kelman dga 900 operator guide - kama solutions...remotely over a network via a web-based interface...
TRANSCRIPT
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 1 of 92
GE Grid Solutions
Kelman™ DGA 900 Operator Guide Transformer Oil Dissolved Gas and Moisture Monitor
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 2 of 92
Contents Page 1 Introduction ............................................................................................... 7
1.1 Product Overview ................................................................................................................................ 7
1.2 Scope ........................................................................................................................................................ 9
1.3 Front Panel LEDs .................................................................................................................................. 9
2 Safety........................................................................................................ 10
2.1 Symbols ................................................................................................................................................. 10
2.2 Warnings .............................................................................................................................................. 10
2.3 Hazardous Substances ................................................................................................................... 11
3 Technical Specifications ......................................................................... 12
4 Compliance .............................................................................................. 14
5 Power........................................................................................................ 15
6 HMI ............................................................................................................ 16
6.1 Introduction......................................................................................................................................... 16
6.2 Connections ........................................................................................................................................ 17
6.3 Start-Up Procedure .......................................................................................................................... 18
6.4 Login ....................................................................................................................................................... 18
6.5 Dashboard............................................................................................................................................ 19 6.5.1 Quick Access ................................................................................................................................................................. 21
6.6 GAS / Diagnostics .............................................................................................................................. 23 6.6.1 Active Alarms ............................................................................................................................................................... 23 6.6.2 Measurements ............................................................................................................................................................. 23 6.6.3 Duval Triangle .............................................................................................................................................................. 24 6.6.4 Gas Ratio ........................................................................................................................................................................ 25 6.6.5 Scheduler ....................................................................................................................................................................... 26
6.7 Calculations ......................................................................................................................................... 26 6.7.1 Gas Ratios ...................................................................................................................................................................... 26 6.7.2 Relative Saturation .................................................................................................................................................... 27 6.7.3 Gas Rate of Change ................................................................................................................................................... 27 6.7.4 Analog Inputs RoC Configuration ....................................................................................................................... 28
6.8 Alarms ................................................................................................................................................... 29 6.8.1 Gases ................................................................................................................................................................................ 29 6.8.2 Gas Ratios ...................................................................................................................................................................... 30 6.8.3 Gas Rate of Change ................................................................................................................................................... 31 6.8.4 Relative Saturation .................................................................................................................................................... 32 6.8.5 Analog Inputs ............................................................................................................................................................... 32 6.8.6 Analog Inputs Rate of Change .............................................................................................................................. 33 6.8.7 Digital Inputs ................................................................................................................................................................ 33 6.8.8 Digital Inputs Transition Total .............................................................................................................................. 34
6.9 Peripherals ........................................................................................................................................... 35 6.9.1 Peripheral Scheduler ................................................................................................................................................ 35 6.9.2 Analog Inputs ............................................................................................................................................................... 35 6.9.3 Digital Inputs ................................................................................................................................................................ 36 6.9.4 Input Measurements ................................................................................................................................................ 36
6.10 Settings ................................................................................................................................................. 37 6.10.1 Communications ........................................................................................................................................................ 37 6.10.2 Date & Time .................................................................................................................................................................. 38
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 3 of 92
6.10.3 SMS Alerting.................................................................................................................................................................. 38 6.10.4 Firewall ............................................................................................................................................................................ 39 6.10.5 Communication Services ........................................................................................................................................ 40
6.11 Service ................................................................................................................................................... 41 6.11.1 Measurement ............................................................................................................................................................... 41 6.11.2 Controller Reprogramming .................................................................................................................................... 42 6.11.3 I/O PCB Reprogramming ......................................................................................................................................... 43 6.11.4 Oxygen Sensor ............................................................................................................................................................. 44 6.11.5 Gas Normalization ..................................................................................................................................................... 45 6.11.6 Factory ............................................................................................................................................................................. 45 6.11.7 User Administration .................................................................................................................................................. 48
6.12 TransOpto ............................................................................................................................................ 50 6.12.1 Measurements ............................................................................................................................................................. 50 6.12.2 Rate of Change ............................................................................................................................................................ 50 6.12.3 Alarms .............................................................................................................................................................................. 51 6.12.4 Rate of Change Alarms ............................................................................................................................................ 52 6.12.5 Channels ......................................................................................................................................................................... 53 6.12.6 Settings ........................................................................................................................................................................... 53
6.13 Logout .................................................................................................................................................... 54
6.14 Shutdown Procedure ....................................................................................................................... 55
6.15 Error Notifications ............................................................................................................................ 56 6.15.1 Error Codes.................................................................................................................................................................... 58 6.15.2 Other Notifications .................................................................................................................................................... 59
7 Manual Oil Sampling ............................................................................... 60
7.1 Sampling Arrangement ................................................................................................................... 60
7.2 Local HMI for manual sampling ................................................................................................... 61
7.3 Sampling Process .............................................................................................................................. 65
8 Communications ..................................................................................... 67
8.1 DNP3 ...................................................................................................................................................... 67
8.2 IEC 61850 ............................................................................................................................................. 67
8.3 Modbus Protocol ............................................................................................................................... 67
8.4 HTTP / HTTPS Protocol .................................................................................................................... 67
9 Technical Support ................................................................................... 67
Appendix A Security Configuration ............................................................ 68
Appendix B Transportation PGA Lock ........................................................ 75
Appendix C Maintenance Activities ........................................................... 79
Appendix D Time Sync Implementation ..................................................... 85
Appendix E Alarm Settings: General Advice ............................................. 87
Contact & Copyright Details .......................................................................... 92
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 4 of 92
List of Tables and Figures Page Figure 1-1: Inside the DGA 900 ................................................................................................................................................ 7 Table 1-1: Hub front panel LED lights ................................................................................................................................... 9 Table 3-1: Measurements ........................................................................................................................................................ 12 Table 4-1: Type tests .................................................................................................................................................................. 14 Figure 5-1: Fuse holder ............................................................................................................................................................. 15 Table 5-1: External LED status indicators ........................................................................................................................ 15 Figure 6-1: Inside the Hub – LCD top left.......................................................................................................................... 16 Figure 6-2: Ethernet / USB HMI connection .................................................................................................................... 17 Figure 6-3: Log-in page............................................................................................................................................................. 18 Table 6-1: User access rights ................................................................................................................................................. 18 Figure 6-4: Local HMI: Quick Access page ....................................................................................................................... 19 Figure 6-5: Dashboard .............................................................................................................................................................. 20 Figure 6-6: Quick Access .......................................................................................................................................................... 21 Figure 6-7: Quick Access – Rapid Mode ............................................................................................................................ 22 Figure 6-8: Active Alarms ......................................................................................................................................................... 23 Figure 6-9: Measurements ...................................................................................................................................................... 24 Figure 6-10: Duval Diagnostic ............................................................................................................................................... 25 Figure 6-11: Gas Ratio ............................................................................................................................................................... 25 Figure 6-12: DGA Scheduler ................................................................................................................................................... 26 Figure 6-13: Gas Ratio Settings............................................................................................................................................. 26 Figure 6-14: Gas Ratio Settings – Ratio 1 definition .................................................................................................... 26 Figure 6-15: Relative Saturation Settings ........................................................................................................................ 27 Figure 6-16: Gas RoC Configuration ................................................................................................................................... 27 Figure 6-17: Analog Inputs Rate of Change Configuration ..................................................................................... 28 Figure 6-18: Gas Alarms Configuration............................................................................................................................. 29 Figure 6-19: Hydrogen alerts ................................................................................................................................................. 30 Figure 6-20: Gas Ratio Alarms Configuration ................................................................................................................ 30 Figure 6-21: Gas Ratio Alarms Configuration – Ratio 1 High-High Gas Rate of Change .......................... 30 Figure 6-22: Gas RoC Configuration ................................................................................................................................... 31 Figure 6-23: Relative Saturation Alarms Configuration ............................................................................................ 32 Figure 6-24: Relative Saturation Alarms Configuration – High-High .................................................................. 32 Figure 6-25: Analog Inputs Alarms Configuration ....................................................................................................... 32 Figure 6-26: Analog Inputs RoC Alarms Configuration.............................................................................................. 33 Figure 6-27: Digital Inputs Alarms Configuration ......................................................................................................... 33 Figure 6-28: Digital Inputs Transition Total Alarms Configuration ...................................................................... 34 Figure 6-29: Peripheral Scheduler ....................................................................................................................................... 35 Figure 6-30: Analog Inputs Configuration ....................................................................................................................... 35 Figure 6-31: Analog Input 4 (4-20 mA Temperature Sensor) .................................................................................. 36 Figure 6-32: Digital Input Configuration ........................................................................................................................... 36 Figure 6-33: Input Measurements ....................................................................................................................................... 36 Figure 6-34: Communications Settings ............................................................................................................................. 37 Figure 6-35: Date & Time ......................................................................................................................................................... 38 Figure 6-36: SMS Alerting ......................................................................................................................................................... 38 Figure 6-37: Firewall configuration ..................................................................................................................................... 39 Figure 6-38: Communication Services .............................................................................................................................. 40 Figure 6-39: Measurement Settings ................................................................................................................................... 41 Figure 6-40: Controller Reprogramming .......................................................................................................................... 42 Figure 6-41: Upgrade in progress ........................................................................................................................................ 42 Figure 6-42: I/O Board Reprogramming ........................................................................................................................... 43 Figure 6-43: Upgrade in progress ........................................................................................................................................ 43 Figure 6-44: Oxygen Sensor ................................................................................................................................................... 44
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 5 of 92
