    Project : ITCC - MOSQUE

    Subject : BMS I nput / Output List - Plumbing& Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DO

    Plumbing & Fire Protection

    Water Meters

    1 Incoming Water Flow [Water Meter] 1 Flow Meter

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Water Meters Points

    Sump Pumps-SP1 TO SP2 [1-Duty & 1-Lag] - 2 Lift Sta.

    1 Pump on/off Status 2 From Pump Control Panel

    2 Pump Trip Status 1 From Pump Control Panel

    3 Pressure in the Common Discharge Header 1 Liquid Pressure Sensor

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Sump High & Low Level 2 From Tank Float Switch

    Total per Unit 1 6 0 0

    Total for all Units 2 24 0 0

    Total Sump Pumps Points

    Electric Water Heaters [EWH]

    1 EWH On/Off Status 1 From Building Local Control Panel

    TOTAL 0 1 0 0

    Total Electric Water Heaters -Points 0 1 0 0

    Total Electric Water Heaters -Points

    1

    Item Point DescriptionQty.

    4

    1

    Required Points OPCClient

    1

    RemarksBACnet

    Network

    Thermostat

    Software

    Integration

    1

    26

    1 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    2/21

    Project : ITCC -COMMERCIAL STORESSubject : BMS Input / Output List - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DO

    Plumbing and Fire Protection Equipments

    Water Meters

    1 Incoming Water Flow [Water Meter] 1 Flow Meter

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Water Meters Points

    Sump Pumps-SP1 TO SP5 [1-Duty & 1-Lag] -5 Lift Sta.

    1 Pump on/off Status 2 From Pump Control Panel

    2 Pump Trip Status 1 From Pump Control Panel

    3 Pressure in the Common Discharge Header 1 Liquid Pressure Sensor

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Sump High & Low Level 2 From Tank Float Switch

    Total per Unit 1 6 0 0

    Total for all Units 5 60 0 0

    Total Sump Pumps Points

    Air Purification Unit (Aerator) - 1 no. each Grey Water Treatment Plant

    1 Aerator On/Off /Fault Status 3 From Grey Water Treatment Plant Panel

    TOTAL 0 3 0 0

    Total Aeratot Unit Points 0 3 0 0

    Total Aerator Unit Points

    Sand Filters & Activated Carbon Filters for Grey Water Treatment Plant [1 nos. Sand Filters x 1 nos.plant + 1 nos. Activated C.Filters x 1 plant]

    1 High D P of Sand Filters 1 DP Differential Pressure Switch from Grey Water

    Treatment Plant Panel

    TOTAL 1 0 0 0

    Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points 2 0 0 0

    Total Sand Filter and Carbon Filters for Grey Water Treatment Plant -Points

    Electric Water Heaters [EWH]

    1 EWH On/Off Status 1 From Building Local Control Panel

    TOTAL 0 1 0 0

    Total Electric Water Heaters -Points 0 10 0 0

    Total Electric Water Heaters -Points

    2

    2

    10

    10

    1

    1

    10

    65

    1

    3

    Item Qty. Point DescriptionRequired Points BACnet

    Network

    Thermostat

    Software

    IntegrationOPC Client Remarks

  • 7/27/2019 ITCC- BMS IO-PG

    3/21

    Project : ITCC -COMMERCIAL CENTERSubject : BMS Input / Output Li st - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DO

    Plumbing and Fire Protection Equipments

    Water Meters

    1 Incoming Water Flow [Water Meter] 1 Flow Meter

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Water Meters Points

    Grey Water Tanks

    1 Tank Low Level 1 From Tank Float Switch

    2 Tank High Level 1 From Tank Float Switch

    3 Potable Make-up Incoming Water Flow 1 Solenoid valve

    4 Influent Dirt Interceptor SHOCKED Alarm 1 Float Switch

    5 Tank water volume reading 1 Relay Output From BMS

    6 Tank Level (%) Monitor 1 (4-20)mA from the Level Indicator

    Total per Unit 3 3 0 0

    Total for all Units 3 3 0 0

    Total Grey Water Tanks Points

    Sump Pumps-SP1 TO SP-5 [1-Duty & 1-Lag] - 5 Lift Sta.

