lightstack ultra high density fiber...

10
LightStack Ultra High Density Fiber Enclosure As today’s high density Data Centers migrate from 10 to 40 and 100 gigabit speeds, they require low loss fiber connectivity to support multiple mated connections for flexible patching options over a wide range of distances and configurations while remaining within link loss budgets. At the same time, these connections need to be easily accessed and managed to quickly and effectively make changes. With superior best-in-class features, Siemon’s LightStack ultra high density fiber Plug and Play system offers superior density, port access and cable management in a sleek, modern enclosure that easily supports today’s advanced Data Center and storage area network environments, while providing fast, seamless migra- tion to advanced 40 and 100 gigabit applications. Mounting options Rack mounting brackets can be attached at any of 3 horizontal positions Visually appealing magnetic door - Easy to open and close - Eliminates potential pinch points ULtra High Density 144 fibers per 1U (LC interface) and 864 fibers per 1U (MTP interface) 576 fibers per 4U (LC interface) and 3456 fibers per 4U (MTP interface) Cable Management Clips Unlatch and swing open for full access to any jumper High Capacity Design Handles both traditional 2mm zipcord and 2 fiber, interconnect tight-buffered jumper types 1. Innovative labeling solution and port ID Drop-down label strip holder for high visibility Module Insertion and Removal Can be quickly and easily installed or removed from the front or rear of the enclosure LightStack 1U Front View

Upload: duongthu

Post on 27-Jul-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LightStack Ultra High Density Fiber Enclosurefiles.siemon.com/int-download-product-specsheets/siemon... · 2018-04-26 · LightStack™ Ultra High Density Fiber Enclosure ... Siemon’s

LightStack™ Ultra High Density Fiber EnclosureAs today’s high density Data Centers migrate from 10 to 40 and 100 gigabit speeds, they require low loss

fiber connectivity to support multiple mated connections for flexible patching options over a wide range of

distances and configurations while remaining within link loss budgets. At the same time, these connections

need to be easily accessed and managed to quickly and effectively make changes.

With superior best-in-class features, Siemon’s LightStack ultra high density fiber Plug and Play system offers

superior density, port access and cable management in a sleek, modern enclosure that easily supports

today’s advanced Data Center and storage area network environments, while providing fast, seamless migra-

tion to advanced 40 and 100 gigabit applications.

Mounting optionsRack mounting brackets can beattached at any of 3 horizontalpositions

Visually appealing magnetic door- Easy to open and close- Eliminates potential pinch points

ULtra High Density144 fibers per 1U (LC interface) and 864fibers per 1U (MTP interface)

576 fibers per 4U (LC interface) and 3456fibers per 4U (MTP interface)

Cable Management ClipsUnlatch and swing open for full accessto any jumper

High Capacity DesignHandles both traditional 2mm zipcord and 2fiber, interconnect tight-buffered jumper types

1.

Innovative labelingsolution and port IDDrop-down label stripholder for high visibility

Module Insertion and RemovalCan be quickly and easily installed orremoved from the front or rear of theenclosure

LightStack 1U Front View

SS_LightStack_I.qxp_I 4/19/18 1:56 PM Page 1

Page 2: LightStack Ultra High Density Fiber Enclosurefiles.siemon.com/int-download-product-specsheets/siemon... · 2018-04-26 · LightStack™ Ultra High Density Fiber Enclosure ... Siemon’s

2.

LightStack® EnclosuresSiemon’s LightStack ultra high density fiber Plug and Play enclosure offers superior density, port

access and cable management in a sleek, modern enclosure that easily supports today’s advanced data

center and storage area network environments.

