Intercal Wärmetechnik GmbH Im Seelenkamp 30 32791 Lage (Germany) Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/2 Wärmetechnik

Upload: duongkhue

Post on 04-Jun-2018

241 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

Intercal Wärmetechnik GmbHIm Seelenkamp 30

32791 Lage (Germany)

Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2

Fuel oil EL as per DIN 51 603, part 1

Installation Operation MaintenanceSL 400/2, SL 410/2, SL 420/2

Wärmetechnik

Page 2: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

2

Page 3: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

Contens

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/23

1 STANDARDS AND REGULATIONS .................................................................... 51.1 Standards and regulations .................................................................................... 51.2 Exhaust system and effective heat demand ......................................................... 51.3 Nozzle selection .................................................................................................... 52 GENERAL ............................................................................................................. 62.1 Modern concept .................................................................................................... 62.2 Two-stage burners SL 400/2 und SL 410/2 ........................................................... 62.3 Modern design ...................................................................................................... 63 INSTALLATION ..................................................................................................... 73.1 Simple installation ................................................................................................. 73.2 Instructions for using the burner ........................................................................... 74 OPERATION ......................................................................................................... 84.1 Operation and adjusting ........................................................................................ 84.2 Air intake nozzle .................................................................................................... 84.3 Adjusting the oil pressures SL 400/2 to SL 410/2 .................................................. 94.4 Adjustment dimensions .......................................................................................... 104.5 Ignition electrode setting ......................................................................................... 105 MAINTENANCE ...................................................................................................... 115.1 Maintenance and service ........................................................................................ 116 TROUBLESHOOTING ............................................................................................126.1 Troubleshooting ...................................................................................................... 12

7 TECHNICAL DOCUMENTATION .......................................................................... 147.1 Basic settings table and adjustment dimensions SL 400/2 - SL 420/2 ................... 147.2 Electrical connection ............................................................................................... 157.3 Boiler connection .................................................................................................... 157.4 Working fi eld ........................................................................................................... 157.5 Defi ning the oil feed pipe ........................................................................................ 167.6 Circuit diagram SL 400/2 ........................................................................................ 177.7 Circuit diagram SL 410/2 - 420/2 ............................................................................ 187.8 Explosion drawing SL 400/2.................................................................................... 217.9 Key for explosion drawing SL 400/2 ....................................................................... 227.10 Explosion drawing SL 410/2 - SL 420/2 .................................................................. 237.11 Key for explosion drawing SL 410/2 - SL 420/2 ...................................................... 247.12 Burner dimensions .................................................................................................. 258 GUARANTEE .......................................................................................................... 268.1 Guarantee ............................................................................................................... 268.2 Oil tank and oil pipes .............................................................................................. 268.3 Spare parts ............................................................................................................. 26Manufacturer‘s certifi cate ................................................................................................... 27

Page 4: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance4

Safety instructions – Please observe!

Please comply with the assembly, operation and maintenance instructions for installing and adjusting the light oil pressure jet burner!

Please read this installation manual carefully before starting installation. We cannot assume any liability or guarantee for damage caused by failure to comply with this installation manual!

Work which is not carried out properly can cause injury to persons or damage to property!

Work on the heating system Installation, commissioning, maintenance and servicing work may only be carried out by an authorised firm of heating contractors.

When working on burner and boiler switch off the heating system emergency switch and secure it to prevent it being switched on again.

shut off the oil feed pipe and secure it to prevent it being opened unintentionally.

This symbol refers to instructions which must be heeded for your own safe-ty and that of other people, and to avoid damage to property.

This symbol refers to instructions which must be heeded for the burner to operate safely and function correctly. It also draws attention to statutory regulations which need to be observed.

Page 5: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

1. Standards and regulations

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/25

1.1 Standards and regulations

The following standards and regulations are to be observed during installa-tion and operation of the burner.

HeizAnlVHeating system ordinance

FeuVoFiring ordinance of the German federal states

1. BImSchVFirst ordinance for implementation of the German Emission Pro-tection Law

VDI 2035Guidelines for preventing damage from corrosion and scale formation in hot water heating installations

VDERegulations and special requirements issued by the energy utility companies

EN 303, Part 1 and Part 2Heating boilers with forced draught burners

EN 60335, Part 1Safety of household and similar electrical appliances

DIN 4705Calculating the dimensions of chimneys

DIN 4751Hot water heating installations – safety requirements

DIN 4755Oil fi ring installations – construction, execution, safety require-ments

DIN EN 267Automatic forced draught burners for liquid fuels – defi nitions, requirements, construction and testing

DIN 51603, Part 1Fuel oils extra light

DIN 57116Electrical equipment of fi ring installations

Please comply with the valid regional building code.