    1 Pump on/off Status 2 From Pump Control Panel

    2 Pump Trip Status 1 From Pump Control Panel

    3 Pressure in the Common Discharge Header 1 Liquid Pressure Sensor

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Sump High & Low Level 2 From Tank Float Switch

    Total per Unit 1 6 0 0

    Total for all Units 5 60 0 0

    Total Sump Pumps Points

    Odor Control Unit, Chlorination Unit & Coloring Dye Unit of Grey Water Treatment Plant (1 unit each plant x 1no. plant)

    1 Dosing Pump On/Off Status 1 From Grey Water Treatment Plant Panel

    2 Chemical flow status 1 Flow switch3 Dosing Pump Trip Alarm 1 From Grey Water Treatment Plant Panel

    4 Dosing Pump Auto / Manual Status 1 From Grey Water Treatment Plant Panel

    5 Dosing Pump Start/stop command 1 Relay Output From BMS

    6 Chemical Tank Level 1 From Grey Water Treatment Plant Panel

    7 Chemical Tank Low Level Alarm 1 From Grey Water Treatment Plant Panel

    TOTAL 0 6 0 1

    Total Odor Control, Chlorination, Coloring Dye Units Points 0 18 0 3

    3

    1

    1

    1

    6

    10

    65

    Item Qty. Point DescriptionRequired Points BACnet

    Network

    Thermostat

    Software

    IntegrationOPC Client Remarks

  • 7/27/2019 ITCC- BMS IO-PG

    4/21

    Project : ITCC -COMMERCIAL CENTERSubject : BMS I nput / Output Li st - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    IntegrationOPC Client Remarks

    Total Odor, Chlorination, Coloring Dye Units Points

    Air Purification Unit (Aerator) - 1no. each Grey Water Treatment Plant

    1 Aerator On/Off /Fault Status 3 From Grey Water Treatment Plant Panel

    TOTAL 0 3 0 0

    Total Aerator Unit Points 0 3 0 0

    Total Aerator Unit Points

    Non-Potable water pumps [2-Duty&1-Standby]- 1set

    1 Pump On/Off Status 1 VFC From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 VFC From Pump Control Panel

    4 Pump Auto / Manual Status 1 VFC From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Discharge header pressure 1 Liquid pressure sensor

    8 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 2 5 0 1

    Total Non-Potable Water Pumps Points 6 15 0 3

    Total Non-Potable Water Pumps Points

    Filter Pumps for Grey Water Treatment Plant, [2-pumps x 1-set]

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 1 5 0 1

    Total Filter Pumps for Potable Water -Points 2 10 0 2Total Filter Pumps for Potable Water -Points

    Sand Filters & Activated Carbon Filters for Grey Water Treatment Plant [1 nos. Sand Filters x 1 nos.plant + 1 nos. Activated C.Filters x 1 plant]

    1 High D P of Sand Filters 1 DP Differential Pressure Switch from Grey Water

    Treatment Plant Panel

    TOTAL 1 0 0 0

    Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points 2 0 0 0

    2

    14

    2

    21

    1

    3

    3

    24

  • 7/27/2019 ITCC- BMS IO-PG

    5/21

    Project : ITCC -COMMERCIAL CENTER

    Subject : BMS I nput / Output Li st - Plumbing & F ir e Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    IntegrationOPC Client Remarks

    Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points

    Electric Water Heaters [EWH]

    1 EWH On/Off Status 1 From Building Local Control Panel

    TOTAL 0 1 0 0

    Total Electric Water Heaters -Points 0 16 0 0

    Total Electric Water Heaters -Points

    2

    16

    16

    5 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    6/21

    Project : ITCC - SPORTS CLUB

    Subject : BMS I nput / Output List - Plumbing & F ire Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DO

