kentrox modules version 2.91 release notes rev a may...

33
© Westell Technologies Part # 030-300762 Rev A WESTELL.COM RELEASE NOTES Kentrox Modules Version 2.91 Release Notes Rev A May 2016

Upload: ngocong

Post on 30-Jan-2018

349 views

Category:

Documents


8 download

TRANSCRIPT

Page 1: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Kentrox Modules

Version 2.91

Release Notes Rev A May 2016

© Westell Technologies

Part # 030-300762 Rev A

WESTELL.COM

RELEASE N

OTES

Page 2: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Copyright © 2016 by Westell Inc. All Rights Reserved. Westell, Kentrox® and Optima Management System® are registered trademarks of Westell. All other names are trademarks of their respective owners.

Information is correct at time of publication and is subject to change without notice. Contact Westell in Aurora, Illinois to verify current product information. Westell, Inc. is an Equal Opportunity/Affirmative Action employer.

Westell, Inc.750 North Commons Drive

Aurora, IL 60504 USAToll Free: (800) 377-8766

International: +1 (630) 375-4950 Fax: +1 (630) 375-4931

TABLE OF CONTENTSAffected Types Pages 2-3

New Supported Devices Pages 4-21

74996 -- Alpha AMPS24 UPS Page 475652 -- ZTE new SNMP MIB Page 1175773 -- Corning Core v7.2 Page 1776107 -- Huawei Rectifier Page 1776117 -- Commscope ION-E v1.6 Page 1976274 -- Commscope ION-M/B v7.20 Page 2176275 -- Commscope ION-U v1.7 Page 21

New Features Pages 22-24

76174 -- Module Eltek Smartpack monitoring enhanced to process traps Page 22SNMP Configuration Enhancements Page 2276304 -- Shared Discrete Description Configuration Page 2275939, 75938, 75937-- SPX NeType names updated Page 2276004 -- BatteryDAQ rectifier integration Page 2376074 -- UDiT Updates (components, fix actions) Page 24

Fixes Pages 25-26

Issue List Pages 26-27

Modules Version 2.91 Device Compatibility Information Pages 28-31

WESTELL.COM

Page 1

1-800-377-8766

Page 3: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Kentrox ModulesRelease Notes

Version 2.91May 2016

Affected Types

Vendor Models Configured Types Issue(s)

Alpha Technologies FXM AlphaAMPS24 74996

APC Galaxy 5000 APCBatteryString 76004

Basler DGC-2020 BaslerDGC20202Generator 75911

Battery DAQ 2402W2/M6 BatteryDAQBatteryMonitor 76004

Commscope

ION-E AndrewIONDAS 76117

ION M AndrewIONDAS 76274, 76071

ION-B AndrewIONDAS 76274, 76071

ION-U AndrewIONDAS 76275

Corning SC450 MobileAccessSC450DAS 75773

CSI UDiT CSIUDiTDASPanel 76074

Deep Sea Electronics

5210 DeepSea5210Generator 75911

5220 DeepSea5220Generator 75911

7320 DeepSea7320Generator 75911

Eltek SmartpackEltekSmartPackRectifier 75911

EltekBatteryString 76004

Emerson Rectifier Battery String EmersonBatteryString 76004

WESTELL.COM

1-800-377-8766

Page 2

Page 4: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Generac

EPanel GeneracEPanelGenerator 75911

EPanel with Annunciator GeneracEPanelGeneratorWithAnnunciator

75911

H100 GeneracH100GeneratorGeneracH100HTSGenerator

75911

HTS GeneracH100HTS 75911

Huawei 5210 Rectifier HuaweiSMURectifier 76107

Intelilite AMF25 InteliliteAMF25Generator 75911

Kentrox

Virtual Battery String VirtualBatteryString 76004

Analog Battery Sensor BatteryStringVoltageSensor 76004

Discrete Test ATS DiscreteControlledATS 76304

Discrete Power Detection DiscretePowerDetection 76304

Discrete Fule Quality DiscreteFuelQuality 76304

Discrete Generator DiscreteGenerator 76304

Shared Discrete Generator SharedDiscreteGenerator 76304

Discrete Controller Generator

DiscreteControlledGenerator 76304

Discrete IP Camera DiscreteIPCamera 76304

Lovato RGK60 LovatoRKG60Generator 75911

Marvair CommStat4 MarvairCS4HVACSystem 75948

Mobile Access SC450 (Corning Core) MobileAcccessSC450DAS 75960

SPX

Vanguard SPXVanguard 75939, 76179

36305 (LED) SPX36305 75938

903803 (Xenon/Eagle) SPX903803 75937

ZTE ZXDU68ZTEZxduRectifier 75652

ZTEBatteryString 76004

Vendor Models Configured Types Issue(s)

WESTELL.COM

Page 3

1-800-377-8766

Page 5: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

New Supported Devices

74996 -- Alpha AMPS24 UPS

The AMPS24 is a typical UPS system comprised of inverter modules, a battery, and rectifier modules. This system is monitored using SNMP polling. The application collects measurements on a regular poll cycle (default 60 seconds). The application also listens for trap notifications from the AMPS24 and reports alarms accordingly. Furthermore, the application will perform SNMP polls to determine alarm status at start-up, at a user's request (using "sync" control-action), and on a configurable regular cycle (default 24 hours).

