kx series power systems catalog - kohler powerkohlerpower.com.sg/common/pdfs/kx series brochure...

12
1 KX Series Power Systems Catalog 715 kVA - 3300 kVA, 50 HZ 700 kW - 3200 kW, 60 HZ

Upload: duongdien

Post on 11-Jun-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

1

KX SeriesPower Systems Catalog715 kVA - 3300 kVA, 50 HZ700 kW - 3200 kW, 60 HZ

Page 2: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

2

ToTal SySTem InTegraTIon. EvErything WorKS togEthEr.

Disclaimer: Information in this publication represents product data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability.

Reliability of power systems is critical. Your business depends on it. At Kohler, we build industrial power systems that are proven to work because total system integration is engineered in from the start. For more than 90 years, Kohler has earned a global reputation as a pure power expert — in large part to our strict quality standards. Our power systems are equipped with Kohler innovation, including generators, transfer switches, switchgear and controllers. Enduring the industry’s toughest testing process, including transient power testing, cooling sound and more, every part is built to work with the entire system and perform in the most demanding environments before they are shipped out. Our power systems are built for nearly every application, powering everything from gas stations to hotels and hospitals, as well as military operations and airports. So you can be rest assured that our products will work when you need them most.

DEpEnDablE poWEr anD pErformancEtriED, tEStED anD provEn to WorK.

The new KX-series generators offer total, reliable and continuous power with a higher load factor^ as well as competitive fuel consumption rates. Incorporating Kohler’s innovative technology, the KX range enables a seamless integration that allows versatile system configurations for optimal performance.

Today, Kohler provides integrated solutions to streamline the specifying process. Our industrial generators are diesel-fueled models — ranging from 5.5 kVA to 3,300 kVA @ 50 Hz (11 kW to 3200 kW @ 60 Hz) complete with electronic controls and automatic transfer switches. To help cater to unique installation environments, we also offer a range of accessories, including controls, silencers, enclosures, fuel tanks and block heaters.

^ 85% for standby rating; 75% for prime rating (70% for ISO standard).

Page 3: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

3

KohlEr SErvicE anD SupportthE hElp you nEED. any timE, anyWhErE.

Anybody can claim to offer an unrivaled level of support, but it is another thing to deliver on that promise. Today, Kohler’s distribution network spans across multiple sales offices in countries throughout the Asia Pacific region.

Unlike other generator manufacturers, Kohler certified distributors and dealers specialize in power. This means our service network can be called on for anything related to your generator and its

components.

With Kohler, you enjoy world-class service and support from a global service network.

Kohler Manufacturing – China

Kohler Manufacturing – India

Kohler Manufacturing – France

Kohler Manufacturing – Singapore

Kohler Headquarters/Manufacturing – U.S.

Page 4: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

4

KX880C KX1850C

TECHNICAL SPECIFICATIONS

50 Hz Specifications400-230 V

60 Hz Specifications480-277 V

General Specifications

Generator Set Model (1)

kVACos 0.8 Cons

3/4 L/h

Generator Set Model (2)

kWeISO 8528* Cons

3/4 L/h

Engine Alternator Compact Version(5)

PRP(3)

ESP(4)

PRP(3)

ESP(4) Engine type cyl

Bore(mm)

Stroke(mm)

Cyl(L)

TypeDimensionsLxWxH, m

Weight(6)

(kg)

KX715C 650 715 109 - - - - 12V2000G25 12V 130 150 23.9 491S4 3.97x1.63x1.94 4989

KX800C 727 800 113 KX700UC2 636 700 131 12V2000G65R/45 12V 130 150 23.9 491M6 3.97x1.85x2.1 5262

KX880C 800 880 131 KX800UC2 727 800 148 12V2000G65/85 12V 130 150 23.9 491L9A 3.97x1.63x1.96 5474

KX1000 C 910 1001 154 KX900UC2 818 900 168 16V2000G25/45 16V 130 150 31.8 491L10 4.37x1.84x2.19 6118

KX1100C 1000 1100 169 KX1000UC2 909 1000 184 16V2000G65/85 16V 130 150 31.8 491L11 4.37x1.84x2.19 6588

KX1250C 1136 1250 192 KX1200UC2 1091 1200 217 18V2000G65/85 18V 130 150 35.8 502M6 4.45x2.21x2.19 7383

KX1400C 1272 1400 209 - - - - 12V4000G21 12V 165 190 48.75 502L7 3.6x1.88x2.16 9778

