOWN THEASSOCIATED FAN.

4. TEMPERATURE ALARMSa. MONITOR SUPPLY AIR TEMPERATURE. PROVIDE LOW TEMPERATURE ALARM IF SUPPLY AIR TEMPERATUREDROPS BELOW 55° F.

HV CONTROL SEQUENCE

SPECIFIC CONTROL

1. START-UP OCCUPIED MODEa. NORMALLY CLOSED OUTDOOR AIR DAMPER AND EXHAUST FAN DAMPER SHALL OPEN. ONCE THE DAMPER

POSITION IS PROVEN, THE SUPPLY FAN SHALL START AND RAMP TO 50% AIRFLOW. WHENEVER THE SYSTEMIS IN OPERATION IN THE OCCUPIED MODE THE SUPPLY FAN SHALL OPERATE CONTINUOUSLY.

b. ONCE THE TEMPERATURE WITHIN THE BUILDING IS HEATED TO 65° F, THE BAS SHALL MONITOR THE ROOMTEMPERATURE SENSORS.

2. FAN SPEED CONTROLa. IN THE NORMAL OCCUPIED MODE THE SUPPLY FAN SPEED CONTROLS SHALL BE VIA THE DUCT MOUNTED

STATIC PRESSURE SENSOR TO MAINTAIN 100% OF SUPPLY CFM BASED ON DUCT STATIC.

3. GAS FURNACE CONTROLa. THE GAS FURNACE SHALL MODULATE IN ORDER TO MAINTAIN IT'S DISCHARGE TEMPERATURE SETPOINT AT

AN ADJUSTABLE SETPOINT OF 60° F.

4. SMOKE CONTROLa. UPON AN INDICATION OF SMOKE SENSED BY THE SUPPLY OR EXHAUST DUCT DETECTOR, THE FIRE ALARM

SYSTEM PROVIDE SIGNAL TO BAS SYSTEM TO SHUTDOWN SUPPLY FAN AND EXHAUST FAN, AND CLOSEOUTSIDE AIR DAMPER AND EXHAUST DAMPER.

b. FIRE SMOKE CONTROL PANEL SHALL PROVIDE SIGNAL TO BAS SYSTEM TO RESTART UNIT IN NORMAL MODE.

5. EXHAUST FAN CONTROLa. EXHAUST FAN SHALL BE ENERGIZED WHEN HV IS OPERATING IN NORMAL MODE.b. BEFORE STARTING EXHAUST FAN OPEN NORMALLY CLOSED AIR DAMPER. VERIFY DAMPER IS OPEN WITH

DAMPER END SWITCH.c. LOW PRESSURE SENSOR SHALL SHUTDOWN EXHAUST FAN AND PROVIDE ALARM TO THE OPERATOR.d. IN NORMAL OCCUPIED MODE THE EXHAUST FAN SPEED CONTROLS SHALL BE VIA THE DUCT MOUNTED STATIC

PRESSURE SENSOR TO MAINTAIN 100% OF EXHAUST CFM BASED ON STATIC.

SUPPLY AIR HIGH PRESSURE

EXHAUST FAN (VFD)

EXHAUST AIR STATIC PRESSURE SENSOR

Scale: NTS

HV CONTROL SEQUENCE

1

OA (NC)

AO

OUTSIDEAIR DAMPER

M

ENDSWITCH

ESDI

RA

H L

DI

FILTER

DX COOLINGCOIL

VFDLAN

AI CURRENT SENSINGAO SPEEDTO FIRE ALARM

DO START/STOP

SF

GAS FURNACE

HEATEXCHANGERPLATE

SUPPLY AIRTEMPERATURESENSOR

AI

TO FIREALARM

SMOKEDETECTOR

STATICPRESSURESENSOR

HL

AI

ENDSWITCH

ES

AO

DI

M

(NC)

AO

EXHAUSTAIR DAMPER (NC)

MENDSWITCH

ESDI

VFDLAN

AI CURRENT SENSINGAO SPEEDTO FIRE ALARM

DO START/STOP

EF

STATICPRESSURESENSOR

HL

AI

RETURN AIRTEMPERATURESENSOR

AI

H L

DI

EA

SA

DI

DWYER 1900HIGH PRESSURELIMIT WITH MANUALRESET

HL

DI DWYER 1900HIGH PRESSURELIMIT WITH MANUALRESET

HL

SUPPLY AIR HIGH PRESSURE

EXHAUST AIR HIGH PRESSURE

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

TO FIREALARM

SMOKEDETECTOR

SUPPLY/RETURN SMOKE DETECTORS

DETE

CTOR

TRI

PPED

AHU CONTROLDIAGRAM

M-509

M

AO

OUTSIDE AIRDAMPER

AI

MIXED AIRAVERAGINGTEMPERATURESENSOR

RA

H L

DI

FILTERS

DI

LH

AIHEATING DISCHARGEAVERAGINGTEMPERATURESENSOR

LOW LIMIT

CC

VFDLAN

SUPPLY AIRTEMPERATURESENSOR

AI

TEMPERATURE

-COLO

R GR

APHI

CS

EMER

GENC

Y PO

WER

PRO

GRAM

COIL

RESE

T PR

OGRA

M

ECON

OMIZ

ER P

ROGR

AM

NIGH

T SE

TBAC

K PR

OGRA

M

OPTI

MUM

STAR

T / S

TOP

PROG

RAM

TIME

SCH

EDUL

ING

EVEN

T PR

OGRA

M

FAN

SPEE

D

BTU

-LOW

LIMI

T

HIGH

LIMI

T

ANALOG

ALAR

MS

PROO

F FA

ILURE

-

OUTPUTS

POSI

TION

ING

SPEE

D CO

NTRO

L

-

ANALOGOP

EN/C

LOSE

BYPA

SS S

TART

ER

STAR

T/ST

OP

CO2,

PPM

MOTO

R SP

EED

CURR

ENT

SENS

ING

DIFF

EREN

TIAL

PRE

SSUR

E

PRES

SURE

STAT

US -

OPEN

/CLO

SE

ENERGY MANAGEMENTAPPLICATIONS

APPLICATION SOFTWARE

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

DIGITAL DIGITAL

ALARMS

TYPE

STAT

US -

ON/O

FF

AHU SYSTEM DDC INPUT / OUTPUT SUMMARY

DIFF

EREN

TIAL

PRE

SSUR

E

TEMP

ERAT

URE

RELA

TIVE

HUM

IDIT

Y

FLOW

RAT

E, C

FM

DETE

CTOR

TRI

PPED

- HIGH

LIMI

T

LOW

LIMI

T

CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

SCHE

DULE

- OC

CUPI

ED/U

NOCC

UPIE

D

RUN

TIME

TREN

D

SUPPLY AIR TEMPERATURE SENSOR

SUPPLY AIR STATIC PRESSURE SENSOR

RETURN AIR TEMPERATURE SENSOR

SUPPLY FAN (VFD)

COMPRESSOR CONTROLS (TYP.)

LOW TEMPERATURE SENSOR ALARM

HOT WATER PREHEAT COIL

MIXED AIR TEMPERATURE SENSOR

DIRTY FILTER SWITCH (TYPICAL FOR 2)

OUTSIDE AIR DAMPER & END SWITCH

HEATING DISCHARGE TEMPERATURE SENSOR

RETURN AIR DAMPER & END SWITCH

ENDSWITCH

ES

TO FIRE ALARM

DI

M

SMOKE DAMPER

SUPPLY AIR SMOKE DAMPER & END SWITCH

TO FIREALARM

SMOKEDETECTOR

DI

DWYER 1900HIGH PRESSURELIMIT WITH MANUALRESET

HL

SUPPLY AIR HIGH PRESSURE

VIBRATIONSENSOR (TYP)

VIBRATIONSWITCH W/ DI

CONTROL POINTON EACH FAN

AI CURRENT SENSINGAO SPEEDTO FIRE ALARM

DO START/STOP

RELIEF AIR DAMPER & END SWITCH

LOCATED 2/3 DISTANCEDOWNSTREAM LONGEST DUCT

REMOTESTATICPRESSURESENSOR

HL

AI

ES

DI

ENDSWITCH

(NC)

11. SUPPLY AIR TEMPERATURE RESET CONTROLa. BAS SYSTEM SHALL MONITOR ALL ROOM THERMOSTATS AND VAV BOX DAMPER POSITION.b. IF ALL THERMOSTATS ARE SATISFIED, AND ALL VAV BOX DAMPERS ARE LESS THAN 75% OPEN (ADJ.) AND THE

HUMIDITY LEVEL IS BELOW 50% RH THEN ENERGIZE THE SUPPLY AIR TEMPERATURE RESET MODE.c. RESET SUPPLY AIR TEMPERATURES 3° F HIGHER AND MONITOR THERMOSTATS, VAV BOX DAMPER POSITION AND

RETURN DUCT HUMIDITY LEVELS FOR 15 MINUTES (ADJ.).d. IF ALL CONDITIONS ARE SATISFIED FOR 15 MINUTES THEN INCREASE SUPPLY AIR TEMPERATURE AN ADDITIONAL

3° F EVERY 15 MINUTES UNTIL WE NO LONGER SATISFY ALL CONDITIONS.e. RESET SUPPLY AIR TEMPERATURE BACK TO INITIAL SETPOINT OF 55° F WHEN ALL CONDITIONS ARE NOT

SATISFIED.

