line protection avsramesh 28 sep 2006

Upload: santoshnarinoi241

Post on 07-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    1/66

    Protective RelaysAVS RameshDy.Manager (Operation Services)POWERGRID

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    2/66

    One and Half Breaker Scheme

    Ckt-1 Ckt-2

    Bus-1

    Bus-2

    21

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    3/66

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    4/66

    Distance Protection

    Distance Protection schemes shall have

    Three independent zones

    Separate measurements for all Phase to Phase &Phase to ground faults.

    Single and three pole tripping capability.

    Directional characteristics for Zone-1, Zone-2 and

    Zone-3. Capability of operation for close up three phase and

    switch on to faults.

    Adjustable characteristic angle to match line angle.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    5/66

    Distance ProtectionDistance Protection schemes shall have

    Accuracy of better than or equal to 5% of set value for

    reach measurement in Zone-1 & Better than equal to10% of set value for Zone-2 & Zone-3.

    Accuracy of better than or equal to 5% of set value

    for time measurement of Zone-2 & Zone-3.

    Power Swing detection feature for selective blocking,

    as required.

    Suitable fuse failure protection to monitor all types of

    fuse failure and block the protection.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    6/66

    Distance Protection - Setting criteria

    Reach Setting:

    Zone-1 : To cover 80-85% of protected line section.

    Zone-2 : To cover minimum 150% of length ofprincipal line section.

    Zone-3 : To cover 120% of principal section plusadjacent longest section.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    7/66

    Zone-1Zone-2

    Zone-3

    A B C85%

    150%

    ZAB + 120%

    Distance Protection - Setting criteria

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    8/66

    Time setting:

    Zone-1 : Instantaneous Zone-2 : 0.3 sec,0.5 sec

    (For short line followed by long line)

    Zone-3 : 1.0 sec.

    Distance Protection - Setting criteria

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    9/66

    Power Swing

    LoadArea

    X

    R

    Z1

    Z2

    Z3

    RecoverableSwing

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    10/66

    Phase Comparison Protection

    Current Phase comparison type

    Suitable for operation without PLCC

    High sensitivity for all types of faults

    Capable of single and three pole tripping

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    11/66

    Phase Comparison Relay(Through fault)

    A B

    A

    B

    A+B

    B

    A

    A+BNo Trip No Trip

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    12/66

    Phase Comparison Relay(In-Zone fault)

    A B

    A

    B

    A+B

    B

    A

    A+BTrip Trip

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    13/66

    Phase Comparison Protection shall be

    Un-Affected by :

    Heavy load transfer Power swings

    CT saturation

    CT Phase errors Propagation delays

    Capacitance current

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    14/66

    Technology comparison for Protective Relays

    Sl.No.

    Subject Electro-mechanical

    Static/Electronic

    Numerical

    1. MeasuringElements/Hardware

    Induction disc,Electromagnets, Induction cup,Balance beam

    Discrete R, L, C,Transistors,

    Analogue ICs,Comparators

    Microprocessors, Digital ICs,Digital SignalProcessors

    2. Construction

    size

    Bulky Modular,

    Compact

    Most compact

    3. Parametersetting

    Plug setting,Dial setting

    Thumb wheel,Potentiometers,Dual In Lineswitches

    Keypad forNumericalvalues

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    15/66

    Technology comparison for Protective Relays

    continued

    Sl.

    No.

    Subject Electro-

    mechanical

    Static/

    Electronic

    Numerical

    4. CT Loading/

    burden

    8-10 VA 1 VA < 0.5 VA

    5. Self

    monitoring

    No Yes

    .Hardware

    partially

    .Powersupply

    Yes

    .Hardware

    .Power supply

    .Output relays

    .Software

    .CT, PT,Ckts

    6. Temperature

    stability

    Yes No Yes

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    16/66

    Technology comparison for Protective

    Relays continued

    Sl.

    No.

    Subject Electro-

    mechanical

    Static/

    Electronic

    Numerical

    7. Vibration

    proof

    No Yes Yes

    8. Harmonic

    immunity

    No Possible through

    analog

    filtering

    Yes, digital

    filtering

    incorporated

    9. Calibration Frequently

    required as

    settings drift

    due to ageing

    Required as

    settings drift

    due to ageing

    Not required as

    settings are

    stored in memory

    in digital format

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    17/66

    Technology comparison for Protective

    Relays continued

    Sl.No.

    Subject Electro-mechanical

    Static/Electronic

    Numerical

    10. Auxilliarysupply

    Required Required Required

    11. Electromagnetic/electrostatic

    /HF

    disturbance

    Immune Susceptible Immune

    12. Multiplecharacteristics

    Not possible Not possible Possible

    13. Integratedprotective

    functions

    Not possible Not possible Possible

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    18/66

    Technology comparison for ProtectiveRelays continued

    Sl.No.