Configuration Example

config site module tower

application UPSmonitoring

application Rectifiermonitoring

config site network-element-set UPS

instance ups1

display-name UPS1

exit

config site newtork-element ups1

type AlphaAMPS24

param deviceIP 10.48.154.12

Inventory Example

UPS

|-- Battery

|-- Inverters

| |-- Inverter 01

| |-- Inverter 02

WESTELL.COM

1-800-377-8766

Page 4

Page 6: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

| |-- Inverter 03

| |-- Inverter 04

| |-- Inverter 05

| |-- Inverter 06

| |-- Inverter 07

| |-- Inverter 08

| |-- Inverter 09

| |-- Inverter 10

| |-- Inverter 11

| |-- Inverter 12

\-- Rectifiers

Detailed Table of Information Provided by the AMPS24

Type Attribute Sample Content

Element: ups

Alarm Communication Communication Warning (Poll: Timeout)

Alarm Compatibility Minimum Supported Version “3.13” Received Version “3.12”

Alarm BatteryBreakerAlarm Battery Breaker Alarm

Alarm BypassmodeOn Bypass mode On

Alarm Digital4 Digital 4

Alarm InputBreakeroff Input Breaker off

Alarm TVSS TVSS

Alarm Digital7 Digital 7

Alarm Digital8 Digital 8

Alarm BatteryCurrentHigh Battery Current High

Alarm LoadCurrentHigh Load Current High

WESTELL.COM

Page 5

1-800-377-8766

Page 7: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Alarm ACMainsHigh AC Mains High

Alarm AC MainsLow AC Mains Low

Alarm HighVoltage1 High Voltage1

Alarm HighVoltage2 High Voltage 2

Alarm LowVoltage Low Voltage

Alarm LowBatteryVoltage Low Battery Voltage

Alarm MidpointMonitor1 Midpoint Monitor 1

Alarm MidpointMonitor2 Midpoint Monitor 2

Alarm MidpointMonitor3 Midpoint Monitor 3

Alarm MidpointMonitor4 Midpoint Monitor 4

Alarm MidpointMonitor5 Midpoint Monitor 5

Alarm TempSensor1Fail Temp Sensor 1 Fail

Alarm TempSensor2Fail Temp Sensor 2 Fail

Alarm TempSensor3Fail Temp Sensor 3 Fail

Alarm TempSensor4Fail Temp Sensor 4 Fail

Alarm TCSensorFail TC Sensor Fail

Alarm Custom1 Custom 1

Alarms Custom2 > Custom20 Custom 2 > Custom 20

Alarm RealTimeClockError Real Time Clock Error

Alarm InvalidDeviceFirmware Invalid Device Firmware

Alarm GroundFaultDetected Ground Fault Detected

Alarm ImproperControllerShutdown Improper Controller Shutdown

Alarm InvalidBatteryVoltage Invalid Battery Voltage

Alarm SystemMajor System Major

Alarm SystemMinor System Minor

Alarm LVD1 LVD1

Type Attribute Sample Content

WESTELL.COM

1-800-377-8766

Page 6

Page 8: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Alarms LVD2 > LVD10 LVD 2 > LVD 10

Alarm CEMFControl CEMF Control

Alarm HVSDControl HVSD Control

Alarm LVDInhibit LVD Inhibit

Alarm* CellDeviation Cell Deviation

Alarm* CurrentAlarm Current Alarm

Alarm* VoltageAlarm Voltage Alarm

Alarm* TemperatureAlarm Temperature Alarm

Alarm* CommsAlarm Comms Alarm

*NOTE: There are 16 sets of the above five Adio Alarms.

Alarm ConverterFail Converter Fail

Alarm ConverterMinor Converter Minor

Alarm ConvMajorFailCount Conv. Major Fail Count

Alarm ConvMinorFailCount Conv. Minor Fail Count

Alarm ConvOutOfTolerance Conv. Out Of Tolerance

Alarm ConvCommsLost Conv. Comms Lost

Alarm ConvInputVoltageFail Conv. Input Voltage Fail

Alarm InnvFanFail Conv. Fan Fail

Alarm ConvLoadCurrentHigh Conv. Load Current High

Alarm ConvLowOutputVoltage Conv. Low Output Voltage

Alarm ConvHighOutputVoltage Conv. High Output Voltage

Attribute softwareVersion 3.13

Element: upsBattery

Alarm BatteryRuntimeLow Battery Runtime Low

Alarm BatteryCapacityLow Battery Capacity Low

Alarm BatteryOvertemp Battery Overtemp

Type Attribute Sample Content

WESTELL.COM

Page 7

1-800-377-8766

Page 9: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Alarm BatteryOnDischarge Battery On Discharge