Figure 6-45: Gas Normalization Settings ......................................................................................................................... 45 Figure 6-46: Factory Settings ................................................................................................................................................. 45 Table 6-2: Factory Settings: Data and configuration cleardown ......................................................................... 47 Figure 6-47: Simulation mode ............................................................................................................................................... 48 Figure 6-48: Restart the device ............................................................................................................................................. 48 Figure 6-49: User Administration ......................................................................................................................................... 48 Figure 6-50: Change Password ............................................................................................................................................. 49 Table 6-3: Password Strength ............................................................................................................................................... 49 Figure 6-51: TransOpto Measurements ............................................................................................................................ 50 Figure 6-52: TransOpto RoC Configuration ..................................................................................................................... 50 Figure 6-53: TransOpto Alarms Configuration .............................................................................................................. 51 Figure 6-54: Channel 1 High alerts...................................................................................................................................... 51 Figure 6-55: TransOpto RoC Alarms Configuration ..................................................................................................... 52 Figure 6-56: Channel 2 High-High alerts .......................................................................................................................... 52 Figure 6-57: TransOpto Channels Settings...................................................................................................................... 53 Figure 6-58: TransOpto Settings ........................................................................................................................................... 53 Figure 6-59: Logout .................................................................................................................................................................... 54 Figure 6-60: Log-in page .......................................................................................................................................................... 54 Figure 6-61: System Info – Standby .................................................................................................................................... 55 Figure 6-62: Measurement started ..................................................................................................................................... 55 Figure 6-63: PGA and Oxygen Sensor Error States ..................................................................................................... 56 Figure 6-64: PGA Errors ............................................................................................................................................................. 57 Table 6-4: PGA Errors ................................................................................................................................................................. 58 Table 6-5: Oxygen sensor error codes .............................................................................................................................. 59 Figure 65: MicroSD card memory usage .......................................................................................................................... 59 Figure 7-1: Oil filter and oil ports (front view of Analysis module) ........................................................................ 60 Figure 7-2: Valve orientation .................................................................................................................................................. 61 Figure 7-3: Sampling assembly ............................................................................................................................................. 61 Figure 7-4: Luer fitting on assembly ................................................................................................................................... 61 Figure 7-5: Local HMI: Quick Access ................................................................................................................................... 61 Figure 7-6: Manual Sampling ................................................................................................................................................. 62 Figure 7-7: Purging Oil ............................................................................................................................................................... 62 Figure 7-8: Take manual oil sample ................................................................................................................................... 63 Figure 7-9: Manual Sampling cannot be started ......................................................................................................... 63 Figure 7-10: Dashboard: Stop Measurement ................................................................................................................. 64 Figure 7-11: Manual oil sampling flowchart ................................................................................................................... 65 Table A-1: External Interfaces................................................................................................................................................ 69 Table A-2: Protocols .................................................................................................................................................................... 69 Figure A-1: Settings > Communication Services........................................................................................................... 70 Figure A-2: Communication Services ................................................................................................................................. 70 Figure A-3: Firewall Settings ................................................................................................................................................... 72 Figure A-4: Default policy options........................................................................................................................................ 73 Figure A-5: Specific policy options ....................................................................................................................................... 73 Figure A-6: LAN interface ......................................................................................................................................................... 73 Figure A-7: LAN interface ......................................................................................................................................................... 73 Figure A-8: Accept HTTPS ........................................................................................................................................................ 74 Figure B-1: PGA lock – engaged ........................................................................................................................................... 75 Figure B-2: PGA lock – pins and locking bracket secured with cable ties ........................................................ 75 Figure B-3: PGA lock – remove pins .................................................................................................................................... 76 Figure B-4: PGA lock – remove plastic nuts .................................................................................................................... 76 Figure B-5: PGA lock – remove metal bracket ............................................................................................................... 76 Figure B-6: PGA lock – insert metal bracket ................................................................................................................... 77 Figure B-7: PGA lock – attach plastic nuts ....................................................................................................................... 77 Figure B-8: PGA lock – insert pins ........................................................................................................................................ 77
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 6 of 92
Figure B-9: PGA lock – pin to enclosure hole .................................................................................................................. 78 Figure B-10: PGA lock – pins and locking bracket secured with cable ties ..................................................... 78 Figure C-1: Controller PCB coin cell battery .................................................................................................................... 79 Figure C-2: Marshalling PCB coin cell battery ................................................................................................................ 79 Figure C-3: Hub fan air inlet .................................................................................................................................................... 80 Figure C-4: Detached inlet cover with filter – facedown .......................................................................................... 80 Figure C-5: Detached inlet cover with filter removed ................................................................................................ 80 Figure C-6: Filter mesh cartridge – face up ..................................................................................................................... 80 Figure C-7: Louvre catchment tray – attached ............................................................................................................. 81 Figure C-8: Louvre gasket – tray removed ...................................................................................................................... 81 Figure C-9: Louvre catchment tray – detached & filter removed ........................................................................ 81 Figure C-10: Louvre air filter ................................................................................................................................................... 81 Figure C-11: Oil connections .................................................................................................................................................. 82 Figure C-12: Oil filter ................................................................................................................................................................... 82 Figure C-13: Internal push-fit cover removal ................................................................................................................. 82 Figure C-14: Peltier cooler ....................................................................................................................................................... 84 Figure C-15: Fan group electrical connection ............................................................................................................... 84 Figure C-16: Peltier cooling fins ............................................................................................................................................ 84 Figure C-17: Fan group detached from cooler .............................................................................................................. 84 Table D-1: Timing ......................................................................................................................................................................... 85 Table D-2: UNIX time registers .............................................................................................................................................. 85 Table D-3: Access flags ............................................................................................................................................................. 86 Table D-4: Modifier flags .......................................................................................................................................................... 86 Table E-1: Main Tank: Gas Level Alarms ........................................................................................................................... 88 Table E-2: ROC alarms (key gas values) ............................................................................................................................ 88 Table E-3: ROC alarms (for ROC in ml/day) ...................................................................................................................... 90 Table E-4: Measurement intervals ....................................................................................................................................... 90
Related Documents Ref# Title
MA-024 DGA 900 Installation Manual
Abbreviations & Definitions Abbreviation Meaning
HMI Human Machine Interface
Controller PCB Controller Printed Circuit Board
I/O PCB Input / Output Printed Circuit Board
Marshalling PCB Marshalling Printed Circuit Board
PPE Personal Protective Equipment
PCC Power, Communications and Control (cable)
RoC Rate of Change
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 7 of 92
1 INTRODUCTION
1.1 Product Overview
The Kelman™ DGA 900 (the product) is a multigas online DGA (Dissolved Gas Analysis) and
moisture monitoring system for implementing Asset Performance Management (APM)
across electrical generation, transmission, distribution and industrial applications.
The product as shown in Figure 1-1 can detect and diagnose incipient faults and trend
asset health via the monitoring of critical gases including moisture in the transformer oil.
This includes any mineral oil or ester-based fluid (natural or synthetic). The product
measures nine certified fault gases: hydrogen, methane, ethane, ethylene, carbon
monoxide, carbon dioxide, acetylene, oxygen, nitrogen as well as water content and the
transformer load current. Such data provides insight on transformer condition criteria,
such as developing faults, paper degradation and electrical arcing.
Once installed, operation is intuitive and programmable. The product can be managed
remotely over a network via a web-based interface or locally via a touchscreen interface.
All results are stored within the product, but online management is recommended. Results
and the full product database can also be downloaded to a PC for analysis, aggregation and
trending with the Perception software suite.
Figure 1-1: Inside the DGA 900
The product features:
▪ An innovative two-enclosure design connecting the two modules by a Power, Communications and Control (PCC) cable for a more flexible installation configuration. The Analysis module contains the PGA measurement technology, whereas the Hub module contains the communications technology and HMI screen. The modules have IP56-rated aluminium enclosures (compliant in the installed upright position) and are powder coated to the RAL 9002 colour.
▪ Automated headspace gas extraction manifold to extract target gases from the oil sample.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 8 of 92
▪ Advanced high precision Photo-Acoustic Spectroscopy (PAS) sensing technology based on a robust multi-point individual gas calibration process using certified gases to calibrate the PGA (Photoacoustic Gas Analyser).
▪ Complete multi-gas analysis (nine gases and moisture) with a user-configurable sampling frequency from once per hour to once every four weeks including remote alert capabilities. All gas sensing is carried out internally without a need for carrier gases or recalibration. Minimal maintenance*1 and no requirement for costly consumables.
▪ A new ‘Rapid Mode’ allows sampling to be completed in around 30 minutes using five key gases and is useful in critical situations to give immediate insight on fast-developing faults.
▪ Improved lower detection limits and measurement repeatability for earlier detection of imminent faults on the transformer being monitored.
▪ Transformer load tracking (CT analogue input as standard).
▪ Watchdog relay as standard to monitor power usage.
▪ Six configurable relay contacts based on absolute gas and moisture values (with one dedicated service).
▪ Five optional 4-20 mA configurable analogue input cards.
▪ Three digital inputs (optional configurations available).
▪ Compatible with AC or DC power.
▪ Four sunlight-visible LED arrays on the exterior of the Hub module — red for alarm, yellow for caution (both user-configurable) — and green for power, blue for service.
▪ A fully embedded microprocessor with 4 GB non-volatile internal memory storage, highly scalable analogue and digital I/Os, an embedded webserver, 8 GB SD card to hold measurement data and an integrated 7 in. colour LCD screen with resistive touch for simplified local user interaction and visualization of data.
▪ The infrastructure provides a platform for expansion and future feature enhancements complemented by an extensive range of secure communications options. These include Ethernet, RS-485, cellular modem (SMS Text Alerts /GPRS), and fibre optic options (IEC61850 or DNP3). Internal USB connection is provided for commissioning and service, or local data download. Other options may be available on request.
▪ Compatibility with GE’s Perception transformer fleet management software for data download, trending and analysis as well as other SCADA systems. The product is a DS-Agile and Predix-Grid APM ready device with support for industry standard protocols.
*1 Note: The only recommended maintenance is periodic cleaning of the air filters, in-line oil filter and battery replacement.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 9 of 92
1.2 Scope
This guide outlines the use of the HMI, manual sampling function and general maintenance
activities.
1.3 Front Panel LEDs
Table 1-1 outlines the LEDs on the front panel of the Hub module.
Table 1-1: Hub front panel LED lights
LED Colour Symbol Meaning
Alarm
A measured parameter has exceeded a user-programmed “alarm” threshold.
Caution
A measured parameter has exceeded a user-programmed “warning” threshold.
Power
24 V Power OK.
Service
Service required. Triggered by a warning service event if the product detects internal issues or if equipment settings are exceeded. If scheduled, the product will still attempt another measurement and clear any service condition if the issue is no longer present.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 10 of 92
2 SAFETY
2.1 Symbols
The meaning of symbols used on the Kelman™ DGA 900:
Caution. Refer to the Installation Manual / Operator Guide to prevent death, bodily injury, equipment damage or loss of data.
Electrical Hazard. Risk of electric shock.
Primary Protective Earth connection.
Hot surfaces may be present.
The meaning of symbols used in this guide:
Warning: A procedure, practice, or condition could cause death or serious injury and/or significant equipment damage.
[Caution]: A procedure, practice, or condition could cause minor injury, equipment damage or loss of data.
Electrical Hazard: Risk of electric shock.
Hot surfaces may be present.
2.2 Warnings
The following warnings must be observed:
WARNING: The minimum ambient temperature for installation and service activities is −10 °C.
WARNING: If the equipment is installed or used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
WARNING: If working at height, third parties must have received appropriate training for working at height prior to work commencing. This includes, but is
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 11 of 92
not limited to, ‘Working at height’ and ‘Using Mobile Elevated Working Platforms’ training.
WARNING: If working at a height greater than 4 feet (1.2 metres) or at a height greater than that stipulated by national or site regulatory requirements, it is the responsibility of the installer to ensure that planned work complies with those requirements.
WARNING: The user shall also ensure that any third-party equipment, such as an approved platform, scaffold or lift is suitable and safe before commencing work. Ladders or improvised platforms do not meet GE service engineer requirements.
WARNING: Once installed, this product may have more than one source of supply. Disconnect all supplies at their source before accessing the cabinet for servicing. Follow the site lockout-tagout (LOTO) procedure.
WARNING: Disconnection from the supply is achieved through the external circuit breaker or switch.
WARNING: Ensure all power sources, including relays, are de-energised as stipulated by lockout-tagout (LOTO) requirements before performing any maintenance work inside the product.
WARNING: The product is operated with the door shut under normal use. The door shall be kept locked and should only be opened for service access by suitably qualified and authorised service personnel. During service access, hazardous voltages are accessible.
WARNING: Only GE-trained and certified personnel may commission GE Kelman products. Commissioning tasks include making any connections and/or performing any work within the enclosure, or performing tasks such as purging the oil circuit between the transformer and the product, and/or all first start-up procedures relating to equipment or firmware/software.
WARNING: The product provides IP56 water spray protection. It is possible for a water deluge system to exceed IP56 thresholds depending on the location, pressure and direction of the water jets. Should customers require testing a water deluge system in the area in which the product is installed, GE recommends powering down the product and draping it with a suitable waterproof covering.
2.3 Hazardous Substances
The gases measured in the product are extracted from the oil and expelled to the
atmosphere via the exhaust vent on the external base of the Analysis module. The area
around the exhaust vent should be kept clear and unobstructed. All expelled gases are at
concentrations that are nonflammable, nontoxic and quickly diluted in the surrounding
atmosphere. The expelled gases are not hazardous to health or life.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 12 of 92
3 TECHNICAL SPECIFICATIONS
The product meets the following technical specification as outlined in Table 3-1.