12. MORNING WARM-UPa. CLOSE OUTSIDE AIR DAMPER.b. SUPPLY FAN SHALL START AND RAMP UP TO FULL AIRFLOW OR TO SATISFY DUCT STATIC PRESSURE SETPOINT

OF 1.5" WG.c. OPEN PREHEAT COIL CONTROL VALVE UNTIL BUILDING TEMPERATURE RETURNS TO 70° F.d. AFTER BUILDING REACHES 70° F, RESET TO NORMAL OPERATING MODE AND OPEN OUTSIDE AIR DAMPER TO

MINIMUM POSITION (10% OF OUTSIDE AIR).

13. MORNING COOL DOWNa. CLOSE OUTSIDE AIR DAMPERb. SUPPLY FAN SHALL START AND RAMP UP TO FULL AIRFLOW OR TO SATISFY DUCT STATIC PRESSURE SETPOINT

1.5" WG.c. CYCLE COMPRESSORS ON/OFF UNTIL BUILDING TEMPERATURE RETURNS TO 75° F.d. AFTER BUILDING REACHES 75° F, RESET TO NORMAL OPERATING MODE AND OPEN OUTSIDE AIR DAMPER TO

MINIMUM POSITION (10% OF OUTSIDE AIR).

14. DUCT STATIC RESETa. BAS SYSTEM SHALL MONITOR ALL VAV BOXES DAMPER POSITION.b. IF ALL DAMPERS ARE CLOSED MORE THAN 75%, THEN RESET SUPPLY AIR STATIC FROM 1.5" WG DOWN BY 0.25"

WG UNTIL ALL VAV BOX DAMPERS ARE LESS THAN 75% CLOSED. KEEP RESETTING 0.25"WG STEPS UNTIL ALL BOXDAMPERS ARE LESS THAN 75% CLOSED.

c. MONITOR ALL ROOM TEMPERATURES. IF ANY ROOM IS NOT MEETING ITS SETPOINT THEN RESET BACK TO 1.5"WG.

SAFETIES AND ALARMS

1. AHU FILTER PRESSURE DROP - THE PRESSURE DROP ACROSS THE FILTER SHALL BE MONITORED BY THE BASSYSTEM ON THE RTU UNIT AS INDICATED. AN ALARM SHALL BE INDICATED AT THE WORKSTATION UPON CLOSUREOF ANY DIFFERENTIAL PRESSURE SWITCH.

2. ALL FREEZESTATS SHALL BE MOUNTED DOWNSTREAM FROM THE PREHEAT COIL THEY ARE PROTECTING. THEFREEZE STAT SHALL BE SERPENTINED ACROSS THE DISCHARGE DUCTWORK. UPON ACTIVATION OF THEFREEZESTAT, THE FAN(S) SHALL BE DE-ENERGIZED. OUTDOOR AND RELIEF AIR DAMPERS SHALL CLOSECOMPLETELY AND THE RETURN AIR DAMPER SHALL OPEN, COMPRESSORS SHALL CYCLE ON/OFF AND THEOPERATOR IS NOTIFIED OF AN ALARM CONDITION. BAS SYSTEM SHALL BE CAPABLE TO RESET THE FREEZESTATTO NORMAL MODE.

3. SMOKE DETECTORS LOCATED IN THE SUPPLY AND RETURN DUCTWORK SHALL ALARM THE FIRE ALARM CONTROLPANEL IF A SMOKE CONDITION EXISTS. IN TURN THE FIRE ALARM CONTROL PANEL SHALL DE-ENERGIZE THESUPPLY FANS.

4. LOW PRESSURE AND HIGH PRESSURE SENSOR SHALL ALARM THE OPERATOR AND SHUT-DOWN THE ASSOCIATEDFAN.

AHU CONTROL SEQUENCE

SPECIFIC CONTROL

1. START-UP OCCUPIED MODEa. NORMALLY CLOSED OUTDOOR AIR DAMPER WILL REMAIN CLOSED AND NORMALLY OPEN RETURN AIR DAMPER

OPEN. UPON UNIT ACTIVATION THE SUPPLY SMOKE DAMPER SHALL BE POWERED OPEN. ONCE THE OPENPOSITION IS PROVED, THE SUPPLY FAN SHALL START AND RAMP TO STATIC PRESSURE SETPOINT (1.5" WG).WHENEVER THE SYSTEM IS IN OPERATION IN THE OCCUPIED MODE, THE SUPPLY FAN SHALL OPERATECONTINUOUSLY.

b. ONCE THE TEMPERATURE WITHIN THE BUILDING IS HEATED OR COOLED TO 70° TO 75° F RESPECTFULLY, THEOUTDOOR AIR DAMPER SHALL MODULATE TO ITS MINIMUM POSITION. (10% SUPPLY AIRFLOW)

2. START-UP UNOCCUPIED MODE a. NORMALLY CLOSED OUTDOOR AIR DAMPER WILL REMAIN CLOSED AND NORMALLY OPEN RETURN AIR DAMPER

OPEN. UPON UNIT ACTIVATION THE SUPPLY SMOKE DAMPER SHALL BE POWERED OPEN. ONCE THE OPENPOSITION IS PROVED, THE SUPPLE FAN SHALL START AND RAMP TO STATIC PRESSURE SETPOINT (1.5"WG). WHENEVER THE SYSTEM IS IN OPERATION IN THE UNOCCUPIED MODE, THE SUPPLY FAN SHALL STARTAND STOP AS REQUIRED TO MEET THE SET-BACK TEMPERATURE OF 55 ° F WINTER AND 80° F SUMMER.

3. SUPPLY FAN SPEED CONTROLa. IN THE OCCUPIED MODE THE SUPPLY FAN SPEED CONTROLS SHALL BE VIA THE DUCT-MOUNTED STATIC

PRESSURE SENSOR CONTROLLED AT (1.5" WG)(VERIFIED IN THE FIELD).b. IN THE UNOCCUPIED MODE, THE SUPPLY FAN SHALL OPERATE AT STATIC PRESSURE SETPOINT (1.5" WG).c. BAS CONTROL PANEL SHALL SUM ALL VAV BOXES CONNECTED TO AHU-1 TO PROVIDE SUPPLY AIR TOTAL.

4. RETURN FAN SPEED CONTROLa. IN THE OCCUPIED MODE THE RETURN FAN SPEED CONTROL SHALL BE VIA THE RETURN AIRFLOW MEASURING

STATION.b. THE BAS CONTROL PANEL SHALL COMPARE RETURN AIRFLOW TOTAL AND PROVIDE SIGNAL TO VFD TO

PROVIDE 500 CFM (ADJ.) OFFSET CALCULATED BY SUBTRACTING OUTSIDE AIR FROM AHU-1 SUPPLY AIR TOTAL,PLUS 500 CFM FOR BUILDING PRESSURIZATION. SEE AIR BALANCE SCHEDULE.

c. OUTSIDE AIR SHALL CHANGE WITH DEMAND CONTROL VENTILATION.

5. ECONOMIZERa. THE ECONOMIZER SHALL UTILIZE COMPARATIVE ENTHALPY ANALYSIS AS THE FIRST STAGE OF COOLING. THE

BAS SHALL CALCULATE THE OUTSIDE AND RETURN AIR ENTHALPY BASED ON OUTSIDE AND RETURN AIRHUMIDITY SENSORS. IF THE OUTDOOR AIR ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY, THEN THEOUTDOOR AIR AND RETURN AIR DAMPERS SHALL BE MODULATE TO MAINTAIN THE DISCHARGE AIRTEMPERATURE SETPOINT. IF ADDITIONAL COOLING IS REQUIRED THE UNIT MOUNTED CONTROL PANEL SHALLCYCLE COMPRESSORS ON/OFF TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT. WHEN THEOUTSIDE AIR HAS A HIGHER ENTHALPY THAN THE RETURN AIR, THE OUTDOOR AIR DAMPER SHALL REMAIN INITS MINIMUM POSITION.

6. HEATING CONTROLa. THE PREHEAT COIL CONTROL VALVE SHALL MODULATE IN ORDER TO MAINTAIN ITS DISCHARGE TEMPERATURE

SETPOINT AT AN ADJUSTABLE SETPOINT OF 50° F.