1.2 Exhaust system and effective heat demandBoiler, burner and exhaust system (chimney) constitute an operating unit; account must be taken of low exhaust temperatures when reducing the output.For exhaust temperatures below 160°C, the system must be designed so as to avoid damage from condensation.It is advisable to install draught limiters (secondary air systems) to achieve stable combustion values under varying conditions and to reduce possible humidity in the chimney. These should be in-stalled in the chimney where possib-le, to avoid any noises in the fl ue pipe.

1.3 Nozzle selectionPlease note that trouble-free and low-pollution combustion can only be achieved with nozzles which are rated to the burner. The nozzles stated in chapter 7.1 are certifi ed for light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 and should be used accordingly.

Page 6: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

2. General

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance6

2.1 Modern conceptThe oil burners SL 400/2, SL 410/2, SL 420/2 are fully automatic oil jet burners in monobloc design, made and tested to DIN EN 267 respectively DIN 4787.

The burners are equipped with automatic oil fi ring units for intermittent operation to DIN EN 230 respectively DIN 4787; automatic units for continuous operation are available on request.

The two-stage burners of this series consist of overpressure burners with very high fan pressing and steep cha-racteristic curve. Together with the variable adjustment of the air intake nozzle, these features mean that these burners are ideal equally for modern U-fi red heavy-duty boilers or for older natural draft boilers.

Advantages of the modern design: Load stages 1 and 2 are achieved with only one oil nozzle and two different oil quanti-ties. Nozzle and baffl e plate are fi tted symmetrically in every operating state.

The performance spread of 70:100 guarantees adequate graduation of the two load stages and also safeguards an ade-quate exhaust temperature even in the small load stage.

2.2 Two-stage burners SL 400/2, SL 410/2, SL 420/2

Housing of die cast light metal, output-dependent burner pipes with adjustable nozzle connection, mixing system, AC motor (SL 400/2) respectively three phase motor with motor contactor (SL 410/2, SL 420/2), ignition transfor-mer, fan wheel, adjustable air intake nozzle and throttle actuator for twostage operation, oil pump with two separa-tely adjustable pressure ranges, solenoid valves, joint nozzle for stage 1 and 2, oil hoses, automatic oil fi ring unit with photo resistance, connection plug and fi tting fl ange with fastening screws. Burner heat tested.

2.3 Modern design

There are constructional advantages in using a modern, symmetrically designed combustion system with only one nozzle. The symmetrical arrangement of nozzle and mixing system/baffl e plate means that in two-stage operation with corresponding oil pressures and settings of the oil throttle, optimum combustion values can be achieved with almost sootfree operation. Two-stage operation is achieved in SL 400/2, SL 410/2 and SL 420/2 by adjusting the oil pressure in the range from 10 to 25 bar. The resulting performance spread of 70:100 allows precise adjustment to current heating needs, taking account of the tolerable exhaust temperature.

Fig. 1:

Page 7: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

3. Installation

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/27

3.1 Simple installation

The clear arrangement of all parts and complete equipment with output-related nozzles and oil hoses makes it easy for the engineer to install. In the individual burner sizes, the burner output can be adjusted by changing the nozzle and correcting the adjustment dimensions. The burners are ready wired to connection plugs. The necessa-ry burner head length can be easily adjusted by a clamping fl ange. All maintenance work can be carried out with a minimum of tools.

The quality of the equipment, solid workmanship and a comprehensive system of production controls and subse-quent heat testing guarantee a uniformly high production standard.

3.2 Instructions for using the burner

The oil-burners SL 400/2, SL 410/2, SL 420/2 are basically suitable for use in commercially available heating boilers (intermittent operation) for heating residential buildings and for service water. Product development and the test procedures have been geared to the operating conditions of these systems.