    Plumbing and Fire Protection Equipments

    Water Meters

    1 Incoming Water Flow [Water Meter] 1 Flow Meter

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Water Meters Points

    Flow Meter for Swimming Pool

    1 Water Flow 1 Flow Meter

    Total per Unit 1 0 0 0

    Total for all Units 2 0 0 0

    Total FlowMeters Points

    Swimming Pool Surge Tank

    1 Tank Low Level Alarm 1 From Tank Float Switch

    2 Tank High Level Alarm 1 From Tank Float Switch

    3 Potable Make-up Incoming Water Flow 1 Solenoid valve

    4 Tank Level (%) Monitor 1 (4-20)mA from the Level Indicator

    Total per Unit 2 2 0 0

    Total for all Units 2 2 0 0

    Total Swimming Pool Surge Tank Points

    Grey Water Tanks

    1 Tank Low Level 1 From Tank Float Switch

    2 Tank High Level 1 From Tank Float Switch

    3 Potable Make-up Incoming Water Flow 1 Solenoid valve

    4 Influent Dirt Interceptor SHOCKED Alarm 1 Float Switch

    5 Tank water volume reading 1 Relay Output From BMS

    6 Tank Level (%) Monitor 1 (4-20)mA from the Level Indicator

    Total per Unit 3 3 0 0

    Total for all Units 3 3 0 0

    Total Grey Water Tank Points

    1

    6

    1

    1

    2

    2

    1

    4

    Item Qty. Point DescriptionRequired Points BACnet

    Network

    Thermostat

    Software

    IntegrationOPC Client Remarks

    6 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    7/21

    Project : ITCC - SPORTS CLUB

    Subject : BMS Input / Output Li st - Plumbing & F ire Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    IntegrationOPC Client Remarks

    Sump Pumps-SP1 TO SP-2 [1-Duty & 1-Lag] - 2Lift Sta.

    1 Pump on/off Status 2 From Pump Control Panel

    2 Pump Trip Status 1 From Pump Control Panel

    3 Pressure in the Common Discharge Header 1 Liquid Pressure Sensor

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Sump High & Low Level 2 From Tank Float Switch

    Total per Unit 1 6 0 0

    Total for all Units 2 24 0 0

    Total Sump Pumps Points

    Chrlorine Injection Unit & Acid Injection Unit for Swimming Pool

    1 Dosing Pump On/Off Status 1 From Swimming Pool Control Panel

    2 Chemical flow status 1 Flow switch

    3 Dosing Pump Trip Alarm 1 From Swimming Pool Control Panel

    4 Dosing Pump Auto / Manual Status 1 From Swimming Pool Control Panel5 Dosing Pump Start/stop command 1 Relay Output From BMS

    6 Chemical Tank Level 1 From Swimming Pool Control Panel

    7 Chemical Tank Low Level Alarm 1 From Swimming Pool Control Panel

    TOTAL 0 6 0 1

    Total Chlorine Unit & Acid Unit Points 0 12 0 2

    Total Chlorine & Acid Unit Points

    Odor Control Unit, Chlorination Unit & Coloring Dye Unit of Grey Water Treatment Plant (1 unit each plant x 1no. plant)

    1 Dosing Pump On/Off Status 1 From Grey Water Treatment Plant Panel2 Chemical flow status 1 Flow switch

    3 Dosing Pump Trip Alarm 1 From Grey Water Treatment Plant Panel

    4 Dosing Pump Auto / Manual Status 1 From Grey Water Treatment Plant Panel

    5 Dosing Pump Start/stop command 1 Relay Output From BMS

    6 Chemical Tank Level 1 From Grey Water Treatment Plant Panel

    7 Chemical Tank Low Level Alarm 1 From Grey Water Treatment Plant Panel

    TOTAL 0 6 0 1

    Total Odor Control, Chlorination, Coloring Dye Units Points 0 18 0 3

    Total Odor, Chlorination, Coloring Dye Units Points

    3

    21

    4

    26

    2

    14

    7 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    8/21

    Project : ITCC - SPORTS CLUB

    Subject : BMS Input / Output Li st - Plumbing & F ire Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    IntegrationOPC Client Remarks