7. COOLING CONTROLa. THE UNIT MOUNTED CONTROL PANEL SHALL CYCLE COMPRESSORS ON/OFF IN THE AIR COOLED CONDENSING

UNIT IN ORDER TO MAINTAIN ITS DISCHARGE TEMPERATURE SETPOINT AT AN ADJUSTABLE SETPOINT OF 53° F.DX COOLING COIL AND THE PREHEAT COIL VALVES SHALL NEVER OPERATE AT THE SAME TIME.

8. SMOKE CONTROLa. UPON AN INDICATION OF SMOKE SENSED BY THE SUPPLY OR RETURN DUCT DETECTOR, THE FIRE ALARM

SYSTEM SHALL PROVIDE SIGNAL TO BAS SYSTEM TO SHUTDOWN SUPPLY FAN AND RETURN FAN, CLOSEOUTSIDE AIR DAMPER AND CLOSE ALL SMOKE DAMPERS.

b. FIRE SMOKE CONTROL PANEL SHALL PROVIDE SIGNAL TO BAS SYSTEM TO RESTART RTU SUPPLY IN NORMALMODE.

9. FREEZE PROTECTIONa. WHEN SUPPLY AIR TEMPERATURE FALLS BELOW 40°F WITHIN THE UNIT AND THE BUILDING IS IN UNOCCUPIED

MODE OPEN PREHEAT COIL VALVE AND START SUPPLY FAN TO HEAT THE BUILDING TO 60°F.

10. DEHUMIDIFICATION CONTROLa. WHEN DUCT MOUNTED HUMIDITY SENSOR SENSES HUMIDITY LEVELS ABOVE 55% RH THEN START

DEHUMIDIFICATION MODE.b. DEHUMIDIFICATION SHALL BE ACHIEVED WITH SUBCOOLING FROM DX COIL AND REHEAT FROM PREHEAT COIL

REHEAT COIL FOR FIRST STAGE.c. SECOND STAGE: MODULATE HOT WATER REHEAT CONTROL VALVE AT VAV BOX TO MAINTAINING ROOM

TEMPERATURE.d. RESET BACK TO NORMAL OPERATING MODE WHEN HUMIDIFY LEVELS DROP TO 45% RH FOR 20 MINUTES. UNIT

SHALL BE RESET TO THE PREVIOUS ROOM OR DISCHARGE AIR TEMPERATURE AFTER HUMIDITY LEVELS REMAINSTEADY FOR 20 MINUTES.

ALAR

M

DUCT SMOKE DAMPERS & END SWITCHES(TYP.)

AO

RETURN AIRDAMPER

M

ENDSWITCH

ESDI

M

AO

RELIEF AIRDAMPER

ES

DI

ENDSWITCH

VFDLAN

VIBRATIONSENSOR (TYP)

VIBRATIONSWITCH W/ DI

CONTROL POINTON EACH FAN

AI CURRENT SENSINGAO SPEEDTO FIRE ALARM

DO START/STOP

RF1

RELIEF AIR OUTSIDE AIR

RETURN AIRHUMIDITYSENSOR

RETURN AIRTEMPERATURESENSOR

AIAI

TO FIREALARM

SMOKEDETECTOR

CO2SENSOR

AI

DX COOLINGCOIL AI

CONDENSING UNITOUTDOOR AIR COOLED

CH

HWR

HWS

(NO)

Scale: NTS

AHU-1 CONTROL DIAGRAM

1

OUTSIDE AIR HUMIDITY SENSOR

OUTSIDE AIR TEMP SENSOR

OUTSIDE AIRTEMPERATURESENSOR

AIAI

OUTSIDE AIRHUMIDITYSENSOR

ROOM CO2SENSOR

AI

AO

M

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

FZ FREEZESTAT

SUPPLY/RETURN SMOKE DETECTORS

FREEZESTAT

HEATING HOTWATER

CONTROLDIAGRAMS

M-510

MECHANICAL ROOM

HOT WATER PUMPS

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

DIGITAL ANALOG

OUTPUTS

DIGITAL ANALOG

ALARMS

TYPE

SOFTWARE

APPLICATION ENERGY MANAGEMENT

COLO

R GR

APHI

CS

DIFF

EREN

TIAL

PRE

SSUR

E SW

ITCH

TEMP

ERAT

URE

DIFF

EREN

TIAL

PRE

SSUR

E

OPEN

/ CLO

SE

STAR

T/ST

OP

POSI

TION

ING

SPEE

D CO

NTRO

L

HIGH

LIMI

T

LOW

LIMI

T

TIME

SCH

EDUL

ING

EVEN

T PR

OGRA

M

PEAK

DEM

AND

LIMIT

ING

PROG

RAM

EMER

GENC

Y PO

WER

PRO

GRAM

OPTI

MUM

STAR

T / S

TOP

PROG

RAM

TOTA

LIZAT

ION

TREN

D

HIGH

LIMI

T

LOW

LIMI

T

CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

PROO

F FA

ILURE

RUN

TIME

STAT

US -

ON / O

FF

FLOW

RAT

E - T

ONS

CONS

UMPT

ION

- TON

HOU

RS E

06

CURR

ENT

SENS

ING

MOTO

R SP

EED

BYPA

SS S

TART

ER

SETP

OINT

ADJ

USTM

ENT

TEMP

ERAT

URE

BTU

POSI

TION

/ MOD

E DI

SPLA

Y

HEATING HOT WATER SYSTEM - DDC INPUT / OUTPUT SUMMARY

VFD

DO START / STOPAO SPEED ADJUSTMENT

SERIAL INTERFACE INTO BAS (DDC)

LAN

AI CURRENT SENSING

BOILER HOT WATER PUMP BP/1(TYP FOR BP/2)

ALAR

M

BOILER B/1

OPEN

/CLO

SED

BOILER B/2

DIFFERENTIAL PRESSURE AT BP/1, BP/2

HEATING HOT WATER SUPPLY TEMPERATURE

HEATING HOT WATER RETURN TEMPERATURE

GENERAL

A. THE HEATING HOT WATER SYSTEM CONSISTS OF TWO BOILERS AND TWO PUMPS, LOCAL DIFFERENTIAL PRESSURE TRANSMITTERS, TEMPERATURETRANSMITTERS AND PIPING. THE REHEAT WATER PUMP(P-3) IS SIZED TO HANDLE 100% OF THE REHEAT WATER FLOW. THE SECOND PUMP(P-4) PROVIDES100% BACKUP CAPACITY FOR ONE HOT WATER PUMP. EACH BOILER PUMP IS SIZED FOR 100% FLOW OF EACH BOILER.

B. THE BAS SHALL SHALL PROVIDE FOR AUTOMATIC ROTATION OF THE PUMPS AND BOILERS BASED ON RUN TIME. IT IS DESIRABLE TO EQUALIZE THE RUN TIMEOF THE PUMPS, ANY PUMP MAY BE DESIGNATED AS THE STANDBY PUMP AT ANY TIME FROM THE BAS. THIS ACTION SHALL CAUSE THE NEWLY DESIGNATEDSTANDBY PUMP TO BE AUTOMATICALLY COMMANDED OFF, IF IT IS RUNNING. THE PREVIOUSLY DESIGNATED STANDBY PUMP SHALL ASSUME THE ROLE FORTHE NEWLY DESIGNATED OPERATING PUMP. AUTOMATIC DESIGNATION OF THE STANDBY PUMP SHALL OCCUR WEEKLY OR OTHER TIME DURATION ASREVISED BY THE BAS SYSTEM OPERATOR'S CONSOLE, BASED ON HOURS OF OPERATION. THE PUMP WITH THE LOWEST RUNNING HOURS SHALL BEDESIGNATED THE OPERATING PUMP.

C. UPON CALL FOR THE FIRST PUMP TO START, IF FLOW IS NOT PROVEN WITH 20 SECONDS (ADJUSTABLE), THE "NEXT" PUMP SHALL BE SEQUENCED "ON" AND ANALARM SHALL BE REGISTERED AT THE BAS OPERATOR'S CONSOLE. THE "NEXT" PUMP SHALL BE SEQUENCED "ON" IN THE EVENT OF ANY PUMP FAILUREDURING OPERATION.

D. PUMPING SEQUENCE - DIFFERENTIAL PRESSURE (DP) TRANSMITTERS SHALL BE LOCATED AT THE MAIN PIPING RUN ACROSS THE SUPPLY AND RETURN PIPING.THE VARIABLE FREQUENCY MOTOR SPEED CONTROLLER SHALL BE MODULATED TO AN AVERAGE SETPOINT MAINTAIN SETPOINT AT THE TRANSMITTERS. IFTHE VARIABLE FREQUENCY SPEED CONTROLLER IS AT A MINIMUM THEN THE CONTROL VALVE AT THE END OF THE MAINS SHALL MODULATE OPEN TO MAINTAINTHE PRESSURE IN THE SYSTEM. DIFFERENTIAL PRESSURE SHALL BE 30 PSIG (ADJUSTABLE).