The areas of application listed below make particular requirements with special operating conditions for the burner, so that Intercal Wärmetechnik reserves the right to issue explicit approval in these cases:

dark radiators baking ovens annealing furnaces drying chambers industrial applications

In the case of rooms where the air must be expected to be contaminated by halogenated hydrocarbons, e.g. hair-dressers, printers, chemical dry cleaners, laboratories, etc. the burners must only be operated if suitable measures are taken to ensure that there is an adequate supply of uncontaminated combustion air.

Always consult Intercal Wärmetechnik if in any doubt.

The burners must not be operated in rooms with high dust levels or high humidity (e.g. laundries). The heating room must be protected from frost and well aired.

Failure to comply with these instructions renders the warranty null and void for any damage resulting from one of these causes.

Page 8: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

4. Operation

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance8

4.1 Operation and adjusting

Every burner is preset and heat tested. The basic setting can be seen in chapter 7.1. The following instructions should be observed when making adjustments:

Only a qualifi ed engineer may proceed with adjustments and initial commissioning. The oil pressure is adjusted at the oil pump; see section „adjusting the oil pressure“.

When adjusting the burner, it is advisable to measure the air pressure before the baffl e plate (see table values for air pressure in chapter 7.1). The measuring fi tting is located next to the nozzle connection on the fl ange cover.

The combustion air can be adjusted in three ways:

a. Adjusting the air intake nozzle; adjustment according to burner output and local conditions:- position 0 - 5 (0 - 1) for natural draft boilers- position 6 - 9,5 (2 - 4) for counter-pressure boilers

b. Adjustment of the baffl e plate in the burner pipe (see table basic setting); in this way, the air velocity in the combustion head and the fl ame form can be adjusted to the combustion chamber conditions.

c. Adjustment of the air throttle for the 1st and 2nd stage via cam switch for stage 1 (blue) and stage 2 (orage); turn to the left to reduce the air fl ow and to the right to increase the air fl ow. Inadequate air fl ow in stage 1 is changed as follows:- Adjust the cam switch (blue) upwards (more air)- Briefl y switch over to stage 2 on boiler thermostat 2. After switching back, the actuator turns back to the required position.

Fig. 2:

For too much air fl ow in stage 1 or inadequate fl ow in stage 2, adjust the corresponding cam switch. To reduce too much air fl ow, adjust the cam switch (orange) accordingly. Close the actuator briefl y by changing over to the second stage at the controller, or pulling the green 4-pole connector, and then return to the opera-ting state.

The long black cam switch can be used to change the switching point for the 2nd solenoid valve (stage 2). When the burner is switched off normally and because of faults, the air throttle can be brought to the closed position by using the actuator cam switch (black, short).

4.2 Air intake nozzle Fig. 3: Adjusting the air intake nozzle:The intake nozzle can be adjusted after opening the burner. For this purpo-se, the two screws of the air intake nozzle should only be loosened and then tightened again after the adjustment has been made.

Page 9: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

4. Operation

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/29

4.3 Adjusting the oil pressures

If no oil is supplied when oil is sucked in for the fi rst time, this must be interrupted after max. 3 minutes to avoid damage to the pump. The operating condition has been achieved once the oil fi lter is fi lled with oil.

The oil pressure is adjusted at the oil pump.

The adjustment screwsP1 (upper screw = low pressure = stage 1) andP2 (lower screw = high pressure = stage 2).

The adjustment screws are located on the pump cover or on the side of the pump, depending on pump type.

The pressure in stage 1 must always be lower than in stage 2.

V = vacuumP = oil pressure

Never turn the setting screw before venting the pump!

Fig. 5:

Fig. 6:

V

P P2

P1

Page 10: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

4. Operation

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance10

4.4 Adjustment dimensions

4.6 Ignition electrode setting

4.5 Adjustment dimensions

Fig. 7: Adjustment dimensions SL 400/2

Fig. 8: Adjustment dimensions SL 410/2 and SL 420/2

Fig. 10:

Page 11: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

5. Maintenance

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/211

5.1 Maintenance and service

On the basis of statutory regulations, it is recommended for oil fi ring systems to be serviced by a qualifi ed engi-neer every twelve months. The burner settings and functions must be checked, the burner cleaned (fan wheel, mixing system, ignition system) and the nozzle replaced if necessary.

The oil hoses should be checked every year and replaced after 5 years.