Table 3-1: Measurements
PARAMETER VALUE/MEETS
GAS MEASURED *1 & 10 RANGE ACCURACY *2 & 3 REPEATABILITY *2
Hydrogen (H2) 5 – 5,000 ppm ± 5% or ± LDL
<3%
Methane (CH4) 2 – 50,000 ppm ± 3% or ± LD L <2%
Ethane (C2H6) 1 – 50,000 ppm ± 3% or ± LDL <2%
Ethylene (C2H4) 1 – 50,000 ppm ± 3% or ± LDL <2%
Acetylene (C2H2) 0.5 – 50,000 ppm ± 3% or ± LDL <2%
Carbon Monoxide (CO) 1 – 50,000 ppm ± 3% or ± LDL <2%
Carbon Dioxide (CO2) 20 – 50,000 ppm ± 3% or ± LDL <3%
Oxygen (O2) 100 – 50,000 ppm ± 5% or ± LDL <3%
Nitrogen (N2) *4 10,000 – 100,000 ppm ± 15% or ± LDL
<3%
Moisture (H2O) 0 – 100% Relative Saturation
*5
± 3.5% <3%
Measurement frequency Variable – Once per hour to once every 4 weeks
ENVIRONMENTAL*11 Operating external temperature range
−40 °C to 55 °C
Storage temperature range 0 °C to 45 °C
Oil temperature range *6
−20 °C to 120 °C
Altitude Up to 2000 m
Atmospheric pressure Up to 1050 mbar
Operating humidity 10 – 95% RH non-condensing
Enclosure IP56
Weight *7
Analysis module: 33.4 kg (73.6 lb)
Hub module: 18.5 kg (40.8 lb)
2 m PCC cable: 0.8 kg (1.83 lb)
Product weight: 52.7 kg (116.3 lb)
POWER REQUIREMENTS Nominal input voltage range:
100-250 V DC 4 A
100-240 V AC, 50/60 Hz, 4 A
Input voltage range:
90-264 V AC
90-275 V DC
AC frequency range:
45-65 Hz
Single phase Alarm Relays: NO and NC provided*
8
10 A 250 V AC, 10 A 30 V DC, 0.3 A 110 V DC, 0.12 A 220 V DC
Fuses *9 10 A 600 V AC/DC EATON KLM-10
Coin cells Panasonic CR2450 3 V 620 mAh
*1 Note: Parameters specified in application with mineral oil.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 13 of 92
*2 Note: Accuracy and repeatability are quoted for the detectors under factory calibration and test levels. Gas-in-oil measurements may be affected by sampling and/or oil type.
*3 Note: Whichever is greater.
*4 Note: Available on free-breathing transformers only.
*5 Note: Given in ppm.
*6 Note: Based on testing carried out using VOLTESSO™ 35 mineral oil over a ¼ in. pipe run of 10 metres or less from oil supply or return valve to product connection point, and on transformer oil supply valve volumes of 200 ml or less. For oil temperatures colder than −20 ºC, GE recommends the use of heat trace cabling on piping. Low oil viscosity reduces oil flow.
*7 Note: The weight depends on the order specification. The stated weight is for a base product without packaging and excludes options such as a mounting stand. Check the shipping document for the exact packaged weight.
*8 Note: Maximum DC breaking capacity for a resistive load.
*9 Note: Use only the approved and recommended fuse to ensure continued fire protection and compliance.
*10 Note: Laboratory results can vary greatly worldwide as has been established through many round-robin tests. Any comparison of DGA 900 measurement results against laboratory results need to be considered in this context.
*11 Note: It is possible for a small amount of condensation to form on the inner surface of the Analysis enclosure. This occurs under certain environmental conditions and does not affect the performance or reliability of the product.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 14 of 92
4 COMPLIANCE
The product is designed to meet the following type tests as listed in Table 4-1.
Table 4-1: Type tests
CATEGORY STANDARD CLASS/LEVEL TEST
EMC Emissions EN 61326-1:2006
CISPR 11 A Radiated & Conducted Emissions
FCC Part 15 Meets the requirements of A
Radiated & Conducted Emissions
EN 61000-3-2 A Harmonic Current Emissions Limits
EMC Immunity EN 61326-1:2006
IEC 61000-6-5: 2015
EN 61000-4-2 IV Electrostatic Discharge
EN 61000-4-3 III Electromagnetic Field Immunity
EN 61000-4-4 III Electrical Fast Transients
EN 61000-4-5 III Surge Immunity
EN 61000-4-6 III Conducted RF Immunity
EN 61000-4-8 IV & V Magnetic Field Immunity
EN 61000-4-11 III Voltage Dips & Interruptions
IEC 61000-4-12 2.5 kV & 1 kV Oscillatory Wave
IEC 61000-4-16 A Mains frequency voltage
EN 60255-5 5 kV, 2 kV & 500 V DC
Impulse, Dielectric & Insulation resistance testing
Environmental IEC 60068-2-1 −40 °C Cold
IEC 60068-2-2 55 °C Dry Heat
IEC 60068-2-6 10 – 500 Hz, 0.5 g operation
10 – 500 Hz, 1 g endurance
Vibration
IEC 60068-2-30 55 °C, 95% RH Damp Heat
EN 60529 IP56 Degree of Protection
Safety IEC 61010-1 2010
EN 61010-1 2010
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 15 of 92
5 POWER
The product is wired directly to the mains so is continually powered on. The mains fuse
holder for the product is shown in Figure 5-1 and is located towards the bottom right-hand
side of the Hub module.
Figure 5-1: Fuse holder
The product uses four external sunlight-visible LEDs on the front door. Each LED has two
states – ‘Off’ (-) or ‘On’ as outlined in Table 5-1.
Table 5-1: External LED status indicators
Mode Alarm
red LED
Caution
amber LED
Power
green LED
Service
blue LED
Power Off - - - -
Normal - - On -
Alarm On - On -
Caution - On On -
Service - - On On
Fuse holder
Live Neutral Earth
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 16 of 92
6 HMI
6.1 Introduction
The local HMI features an integrated 7 in. colour LCD panel with resistive touch screen and
embedded webserver. The remote HMI is via a wireless comms option (or direct USB
connection) to a web browser. The latter being the preferred means of interaction with the
product since it offers the convenience of accessing the product from anywhere using a full
screen web browser. The remote HMI is optimised for Chrome, but has also been tested in
Chrome, Firefox and Internet Explorer. The local HMI allows operators to interact directly
with the product onsite without additional equipment. However, the local HMI facility is
intended as an alternative or secondary access method in situations where network
connectivity is unavailable.
To prevent exposure of the internal equipment to extreme weather or other
adverse environmental conditions, ensure additional cover is in place prior to
opening the door.
The LCD panel is in the Hub module and is visible when the door is open as shown in Figure
6-1.
Figure 6-1: Inside the Hub – LCD top left
The LCD and web server are powered on by default as soon as power is supplied to the
product. Access to the HMI can be gained locally via the resistive touch screen (using a
finger or stylus) or remotely through the Web from any computer. Both HMI experiences
are comparable with a similar look and feel.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 17 of 92
Note: This guide uses screenshots from the remote Web access HMI. The images rendered on the local HMI are similar, but some have a different layout due to the smaller screen.
Note: This guide displays screens from an Administrator login. All user logins have a similar look and feel, but some features are dependent on the type of user.
Note: If there are any rendering issues on the remote HMI, press Ctrl + F5 to refresh.
Note: If using Internet Explorer 11, ensure that the option for ‘Compatibility View’ is disabled.
6.2 Connections
The remote HMI can also be accessed from a laptop via a direct physical connection to the
product. The product ships with the default IP address as shown in Figure 6-2. Use either
an Ethernet or USB cable to make the connection as shown in Figure 6-2.
Figure 6-2: Ethernet / USB HMI connection
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 18 of 92
6.3 Start-Up Procedure
When the product is powered on or rebooted, the PGA takes several minutes to initialise. If
using the remote access HMI, the icon denotes that the initialization process is not yet
complete.
6.4 Login
The log-in page prompts for a username and password as shown in Figure 6-3. The product
ships with a default username and password that can be changed after initial login.
Figure 6-3: Log-in page
The system supports three roles with different levels of access as outlined in Table 6-1.
Table 6-1: User access rights
Role Access
Observer View information only (includes downloading if using the remote HMI)
Operator View information and make configuration changes.
Administrator View information, make configuration changes and perform user administration e.g. change passwords.
Note: The session inactivity timeout is 10 minutes.
The Administrator can omit to set a password for the ‘Observer’ role. This means anyone
with physical access to the product or a connected computer can observe the gas levels
and measurements etc. without the need to supply a password. See Section 6.11.7 for user
administration details.
The opening page of the local HMI presents a Quick Access page as shown in Figure 6-4,
whereas the remote access HMI presents a detailed dashboard as shown in Figure 6-5. The
header on each page shows the signal strength, username and menu bar.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 19 of 92
Figure 6-4: Local HMI: Quick Access page
Note: For manual sampling HMI functionality, see Section 7.2.
6.5 Dashboard
After a successful login, the remote HMI displays the Dashboard page in Normal Mode as
shown in Figure 6-5. The Dashboard page displays details of the Last DGA measurement, a
Quick Access panel, System Information and a trend chart below.
Note: The dashboard can be toggled between Normal Mode and Rapid Mode. See Section 6.5.1.3.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 20 of 92
Figure 6-5: Dashboard
The Last DGA Measurement panel shows the measurement date and time stamp, gas
levels (with measurements in PPM) displayed numerically and represented graphically on a
bar chart marked with the configured Caution (H for High) and Alarm (HH for High High)
levels. Blue signifies a reading within the normal limits, yellow a caution — the reading has
exceeded the High (H) level, and red an alarm – the reading has exceeded the High-High
level. Rest the pointer on any gas to obtain the full name in a tooltip. After the next
measurement completes, the details automatically update.
The System Info gives the current date, time, product state, scheduler mode (Normal,
Alarm, Caution) and next scheduled measurement. Indicators show the status of the alarm,
caution and service LEDs as well as the six relays. There is also a free text ID field to assign
a meaningful name to the product. The default is the product’s serial number. Note: Only
Operator or Administrator changes will be saved. The product’s serial and firmware version
numbers are also listed.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 21 of 92
A variety of trend charts are available to choose from — Historical, Thermal, Humidity, and
RTD Sensor. The default trend chart is an Historical Chart that plots selected gas readings
over time. Use the gas legend to identify the gas and the date selector control to change
the timeframe. Rest the pointer on any data point on a plot line to obtain a tooltip with a
timestamped gas value. Click a gas label on the legend to toggle the display of the plotted
gas on or off.
6.5.1 Quick Access
The Quick Access panel in the centre of the HMI as shown in Figure 6-6 offers additional
functionality. Note: Some features are disabled as they are still in development.
Figure 6-6: Quick Access
The following Quick Access features are available:
6.5.1.1 Diagnostics
Click Diagnostics to access the Duval Triangle or Gas Ratio diagnostics.
6.5.1.2 Download Log
Click Download Log to access the available log files. Choose from a System Log, TFD Log
and CFR Log. These service files contain product performance data that is used to check
product functionality. If requested, download and send the relevant log files to the GE M&D
Service Support team for analysis.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 22 of 92
6.5.1.3 Enter Rapid Mode
Rapid mode is a means of on demand sampling and uses a smaller quantity of oil to deliver
a result in around 30 minutes. Rapid mode measures four critical gases — hydrogen,
acetylene, carbon monoxide, carbon dioxide — and water, and charts the measurements
below. The ability to invoke successive quick measurement cycles over a short period can
indicate the speed at which a fault is progressing.
Note: Rapid mode measurements are performed independently of all other measurements and do not affect alarms, relays or calculations.
Click Enter Rapid Mode to access the rapid mode options. The Quick Access panel
displays the available options as shown in Figure 6-7.
Figure 6-7: Quick Access – Rapid Mode
6.5.1.3.1 Start 1x Rapid Mode
To start a single rapid mode measurement, click Start 1x Rapid Mode.
6.5.1.3.2 Start 4x Rapid Mode
To start four rapid mode measurements in succession, click Start 4x Rapid Mode.
6.5.1.3.3 Stop Measurement
To cancel an active Rapid Mode measurement, click Stop Measurement.
6.5.1.3.4 Exit Rapid Mode
To exit Rapid Mode and return to the main dashboard, click Exit Rapid Mode.
6.5.1.4 Start Measurement
Choose Start Measurement to manually initiate a measurement cycle. The state in the
System Info pane updates to reflect that a measurement has started.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 23 of 92
6.6 GAS / Diagnostics
6.6.1 Active Alarms
Select GAS / Diagnostics > Active Alarms to open the Active Alarms page as shown in
Figure 6-8.
