I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc
LPGas
Decanting Instruction and
Training Manual
ATTENTION TO THE CUSTOMER
Please ask your Elgas Customer Representative for advice on your State Licencing and data retention requirements. For Victoria, please also refer to the Industry Code of Practice.
PLEASE NOTE: The latest Material Safety Data Sheet for LPGas is available from Elgas upon request or from the Elgas website www.Elgas.com.au Revision: 0 12 13 14 Date: Apr 89 Jun 06 May 07 Apr 08
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc
Index
Sections 1. Introduction … … … … … … … … … … 3 2. Important safety information … … … … … … … … 4 3. Historical and general information … … … … … … … 6 4. Decanting system … … … … … … … … … 7 5. Decanting procedure … … … … … … … … … 13 6. Maintenance and housekeeping … … … … … … … 18 7. First aid … … … … … … … … … … 20 Super Cold Contact Injury Data Sheet … … … … … … 22 8. Procedures for handling an incident … … … … … … … 23 9. Training and Certification … … … … … … … … 26 Appendix I Elgas Material Safety Data Sheet for LPGas … … … … 28 Appendix II Site Inspection Record … … … … … … … 29 Appendix III Theory Test … … … … … … … … 31 Appendix IV Certificates … … … … … … … … 35 Appendix V Forklift Cylinders … … … … … … … … 39 Appendix VI ALPGA Safety Alert … … … … … … … 40 Appendix VII Decanting Cylinder Location … … … … … … 42 Appendix VIII Details of Decanting Equipment … … … … … … 44 Appendix IX Additional Queensland Requirement … … … … … 46
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 3
SECTION 1 1. INTRODUCTION
Elgas Policy
This manual has been prepared as a reference document and training aid to provide basic instruction
on:
• The potential hazards involved in decanting LPGas;
• Preventative safety measures; and
• Emergency procedures.
Elgas operations are normally undertaken by agreement with the site management, as part of a
complete operation, and it is essential that this safety manual is read in conjunction with the
customer's other safety procedures specific to that site.
The employer is responsible for safety training and the formal recording of that training. Failure to
provide adequate training of staff in the safety procedures associated with the conduct of their work
is a contravention of Federal, State and/or local Authority Regulations. Management shall supervise
personnel undertaking filling as appropriate, ie via the training of a “nominated site trainer”.
This manual is not intended for training personnel in the refilling of Forklift cylinders. For this
particular training, please ensure that the Elgas manual "LPGas Fuelled Forklift Vehicle Filling" is
utilised.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 4
SECTION 2
2. IMPORTANT SAFETY INFORMATION
• Elgas Emergency Phone Number: (24 hours) 1800 819 783
• Decanting is covered in detail in AS/NZS 1596 and it is strongly recommended that the
employer has available a copy of this Standard for reference by the employees.
• Decanting must never take place indoors, in depressions or areas with inadequate ventilation.
• Never fill a cylinder that has not been re-tested and stamped by an approved cylinder test station
within the last ten (10) years.
• A cylinder may be within its 10 year test period, but might exhibit severe rust or corrosion or be
dented. The person filling the cylinder has the right to refuse to fill if he / she is at all concerned
about any aspect of the cylinder’s condition.
• Never fill the decanting cylinder from an auto-gas dispenser.
• Never override the Deadmans Handle Safety Function.
• Be aware of the ALPGA Safety Alert detailed in Appendix VI.
• Be aware of QLD Safety Alert No 31 re Portable Gas Refrigerants
• Be aware of QLD Safety Alert No 33 re the need to fit a screw plug when supplying a cylinder
to a customer
• Always turn off the main cylinder control valve after a fill.
• The cylinder to be filled must be effectively earthed to discharge static electricity. Earthing can
be achieved by placing the cylinder on a steel stand or placing it on the ground. Do not use
plastic milk crates or the rear tray of a ute.
• The operator must always touch the steel body of the main decanting cylinder with a bare hand
at the start of the decanting procedure and before shutting the bleed (ullage valve). This will
allow any static electricity present on the operators body to discharge via the decanting cylinder
to earth preventing the possibility of sparks occurring.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 5
• LPGas cylinders must never be 100% filled. The maximum filling percentage as specified in
AS/NZS 1596 is 80% and is indicated by the correct operation of the bleeder valve.
• There are available rigid decanting connections, ie a metal tube fixed directly to the decant
cylinder outlet valve that enables you to fill small companion type cylinders directly from the
large decant cylinder. The rigid arms have caused problems in the past and Elgas does not
condone their use.
Emergency Phone Numbers
Police
Fire Brigade
Elgas Emergency Response – 24 hour 1800 819 783
Equipment Failure (Non-Emergency) 131 161
Ambulance
Doctor
Licensed Gasfitter
Electrician
Prime Contractor
Fire Fighting Equipment Maintenance
State Statutory Authority
Please ask your Elgas representative to confirm these numbers on a six monthly basis.
Date of last check …………………………………
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 6
SECTION 3
3. LPGas HISTORICAL AND GENERAL INFORMATION
Liquefied Petroleum Gas (LPGas) has been available to the public for many years as a convenient
and environmentally friendly fuel. It has many applications as an energy source for the leisure
industry, camping and caravanning, commercial and industrial use and as an automotive fuel.
The Australian Dangerous Goods Code states that LPGas is composed predominantly of the
following hydrocarbons or a mixture of all or any of them; - propane, propylene, butane or butylene.