Alarm BatteryTestAlarm Battery test Alarm

Alarm BoostModeAlarm Boost Mode Alarm

Element: upsInverters

Alarm InverterMajorFailCount Inverter Major Fail Count

Alarm InverterMinorFailCount Inverter Minor Fail Count

Alarm InverterCommsLost Inverter Comms Lost

Alarm InverterACInputFail IUnverter AC Input Fail

Alarm InverterAlarm Inverter Alarm

Measurement ACInputApparentPower 5.40 kVA

Measurement ACInputCurrent 44.70 A

Measurement ACInputFrequency 60.00 Hz

Measurement ACInputPower 5.28 kW

Measurement ACInputPowerFactor 0.98

Measurement ACInputVoltage 120.00 V

Measurement ACOutputApparentPower 5.30 kVA

Measurement ACOutputCurrent 43.50 A

Measurement ACOutputPower 5.00 kW

Measurement AcOutputPowerFactor 0.94

Measurement ACOUtputVoltage 120.05 V

Measurement DCInputCurrent 0.00 A

Measurement DCInputPower 0.00 kW

Measurement DCInputVoltage 54.12 V

Element: upsInverter_01

Measurement ACInputApparentPower 0.42 kVA

Measurement ACInputCurrent 3.50 A

Type Attribute Sample Content

WESTELL.COM

1-800-377-8766

Page 8

Page 10: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Measurement ACInputFrequency 60.00 Hz

Measurement ACInputPower 0.42 kW

Measurement ACInputPowerFactor 1.00

Measurement ACInputVoltage 120.10 V

Measurement ACOutputApparentPower 0.43 kVA

Measurement ACOutputCurrent 3.50 A

Measurement ACOutputPower 0.40 kW

Measurement AcOutputPowerFactor 0.94

Measurement ACOUtputVoltage 120.10 V

Measurement DCInputCurrent 0.00 A

Measurement DCInputPower 0.00 kW

Measurement DCInputVoltage 53.80 V

Attribute serialNumber 6093

Attribute softwareVersion 196

*NOTE: There will be additional upsInverter_* components for each inverter module. The table index will match the inverter module number..

Element: upsRectifiers

Alarm RectifierFail Rectifier Fail

Alarm RectifierMinor Rectifier Minor

Alarm RectMajorFailCount Rect. Major Fail Count

Alarm RectMinorFailCount Rect. Minor Fail Count

Alarm RectifierLockout RectifierLockout

Alarm OutOfTolerance Out Of Tolerance

Alarm RectCommsLost Rect. Comms Lost

Alarms RectEqualizeActivated Rect. Equalize Activated

Alarm RectACMainsFail Rect. AC Mains Fail

Type Attribute Sample Content

WESTELL.COM

Page 9

1-800-377-8766

Page 11: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

75652 -- ZTE new SNMP MIB

Inventory Example

rectifier

|-- rectifierBatteryString

|-- rectifierInputPower

|-- rectifierOutput1Power

|-- rectifierOutput2Power

|-- rectifierOutput3Power

|-- rectifierTenant1Power

|-- rectifierTenant2Power

|-- rectifierTenant3Power

|-- rectifierTenant4Power

Configuration Example

config site network-element rectifier

type ZTEZXDUNewRectifier

param deviceIP <ipaddress>

Alarm MaxRectifiersExceeded Max Rectifiers Exceeded

Alarm FanFailAlarm Fan Fail Alarm

Alarm PowerSave Power Save

Alarm UrgentRectACMainsFail Urgent Rect. AC Mains Fail

Measurement Current 1.28 A

Measurement Power 68.92 W

Measurement Voltage 53.84 V

Type Attribute Sample Content

WESTELL.COM

1-800-377-8766

Page 10

Page 12: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

param totalTheoreticalMaxCurrent <total max current in amps of all modules>

Alarms

2.7.X and higher offers Device Alarms, so the batched alarms on the ZTE have been refactored into individual Device Alarms:

Type Attribute Sample Content

Element: rectifier

Alarm Communication Communication Error

Alarm Compatibility Minimum Supported Version “1.0G” Received Version “1.0F”