Figure 6-8: Active Alarms
Note: Deadbands are specified in the units relating to what is measured. E.g. PPM for gas, degrees Celsius (°C) for temperature. See Section 6.8 for a definition of deadbands.
6.6.2 Measurements
Select GAS / Diagnostics > Measurements to open the Measurements page as shown in
Figure 6-9. The Measurements page reports the values of all variables from a measurement
cycle. The most recent measurement cycle is listed first. Use the scroll buttons to navigate
to previous measurements.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 24 of 92
Figure 6-9: Measurements
6.6.3 Duval Triangle
Select GAS / Diagnostics > Duval to open the Duval Diagnostic page as shown in Figure
6-10.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 25 of 92
Figure 6-10: Duval Diagnostic
6.6.4 Gas Ratio
Select GAS / Diagnostics > Gas Ratio to open the Gas Ratio page as shown in Figure 6-11.
Figure 6-11: Gas Ratio
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 26 of 92
6.6.5 Scheduler
Select DGA > DGA Scheduler to open the DGA Scheduler page as shown in Figure 6-12.
Use this page to schedule a DGA measurement cycle.
Figure 6-12: DGA Scheduler
6.7 Calculations
6.7.1 Gas Ratios
Select Calculations > Gas Ratios to open the Gas Ratio Settings page as shown in Figure
6-13.
Figure 6-13: Gas Ratio Settings
Choose the relevant > icon to expand the ratio definition as shown in Figure 6-14.
Figure 6-14: Gas Ratio Settings – Ratio 1 definition
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 27 of 92
Type a Ratio Name and select the relevant gases.
Note: Nitrogen (N2) is available as a choice only if Nitrogen Measurement is enabled.
Refer to the IEEE® C57.104 and IEC® 60599 standards for alarm settings or Appendix E.
6.7.2 Relative Saturation
Select Calculations > Relative Saturation to open the Relative Saturation settings page
as shown in Figure 6-15.
Figure 6-15: Relative Saturation Settings
6.7.3 Gas Rate of Change
Select Calculations > Gas Rate of Change to open the Gas RoC Configuration page as
shown in Figure 6-16. See Appendix E for more details on settings.
Figure 6-16: Gas RoC Configuration
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 28 of 92
6.7.4 Analog Inputs RoC Configuration
Select Calculations > Analog Inputs Rate of Change to open the Analog Inputs RoC
Configuration page as shown in Figure 6-17. The default is for a CT to be installed on
Analogue Input 1. The product supports up to five additional analogue inputs.
Figure 6-17: Analog Inputs Rate of Change Configuration
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 29 of 92
6.8 Alarms
Perception allows deadbands to be defined for each alarm. A deadband establishes
another limit for clearing the alarm and prevents an alarm returning to normal until the
alarm condition is cleared by the deadband. This reduces the number of false alarms and
the amount of chattering. For example, an alarm triggered at 200 ppm with a deadband of
3 will remain in the alarm state until the value falls below 197 ppm.
Note: Deadbands are specified in the units being measured. Gases are specified in PPM, temperature in degrees Celsius.
The host network must have the capability to transmit alarms and critical
messages during times of heavy use, including but not limited to network
storm conditions. If this requirement is not met or has not been tested, the
notification of hazardous gas levels could be delayed by a network slowdown.
6.8.1 Gases
Select Alarms > Gases to open the Gas Alarms Configuration page as shown in Figure
6-18.
Figure 6-18: Gas Alarms Configuration
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 30 of 92
Click on a gas alarm icon > e.g. Hydrogen to configure the type of alerts as shown in Figure
6-19.
Figure 6-19: Hydrogen alerts
6.8.2 Gas Ratios
Select Alarms > Gas Ratios to open the Gas Ratio Alarms Configuration page as shown in
Figure 6-20.
Figure 6-20: Gas Ratio Alarms Configuration
Click the relevant ratio icon > e.g. ‘D1 and R1 High-High’ to expand the ratio alarm
definition and configure the type of alerts as shown in Figure 6-21.
Figure 6-21: Gas Ratio Alarms Configuration – Ratio 1 High-High Gas Rate of Change
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 31 of 92
6.8.3 Gas Rate of Change
Select Alarms > Gas Rate of Change to open the Gas RoC Configuration page as shown in
Figure 6-22.
Figure 6-22: Gas RoC Configuration
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 32 of 92
6.8.4 Relative Saturation
Select Alarms > Relative Saturation to open the Relative Saturation Alarms
Configuration page as shown in Figure 6-23.
Figure 6-23: Relative Saturation Alarms Configuration
Click on a Relative Saturation icon > e.g. High-High to expand the relative saturation
definition as shown in Figure 6-24.
Figure 6-24: Relative Saturation Alarms Configuration – High-High
6.8.5 Analog Inputs
Select Alarms > Analog Inputs to open the Analog Inputs Alarms Configuration page as
shown in Figure 6-25.
Figure 6-25: Analog Inputs Alarms Configuration
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 33 of 92
6.8.6 Analog Inputs Rate of Change
Select Alarms > Analog Inputs Rate of Change to open the Analog Inputs RoC Alarms
Configuration page as shown in Figure 6-26.
Figure 6-26: Analog Inputs RoC Alarms Configuration
6.8.7 Digital Inputs
Select Alarms > Digital Inputs to open the Digital Inputs Alarms Configuration page as
shown in Figure 6-27.
Figure 6-27: Digital Inputs Alarms Configuration
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 34 of 92
6.8.8 Digital Inputs Transition Total
Select Alarms > Digital Inputs Transition Total to open the Digital Inputs Transition
Total Alarms Configuration page as shown in Figure 6-28.
Figure 6-28: Digital Inputs Transition Total Alarms Configuration
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 35 of 92
6.9 Peripherals
6.9.1 Peripheral Scheduler
Select Peripherals > Peripheral Scheduler to open the Peripheral Scheduler page as
shown in Figure 6-29.
Figure 6-29: Peripheral Scheduler
The Peripheral Scheduler allows the Measurement Time Interval to be set to 5, 10, 15 or 20
minutes.
6.9.2 Analog Inputs
Select Peripherals > Analog Inputs to open the Analog Inputs Configuration page as
shown in Figure 6-30.
Figure 6-30: Analog Inputs Configuration
If there are analogue cards fitted to the I/O PCB, these will auto populate with default
values as shown in Figure 6-31. The next step is to configure each card to the required
sensor.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 36 of 92
Figure 6-31: Analog Input 4 (4-20 mA Temperature Sensor)
6.9.3 Digital Inputs
Select Peripherals > Digital Inputs to open the Digital Input Configuration page as shown
in Figure 6-32.
Figure 6-32: Digital Input Configuration
6.9.4 Input Measurements
Select Peripherals > Input Measurements to open the Input Measurements page as
shown in Figure 6-33.
Figure 6-33: Input Measurements
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 37 of 92
6.10 Settings
6.10.1 Communications
Select Settings > Communications to open the Communications Settings page as shown
in Figure 6-34.
Figure 6-34: Communications Settings
If a GPRS modem is fitted and the appropriate carrier sim is installed, the IP address also
displays.
See Appendix A.2 for more details on the external interfaces and supported protocols.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 38 of 92
6.10.2 Date & Time
Select Settings > Date & Time to open the Date & Time page as shown in Figure 6-35.
Figure 6-35: Date & Time
6.10.3 SMS Alerting
Select Settings > SMS Alerting to open the SMS Alerting page as shown in Figure 6-36. In
this example, the system is configured to send ‘Richard’ an SMS message whenever a
‘System Error’ is raised.
Figure 6-36: SMS Alerting
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 39 of 92
6.10.4 Firewall
To create a custom security policy, select Settings > Firewall to open the Firewall Settings
page as shown in Figure 6-37. Rules can be added, edited or deleted to create a suitable
access policy for each type of interface. These rules are used to block unused ports and
specify distinct firewall actions (accept, reject or drop) based on the IP address or port.
Figure 6-37: Firewall configuration
See Appendix A.4 for more details on firewall configuration.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 40 of 92
6.10.5 Communication Services
Select Settings > Communication Services to open the Communication Services page as
shown in Figure 6-38.
Note: This functionality is available only to ‘Operator’ and ‘Administrator’ users.
All configuration settings specified on this page apply to all interfaces (Ethernet, USB and
GSM-GPRS modem).
Figure 6-38: Communication Services
Select the relevant slider button to enable/disable the relevant communication service. E.g.
Modbus-TCP, SSH (Secure Shell) and HTTPS — but do not rely on the firewall settings.
To implement a custom security policy, upload a new certificate to replace the GE self-
signed certificate and enable HTTPS requests only.
A certificate can be uploaded from a USB drive. In the Upload certificate field, click the
Select file button, select the new certificate (PEM file) and click Open.
Click the ‘Save’ button in the application header to apply the changes and then restart
the DGA 900.
Note: SSL certificates are small data files that digitally bind a cryptographic key to an organization's details. When installed on a web server, it activates the padlock and the HTTPS protocol and allows secure connections from a web server to a browser.
Note: If HTTPS is disabled, the certificate will be applied when HTTPS is enabled.
Note: The HMI has no automatic redirection between HTTP and HTTPS (or vice versa). This results in the following browser message “Site cannot be reached over HTTP”.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 41 of 92
6.11 Service
6.11.1 Measurement
Select Service > Measurement to open the Measurement Settings page as shown in
Figure 6-39. The Normalization Temperature is a thermostatically controlled internal target
temperature for the Analysis module. Depending on the region, one of two temperatures
can be set 0 °C or 20 °C.
Figure 6-39: Measurement Settings
The following Measurement Flags are available:
Nitrogen Enabled — displays measurement data for nitrogen. This also activates the
display of Total Dissolved Gases (TDG) (disabled by default).
TDG Enabled — lists the Total Dissolved Gases (TDG). Inactive if nitrogen measurement is
not enabled. TDG = H2 + CO2 + CO + C2H4 + C2H6 + CH4 + C2H2 + O2 + N2.
TDH Enabled — lists the Total Dissolved Hydrocarbons. (TDH). TDH = CH4 + C2H2 + C2H4 +
C2H6.
Estimated Safe Handling Limit (ESHL) – expresses the concentration of gases contained
within the oil sample as a percentage. This is a safety indicator and is used to assess the
associated risk of the oil sample. ESHL = H2/LevelH2 + CH4/LevelCH4 + CO/LevelCO +
C2H6/LevelC2H6 + C2H4/LevelC2H4 + C2H4/LevelC2H4.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 42 of 92
6.11.2 Controller Reprogramming
Consult with Technical Support to confirm the availability of new firmware for the
Controller PCB. Upgrade to the latest version of the firmware via an Ethernet connection to
avail of new features.
Note: A firmware upgrade resets passwords back to their default values.
To upgrade the Controller PCB firmware, select Service > Controller Reprogramming to
open the Controller Reprogramming page as shown in Figure 6-40.
Figure 6-40: Controller Reprogramming
Drag and drop the firmware file into the circle or click in the circle to select the file. Click
Upgrade and the status information and a progress bar display as shown in Figure 6-41.
Figure 6-41: Upgrade in progress
Once complete, the firmware image is applied and the system restarts. On initial power up,
the product’s LCD screen remains blank, but the ‘On’ heartbeat LED and ‘Boot’ LED
illuminate (solid blue and red respectively). After a moment, the Boot LED switches off and
the ‘On’ heartbeat LED flashes blue to indicate normal operation. The restart sequence
takes approximately 3 minutes after which the onboard HMI loads up.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 43 of 92
6.11.3 I/O PCB Reprogramming
Consult with Technical Support to confirm the availability of new firmware for the I/O PCB.
Upgrade to the latest version of the firmware via an Ethernet connection to avail of new
features.
Note: A firmware upgrade resets passwords back to their default values.
To upgrade the I/O PCB firmware using an Ethernet connection, select Service > I/O Board
Reprogramming to open the I/O Board Reprogramming page as shown in Figure 6-42.