KX1540C 1400 1540 226 - - - - 12V4000G23R1 12V 170 210 57.2 502L8 4.00x1.88x2.16 10640

KX1650C 1500 1650 251 - - - - 12V4000G23R2 12V 170 210 57.2 502VL10 4.16x1.88x2.16 10820

KX1850C 1663 1830 266 KX1600UC2 1400 1600 282 12V4000G23/43 12V 170 210 57.2 512S55 4.10x1.87x2.16 11405

KX2000C 1818 2000 298 KX1750UC2 1591 1750 319 12V4000G63/83 12V 170 210 57.2 512S55 4.10x1.87x2.16 11405

KX2200C 2000 2200 336 KX2000UC2 1818 2000 377 16V4000G23/43 16V 170 210 76.3 512M60 4.62x1.87x2.16 13280

KX2500C 2272 2500 369 KX230UC2 2091 2300 422 16V4000G63/83 16V 170 210 76.3 512VL90 4.81x1.87x2.16 14235

KX2800C 2545 2800 409 KX2500UC2 2272 2500 471 20V4000G23/43 20V 170 210 95.4 531M80 5.73x2.25x2.44 17290

KX3100C 2818 3100 450 KX2750C2 2500 2750 516 20V4000G63/83 20V 170 210 95.4 531M80 5.73x2.55x2.44 18365

KX3300C 3000 3300 481 - - - - 20V4000G63L 20V 170 210 95.4 54M75 5.73x2.25x2.44 18685

- - - - KX3200UC2 2800 3200 557 20V4000G83L 20V 170 210 95.4 54M9 5.60x2.25x2.44 19241

(1) Also available in the following voltages: 415/240 V - 380/220 V - 240/120 V - 220/110 V

(2) Also available in the following voltages: 440/254 V

(3) PRP: main power available continuously under variable load for an unlimited number of hours annually, in accordance with ISO 8528-1

(4) ESP: Emergency Standby Power available for supplying emergency power in variable load applications in accordance with ISO 8528-1, no overload available for this service.

(5) The dimensions and weights apply to a generator set specified in the price list, without options

(6) Dry weight - without fuel

* ISO 8528: powers specified in compliance with the legislation in force

** TA LUFT certification is given for PRP

emISSIonS oPTImIzaTIon 50-60 Hz

Page 5: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

5

KX715 KX1750U

TECHNICAL SPECIFICATIONS

50 Hz Specifications400-230 V

60 Hz Specifications480-277 V

General Specifications

Generator Set Model (1)

kVACos 0.8

Cons 3/4 L/h

Generator Set Model (2)

kWeISO 8528*

Cons 3/4 L/h

Engine Alternator Compact Version(5)

PRP (3)

ESP(4)

PRP (3)

ESP(4) Engine Type cyl

Bore(mm)

Stroke(mm)

Cyl(L)

TypeDimensionsLxWxH, m

Weight(6)

(kg)

KX715 650 715 104 - - - - 12V2000G25 12V 130 150 23.9 491S4 3.98x1.63x1.95 4989

KX800 727 800 111 - - - - 12V2000G65R 12V 130 150 23.9 491M6 3.97x1.85x2.1 5262

KX880 800 880 123 - - - - 12V2000G65 12V 130 150 23.9 491L9A 3.98x1.63x1.95 5474

KX1000 910 1001 140 - - - - 16V2000G65 16V 130 150 31.8 491L10 4.33x1.84x2.19 6118

KX1100 1000 1100 152 - - - - 16V2000G65 16V 130 150 31.8 491L11 4.37x1.84x2.20 6588

KX1250 1136 1250 177 - - - - 18V2000G65 18V 130 150 35.8 502M6 4.45x2.21x2.20 7383

KX1400 1272 1400 195 - - - - 12V4000G21 12V 165 190 48.75 502L7 3.6x1.88x2.16 9778

KX1540 1400 1540 210 - - - - 12V4000G23R1 12V 170 210 57.5 502L8 4.00x1.88x2.16 10640

KX1650 1500 1650 231 - - - - 12V4000G23R2/43 12V 170 210 57.2 502VL10 4.16x1.88x2.16 10920

KX1850 1663 1830 241 X1600U 1400 1600 265 12V4000G23/43 12V 170 210 57.2 512S55 4.10x1.87x2.16 11405

KX2000 1818 2000 266 X1750U 1591 1750 301 12V4000G63/83 12V 170 210 57.2 512S55 4.10x1.87x2.16 11405