E. HEATING SYSTEM SHALL OPERATE YEARLY TO PROVIDE HEATING HOT WATER TO BUILDING REHEAT AND RADIANT FLOOR HEATING SYSTEM.

F. WINTER MODE - WHEN THE OUTSIDE AIR TEMPERATURE FALLS BELOW 30°F THE HEATING SYSTEM SHALL GENERATE 190°F HOT WATER SUPPLYTEMPERATURE. THE BOILER CONTROLS SHALL MODULATE TO PROVIDE 140°F HEATING HOT WATER SUPPLY TEMPERATURE AT 30°F OUTDOOR AIRTEMPERATURE AND BELOW. THE HEATING HOT WATER SUPPLY TEMPERATURE SHALL BE RESET BASED ON THE OUTDOOR AIR TEMPERATURE ABOVE 30°F TOA SUPPLY WATER TEMPERATURE OF 130°F BASED ON AN OUTDOOR AIR TEMPERATURE OF 60°F.

G. SUMMER MODE - WHEN THE OUTDOOR AIR TEMPERATURE IS ABOVE 60°F AND THE BUILDING IS IN THE COOLING MODE, THE HEATING SYSTEM SHALL SUPPLYHOT WATER REHEAT AT 130°F.

CONTROL SEQUENCES FOR HEATING HOT WATER SYSTEM

BOILER B/1 AND B/2

A. ANY BOILER SHALL OPERATE AT A TIME AND SHALL BE INDEXED ON/OFF BY BAS SYSTEM. THE BOILERS SHALLBE ROTATED BASED ON A USER DEFINED SCHEDULE. THE BOILER HOT WATER PUMP MUST START FIRST.

B. THE BOILER CONTROL PANEL SHALL MAINTAIN THE TEMPERATURE AS NOTED IN ITEM "F" AND "G".

C. THE SECOND BOILER SHALL START IF THE SUPPLY TEMPERATURE IS NOT MAINTAINED.

VFD

DO START / STOPAO SPEED ADJUSTMENT

SERIAL INTERFACE INTO BAS (DDC)

LAN

AI CURRENT SENSING

P3

P4

STANDBY

P1

P2

STANDBY

HWS

HWR

AS1

ET1

AUTOMATICAIR VENT

TO F.D.P

TOF.D.

SYSTEM FILLONLY (N.C.)

HOT WATER REHEATSYSTEM 140°F TO 120°F

HOT WATER RADIANTFLOOR SYSTEM 100°FTO 90°F(ALTERNATE)

BYPASSCHEMICALFEEDER B

1

BP1

B2

BP2

AIAI

TAI

M

TOUTDOORTHERMOSTAT

AI

AOT

AI

AI

M

AO

TAI

TAI

STARTER

LAN

DO START / STOP

AI CURRENT SENSING

D/P

AI

D/P

AI

STARTER

SERIAL INTERFACE INTO BAS (DDC)

LAN

DO START / STOP

AI CURRENT SENSING

REHEAT HOT WATER PUMP P/3 VFD & P/4 VFD

DIFFERENTIAL PRESSURE P/3, P/4

REHEAT HOT WATER SUPPLY TEMPERATURE

REHEAT HOT WATER RETURN TEMPERATURE

3-WAY MIXING CONTROL VALVE

OUTSIDE TEMPERATURE SENSOR

REMOTE DIFFERENTIAL PRESSURE SENSOR

REHEAT SYSTEM

A. REHEAT SYSTEM SHALL MODULATE 3-WAY CONTROL VALVES TO CONTROL WATER TEMPERATURE FROM 160°FWHEN OUTSIDE AIR TEMPERATURE IS BELOW 40°F TO 130°F WHEN OUTSIDE AIR TEMPERATURE IS ABOVE 60°F.

B. WATER TEMPERATURE SHALL BE LINEAR BETWEEN 160°F AND 130°F BASED ON OUTSIDE AIR TEMPERATURE.

HOT WATER PUMPS

VFD

DO START / STOPAO SPEED ADJUSTMENT

SERIAL INTERFACE INTO BAS (DDC)

LAN

AI CURRENT SENSINGVFD

DO START / STOPAO SPEED ADJUSTMENT

SERIAL INTERFACE INTO BAS (DDC)

LAN

AI CURRENT SENSING

Scale: NTS

HEATING HOT WATER SYSTEM CONTROL DIAGRAM

1

REHEAT HOT WATER PUMP P/1 VFD & P/2 VFD

DIFFERENTIAL PRESSURE P/1, P/2

STANDBY

STANDBY

D/P

D/PD/P

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

RADIANT FLOORCONTROLDIAGRAM

M-511A

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

DIGITAL ANALOG

OUTPUTS

DIGITAL ANALOG

ALARMS

TYPE

SOFTWARE

APPLICATION ENERGY MANAGEMENT

COLO

R GR

APHI

CS

DIFF

EREN

TIAL

PRE

SSUR

E SW

ITCH

TEMP

ERAT

URE

DIFF

EREN

TIAL

PRE

SSUR

E

OPEN

/ CLO

SE

STAR

T/ST

OP

POSI

TION

ING

SPEE

D CO

NTRO

L

HIGH

LIMI

T

LOW

LIMI

T

TIME

SCH

EDUL

ING

EVEN

T PR

OGRA

M

PEAK

DEM

AND

LIMIT

ING

PROG

RAM

EMER

GENC

Y PO

WER

PRO

GRAM

OPTI

MUM

STAR

T / S

TOP

PROG

RAM

TOTA

LIZAT

ION

TREN

D

HIGH

LIMI

T

LOW

LIMI

T

CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

PROO

F FA

ILURE

RUN

TIME

STAT

US -

ON / O

FF

FLOW

RAT

E - T

ONS

CONS

UMPT

ION

- TON

HOU

RS E

06

CURR

ENT

SENS

ING

MOTO

R SP

EED

BYPA

SS S

TART

ER

CHILL

ED W

ATER

RES

ET P

ROGR

AM

SETP

OINT

ADJ

USTM

ENT

TEMP

ERAT

URE

BTU

POSI

TION

/ MOD

E DI

SPLA

Y

RADIANT HEATING SYSTEM - DDC INPUT / OUTPUT SUMMARY

HEATING HOT WATER PUMP P/1(TYP. FOR P/2)

ALAR

M

HOT WATER MIXING VALVE

OPEN

/CLO

SED

DIFFERENTIAL PRESSURE AT P/1 & P/2

HOT WATER SUPPLY TEMPERATURE SENSOR (TYP.)

HOT WATER RETURN TEMPERATURE SENSOR (TYP.)

HOT WATER DIFFERENTIAL BYPASS VALVE

HOT WATER BYPASS VALVE DIFFERENTIALPRESSURE SENSOR

GENERAL

A. THE RADIANT HEATING SYSTEM SHALL CONSIST OF FOUR PUMPS, LOCAL DIFFERENTIAL PRESSURE TRANSMITTERS FOR EACH SYSTEMS PUMPS,TEMPERATURE TRANSMITTERS AND PIPING. ONE WATER PUMP EACH IS SIZED TO HANDLE 100% OF THE HEATING WATER FLOW. THE SECOND PUMPPROVIDES 100% BACKUP CAPACITY FOR THE FIRST HEATING WATER PUMP.

B. THE BAS SHALL SHALL PROVIDE FOR AUTOMATIC ROTATION OF THE PUMPS BASED ON RUN TIME. IT IS DESIRABLE TO EQUALIZE THE RUN TIME OF THEPUMPS, EITHER PUMP MAY BE DESIGNATED AS THE STANDBY PUMP AT ANY TIME FROM THE BAS. THIS ACTION SHALL CAUSE THE NEWLY DESIGNATEDSTANDBY PUMP TO BE AUTOMATICALLY COMMANDED OFF IF IT IS RUNNING. THE PREVIOUSLY DESIGNATED STANDBY PUMP SHALL ASSUME THE ROLEFOR THE NEWLY DESIGNATED OPERATING PUMP. AUTOMATIC DESIGNATION OF THE STANDBY PUMP SHALL OCCUR WEEKLY OR OTHER TIME DURATIONAS REVISED BY THE BAS SYSTEM OPERATOR'S CONSOLE, BASED ON HOURS OF OPERATION. THE PUMP WITH THE LOWEST RUNNING HOURS SHALL BEDESIGNATED THE OPERATING PUMP.