Figure 6-42: I/O Board Reprogramming
Drag and drop the firmware file into the circle or click in the circle to select the file. Click
Upgrade and the status information and a progress bar displays as shown in Figure 6-43.
Figure 6-43: Upgrade in progress
Once complete, the firmware image is applied and the system restarts. On initial power up,
the product’s LCD screen remains blank, but the ‘On’ heartbeat LED and ‘Boot’ LED
illuminate (solid blue and red respectively). After a moment, the Boot LED switches off and
the ‘On’ heartbeat LED flashes blue to indicate normal operation. The restart sequence
takes approximately 3 minutes after which the onboard HMI loads up.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 44 of 92
6.11.4 Oxygen Sensor
Select Service > Oxygen Sensor to open the Oxygen Sensor settings page as shown in
Figure 6-44.
Figure 6-44: Oxygen Sensor
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 45 of 92
6.11.5 Gas Normalization
Select Service > Gas Normalization to open the Gas Normalization Settings page as
shown in Figure 6-45.
Figure 6-45: Gas Normalization Settings
6.11.6 Factory
Select Service > Factory to open the Factory Settings page as shown in Figure 6-46.
Figure 6-46: Factory Settings
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 46 of 92
6.11.6.1 Alarm Reflash
The Alarm Reflash option ensures that a relay’s digital output reflashes (if already
activated) when another source triggers the same relay. An alarm reflash applies only to
relays 1-6 and is achieved by deactivating the relevant digital output for a duration of 1
second before reactivating it to achieve a flashing effect. This signifies to an operator or
control room in real time that multiple sources have triggered the same relay.
Note: This ensures that further alarms raised by the same source have no further effect.
6.11.6.2 Clear Historical Data Only
Clears all historical data — DGA measurements, alarm data and Transopto measurements.
Table 6-2 outlines the type of data items that get erased.
6.11.6.3 Reset Configuration Settings
Clears all historical data described previously and resets configuration settings (except
Communications) to the default state. Table 6-2 outlines the type of data items that get
erased.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 47 of 92
6.11.6.4 Factory Reset
Clears everything — historical measurement data, configuration settings and
communication settings, so that the product returns to the initial factory state. Table 6-2
outlines the type of data items that get erased.
Table 6-2: Factory Settings: Data and configuration cleardown
Clear Historical Data Only
Reset of Configuration Settings
Full Factory Reset
DGA
Measurements
Scheduler
Calculations
Gas ratios
Relative Saturation
Gas RoC
Transopto RoC
Analog Input RoC
Alarms Alarms
Peripherals
Transopto Channels
Transopto Measurements
Analog Inputs
Digital Inputs
Settings Communications
Service
Measurement
Oxygen Sensor
Transopto
Gas Normalization
Factory
6.11.6.5 Simulation Mode
The dashboard environment can be switched to Simulation Mode to simulate a realistic
live environment before the product is physically installed or any measurement cycles have
started.
Click Simulation Mode to see the dashboard view populated with mock data. To
differentiate between real and simulation data, the colour scheme for the bar chart
simulation data uses grey scales and the DGA 900 state changes to ‘PGA simulation mode’
as shown in Figure 6-47.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 48 of 92
Figure 6-47: Simulation mode
This allows the HMI to display realistic sample data for showcasing e.g. training and testing
purposes without affecting real-time data, but has no validity since it does not relate to
any underlying measurement cycles.
6.11.6.6 Restart Device
Some configuration changes require a device restart. Click Restart Device to restart the
device and then click Restart to confirm as shown in Figure 6-48.
Figure 6-48: Restart the device
6.11.7 User Administration
Select Service > User Administration to open the User Administration page as shown in
Figure 6-49.
Figure 6-49: User Administration
Click Change Password to enter a new password. On typing, the strength of the password
is assessed as shown in Figure 6-50.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 49 of 92
Figure 6-50: Change Password
A password strength is categorised as listed in Table 6-3.
Table 6-3: Password Strength
Password Strength Rating Description
Not enough No password entered.
Weak 4 characters or more.
Medium 7 characters or more.
The string must contain at least one each of the following characters: lowercase alphabetical, uppercase alphabetical and numeric.
Strong 8 characters or more.
The string must contain at least one each of the following characters: lowercase alphabetical, uppercase alphabetical, numeric and special.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 50 of 92
6.12 TransOpto
6.12.1 Measurements
Select TransOpto > Measurements to open the TransOpto Measurements page as
shown in Figure 6-51.
Figure 6-51: TransOpto Measurements
6.12.2 Rate of Change
Select TransOpto > Rate of Change to open the TransOpto RoC Configuration page as
shown in Figure 6-52.
Figure 6-52: TransOpto RoC Configuration
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 51 of 92
6.12.3 Alarms
Select TransOpto > Alarms to open the TransOpto Alarms Configuration page as shown
in Figure 6-53.
Figure 6-53: TransOpto Alarms Configuration
Click on a channel alarm icon > e.g. ‘Channel 1 High’ to configure the type of alerts as
shown in Figure 6-54.
Figure 6-54: Channel 1 High alerts
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 52 of 92
6.12.4 Rate of Change Alarms
Select TransOpto > Rate of Change Alarms to open the TransOpto RoC Alarms
Configuration page as shown in Figure 6-55.
Figure 6-55: TransOpto RoC Alarms Configuration
Click on a channel alarm icon > e.g. ‘Channel 2 High-High’ to configure the type of alerts as
shown in Figure 6-56.
Figure 6-56: Channel 2 High-High alerts
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 53 of 92
6.12.5 Channels
Select TransOpto > Channels to open the TransOpto Channels Settings page as shown in
Figure 6-57.
Figure 6-57: TransOpto Channels Settings
6.12.6 Settings
Select TransOpto > Settings to open the TransOpto Settings page as shown in Figure
6-58.
Figure 6-58: TransOpto Settings
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 54 of 92
6.13 Logout
Select the Logout option below the username as shown in Figure 6-59.
Figure 6-59: Logout
The Log-in page displays as shown in Figure 6-60.
Figure 6-60: Log-in page
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 55 of 92
6.14 Shutdown Procedure
If the product is to be shut down, perform the following steps:
Log in to the DGA 900 to observe the operating state on the dashboard as shown in
Figure 6-61.
Figure 6-61: System Info – Standby
If the product is in “Standby” state, then proceed to shut down the product as follows:
− Turn the external switch or circuit breaker to the ‘Off’ position.
− Turn the transformer oil valves that connect to the input and output of the product
to the ‘Closed’ position.
If the product is performing a measurement as shown in Figure 6-62, then
− Either wait for the product to finish the active measurement or manually stop the
measurement. For the latter, choose Stop Measurement as shown in Figure 7-10.
− The DGA 900 state changes to “Oil Draining”. This process may take several minutes
after which the product state returns to “Standby” as shown in Figure 6-61.
− Turn the external switch or circuit breaker to the ‘Off’ position.
− Turn the transformer oil valves that connect to the input and output of the product
to the ‘Closed’ position.
Figure 6-62: Measurement started
When the product is to be powered up again, first turn the transformer oil valves that
connect to the input and output of the product to the ‘Open’ position. Then turn ‘On’ the
external switch or circuit breaker. The product will be ready to resume taking scheduled
readings.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 56 of 92
6.15 Error Notifications
The Measurements page reports all errors as shown in Figure 6-63: If there are no errors in
the current measurement cycle, the results are displayed as normal. Errors for the most
recent measurement cycle are listed first. Use the navigation buttons to move through the
various measurement cycles and examine any errors encountered in previous
measurement cycles.
Figure 6-63: PGA and Oxygen Sensor Error States
Errors are reported using a sequence of double-digit codes for the PGA and the Oxygen
sensor (if enabled). The PGA Error State denotes the most recent state within the
measurement cycle where the error occurred. All errors are listed as error codes and the
associated hexadecimal in brackets allows the most recent state to be identified. See
Section 6.15.1 for a definition of the error codes.
Note: The Customer Service Centre requires both the state code(s) and error code(s) to interpret any error.
For example, Figure 6-64 shows that the product has encountered two PGA errors. The
PGA Error code 04 denotes that there is an issue with the gas flow in the Main
Measurement state (23) and error code 13 denotes that the pump pressure is too low.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 57 of 92
Figure 6-64: PGA Errors
Note: If the Oxygen sensor is not enabled, no Oxygen sensor state or error codes display.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 58 of 92
6.15.1 Error Codes
Table 6-4 lists the PGA error codes. All the service alarm error codes are accompanied by
illumination of the blue Service light that is visible on the front door of the product.
Note: Error codes are offset by 1 from the Modbus register bit numbers.
Note: This information relates to PGA firmware version 18.1.5 for DGA 900.
Table 6-4: PGA Errors
Code Error Note
PGA Connection Error
Timeout
01 PGA power supply voltage too low
02 PGA chopper frequency outside range
03 PGA IR-source outside range
04 Gas flow lower than limit
05 Background noise/vibration too high
06 Microphone test failed
07 Not level sensor 1 pulses (level)
08 Not level sensor 3 (drain)
09 Fill level shows Oil
10 Over Fill shows Oil
11 PGA Air temperature outside limits
12 Bad communication with control PCB
13 Gas leak test: Pump pressure too low
14 Gas leak test: Pressure decay too high
15 Unusual ambient gas measurements
16 Oil temperature too low
17 Oil temperature too high
18 Oil pressure too low Check that all oil supply valves are open.
19 Oil pressure too high Check that all oil return valves are open.
20 Oil pump tacho count too high
21 Oil pump pressure too low
22 Oil pump speed out of range
23 Manual oil sampling switch
24 Oil pump tacho count too low
25 Oil pump not turning
26 - Not used.
27 Temperature Sensor(s) 1 disconnected
28 Temperature Sensor(s) 2 disconnected
29 Drain level shows oil
30 Conditioned oil temp. outside limits
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 59 of 92
Table 6-5 lists the Oxygen sensor error codes.
Table 6-5: Oxygen sensor error codes
Code Error Note
0 Oxygen sensor measurement has finished with no error.
1 System error. Internal state. Initial state of state machine.
2 System error. Internal error. Oxygen sensor thread is busy.
3 Oxygen sensor is disabled.
4 Measurement cancelled by user.
5 System error. Measurement just started.
6 PGA measurement has finished before we achieve state 6. We could not run Oxygen sensor measurement.
7 In attempt to write -1 to PGA Oxygen Saturation register, writing fails because the read value is not the same as which has been written.
8 In attempt to clear EE (Electronically Erasable) Store bit in Oxygen sensor Control register, writing fails due to a communication error.
9 PGA Oil Temperature reading fails due to a communication error.
10 Oxygen sensor Oil temperature writing fails due to a communication error.
11 Oxygen sensor (Dissolved Oxygen) DO Trigger command writing fails due to a communication error.
12 Oxygen sensor Status DO_DATA_RDY is not set.
13 Oxygen sensor DO Error Code reading fails due to a communication error.
14 Oxygen sensor Oxygen reading fails due to a communication error.
15 PGA Oxygen Saturation writing fails due to a communication error.
16 Reading PGA state fails due to a communication error.
17 PGA Transfix state is greater than 34. We lose time to write Oxygen Saturation and measurement result may have an error.
18 Oxygen sensor DO Error Code register is not null. Oxygen sensor has an error during measurement.
6.15.2 Other Notifications
If the onboard MicroSD card has exceeded 80% of its storage capacity, the SD card icon
displays. Click the icon to reveal the message as shown in Figure 65. The MicroSD card
should be replaced as soon as possible.
Figure 65: MicroSD card memory usage
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 60 of 92
7 MANUAL OIL SAMPLING
A manual oil sample can be taken via the following arrangement.
Before commencing work, ensure the use of suitable protective gloves, such as nitrile rubber.
7.1 Sampling Arrangement
The product has one manual oil sampling port fitted to the base. This consists of a quick-
connect body and a captive body-protector fitting as shown in Figure 7-1. The product
ensures that there is fresh oil at the sampling point when the sampling process takes
place.