Module Insertion and Removal — Can bequickly and easily installed or removedfrom the front or rear of the enclosure

Strain Relief — Swivel tie down allows forsimplistic approach for anchoring trunksand eliminating pinch points

Sliding Bottom Rear Divider — Acts as a rearcable divider between stacked enclosures (inthe out position). Pushes inward to providecomplete access to connectivity at the rear ofstacked enclosures

Mounting Options — Rack mountingbrackets can be attached at any of 3horizontal positions

Part # Description

LS-1U-01 . . . . . . . . . . . . . . . . . . LightStack enclosure, up to 144 LC fibersor 864 MTP fibers, 1U

LS-4U-01 . . . . . . . . . . . . . . . . . . LightStack enclosure, up to 576 LC fibersor 3456 MTP fibers, mounts in 19 in.racks or cabinets, 4U

Ordering Information:

Cable Management Clips — Unlatch andswing open for full access to any jumper

Innovative Labelling Solution — Drop-down label strip holder for high visibility

Innovative Magnetic Door — Opensand closes easily. Eliminates pinchpoints

1U Enclosure 4U Enclosure

1U 4U

Height 43.9 mm (1.73 in.) 176.8 mm (6.96 in.)

Width 482.3 mm (18.99 in.) 482.3 mm (18.99 in.)

Depth 530.6 mm (20.89 in.) 530.6 mm (20.89 in.)

Weight 9.53 kg (21 lb.) 23.58 kg (52 lb.)

Color Black (RAL 9005) Black (RAL 9005)

Label size 204.5mm (8.05 in.) L x 23.5mm (.925 in.) W 204.5mm (8.05 in.) L x 93mm (3.66 in.) W

SS_LightStack_I.qxp_I 4/19/18 1:56 PM Page 2

Page 3: LightStack Ultra High Density Fiber Enclosurefiles.siemon.com/int-download-product-specsheets/siemon... · 2018-04-26 · LightStack™ Ultra High Density Fiber Enclosure ... Siemon’s

3.

LightStack® Modules

Ultra Slim Design — LightStack modules have anultra slim design to achieve maximum fiber density

High Fiber Count — Up to 12 fibercount per module

Standard Interfaces — LC to MTPinterface. Available in OM4 and SM

LightStack LC-to-MTP Low Loss Plug and Play modules deliver a quick and efficient way to deploy high-perfor-

mance fiber cabling in a low-profile, high density package. Up to 12 of these ultra-slim modules can be installed

in a single 1U LightStack enclosure, seamlessly providing up to 144 easily-managed LC fiber ports. Available

in OM4 Multimode and Singlemode configurations, these modules offer industry leading loss performance of

just 0.35dB.

Low Loss Options — Low lossperformance (0.35dB perMultimode module)

Rear Module Handles — Handles in therear of module help facilitate removalfrom the back of the enclosure

Multiple Adapter Configurations —Aqua LC and MTP adapters for OM4;Blue LC adapters and black MTPadapters for SM

Ordering Information:

PERFORMANCE SPECIFICATIONSInsertionLoss (dB)

ReturnLoss (dB)

InsertionLoss (dB)

ReturnLoss (dB)

Multimode Singlemode

MTP 0.20 20 0.60 60

LC 0.15 30 0.40 55

MTP to LC 0.35 20 1.00 55

Reference Siemon’s White Paper titled: “The Need for Low-Loss Multifiber Connectivity in Today’s Data Center” for information and guidance on design options, channel mod-els and distances for 10, 40, 100Gb Ethernet and Fiber Channel applications.

Shuttered LC adapters — Optional smallplastic shutter door that opens upon insertionwithout touching the connector endface andsprings back into the closed position uponremoval to ensure protection of empty ports.

