lamtec flame monitoring
TRANSCRIPT
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
LAMTECLAMTEC
Flame MonitoringFlame Monitoring
Flame monitoring device F152
1
Flame scanner FFS07 (Ex) Flame scanner FFS08
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
LAMTEC Flame monitoring
Standards and Directives (under approval):
• DIN EN 298:2012
• DIN EN 230:2005
• DIN EN 60730-2-5:2011
• DIN EN 50156:2005, section 10.5
• DIN EN 746-2:2011 (Safety requirements for industrial thermoprocessing equipment)
• 97/23/EG (Pressure equipment directive)
• 2009/142/EG (Gas equipment directive)
• 2006/95/EG (Low voltage directive)
• 2004/108/EG (EMV-directive)
• DIN EN 61508:2011 Ed.2 Teil 2 (Requirements SIL 2)
• DIN EN 60730-1:2012
• DIN EN 60079-0:2012, -15:2011 (Explosive protection)
2
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Characteristics
› Plug-in module for DIN rail mounting
› Two- electronic channel system with self-monitoring for fail safe operation and supervision
› Suppression of strange light sources such as lamps, power frequency radiation sources or direct light, such as solar radiation
› Digital flame frequency evaluation in the range 10 to 200 Hz
› Status display by LED's
› Measuring output for intensity 0-20 mA
› UV and IR flame detectors of series FFS07 ... and FFS08...
3
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Areas of application / Selection criteria
Selection criteria for flame scanners
Sensor type Spectral range Application / fuel
FFS07 / 08 UV-1 260 ... 400 nm Oil, Gas
FFS07 / 08 UV-4 215 ... 360 nm Oil, Gas, (Specialty gases such as refinery and blast furnace gases)
FFS07 / 08 IR-1 1000 ... 2500 nm Oil, gas, firing with strong flue gas recirculation,
yellow colored waste gases without UV- radiation
4
Areas of application• Monitoring of burner flames without complicate selection tasks
• Single and multi-fuel burners in heating stations and process industry
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Indicators / Dimensions - F152
5
LED YE –Flammenintensität 100%
LED RT – Flame OFF
LED GN – Flame ON
LED YE – Flame intensity
LED YE – Flame intensity 100%
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Dimensions Flame Scanner FFS07
6
Flame scanner FFS07
Flame scanner FFS07 Ex
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Dimensions Flame Scanner FFS08
7
Flame scanner FFS08
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Sensitivity adjustments for scanner FFS07
8
X 3 X 5 X 6 X 4 X 2 X1
S1
S2
X9 X10
OFF ON OFF ON
M10
C13
V14
R25
V13
V11
V12
V15
S1S2
100%
75%
50%
25%21
ON
21
ON
21
ON
21
ON
21
ON
21
ON
21
ON
21
ON
Sensitivity
Factory adjustment for UV
Factory adjustment for IR
The adjustment is made to the switches S1 and S2, accessible after opening of the sensor housing
Measurable sensor signals:
• IR-scanner >10mV AC
• UV-scanner >25mV AC
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Sensitivity adjustments for scanner FFS08
9
S1S2
21
ON
21
ON
21
ON
21
ON
21
ON
21
ON
21
ON
21
ON
S1
S2
On
On
RA20 RA21
RB20
RB21
1
2
1
2
X1 X6 X3
min.
Sensitivity
min.
max.
The adjustment is made to the switches S1 and S2, accessible after opening of the sensor housing.
NOTICE!
The FFS08 UV scanners don’t have this sensitivity adjustment. The optimization is
carried out only with the optimum focus to the flame. For optimization is to be used
the measurable voltage output signal at a measuring instrument.
Measurable sensor signals:
• IR-scanner >10mV AC
• UV-scanner >25mV AC
Factory adjustment for IR50%
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Wiring Diagram
10
F152
FFS07 / 08
X15/2
X15/1 PK
X16/1 BK
X16/2 GN
X16/3 BU
X16/4 RD
X15/4 WH
X15/3 YE
- X14/3
X11/4
X11/2, 3
X11/1
+ X14/4
flame signal
status signal
0..20mA
N X12/2
L X12/4
power
X141 4
X151 4
X161 4
X11 4 1
X12 4 1
F152
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Ordering information for flame monitoring device F152
11
Type Product Order-no.
F152 Flame monitoring device 659G0501
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Ordering informations for flame scanner FFS07 (IR)
12
Type Spectral range Choice
FFS07 IR-1IR-spectral range 1.000 – 2.500 nm
3m cable without plug659D21-10 0 3 0
3m cable with plug 659D21-10 0 3 Ste
FFS07 IR-1 Ex 3m cable without plug 659D22-10 0 3 0
Holding devices acc. to product overview, publication DLT7660-12-bDE-002
Connection-/extension cable, length 3 m 1) 659 R 3112
Connection-/extension cable, length 5 m 1) 659 R 3115
Connection-/extension cable, length 10 m 1) 659 R 31141) Only for scanner variants FFS07 and FFS08 with plug
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Ordering informations for flame scanner FFS07 (UV)
13
Type Spectral range Choice
FFS07 UV-1UV-spectral range 260 – 400 nm
3m cable without plug659D21-01 0 3 0
3m cable with plug 659D21-01 0 3 Ste
FFS07 UV-1 Ex 3m cable without plug 659D22-01 0 3 0
FFS07 UV-4UV-spectral range 215 – 360 nm
3m cable with plug659D21-04 0 3 0
3m cable with plug 659D21-04 0 3 Ste
FFS07 UV-4 Ex 3m cable without plug 659D22-04 0 3 0
Holding devices acc. to product overview, publication DLT7660-12-bDE-002
Connection-/extension cable, length 3 m 1) 659 R 3112
Connection-/extension cable, length 5 m 1) 659 R 3115
Connection-/extension cable, length 10 m 1) 659 R 31141) Only for scanner variants FFS07 and FFS08 with plug
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Ordering informations for flame scanner FFS08
14
659D31-04 0 2 0UV-spectral range 215 – 360 nm
2m cable without plugFFS08 UV-4
659D31-04 0 2 Ste2m cable with plug
659D31-01 0 2 0UV-spectral range 260 – 400 nm
2m cable without plugFFS08 UV-1
659D31-01 0 2 Ste2m cable with plug
Type Spectral range Choice
FFS08 IR-1IR-spectral range 1.000 – 2.500 nm
2m cable without plug659D31-10 0 2 0
2m cable with plug 659D31-10 0 2 Ste
Holding devices acc. to product overview, publication DLT7660-12-bDE-002
Connection-/extension cable, length 3 m 1) 659 R 3112
Connection-/extension cable, length 5 m 1) 659 R 3115
Connection-/extension cable, length 10 m 1) 659 R 3114
1) Only for scanner variants FFS07 and FFS08 with plug