Elgas predominantly supplies Propane for decanting and domestic use, and its characteristics are as
follows:-
Propane is produced from the refining of crude oil and also from natural gas separation plants. The
boiling point of Propane is -42oC which is very cold and will cause Super Cold Contact Injuries
(cold burns) if the skin comes in contact with liquid propane. Propane gas is readily compressible to
produce a liquid and at a temperature of 15oC (59oF) has a pressure of approximately 626kPa.
LPGas tanks and cylinders must never be completely filled (80% is the maximum for barbecue
cylinders) so as to allow for thermal expansion of the liquid. One litre of liquid will expand to
approximately 270 litres of vapour and therefore a liquid leak from decanting will expand 270 times
to form a substantial cloud of LPGas vapour.
The LPGas is odourised to allow detection of gas leaks by smell. Propane is not toxic itself but if
the vapour is confined and there is no ventilation, asphyxiation may occur due to lack of oxygen.
Propane has a Specific Gravity of approximately 0.51 as a liquid and 1.53 as a vapour, which means
that as a vapour it is heavier than air and the vapour will collect in hollows, drains or enclosed areas.
As the expansion of gas from liquid is 270:1, LPGas has a tremendous advantage in that a large
quantity of gas may be transported in a small space.
Note: Queensland has issued specific instructions about the transport of LP Gas cylinders in
enclosed vehicles and this has now been incorporated within the latest version of the applicable
Queensland Regulations.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 7
SECTION 4
4. DECANTING SYSTEM
LPGas Liquid Withdrawal Cylinders used for decanting purposes (see Appendix VIII) must be sited
according to the requirements of Australian Standard AS/NZS 1596-(latest edition). A liquid
withdrawal cylinder is different to a typical cylinder alongside a house, in that the main valve
discharges LPGas as a liquid, NOT as a vapour. Decanting should not take place unless the
installation is in accordance with the applicable Regulations and Standards. It is important not to
move the cylinder(s) from the original location as sited by Elgas or other approved personnel.
LPGas is classified as a “Dangerous Good” and where a site is required to be licensed to store
Dangerous Goods, then the Site Owner/Licensee must ensure that he/she completes the correct
application form and submits this to the appropriate State Competent Authority.
4.1 Cylinder Size Criteria
• Any cylinder intended to be filled by a decanting method that is monitored by means of a fixed
liquid level gauge shall not exceed 25 L capacity, or 50 L capacity if used as a fuel container for
a vehicle engine.
• Cylinders larger than 25 L capacity shall not be filled by decanting, except that for cylinders
used as fuel containers for vehicle engines this limit may be increased to 50 L. Larger vehicle
engine fuel containers fitted with an automatic fill limiter (AFL) may be filled by decanting to
permit testing and commissioning of the installation in accordance with AS 1425/NZS 5422.1.
• All cylinders of 5 L capacity and less shall only be filled by decanting.
.2 Location and Installation (see also Appendix VII)
• A decanting cylinder shall NOT BE USED OR STORED INDOORS and shall NOT be
moved from its original installation point, unless with the specific approval of Elgas Ltd.
• The reason for this approval is that the location of the decant cylinder is governed by the
distances detailed in AS/NZS 1596 and moving the cylinders may contravene the standard.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 8
• AS/NZS 1596 refers to "the point of connection" when discussing separation distances. For
further clarification of this, please consult AS/NZS 1596.
• Nearby constructions, fences, walls and vapour barriers shall permit free access to and cross-
ventilation for the cylinders.
• Decant cylinders shall be installed on a firm, level, non-combustible base, and not resting on
soil.
• A cylinder that is liable to accidental dislodgement shall be secured.
Note: Accidental dislodgement is deemed to include a cylinder located in an area which is
likely to be subject to flooding or seismic activity.
• Any cylinder which is liable to damage from manoeuvring vehicles shall be protected by fenders
or their equivalent.
• Cylinders shall not be installed below ground level unless the ventilation provisions are
adequate to prevent the accumulation of any gas which may leak.
• A cylinder shall be installed so that the pressure-relief valve is in contact with the vapour space
and, where practicable, any discharge from this valve shall be away from adjacent structures and
be directed away from adjacent cylinders or combustible structures.
NOTES:
1. Separation distances may be measured horizontally around a vapour barrier or firewall provided
that:
(a) the top of the vapour barrier or firewall is not less than 0.5 m above the level of the filling connection;
(b) a firewall is used when the separation distance involves a protected place.
2. Decanting on a property boundary is permissible provided that there exists a firewall sufficient to
ensure that the separation distances can be realised.
3. Exclusion Zone - See AS/NZS 1596.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 9
4. The AIP and the ALPGA require that decanting cylinders are NOT placed on or near petroleum fuel
(see Appendix VII).
4.3 Security and Protection
When decanting in an area accessible to the public ceases to be under general supervision e.g.
closing for the night, the decanting equipment shall be protected from tampering by one or more of
the following:
(a) The whole of the decanting equipment including the cylinder shall be securely stored.
(b) Decanting pipes and hoses shall be disconnected and removed to a secure indoor storage
and the operating valve of the supply cylinder shall be rendered inaccessible to the public,
i.e. plugged.
(c) Access to decanting hoses, pipes and valves shall be prevented by means of a lockable
cover. (Available only on 190 / 210 kg cylinders).
(d) Storage cylinders shall be located as to minimise potential vehicle impact and wherever
practicable be protected by bollards or other means.