Part # Description

LS-12-LC5V-01. . . . . . . . . . . . . . Module, 12 LC-to-MTP fibers, OM4, XGLO 550, aqua LC and MTP adapters

LS-12-LCEV-01 . . . . . . . . . . . . . Module, 12 LC-to-MTP fibers, OM4, XGLO 550, erika violet LC and MTP adapters

LS-12-LCSM-01 . . . . . . . . . . . . . Module, 12 LC-to-MTP fibers, Singlemode, blue LC adapters, black MTP adapters

LS-12-LS5V-01. . . . . . . . . . . . . . Module,12 LC-to-MTP fibers, OM4, XGLO 550, shuttered aqua LC and MTP adapters

LS-12-LSEV-01 . . . . . . . . . . . . . Module, 12 LC-to-MTP fibers, OM4, XGLO 550, shuttered erika violet LC and MTP adapters

LS-12-LSSM-01 . . . . . . . . . . . . . Module, 12 LC-to-MTP fibers, Singlemode, shuttered blue LC adapters, black MTP adapters

SS_LightStack_I.qxp_I 4/19/18 1:56 PM Page 3

Page 4: LightStack Ultra High Density Fiber Enclosurefiles.siemon.com/int-download-product-specsheets/siemon... · 2018-04-26 · LightStack™ Ultra High Density Fiber Enclosure ... Siemon’s

LightStack® Adapter Plates

LightStack MTP Adapter Plates

• Ultra slim design to achieve maximum fiber density• Up to 72 fiber count• Handles in the rear of module helps facilitate removal from

the back of the enclosure

Ordering Information:

MTP Adapter Plate

LC Adapter Plate

Key Orientation

B = Aligned (key up to key up)C = Opposed (key up to key down)

Adapter Colour

AQ = Aqua**EV = Erika Violet**BK = Black**GR = Grey*

LS-MP(X)-01(X)(XX)

MTP Port Count2 = 2 MTP Ports4 = 4 MTP Ports6 = 6 MTP Ports

Ordering Information:

Fully ready to support 40 and 100 gigabit applications, LightStack low-loss 0.2dB MTP pass-through

adapters are available in 2, 4 and 6-port designs supporting up to 72 fibers per adapter and are offered in

both aligned and opposed key orientation to accommodate all polarity methods. In addition, LightStack

also offers industry exclusive 12-fiber LC pass-through adapter plates for current 10 gigabit Ethernet or

Fiber Channel SAN applications.

• Used in conjunction with LC BladePatch® RazorCore™ trunksfor rear connections only

• 12 LC fibers

LightStack LC Adapter Plates

* Key Orientation B Only

** Key Orientation C Only

4.

* Optional Shuttered LC adapters feature a small plastic shutterdoor that opens upon insertion without touching the con-nector endface and springs back into the closed positionupon removal to ensure protection of empty ports.

Adapter Colour

BG = Beige AQ = Aqua EV = Erika Violet BL = Blue

LS-L(X)12-01C-(XX)

Shutter Door Option

C = Standard LC adapterS = Shuttered LC adapter

SS_LightStack_I.qxp_I 4/19/18 1:56 PM Page 4

Page 5: LightStack Ultra High Density Fiber Enclosurefiles.siemon.com/int-download-product-specsheets/siemon... · 2018-04-26 · LightStack™ Ultra High Density Fiber Enclosure ... Siemon’s

5.

Base 12 MTP to LC BladePatch®

Trunks• LC BladePatch with push pull latch further improves accessibility• Designed to facilitate an interconnect or cross connect point between active

equipment• OM3/OM4 Bend Insensitive Fiber (BIF)• SM Non-Bend Insensitive• 12 Fiber strand count• Specific staggered lengths to active equipment - Nexus, Cisco MDS, Brocade and No stagger• Low Loss performance 0.15 dB for LC and 0.20 dB for Multimode MTP• Standard Loss performance 0.25 dB for LC and 0.60 dB for Singlemode MTP• Integrated cable manager on breakout

L = Low Loss (OM3/OM4 Only)F = Standard Loss (SM Only)

Performance

Jacket Rating

P = PlenumR = RiserL = LSOH

Pulling Eye OptionA = MTP Side (Only available for length >5MC = None

T(X)2(X)(X)(X)(X)(X)(X)(XX)(XXX)(X)

B = 12 Strand Strand Count

LC BP ConnectorLB = RFP (OM3, OM4, SM/UPC)BL = CFP (OM3, OM4, SM/UPC)

MTP GenderM = MTP MaleF = MTP Female

Stagger Type1 = No Stagger

2 = Cisco 9512 & 9412

3 = Cisco NEXUS

4 = Brocade

Length UnitF = FeetM = Meter

Length*Length must be 3 digits Example:003 = 3m010 = 10 ft.

