lead acid battery maintenance and testing · battery replacement criteria Ø failure to hold a...
TRANSCRIPT
![Page 1: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/1.jpg)
1
Lead Acid Battery Maintenance and Testing
![Page 2: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/2.jpg)
2
Moderator Ron Spataro AVO Training Institute Marketing Manager
![Page 3: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/3.jpg)
3
Q&A n Send us your
questions and comments during the presentation
![Page 4: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/4.jpg)
4
Today’s Presenter: Rod Van Wart AVO Training Institute, Senior Battery Instructor and Curriculum Advisor
![Page 5: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/5.jpg)
5
Why Batteries are Needed
Ø Ensure that critical electrical equipment is available and is backed up
• Generating stations and substations for protection and utility control • Telephone, hospital (for life support), & industry • Computer backup, UPS, Power Quality
![Page 6: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/6.jpg)
6
Why Batteries are Needed Ø Prevent unexpected failures Ø Electric generating stations and substations for protection and
control of switches/breakers and relays Ø Telephone companies to support phone service Ø Back up of critical power dependant equipment (life support
systems, business information systems, data centers) Ø Industrial applications for protection and control
Failure is not an Option
![Page 7: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/7.jpg)
7
Why Batteries are Needed Ø To ensure power availability Ø Steady state power is available in case of utility anomalies Ø To aid in mitigating unexpected sags & surges on the
customer service side
![Page 8: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/8.jpg)
8
Two Reasons
Ø To Protect and Support • Critical Equipment & Systems
Ø To Ensure the Safety of Revenue Streams • Due to loss of prime power source
![Page 9: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/9.jpg)
9
Three Questions
Ø What is the capacity and condition of the battery now? Ø 2. When will it need to be replaced? Ø 3. What can be done to extend its life?
![Page 10: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/10.jpg)
10
Battery Types
Ø Lead Acid – Flooded (wet) • Lead Calcium / Lead Antimony • Selenium (3% Antimony)
Ø Valve Regulated • Absorbed Glass Matte • Gel
![Page 11: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/11.jpg)
11
Maintenance Philosophies
Ø Replace batteries if and when they fail Ø Replace after a predetermined time Ø Engage in a recommended maintenance and testing program
![Page 12: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/12.jpg)
12
IEEE Standards
Ø IEEE 450 – Recommended Practice for Maintenance, Testing and Replacement of Vented Lead Acid Batteries for Stationary Applications
Ø IEEE 1188 - Recommended Practice for Maintenance, Testing, & Replacement of Valve-Regulated Lead Acid Batteries for Stationary Applications
![Page 13: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/13.jpg)
13
IEEE Recommended Maintenance Periodicities
VLA VRLAMonthly Quarterly Annually Monthly Quarterly Bi-annual Annually
Total system voltage X XCharger output current, voltage X XAmbient temp. ventilation X XVisual inspection X XElectrolyte levels XPilot cell voltage, Specific Gravity XSpecific gravity all cells XIndividual cell voltage X XIndividual cell temperature 10% XCell impedance readings XIntercell connector resistance X X (UPS) X (other)Detailed internal visual inspection XAC ripple current, voltage X
![Page 14: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/14.jpg)
14
AGM vs. Gel
VRLA batteries follow two main designs: • AGM: liquid electrolyte absorbed in glass mat separators, or
• Gel batteries contain a gelled electrolyte which is "Thixotropic". This Thixotropic gelled electrolyte contains sulfuric acid, fumed silica, pure demineralized and deionized water, and a phosphoric acid. The electrolyte in Gel batteries does not flow like a normal liquid; it has the consistency and look of petroleum jelly.
