Leakage Ratings Through Walls, Dampers, Doors,

Firestops and Joints

Richard N. Walke

Underwriters Laboratories Inc.

Page 3: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc

Topics for Discussion• Leakage Ratings for Walls,

Dampers, Doors, Firestops and Joint Systems

• Recent NFPA Code Proposals Relating to Smoke Leakage

Page 4: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc

Leakage Ratings

Page 5: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc

HVAC SmokeControl Methods

• Engineered Systems

• Static or Passive Systems

Page 6: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc

Walls – UL 263• Air Leakage Assumed to be Smoke

Tight• Standard does not Include

Leakage Ratings

Page 7: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc

Dampers – UL 555S• Air Leakage Through Interior of

Damper• Class I, II and III Performance

Levels at Elevated Temperatures• Codes focus on Class II

Performance at 250 F

Page 8: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc

Doors – UL 1784• Leakage Determined at 0.1, 0.2

and 0.3 in. WC (25, 50 and 75 Pa)• Tested at Ambient and 400 F• Results Published in cfm per sq ft

of Door Opening

Page 9: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc

Firestops – UL 1479• Leakage Determined at 0.3 in. WC

(75 Pa)• Tested at Ambient and 400 F• Results Published in cfm per sq ft

of Opening

Page 10: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc

Joints – UL 2079• Leakage Determined at 0.3 in. WC

(75 Pa)• Tested at Ambient and 400 F• Results Published in cfm per lin ft

of Opening

Page 11: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc

NFPA Code Changes

Page 12: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc

Proposed Leakage Ratings

• Requirements Covers Smoke Barriers Only

• Cumulative Leakage Limited to 0.75 cfm per sq ft of Wall for all Dampers, Doors, Through-Penetration Firestops and Joints

Page 13: Leakage Ratings Through Walls, Dampers, Doors, Firestops and Joints Richard N. Walke Underwriters Laboratories Inc