Figure 7-1: Oil filter and oil ports (front view of Analysis module)
A male quick-connect fitting and valve assembly is provided in the product installation kit.
GE also recommends the use of a 50-mL ground glass syringe.
Note: The manual oil sampling arrangement and the quick-connect sampling port must not be cleaned with any type of solvent as this could affect results for subsequent oil samples.
Oil filter
Manual sampling port
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 61 of 92
Figure 7-2: Valve orientation
Figure 7-3: Sampling assembly
Figure 7-4: Luer fitting on assembly
7.2 Local HMI for manual sampling
The manual sampling functionality is implemented on the Quick Access page of the local
HMI only as shown in Figure 7-5. Press Manual Sampling.
Note: Before proceeding, ensure that the sampling assembly is fitted as outlined in Section 7.1.
Figure 7-5: Local HMI: Quick Access
CLOSED
Oil sampling valve assembly with Luer fitting
OPEN
Quick-connect body protector with pull-down collar for release
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 62 of 92
The Manual Sampling page displays. Press Start as shown in Figure 7-6 to start the manual
sampling process.
Figure 7-6: Manual Sampling
The oil purging process starts. Allow several minutes for the oil to purge and then press
Continue when done.
Figure 7-7: Purging Oil
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 63 of 92
The system prompts the user to take the manual oil sample. See Section 7.3 for more
details on the sampling process.
Press Finish to return to the home page as shown in Figure 7-8.
Figure 7-8: Take manual oil sample
If the product is already performing a measurement, manual sampling is prevented as
shown in Figure 7-9. Press Exit to return to the Quick Access page.
Figure 7-9: Manual Sampling cannot be started
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 64 of 92
Either wait for the current measurement cycle to finish or stop the current measurement
cycle. To stop the current measurement cycle, return to the Dashboard and press Stop
Measurement as shown in Figure 7-10.
Figure 7-10: Dashboard: Stop Measurement
The product is now ready to take a manual sample.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 65 of 92
7.3 Sampling Process
Logon to the product using the local HMI and observe the product state on the Dashboard.
The product state must be in Standby to initiate manual sampling. Figure 7-11 and the
accompanying steps detail the process to obtain a manual oil sample.
Figure 7-11: Manual oil sampling flowchart
Close sampling valve
Remove male fitting and valve assembly
Replace quick-connect body
protector
Standby state Measurement state
Press Stop Measurement
Oil Drains
Standby state
Attach male fitting and valve assembly
with valve closed
Press Manual
Sampling, & Start
Wait at least several minutes for oil to
purge…
Press Continue
Press Finish
Remove quick-connect body
protector
Open sampling valve and take oil
sample
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 66 of 92
Observe the product state on the HMI Dashboard page. Either wait for the product to
return to the Standby state or use the HMI to stop the current measurement cycle.
If the product is in “Standby” state, proceed to step 3. If the product is in a
measurement state, manual sampling is prevented.
Navigate to the Dashboard page and press Stop Measurement. The state changes to
“Oil draining”. If there is oil in the headspace, the draining process may take several
minutes. The product returns to “Standby” state.
On the local HMI Quick Access page, press Manual Sampling.
When the product is in “Standby” state, remove the quick-connect body protector by
pulling the collar down.
Fit the male quick-connect fitting and valve assembly to the correct quick-connect body
on the base of the product as shown in Section 7.1. Ensure that the valve is closed to
prevent oil leakage.
Press Start.
An oil line purging process starts. The product state reads “Oil purging”. To ensure
accurate results, oil must be adequately purged before sampling begins. This brings
fresh oil from the transformer to the manual oil sampling port. Typically this means
waiting approximately 5–10 minutes, but the recommended wait time can vary
depending on the installation (longer tubing and lower temperatures can increase the
purge duration). Consult with Technical Support.
Press Continue when done. The product state reads “Oil sampling”. Note: This indicates
that the oil sampling process can begin.
Remove the Luer fitting cap, connect the oil sampling equipment e.g. syringe, and
perform the oil sampling as per standard process and procedures.
When finished sampling, close the valve and disconnect the oil sampling equipment.
Remove the male fitting and valve assembly, and replace the body protector fitting on
the quick-connect body.
Press Finish when done. The product state returns to “Standby”. Note: If left in the “Oil
sampling” state, the product reverts to “Standby” after one hour. Measurement then
begins at the next scheduled measurement time.
To start a measurement immediately, press the Start button.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 67 of 92
8 COMMUNICATIONS
See the Communications section of ‘MA-024 - DGA 900 Installation Manual’ for available
communication options.
8.1 DNP3
Refer to the document CG-060 – DGA 900 DNP3 Objects & IO Points Index.
8.2 IEC 61850
Refer to the document DGA 900 – IEC 61850 Edition 2.
8.3 Modbus Protocol
Refer to the document CG-062 – DGA 900 Modbus IO Registers.
8.4 HTTP / HTTPS Protocol
The HTTP and HTTPS protocols are used for communication with the Perception software
suite. The login credentials for such communication are independent of the local and
remote HMI. The login credentials to communicate with Perception from the DGA 900 are
as follows:
Username: perception
Password: perception
Refer to the Perception software documentation (v 1.22.3 or later) for further details.
9 TECHNICAL SUPPORT
For technical support, please contact the GE Customer Service Centre (24 hours a day, 365
days a year):
T +44 1785-250-070 (United Kingdom)
T 1-800-361-3652 (United States and Canada)
T +1 514-420-7460 (worldwide)
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 68 of 92
Appendix A Security Configuration
A.1 Introduction
This appendix addresses security configuration for remote operations and the software
firewall.
A.1.1 General Recommendations
GE recommends the ‘Defence in depth’ approach. The Defence in depth approach
advocates multiple layers of independent security controls to make it as difficult as
possible for an attack to succeed. When using GE products and solutions, consider
adopting the following security best practices:
▪ Care must be taken when connecting hardware to a wide area network including but not limited to a corporate network or the Internet at large. The network segmentation and firewall rules at each network interface must be carefully considered to reduce the allowed traffic to the bare minimum needed for operation. Access rules customised to the site's specific needs must be used to access devices from outside the local control networks. Care must be taken to control, limit, and monitor all access, using, for example, virtual private networks (VPN) or Demilitarised Zone (DMZ) architectures. If a device is being used in a manner that does not require wide area network access, it is strongly recommended that the device not be connected to any wide area network to reduce the attack surface.
▪ Harden system configurations by enabling/using the available security features, and by disabling unnecessary ports, services, functionality, and network file shares.
▪ Apply all the latest GE product security updates, SIMs, and other recommendations.
▪ Apply all the latest operating system security patches to control systems PCs.
▪ Use antivirus software on control systems PCs and keep the associated antivirus signatures up to date.
▪ Use whitelisting software on control systems PCs and keep the whitelist up to date.
A.1.2 Sample Checklist
This section provides a sample checklist to help guide the process of securely deploying GE
products.
▪ Create or locate a network diagram.
▪ Identify and record the required communication paths between nodes.
▪ Identify and record the protocols required along each path, including the role of each node.
▪ Revise the network as needed to ensure appropriate partitioning, adding firewalls or other network security devices as appropriate. Update the network diagram.
▪ Configure firewalls and other network security devices.
▪ Enable and/or configure the appropriate security features on each GE product.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 69 of 92
▪ On each GE product, change every supported password to something other than its default value.
▪ Harden the configuration of each GE product, disabling unneeded features, protocols and ports.
▪ Test / qualify the system.
▪ Create an update/maintenance plan.
A.2 Communication Requirements
Communication between different parts of a control system is, and must be, supported.
However, the security of a control system can be enhanced by limiting the protocols
allowed, and the paths across which they are allowed, to only what is needed. This can be
accomplished by disabling every communication protocol that isn’t needed on a particular
device, and by using appropriately configured and deployed network security devices (e.g.
firewalls, routers) to block every protocol (whether disabled or not) that doesn’t need to
pass from one network/segment to another.
GE recommends limiting the protocols allowed by the network infrastructure to the
minimum set required for the intended application. Successfully doing this requires
knowing which protocol is needed for each system-level interaction.
A.2.1 External Interfaces
The product features the following external interfaces as shown in Table A-1.
Table A-1: External Interfaces
External interface Comment
RS-485
Ethernet HMI/SSH access
Ethernet Multi-protocol module DNP3/IEC 61850
GSM-GPRS modem
microSD
USB host
USB device USB-Ethernet
A.2.2 Supported Protocols
The product supports the following protocols as shown in Table A-2.
Table A-2: Protocols
Network Layer Protocol
Link ARP
Internet ICMP
IPv4
Transport TCP
Application DHCP Server
SSH
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 70 of 92
HTTP Server
HTTPS Server
Modbus RTU Slave
Modbus TCP Slave
A.3 Secure Remote Operations
Select Settings > Communication services as shown in Figure A-1.
Note: This functionality is available only to ‘Operator’ and ‘Administrator’ users.
Figure A-1: Settings > Communication Services
The Communication Services page displays as shown in Figure A-2. All configuration
settings specified on this page apply to all interfaces (Ethernet, USB and GSM-GPRS
modem).
Figure A-2: Communication Services
Select the relevant slider button to enable/disable the relevant communication service. E.g.
Modbus-TCP, SSH (Secure Shell) and HTTPS — do not rely on the firewall settings.
To implement a custom security policy, upload a new certificate to replace the GE self-
signed certificate and enable HTTPS requests only.
In the Upload certificate field, click the Select file button, select the new certificate (PEM
file) and click Open.
Click the ‘Save’ button in the application header to apply the changes and then restart
the DGA 900.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 71 of 92
Note: SSL certificates are small data files that digitally bind a cryptographic key to an organization's details. When installed on a web server, it activates the padlock and the HTTPS protocol and allows secure connections from a web server to a browser.
Note: If HTTPS is disabled, the certificate will be applied when HTTPS is enabled.
Note: The HMI has no automatic redirection between HTTP and HTTPS (or vice versa). This results in the following browser message “Site cannot be reached over HTTP”.
A.3.1 Enable/disable Modbus-TCP protocol
▪ Use the HMI to login as either ‘Administrator’ or ‘Operator’.
▪ Select Settings > Communication Services.
▪ Select the Modbus-TCP Enable slider button to enable/disable the Modbus-TCP protocol.
▪ Click the ‘Save’ button in the application header to apply the changes.
▪ Restart the DGA 900.
A.3.2 Enable/disable SSH service (root access over SSH)
▪ Use the HMI to login as either ‘Administrator’ or ‘Operator’.
▪ Select Settings > Communication Services.
▪ Select the SSH Enable slider button to enable/disable the Secure Socket Shell service.
▪ Click the ‘Save’ button in the application header to apply the changes.
▪ Restart the DGA 900.
A.3.3 Enable/disable HTTPS protocol
▪ Use the HMI to login as either ‘Administrator’ or ‘Operator’.
▪ Select Settings > Communication Services.
▪ Select the Enable HTTPS slider button to enable/disable the HTTPS protocol.
▪ Click the ‘Save’ button in the application header to apply the changes.
▪ Restart the DGA 900.
Note: The HMI has no automatic redirection between HTTP and HTTPS (or vice versa). This results in the following browser message “Site cannot be reached over HTTP”.
A.3.4 Apply customer certificates for HTTPS
▪ Use the HMI to login as either ‘Administrator’ or ‘Operator’.
▪ Select Settings > Communication Services.
▪ To implement a custom security policy, upload a new certificate to replace the GE self-signed certificate and enable HTTPS requests only.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 72 of 92
In the Upload certificate field, click the Select file button, select the new certificate (PEM file) and click Open.
▪ Click the ‘Save’ button in the application header to apply the changes.
▪ Restart the DGA 900.
Note: If HTTPS is disabled, the certificate will be applied when HTTPS is enabled.