4.4 Signage
The following notices (or a combined notice) shall be displayed prominently as closely as possible
to the decanting point; or on the decanting cylinder itself.
(a) Standard symbols of at least 100mm diameter, or a warning notice in letters not less than 50mm high, reading.
"FLAMMABLE GAS, NO SMOKING"
(b) Customers may well have their own storage guidelines and these shall always be displayed.
(c) Instructions for the decanting procedures, including a warning to stop filling as soon as the
fixed liquid level gauge indicates that the maximum permitted liquid level has been reached.
(d) A warning (and instructions) regarding Static Electricity.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 10
(e) The liquid withdrawal cylinder shall be marked with the words 'LIQUID WITHDRAWAL
ONLY' in letters not less than 30mm high.
(f) Hazchem signage as per State Regulations.
4.5 Equipment
4.5.1 Storage cylinders and/or vessels for decanting LPGas into cylinders shall meet the following
requirements:
• The vessel shall be of steel, and shall comply with AS 3577 or an approved alternative standard.
4.5.2 Filling Connection
The filling hose shall be suitable for liquid LPGas service, and shall be of not more than 10mm
nominal bore and not more than 1.5 long. An excess-flow valve shall be provided before the
upstream end of the hose.
4.5.3 Decanting Valve
A lever operated decanting valve shall be fitted downstream of the filling hose and immediately
before the filling connector. This valve shall be spring loaded and shall always be in the closed
position unless the lever is activated by hand.
Caution: The valve is often referred to as the "dead-man's handle". It closes and stops the
flow immediately when hand pressure is released. This is an important safety feature in the
decanting system. Locking devices to hold the lever open, such as clamps, tape or wire are
strictly forbidden to be used.
4.5.4 Fittings and Accessories
Any fitting or component shall specifically be designed for LPGas service. In particular the
following requirements shall apply:-
(a) The design pressure shall be no less than the cylinder design pressure.
(b) Cast iron shall not be used.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 11
(c) Adaptors shall have compatible thread sizes and forms.
(d) For cylinders decant filled in QLD, the operator shall have available a supply of
screw plugs as required by QLD Safety Alert No 33.
4.5.5 Fire Fighting Equipment
The location at which cylinders are filled shall be provided with at least one fire hosereel or one fire
extinguisher that comply with the following requirements.
(a) The installation of hosereels shall comply with AS/NZS 1596.
(b) Fire extinguishers shall be of the portable dry powder type having a rating or at least 60B.
They should be located at easily accessible locations.
Fire extinguishers shall comply and be maintained in accordance with the relevant Australia
Standards.
4.6 Ignition Sources
4.6.1 Ignition sources including all electrically operated equipment, e.g. ice and food vending machines,
power points, switches, air compressors, etc, must be identified and care taken in ensuring the
correct separation distances.
4.6.2 Potentially combustible products, i.e. oils, firewood and charcoal etc; must not be stored adjacent to
the decanting cylinder.
4.7 LPGas Tanker Access and Unloading
4.7.1 Decanting cylinders shall be located on sites such that inconvenience to the site and the LPGas
tanker is minimised and that the tanker can drive straight out in an emergency.
When the LPGas storage cylinder or vessel is being filled the following should be observed:
(a) The LPGas tanker shall be parked in a position that does not restrict other vehicles from
entering or leaving the site, and provide the tanker with a clear forward exit.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 12
(b) The tanker’s LPGas filling hose shall not be positioned on the driveway where a vehicle
may come in contact with it.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 13
SECTION 5
5. DECANTING PROCEDURE
5.1 Minimum Site Staff Requirements
The decanting operation should only be carried out by a trained operator, who must remain in
attendance during the entire decanting operation. Customers are not allowed to perform the
decanting operation.
If only one staff member is present at a busy site when approached by a customer to fill a cylinder
by decanting, the staff member should return the cylinder to the customer and advise the customer
when two staff will be present or recommend an alternative location. The customer's cylinder
should not be stored at the site if the cylinder cannot be filled immediately unless this practice is
approved by the site management.
5.2 Decanting Process
5.2.1 Inspection of Customer’s Cylinder
The cylinder shall not be filled if any of the following conditions are observed:
(a) The test date stamp on the cylinder is more than ten (10) years old. If unsure where the
test date is located request your local representative to show you where the month / year
test date is located on the cylinder.
A CYLINDER WHICH DOES NOT HAVE A CURRENT INSPECTION DATE
STAMP MUST NOT BE FILLED UNDER ANY CIRCUMSTANCES
If the cylinder is not in date the customer should be referred to the local Elgas Branch.
(b) The cylinder has a test pressure less than 3.3MPa. Note: this figure is stamped on the
cylinder: if unclear or painted over, do not fill.
(c) Apparent damage, dents or corrosion on the cylinder.
(d) There is no bleed valve, or the bleed valve cannot be operated.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 14
(e) Valves are not in good condition ie very corroded, broken handles etc.
(f) There is a leakage from the cylinder fittings. Normally detected by a hissing sound, a
strong smell or bubbling from a soapy water test. Note: the water must be “soapy”, plain
water is unacceptable for test purposes.
5.2.2 Safety Check
Before the actual decanting can take place the operator should ensure that:
(a) Adequate anti-static clothing with a very high cotton content and thermally insulated gloves
are worn.
(b) No naked flames or source of ignition are within five metres from the decanting cylinder.
Note: This is explained in pictorial form in AS/NZS 1596
(c) Decanting is performed outdoors in a well ventilated area.