In order to carry out maintenance work, the housing cover with the function parts can be separated from the bur-ner housing by loosening the attachment screws, pulled out and hung in the service position.

Check screwed unions for leaks during annual maintenance. Replace defect or worn seals.

Fig. 11:Burner in service position

Page 12: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

6. Troubleshooting

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance12

6.1 Troubleshooting

Check general operating status. Are the stated values maintained?

Fault Cause Remedy

Burner does not work Power failure.Control chain closed?

Automatic fi ring unit defect.

Check main switch and fuses, operating switch, STB, TR

Check burner motor and capacitor (SL 400/2), replace if necessary.

Replace fi ring sequence controller

Burner starts,oil sight glass at oil fi lter remains empty

Plug not removed or incorrect connection during initial commissioning.

Oil pipe was not fi lled during initial commissioning; it takes several minutes for the oil to be sucked in.

Fuel oil in oil tank? Suction pipe valve open?

Wrong direction of fl ow at check valve.

Oil pump not working.

Coupling between motor and oil pump defect

Leaking suction pipe or vacuum too high.

Oil pipe squashed.

Separate valve, e.g. valve outside tank closed

Check oil hoses in case bung not removed, check that correctly connected

Fill oil pipe before initial commissioning.Do not let the oil pump run for longer than 3 minutes without oil!

Check oil tank display and valve in suction pipe.

Check direction of fl ow at check valve.

Check and possibly replace electric connection.

Replace coupling.

See rating the oil pipe (chapter 7.5)

Check oil pipe, replace if necessary.

Open corresponding valve. Check routing of oil pipe.

Burner starts,oil level glass fi lled,ignition stays off,system shuts down

Ignition transformer or cable not OK.

Extremely worn ignition electrodes or damaged insulators.

Incorrect setting of ignition electrodes.

Incidence of secondary light at fl ame monitor

Firing sequence controller damaged.

Replace ignition transformer or cable.

Replace spark electrodes.

Correct setting of ignition electrodes as per settings.

Prevent incidence of secondary light at fl ame monitor

Replace fi ring sequence controller

Page 13: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

6. Troubleshooting

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/213

Fault Cause Remedy

Burner starts,spark visible,fl ame does not ignite orburner switches off during ongoing operation

Oil solenoid does not open.

No passage through oil pipe, preheater and nozzle.

Oil pump delivers no oil, oil tank empty.

Filter in nozzle clogged.

Suction pipe leaks.

Suction pipe not vented.

Mixing device clogged.

Burner setting not OK.

Replace oil solenoid coil, check electrical connection cable.

Check that oil pipe, pre-heater and nozzle are not blocked, replace if necessary

Check oil pump and oil tank display, replace respectively top up tank if necessary.

Replace nozzle.

Check suction pipe, tighten unions

Vent suction pipes at pump pressure gauge connection.

Check and possibly clean mixing device.

Check and possibly correct burner setting.

Burner works,fl ame monitoring does not start.

Flame monitor clogged or defect.

Defect cable connection between fl ame monitor and automatic fi ring unit.

Firing sequence controller damaged.

Check resp. clean fl ame monitor. Measure sensor current.

Replace cable connection resp. fl ame monitor.

Replace fi ring sequence controller

Injection or burning continues after burner has shut down

Oil pipes inadequately vented.

Leak in oil suction pipe with intake of air.

Solenoid does not close properly.

Remedy by venting

Check all sealing points in the oil piping.

Solenoid defect.

Page 14: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

7. Technical documentation

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance14

7.1 Basic settings table and adjustment dimensions

Burner typeSuitable for boiler output

kW

Nozzle / Make / TypeUSG

Size Amm

Size B

mm

Size D

mm

Air pressure Oil pressureAir intake

nozzle

Total weight

kgSt. 1mbar

St. 2mbar

St. 1bar

St. 2bar

SL 400/2 260 - 290290 - 315

Steinen 4,50 60°SSteinen 5,00 60°S

2121

6262

114114

4,05,0

7,58,5

1717

2727

2,23,5

4545

SL 410/2

315 - 360360 - 420420 - 500450 - 520

Steinen 5,50 60°SSteinen 6,50 60°SSteinen 7,50 60°SSteinen 8,00 60°S

20202020

125120115110

130130130130

6,88,08,68,8

11,512,513,513,5

13151414

20232224

46

7,57,5

45454545

SL 420/2 520 - 580570 - 630600 - 670

Steinen 9,00 60°SSteinen 10,00 60°SSteinen 11,00 60°S

202020

1009590

134134134

8,88,09,0

14,013,013,0

141314

262523

7,57,57,5

454545

Page 15: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

7. Technical Dokumentation

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/215

7.2 Electrical connection

7.4 Working fi eld

The diagrams shown here indicate approximately the output range of the various sizes as a function of the com-bustion chamber resistance during operation. The curves represent maximum values and correspond to the type sample testing to DIN 4787.

