  • 5.3 Partialdischargemeasurernent

    1a

    IEC 60076-11, clause 22.4.1.126 February 2013

    Standard and dateStandardTest date

    Ambient air pressureHumidity

    -l-

    Trc 1370-'13

    '1030 ht)ai g/m

    Environmental conditionsAmbient temperatureTemperature of test object

    Characteristic test dataCalibrationNoise levelCoupling capacitors 260A . PFBandwidth

    .t0O-aLf9-*fJ7Test frequeircy, I- ; t ,,tt ,. A9L-H.L:Rated voltage (U)Test conditions | '. ,This test voltage is 80% of the sp'ecified test.levei.

    20 0c'19 "c

    5pc1pc

    -l t_1,o.* lf'JL-EL.-

    Low-vo[age winding-

    High-votlage winding-

    Coupling pacitorCPL

    - Quadripole/Messuing impedance

    - AQuisition unil

    - MCU-Controlunil

    HVCK

    terminal voltage applicationl) duration

    (s)

    partialdischarge

    level

    (pc)

    inception extinction result

    ..xU,/./3

    phase-to-earth voltage

    (kv) (kv) (pc) (kv) (pc)A 1,6 10,2 30

    1,3 8,3 1g0 2) nd passed

    B 1,6 10,2 30

    1,3 8,3 190 ') nd passedC 1,6 10,2 30

    1,3 8,3 190 2) nd passed

    1) The transformer was supplied with a three-phase voltage on the LV winding2) The partial discharge value was measured at the end ofthe 180 seconds

    Requirements

    The partial discharge levels at 1 ,3 U, shall not exceed 10 pC.

    Result

    The transformer passed the test.