C. UPON CALL FOR A PUMP TO START HEATING, IF FLOW IS NOT PROVEN WITH 20 SECONDS (ADJUSTABLE), THE "NEXT" PUMP SHALL BE SEQUENCED "ON"AND AN ALARM SHALL BE REGISTERED AT THE BAS OPERATOR'S CONSOLE. THE "NEXT" PUMP SHALL BE SEQUENCED "ON" IN THE EVENT OF ANY PUMPFAILURE DURING OPERATION.

D. PUMPING SEQUENCE - A DIFFERENTIAL PRESSURE (DP) TRANSMITTER AT THE MAIN RUN ACROSS THE SUPPLY AND RETURN PIPING. THE VARIABLEFREQUENCY MOTOR SPEED CONTROLLER SHALL BE MODULATED TO MAINTAIN SETPOINT AT THE TRANSMITTER. IF ALL VALVES ON THE HEATING ARECLOSED AND THE DIFFERENTIAL PRESSURE SENSOR READS A HIGH PRESSURE AND THE VARIABLE FREQUENCY SPEED CONTROLLER IS AT A MINIMUMTHEN THE BYPASS CONTROL VALVE AT THE MAIN SHALL MODULATE OPEN TO MAINTAIN THE PRESSURE OF 30 PSIG IN THE SYSTEM.

E. THE RADIANT HEATING SYSTEM SHALL BE ENABLED WHENEVER THE OUTDOOR AIR TEMPERATURE IS 30°F (ADJUSTABLE) OR BELOW.

F. WHENEVER THE RADIANT HEATING CONTROL VALVES ARE CLOSED AND THE PUMP VFD IS AT A MINIMUM AND THE MAIN SENSES A HIGH PRESSURE ATTHE MAIN CONTROL VALVE SHALL MODULATE OPEN TO MAINTAIN AN ADJUSTABLE PRESSURE SETTING AT THE DIFFERENTIAL PRESSURE SENSOR.

CONTROL SEQUENCES FOR RADIANT HEATING SYSTEM

HEATING CONTROL

A. RADIANT HOT WATER SUPPLY AND RETURN TEMPERATURES SHALL BE MONITORED BY THE BAS SYSTEM.

B. A 3-WAY MIXING VALVE SHALL MIX 180°F BUILDING HEATING HOT WATER AND RADIANT HOT WATER RETURN TOPROVIDE 90°F RADIANT HOT WATER SUPPLY.

C. IF RADIANT HOT WATER SUPPLY TEMPERATURE REACHES ABOVE 100°F, PROVIDE AN ALARM AT BAS OPERATORSSTATION AND DE-ENERGIZE P/4 AND OR P/5.

D. MODULATE NORMALLY OPEN 2-WAY CONTROL VALVE (ON THE PRIMARY HOT WATER RETURN LINE) CLOSED TOMAINTAIN 20°F DELTA TEMPERATURE DIFFERENCE BETWEEN PRIMARY HOT WATER SUPPLY AND RETURN.

VPC MAIN FLOOR

LEVEL 00

HWR(RAD)

HWS(RAD)

HWR(180°F)HWS(180°F)

HWR(

RAD)HW

S(RA

D)

HWS(RAD)

HWR(RAD)

HEADERSTYP.

MANIFOLDPANEL TYP.

M

VFD

SERIAL INTERFACE INTO BAS (DDC)

LAN

DO START / STOPAO SPEED ADJUSTMENTAI CURRENT SENSINGVFD

SERIAL INTERFACE INTO BAS (DDC)

LAN

DO START / STOP

AO SPEED ADJUSTMENTAI CURRENT SENSING

D/P

AI

D/P

AI

T

AI

ROOM WALLTEMPERATURESENSOR (TYP.)

TAI

TAI

AO

ROOM CONTROL

A. ROOM TEMPERATURE SENSOR SHALL MONITOR ROOM TEMPERATURE SETPOINT OF 65°F (ADJUSTABLE) HEATING.THE OCCUPANT SHALL BE ABLE TO ADJUST +/- 2°F FROM SETPOINT.

B. UPON A CALL FOR HEATING BY THE ROOM SENSOR THE TWO THREE-WAY VALVES SHALL MODULATE FULL OPEN FORHEATING SENDING HOT WATER TO THE MANIFOLD PANEL.

C. EACH MANIFOLD PANEL WILL HAVE UP TO 8 - 5/8" CIRCUITS, EACH BALANCED TO 1.5 GPM PER CIRCUIT. MAXIMUMCIRCUIT LENGTH SHALL BE 400 FEET.

ROOM TEMPERATURE SENSOR (TYP.)

MAO

D/P

AOHOT WATER

MIXING VALVE

TAI

TAI

M

RADIANT HEATING WATER(100°F TO 90°F)

P1 P

2

STANDBY

INLINE PUMPWITH VFD

INLINE PUMPWITH VFD

Scale: NTS

RADIANT HEATING CONTROL DIAGRAM

1

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

VAV CONTROLDIAGRAMS

M-512

NOTES:

1) REFER TO THE PLAN DRAWINGS FOR THE NUMBER OF AIR TERMINALS IN EACHZONE.

2) PROVIDE TEMPERATURE SENSORS FOR EACH TERMINAL AS SHOWN ON PLANS.

3) VAV TERMINALS SHALL HAVE THE MINIMUM AIRFLOW QUANTITY SET AT QTYSHOWN IN SCHEDULES.

4) REFER TO PLAN DRAWINGS FOR THE NUMBER AND LOCATION OF TERMINALSTO BE PROVIDED WITH 3-WAY VALVES.

ZONE

HC AI

AO

SENSORTEMPERATURE

CONTROLLER

AIR VOLUMESENSOR

AIRTEMPERATURESENSOR

AIRSUPPLY

HWS

HWR

AIRSUPPLY

SUPPLY AIR TERMINAL

LAN TRUNK

POWERS

--ROOM

OCC

UPIE

D / U

NOCC

UPIE

D

MAIN

TENA

NCE

ALAR

M

ABNO

RMAL

ALA

RM

CRIT

ICAL

ALA

RM

-LOW

LIMI

T

HIGH

LIMI

T

-POSI

TION

ING

CO2 L

EVEL

S

FLOW

RAT

E

TEMP

ERAT

URE

-

OCCUPANCY SENSOR

VAV TERMINAL DDC INPUT / OUTPUT SUMMARY

OUT -PUTS

STAT

US -

OCCU

PIED

/ UNO

CCUP

IED

APPLICATIONSOFTWARE

REHEAT COIL VALVE

VAV SUPPLY AIR TERMINAL

TYPE

ALARMS

DIGITALANALOG

INPUTS

ANALOGDIGITAL

CONNECTED POINTS

POINT DESCRIPTION

SPACE TEMPERATURE TRANSMITTER

DISCHARGE AIR TEMPERATURE SENSOR

AO

VAV CONTROL SEQUENCENORMAL OPERATION

1. VAV SUPPLY TERMINAL SHALL MODULATE BETWEEN MAXIMUM AND MINIMUM AIR VOLUMES TO MAINTAIN SPACE TEMPERATURE. AT MINIMUM AIR VOLUME (40%), IF SPACETEMPERATURE FALLS BELOW SETPOINT, THE REHEAT COIL VALVE SHALL MODULATE OPEN AS REQUIRED TO RAISE SPACE TEMPERATURE TO SETPOINT. THE VAV TERMINALAND REHEAT COIL VALVE SHALL BE CONTROLLED FROM THE AIR TEMPERATURE SENSOR DOWNSTREAM FROM THE REHEAT COIL, WHICH SHALL HAVE ITS SETPOINT RESETFROM THE ROOM TEMPERATURE SENSOR.

2. THE TEMPERATURE OF THE SUPPLY AIR, ALONG WITH THE RESPECTIVE AIR VOLUME, SHALL BE MEASURED AND INPUT INTO THE CONTROLLER. THE CONTROLLER SHALLADJUST THE HEATING VALVE ON THE SUPPLY AIR REHEAT COIL, BASED ON THOSE INPUTS AS WELL AS AN INPUT FROM A SPACE TEMPERATURE SENSOR. IF THE DISCHARGEAIR TEMPERATURE REQUIRED TO SATISFY THE SPACE TEMPERATURE EXCEEDS DESIGN, RESET THE HEATING CFM (OR MIN SUPPLY CFM) UP TO A LARGER CFM (60%) UNTILTHE DISCHARGE TEMPERATURE IS LESS THAN THE DESIGN DISCHARGE TEMPERATURE SETPOINT. MAXIMUM DESIGN DISCHARGE AIR TEMPERATURE SHALL BE 95°F.

3. FOR ROOMS THAT HAVE MULTIPLE ZONES, THE VAV TERMINAL CONTROLS SHALL BE TIED TOGETHER IN ORDER TO PREVENT SIMULTANEOUS HEATING AND COOLING OF THESAME SPACE.