KX2200 2000 2200 306 X2000U 1818 2000 358 16V4000G23/43 16V 170 210 76.3 512M60 4.62x1.87x2.16 13280

KX2500 2272 2500 331 X2300U 2091 2300 398 16V4000G63/83 16V 170 210 76.3 512VL90 4.81x1.87x2.16 14235

KX2800 2545 2800 386 X2500U 2272 2500 452 20V4000G23/43 20V 170 210 95.4 531M80 5.73x2.25x2.44 17290

KX3100 2818 3100 420 X2750U 2500 2750 487 20V4000G63/83 20V 170 210 95.4 531M80 5.73x2.25x2.44 18365

KX3300 3000 3300 445 - - - - 20V4000G63L 20V 170 210 95.4 54M75 5.73x2.25x2.44 18685

- - - - X3200U 2800 3200 530 20V4000G83L 20V 170 210 95.4 54M9 5.73x2.25x2.44 18685

(1) Also available in the following voltages: 415/240 V - 380/220 V - 240/120 V - 220/110 V

(2) Also available in the following voltages: 440/254 V

(3) PRP: main power available continuously under variable load for an unlimited number of hours annually, in accordance with ISO 8528-1

(4) ESP: Emergency Standby Power available for supplying emergency power in variable load applications in accordance with ISO 8528-1, no overload available for this service.

(5) The dimensions and weights apply to a generator set specified in the price list, without options

(6) Dry weight - without fuel

* ISO 8528: powers specified in compliance with the legislation in force

ConSumPTIon oPTImIzaTIon 50-60 Hz

Page 6: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

6

GENERATOR SET MODEL ENGINESILENT SUPER SILENT

87-92 dB(A)@1 m 85 - 88 dB(A)@1 m 79-87dB(A)@7 m 79-82 dB(A)@7 m

KX700UC2 to KX880C 12V2000 ISO 20 Si X CIR 20 SSi X

KX900UC2 to KX1100C 16V2000 ISO 20 Si X CIR 20 SSi X

KX1200UC2 to KX1250C 18V2000 ISO 20 Si X CIR 20 SSi X

KX1540C to KX2000C 12V4000 ISO 40 Si EUR 40 Si X EUR 40 SSi

KX2000UC2 to KX2500C 16V4000 ISO 40 Si EUR 40 Si X EUR 40 SSi

The CONTENERGY concept offers a range of soundproof containers featuring a multitude of options.

With the standard dimensions, CONTENERGY containers are easy to transport and, once on site, very simple to install: we would recommend that you install them outside the building on a concrete floor plate fitted with a tunnel for the cables and pipes.

Highly economical thanks to its cooling system, integrated sound traps and silencers, the CONTENERGY concept is completely self-contained, with a fuel capacity which enables it to operate immediately, without connection to an additional tank.

Kohler understands the many factors that have an influence on your equipment's operation. That is why our containers are designed to withstand harsh climate conditions. Whether your equipment needs to operate in extreme cold or tropical environments, let us know your requirements - we are sure to have the solution you're looking for.

Trailers compliant with international standards are also available, allowing you to transform your generating set into a mobile unit.

CONTENERGY ISOThe dimensions of CONTENERGY ISO containers comply with CSC certification. They have been specially designed to withstand significant loads and pressures during transport without incurring damage, and can be shipped without any special constraints. They are available in two sizes: 20 and 40 feet “High Cube”.

CONTENERGY CIRCIR type containers are specially designed with mobile and rental applications in mind. This highly compact model has a very low sound level and features an optional high volume tank, giving it up to 10 hours of autonomy.This model is available as a 20 feet “High Cube”

Our containers comply with all current standards and regulations governing these products, including:• ISO 668• NF90-005• NF ISO 1496-1 (ISO 8323)

The ConTenergy ConCePT 50-60 Hz

Page 7: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

7

Three control units are available in our 715 to 3300 kVA range: the M80, the KOHLER® DEC4000 control unit and the KERYS. Your control unit can be chosen according to your equipment type and perfectly adapted to suit your needs using the available options. This modularity is made even easier by the fact that each optional peripheral device (air cooler, daily service tank, oil top-up, etc.) has its own protection.

For power plants, separate control boxes may be used in place of the control units: Please contact us for more information.

The M80 control unit has a dual functionality. It can be used as a basic terminal block for connecting a control box and as an instrument panel with a direct read facility that provides a global view of your generator set's basic parameters.

