industrial flame monitoring - cicsacicsa-maxon.com.mx/media/industrial-flame-monitoring.pdf ·...

34
Industrial Flame Monitoring Fuel Fired Process Safety Monitoring LAR TRAINING MAY 2015

Upload: others

Post on 29-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Industrial Flame Monitoring Fuel Fired Process Safety Monitoring

LAR TRAINING

MAY 2015

Page 2: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

How is IFM Used (Not Just as a Flame Switch!)

Page 3: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Typical Process Application for IFM

Page 4: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Functional Safety Application

SIF: A Safety Instrumented Function (SIF) is a safety function with a specified Safety Integrity Level (SIL) which is implemented by a SIS in order to achieve or

maintain a safe state.

Relation Between SIS, SIF, SIL

Page 5: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Used in Voting Architecture Applications

Page 6: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

IFM Portfolio

Page 7: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Where Used?

•Industries:

Pretoleum/Refineries

Petrochemical

Pulp and paper

Metals Processing

Page 8: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Process Applications

•Typical applications:

Industrialsprocess boilers

Black liquorrecovery

Co-generationboilers

Grate firedboilers

Cement or lime klins

Claus reactors(sulfur recovery)

Thermal oxidizers Gas turbines

Flare stacks

Page 9: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Viewing Head and Signal Processor CombinationsViewing Head and Signal Processor Combinations

Page 10: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Typical Flame Envelope

Page 11: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Light Spectrum (What is Visible?)

Page 12: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Viewing Head Sensors

•Infrared (IR) - Solid state sensor

•Ultraviolet (UV) – UVTron tuve

•Flare Stack model (UV) – UVTron tuve

•Dual IR/UV – Solid state + UVTron tuve

•Integrated IR/UV VH/SP – 2 Solid state + UVTron tube

Page 13: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

•Viewing Head Sensors Infrared (IR) - Solid state sensoro Peak response at 1,400nm in the light spectrum

Responds to IR radiation/flicker in the flame above (selectable):o 9Hz (U2)

o 16Hz (S55XB, S55XBE)

o 33Hz/155Hz (S70X/S80X)

Outout = Pulse stream of randomly spaced pulses whose averagerate is proporcional to the IR radiation/flicker frequency present in the flame

Think of: AC Voltage with a DC component

Sensors (Continued)

Page 14: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

•Viewing Head SensorsUltraviolet (UV) – UVTron tuveo Peak response at 210nm in the light spectrum

Outout = Pulse stream of randomly spaced pulses whose averagerate is proporcional to the UV radiation present in the flame

Think of: DC Voltage

Sensors (Continued)

Page 15: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

•Infrared (IR) - Solid state sensor IR Solid state sensoro Longer wavelenght discrimination

Measure flame strenght flickero Amplitude + modulations of the flame in the target zone

o High IR levels that are not characteristic of the flame are ignored

o 33Hz/155Hz (S70X/S80X)

Programmed + monitored via signal processor

Sensors (Continued)

Page 16: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

•Ultraviolet (UV) – UVTron tuveUV Tube sensor o Very short wavelenght discrimination

Measure UV portion generated by the flameo Amplitude + random UV Tube pulses/firings in the target zone

Programmed + monitored via signal processor

Sensors (Continued)

Page 17: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

•Dual IR/UV Viewing Heads Independent configuration for each sensor

Programmed + monitored via signal processor

Sensors (Continued)

Page 18: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

•Integrated IR and/or UV Viewing & Signal ProcessorFeatureso 24 Vdc input

o Touchscreen interface with scrolling menú structure

o 100% programable through interface

o 8 Files/flame profiles

o Hazardous location approvals

Sensors (Continued)

Page 19: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Sensors (Continued)

•Integrated IR/UV Viewing Head & Signal Processor

•The U2 has a unique touchscreen interface• Circular scroll finger “touch Wheel” menú structure (similar to the IPod

Page 20: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Sensors (Continued)

WATCHDOG III FLARE STACK MONITOR

IRIS MODELS P222 and S256B UV

Page 21: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Select Signal Processors

Page 22: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Flame Discrimination Adjustments

•Viewing Head HighlightsAdjustable FLAME ON and FLAME OFF settingso The “pull-in” and “drop-put” thresholds of the flame relay.

Adjustable UV and IR GAIN settingso Increase/decrease flame signal for flame discrimination + recognition

Multiple SOLID STATE high pass flicker frequency settingso Adjust filter based on the flicker frequency on the flame

o Provides good discrimination between flames and background

o Ingnore everything below

UV flare stack application specif model

Integrated IR/UV scanner and processor model

Page 23: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Example Processor Set-up Considerations

Page 24: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Example Processor Set-up Considerations

Page 25: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Example Processor Set-up Considerations

Page 26: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Scenerios that can be monitored

Page 27: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Viewing head mounting examples

Page 28: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Accessories

Page 29: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Get a Better View with Fiber Optics

Page 30: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Fiber Optic Considerations

Page 31: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

Fiber Optic Assembly

Page 32: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

GHE Series Ignitors

Page 33: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

GHE Series Ignitors

•Specifications: 1-7/8 (4.763) diameter/1-3 MMBTU/hr (~1-3 GJ/hr)

2-7/8 (7.303) diameter/2-10 MMBTU/hr (~2-10 GJ/hr)

• Components Burner mounting tube with flange, gas insert & gas/air flex hoses

Inner probe assembly with probe, igniter tip & junction box

Power pack (2,000Vdc, 12Joules)

Cable with canon plug

Page 34: Industrial Flame Monitoring - CICSAcicsa-maxon.com.mx/media/Industrial-Flame-Monitoring.pdf · Industrial Flame Monitoring Fuel Fired Process Safety Monitoring ... Relation Between

GHE General Dimensions