UNOCCUPIED ROOM OPERATION

1. THE UNOCCUPIED MODE OF OPERATION FOR MEETING ROOMS IS DETERMINED BY OCCUPANCY SENSOR. DURING THIS MODE OF UNOCCUPIED OPERATION THE SPACETEMPERATURE COOLING AND HEATING SETPOINTS SHALL BE RESET BY AN ADJUSTABLE VALUE THAT CHANGES FOR OCCUPIED PERIODS AND UNOCCUPIED PERIODS. THEDESIGN SHOULD START WITH A ±1° F DURING OCCUPIED PERIODS AND ±3° F DURING UNOCCUPIED PERIODS. AS THE SPACE REQUIRES MORE AIR FLOW TO MAINTAIN THECOOLING TEMPERATURE SETPOINT, THE SUPPLY AIR TERMINALS SHALL MODULATE, ENSURING THAT THE DESIGN IS MAINTAINED. AT ALL TIMES THE COOLING MAXIMUM CFMVALUE SHALL BE POSSIBLE, SHOULD SPACE SENSIBLE COOLING LOAD REQUIRE THIS VALUE. UPON A RETURN TO OCCUPANCY SENSED BY THE OCCUPANCY SENSOR, ATEMPERATURE CONTROL ALGORITHM SHALL CONTROL THE TERMINALS AND REHEAT TO MINIMIZE CHANGES IN SPACE TEMPERATURE TO LESS THAN ±1° F.

UNOCCUPIED BUILDING OPERATION

1. THE UNOCCUPIED MODE OF OPERATION IS DETERMINED BY THE BUILDING SCHEDULE. SPACE TEMPERATURE SHALL BE MONITORED BY THE BAS. THE SPACES SHALLINCREASE TO A MAXIMUM OF 80° F SUMMER OR DECREASE A MINIMUM OF 55° F WINTER.

2. WHEN THREE(3) OR MORE ZONES REACH MAXIMUM OR MINIMUM SPACE SET POINT, PROVIDE SIGNAL TO BAS SYSTEM TO RESTART ROOFTOP UNIT (RTU) AND RESET VAVCONTROL TO MAXIMUM COOLING OR MAXIMUM REHEAT TO RECOVERY SPACE TEMPERATURE BACK TO 70° F AND THEN SHUT DOWN RTU.

AIRRETURN

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

ANALOG DIGITAL

ALARMS

TYPE

VAV SUPPLY AIR TERMINAL

REHEAT COIL VALVE

SPACE TEMPERATURE TRANSMITTER

APPLICATIONSOFTWARE

STAT

US -

OCCU

PIED

/ UNO

CCUP

IED

OUT -PUTS

VAV TERMINAL DDC INPUT / OUTPUT SUMMARY

- TEMP

ERAT

URE

PRES

SURE

POSI

TION

ING

- HIGH

LIMI

T

LOW

LIMI

T

- CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

ROOM

OCC

UPIE

D / U

NOCC

UPIE

D

- -

POWERS

LAN TRUNK

SUPPLY AIR TERMINAL

SUPPLYAIR

HWR

HWS

SUPPLYAIR

AIRTEMPERATURESENSOR

AIR VOLUMESENSOR

CONTROLLER

TEMPERATURESENSOR

AI

RETURNAIR

AICH

ZONE

NOTES:

1) REFER TO THE PLAN DRAWINGS FOR THE NUMBER OF AIR TERMINALS IN EACH ZONE.

2) PROVIDE TEMPERATURE SENSORS FOR EACH TERMINAL AS SHOWN ON PLANS.

3) VAV TERMINALS SHALL HAVE THE MINIMUM AIRFLOW QUANTITY SET AS SHOWN INSCHEDULES.

4) REFER TO THE PLAN DRAWINGS FOR THE NUMBER AND LOCATION OF AIR TERMINALSTO BE PROVIDED WITH 3-WAY VALVES.

AIRF

LOW

RAT

E

VAV CONTROL SEQUENCENORMAL OPERATION

1. VAV SUPPLY TERMINAL SHALL MODULATE BETWEEN MAXIMUM AND MINIMUM AIR VOLUMES TO MAINTAIN SPACE TEMPERATURE. AT MINIMUM AIR VOLUME (40%), IF SPACETEMPERATURE FALLS BELOW SETPOINT, THE REHEAT COIL VALVE SHALL MODULATE OPEN AS REQUIRED TO RAISE SPACE TEMPERATURE TO SETPOINT. THE VAV TERMINALAND REHEAT COIL VALVE SHALL BE CONTROLLED FROM THE AIR TEMPERATURE SENSOR DOWNSTREAM FROM THE REHEAT COIL, WHICH SHALL HAVE ITS SETPOINT RESETFROM THE ROOM TEMPERATURE SENSOR.

2. THE TEMPERATURE OF THE SUPPLY AIR, ALONG WITH THE RESPECTIVE AIR VOLUME, SHALL BE MEASURED AND INPUT INTO THE CONTROLLER. THE CONTROLLER SHALLADJUST THE HEATING VALVE ON THE SUPPLY AIR REHEAT COIL, BASED ON THOSE INPUTS AS WELL AS AN INPUT FROM A SPACE TEMPERATURE SENSOR. IF THE DISCHARGEAIR TEMPERATURE REQUIRED TO SATISFY THE SPACE TEMPERATURE EXCEEDS DESIGN, RESET THE HEATING CFM (OR MIN SUPPLY CFM) UP TO A LARGER CFM (60%) UNTILTHE DISCHARGE TEMPERATURE IS LESS THAN THE DESIGN DISCHARGE TEMPERATURE SETPOINT. MAXIMUM DESIGN DISCHARGE AIR TEMPERATURE SHALL BE 95°F.

UNOCCUPIED BUILDING OPERATION

1. THE UNOCCUPIED MODE OF OPERATION IS DETERMINED BY THE BUILDING SCHEDULE. SPACE TEMPERATURE SHALL BE MONITORED BY THE BAS. THE SPACES SHALL INCREASETO A MAXIMUM OF 80° F SUMMER OR DECREASE A MINIMUM OF 55° F WINTER.

2. WHEN THREE(3) OR MORE ZONES REACH MAXIMUM OR MINIMUM SPACE SET POINT, PROVIDE SIGNAL TO BAS SYSTEM TO RESTART ROOFTOP UNIT (RTU) AND RESET VAVCONTROL TO MAXIMUM COOLING OR MAXIMUM REHEAT TO RECOVERY SPACE TEMPERATURE BACK TO 70° F AND THEN SHUT DOWN RTU.

-

AO

AO

DISCHARGE AIR TEMPERATURE SENSOR

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

ANALOG DIGITAL

ALARMS

TYPE

VAV SUPPLY AIR TERMINAL

REHEAT COIL VALVE

SPACE TEMPERATURE TRANSMITTER

APPLICATIONSOFTWARE

STAT

US -

OCCU

PIED

/ UNO

CCUP

IED

OUT -PUTS

VAV TERMINAL DDC INPUT / OUTPUT SUMMARY- TE

MPER

ATUR

E

PRES

SURE

POSI

TION

ING

- HIGH

LIMI

T

LOW

LIMI

T

- CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

ROOM

OCC

UPIE

D / U

NOCC

UPIE

D

- -

POWERS

LAN TRUNK

SUPPLY AIR TERMINAL

SUPPLYAIR

HWR

HWS

SUPPLYAIR

AIRTEMPERATURESENSOR

AIR VOLUMESENSOR

CONTROLLER

TEMPERATURESENSOR

RETURNAIR

AICH

ZONE

NOTES:

1) REFER TO THE PLAN DRAWINGS FOR THE NUMBER OF AIR TERMINALS IN EACH ZONE.

2) PROVIDE TEMPERATURE SENSORS FOR EACH TERMINAL AS SHOWN ON PLANS.

3) VAV TERMINALS SHALL HAVE THE MINIMUM AIRFLOW QUANTITY SET AS SHOWN INSCHEDULE.

4) REFER TO THE PLAN DRAWINGS FOR THE NUMBER AND LOCATION OF TERMINALS TOBE PROVIDED WITH 3-WAY VALVES.

CO2 SENSOR

AIRF

LOW

RAT

E

CO2 SENSOR

CO 2

LEVE

LS

AI

AO

AO

DISCHARGE AIR TEMPERATURE SENSOR

VAV CONTROL SEQUENCENORMAL OPERATION

1. VAV SUPPLY TERMINAL SHALL MODULATE BETWEEN MAXIMUM AND MINIMUM AIR VOLUMES TO MAINTAIN SPACE TEMPERATURE. AT MINIMUM AIR VOLUME (40%), IF SPACE TEMPERATURE FALLSBELOW SETPOINT, THE REHEAT COIL VALVE SHALL MODULATE OPEN AS REQUIRED TO RAISE SPACE TEMPERATURE TO SETPOINT. THE VAV TERMINAL AND REHEAT COIL VALVE SHALL BECONTROLLED FROM THE AIR TEMPERATURE SENSOR DOWNSTREAM FROM THE REHEAT COIL, WHICH SHALL HAVE ITS SETPOINT RESET FROM THE ROOM TEMPERATURE SENSOR.