    Subject Electro-mechanical

    Static/Electronic

    Numerical

    14. Range of settings Limited Wide Wide

    15. Operational valueindication

    Not possible Possible Possible

    16. Fault disturbancerecording

    Not possible Not possible Possible

    17. Digitalcommunicationport

    Not possible Not available Available

    18. Commissioningsupport from relay

    No No Yes

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    19/66

    Analog filter

    Sample & Hold

    Multiplexer

    Signal Input

    A/D converter

    Digital Filter Protn. algorithm

    Relay logic

    Trip /alarm

    Numerical Distance Relay

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    20/66

    Numeric Protection Sample and hold amplifier

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    21/66

    Numeric Protection

    Signal Sampling principle

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    22/66

    Numeric Protection

    Typical numeric relay hardware

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    23/66

    Numeric Protection

    Distance relay model ofTransmission Line

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    24/66

    Numeric Protection

    Impedance measuring algorithm

    Vr = Rir + L (dir /dt) -------------- (1)

    where

    R = Series ResistanceL = Inductance

    vr = Relaying voltage

    ir = Relaying current

    The current derivative of equation (1) can be written as

    Vr = Rir + L ir where ir = (dir/dt)

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    25/66

    Numeric Protection

    Impedance measuring algorithm ..contd.

    To solve for two unknowns, two equations are required..

    Hence two sets of relay voltages, currents and currentderivatives are utilised.

    Vr1 = Rir1 + L ir1Vr2 = Rir2 + L ir2

    Combining the above two equations,

    R = (Vr1ir2 - Vr2 ir1)/(ir1ir2 - ir2 ir1)

    L = (Vr2 ir1 - Vr1ir2 ) / (ir1ir2 - ir2 ir1 )

    For convenience, let D = (ir1ir2 - ir2 ir1 )

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    26/66

    Numeric Protection

    Impedance measuring algorithm ..contd

    The apparent resistance and reactance presented to the relaymay be calculated as follows:

    R x D = (Vr1ir2 - Vr2 ir1) and

    X x D = LD = (Vr2 ir - Vr1ir2 )

    where is power system frequency and X is reactance

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    27/66

    Numeric Protection Impedance measuring

    algorithm ..Time spaced solution

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    28/66

    Numeric Protection Impedance

    measuring algorithm ..current derivative

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    29/66

    Numeric Protection Quadrilateral

    characteristic and counting strategy

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    30/66

    Auto Reclosing scheme Single Phase and /or three Phase reclosing facilities

    Continuously variable single phase and three phasedead time.

    Continuously variable reclaim time

    Facility of selecting single phase / three phase /Single & three phase auto reclosure/ Non-autoreclosure modes.

    Facility for selecting check synchronising or dead linecharging features.

    Sequential reclosing facility of breakers in multiplebreaker arrangement.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    31/66

    Auto Reclosing scheme Setting criteria of auto reclosure

    Dead time : 1 sec

    Reclaim time : 25 Sec

    Protections which shall start autoreclosing

    Main-I Protection

    Main-II Protection

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    32/66

    Y Y

    B B

    R R

    Y Y

    B B

    R R

    Y Y

    B B

    R R

    I II

    III

    Auto Reclosure Sequence

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    33/66

    Auto Reclosing scheme Protections which block auto reclosing:

    LBB

    Line reactor Protection Over Voltage Protection

    Bus Bar Protection

    Zone-2/3 of distance Protection

    Circuit breaker problem

    Carrier fail

    Receipt of DirectTrip signal.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    34/66

    Over Voltage Protection Two stages

    High drop off to pick up ratio.

    Adjustable setting range for voltage and time.

    Low set stage and shall monitor any onePhase Phase voltage and shall have

    associated timer. High set stage shall monitor all three voltage

    and shall have associated timer.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    35/66

    59

    Vn

    1.1 Vn

    CVT

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    36/66

    Over Voltage Protection Over Voltage Protection shall be

    connected to:

    Trip connected line breaker(s)

    Start LBB

    Block auto reclose

    Send direct trip command

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    37/66

    Over Voltage Protection-Settings

    Low set stage at110% with typical timedelay of 5 seconds.

    High set stage at150% with time delayof100mSec

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    38/66

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    39/66

    Transformer Protection Transformer differential protection

    Restricted earth fault protection

    Over fluxing protection

    Back up directional Over current &Earth fault protection on HV side

    Back up directional Over current &Earth fault protection on IV side

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    40/66

    Transformer Differential Protection

    R

    Y

    B

    RYB

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    41/66

    Transformer Protection Protections & Monitors built-in to transformer

    Buchholz relay

    Winding temperature Oil temperature

    Oil level

    Pressure relief

    Fire protection

    Protection of tertiary winding

    Over load alarm

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    42/66

    Differential Protection Triple pole feature with individual phase

    indication

    Unrestrained instantaneous high set O/C unitswhich should not operate during in rush.

    Adjustable for multi bias setting

    Second harmonic or other inrush proof feature.