Alarm ACInSwitchOFF AC In Switch OFF

Alarm ACPowerOFF AC Power OFF

Alarm ACSPD AC SPD

Alarm BLVDLoopEBroken BLVD Loop E Broken

Alarm BatteryTestFail Battery Test Fails

Alarm CAN CAN

Alarm Common Common

Alarm DCSPD DC SPD

Alarm DCHVoltageHigh DC Voltage High

Alarm DCVoltageLow DC Voltage Low

Alarm DoorMagnet Door Magnet

Alarm EnvironmentHumidityHigh Environment Humidity High

Alarm EnvironmentHumidityInvalid Environment Humidity Invalid

Alarm EnvironmentHumidityLow Environment Humidity Low

Alarm EnvironmentTemperatureHigh Environment Temperature High

Alarm EnvironmentTemperatureInvalid

Environment Temperature Invalid

Alarm EnvironmentTemperatureLow Environment Temperature Low

WESTELL.COM

Page 11

1-800-377-8766

Page 13: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Alarm Extend Extend

Alarm Flood Flood

Alarm GlassBroken Glass Broken

Alarm HighTemperatureDownload High Temperature Download

Alarm Intrusion Intrusion

Alarm LLVD1LoopEBroken LLVD1 Loop E Broken

Alarm LLVD2LoopEBroken LLVD2 Loop E Broken

Alarm LLVD3LoopEBroken LLVD3 Loop E Broken

Alarm LowTemperatureDownload Low Temperature Download

Alarm LowVoltageDownload1 Low Voltage Download 1

Alarm PhaseVoltageImbalance Phase Voltage Imbalance

Alarm Radiator Radiator

Alarm Smoke Smoke

Alarm System Current System Current

Alarm TotalAlarmDisabled Total Alarm Disabled

Element: rectifierPower

Alarm <major> Communication Communication Error

Elements: AlphaDCPower, BetaDCPower, GammaDCPower

Alarm <major> Communication Error communicating with the meter

Alarm <critical> Failure Power failure detected (<20.0 VDC)

Element: TenantXDCPower

Alarm <major> Communication Error communicating with the meter

Element: batteryString

Alarm Communication Communication Alarm

Alarm BatteryBreaker Battery Breaker

Type Attribute Sample Content

WESTELL.COM

1-800-377-8766

Page 12

Page 14: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Measurements and Status Points

Alarm BatteryLowVoltageDownload Battery Low Voltage Download

Alarm Battery Battery

Type Attribute Sample Content New Reference Oid

Element: rectifier

Measurement CapacityUtilization 33.60% (totalDCCurrent (calculated) / totalTheoreticalMaxCurrent (parameter)) * 100

Measurement Efficiency 89.10% (totalDCPower (calculated) / totalACPower (calculated)) * 100

Measurement Source_ACPowerHours 0 hours

Measurement Source_ACPowerMinutes 5 minutes

Measurement Source_ACPowerSeconds 328 seconds

Measurement Source_BatteryHours 0 hours

Measurement Source_BatteryMinutes 0 minutes

Measurement Source_BatterySeconds 0 seconds

Measurement Source_BatteryTestHours

0 hours

Measurement Source_BatteryTestMinutes

0 minutes

Measurement Source_BatteryTestSeconds

0 seconds

Measurement Source_OfflineHours 0 hours

Measurement Source_OfflineMinutes 0 minutes

Measurement Source_OfflineSeconds 0 seconds

Status Point Source ACPower or BatteryTest or Offline

Type Attribute Sample Content

WESTELL.COM

Page 13

1-800-377-8766

Page 15: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Element: rectifierPower

Measurement CommunicationCount 0

Measurement CommunicationDurationMinutes

0 minutes

Measurement CommunicationDurationSeconds

0 seconds

Measurement L1N_Voltage 228 V .1.3.6.1.4.1.3902.2800.1.2.3.2.15.1.2.1.1 * 1.0

Measurement L1_Current 2 A .1.3.6.1.4.1.3902.2800.1.2.3.2.16.1.2.1.1 * 1.0

Measurement L2N_Voltage 229 V .1.3.6.1.4.1.3902.2800.1.2.3.2.15.1.2.1.2 * 1.0

Measurement L2_Current 2 A .1.3.6.1.4.1.3902.2800.1.2.3.2.16.1.2.1.2 * 1.0

Measurement L3N_Voltage 229 V .1.3.6.1.4.1.3902.2800.1.2.3.2.15.1.2.1.3 * 1.0

Measurement L3_Current 2 A .1.3.6.1.4.1.3902.2800.1.2.3.2.16.1.2.1.3 * 1.0

Measurement TotalRealPower 1.37 kW (L1N_Voltage * L1_Current * 0.001) + (L2N_Voltage * L2_Current * 0.001) + (L3N_Voltage * L3_Current * 0.001)

Element: AlphaDCPower

Measurement CommunicationCount 0

Measurement CommunicationDurationHours

0 hours

Measurement CommunicationDurationMinutes

0 minutes

Measurement CommunicationDurationSeconds

0 seconds

Type Attribute Sample Content New Reference Oid

WESTELL.COM

1-800-377-8766

Page 14

Page 16: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Measurement Current 8.9 A .1.3.6.1.4.1.3902.2800.1.2.3.3.2.1.2.1.1 * 0.1

Measurement FailureCount 0

Measurement FailureDurationHours 0 hours

Measurement FailureDurationMinutes 0 minutes

Measurement FailureDurationSeconds 0 seconds

Measurement Power 0.48 kW Voltage * Current * 0.001

Measurement Voltage 53.8 V .1.3.6.1.4.1.3902.2800.1.2.3.3.1.1.2.1.1 * 0.1

Element: BetaDCPower

Measurement CommunicationCount 0

Measurement CommunicationDurationSeconds

0 seconds

Measurement Current 8.7 A .1.3.6.1.4.1.3902.2800.1.2.3.3.2.1.2.1.2 * 0.1

Measurement FailureCount 0

Measurement FailureDurationHours 0 hours

Measurement FailureDurationMinutes 0 minutes

Measurement FailureDurationSeconds 0 seconds

Measurement Power 0.48 kW Voltage * Current * 0.001

Measurement Voltage 53.8 V .1.3.6.1.4.1.3902.2800.1.2.3.3.1.1.2.1.2 * 0.1

Element: GammaDCPower

Measurement CommunicationCount 0

Measurement CommunicationDurationSeconds

0 seconds

Measurement Current 8.4 A .1.3.6.1.4.1.3902.2800.1.2.3.3.2.1.2.1.3 * 0.1

Type Attribute Sample Content New Reference Oid

WESTELL.COM

Page 15

1-800-377-8766

Page 17: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Measurement FailureCount 0