(d) The hose and fittings on both storage cylinder(s) and customer cylinder(s) are not leaking
and generally in good working order (leakage can be detected with soapy water) - never a
naked flame.
* A typical soapy water tester could be a small lever operated plastic spray bottle. Simply
add a small amount of detergent, fill with water and squirt around the valve and fittings. If
there is a leak, then small bubbles will appear.
(e) Customer cylinder is positioned upright.
(f) Non-metallic bases such as milk crates and other plastic or wooden containers are not to be
used.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 15
5.2.3 Filling Procedure
The staff member who performs the filling operation will:
(a) Wear the correct PPE, i.e. eye protection, safety boots and at stage (e) of the filling
procedure, put on gloves.
(b) Inspect the customer's cylinder for test date, corrosion and dents etc, paying particular
attention to the underside of the cylinder. If significant corrosion is present do not fill the
cylinder and refer the customer to a registered cylinder test station.
(c) Unlock the decant vessel cover/valve. Ensure that the dead-man's valve on the filling
assembly is closed and the assembly is tightly connected to the storage vessel.
(d) Touch the main decanting cylinder with bare hands to discharge static electricity.
(e) Put on correct gloves, connect filling (hose) to customer cylinder.
(f) Open the valve on the customer's cylinder by turning the valve handle in an anti-clockwise
direction.
(g) Check that the bleed valve on the customer's cylinder is directed away from the operator and
towards a well-ventilated area before opening the bleed valve one half turn using the correct
tool. This will reduce the pressure in the customer's cylinder to be filled. The bleed valve is
normally located under the cylinder’s on-off valve and is operated by inserting a suitable tool
and turning in an anti-clockwise direction.
(h) Open the main valve on the decant vessel by turning in an anti-clockwise direction.
(i) Release the safety catch and activate dead-man's valve on the filling assembly, to start the
filling process. Appendix VIII item 4 shows the handle.
(j) Stay in attendance during the entire process of filling. Do not use any device (e.g. clamps,
rubber bands) to hold the dead-man's valve open. Check all connections during filling
for possible leaks.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 16
(k) Allow the filling to continue until a steady white cloud/mist emerges from the customer
cylinder bleed valve, which indicates that the cylinder is full (the maximum fill level has
been reached). Note: If surging is occurring within the cylinder being filled, there may
be sporadic bursts of the cloud/mist emerging prior to the cylinder being filled to its
maximum level. Note: Surging occurs when mini waves/depressions are formed inside
the cylinder whilst filling and filling should be stopped for a few seconds to allow the
true level to be established.
(l) Immediately release the dead-man's valve to stop filling.
Caution: It is extremely important that cylinders are not left or returned to the
customer overfilled. This decreases the space into which the liquid may expand should the
temperature increase, and could cause the cylinder to vent. This is why it is so important to
stop filling the second a white liquid cloud emerges from the bleed valve.
(m) Remove a glove and touch the main decant vessel with bare hands (to discharge any static
electricity that may have built up during the decant operation from the body of the person
decanting). Replace the glove and continue.
(n) Close the main valve on the customer's cylinder.
(o) Wait until the white cloud / mist stops emerging before closing the bleed valve.
(p) Close the main valve on the decant vessel, close the bleed valve.
(q) Carefully disconnect the filling assembly hose from the customer's cylinder. When breaking
the connection, a small amount of vapour trapped between the two valves will escape.
(r) Confirm the customer's cylinder is leak free by applying soapy water with a spray bottle to
the following:
a. Outlet of the main valve.
b. Thread where the main valve is attached to the customer's cylinder.
c. Bleed valve opening.
(s) For cylinders decant filled in QLD, ensure that Safety Alert No 33 is complied with.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 17
(t) If a cylinder is leaking and the leak cannot be stopped, recommend that the customer does
not remove the cylinder. (Note: they have a legal right to demand the return of the cylinder.
If they don’t take the cylinder, remove to a remote part of the site and call Elgas.
(u) Secure or remove the decant hose when the site is unattended and ensure that the cover of the
supply cylinder is locked at all times when not in use.
(v) If LPGas in liquid form comes in contact with bare skin or eyes, immediately wash the
affected areas with cold or warm water (never hot) for at least ten (10) minutes and then
proceed to your nearest Medical Centre: WARNING! Water hoses or taps on a site and
when exposed to the sun can contain extremely hot water. Always let the water run and cool
down before application.
5.2.4 Forklift Cylinders
This manual does NOT include instructions on refilling forklift cylinders. Refer to the Elgas
LPGas Fuelled Forklift Vehicle Filling Safety Manual.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 18
SECTION 6
6. MAINTENANCE AND HOUSEKEEPING
Good preventative maintenance and housekeeping go hand in hand with safety and helps to avoid
breakdowns and incidents including vandalism with malicious intent.
Maintenance is often seen as breakdown repairs to be taken care of by qualified persons only, but in
its broader sense, it is an on-going activity and an integral part of the daily operation.
It requires devoted efforts in maintaining standards, planning the activities and keeping proper
records, as outlined below.
6.1 Inspecting Schedule
6.1.1 Decanting Equipment
Decanting equipment and the site should be inspected daily by a delegated person to ensure that the
system is in safe and working condition. Refer to Appendix II for those items that need to be
inspected.
A record of the daily inspections should be made and kept for at least 12 months. Appendix II
shows a form of inspection record to be used.