Oil pressure

TachometerCoolant temperature

Emergency stop button

BASIC TERMINAL BLOCK M 80

MEASUREMENTS Tachometer (54 mm) X •

ENGINE PARAMETERS

Oil pressure gauge X •Coolant temperature indicator X •

Oil temperature indicator X O

CONTROLS Emergency stop • •

MISCELLANEOUSCE compliant • •

Customer connection terminal block • •

• As standard

X Not available

O Options

SPECIFICATIONS

M80

generaTor SeT ConTrolS 50-60 Hz

Page 8: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

8

The KOHLER® DEC4000 Control unit is straightforward and user-friendly, with the emphasis on communicationUSB connections, PC connections, control software and remote operation.

thE DEc4000 DESign offErS Simplicity With a rEDucED

numbEr of buttonS to opEratE your gEnErator SEt.

ADDITIONALFEATURESINCLUDE:

• Integrated maintenance monitoring programs (on-screen display of future maintenance operations)

• Built-in troubleshooting tool guides the user in the event of any alarms or faults

• Ability to send e-mail, SMS or Fax in the event of any alarms or faults as an option

• Optional tropical insulation of the circuit boards to provide protection in extremely humid conditions

• Compliance with various requirements or regulations (CE, UL, etc.)

• Screen with contrast adapted to all types of lighting

• Five languages featured, with numerous other optional languages

• Remote monitoring and field updates via USB connection

DEC4000

generaTor SeT ConTrolS 50-60 Hz

Page 9: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

9

KERYS

MMI (MAN-MACHINE INTERFACE)

The KERYS command and control unit has been designed to fulfil the specific requirements of professionals in terms of managing and monitoring generator sets. It therefore offers a wide range of functions.This control unit is fitted as standard to all generator sets designed to be used for coupling and is offered as an option across the rest of our range.The KERYS can be built into the central console, fitted directly on the generator set, or in a separate cabinet, to fulfil all the requirements for low and high output power plants.

AUTOMATIC CONTROLLER DEDICATED TO GENERATING SET APPLICATIONS•Choiceofarangeofbasicstandardconfigurations.•Additionallogicscanbeaddedwithoutanyexternal

tools.•Libraryoffunctionalmodules.

FAULT FINDING HELP•Validationofoperationbysimulation.•Displayofthestatusofvariables.•Breakdownguidewithkeywordsearch.

ASSISTANCE AND MAINTENANCE•Emailssentautomaticallyformaintenancerequests,

and for the appearance of alarms or faults.•Logofoperationscarriedout(maintenanceor

breakdown).

LOAD IMPACTSImprovement of generating set performance during application of a significant load.

GRAPHS AND ARCHIVING OF ELECTRICAL AND MECHANICAL PARAMETERSAdjustable sampling and configurable triggering criteria.

COMPLIANCE WITH INTERNATIONAL STANDARDSThe KERYS has undergone very stringent tests in independent laboratories (climatic tests, electromagnetic compatibility tests, vibration tests, etc.) It is CE compliant.

MAN-MACHINE INTERFACE MODULE The man-machine interface is available with a colour screen and a 7-inch touch panel. The MMI module is equipped with all the keys required to ensure the generator set can be controlled and the system configured, thanks to a screen navigator and an alphanumeric keypad.

Displayscreen:

7.4inchLCDTFTdisplay

Detailedcolourdisplay

Touch screen

Dimensions:154x86mm

Control keypad

withdisplayLEDs

Manual mode selection

Stop mode selectionAutomatic mode selection

Generating set circuit breaker open/

close

Test activation/deactivation

Grid circuit breaker

open/close

LEDtest

Horn off

Clear faults

Arrow keys

withoperationLEDs

Alphanumeric keypad

for setting parameters,

navigation and direct access

to screens

generaTor SeT ConTrolS 50-60 Hz

Page 10: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

10

gEnErator SEt automatic control•Singlegeneratorsetoraspartofpowerplant•OperationinHT(hightension)orLT(lowtension)•Normal/Emergencyoperation•Operationinpermanentortemporarygridcouplingwithout

cut-out: •Uponreturntogridpower •Duringpeakshaving •Duringtrialsortests•Invertedemergencyoperation•Powerproductionunit•Cogeneration

mEaSurEmEntS anD DiSplaySMechanical:•Temperatures•Pressuresandlevels depending on engine configuration