Ordering Information:

L = OM3, XGLO 300 50/125 Multimode AquaV = OM4, XGLO 550 50/125 Multimode AquaE = OM4, XGLO 550 50/125 Multimode Erika VioletA = OS1/OS2, Singlemode Yellow

Fiber Type

Base 12 Next Generation MTP to MTP TrunksSiemon's Next Generation MTP to MTP trunks are designed to achieve 45kg (99.2 lbs.) pull strength to han-

dle more aggressive pathway environments. They come with a foamed zipper pulling eye for quick

removal saving on installation time and are reusable if relocation of a trunk is required after the initial

installation. They are available in 12/24 fiber counts and Low Loss options only.

• OM3/OM4 Bend Insensitive Fiber (BIF)• SM Non-Bend Insensitive Fiber• 12 and 24 Fiber strand counts• Polarity methods A, B and C options• Low Loss performance (0.20dB for Multimode MTP and 0.60dB for

Singlemode MTP)• Integrated breakout and zipper pulling eye work together to achieve

45kg (99.2 lbs.) tensile pull strength• Zipper pulling eye allows for quicker installs - Allows pulling eyes to be reused when relocating trunks

during MAC work

B = 12C = 24

Strand Count

Cable Type

P = PlenumR = RiserL = LSOH

FR2-(X)-(X)(X)(XXX)(X)(X)

Fiber TypeLength Unit

F = FeetM = Meters

Polarity Method (Per TIA-568-C.0)

LengthLength must be 3 digitsExample: 003 = 3m010 = 10 ft.

Ordering Information:

A = Method AB = Method BC = Method C

L = OM3, XGLO 300 50/125 Multimode AquaV = OM4, XGLO 550 50/125 Multimode AquaE = OM4, XGLO 550 50/125 Multimode Erika VioletA = OS1/OS2, Singlemode Yellow

SS_LightStack_I.qxp_I 4/19/18 1:56 PM Page 5

Page 6: LightStack Ultra High Density Fiber Enclosurefiles.siemon.com/int-download-product-specsheets/siemon... · 2018-04-26 · LightStack™ Ultra High Density Fiber Enclosure ... Siemon’s

Ordering Length

1 meter (3.3 ft) 1 meter (3.3 ft)

6.

** Order length is measured connector tip to connector tip. Multi-leg ver-sions offered with standard 1 meter legs. Minimum order length is 1meter for 12 strand and 3 meters for 24 strands or greater(See diagram at right)

* Fiber Extenders ship with MTP Adapter for quick transition.

Combining Siemon’s reduced-diameter RazorCoreTM cable with 12-fiber MTP connectors, Plug and Play

Reels are designed to be quickly pulled and connected to Siemon Plug and Play Modules and MTP Adapter

Plates. Custom configurable to precise application requirements, these reels efficiently put high-perfor-

mance, high-density fiber connections exactly where you need them. Extenders offer Male MTP

Connectors on one end and female MTP adapters on the other to allow field extension of MTP Reels.