The starting-up resistance of the boiler is of decisive importance for the actually possible burner output.

Burner type Motor-voltage

Motor-output Connection value

SL 400/2 230 V WS 50 Hz 0,45 kW 0,7 kW, ca. 3,2 A

SL 410/2 400 V DS 50 Hz 1,1 kW 1,4 kW, ca. 3,0 A

SL 420/2 400 V DS 50 Hz 1,1 kW 1,4 kW, ca. 3,0 A

Fig. 14: 7.3 Boiler connection

D1 D2 M

150 180 − 205 10

Page 16: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

7. Technical documentation

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance16

7.5 Defi ning the oil feed pipe

H = difference in height between suction point (foot valve) and burner pump

Positive H value = higher tank

Negative H value = lower tank

L = suction length (2-pipe installation) for pipe inner diameter

di = 8 to di = 16 – indicative values (including 4 elbows, fi lter and non-return valve)

SL 400/2 - SL 410/2 - SL420/2

H (m)

L (m)

di=8 di=104,0 53 100 3,0 47 100 2,0 41 100 1,0 34 88 0,5 31 79 0,0 27 71

-0,5 24 62 -1,0 20 54 -2,0 13 37 -3,0 6 20

Page 17: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

7. Technical documentation

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance17

7.6 Circuit diagram SL 400/2

Indication Pos. Observe local and VDE-regulations.

Connections to earth potential being executed carefully.

DKW 972 with MZ 770 for warm air heater

On-off switch b2Safety thermostat b3On-off thermostat 1 b4On-off thermostat 2 b5Photo resistor f1Motor with condenser m1Ignition transformer m2Servomotor m3Solenoid valve 1 s1Solenoid valve 2 s2Control device u1

Fig. 15:

Page 18: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

7. Technical documentation

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/218

7.7 Circuit diagram SL 410/2 - 420/2

Fig. 16:

Page 19: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

7. Technical documentation

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/220

7.8 Explosion drawing SL 400/2

SL4

00/2

Fig. 18:

Page 20: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

7.9 Key for explosion drawing SL 400/2

7. Technical documentation

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance21

Pos. SL 400/2 Designation (part designation) Part number

1 1 Burner casing2 1 Housing cover3 1 Burner pipe DZ 3.0/GZ 3.06 1 Baffl e plate with electrode block

11 1 Nozzle 4,50/60 Grd S11 Nozzle 5,00/60 Grd S12 1 Nozzle holder with pipe and scale14 1 Ignition electrode block15 2 Ignition cable16 1 Photo resistance. FZ 711S, white16 1 Photo resistance MZ 770 S17 1 Servomotor LKS160-5218 1 Lever for air damper, complete19 1 Flange cover20 1 Ignition transformer ZM 20/12-71721 1 Automatic oil fi ring unit TF 802.221 1 Automatic oil fi ring unit TF 802.121 1 Automatic oil fi ring unit TF 832.322 1 Console for automatic oil fi ring unit23 1 Spring for air damper24 1 Air throttle axis DZ 325 1 Air damper27 1 Silencer complete30 1 Counter plug (boiler)32 1 Plug part, green, complete33 1 Union Rp 1/8, zyl., 6 mm34 1 Oil pipe complete DZ 335 1 Oil pump AT 2/6536 2 Double nipple, Rp ¼ x 3/837 2 Silver hose NW 8x1500,R 3/839 1 Coupling piece 1-surface40 1 E-motor with condenser, 450 W41 1 Fan wheel, 220 x 82 mm42 1 Air intake nozzle43 1 Burner hood44 2 Safety cover45 2 Plug pin48 1 Burner fastening set49 1 Burner head seal50 1 Burner head seal53 1 Shim lining for oil pump59 1 Solenoid valve, Suntec for pump AS 47 / AT2-3 (1.St.)59 1 Solenoid valve coil, Suntec for pump AS 4760 4 Hexagon nut, M8