6.1.2 Fire Fighting Equipment
Hose reels and fire extinguishers shall be properly maintained by the operator at six monthly
intervals according to manufacturers recommendations and statutory requirements.
On a typical service station for example, there would normally be two portable powder fire
extinguishers with a rating of at least 2A 60B (E) with at least one close to the decant point, and a
fire water hose reel.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 19
6.2 Site Upkeep
The area around the decant area should be maintained in a safe condition in particular:-
(a) The area shall be kept clean of all extraneous material and rubbish.
(b) Vegetation and overhanging trees which might become a fire hazard shall be kept under
control. Other extraneous combustible materials shall be kept clear within 1m of LPGas
storage.
(c) Signs and notices shall be kept in a clearly legible condition.
(d) The surface of all storage cylinders shall be kept clear of dirt and debris and the surface
coating shall be maintained in good condition to prevent corrosion.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 20
SECTION 7
7. FIRST AID
7.1 Super Cold Contact Injuries
Should LPGas in the liquid phase come in contact with the skin, then a Super Cold Contact Injury
could occur, which is very similar to Frostbite.
This type of accident should not occur if protective gloves suitable for liquid LPGas operations are
worn during possible contact periods.
The following two sheets detail the recommended procedures to be followed for the treatment of
injuries, should a Super Cold Contact Injury occur.
7.2 Burns
Should the LPGas ignite and burn an operator and/or customer then the staff shall follow their
standard site procedures.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 21
Instruction to Drivers and Customers First-Aid Procedures for Dealing with Super Cold Contact Injuries
Contact temperatures are usually below -30oC and tissue contact at this temperature results in snap freezing of the affected area causing damage similar to heat burn. Also, unprotected parts of the skin which come in contact with equipment at below zero temperatures may stick fast and the flesh may be torn on removal. As LPGas has a boiling point of -42oC, direct bodily contact with LPGas in its liquid state must be avoided, as the above type of injury could occur. Other examples of liquefied gases are liquid nitrogen, oxygen and argon which have boiling points below -183oC. IMMEDIATE TREATMENT 1. Remove any clothing splashed by LPGas and place injured person (or self) in a warm area as
soon as possible. 2. Cold injuries must be rapidly rewarmed to body heat. Do not allow to thaw slowly as thawing
of the frozen tissue can cause intense pain and shock may occur. 3. Explosure Area
Small exposure: Foot, leg, hand Bathe affected part with warm water (NOT HOT) preferably 33-35oC, immersing if possible. Larger areas: Trunk or multiple areas Immerse in bath of warm water preferably 33-35oC. (If tepid water unavailable, tap water will do, but take care as prolonged immersing may cause a cooling hypothermia.) Eyes: Immediately hold eyes open and wash continuously with water for 15 minutes. Seek medial attention.
4. Loosen any article of clothing that is not frozen but may restrict blood circulation or respiration. 5. Gently cover or drape injured area with dry, sterile dressings or sheet. Do not restrict blood
circulation. 6. Give warm non-alcoholic liquids. 7. Seek medical attention for all but the most superficial "frostbite" injuries. DO NOT apply direct heat or cold such as heat lamps, hot water, snow or ice to the affected parts.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 22
Hospital Information Sheet
Recommended Procedure for Treatment of Super Cold Contact Injuries
NOTE: This is NOT a heat burn and the patient has been splashed by LPGas in its liquid state, at a probable temperature of -42oC. Super cold temperatures causing this injury are usually below -30oC and tissue contact at this or lower temperature results in snap freezing of the affected area without intra-cellular fluid crystallisation occurring. Local pain usually gives warning of freezing but sometimes no pain is felt, or is short-lived. Frozen tissues are painless and appear waxy, with a pale yellowish colour. Thawing of the frozen tissue can cause intense pain and shock may also occur. • Do not delay the warming process - such injuries must be RAPIDLY returned to body
heat. • Treat for hypothermia if present. • Immerse the affected area in a bath of 33-35oC. (Do not exceed 35oC.) Maintain at this
temperature. • Use a blanket or mattress if available. • Administer adequate analgesic cover. • If serious, commence warm IV therapy to assist thawing process. • Once rewarmed, treat as for thermal burn. Use non-adherent dressings, e.g. Bactigras wrapping, Vasgauze or other dry non-adherent dressing. Full extent of damage may be delayed up to 48 hours (skin may look normal after thawing). It is recommended that admission for observation be undertaken if there is any difficulty in assessing the extent of tissue damage. For further information, please contact your State Burns Unit: NSW Phone: 02 9767 5000 Concord Hospital
VIC Phone: 03 9267 2000 Alfred Hospital
QLD Phone: 07 3636 8111 Royal Brisbane
SA Phone: 08 8222 4000 Royal Adelaide
WA Phone: 08 9224 2244 Royal Perth
NT Phone: 08 8922 8888 Royal Darwin
TAS Phone: 03 6222 8308 Royal Hobart
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 23
SECTION 8 8. PROCEDURES FOR HANDLING INCIDENTS
Incidents associated with LPGas decanting can be minimised if the recommendations in this
document are followed properly. However, it should be emphasised that the Site Emergency Plan
which is specific to the site shall be adhered to in case of an incident or accident. All incidents shall
be reported as specified in the Emergency Plan and fully investigated. Where the site has a full and
detailed Safety Management and/or Loss Prevention System then this shall be complied with.
Should your site not have an Emergency Plan however, please still ensure that all decanting
incidents are reported to Elgas.