SafEty fEaturESMechanical: Electrical:•Speed •Currents•Alarms •Voltages•Enginesafety •Outputs•Specialcustomer •Frequency features •Microcut-outs

communication•Built-inwebserver•User-friendlyman-machineinterface•5 basic languages (French, English, Spanish, Portuguese,

German), one of which is interchangeable (please consult us)•EthernetPort•Dialoguewithallenginesequippedwithabuilt-inECU•RS485portforModbusRTU•RS232port•Option of PSTN communication (Public Switched Telephone

Network)

controlSMechanical:•Speed•Synchronisation•Coupling•Distributionorsettingof grid or generator set active power•Wattmetricprogramming

Inclusive of many more control parameters*

FUNCTIONS

*Formoredetailedinformation,refertotheKERYSdocumentationorcontactyourKohlersalesrepresentative.

1- Operation screen

3- Graph display

2- Synchronisation screen

4- Mechanical measurements screen

DiSplay ScrEEnS

Electrical:•Voltages•Currents•Frequencyandpower•Powerfactor•Outputs•Mechanicalandelectrical

metering.

Electrical:•Voltage•Voltageequalising•Distributionorsettingofgridor

generator set reactive power•Adjustmentofthegridor

generator set power factor (cos Phi).

generaTor SeT ConTrolS 50-60 Hz

Page 11: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

11

Rating 1250 A 1600 A 2000 A 2500 A 3600 A

With manual control on the front

Fixed3-polepowercircuitbreaker O O O O O

Fixed4-polepowercircuitbreaker O O O O O

Motorised control option (1)

With3or4-poleopencircuitbreakeronly O O O O O

Voltage 208-440 V • • • • •Auxiliary unit option (2) O O O O O

Powerconnectionbusbars • • • • •Remote control terminal block • • • • •

Protectionindex IP207 IP207 IP207 IP207 IP207

DIMENSIONS (without air cooler unit)

height (mm) 1260 1260 1260 1260 1260

width (mm) 683 683 683 683 683

depth (mm) 365 365 365 365 365

DIMENSIONS(with air cooler unit)

height (mm) 1664 1664 1664 1664 1664

width (mm) 683 683 683 683 683

depth (mm) 365 365 365 365 365

DIMENSIONS (with connection unit

on upper section)

height (mm) 1883 1883 1883 1883 1883

width (mm) 683 683 683 683 683

depth (mm) 365 365 365 365 365

(1) The motorised control includes a closure solenoid valve, a shunt trip coil and an AC motor(2) Theauxiliaryunitoptionismountedabovethemainunit.Itisusedforthepowerconnectionsofgeneratorsetauxiliaries,e.g.: - air cooler output - fuel pump unit output

• Standard O Option

1

2

2

SPECIFICATIONS aiprEach generator set may be supplied with a protection unit. This unit is mounted on the chassis with connection cables to the alternator. It is located on the right-hand side of the generator set.

Page 12: KX Series Power Systems Catalog - Kohler Powerkohlerpower.com.sg/common/pdfs/KX Series Brochure (715-3300kVA).pdfKX Series Power Systems Catalog ... The new KX-series generators offer

12

SPeC your job aT KohlerPower.Com.Sg

for more information call +65 6264 6422

or visit Kohlerpower.com.sg/industrial

printed in SingaporegSf-721 04/12

©2012 by Kohler co.

KohlEr® is a registered trademark of Kohler co.use of this material for reproduction on the internet and World Wide Web

is strictly prohibited without written permission from Kohler co.

North Asia

Kohler Power Systems - JapanSBS Hills-II, No. 534-10-3, Yoga, Setagaya-Ku Tokyo 158-0097 Japan Tel: +81 3 6807 1730 Fax: +81 3 3708 4377 Email: [email protected]

Kohler Power Systems - KoreaRoom 1201 Lg Twintel 2157-3 Samsung–Dong Gangnam-GuSeoul 135-090 Korea Tel: +82 2 563 9266 Fax: +82 2 563 9730 Email: [email protected]

S.E. Asia, Taiwan, Hong Kong & Bangladesh

Kohler Power Systems – Singapore (Regional HQ)7 Jurong Pier RoadSingapore 619159 Tel: +65 6264 6422 Fax: +65 6264 6455 Email: [email protected]

Australasia

Kohler Power Systems – AustraliaC/O P O Box 324, HighgateSouth Australia 5063 Tel: +61 439 338 166 Fax: +61 8 8338 6424 Email: [email protected]