Page 21: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

SL 4

10/2

SL 4

20/2

7.10 Explosion drawing SL 410/2 - SL 420/2

7. Technical documentation

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance22

Fig. 19:

Page 22: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

7. Technical documentation

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/223

7.11 Key for explosion drawing SL 410/2 - SL 420/2

Pos. SL 410/2 SL 420/2 Designation (part designation) Part number

1 1 1 Burner casing2 1 1 Housing cover3 1 1 Burner pipe with head6 1 1 Baffl e plate with electrode block6 Baffl e plate D=134, DZ3.2 -3240

10 Air conductance device 15Grd11 1 Nozzle 5,50/60 Grd S11 1 Nozzle 6,50/60 Grd S11 1 Nozzle 7,50/60 Grd S11 1 Nozzle 8,00/60 Grd S11 1 Nozzle 9,00/60 Grd S11 1 Nozzle 10,00/60 Grd S11 1 Nozzle 11,00/60 Grd S12 1 1 Nozzle holder with pipe and fl ange14 1 1 Ignition electrode block15 2 2 Ignition cable16 1 1 Photo resistance. FZ 711S, white17 1 1 Servomotor LKS160-5218 1 1 Lever for air damper, complete20 1 1 Ignition transformer ZM 20/12-71721 1 1 Automatic oil fi ring unit TMO 720-422 1 1 Console for automatic oil fi ring unit23 1 1 Spring for air damper24 1 1 Air throttle axis DZ 325 Air damper25 1 1 Air damper27 Silencer27 1 1 Silencer complete29 1 1 Lining part, brown/black, complete30 1 1 Counter plug (boiler)31 1 1 Lining part, green, complete32 1 1 Plug part, green, complete33 1 1 Union Rp 1/8, zyl., 6 mm34 1 1 Oil pipe complete DZ 335 1 1 Oil pump AT 2/75C36 2 2 Double nipple, Rp ¼ x 3/837 2 2 Silver hose NW 8x1500,R 3/838 2 2 Sealing rig 13 x 18; Cu39 1 1 Coupling piece 1-surface40 1 1 E-Motor, 1,1 kW41 1 1 Fan wheel, 220 x 82 mm42 1 1 Air intake nozzle43 Burner hood with push button43 Spacer for hood DZ 3

Page 23: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

Pos. SL 410/2 SL 420/2 Designation (part designation) Part number

43 Push button43 1 1 Burner hood44 2 2 Safety cover45 2 2 Plug pin48 1 1 Burner fastening set49 Burner head seal49 1 1 Burner head seal50 Burner head50 1 1 Burner head seal53 1 1 Shim lining for oil pump55 1 1 Power contactor 3TF2001-OAL255 1 1 Power contactor 3RT1016-1AP02 [ab BJ 2003]56 1 1 Bimetal relay 3UA7021-1E57 1 1 Lining part, black, complete58 1 1 Connector part, black, complete59 1 1 Solenoid valve, Suntec for pump AS 47 / AT2-3 (1.St.)59 1 1 Solenoid valve coil, Suntec for pump AS 4761 1 1 Solenoid valve SV 01 62 4 4 Threaded pin, M6x2563 4 4 Hexagon nut, M8

7. Technical documentation

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance24

Page 24: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

7.12 Burner dimensions

7. Technical documentation

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance25

Fig. 20:

Burner type

Dimension L1

approx.

Dimension L2

approx.

Dimension L3

approx.

Dimension D1 ø

Dimension D2 ø

Dimension H1

Dimension H2

Dimension B

SL 400/2SL 410/2SL 420/2

200265265

130130130

830850850

140140140

140175175

490490490

380380380

386386386

Page 25: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

8. Guarantee

Installation Operation Maintenance SL 400/2, SL 410/2, SL 420/226

8.1 Guarantee

The burner by Intercal functions perfectly when installed and operated correctly and when using fuel oil EL as per DIN 51 603, Part 1.

The guarantee is valid for 24 months after initial Operation but maximum 27 months after the date of dispatch and is restricted to the replacement of defect parts.