Measurement FailureDurationHours 0 hours

Measurement FailureDurationMinutes 0 minutes

Measurement FailureDurationSeconds 0 seconds

Measurement Power 0.45 kW Voltage * Current * 0.001

Measurement Voltage 53.6 V .1.3.6.1.4.1.3902.2800.1.2.3.3.1.1.2.1.3 * 0.1

Element: TenantXDCPower

Measurement CommunicationCount 0

Measurement CommunicationDurationSeconds

0 seconds

Measurement Current -0.30 A .1.3.6.1.4.1.3902.2800.1.2.3.4.29.1.2 * 0.1

Measurement TotalExportEnergy 69.19 kWh .1.3.6.1.4.1.3902.2800.1.2.3.4.41.1.2 * 0.01

Measurement IntervalExportEnergy 0.00 kWh NOTE: Only provided in Optima

Element: batteryString

Measurement ChargeLevel 100% .1.3.6.1.4.1.3902.2800.1.2.3.4.14.1.2.1.1 * 1.0

Measurement Current 21.3 A .1.3.6.1.4.1.3902.2800.1.2.3.4.29.1.2.1.1 * 0.1

Measurement Temperature 31 C .1.3.6.1.4.1.3902.2800.1.2.3.4.6.1.2.1.1 * 1.0

Measurement TimeUntilDischarged ? .1.3.6.1.4.1.3902.2800.1.2.3.4.12.1.2.1.1 * 1.0

Measurement Voltage ‘54.0 V .1.3.6.1.4.1.3902.2800.1.2.3.4.4.1.2 * 0.1

Type Attribute Sample Content New Reference Oid

WESTELL.COM

1-800-377-8766

Page 16

Page 18: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

75773 -- Corning Core v7.2

Updated the alarm mapping to match what is currently implements in the Corning Core.

76107 -- Huawei Rectifier

The Huawei SMU is a newly supported rectifier.

Configuration Example

config site module Tower

application RectifierMonitoring enable

config site network-element rectifier

type HuaweiSMURectifier

param deviceIp 10.48.154.12

The following is a detailed table of the information provided by the Huawei SMU network-element:

Trap OID Trap Name

48 btscSyncAlarmSet

49 btscSuyncAlarmClear

1051 hxnGeneralServiceSet

1052 hxnGeneralServiceClear

Type Attribute Sample Content

Element: rectifier

Alarm <major> Communication Communication Error

Measurement CapacityUtilization 5.00%

Measurement TotalOutputPower 0.60 kW

WESTELL.COM

Page 17

1-800-377-8766

Page 19: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Element: rectifierPower

Alarm <major> Communication Communication Error

Measurement CommunicationCount 0

Measurement CommunicationDurationSeconds

0 seconds

Measurement L1N_Voltage 215.00 V

Measurement L2N_Voltage 0.00 V

Measurement L3N_Voltage 0.00 V

Measurement L1_Current 1.0 A

Measurement L2_Current 1.0 A

Measurement L3_Current 1.0 A

Element: rectifierDCPowerX

Alarm <major> Communication Error communicating with the meter

Alarm <critical> Failure Power failure detected (<20.0 VDC)

Measurement CommunicationCount 0

Measurement CommunicationDurationSeconds

0 seconds

Measurement Current 6.30 A

Measurement FailureCount 0

Measurement FailureDurationSeconds 0 seconds

Measurement Power 0.32 kW

Measurement Voltage 51.50 V

Element: batteryStringX

Alarm <major> Communication Communication Alarm

Measurement ChargeLegel 100.00%

Measurement Current 1.70 A

Type Attribute Sample Content

WESTELL.COM

1-800-377-8766

Page 18

Page 20: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

76117 -- Commscope ION-E v1.6

This system is monitored using SNMP polling. The application also listens for trap notifications from the ION-E and reports alarms accordingly. Furthermore, the application will perform SNMP polls to determine alarm status at start-up, at a user's request (using "sync" control-action), and on a configurable regular cycle (default 24 hours).