    Air Purification Unit (Aerator) - 1no. each Grey Water Treatment Plant

    1 Aerator On/Off /Fault Status 3 From Grey Water Treatment Plant Panel

    TOTAL 0 3 0 0

    Total Aerator Unit Points 0 3 0 0

    Total Aerator Unit Points

    Non-Potable water pumps [2-Duty&1-Standby]- 1set

    1 Pump On/Off Status 1 VFC From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 VFC From Pump Control Panel

    4 Pump Auto / Manual Status 1 VFC From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Discharge header pressure 1 Liquid pressure sensor

    8 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 2 5 0 1

    Total Non-Potable Water Pumps Points 6 15 0 3

    Total Non-Potable Water Pumps Points

    Filter Pumps for Grey Water Treatment Plant, [2-pumps x 1-set]

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 1 5 0 1

    Total Filter Pumps for Grey Water Treatment Plant -Points 2 10 0 2

    Total Filter Pumps for Grey Water Treatment Plant -Points

    Sand Filters & Activated Carbon Filters for Grey Water Treatment Plant [1 nos. Sand Filters x 1 nos.plant + 1 nos. Activated C.Filters x 1 plant]1 High D P of Sand Filters 1 DP Differential Pressure Switch from Grey Water

    2

    14

    1

    3

    3

    24

    8 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    9/21

    Project : ITCC - SPORTS CLUB

    Subject : BMS Input / Output List - Plumbing & F ire Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    IntegrationOPC Client Remarks

    Treatment Plant Panel

    TOTAL 1 0 0 0

    Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points 2 0 0 0

    Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points

    Swimming Pool Filter

    1 High D P of Sand Filters 1 DP Differential Pressure Switch from Swimming

    Pool Control Panel

    TOTAL 1 0 0 0

    Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points 2 0 0 0

    Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points

    Swimming Pool Circulating Pumps [2-Duty&1-Standby]- 1set

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Discharge header pressure 1 Liquid pressure sensor

    8 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 2 5 0 1

    Total Swimming Pool Circulating Pumps Points 6 15 0 3

    Total Swimming Pool Circulating Pumps Points

    Hot Water Circulating Pumps [1-Duty & 1-Standby]

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Pump Trip Alarm 1 From Pump Control Panel

    3 Pump Start/stop command 1 Relay Output From BMS

    4 Discharge header pressure 1 Liquid pressure sensor

    5 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 2 2 0 1

    Total Hot Water Circulating Pumps Points 4 4 0 2Total Hot Water Circulating Pumps Points

    3

    24

    2

    10

    2

    2

    2

    9 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    10/21

    Project : ITCC - SPORTS CLUB

    Subject : BMS I nput / Output List - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    IntegrationOPC Client Remarks

    Water Quality Monitor Unit for swimming pool

    1 PH of swimming pool water 1 From Swimming Pool Control Panel

    TOTAL 0 1 0 0

    Total Water Quality Monitor Points 0 1 0 0

    Total Water Quality Monitor Points

    UV Reactor for Swimming Pool

    1 UV Reactor ON/Off /Fault Status 3 From UV Reactor Panel

    2 UV Lamps run hours 1 Relay Output From BMS

    TOTAL 0 3 0 1

    Total Aerator Unit Points 0 3 0 1

    Total Aerator Unit Points

    Electric Water Heaters [EWH] for Swimming Pool

    1 EWH On/Off Status 1 From Swimming Pool Control Panel

    TOTAL 0 1 0 0

    Total Electric Water Heaters -Points 0 1 0 0

    Total Electric Water Heaters -Points

    Electric Water Heaters [EWH] for Building

    1 EWH On/Off Status 1 From Building Local Control Panel

    TOTAL 0 1 0 0

    Total Electric Water Heaters -Points 0 11 0 0

    Total Electric Water Heaters -Points

    1

    4

    1

    1

    11

    11

    1

    1

    10 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    11/21

    Project : ITCC -SCHOOL

    Subject : BMS I nput / Output List - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DO