The following items outline the procedures for the most likely incidents:-
8.1 Gas Leaks
8.1.1 Gas Leaks without Fire
The immediate priority is to stop or minimise the leak.
Follow the Site Emergency Plan which should include the following:-
• Approach the leaking cylinder from an UPWIND direction wearing all the correct PPE.
• Close all valves on the leaking cylinder. Always keep cylinders upright.
• Keep bystanders well away. Note: a safe distance is difficult to detail as very dependent upon
wind and site conditions. The site should cover this issue as part of a safety toolbox meeting.
• Ensure that there are no sources of ignition within the affected area such as Hot Water Systems,
cars with running engines, people smoking etc.
• Disperse gas with water spray by directing the spray at the valve and the leak.
If leak is uncontrolled, follow the instructions in the Site Emergency Plan.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 24
8.1.2 Gas Leak with a Fire
The immediate priority is to stop or minimise the leak, and to prevent fire from impinging on other
cylinders or buildings etc.
Follow the Site Emergency Plan which, besides the instruction to contact the emergency services,
should include the following:-
• Approach only from an UPWIND direction wearing the correct PPE.
• Close all valves on the cylinder (if possible).
• If fire continues but the flame does not impinge on any adjacent cylinder, DO NOT extinguish
but control the fire taking these precautions.
• Keep cylinders upright.
• Keep the tops of decant and customer cylinders cool with water spray, i.e. put water ONLY on
the vapour space (the top) of the cylinders.
• Keep bystanders well away.
• Remove other cylinders and flammable materials from the area.
If flame impinges on any cylinder:-
• Attempt to extinguish fire with a dry powder extinguisher.
• If fire is extinguished apply water spray to disperse leaking gas and attempt to close valves.
• If the fire remains uncontrolled then the site emergency plan for evacuation should be followed.
• NOTE: DO NOT re-use cylinders and equipment involved in a fire. These must be checked by
Elgas or a cylinder test station as soon as possible.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 25
8.2 Overfilling
8.2.1 Overfilling a Cylinder
If the decanting procedures are not properly followed it is possible to overfill the cylinder being
filled. In this case the white cloud/mist will continuously emerge from the open bleed valve. When
overfilling occurs, remove the cylinder to a location as far from people and property as possible.
Then the bleed valve must be kept slightly open until the white cloud/mist ceases to emerge. Then
close the bleed valve and apply soapy water to check for possible leaks.
If you cannot find a suitably remote location and are unsure about having the bleed valve open, then
it may be preferable to keep the bleed valve closed and call Elgas for advice.
• Ensure that you are wearing all the required PPE
• Keep all ignition sources (smoking, vehicles etc) away
• Leave the bleed valve open to bleed off excess liquid (appears as white cloud/mist).
• Stay in attendance during the entire process but at a safe distance.
• After the white cloud/mist disappears close the bleed valve.
• Apply soapy water all over the valve to check for leaks.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 26
SECTION 9
TRAINING AND CERTIFICATION
9.1 Disclaimer
It is not intended nor implied that this document has legal authority, or that information therein may
take place of, or otherwise be adopted to the exclusion of statutory requirements.
Elgas cannot accept responsibility for any incident or consequence thereof, whether or not in
violation of any law or regulation, which arises or is alleged to have arisen from the application of
this document or from the handling of LPGas.
However, it is intended that this document sets forth general safety procedures that reflect good
industry practices. It is imperative that if a person(s) involved in the handling of LPGas is uncertain
as to the safe operating practices after reading this manual, that they seek professional advice before
proceeding.
9.2 Training
9.2.1 This document contains detailed information for the use of the decanting site owner and/or operator
and under State and Federal Occupational Health and Safety Legislation the responsibility for
ongoing training must rest firmly with the site operator.
The site operator, franchisee, dealer or nominated manager must ensure that their site personnel are
trained to a level of proficiency to confidently carry out decanting a safe manner without risks to
their health and safety and to that of customer and/or other parties on site.
Ongoing training due to staff turnover etc will be the responsibility of the site management.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 27
9.2.2 Operators
9.2.2.1 The minimum requirements for operator training should cover the following:-
• Operator's legal responsibilities for maintaining safe working practices
• Cylinder inspection
• Protective clothing and other Personnel Protective Equipment (PPE)
• Decanting equipment
• Maintenance of equipment
• Static electricity
• Practical training in decanting
• Trouble shooting
• Emergency response
• First aid
9.2.2.2 A register should be maintained by the site operators or other nominated management
documentation as follows:
• Name of site person nominated to undertake LPGas decanting training
• Name of trained operator(s)
• Completion date of successful training
9.2.2.3 The register should be available for inspection at the site.
9.2.2.4 Elgas will undertake initial training on the site when requested by the site operator and has included
a theory test for the use of the site (see Appendix III).
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 28
APPENDIX I
LPGas
Material Safety
Data Sheet
PLEASE NOTE: The latest Material Safety Data Sheet for LPGas is available upon request or
from the Elgas website www.Elgas.com.au
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 29
APPENDIX II
Site Inspection Record
for use of
Site Operator
Note: The following page is the Master Copy.