![Page 15: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/15.jpg)
15
Monthly Visual Checks - Failures
Ø Category 1 Failures are considered critical and must be dealt with immediately
Ø Category 2 Failures are considered non-critical but will need closer observation and may reach Cat 1 status in a short time
Ø See Annex D of IEEE 450 D.5
![Page 16: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/16.jpg)
16
VLA Failure Modes
Ø Plate sulfation Ø Positive grid corrosion Ø Sediment (plate shedding) build-up Ø Top lead corrosion Ø Hard shorts (paste lumps)
![Page 17: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/17.jpg)
17
Plate Sulfation Ø Plate sulfation
• Sloughing off of active material from the plates • Causes electrical path problems • Easily detected by impedance testing • Visual inspection may find traces
Ø Forms when • Charger voltage is not set high enough • Incomplete recharge after an outage
![Page 18: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/18.jpg)
18
Positive Grid Corrosion
Ø Lead alloy (plates) that convert to lead oxide over time • Lead oxide crystal is larger than the metal, it grows over time • Part of design, many data sheet give clearance at bottom of jar
over rated life time (20 years) • Growth can and does force off tops of battery
![Page 19: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/19.jpg)
19
Positive Grid Corrosion
Ø Other effects that cause growth • Excessive cycling • Excessive temperature • Over charging
Ø Maintenance and environmental conditions can increase or decrease risk of battery failure
![Page 20: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/20.jpg)
20
Positive Grid Growth
![Page 21: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/21.jpg)
21
Ohmic Testing • Impedance, Conductance &
Resistance • IEEE uses term ohmic • DC based on V=IR : AC based on V=IZ • As a battery ages it may corrode,
sulfate, dry-out or suffer a host of other effects based on maintenance, chemistry and usage. All of these effects cause a chemical change in the battery; which in turn causes a change in the batteries internal impedance / resistance.
• Ohmic testing measures the SOH.
![Page 22: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/22.jpg)
22
Sediment Buildup (shedding)
Ø Function of battery cycling Ø Sloughing off of active material from the plates, converts
it to white lead sulfate (plate sulfation) Ø Shedding is normal Ø Excessive shedding when added to positive grid growth
can cause shorts • May cause voltage drop
![Page 23: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/23.jpg)
23
Top Lead Corrosion
Ø Connection between plates and post • Difficult to detect, hidden by cover
• Corrosion can lead to heat buildup during high amp discharge
• Melt, crack, causing catastrophic failure when battery string drops off line
![Page 24: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/24.jpg)
24
VRLA Failure Modes
Ø Dry out (loss of compression) Ø Soft & hard shorts Ø Thermal run-away Ø Post leakage Ø Positive grid corrosion Ø Plate sulfation
![Page 25: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/25.jpg)
25
Dry-Out (Loss of Compression) Ø Dry-out is a phenomenon that occurs due to excessive heat,
over charging can cause elevated internal temperatures as well as high ambient (room) temperatures.
Ø At elevated internal temperatures, the sealed cells will vent through the PRV.
Ø When sufficient electrolyte is vented, the glass matte no longer is in contact with the plates, thereby increasing the internal impedance and reducing battery capacity.
![Page 26: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/26.jpg)
26
Ohmic Readings Rise
![Page 27: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/27.jpg)
27
Ø During deep discharge, specific gravity drops with corresponding voltage drop
Ø When SG gets to low, lead (from the plates) dissolves into the acid which is in the glass matte
Ø During recharge, lead comes out of solution forming threads of thin lead known as dendrites inside the matte
Soft Shorts (VRLA)
![Page 28: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/28.jpg)
28
Hard Shorts
Ø Hard shorts caused by: • Paste lumps pushing thru the matte and shorting out opposite
polarity plate
Ø This condition also reveals itself during ohmic testing with a severe decrease in impedance
![Page 29: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/29.jpg)
29
Changes in Impedance as a Result of Battery Capacity
![Page 30: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/30.jpg)
30
Thermal Run-Away
Ø Battery internal components melt down in a self sustaining reaction
Ø Two weeks to four months prediction time
Ø Impedance and float current increases
Ø Megger recommends quarterly impedance testing of VRLAs
![Page 31: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/31.jpg)
31
Thermal Run-Away
Ø To prevent, use temperature compensated chargers and properly vent battery room
• Charges reduce current as temperature increases • Heating is a function of the square of the component (I2R)
![Page 32: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/32.jpg)
32
No Temperature Compensation
![Page 33: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/33.jpg)
33
Post Leakage & Corrosion
![Page 34: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/34.jpg)
34
Determining Available Capacity
Ø Capacity testing or load testing • cost and time of battery out of service • recharge time • detrimental effect on battery life
![Page 35: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/35.jpg)
35
Capacity Testing Scenarios
Ø Acceptance Test: • A capacity test made on a new battery to determine if it meets
specifications or manufacturer’s ratings.