Configuration Example

config site module Tower

application DASMonitoring enable

config site network-element DAS

type AndrewIONDAS

param deviceIp 10.11.12.13

Inventory Example

das_01

|-- das_01_00

| |-- das_01_00_BKP

| |-- das_01_00_CAT

| | \-- das_01_00_CAT_L1

| | |-- das_01_00_CAT_L1_01

| | |-- das_01_00_CAT_L1_02

| | |-- das_01_00_CAT_L1_03

| | \-- das_01_00_CAT_L1_04

Measurement Temperature 19.00 C

Measurement TimeUntilDischarged 2192.00 minutes

Type Attribute Sample Content

WESTELL.COM

Page 19

1-800-377-8766

Page 21: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

| |-- das_01_00_EPOI

| | |-- das_01_00_EPOI_00

| | \-- das_01_00_EPOI_01

| |-- das_01_00_OPT

| | \-- das_01_00_OPT_L5

| | |-- das_01_00_OPT_L5_01

| | |-- das_01_00_OPT_L5_02

| | |-- das_01_00_OPT_L5_03

| | \-- das_01_00_OPT_L5_04

| |-- das_01_00_PSU

| | |-- das_01_00_PSU_00

| | |-- das_01_00_PSU_01

| | \-- das_01_00_PSU_03

| |-- das_01_00_RFD

| | \-- das_01_00_RFD_R1

| | |-- das_01_00_RFD_R1_01

| | |-- das_01_00_RFD_R1_02

| | |-- das_01_00_RFD_R1_03

| | \-- das_01_00_RFD_R1_04

| |-- das_01_00_SUI

| | \-- das_01_00_SUI_M3

| \-- das_01_00_WCS

\-- das_01_17

|-- das_01_17_BKP

|-- das_01_17_CAT

| \-- das_01_17_CAT_L1

WESTELL.COM

1-800-377-8766

Page 20

Page 22: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

| \-- das_01_17_CAT_L1_02

|-- das_01_17_OPT

| \-- das_01_17_OPT_R1

| |-- das_01_17_OPT_R1_01

| |-- das_01_17_OPT_R1_02

| |-- das_01_17_OPT_R1_03

| \-- das_01_17_OPT_R1_04

|-- das_01_17_PSU

| |-- das_01_17_PSU_00

| |-- das_01_17_PSU_01

| \-- das_01_17_PSU_03

\-- das_01_17_WCS

76274 -- Commscope ION-M/B v7.20

Internal performance improvements.

76275 -- Commscope ION-U v1.7

Internal performance improvements.

WESTELL.COM

Page 21

1-800-377-8766

Page 23: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

New Features

76174 -- Module Eltek Smartpack monitoring enhanced to process traps

Version 2.91 enhances Eltek Smartpack monitoring to support and process traps received from SNMP host entries added in the Eltek Web User Interface instead of polling alarms.

SNMP Configuration Enhancements

Removing snmpManagerIp from all SNMP devices

Removing snmpManagerPort from all SNMP devices

Added deviceSnmpTrapPort (defaults to 162)

76304 -- Shared Discrete Description Configuration

Version 2.91 adds a new optional parameter, “discreteDescription,” providing a way to describe a shared discrete input which generates multiple alarms and/or measurements. This can be used to describe, for example, a shared discrete input providing alarms, measurements and/or messages including powerDistribution, mainsPowerDetection, and generatorRunning.

If the discreteDescription parameter is filled in, it will be applied to the discrete. If multiple NEs share a discrete, only one should fill in that value. It will exist until all NEs sharing the discrete are deconfigured.

75939, 75938, 75937-- SPX NeType names updated

All SPX Flash Technology tower light type names have been updated in Version 2.91 for consistency and clarity:

The words “TowerLight” have been removed from each type.

Flash Vanguard types are now called SPXVanguard.

Flash LED tower light types are now called SPX36305.

Flash Eagle tower light types are now called SPX903803

WESTELL.COM

1-800-377-8766

Page 22

Page 24: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Refer to the following table:

76004 -- BatteryDAQ rectifier integration

Version 2.91 fulfills a new feature on the BatteryDAQ M6 that will take battery current (as pulled from a rectifier or meter) as a Modbus set. It then uses that for additional calculation. The

Old Type NameStill valid but deprecated; will be removed in a future release

New Type Name

DialightHighIntensityDiscreteTowerLightDialightHighIntensity

DialightHighIntensityTowerLight

DialightMediumIntensityDiscreteTowerLightDialightMediumIntensity

DialightHighIntensityTowerLight

DialightRedOnlyDiscreteTowerLightDialightA2_A6Style

DialightRedOnlyTowerLight

DialightRedOnlySmallDiscreteTowerLightDialightA2_A6Style

DialightRedOnlySmallTowerLight

FlashEagle11DiscreteTowerLight

SPX9038XXFlashEagle11TowerLight

FlashEagle11EthernetDiscreteTowerLight

FlashEagle11EthernetTowerLight

FlashLEDTowerLightSPX36503

FlashLEDDiscreteTowerLight

FlashVanguardSerialDiscreteTowerLight

SPXVanguardFlashVanguardSerialTowerLight

FlashVanguardEthernetDiscreteTowerLight

FlashVanguardEthernetTowerLight

No longer valid; will no longer work:

FlashVanguardTowerLight N/A

WESTELL.COM

Page 23

1-800-377-8766

Page 25: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

application will make the M6 soft dependent on rectifiers and supply that value if applicable. The module will now write the battery current value from a rectifier into the appropriate register on the BatteryDAQ every five seconds..