A.4 Software Firewall
The DGA 900 has a built-in firewall that defines the security settings for the various
interfaces. Firewall policies are configured separately for each interface (Ethernet, USB,
GSM-GPRS modem). The DGA 900 ships with a standard GE self-signed certificate with the
firewall enabled by default to accept all HTTP requests. You should customise the firewall.
To create a custom security policy, select Settings > Firewall to open the Firewall Settings
page as shown in Figure A-3.
Figure A-3: Firewall Settings
Rules can be added, edited or deleted to create a suitable access policy for each type of
interface. These rules are used to block unused ports and specify distinct firewall actions
(accept, reject or drop) based on the IP address or port.
A.4.1 Default Policy
The default policy is to accept all incoming requests and applies for all cases not covered
by specific policies. The default policy provides a dropdown list of three options as shown
in Figure A-4.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 73 of 92
Figure A-4: Default policy options
A.4.2 Specific Policies
The specific policy adds exceptions to the default policy.
Click the ‘Create new rule’ button to create a new policy. The rule options are as
shown in Figure A-5.
Figure A-5: Specific policy options
A.4.3 Disable all Connections on a dedicated interface
In the Firewall Settings page, select the interface type e.g. lan and in the Default policy
dropdown, select REJECT as shown in Figure A-6.
Figure A-6: LAN interface
A.4.4 Disable all Connections except HTTPS
In the Firewall Settings page, select the interface type e.g. lan and in the Default policy
dropdown, select REJECT as shown in Figure A-7.
Figure A-7: LAN interface
Click the ‘Create new rule’ button to create a new policy. The policy requires
completing several fields as shown in Figure A-8.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 74 of 92
Figure A-8: Accept HTTPS
In the ‘Rule Name’ field, type a descriptive name e.g. Accept HTTPS.
In the ‘IP’ field, select the IP checkbox and specify/edit the IP address e.g.
192.168.0.124.
In the ‘Port’ field, select the Port checkbox and type 443.
In the ‘Firewall Action’ dropdown list, select ACCEPT.
Repeat the above steps for each interface type to ensure that only HTTPS requests are
permitted on those interfaces e.g. ‘usb’ and ‘gsm’.
After all interfaces have been configured, click the ‘Save’ button in the application
header to save the security settings and then restart the DGA 900.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 75 of 92
Appendix B Transportation PGA Lock
The Analysis module is equipped with a factory-fitted transportation PGA lock that
consists of a metal locking bracket, two metal securing pins, two plastic nuts and three
cable ties as shown in Figure B-1.
Figure B-1: PGA lock – engaged
The lock is engaged prior to shipping, but must be disengaged prior to operation of the
product. The lock must be refitted if there is ever a requirement to transport the module
(or if the product is ever to be laid horizontally). If the product is to be relocated or
transported, it must be shutdown using the procedure outlined in Section 6.14.
Note: If the product is to be removed from the transformer, ensure that the transformer inlet and outlet valves, and the pipework valves are closed before removing the pipework.
To access the lock, open the Analysis module, remove the black push-fit insulating cover as
described in Section C.3 and follow the relevant procedure outlined below.
B.1 Remove the lock
To remove the PGA lock after transportation of the product, follow this procedure:
▪ Cut the three cable ties to release the two securing pins and the locking bracket as shown in Figure B-2.
Figure B-2: PGA lock – pins and locking bracket secured with cable ties
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 76 of 92
▪ Pull each pin forward and out to remove it from the vibration mount assembly as shown in Figure B-3.
Figure B-3: PGA lock – remove pins
▪ Loosen and remove the two plastic nuts securing the metal bracket to the anti-vibration mounts as shown in Figure B-4.
Figure B-4: PGA lock – remove plastic nuts
▪ Remove the metal bracket as shown in Figure B-5. Note: Retain the metal bracket, pins and plastic nuts for future use of the lock.
Figure B-5: PGA lock – remove metal bracket
The transportation PGA lock is now disengaged rendering the PGA anti-vibration mounts
active. If the product is transported and reconnected to a different substation asset, it
must be recommissioned by a GE-approved commissioning engineer.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 77 of 92
B.2 Fit the lock
To fit the PGA lock, reverse the procedure outlined in Appendix B.1:
▪ Insert the metal bracket into the vibration mount assembly as shown in Figure B-6.
Figure B-6: PGA lock – insert metal bracket
▪ Secure the metal bracket to the anti-vibration mounts using the two plastic nuts as shown in Figure B-9.
Figure B-7: PGA lock – attach plastic nuts
Note: Hold the base of the anti-vibration mount while tightening the plastic nuts to prevent twisting of the soft silicone.
▪ Push each metal pin into the vibration mount assembly as shown in Figure B-9.
Figure B-8: PGA lock – insert pins
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 78 of 92
▪ Ensure that each pin end is fully inserted into the hole in the back wall of the enclosure as shown in Figure B-9.
Figure B-9: PGA lock – pin to enclosure hole
▪ Use three cable ties to secure the pins to the metal bracket at the appropriate holes as shown in Figure B-10.
Figure B-10: PGA lock – pins and locking bracket secured with cable ties
The transportation PGA lock is now engaged rendering the PGA anti-vibration mounts
inactive. After the product is removed, ensure that it is stored in an upright position. Note:
Any remaining oil in the pipework should be drained into a suitable container.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 79 of 92
Appendix C Maintenance Activities
C.1 Battery
The product uses non-rechargeable lithium coin cell batteries (Panasonic CR2450
3 V 620 mAh) — one in the Hub module on the Controller PCB as shown in Figure C-1, and
the other in the Analysis module on the Marshalling PCB as shown in Figure C-2. If either
battery needs to be replaced, data from the product must be backed up. Failure to do so
may result in historical data loss.
Figure C-1: Controller PCB coin cell battery
Figure C-2: Marshalling PCB coin cell battery
The following steps describe how to change the battery:
1. Back up the product data — contact your GE representative.
2. Power off the relevant module.
3. Open the door on the relevant module to locate the battery on the relevant board.
4. Slide the battery out of its housing.
5. Replace with a new Panasonic CR2450 3 V 620 mAh coin cell.
6. Close the door.
7. Power on the relevant module and confirm that all product data remains intact.
There is a danger of a new battery exploding if installed incorrectly.
Dispose of the used battery in accordance with local regulations — not in a fire or with household waste. Contact your local waste disposal agency for the address of the nearest battery deposit site. Perchlorate material — special handling may apply.
See: www.dtsc.ca.gov/hazardouswaste/perchlorate/
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 80 of 92
C.2 Air Filter Replacement
The Hub module draws air from the base and expels it via the air outlet on the front door.
The intake air is filtered to remove the largest particles, so depending on environmental
conditions, the air filter cartridge may need periodic replacement.
To replace the air intake filter:
First isolate the product through the external circuit breaker or external switch
and apply LOTO.
Remove the four M8 hex nuts from the four M2.5 hex bolts securing the filter holder
assembly as shown in Figure C-3 and then prise the holder off the base plate as
shown in Figure C-4.
Remove the used filter mesh cartridge from the holder and dispose of it as shown in
Figure C-5. Replace with a new filter mesh cartridge as shown in Figure C-6 in the
orientation shown in Figure C-4. Note: the metallic mesh cover must face
downwards and outwards in the holder.
Place the filter holder assembly back onto the module’s base plate and secure in
place using the four nuts and bolts previously removed as shown in Figure C-3.
Figure C-3: Hub fan air inlet
Figure C-4: Detached inlet cover with filter – facedown
Figure C-5: Detached inlet cover with filter removed
Figure C-6: Filter mesh cartridge – face up
The air outlet filter on the rear of the front door should also be periodically checked and
replaced if required.
To replace the air outlet filter:
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 81 of 92
First isolate the product through the external circuit breaker or external switch
and apply LOTO before opening the door.
Remove the eight M5 aerotight nuts that secure the Louvre catchment tray to the
top rear of the front door as shown in Figure C-7, and then lift the tray away from the
neoprene 3 mm gasket as shown in Figure C-8.
Remove the used white filter from the tray (it’s disposable and can be pulled out) as
shown in Figure C-9. Insert a new Louvre air filter as shown in Figure C-10 into the
tray ensuring that the filter evenly fills the entire space.
Refit the tray to the gasket on the front door and secure in place using the eight nuts
previously removed as shown in Figure C-7.
Figure C-7: Louvre catchment tray – attached
Figure C-8: Louvre gasket – tray removed
Figure C-9: Louvre catchment tray – detached & filter removed
Figure C-10: Louvre air filter
C.3 Oil Filter Cleaning
The oil is filtered to prevent particles from entering the product or being returned to the
transformer. Therefore, this filter may need occasional cleaning.
Note: A non-critical error in the product data file, such as error code 18 or 20 can be suggestive of such action.
Figure C-11 shows the oil connections on the base of the Analysis module.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 82 of 92
Figure C-11: Oil connections
Figure C-12 shows the oil filter location with the filter element removed.
Figure C-12: Oil filter
Before removing the filter housing, first isolate the product through the external switch or circuit breaker and ensure that the oil supply valve is closed.
To clean the oil filter:
If a measurement is in progress, press Stop Measurement on the HMI to abort the
measurement process and return the product to Standby mode. Power off the
product at the external switch or circuit breaker once it is in Standby mode.
Close the product’s supply and return oil valves.
Open the door of the Analysis module.
Pull the black insulating push-fit cover by the moulded handle nearer the centre top
until the top of the cover opens, then lift the cover vertically up and out of the way as
shown in Figure C-13.
Figure C-13: Internal push-fit cover removal
Remove the four M3 hex bolts holding the oil filter cover.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 83 of 92
Remove the stainless steel filter element and clean it using a brush and compressed air
(or replace with a new filter, order FITT01029H). Then replace the filter back into its
housing and re-secure the oil filter cover using the four M3 hex bolts.
Replace the black insulating push-fit cover by inserting the bottom end first. Note: Take
care to route the earthing cable through the groove in the insulation. And then press fit
the top of the cover home.
Close and lock the door.
Re-open the product’s supply and return valves.
Re-energise the product and it will automatically begin measuring at the next scheduled
time.
C.4 Peltier Cooler
The product uses a thermoelectric cooler attached to the outer left side of the Analysis
module to regulate the temperature within the module. The Peltier cooler as shown in
Figure C-14 is self-contained and requires minimal maintenance other than periodic
cleaning.
Follow this procedure to clean the cooler:
Power down the product as described in Section 6.14.
WARNING: Ensure the product is powered off and disconnect all supplies at their source before continuing.
Remove the six M2.5 hex bolts holding the external fan group as highlighted in Figure
C-14 and separate the mating connectors of the electrical cable to free the fan group
from the unit as shown in Figure C-15 to Figure C-17.
Use dry compressed air to blow any dust, insect matter or other debris from the
fans, cooling fins and the top vent (if necessary, remove the hood held by two M2.5
hex bolts).
Use a clean dry cloth to remove any hardened deposits from the general area.
If necessary, protect the electrical connector and use a non-pressurised hose pipe to
direct deionised water through the top fins of the cooler and continue to flush water
through the fins until the water running out from the bottom of the cooler turns
clear.
Reconnect the electrical cable at the clip, replace the external fan group (and hood if
removed), and secure in place with the M2.5 hex bolts.
Use only deionised water and a non-pressurised hose to direct water through both fan inlets for as short a time as possible; typically, less than 10 seconds is sufficient to clean each fan inlet (with a typical total duration of under 3 minutes).
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 84 of 92
Power on the product.
Figure C-14: Peltier cooler
Figure C-15: Fan group electrical connection
Figure C-16: Peltier cooling fins
Figure C-17: Fan group detached from cooler
Hood
Cooling fins Detached fan group
Electrical clip connector
Hex bolts (six highlighted)
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 85 of 92
Appendix D Time Sync Implementation
The product has a time-sync feature that allows users to synchronize the clock. This
Appendix explains the data format options for the “time sync” and its implementation.
D.1 Time Format
Under the standard Modbus® register list, the timing is defined in Table D-1.