    One bias winding per phase and per CT input

    An adjustable operating current

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    43/66

    Bias

    1.0 2.0 3.0 4.0

    0.2

    1.0

    2.0

    3.0

    Through Bias Current

    Operate

    Not-Operate

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    44/66

    Restricted earth fault protection

    64

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    45/66

    Over Fluxing Protection Phase to Phase connected

    Operating on the principle of measurement of

    voltage to frequency ratio. Provided with inverse time characteristics

    compatible with transformer over fluxing.

    Provided with independent alarm with a

    definite time delay at value of V/F between100% to 130% of rated value.

    Having high reset ratio of 98% or better.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    46/66

    51

    51

    220KV

    400/220 KVTransformer

    A

    B

    Back-Up Over currentprotection

    400KV

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    47/66

    Over Load alarm Single Pole feature

    Definite time over current feature

    Continuously variable current range of50-200% of rated current andcontinuously variable timer setting

    range of1

    to10

    Secs. Drop off to Pick up ratio of 95% or

    better.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    48/66

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    49/66

    Reactor Protection Differential Protection

    Restricted earth fault Protection

    Reactor Back-up protection Buchholz relay

    Winding temperature

    Oil Temperature

    Pressure relief

    Oil Level

    Fire Protection

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    50/66

    R

    Y

    B B

    Y

    R

    Shunt Reactor

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    51/66

    R

    Y

    B B

    Y

    R

    Single line to Ground Fault

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    52/66

    Differential Protection -

    Reactor Operating current sensitivity of atleast

    10% of nominal current

    Tuned to system frequency Suitable non-linear resistors to limit peak

    voltage during in-zone faults

    High or low impedance principle

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    53/66

    Differential Protection -

    Reactor

    Operating current sensitivity of atleast

    10% of nominal current

    Tuned to system frequency

    Suitable non-linear resistors to limit peak

    voltage during in-zone faults

    High or low impedance principle

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    54/66

    Backup Protection-Reactor Either Impedance type or definite time O/C & E/F

    type

    Impedance type reactor back up Protection shall be

    Triple Pole type

    Single step Polarised MHO or impedance distancerelay

    Having characteristic angle between 60 80

    degree. Provided with adjustable definite time delay relay

    Provided with suitable range for covering 60% ofreactor impedance.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    55/66

    Bus Bar Protection

    87

    Ckt-1Ckt-2

    87Main Zone

    Check Zone

    RYB

    N

    RY

    B

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    56/66

    Bus Bar Protection 3 Phase type and operate selectively for each

    bus bar section

    Operating on differential principle and shallprovide independent zones of protection foreach bus.

    Provided with Zone indication

    Stable for through fault condition Provided with continuous supervision for CT

    secondaries.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    57/66

    Local Breaker Backup

    protection Short operation and drop-off times

    Three phase current elements with facility

    for phase wise initiation Current setting range such that the relay can

    be set at minimum 200mA (for line) and 50mA (for generator) for 1Amp CT secondary

    Associated timer with adjustable setting.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    58/66

    Distance to Fault locator Shall be electronic or microprocessor

    based

    On line type

    Shall be suitable for CB operation of2cycles

    Built-in display(KM)

    3% accuracy for all type of faults

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    59/66

    Distance to Fault locator Accuracy shall not be affected by Remote end

    infeed

    Dc component in fault current Arc resistance

    CVT transients

    Mutual compensation facility

    Based on traveling wave generated by fault

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    60/66

    Event Logger To record the state of switchyard

    equipments and relays.

    To record the occurrence of alarms.

    To record changes in digital inputs

    To record switching of primary plant

    within sub-station.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    61/66

    Event Logger Time synchronised with GPS clock

    Permissible drift +/- 0.5seconds/day

    Print out of current alarm and plant status available on request.

    To entry of date and time from key board.

    Programmability at site. Shall record 40 changes in 10mSec interval.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    62/66

    Disturbance Recorder To understand behavior of the Power

    network before or after any

    disturbance.

    Useful info in planning of newinstallations.

    For further improvement in theequipment

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    63/66

    Disturbance Recorder-Functions Records instantaneous values of V, I, In and open delta

    voltage.

    Status of relay contacts and CB during disturbance. Requirement

    Recoding capacity-8 analog + 16 digital.

    Memory 5 sec

    Min. Pre fault 160mSec Post Fault 2sec- min , not less than 5sec.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    64/66

    Disturbance Recorder-TriggersAny digital signal triggering.

    Analog triggering by threshold levels.

    Trigger selection of over/under levelsshould be possible.

    Time tagging:

    Built-in real time clock. Drift of the clock shall not be more than

    0.5sec per day.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    65/66

    Disturbance Recorder Sampling rate : 1 Khz

    Recording : 5Hz to 250Hz.

    Special requirement: Sync. With GPS

    16Analog + 32 digital for D/C lines

    DR + FL

    If DR is part of Numerical Protection,externalbinary input should be possible.

  • 8/6/2019 Line Protection AVSRamesh 28 Sep 2006

    66/66