76074 -- UDiT Updates (components, fix actions)

DAS type UDiT has been updated in Version 2.91 to make use of device alarms and provide fix actions.

Configuration Example

config site module Tower

application DASMonitoring enable

config site network-element DAS

instance das1

display-name DAS1

exit

config site network-element das1

type CSIUDiTDASPanel

param deviceIp 10.48.154.12

Inventory Example

DAS1

|--SubRack01

| |-- Slot01 POI_1

| \-- Slot02 POI_2

\--SubRack02

|-- Slot01 L7ABC

|-- Slot02 AWS

\-- Slot03 SMR

WESTELL.COM

1-800-377-8766

Page 24

Page 26: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Fixes

76071 - TSUN Alarms on Node 0 aren’t shown

Alarms that come in with a CTA of 0 can now be set and cleared on the top level DAS element.

76112 - cabinetBattery Alarm Typo

A misspelling in a cabinetBattery alarm message has been corrected: “Battery fully discharged.”

76179 - Flash Vanguard Tower Light Type Issue

Eagle systems can now update their lighting type to white only. They should identify the correct tower light style D1 when white only instead of E1.

75948 - When configEnforcementDelay is set to 0, module should never set Marvair coolingSetpoint and emergencyShutoffTemperature

Module will no longer incorrectly enforce Marvair config on startup when the configEnforcementDelay is 0.

75911 - Generac H100 generator status continues to show running if serial communication to generator is lost during run

Now every serial-based generator will set the State status point to Offline when there is a communication alarm currently active.

WESTELL.COM

Page 25

1-800-377-8766

Page 27: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

76358 - Direct Connect sites with alarms not syncing

In certain cases, components would not function correctly after changing a parameter on the top-level network element. This has been resolved so that alarms and status points will continue to function after making config changes..

Issue List

Issue ID Version Description

76304 2.9.0 Allow setting discrete description for shared discrete inputs

76275 2.9.0 Support Commscope ION-U firmware 1.7

76274 2.9.0 Support Commscope ION-M/B firmware 7.20

76174 2.9.0 Module Eltek Smartpack monitoring -- currently an snmp polling solution -- request to enhance to process traps

76171 2.9.0 SNMP simulator should work on multiple sub interfaces

76117 2.9.0 Application support for Commscope ION-E v1.6

76107 2.9.0 Application support of Huawei rectifier

76074 2.9.0 Update UDiT to function as other DAS types

76005 2.9.0 Report firmware version as an attribute

76004 2.9.0 Provide rectifier battery current to BatteryDAQ M6 if that combo is being used

75773 2.9.0 Support Corning Core v7.2

74996 2.9.0 Support AlphaTechnologies AMP24 UPS

76347 2.9.0 The single trap listener needs to be able to handle multiple trap community strings

76361 2.9.0 CAS-13954//ATC//ATC DAS SC450 alarms not showing up in Optima or the RMM - Site 332224 Park Meadows Mall

76358 2.9.0 344199 Southcenter_DC alarms not syncing

76332 2.9.0 Module 2.8.4 issue: making param changes to an NE does not actually make changes until module restart

76328 2.9.0 ValueError? when parsing snmp parameters - Emerson Netsure

WESTELL.COM

1-800-377-8766

Page 26

Page 28: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

76322 2.9.0 v2.9.0 Module Validation - snmpMangerPort param no longer required?

76314 2.9.0 Support ION-E device management table

76302 2.9.0 Top level DAS alarms not clearing on syncAlarms control action

76256 2.9.0 Generac E-panel Annunciator communication - short duration (1-9 second) comm alarm events

76215 2.9.0 deviceSnmpTrapCommunity is actually used

76200 2.9.0 MissingAlias? alarms will not clear in Optima

76179 2.9.0 Case # 13480 // ATC US // 88468 Sanderson - Tower Type Issue on Flash Vanguard

76087 2.9.0 Battery DAQ writing to wrong register to update battery sting current

76048 2.9.0 Writing to BatteryDAQ Current register won’t recover after One Failure

76015 2.9.0 Directconnection doesn't measure every 15 minutes uptime data on the capacity server

75996 2.9.0 RunMode Status Point not Added to all Generator Types

75948 2.9.0 When configEnforcementDelay is set fo 0, module should never set marvair coolingSetpoint and emergencyShutoffTemperature

75911 2.9.0 Generator status continues to show running if serial communication to generator is lost during run. Generac H100 generator.