Base 12 Plug and Play Cable Assemblies

Ordering Information: Non-Armoured

Fiber Count

12 = 1224 = 2436 = 3648 = 4872 = 7296 = 96144 = 144

Fiber Type

Length**

Configuration

F(X)(XX)-(XX)(X)(XXX)(X)-(X) . . . . Fiber Plug & Play cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . assembly, 12 fiber MTP

connectors

Jacket Rating

R = RiserP = PlenumL = LSOH

Length UnitF = FeetM = Meters

R = Standard LossL = Low Loss

(0M3/0M4 only)E* = Standard Loss ExtenderB* = Low Loss Extender

(0M3/0M4 only)

F(X)(XX)-(XX)(XX)(XXX)(X)(X) . . . . Armoured Fiber Plug & Play cablereel assembly, 12 fiber MTP femaleconnectors

Fiber Count

12 = 1224 = 2436 = 3648 = 4872 = 7296 = 96144 = 144

Fiber Type Jacket Rating

AR = Armoured RiserAP = Armoured Plenum

Length UnitF = FeetM = Meters

Ordering Information: Armoured

ConfigurationR = Standard LossL = Low Loss

(0M3/0M4 only)

Polarity Method (Per TIA-568-C.0)A = Method AB = Method BC = Method CBlank = Fiber Extender (FE and FB)

Polarity Method (Per TIA-568-C.0)A = Method AB = Method BC = Method C

6 = OM1, 62.5/125 Multimode Orange5L = OM3, XGLO 300 50/125 Multimode Aqua5V = OM4, XGLO 550 50/125 Multimode AquaEV = OM4, XGLO 550 50/125 Multimode Erika VioletSM = OS1/OS2, Singlemode Yellow

Length must be 3 digitsExample: 003 = 3m

010 = 10 ft.

6 = OM1, 62.5/125 Multimode Orange5L = OM3, XGLO 300 50/125 Multimode Aqua 5V = OM4, XGLO 550 50/125 Multimode AquaEV = OM4, XGLO 550 50/125 Multimode Erika Violet SM = OS1/OS2, Singlemode Yellow

Length**

Length must be 3 digitsExample: 003 = 3m

010 = 10 ft.

Reduced Pathway Fill — Siemon'sRazorCore cable has significantlyreduced cable O.D. resulting in lesscable tray fill and pathway restrictions

Custom Configurations — Availablefrom 12 to 144 fiber counts in increments of 12 fibers

Multiple Fiber Types — Available in Multimode(62.5/125, and laser optimised 50/125OM3/OM4) and Singlemode.

40 Gb/s and 100 Gb/s Ready — Enables simple upgradepath to future 40 Gb/s and 100 Gb/s applications overMultimode 50/125 laser optimised fiber

Note: LSOH versions available. Contact CustomerService for details.

SS_LightStack_I.qxp_I 4/19/18 1:56 PM Page 6

Page 7: LightStack Ultra High Density Fiber Enclosurefiles.siemon.com/int-download-product-specsheets/siemon... · 2018-04-26 · LightStack™ Ultra High Density Fiber Enclosure ... Siemon’s

7.

T(X)(X)(X)(XX)(X)(XX)LC(XXX)(X). . . . . . . . . . MTP to LC Trunk (distribution to breakout)

1 meter

> 1 meter

50cm

1 meter

See performance details on page 6.27.

Custom Configurations — Available from 12 to144 fiber counts in increments of 12 fibers

Multiple Fiber Types — Available in Multimode(62.5/125 and laser optimised 50/125 OM3/OM4)and Singlemode.

Base 12 MTP®

to LC Trunks

Utilising high quality Siemon RazorCore™ cable, MTP to LC Trunks offer a connectivity transition from

12-fiber MTP connectors to duplex LC connectors. These may be implemented using Siemon’s MTP to

MTP Adapter Plates to provide direct MTP to LC patching options over a wide range of distances and

infrastructure configurations.

Ordering Information:

Fiber Count

B = 12C = 24E = 36F = 48G = 72H = 96J = 144

Pulling Eye

A = Side AB = Side BC = None

Fiber TypeMM = MaleMF = Female

MTP Connector Gender

Length*

Jacket RatingP = PlenumR = RiserL = LSOH

Length UnitF = FeetM = Meters

Configuration

L = Low Loss (OM3/OM4 only)F = Standard Loss

Length must be 3 digitsExample: 003 = 3m

010 = 10 ft.