The Decant Outlet should take multiple copies of this page and keep as a separate
record, should the site be inspected and/or audited by a third party, e.g. the relevant
State Authorities.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 30
Site Inspection Record (Note: the list below is a simple checksheet for use by decant sites that do not have their own in-house procedures) DATE:
STATUS ATTENTION REQUIRED Date Reported and
to whom
Date Action
Completed and by
whom
Place ���� if OK Place ���� if attention required
Storage Cylinder or Vessel:- External Condition (rust, corrosion, damage, etc) Signs (in place, legible) Location (has it been moved) Cover and lock for 190/210kg cylinders Impact protection from traffic etc Fire Fighting Equipment and PPE:- Hose Fire Extinguishers Safety glasses and gloves Fittings:- Adaptors Pressure Relief Valve (capped and not leaking) Other valves Hose Dead man's handle (decanting valve) Housekeeping:- Rubbish Vegetation Sources of Ignition Access
If there is any concern over the LPGas Storage Cylinder and/or Fittings contact Elgas at your local branch.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 31
APPENDIX III
Theory Test
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 32
THEORY TEST FOR LPGas DECANTING OPERATORS
1. Q. What to the initials LPGas mean - Liquid Petroleum Gas, Liquefied Petrol Gas or Liquefied
Petroleum Gas
A. Liquefied Petroleum Gas
2. Q. What type of Liquefield Petroleum Gas is used for decanting?
A. Propane
3. Q. Can you fill cylinders direct from the Auto-Gas Dispenser?
A. Never; because of the LPGas blends used for Auto-Gas and possible over filling.
4. Q. What are three hazards of LPGas?
A. (a) It is highly flammable.
(b) It could asphyxiate in an enclosed area.
(c) It can cause super cold contact injuries.
5. Q. Would you fill LPGas Cylinders in a confined area?
A. No. LPGas must only be decanted in a well ventilated area. As the gas is heavier than
air any leakage will collect in low lying areas and present a hazard.
6. Q. What is the time period between cylinder tests?
A. Ten years
7. Q. When would you fill a cylinder that was out of test period?
A. Never
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 33
8. Q. Name six (7) important points to check before filling cylinders?
A. (a) Is the cylinder being filled overdue for retest.
(b) No damage to cylinder.
(c) No sign of rust.
(d) All valves in working order.
(e) Test for leakage.
(f) The cylinder has a “Test Station” stamp.
(g) All the required PPE is on site and being worn.
9. Q. In the event of a liquid spill what is the first thing to do?
A. Turn off the valve at the source of the spill.
10. Q. In the event of an LPGas escape, where is the bulk of escaping gas likely to flow and
collect?
A. Downhill or collect in gullies, trenches and drains, remaining there until ventilated.
11. Q. What checks must be carried out when filling a cylinder?
A. A leak test to be applied to the hose connection to the cylinder, around the valve
thread, valve spindle and gland nut and any other fitting on the cylinder.
12. Q. What solution would you use for leak detection?
A. A solution of soap and water, or a detergent solution.
13. Q. What must be done if a fault is found with a cylinder being filled?
A. Cease filling. Place in an open area, away from sources of ignition, vent gas in small
quantities, and refer immediately to nearest testing station.
14. Q. When do you know that the cylinder has been overfilled?
A. When liquid appears at the bleed valve as a continuous white cloud.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 34
15. Q. What is the first action you would take in an emergency involving a LPGas escape where –
(a) it catches alight; and (b) it does not catch alight?
A. (a) and (b) close a valve upstream of the escape.
16. Q. Why is a liquid LPGas leak more dangerous than a vapour LPGas leak?
A. Any given volume of liquid LPGas will produce 270 volumes of vapour, so that even a
small liquid leak will release a large volume of vapour.
17. Q. What are LPGas Super Cold Contact Injuries?
A. Cold burns are caused by extremely cold propane (in the liquid phase) vapourising on
the skin and causing the injuries as detailed on the Super Cold Contact Injuries Sheet.
18. Q. When decanting cylinders and the filling process is commenced, can the operator attend to
other matters?
A. No. It is required that the operator be in attendance until the completion of the filling
procedure. He or she must NOT leave the filling location.
19. Q. Can the main storage decanting cylinder be filled from the Auto-Gas outlet?
A. No. Again, because the decanting storage cylinder must only contain propane
whereas, Auto-Gas can be a propane-butane blend.
20. Q. Initially and before turning the bleed-screw when the customer's cylinder is full should you
touch the main decanting cylinder with your bare hands and why?
A. Yes. It is very important to remove static electricity from the operator's body, so the
main decanting cylinder must always be touched by the operator with a bare hand,
before turning the bleed screw.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 35
APPENDIX IV
Certificates
Notes:
Where the certificate states “Description of Decnating Equipment on
site”, simply enter the following:
- Cylinder size and cylinder serial number (s) and test date (s)
- Approx length of decanting hose
- Confirm deadman’s handle fitted
- General note on condition of equipment on site, i.e. good, clamp
observed on deadman’s handle, site clean, rubbish around
cylinder, milk crate being used etc.