2. THE TEMPERATURE OF THE SUPPLY AIR, ALONG WITH THE RESPECTIVE AIR VOLUME, SHALL BE MEASURED AND INPUT INTO THE CONTROLLER. THE CONTROLLER SHALL ADJUST THE HEATINGVALVE ON THE SUPPLY AIR REHEAT COIL, BASED ON THOSE INPUTS AS WELL AS AN INPUT FROM A SPACE TEMPERATURE SENSOR. IF THE DISCHARGE AIR TEMPERATURE REQUIRED TOSATISFY THE SPACE TEMPERATURE EXCEEDS DESIGN, RESET THE HEATING CFM (OR MIN SUPPLY CFM) UP TO A LARGER CFM (60%) UNTIL THE DISCHARGE TEMPERATURE IS LESS THAN THEDESIGN DISCHARGE TEMPERATURE SETPOINT. MAXIMUM DESIGN DISCHARGE AIR TEMPERATURE SHALL BE 95°F.

CO2 OPERATION

1. IF THE CO2 SENSOR MEASURES CO2 CONCENTRATION ABOVE 800 PPM (ADJUSTABLE), THE VAV TERMINAL SHALL INCREASE THE AIRFLOW TO MAINTAIN 800 PPM ± 50 PPM TO THE SPACE ANDMODULATE THE HEATING VALVE ACCORDINLY TO MAINTAIN SPACE TEMPERATURE.

UNOCCUPIED ROOM OPERATION

1. THE UNOCCUPIED MODE OF OPERATION IS DETERMINED BY OCCUPANCY SENSOR. DURING THIS MODE OF UNOCCUPIED OPERATION THE SPACE TEMPERATURE COOLING AND HEATINGSETPOINTS SHALL BE RESET BY AN ADJUSTABLE VALUE THAT CHANGES FOR OCCUPIED PERIODS AND UNOCCUPIED PERIODS. THE DESIGN SHOULD START WITH A ± 1° F DURING OCCUPIEDPERIODS AND ±3° F DURING UNOCCUPIED PERIODS. AS THE SPACE REQUIRES MORE AIR FLOW TO MAINTAIN THE COOLING TEMPERATURE SETPOINT, THE SUPPLY AIR TERMINALS SHALLMODULATE, ENSURING THAT THE DESIGN IS MAINTAINED. AT ALL TIMES THE COOLING MAXIMUM CFM VALUE SHALL BE POSSIBLE, SHOULD SPACE SENSIBLE COOLING LOAD REQUIRE THISVALUE. UPON A RETURN TO OCCUPANCY SENSED BY THE OCCUPANCY SENSOR, A TEMPERATURE CONTROL ALGORITHM SHALL CONTROL THE TERMINALS AND REHEAT TO MINIMIZECHANGES IN SPACE TEMPERATURE TO LESS THAN ±1° F.

UNOCCUPIED BUILDING OPERATION

1. THE UNOCCUPIED MODE OF OPERATION IS DETERMINED BY THE BUILDING SCHEDULE. SPACE TEMPERATURE SHALL BE MONITORED BY THE BAS. THE SPACES SHALL INCREASE TO AMAXIMUM OF 80° F SUMMER OR DECREASE A MINIMUM OF 55° F WINTER.

2. WHEN THREE(3) OR MORE ZONES REACH MAXIMUM OR MINIMUM SPACE SET POINT, PROVIDE SIGNAL TO BAS SYSTEM TO RESTART ROOFTOP UNIT (RTU) AND RESET VAV CONTROL TOMAXIMUM COOLING OR MAXIMUM REHEAT TO RECOVERY SPACE TEMPERATURE BACK TO 70° F AND THEN SHUT DOWN RTU.

AI AI

OS

AI

AI

SENSOROCCUPANCY

OCCUPANCY SENSOR

OS

AI

SENSOROCCUPANCY

AI

AI

(TYPICAL LARGE MEETING ROOMS OR DINING AREAS)

Scale: NTS

VAV W/REHEAT CONTROL

1

Scale: NTS

VAV W/REHEAT AND UNOCCUPIED ROOMS

2

Scale: NTS

VAV W/REHEAT CONTROL AT HIGH OCCUPANCY SPACES

3

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR

MISCELLANEOUSMECHANICAL

CONTROLDIAGRAMS

M-513

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

DIGITAL DIGITAL TYPE

HOT WATER TEMPERATURE TRANSMITTER

APPLICATIONSOFTWARE

WAT

ER

CABINET UNIT HEATER DDC INPUT / OUTPUT SUMMARY

- TEMP

ERAT

URE

- - POSI

TION

ING

- - CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

HEAT

ING

/ COO

LING

MODE

-

SPACE TEMPERATURE TRANSMITTER

CONTROLLER

POWERS

LAN TRUNK

CABINET UNIT

SENSORTEMPERATURE

AI

ZONE

ROOM

OCC

UPIE

D / U

NOCC

UPIE

D

CABINET UNIT HEATER CONTROL SEQUENCE1. UPON A CALL FOR HEATING BY THE THERMOSTAT, THE CABINET HEATER SUPPLY FAN SHALL CYCLE ON AND MODULATE THE NORMALLY

CLOSED HOT WATER CONTROL VALVE TO MAINTAIN ROOM TEMPERATURE SETPOINT. WHEN THE TEMPERATURE IS SATISFIED, THE FANSHALL CYCLE OFF.

2. SPACE TEMPERATURE SETPOINT DURING OCCUPIED PERIODS SHALL BE 72°F (ADJUSTABLE) HEATING (OCCUPANT ADJUSTABLE +/- 2°F).

3. TEMPERATURE AT THERMOSTAT SHALL ALARM TO THE BAS SYSTEM IF BELOW 60°F. ALARM SETPOINT AT EACH THERMOSTAT SHALL BEADJUSTABLE

4. OCCUPIED / UNOCCUPIED SCHEDULE SHALL BE PROGRAMMABLE FOR EACH DAY OF THE WEEK INDIVIDUALLY.

5. UNOCCUPIED SETBACK TEMPERATURE SETPOINT SHALL BE 50°F (ADJUSTABLE) THROUGH THE BAS SYSTEM FOR SPACE TYPE, DAY OFWEEK AND SEASON.

6. THE BAS SHALL START AND STOP THE FAN WHENEVER HEATING IS REQUIRED.

7. CABINET UNITS SHALL BE SUPPLIED WITH 3-SPEED FAN SWITCH (LOW, MEDIUM AND HIGH) TO BE UNIT MOUNTED.

OUTPUTS ALARMS

-STAR

T FA

N

DO

CABINET UNIT

HWS

HWR

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

DIGITAL DIGITAL TYPE

APPLICATIONSOFTWARE

WAT

ER

UNIT HEATER DDC INPUT / OUTPUT SUMMARY

- TEMP

ERAT

URE

- - POSI

TION

ING

- - CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

HEAT

ING

/ COO

LING

MODE

-

SPACE TEMPERATURE TRANSMITTER

CONTROLLER

POWERS

LAN TRUNK

UNIT HEATER

SENSORTEMPERATURE

AI

ZONE

ROOM

OCC

UPIE

D / U

NOCC

UPIE

D

UNIT HEATER CONTROL SEQUENCE1. UPON A CALL FOR HEATING BY THE THERMOSTAT, THE CABINET HEATER SUPPLY FAN SHALL CYCLE ON AND MODULATE THE NORMALLY

CLOSED HOT WATER CONTROL VALVE TO MAINTAIN ROOM TEMPERATURE SETPOINT. WHEN THE TEMPERATURE IS SATISFIED, THE FANSHALL CYCLE OFF.

2. SPACE TEMPERATURE SETPOINT DURING OCCUPIED PERIODS SHALL BE 72°F (ADJUSTABLE) HEATING (OCCUPANT ADJUSTABLE +/- 2°F).

3. TEMPERATURE AT THERMOSTAT SHALL ALARM TO THE BAS SYSTEM IF BELOW 60°F. ALARM SETPOINT AT EACH THERMOSTAT SHALL BEADJUSTABLE

4. OCCUPIED / UNOCCUPIED SCHEDULE SHALL BE PROGRAMMABLE FOR EACH DAY OF THE WEEK INDIVIDUALLY.

5. UNOCCUPIED SETBACK TEMPERATURE SETPOINT SHALL BE 50°F (ADJUSTABLE) THROUGH THE BAS SYSTEM FOR SPACE TYPE, DAY OFWEEK AND SEASON.