6 = OM1, 62.5/125 Multimode Beige5L = OM3, XGLO 300 50/125 Multimode Aqua5V = OM4, XGLO 550 50/125 Multimode AquaEV = OM4, XGLO 550 50/125 Multimode Erika VioletSM = OS1/OS2, Singlemode Yellow

* Minimun order length is 1 meter. Order length is measured connector tip to connector tip. Trunks greater than 1 meter (3.28 ft.) have breakout length of 1 meter. 1 meter trunks have a 50cm breakout length (See diagram below)

SS_LightStack_I.qxp_I 4/19/18 1:56 PM Page 7

Page 8: LightStack Ultra High Density Fiber Enclosurefiles.siemon.com/int-download-product-specsheets/siemon... · 2018-04-26 · LightStack™ Ultra High Density Fiber Enclosure ... Siemon’s

8.

TFU(X)(X)(X)(X)(X)(X)(X)(X)(XXX)(X)

Note: These products are made to order. Call for lead time and availability.

Ordering Length(Side A) (Side B)

1 meter 1 meter

Ordering length is measured connector tip to connector tip. 2. 4 unitube duplex, 2.0mm duplex and simplex 900 micron bufferedMinimum order length is 3 meters (9.8 ft).

Fiber CountA = 6B = 8C = 12D = 16E = 24F = 36G = 48H = 72J = 96K = 144

Pulling EyeA = Side AB = Side BC = Side A&BD = None

Fiber Type

Connector Type (Side B)

Cable LengthLength must be 3 digitsExample: 004 = 4m

012 = 12 ft.

Unit of MeasureF = FeetM = Meters

Connector Type (Side A)

Cable Type

P = Plenum - Indoor Distribution (OFNP)R = Riser - Indoor Distribution (OFNR)L = LSOH - Indoor Distribution (IEC 60332-3C)

A = Simplex 900µmB = Duplex 2.0mmC = Uni-Tube Duplex 2.4mm LC BladePatch only

LEG OD (Side A) A = Simplex 900µmB = Duplex 2.0mmC = Uni-Tube Duplex 2.4 LC BladePatch only

LEG OD (Side B)

(3.28 ft.) (3.28 ft.)

A = OS1/OS2, 62.5/125 Singlemode YellowB = OM1, 62.5 Multimode OrangeL = OM3, XGLO 300 50/125 Multimode Aqua V = OM4, XGLO 550 50/125 Multimode AquaE = OM4, XGLO 550 50/125 Multimode Erika Violet

A = LC MultimodeB = LC UPC SinglemodeC = LC APC SinglemodeD = LC BladePatch Multimode RFP Polarity only

E = LC BladePatch UPC Singlemode RFP Polarity onlyF = SC MultimodeG = SC UPC SinglemodeH = SC APC Singlemode

J = ST MultimodeK = ST UPC Singlemode

A = LC MultimodeB = LC UPC SinglemodeC = LC APC SinglemodeD = LC BladePatch Multimode RFP Polarity only

E = LC BladePatch UPC Singlemode RFP Polarity onlyF = SC MultimodeG = SC UPC SinglemodeH = SC APC Singlemode

J = ST MultimodeK = ST UPC Singlemode

2.4mm Unitube Duplex Breakout - LC BladePatch®

XGLO® and LightSystem® Fiber Trunks

900µm Simplex Breakout 2.0mm Duplex Breakout

SS_LightStack_I.qxp_I 4/19/18 1:56 PM Page 8

Page 9: LightStack Ultra High Density Fiber Enclosurefiles.siemon.com/int-download-product-specsheets/siemon... · 2018-04-26 · LightStack™ Ultra High Density Fiber Enclosure ... Siemon’s

9.

XGLO® and LightSystem® LC & SCFiber Trunks

JacketType

Fiber StrandCount

Cable Diametermm (in.)

Min Bend Radius Operational

mm (in.)

Min Bend RadiusInstallation

mm (in.)

Max Pulling EyeDiametermm (in.)