    Plumbing and Fire Protection Equipments

    Water Meters

    1 Incoming Water Flow [Water Meter] 1 Flow Meter

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Water Meters Points

    Sump Pumps [1-Duty & 1-Standby] - 1 no. Lift Sta.

    1 Pump on/off Status 2 From Pump Control Panel

    2 Pump Trip Status 1 From Pump Control Panel

    3 Pressure in the Common Discharge Header 1 Liquid Pressure Sensor

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Sump High & Low Level 2 From Tank Float Switch

    Total per Unit 1 6 0 0

    Total for all Units 1 12 0 0

    Total Sump Pumps Points

    Electric Water Heaters [EWH]

    1 EWH On/Off Status 1 From Building Local Control Panel

    TOTAL 0 1 0 0

    Total Electric Water Heaters -Points 0 3 0 0

    Total Electric Water Heaters -Points

    1

    1

    2

    13

    3

    3

    Item Qty. Point DescriptionRequired Points BACnet

    Network

    Thermostat

    Software

    IntegrationOPC Client Remarks

    11 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    12/21

    Project : ITCC -APPARTMENT

    Subject : BMS Input / Output List - Plumbing & F ire Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DO

    Plumbing and Fire Protection Equipments

    Water Meters

    1 Incoming Water Flow [Water Meter] 1 Flow Meter

    Total per Unit 1 0 0 0

    Total for all Units 1 0 0 0

    Total Water Meters Points

    Sump Pumps [1-Duty & 1-Standby] - 1 no. Lift Sta.

    1 Pump on/off Status 2 From Pump Control Panel

    2 Pump Trip Status 1 From Pump Control Panel

    3 Pressure in the Common Discharge Header 1 Liquid Pressure Sensor

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Sump High & Low Level 2 From Tank Float Switch

    Total per Unit 1 6 0 0

    Total for all Units 1 12 0 0

    Total Sump Pumps Points

    Electric Water Heaters [EWH]

    1 EWH On/Off Status 1 From Building Local Control Panel

    TOTAL 0 1 0 0

    Total Electric Water Heaters -Points 0 3 0 0

    Total Electric Water Heaters -Points

    1

    1

    2

    13

    3

    3

    Item Qty. Point DescriptionRequired Points BACnet

    Network

    Thermostat

    Software

    IntegrationOPC Client Remarks

    12 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    13/21

    Project : ITCC CLUSTER

    Subject : BMS I nput / Output List - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DO