Ø Capacity Test: • A controlled constant-current or constant-power discharge of a
battery to a specified terminal voltage.
![Page 36: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/36.jpg)
36
Capacity Testing Scenarios
Ø Performance Test: • A constant-current or constant-power capacity test made on a
battery after it has been in service.
Ø Modified Performance Test: • A test, in the “as found” condition, of battery capacity and the
ability of the battery to satisfy the duty cycle.
![Page 37: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/37.jpg)
37
Battery Replacement Criteria
Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator for further investigation into the need for battery replacement
Ø Conducting a Load test will show what capacity if any is left in the battery
Ø After completion of a capacity test, the user should review the sizing criteria to determine if the remaining capacity is sufficient for the battery to perform its intended function.
![Page 38: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/38.jpg)
38
Battery Replacement Criteria
Ø The recommended practice is to replace the battery if its capacity as determined is below 80% of the manufacturer’s rating.
Ø This is typically 1.75 VPC, but may range from 1.67 to 1.82 VPC dependent upon manufacturer
![Page 39: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/39.jpg)
39
When Batteries Fail …
![Page 40: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/40.jpg)
40
Ø Proper maintenance is critical to battery life Ø Battery “health” is critical for many safety systems Ø Regular testing allows you to trend the battery Ø Decreases chance of battery bank failure Ø Load testing is critical for measuring capacity Ø Allows timely replacement Ø Follow manufacturers recommendations and IEEE Guidelines
Summary
![Page 41: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/41.jpg)
41
Battery Maintenance & Testing Course
Battery Maintenance & Testing 4 Days – 3.2 CEUs
Click for Course Catalog Download
www.avotraining.com
![Page 42: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/42.jpg)
42
RecommendedEquipment
BITE2/2P • Ohmic value • Voltage of each cell • Float voltage and current • Ripple current • Strap resistances • Battery continuity verification
BITE3 • Ohmic value • Voltage of each cell • Float voltage and current • Ripple current • Strap resistances
PowerDB Software • Default & customized test forms • Database • Trending • Asset organization • Reporting capabilities • Compliance scheduler
TORKEL900 • Performance test • Modified performance test • Capacity testing • Overall battery voltage logger
![Page 43: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/43.jpg)
43
Join Us For Our Next Webinar
Ø Title: “Substations: Looking from outside... in.”
Ø Tuesday, March 20, 2018 at 1 PM CST
Ø Register here: Ø https://attendee.gotowebinar.com/register/879540421804228355
![Page 44: Lead Acid Battery Maintenance and Testing · Battery Replacement Criteria Ø Failure to hold a charge, as shown by cell voltage and specific-gravity measurements, is a good indicator](https://reader030.vdocuments.us/reader030/viewer/2022040804/5e4102b2741d4e5b4f719acd/html5/thumbnails/44.jpg)
44
Questions? After more than 50 years, AVO Training remains a global leader in safety and maintenance training for the electrical industry. We deliver an engaging, hands-on experience for our clients in a professional, real-world environment. We strive to provide industry relevant courses in a practical and flexible learning environment through an ongoing commitment to quality service, integrity, instruction, and client satisfaction. Our goal is to convey practical job skills and career development for our clients and students by saving lives through a world-class learning experience.