Table D-1: Timing
Register Permissions Group Size
Description Data Format
1200
R/W 4*
UTC Clock: Years YYYY (BCD)
1201 UTC Clock: Months, days MMDD (BCD)
1202 UTC Clock: Hours, minutes HHMM (BCD)
1203 UTC Clock: Seconds, Day of week (0-6, 0 Sunday)
SSWW (BCD)
This R/W (read/write) register is in BCD format (Binary Coded Decimal). Some systems are
not compatible with this data format. *The time registers can be written separately in 5
second intervals in any order.
D.2 UNIX® Epoch register
A UNIX Epoch register was added to the host board firmware (v1.12.2) to make systems
integration easier in cases of system incompatibility. Both register formats (BCD & UNIX)
will be maintained in future firmware versions and both affect the same single clock. The
details of the UNIX time registers are listed in Table D-2.
Table D-2: UNIX time registers
Register Access Flags
Version Storage Class
Effect After
Name Description Data Format
1197 rg2,wg2 1.12.2 RAM immediately RTC_UNIX_TIME
Current Time UTC in UNIX format
32-bit integer 1198
These registers are readable and writable, but should be written together as a single 32-bit
value.
D.2.1 UNIX Time Format
The number of seconds from the UNIX epoch time of Jan 1st 1970 00:00:00.
D.2.2 UNIX Time Example
For reference, the time on a device is reported in the UTC format on the HMI as 11/29/2017
00:00:00 BST and the corresponding value in the registers mentioned above is
1511913600.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 86 of 92
When testing, please check that you are reading registers 1197-1198 (assuming addresses
start at 999 +1) and decoding an unsigned 32-bit big endian number. The epoch time is in
UTC. This matches the device time. An online converter e.g.
http://www.epochconverter.com/ can be used to verify.
D.2.3 Register Access Control
The product registers are protected with access flags. The register map details the relevant
access flags for each register. Each register may have one or more access flags, separated
by commas. Table D-3 lists the supported access flags:
Table D-3: Access flags
Flag Access Description
R Read Read access to a single register
rgN Read group Read access to a group of length N (Nmax = 120)
W Write Write access to a single register
wgN Write group Write access to a group of length N (Nmax = 120)
Access flags may be modified with the addition of the modifier flags listed in Table D-4.
Table D-4: Modifier flags
Flag Access Description
u User Only accessible if the master is authorised with user access
c Config Only accessible if master is authorised as config (commissioning) user
f Factory Only accessible if master is authorised as factory (service) user
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 87 of 92
Appendix E Alarm Settings: General Advice
Note: This Appendix is based on Technical Bulletin No 18 (amended below for DGA 900).
E.1 Introduction
There are published standards for interpretation of DGA results. The main internationally
recognised standards are IEEE® C57.104 and IEC® 60599. It is recommended that the
customer refers to these or local standards for more information on DGA interpretation.
As every transformer is different due to design, manufacturing tolerances, operating
regime, etc., there are no rules that can be applied to every transformer. Therefore, alarm
settings should be individually set for each transformer.
IEEE C57.104 provides a 4-level criterion to classify risks to transformers. Condition 1 gives
the average gas values below which a ‘normal transformer’ is operating satisfactorily.
If there is DGA history available for the transformer, then the customer should also consult
this information when deciding on the alarm settings for the transformer.
E.2 Setting Alarms
All online DGA monitors should have alarm levels set at commissioning. This will ensure
that the customer is alerted should the gas concentrations increase. While it is the
customer’s responsibility to set appropriate alarms, it is recommended that there always
be some alarms set on the DGA monitor as there have been some cases where alarm
levels have not been set and the transformer has failed without any notification to the
customer.
Customers with experience in monitoring transformers may have their own methodology
for setting alarms. In this case, the customer methodology should be used to set alarms on
the DGA monitoring system.
Where a customer wishes to monitor the transformer for a period before deciding on the
alarm settings, it is recommended that some preliminary alarm levels are set at the time of
commissioning using the method outlined in E.3.
E.3 Main Tank: Gas Level Alarms
If the customer does not have their own system for setting alarms, the following procedure
may be used, at the customer’s discretion, to set preliminary alarms on the DGA monitor:
• Run the analyser for several hours, preferably overnight, at hourly measurements.
• Compare the results to IEEE Standard C57.104-2008 to see if any of the results are
outside the established norms.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 88 of 92
Table E-1: Main Tank: Gas Level Alarms
µL/L or ppm
Hydrogen
(H2)
Methane
(CH4)
Acetylene
(C2H2)
Ethylene
(C2H4)
Ethane
(C2H6)
Carbon
monoxide
(CO)
Carbon
dioxide
(CO2)
TDCG
IEEE STD Condition 1
100 120 1 50 65 350 2500 720
1) Set alarms to the following only if the measurements taken are LESS THAN the above values. (C2H2 is set slightly higher to avoid spurious alarms)
Caution 100 120 2 or 4* 50 65 350 2500
Alarm 120 144 3 or 6* 60 78 420 3000
* To avoid spurious alarms on the DGA 900, C2H2 Caution and Alarm limits should be set no lower than 2 and 3 ppm respectively.
2) Set alarms to the following only if the measurements taken are ABOVE the IEEE Condition 1 values.
Measured Value * yyy% = ppm caution/alarm value)
Caution Value *120% Value *120%
Value *120% Value *120%
Value *120%
Value *120% Value *120%
Alarm Value *150% Value *150%
Value *150% Value *150%
Value *150%
Value *150% Value *150%
Note: The values cited in this table assume that no previous tests on the transformer for dissolved gas analysis have been made or that no recent history exists. If a previous analysis exists, it should be reviewed to determine if the situation is stable or unstable.
Note: See the example in Section E.8 at the end of this Appendix.
E.4 Main Tank: Gas Rate Of Change Alarms
Set the Rate of Change (ROC) alarms to the following values listed in Table E-2 for the most
critical gases:
▪ Daily Rate of Change (ROC) alarms – if oil volume is unknown
Table E-2: ROC alarms (key gas values)
ppm / day
Hydrogen
(H2)
Methane
(CH4)
Acetylene
(C2H2)
Ethylene
(C2H4)
Ethane
(C2H6)
Carbon
monoxide
(CO)
Carbon
dioxide
(CO2)
TDCG
Caution - - 0.5 0.5 - 2 - 2
Alarm - - 1.0 1.0 - 5 - 8
▪ Daily Rate Of Change (ROC) alarms – if oil volume or weight is known
If the oil volume is known, the severity of defects based on ROC depends on the volume (or
weight) of oil contained in the transformer. For instance, a 1 ppm/day gas increase in a
large transformer (80,000 l oil) means a ROC of 80 ml/day of such gas. In a smaller
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 89 of 92
transformer (4,000 l oil), the same 1 ppm/day gas increase means a ROC of 4 ml/day. In
either case there is a defect, but in the larger transformer the defect is much more severe.
E.4.1 Using Oil Volume
It is strongly recommended to use ROC in ml/day. Convert the ppm/day figure to ml/day
based on the oil volume or weight:
1) ( )
daymlmROC
ROC /
=
Transformer owner may calculate ROC in ml/day by using following formula (IEC 60599):
2) ( )
( )dayml
dd
myyROC /
12
12
−
−=
where:
▪ y1 is the last reading, in ppm;
▪ y2 is the previous reading, in ppm;
▪ m is the oil mass / weight, in kilograms;
▪ ρ is the oil density, in kilograms per cubic metre;
▪ d1 is the date of y1, and
▪ d2 is the date of y2.
Note: This is a very generic formula. As Kelman® equipment readings are taken every day, then (d2 – d1) = 1
E.4.2 Using Oil Mass
Should the transformer owner use oil mass instead of oil volume, then ρ = 1,000. Thus,
formula can be simplified to:
3) ( ) )/(12 daymlMyyROC −=
where:
▪ (y2 – y1) is the difference between two consecutive readings in 24 hours, in ppm
▪ M is the oil mass, in metric tons
Note: Pay attention to the units of measure.
▪ In formula 2), oil density is given in kilograms per cubic metre, thus typical oil density is about 960 kg/m3.
▪ In formula 3), gas concentration is given in ppm and oil mass is given in metric tons).
If using ROC in ml/day, use Table E-3 to set ROC alarms:
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 90 of 92
Table E-3: ROC alarms (for ROC in ml/day)
ml/day Hydrogen
(H2)
Methane
(CH4)
Acetylene
(C2H2)
Ethylene
(C2H4)
Ethane
(C2H6)
Carbon
monoxide
(CO)
Carbon
dioxide
(CO2)
TDCG
Caution 2.5 1 0.05 1 1 25 - 5
Alarm 5 2 0.1 2 2 50 - 10
E.5 Measurement Intervals
If the customer does not have a policy for measurement intervals, use the following
measurement intervals (in hours):
Table E-4: Measurement intervals
In Hours DGA 900
Normal 8
Caution 4
Alarm 1
E.6 Other Settings / Alarm Setups
In TransConnect, remember to map Caution and Alarm values to Caution/Alarm indicators,
Caution/Alarm modes, any wired relays and SMS messaging as required.
E.7 Important Notes
All alarm and measurement interval settings must be approved and signed off by the
customer.
After oil treatment (degassing, regeneration, drying, mixing, etc.), the alarm settings
should be reviewed and changed if necessary.
E.8 Example (Main Tank)
The maximum measured value of ethylene is 48 ppm.
This is close to the limit in Table E-1, so the Caution should be set to 120% of the value and
Alarm to 150% of the value.
Caution 58 ppm
Alarm 72 ppm
The rate of change alarms should also be set.
Caution 0.4 ppm/day
Alarm 1.0 ppm/day
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 91 of 92
E.8.1 Caution
There may be cases where the transformer suddenly fails (between measurements at the
normal measurement interval). The customer should be made aware that online
monitoring equipment is not capable of detecting such rapid (often catastrophic) failures.
DGA monitoring is designed for the detection of incipient slow-developing faults. Other
protective devices (Buchholz relay, pressure relief device, over-current and differential
current protection, etc…) should be used in conjunction with DGA monitoring equipment to
provide complete protection for the transformer.
E.8.2 Stray Gassing (CIGRE® TF 15/12.01.11)
Some modern, unused oils are recognised as ‘stray gassing’. This means that the oil itself
can produce some hydrogen in the absence of defects. Should the online monitor be
installed before or within a few months after the commissioning of the transformer,
hydrogen concentration may rise to 250 ppm. This should be taken into consideration
when establishing the caution and alarm settings.
In stray gassing oils, hydrogen concentration increases very rapidly when the transformer
is energised, reaches a plateau at about 250 ppm and then decreases slowly to normal
values. The transformer owner should know this behaviour before setting up caution and
alarm values and adapt them during the first year or two of transformer operation. If
Kelman equipment is installed on a transformer already in service, this note is not
applicable unless a passivator or an additive has been recently added to the oil.
After any oil treatment (degassing, regeneration, drying, mixing, etc.), the alarm settings
should be reviewed and changed if necessary.
MA-025 – DGA 900 Operator Guide – Rev 2.0 12-Apr-19 Page 92 of 92
Contact & Copyright Details
GE Grid Solutions (UK) Ltd
Lissue Industrial Estate East
Unit 1, 7 Lissue Walk, Lisburn, Co. Antrim
Northern Ireland, United Kingdom BT28 2LU
GEGridSolutions.com
For further assistance or queries please contact:
Customer Service Centre (24 hours a day, 365 days a year)
T +44 1785-250-070 (United Kingdom)
T 1-800-361-3652 (United States and Canada)
T +1 514-420-7460 (worldwide)
GE, the GE monogram and Kelman are trademarks of the General Electric Company.
Other company or product names mentioned in this document may be trademarks or
registered trademarks of their respective companies.
GE reserves the right to make changes to specifications of products described at any
time without notice and without obligation to notify any person of such changes.
This material is accurate at the time of writing. For the latest release, please visit:
http://www.gegridsolutions.com/md/catalog/dga900.htm
Copyright, General Electric Company, 2019. All Rights Reserved.