    Plumbing & Fire Protection

    Combined Potable Water & Fire Water Tanks

    1 Tank Low Level 1 From Tank Float Switch

    2 Tank High Level 1 From Tank Float Switch

    3 Motorized valve feedback 1 From the valve

    4 Main water Tank Incoming Water Flow [Water Meter] 1 Flow Meter

    5 Motorized valve control 1 Relay Output From BMS

    6 Tank water volume reading 1 Relay Output From BMS

    7 Tank Level (%) Monitor 1 (4-20)mA from the Level Indicator

    Total per Unit 3 3 0 1

    Total for all Units 6 6 0 2

    Total Combined Potable water and Fire Water Tanks Points

    Grey Water Tanks

    1 Tank Low Level 1 From Tank Float Switch

    2 Tank High Level 1 From Tank Float Switch

    3 Potable Make-up Incoming Water Flow 1 Solenoid valve

    4 Influent Dirt Interceptor SHOCKED Alarm 1 Float Switch

    5 Tank water volume reading 1 Relay Output From BMS

    6 Tank Level (%) Monitor 1 (4-20)mA from the Level Indicator

    Total per Unit 3 3 0 0

    Total for all Units 12 12 0 0

    Total Grey Water Tanks Points

    Underground Fountain Water Tank No. 1 for Fountains Nos. 1 & 2

    1 Tank Quick Fill Level 1 From Tank Float Switch

    2 Tank Running Level 1 From Tank Float Switch

    3 Tank Safe Off Level 1 From Tank Float Switch

    4 Motorized valve feedback 1 From the valve

    5 Main water Tank Incoming Water Flow [Water Meter] 1 Flow Meter

    6 Motorized valve control 1 Relay Output From BMS

    7 Tank water volume reading 1 Relay Output From BMS

    8 Tank Level (%) Monitor 1 (4-20)mA from the Level Indicator

    Total per Unit 3 4 0 1

    Total for all Units 3 4 0 1

    Total Underground Fountain Water Tanks No. 1 Points

    Item Qty. Point DescriptionRequired Points BACnet

    Network

    Thermostat

    Software

    Integration

    OPC

    ClientRemarks

    2

    14

    4

    24

    1

    8

    13 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    14/21

    Project : ITCC CLUSTER

    Subject : BMS Input / Output Li st - Plumbing & Fir e Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    Integration

    OPC

    ClientRemarks

    Sump Pumps-SP1 [1-Duty & 1-Standby] - 4 Lift Sta.

    1 Pump on/off Status 2 From Pump Control Panel

    2 Pump Trip Status 1 From Pump Control Panel

    3 Pressure in the Common Discharge Header 1 Liquid Pressure Sensor

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Sump High & Low Level 2 From Tank Float Switch

    Total per Unit 1 6 0 0

    Total for all Units 4 48 0 0

    Total Sump Pumps Points

    Sump Pumps-SP2 [1-Duty & 1-Standby] - 14 Lift Sta.

    1 Pump on/off Status 2 From Pump Control Panel

    2 Pump Trip Status 1 From Pump Control Panel

    3 Pressure in the Common Discharge Header 1 Liquid Pressure Sensor

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Sump High & Low Level 2 From Tank Float Switch

    Total per Unit 1 6 0 0

    Total for all Units 14 168 0 0

    Total Sump Pumps Points

    8

    52

    28

    182

    14 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    15/21

    Project : ITCC CLUSTER

    Subject : BMS I nput / Output List - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    Integration

    OPC

    ClientRemarks

    Diesel Fuel Transfer Pumps + Bulk Storage Tank [1-Submersible Pump Duty & 1-Manual Pump Standby] -5 sets

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Fuel flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Discharge header pressure 1 Liquid pressure sensor

    8 Pump motor temperature high 1 From Pump Control Panel

    9 Bulk Storage Tank Fuel Level 1 From Pump Control Panel

    10 Bulk Storage Tank Low Level Alarm 1 From Pump Control Panel

    Total per Unit 2 7 0 1

    Total for all Units 10 35 0 5

    Odor Control Unit, Chlorination Unit & Coloring Dye Unit of Grey Water Treatment Plant (1 unit each plant x 4 nos. plants)