1) Decanters Certificate to Operate (Operator's Copy)
2) Decanters Certificate to Operate (Elgas Copy)
3) Site Staff: Names of Staff Training and Date(s) of Training
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 36
Decanters Certificate to Operate
Customer Details Customer Name:_______________________________________________________(Customer) Address:___________________________________________________________(the Premises) Ph:_____________________ Account Number:________________ Date of Training:__________
Installation Details LPG Vessel(s)/Cylinder(s) on site: Size________________ No. of Vessels/Cylinders________ Description of Decanting Equipment on site:____________________________________________ I, the Customer, acknowledge having been trained in the safe handling and filling of LPG cylinders by the Decant method. I also understand my obligation to instruct all employees or other personnel, who may fill cylinders at the Premises, in the correct procedures to be followed. The following have been supplied: 1. Decanting Instructions 2. Instructions for Cylinder Filling as per AS/NZS 1596 3. Copy of Cylinder Filling Check List 4. Emergency Procedure Guide I have read and understood the relevant section of the Regulations and undertake to comply with all requirements. Particular attention has been drawn to the location of the decanting cylinder(s) with reference to distances from public areas, buildings on adjoining property, naked flames, flammable material and any other sources of ignition including all electrically operated equipment (e.g. compressors and food vending machines). SIGNED for and on behalf of the Customer ................................................... by a duly authorised officer in the presence of: Authorised Officer Signature . ................................................................. ................................................... Witness Name
...................................................
Position SIGNED for ELGAS LIMITED in the presence of : ................................................... Authorised Officer Signature ............................................................... .......................................……….. Witness Name
.............................…................... Position
ELGAS COPY
Elgas’ Copy
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 37
Decanters Certificate to Operate
Customer Details Customer Name:_______________________________________________________(Customer) Address:___________________________________________________________(the Premises) Ph:_____________________ Account Number:________________ Date of Training:__________
Installation Details LPG Vessel(s)/Cylinder(s) on site: Size________________ No. of Vessels/Cylinders______ _ Description of Decanting Equipment on site:____________________________________________ I, the Customer, acknowledge having been trained in the safe handling and filling of LPG cylinders by the Decant method. I also understand my obligation to instruct all employees or other personnel, who may fill cylinders at the Premises, in the correct procedures to be followed. The following have been supplied: 5. Decanting Instructions 6. Instructions for Cylinder Filling as per AS/NZS 1596 7. Copy of Cylinder Filling Check List 8. Emergency Procedure Guide I have read and understood the relevant section of the Regulations and undertake to comply with all requirements. Particular attention has been drawn to the location of the decanting cylinder(s) with reference to distances from public areas, buildings on adjoining property, naked flames, flammable material and any other sources of ignition including all electrically operated equipment (e.g. compressors and food vending machines). SIGNED for and on behalf of the Customer ................................................... by a duly authorised officer in the presence of: Authorised Officer Signature . ................................................................. ................................................... Witness Name
...................................................
Position SIGNED for ELGAS LIMITED in the presence of : ................................................... Authorised Officer Signature ............................................................... ..........................................…….. Witness Name
................................................... Position
CUSTOMER COPY
Customer’s Copy
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 38
Training Record of Site Personnel
The following personnel have received LPGas Decanting Training in accordance (as a minimum)
with the information and requirements as detailed in the Elgas LPGas Decanting Instruction and
Training Manual.
Name of Trainee (please print)
Name of Trainer (please print)
Date of Training
Signature of Trainee
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 39
APPENDIX V
Forklift Cylinders
Restricted dispensing - the filling of cylinders and automotive fuel containers shall
be subject to the following restrictions:-
(a) Cylinders or fuel containers other than those that are mounted on a vehicle,
and installed to supply fuel to an engine only, shall not be filled from the
automotive fuel-dispensing unit of a service station.
(b) A tank that supplies propane/butane blends for engine fuel shall not be used
to fill cylinders for applications other than for engine fuel.
(c) Subject to Item (b), cylinders may be filled from dispensers other than at a
service station provided that the cylinder fittings and the site equipment and
procedures are appropriate to the prevention of overfilling. Where any such
cylinder is less than 25L capacity, and the filling is by methods other than
decanting, filling shall be controlled by weight.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 40
APPENDIX VI
ALPGA Safety Alert
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 41
The Two Separate Fuels A Safety Alert
At service stations two grades of LIQUEFIED PETROLEUM GAS are stored. These grades are not interchangeable. One is for automotive use only and could be a PROPANE - BUTANE mix. Refueling is by means of driveway dispenser. The other is PROPANE which is used exclusively for decanting into small cylinders for caravans, barbecues and camping. The Australian Standard Code AS/NZS 1596 LP GAS STORAGE AND HANDLING does not allow the filling of non-automotive cylinders from automotive dispensing units. AS/NZS 1596 is endorsed by Regulations in most States and therefore has the full force of law. The observance of this requirement is essential to ensure safety. The Manager of an LP Gas installation is legally responsible for the competence of any supervisory staff or dispenser attendant. It is also the Manager's responsibility to prevent the filling of non-automotive (domestic or leisure) LP Gas cylinders with any automotive LP Gas blend. Appliances in Australia have been manufactured to operate with PROPANE ONLY. A Propane/Butane blend will not burn correctly in some appliances. Products of incomplete combustion such as carbon monoxide may cause serious injuries and can even be fatal. A DANGEROUS SITUATION COULD DEVELOP IF A PROPANE/BU TANE BLEND IS USED FOR NON-AUTOMOTIVE PURPOSES, INCLUDING DOMESTI C AND LEISURE APPLIANCES.
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 42
APPENDIX VII
Decanting Cylinder
Location
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 43
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 44
APPENDIX VIII
Details of Decanting
Equipment
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 45
I:\Alan Coulson\Safety Workbooks - Manuals\Decanting and Training Manual - Apr 08.doc Page 46
APPENDIX IX
Queensland Safety Alert No 31 Queensland Safety Alert No 33
Notes:
1) Full details of the above alerts are available at
<www.dme.qld.gov.au> petroleum and gas safety.
2) Contact your local Elgas branch for details of suppliers of
suitable plugs.