*Required DuctDiameter mm (in.)

Riser 6 3.0 (0.12) 30 (1.2) 45 (1.8) 44.5 (1.75) 69.9 (2.75)

Riser 8 3.0 (0.12) 30 (1.2) 45 (1.8) 44.5 (1.75) 69.9 (2.75)

Riser 12 3.0 (0.12) 30 (1.2) 45 (1.8) 44.5 (1.75) 69.9 (2.75)Riser 16 3.8 (0.15) 38 (1.5) 57 (2.2) 44.5 (1.75) 69.9 (2.75)

Riser 24 3.8 (0.15) 38 (1.5) 57 (2.2) 44.5 (1.75) 69.9 (2.75)Riser 36 9.4 (0.37) 94 (3.7) 141 (5.6) 63.5 (2.5) 88.9 (3.5)

Riser 48 9.4 (0.37) 94 (3.7) 141 (5.6) 63.5 (2.5) 88.9 (3.5)Riser 72 9.4 (0.37) 94 (3.7) 141 (5.6) 63.5 (2.5) 88.9 (3.5)

Riser 96 13.2 (0.52) 132 (5.2) 198 (7.8) 88.9 (3.25) 114.3 (4.5)Riser 144 13.2 (0.52) 132 (5.2) 198 (7.8) 88.9 (3.25) 114.3 (4.5)

Plenum 6 3.0 (0.12) 30 (1.2) 45 (1.8) 44.5 (1.75) 69.9 (2.75)

Plenum 8 3.0 (0.12) 30 (1.2) 45 (1.8) 44.5 (1.75) 69.9 (2.75)

Plenum 12 3.0 (0.12) 30 (1.2) 45 (1.8) 44.5 (1.75) 69.9 (2.75)

Plenum 16 3.8 (0.15) 38 (1.5) 57 (2.2) 44.5 (1.75) 69.9 (2.75)

Plenum 24 3.8 (0.15) 38 (1.5) 57 (2.2) 44.5 (1.75) 69.9 (2.75)

Plenum 36 7.5 (0.30) 75 (3.0) 113 (4.4) 63.5 (2.5) 88.9 (3.5)

Plenum 48 7.5 (0.30) 75 (3.0) 113 (4.4) 63.5 (2.5) 88.9 (3.5)

Plenum 72 8.5 (0.33) 85 (3.3) 128 (5.0) 63.5 (2.5) 88.9 (3.5)Plenum 96 13.6 (0.54) 136 (5.4) 204 (8.0) 88.9 (3.25) 114.3 (4.5)

Plenum 144 13.6 (0.54) 136 (5.4) 204 (8.0) 88.9 (3.25) 114.3 (4.5)

LSOH 6 3.0 (0.12) 30 (1.2) 45 (1.8) 44.5 (1.75) 69.9 (2.75)LSOH 8 3.0 (0.12) 30 (1.2) 45 (1.8) 44.5 (1.75) 69.9 (2.75)

LSOH 12 3.0 (0.12) 30 (1.2) 45 (1.8) 44.5 (1.75) 69.9 (2.75)LSOH 16 3.8 (0.15) 38 (1.5) 57 (2.2) 44.5 (1.75) 69.9 (2.75)LSOH 24 3.8 (0.15) 38 (1.5) 57 (2.2) 44.5 (1.75) 69.9 (2.75)

LSOH 36 6.5 (0.26) 65 (2.6) 98 (3.3) 63.5 (2.5) 88.9 (3.5)LSOH 48 6.5 (0.26) 65 (2.6) 98 (3.3) 63.5 (2.5) 88.9 (3.5)

LSOH 72 7.0 (0.28) 70 (2.8) 105 (4.1) 63.5 (2.5) 88.9 (3.5)LSOH 96 12.5 (0.49) 125 (4.9) 188 (7.4) 88.9 (3.25) 114.3 (4.5)