6. THE BAS SHALL START AND STOP THE FAN WHENEVER HEATING IS REQUIRED.

7. BAS CONTROL PANEL SHALL MONITOR HOT WATER SUPPLY TEMPERATURE.

OUTPUTS ALARMS

-STAR

T FA

N

DO

UNIT HEATER

HWS

HWR

TAI

TAI

HOT WATER TEMPERATURE TRANSMITTER

DX AIR CONDITIONING UNIT(WALL OR CEILING MOUNTED)

LOCAL COOLINGONLY THERMOSTAT

DX AIR CONDITIONING UNIT CONTROL SEQUENCE1. UPON A CALL FOR COOLING BY THE THERMOSTAT, THE AC UNIT FACTORY CONTOLS SHALL MODULATE TO MAINTAIN ROOM TEMPERATURE

SETPOINT.

2. SPACE TEMPERATURE SETPOINT SHALL BE 70°F (ADJUSTABLE) FOR OCCUPIED & UNOCCUPIED PERIODS.

3. THE SPACE TEMPERATURE TRANSMITTER SHALL ALARM THE DDC SYSTEM IF RISES ABOVE 78°F (ADJUSTABLE). ALARM SETPOINT AT EACHTEMPERATURE SENSOR SHALL BE ADJUSTABLE BY THE BAS.

4. MONITORING DDC TEMPERATURE SENSOR SHALL BE WALL MOUNTED BESIDE THE LOCAL SPACE TEMPERATURE CONTROLLER. DDC SHALLALARM UPON MONITORING TEMPERATURE SENSOR READING ABOVE 80 DEG. F (ADJUSTABLE).

ROOM

OCC

UPIE

D / U

NOCC

UPIE

D

ZONE

RL

RS

-HEAT

ING

/ COO

LING

MODE

MAIN

TENA

NCE

ALAR

M

ABNO

RMAL

ALA

RM

CRIT

ICAL

ALA

RM

-LOW

LIMI

T

HIGH

LIMI

T

-POSI

TION

ING

--TEMP

ERAT

URE

-

DX SPLIT SYSTEM DDC INPUT / OUTPUT SUMMARY

OUT -PUTS

APPLICATIONSOFTWARE

AIR CONDITIONING UNIT

TYPE

ALARMS

DIGITALANALOG

INPUTS

ANALOGDIGITAL

CONNECTED POINTS

POINT DESCRIPTION

NOTES:

1) REFER TO THE PLAN DRAWINGS FOR THE NUMBER OF AIR TERMINALS IN EACH ZONE.

2) PROVIDE TEMPERATURE SENSORS FOR EACH TERMINAL AS SHOWN ON PLANS.

LAN CONTROLLER

STAT

US -

ON/O

FF

AI

SPACE SENSOR

MONITORINGTEMPERATURE

SENSORAIT

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

DIGITAL DIGITAL TYPE

APPLICATIONSOFTWARE

WAT

ER

GAS FIRED UNIT HEATER DDC INPUT / OUTPUT SUMMARY

- TEMP

ERAT

URE

- - POSI

TION

ING

- - CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

HEAT

ING

/ COO

LING

MODE

-

SPACE TEMPERATURE TRANSMITTER

CONTROLLER

POWERS

LAN TRUNK

GAS FIREDUNIT

HEATER

SENSORTEMPERATURE

AI

ZONE

ROOM

OCC

UPIE

D / U

NOCC

UPIE

D

GAS FIRED UNIT HEATER CONTROL SEQUENCE1. UPON A CALL FOR HEATING BY THE THERMOSTAT, THE UNIT HEATER SHALL CYCLE ON AND UNIT HEATER INTEGRAL CONTROLLER

ACTIVATES STAGES OF HEAT TO MAINTAIN ROOM TEMPERATURE SETPOINT. WHEN THE TEMPERATURE IS SATISFIED, THE FAN SHALLCYCLE OFF.

2. SPACE TEMPERATURE SETPOINT DURING OCCUPIED PERIODS SHALL BE 65°F (ADJUSTABLE) HEATING (OCCUPANT ADJUSTABLE +/- 2°F).

3. TEMPERATURE AT THERMOSTAT SHALL ALARM TO THE BAS SYSTEM IF BELOW 45°F. ALARM SETPOINT AT EACH THERMOSTAT SHALL BEADJUSTABLE

4. OCCUPIED / UNOCCUPIED SCHEDULE SHALL BE PROGRAMMABLE FOR EACH DAY OF THE WEEK INDIVIDUALLY.

5. UNOCCUPIED SETBACK TEMPERATURE SETPOINT SHALL BE 50°F (ADJUSTABLE) THROUGH THE BAS SYSTEM FOR SPACE TYPE, DAY OFWEEK AND SEASON.

6. THE BAS SHALL START AND STOP THE UNIT HEATER WHENEVER HEATING IS REQUIRED.

OUTPUTS ALARMS

-STAR

T HE

ATER

DO

UNIT HEATER

POINT DESCRIPTION

CONNECTED POINTS

DIGITAL ANALOG

INPUTS

DIGITAL DIGITAL TYPE

APPLICATIONSOFTWARE

WAT

ER

GAS AIR CURTAIN DDC INPUT / OUTPUT SUMMARY

- TEMP

ERAT

URE

- - POSI

TION

ING

- - CRIT

ICAL

ALA

RM

ABNO

RMAL

ALA

RM

MAIN

TENA

NCE

ALAR

M

HEAT

ING

/ COO

LING

MODE

-

SPACE TEMPERATURE TRANSMITTER

CONTROLLER

POWERS

LAN TRUNK

AIR CURTAIN

SENSORTEMPERATURE

AI

ZONE

ROOM

OCC

UPIE

D / U

NOCC

UPIE

D

GAS AIR CURTAIN CONTROL SEQUENCE1. PROVIDE ALL INTERCONNECTING CONTROL WIRING FROM ALL REMOTE MOUNTED CONTROL DEVICES SUPPLIED WITH THE AIR CURTAIN.

2. UPON A CALL FOR HEATING BY THE THERMOSTAT, THE AIR CURTAIN SHALL CYCLE ON AND AIR CURTAIN INTEGRAL CONTROLLERACTIVATES STAGES OF HEAT TO MAINTAIN ROOM TEMPERATURE SETPOINT. WHEN THE TEMPERATURE IS SATISFIED, THE FAN SHALLCYCLE OFF.

3. SPACE TEMPERATURE SETPOINT DURING OCCUPIED PERIODS SHALL BE 65°F (ADJUSTABLE) HEATING (OCCUPANT ADJUSTABLE +/- 2°F).

4. TEMPERATURE AT THERMOSTAT SHALL ALARM TO THE BAS SYSTEM IF BELOW 50°F. ALARM SETPOINT AT THERMOSTAT SHALL BEADJUSTABLE.

5. UNOCCUPIED SETBACK TEMPERATURE SETPOINT SHALL BE 50°F (ADJUSTABLE) THROUGH THE BAS SYSTEM FOR SPACE TYPE, DAY OFWEEK AND SEASON.

6. THE BAS SHALL START AND STOP THE FAN WHENEVER HEATING IS REQUIRED.

7. UNIT SHALL BE SUPPLIED WITH 3-SPEED FAN SWITCH (LOW, MEDIUM AND HIGH) TO BE UNIT MOUNTED.

OUTPUTS ALARMS

-STAR

T FA

N

DO

AIR CURTAIN

MOTOR CONTROLPANEL

S

DO

DOOR SWITCH

SB

PUSH BUTTONSTART SWITCH

Scale: NTS

CABINET UNIT HEATER CONTROL

1

Scale: NTS

UNIT HEATER CONTROL

2

Scale: NTS

DX SPLIT SYSTEM CONTROL

3

Scale: NTS

GAS FIRED UNIT HEATER CONTROL

5

Scale: NTS

GAS AIR CURTAIN CONTROL

4

NCNC

HOT WATER CONTROL VALVE HOT WATER CONTROL VALVE

CONSULTANTS

PROJECT IDENTIFICATION

ISSUE BLOCK

PROJECT NO.:DESIGNED BY:DRAWN BY:CHECKED BY:APPROVED BY:COPYRIGHT:

SHEET TITLE

SEALS

A

B

C

3019039

MARK DATE DESCRIPTION BY

D

E

32 4 5 61

PRPA VMF

KITTY HAWK AVE.PHILADELPHIA, PA

32 4 5 61

STV

205 West Welsh DriveDouglassville, PA 19518

t 610.385.8200 f 610.385.8500www.stvinc.com

0 02/23/18 FINAL BRIDGING DOCS KDB

G. KAUR

J. HELHOWSKIK. BOMBOY

G. KAUR