For details please consult the burner card.

8.2 Oil tank and oil pipes

When fi lling the tank, switch the burner off and leave off subsequently for 3 hours so that suspended particles can settle.

Defl agration can be caused by the formation of air bubbles as a result of leaky oil pipes and an empty tank.

Do not tolerate any oil leaks!Fire risk!

8.3 Spare parts

Only use original spare parts when replacing parts. Some components, e.g. fl ame monitor, oil pump, pre-heater, are specially designed and manufactured these burners.

Please always state the burner number when ordering spare parts.

All dimensions in mm.Subject to technical modifi cations and changes in components.

Page 26: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

Manufacturer‘s certifi cate

SL 400/2, SL 410/2, SL 420/2 Installation Operation Maintenance27

Wärmetechnik GmbH ▫ Im Seelenkamp 30 ▫ D-32791 Lage Telefon 0049 (0)5232 6002-0 ▫ Fax 0049 (0)5232 6002-18 ▫ [email protected] ▫ www.intercal.de Umsatzsteuer Ident-Nummer (USt-Id. Nr.): DE 811155318 ▫ Steuer-Nummer: 43 801 86006 Wärmetechnik

Herstellerbescheinigung (§ 7 (2) 1.BImSchV) Lage, 10.01.2008

Die Firma Intercal Wärmetechnik GmbH bescheinigt hiermit, dass der nachstehend aufgeführte Öl-/Gas-Spezialheizkessel

Produkt Ölbrenner Handelsbezeichnung Leichtöl- Druckzerstäuber Typ / Baumuster-Nr. SL400/2 - SL410/2 - SL420/2 / 5G852/02 (MHG Heiztechnik DZ 3.0, DZ 3.1, DZ 3.2) Prüfnormen DIN EN 267 Prüfstelle TÜV Hannover / Sachen-Anhalt e.V.

Diese Produkte erfüllen die Anforderungen der aufgeführten Richtlinien und Normen und stimmen mit dem bei der obigen Prüfstelle geprüften Baumuster überein. Mit dieser Erklärung ist jedoch keine Zusicherung von Eigenschaften verbunden.

Außerdem werden mit diesen Brennern ab der Leistung 120 kW die Anforderungen der 1.BImSchV erfüllt.

Die oben bezeichneten Ölbrenner sind ausschließlich zum Einbau in den Kessel bestimmt, die ebenfalls nach entsprechnden Richtlinien und Normen zugelassen sind.

Von dem Anlagenersteller ist zu gewährleisten, dass alle für das Zusammenwirken von Anlagenteilen gültigen Vorschriften beachtet werden.

M. Niedermayer i. A. S. RaaschGeschäftsführer Technik

Konformitätserklärung Lage, 10.01.2008

Die Firma Intercal Wärmetechnik GmbH bescheinigt hiermit, dass die nachstehend aufgeführten Ölbrenner:

Produkt Ölbrenner Handelsbezeichnung Leichtöl- Druckzerstäuber Typ SL400/2 - SL410/2 - SL420/2 unter Berücksichtigung folgender Normen und Richtlinien hergestellt wurde:

Niederspannungsrichtlinie 73/23 EWG - 01.1973 EMV - Richtlinie 89/337 EWG - 05.1989

Maschienenrichtlinie 98/37/EG - 22.06.1998 unter Bezug auf die Ölbrenner-Norm DIN EN 267

M. Niedermayer i. A. S. RaaschGeschäftsführer Technik

Manufacturer‘s certifi cate

Page 27: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,
Page 28: Light oil pressure jet burner SL 400/2, SL 410/2, SL 420/2 · SL 400/2, SL 410/2, SL 420/2 Fuel oil EL as per DIN 51 603, part 1 Installation Operation Maintenance ... DIN 51603,

Intercal Wärmetechnik GmbHIm Seelenkamp 30D-32791 LageTel.: +49 (0)5232-60 02-0Fax: +49 (0)5232-60 [email protected]ärmetechnik 01

/ 20

09 I

nsta

llatio

n O

pera

tion

Mai

nten

ance

SL4

00/2

, SL4

10/2

, SL4

20/2

-G

ER

-

subj

ect t

o te

chni

cal m

odifi

catio

ns a

nd fa

lsiti

es