Luigi Serio
CRYOGENICS PERFORMANCE AND OPERATION
L. Serio, on behalf of the
LHC Cryogenics Operation andCryogenics Performance Panel
2Luigi Serio
Contents
• Introduction on cooling down and commissioning time
• Tuning loops adjustment & CV910 puppets – acquired knowledge and expected improvement
• Measured recovery time after quenches vs. theoretical expectations. DFBs filling
• Availability study for cryogenic system - can system components or related services be improved to maximize overall availability
• Improvement of He quality with new compressor. Translation to other sectors
• Vacuum minor leaks' impact on 1.9 K stability - improved strategy for GLPT in 45/81
• Time to repair a fault occurring just before the week-end: is it adequate for running LHC?
• Is recovery time after problems resource dependant? If so, can extra resource be made available when required eg weekends, nights?
• Interlocks: New PIC-Cryo channels
• Is it likely that if multiple sectors are commissioned, a cryo problem in one sector will not affect other sectors – thus allowing effort to be put elsewhere?
Luigi Serio
Global tuning
And
DFBs commissioning
PoweringCool-down
(Big gain expected)(2-3 wks w.r.t 9 wks)
4Luigi Serio
LHC Cryogenics: duration of cool-down phases
DesignLHC 7-8Final
9 d21 d
3 d14 d
1 d14 d
1 d21 d
80 K
20 K
4.5 K
1.9 K
Total
DesignLHC 7-8Final
DesignLHC 7-8Final
DesignLHC 7-8Final
DesignLHC 7-8Final
14 d / 2 wks70 d / 10 wksELQA
14 d
4 d
3 d
7 d
28 d / 4 wks
Excluding ELQA or extra-works :
Sketches intended to illustrate achievements and ultimate expectations
S. Claudet - Jul’07
5Luigi Serio
Data for LHC scheduling purposes
• First time a given cryoplant type is used:4-5 , 8-1 , 3-4 , 7-8: 8 wks + ELQA
• Second time a given cryoplant type is used:5-6 , 6-7: 6 wks + ELQA
• For 2008 onwards:4-5 , 3-4: 4 wks + ELQA
• Warm-up:Complete sector: 4 wks the first time (Design: 2 wks)QRL + some cells: 2 wks
Proposed durations with expected learning effects to be checked autumn 2007
S. Claudet - Jul’07
6Luigi Serio
Tuning loop adjustments
• June 18: Simultaneous, sawtooth ramping of D2 and Q4
7Luigi Serio
Tuning loop adjustments
1.85
1.86
1.87
1.88
1.89
1.9
7/07/20070:00
7/07/20076:00
7/07/200712:00
7/07/200718:00
8/07/20070:00
8/07/20076:00
8/07/200712:00
8/07/200718:00
9/07/20070:00
LQTCG_11L8_TT821LBBRP_11L8_TT821LBARA_11L8_TT821LQNCE_10L8_TT821LBBRG_10L8_TT821LBARE_10L8_TT821Regulation Temperature
[K]
inlet magnets cell
outlet magnets cell
8Luigi Serio
Valves: Flow caracteristics
Installed R ~ 25
New R ~ 100Large sensitivity gain
9Luigi Serio
Availability: From 7-8 to others
DFBMs
Cryo Maintain LSS: 85% (Since 1st May)
DFBAs
Cryo Maintain ARC: 66% (Since 1st June)
Target LSS: 90%(incl. time lost for quench recovery)
Target ARC: 80%(incl. time lost for quench recovery)
Luigi Serio
Luigi Serio
Quench recovery for one quadrupole
Quench 720 A => TTregulation + 20 mK
Quench 2000 A => TTregulation + 200 mK & 5 minutes for Cryostart (2 K)
Quench 6500 A => TTregulation + 1.3 K & ~ 40 minutes for Cryostart (< 2 K)
New : Quench 2 x 6500 A => TTregul + 4 K & 2h30 for Cryostart (< 2 K)
=> No effect on cold compressorsNB : Cryostart recovery time not yet optimised (presence output limit high on JT valve to limit overshoot)
1.8
2.3
2.8
3.3
3.8
4.3
4.8
5.3
5.8
6/27/200712:00
6/27/200712:28
6/27/200712:57
6/27/200713:26
6/27/200713:55
6/27/200714:24
6/27/200714:52
6/27/200715:21
12Luigi Serio
Recovery Time after Limited Resistive Transitions
• More than 14 cells or full sector recovery up to 48 hours• In case of fast discharge (even w/o quench) 2 h recovery (heating due to eddy currents).
13Luigi Serio
Interlocks: New PIC-Cryo channels
• For operation reasons a cryo-start signal for 60 Amps will be implemented taking into account beam screen temperature (heat intercept) and eventually the thermal screen temperature
• Details to be discussed with system owner and PIC team
• To be implemented already for sector 4-5
14Luigi Serio
Helium quality for distribution
• Improvement of He quality with for other refrigerators (sectors)
Problem only for ex-LEP cryoplants from Air Liquide for which the sub-cooler was just made for isothermal refrigeration (LEP) and not for non-isothermal refrigeration (LHC)
Problem identified Autumn’06
Proposal received for modification, but no agreed yet
The change of refrigerator did not show big impact on commissioning. Major gain to be expected in pseudo liquefaction mode when re-filling after a stop
15Luigi Serio
Vacuum minor leaks
• No major problems for stability /cooling power with the levels accepted in sector 7-8
• Can have (depending on the level) some impact on recovery time
• More problematic is the leak (no connection) of the Y tube in the bayonet heat exchanger– Can still function with adjacent cell but increase in recovery of cryo start
conditions (cooldown)
16Luigi Serio
Time to repair a fault outside working hours
• Time to repair a fault occurring just before the week-end: is it adequate for running LHC?
=> We are not running the LHC we are commissioning it and cryogenics is part of the commissioning …
• Is recovery time after problems resource dependant? If so, can extra resource be made available when required eg weekends, nights?
Efforts put on control logic (long term) rather than on manpower (short term) Furthermore resources need to be trained or be expert in the domain for most of
the problems encountered Efforts and intervention are anyway already performed during the weekends and
nights even if you do not realize it
• Is it likely that if multiple sectors are commissioned, a cryo problem in one sector will not affect other sectors – thus allowing effort to be put elsewhere?
=> YES, machines and teams independent