    1 Dosing Pump On/Off Status 1 From Grey Water Treatment Plant Panel

    2 Chemical flow status 1 Flow switch

    3 Dosing Pump Trip Alarm 1 From Grey Water Treatment Plant Panel

    4 Dosing Pump Auto / Manual Status 1 From Grey Water Treatment Plant Panel

    5 Dosing Pump Start/stop command 1 Relay Output From BMS

    6 Chemical Tank Level 1 From Grey Water Treatment Plant Panel

    7 Chemical Tank Low Level Alarm 1 From Grey Water Treatment Plant Panel

    TOTAL 0 6 0 1

    Total Odor Control, Chlorination, Coloring Dye Units Points 0 72 0 12

    Total Odor, Chlorination, Coloring Dye Units Points

    Air Purification Unit (Aerator) - 2 no. each Grey Water Treatment Plant

    1 Aerator On/Off /Fault Status 3 From Grey Water Treatment Plant Panel

    TOTAL 0 3 0 0

    Total Aerator Unit Points 0 24 0 0

    Total Aerator Unit Points

    Chlorination Unit, PH Control Unit & Sanitizer Unit of Fountains [1 unit each for 2 fountain system]

    1 Dosing Pump On/Off Status 1 From Fountain Control Panel

    5

    50

    12

    84

    8

    24

    15 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    16/21

    Project : ITCC CLUSTER

    Subject : BMS I nput / Output List - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    Integration

    OPC

    ClientRemarks

    2 Chemical flow status 1 Flow switch

    3 Dosing Pump Trip Alarm 1 From Fountain Control Panel

    4 Dosing Pump Auto / Manual Status 1 From Fountain Control Panel

    5 Dosing Pump Start/stop command 1 Relay Output From BMS

    6 Chemical Tank Level 1 From Fountain Control Panel

    7 Chemical Tank Low Level Alarm 1 From Fountain Control Panel

    TOTAL 0 6 0 1

    Total Odor Control Unit Points 0 36 0 6

    Total Odor Control Unit Points

    Potable water pumps-DP-1 [2-Duty&1-Standby]- 4 sets

    1 Pump On/Off Status 1 VFC From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 VFC From Pump Control Panel

    4 Pump Auto / Manual Status 1 VFC From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Discharge header pressure 1 Liquid pressure sensor

    8 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 2 5 0 1

    Total Potable Water Pumps Points 8 60 0 12

    Total Potable Water Pumps Points

    Non-Potable water pumps-DP-1 [2-Duty&1-Standby]- 4 sets

    1 Pump On/Off Status 1 VFC From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 VFC From Pump Control Panel

    4 Pump Auto / Manual Status 1 VFC From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Discharge header pressure 1 Liquid pressure sensor

    8 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 2 5 0 1

    Total Non-Potable Water Pumps Points 8 60 0 12

    Total Non-Potable Water Pumps Points

    6

    42

    12

    80

    12

    80

    16 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    17/21

    Project : ITCC CLUSTER

    Subject : BMS I nput / Output List - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    Integration

    OPC

    ClientRemarks

    Fountain No. 1 - Pumps [F1A & F1B]

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Discharge header pressure 1 Liquid pressure sensor

    8 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 2 5 0 1

    Total Fountain No. 1- Water Pumps Points 4 10 0 2

    Total Fountain No. 1- Water Pumps Points

    Fountain No. 3 - Pumps [F3A & F3C]

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Discharge header pressure 1 Liquid pressure sensor

    8 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 2 5 0 1

    2

    16

    2

    17 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    18/21

    Project : ITCC CLUSTER

    Subject : BMS I nput / Output List - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    Integration

    OPC

    ClientRemarks

    Total Fountain No. 3- Water Pumps Points 4 10 0 2

    Total Fountain No. 3- Water Pumps Points

    Filter Pumps for Potable Water Filter, [2-pumps x 4 nos. Filters]

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 4 5 0 1

    Total Filter Pumps for Potable WaterFilters -Points 32 40 0 8

    Total Filter Pumps for Potable Water Filters -Points

    Filter Pumps for Grey Water Treatment Plant, [2-pumps x 4sets]

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 1 5 0 1

    Total Filter Pumps for Grey Water Treatment Plant -Points 4 40 0 8

    Total Filter Pumps for Grey Water Treatment Plant -Points

    Filter Pumps for Fountains No. 1 & 2 ,[1-Duty & 1-Standby]