76382 2.9.0 SC-450 not reading firmware version until syncInventory

76380 2.9.0 Unnecessary component updates after first syncInventory event

76365 2.9.0 No logger property for controls

76339 2.9.0 Remove excess logging

76293 2.9.0 Measurement precision is not working correctly

76170 2.9.0 Clean up the RemoteConfigurations that apply to ip tables

76112 2.9.0 The word discharged is misspelled on the “Battery fully dicharged”

76093 2.9.0 unnecessary Communication alarms on monitor ne

76011 2.9.0 Only supply battery current to M6 if optional parameter is specified

76008 2.9.0 Updating NE display name only is ignored by module

Issue ID Version Description

WESTELL.COM

Page 27

1-800-377-8766

Page 29: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

76385 2.9.1 Allow optional trap community string configuration

Issue ID Version Description

WESTELL.COM

1-800-377-8766

Page 28

Page 30: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Modules Version 2.91 Device Compatibility Information

Vendor Model / Variant Version(s)APC Galaxy 500 GDENA9S300IC303

Acrel PZ Series

Airsys ASLLC.2 13B64

AlphaAMPS24 3.13

FXM 2.00.01

Basler DCG-2020 3.17.02

BatteryDAQ 2402W2/M6

CCS WattNode

CSI UDiT 01.03.01

Commscope

ION MMC Plus Linux ION-M 6.50.0, 7.20.0

MMC Plus Windows ION-M 5.30.0

RMC1600 Linux ION-M 6.50.0, 7.0.1, 7.10.0, 7.20.0

RMC1600 Linux ION-U 1.64.1, 1.70.0

TSUN1/2 ION-B 5.1.1, 5.1.2

TSUN4 Linux ION-M 6.50.0, 7.20.0

TSUN4 Windows ION-M 5.30.0

Corning SC-450 7.0, 7.2

Deep Sea Electronics

5210 6.2a

5220 6.2a

5220/7320

7320 9.x.x

WESTELL.COM

Page 29

1-800-377-8766

Page 31: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Dialight

A0-A1 Style A.1

High Intensity A.31

Medium Intensity B.6

Medium Intensity Red A.6

Medium Intensity Small Red A.1

Red Only A2-A6 Style A.6

Eaton 9130 4.30, 4.32, 4.34, 4.36, 4.38

ElkorWattsOn Split Phase

WattsOn Three Phase

Eltek SmartPack 4.6, 4.7, 4.8, 4.9, 4.10

EmersonEmerson Rectifier

NetSure 4.00, 4.02, 4.04, 4.10, 4.21

FenceHawk RG-7781

Flash

Eagle 4747/9038

Eagle Ethernet 4747/9038

LED JUN 26 2012 10:47:38

Vanguard 2.7, 2.8, 2.9, 3.0,, 3.1, 3.2

Vanguard Ethernet 2.7, 2.8, 2.9, 3.0,, 3.1, 3.2

ForlongDRT-301C

DRT-301C2

Generac

EPanel

EPanel with Annunciator

H100 3.4-4.0

HTS 4.0

HTS Ethernet 4.0

GreystoneRH310A02C2E6

RH310A03C2A6

Huawei SMU V500R001C20SPC901T

Intelilite AMF25 1.4

WESTELL.COM

1-800-377-8766

Page 30

Page 32: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

iSnail

VC

VC10

VC25

LovatoEXM10

RGK60 42

Marvair CommStat4 v62

Measurlogic DTS DC

Microwave Photonics OFW3478

SOLiD DMS-1200 4.2.0, 6.1.0

SPX

36305 JUN 26, 2012 10:47:38

9038XX 4747/9038

Vanguard 2.7, 2.8, 2.9, 3.0, 3.1, 3.2

Standardel DPS520

TE Prism 8.1.0, 8.1.7

ZTE

ZXDU

ZXDU68 W301 V.5.0 1.0G

ZXDU68 W301 V.5.0R06M04 1.12.01.01

Kentrox

Access Manager

Analog Battery Sensor

Analog Fuel Sensor

Discrete ATS

Discrete Asset Monitor

Discrete Controlled Generator

Discrete Door Sensor 18-130-101

Discrete Fuel Quality

Discrete Generator

Discrete Monitor

Discrete Power Detection

WESTELL.COM

Page 31

1-800-377-8766

Page 33: Kentrox Modules Version 2.91 Release Notes Rev A May …support.westell.com/documents/Release-Notes/Modules291_RN.pdf · ZTE ZXDU68 ZTEZxduRectifier 75652 ZTEBatteryString 76004 Vendor

Modules Version 2.91 Release Notes

Kentrox (continued)

Discrete Rectifier

Discrete Siren

Discrete Smoke Detector

Discrete Test ATS

Dual Discrete ATS

HPM

MeasTable

Module Monitor

RMB

RMC Power Detection

SBTEMP-RJ45

SBTEMPHUMIDITY-RJ45

SMS Backhaul Sender

Shared Discrete Generator

Tenant-Based Site Power Detection

Three Phase Voltage Teansducer

Virtual ATS

Virtual Battery String

Virtual Equipment Power Meter

Virtual Generator

Virtual HVAC System Energy Meter

Virtual HVAC Unit Energy Meter

Virtual Power Detection

Virtual Power Distribution

Virtual Power Management

Virtual Split Phase

Virtual Split Phase Power Detection

Virtual Three Phase

Virtual Three Phase Power Detection

WESTELL.COM

1-800-377-8766

Page 32