LSOH 144 14.9 (0.59) 149 (5.9) 224 (8.8) 88.9 (3.25) 114.3 (4.5)

*Pulling eye assembly shall be capable of passing through these minimum duct diameter requirements during product installation.Pulling eye max pull force 18.1kg (40lbs)

CABLE — Optical and Physical Specifications

Fiber Type Performance Class

Max Insertion Loss (dB)

Min Return Loss (dB)

62.5/125 µm Multimode, OM1 LightSystem 0.50 25

50/125 µm Laser Optimised Multimode, OM3,OM4 XGLO 0.25 30

Singlemode UPC, OS1/OS2 XGLO 0.40 55

Singlemode APC, OS1/OS2 XGLO 0.40 65

CONNECTORS — Optical Specifications

SS_LightStack_I.qxp_I 4/19/18 1:56 PM Page 9

Page 10: LightStack Ultra High Density Fiber Enclosurefiles.siemon.com/int-download-product-specsheets/siemon... · 2018-04-26 · LightStack™ Ultra High Density Fiber Enclosure ... Siemon’s

SS-L

ight

Stac

k R

ev I

4/18

©

2018

Siem

on

10.

STANDARD LOSS ASSEMBLIES

CABLE - OPTICAL AND PHYSICAL SPECIFICATIONS

CONNECTORS - PHYSICAL SPECIFICATIONS

Product Specifications

Fiber Type

MAX Insertion(dB)

MAX Return Loss(dB) Performance Class

MTP LC MTP LC

5L-MM50/125(OM3) 0.50 0.25 20 30 XGLO® 300

5V-MM50/125(OM4) 0.50 0.25 20 30 XGLO 550

SM-LWP SM (OS1/OS2) 0.60 0.40 60 55 XGLO

Fiber Type

MAX Insertion(dB)

MAX Return Loss(dB) Performance Class

MTP LC MTP LC

5L-MM50/125(OM3) 0.20 0.15 20 30 XGLO 300

5V-MM50/125(OM4) 0.20 0.15 20 30 XGLO 550

LOW LOSS ASSEMBLIES

* XGLO singlemode fiber meets low water peak specifications per ITU-TG.652.C

Plug and Play Fiber System OpticalPerformance

Cable Type

Multimode

SinglemodeXGLO50/125 OM3 (850/1300nm)

XGLO50/125 OM4 (850/1300nm)

Fiber Cable Attenuation, MAX (dB/km) 3.0 / 1.0 3.0 / 1.0 0.4/ 0.4/ 0.3*

LED Bandwidth, MIN (MHz/km) 1500 / 500 3500 / 500 N/A

Effective Modal Bandwidth, MIN (MHz/km) 2000 4700 N/A

Cable Outer Jacket, Colour (Per TIA-598-C) Aqua Aqua/ Erika Violet Yellow

ConnectorType

IEC Intermateability

Compliance

TIA Intermateability

Compliance

Housing Colour Boot Colour

MM SM MM SM

MTP IEC 61754-7 TIA/EIA-604-5 Aqua/ Erika Violet Green Black (Base 8)Blue (Base12)

Black (Base 8)Blue (Base12)

Because we continuously improve our products, Siemon reserves the right to change specifications and availability without prior notice.

Worldwide Headquarters North AmericaWatertown, CT USA

Phone (1) 860 945 4200

Regional Headquarters Europe Russia AfricaChertsy, Surrey, England

Phone (44 ) 0 1932 571771

Regional Headquarters ChinaShanghai, P.R. China

Phone (86) 215385 0303

Regional Headquarters Latin America Bogota, Colombia

Phone (571) 657 1950/51/52

Regional Headquarters India Middle EastDubai, United Arab Emirates

Phone (971) 4 3689743

Siemon Interconnect SolutionsWatertown, CT USAPhone (1) 860 945 4213 US

www.siemon.com/SIS

Regional HeadquartersAsia PacificSydney, Australia

Phone (61) 2 8977 7500