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 1 5 0 1

    16

    8

    80

    8

    52

    2

    18 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    19/21

    Project : ITCC CLUSTER

    Subject : BMS I nput / Output List - Plumbing & Fi re Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    Integration

    OPC

    ClientRemarks

    Total Filter Pumps for Fountains Nos. 1 & 2 -Points 2 10 0 2

    Total Filter Pumps for Fountains Nos. 1 & 2 -Points

    Filter Pumps for Fountains No.3 ,[1-Duty & 1-Standby]

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Discharge header pressure switch 1 Liquid pressure switch

    7 Pump motor temperature high 1 From Pump Control Panel

    TOTAL 1 5 0 1

    Total Filter Pumps for Fountain No. 3 -Points 2 10 0 2

    Total Filter Pumps for Fountain No. 3 -Points

    Sand Filters for Potable Water Supply (1-no. x 4 Booster set)

    1 High D P of Sand Filters 1 DP Differential Pressure Switch

    TOTAL 1 0 0 0

    Total Sand Filter for Potable Water Supply -Points 4 0 0 0

    Total Sand Filter for Potable Water Supply -Points

    Sand Filters & Activated Carbon Filters for Grey Water Treatment Plant [2 nos. Sand Filters x 4 nos.plants + 2 nos. Activated C.Filters x 4 plants]

    1 High D P of Sand Filters 1 DP Differential Pressure Switch from Grey Water

    Treatment Plant Panel

    TOTAL 1 0 0 0

    Total Sand Filter& Carbon Filters for Grey Water Treatment Plant -Points 16 0 0 0

    Total Sand Filter & Carbon Filters for Grey Water Treatment Plant -Points

    Sand Filters for Fountain No. 1 & 2

    1 High D P of Sand Filters 1 DP Differential Pressure Switch from Fountain

    Control Panel

    TOTAL 1 0 0 0

    Total Sand Filter for Fountains 1 & 2 -Points 3 0 0 0

    Total Sand Filter for Fountains 1 & 2 -Points

    14

    2

    14

    4

    4

    16

    16

    3

    3

    19 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    20/21

    Project : ITCC CLUSTER

    Subject : BMS I nput / Output List - Plumbing & F ire Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    Integration

    OPC

    ClientRemarks

    Sand Filters for Fountain No. 3

    1 High D P of Sand Filters 1 DP Differential Pressure Switch from Fountain

    Control Panel

    TOTAL 1 0 0 0

    Total Sand Filter for Fountain No. 3 -Points 1 0 0 0

    Total Sand Filter for Fountain No. 3-Points

    Fountain Basins for Fountains Nos. 1, 2 & 3

    1 Fountain Basin Level (%) Monitor 1 (4-20)mA from the Level Indicator

    2 Fountain Basin Low Level 1 From Basin Float Switch

    TOTAL 1 1 0 0

    Total Fountain Basin for Fountains Nos. 1,2 &3- Points 12 12 0 0

    Total Fountain Basins for Fountains Nos. 1,2&3 - Points

    Electric Water Heaters [EWH]

    1 EWH On/Off Status 1 From Building Local Control Panel

    TOTAL 0 1 0 0

    Total Electric Water Heaters -Points 0 58 0 0

    Total Electric Water Heaters -Points

    Diesel Driven Fire pumps

    1 Pump On/Off Status 1 From Diesel Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Diesel Pump Control Panel

    4 Pump Auto / Manual Status 1 From Diesel Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Low diesel tank level 1 Level switch

    7 Low charge batteries 1 From Diesel Pump Control Panel

    8 Low pressure discharge switch 1 Liquid pressure switch

    9 Low pressure switch 1 Liquid pressure switch

    TOTAL 8 1

    Total Diesel Driven Fire Pumps Points 0 8 0 1

    Total Diesel Driven Fire Pumps Points

    1

    1

    12

    24

    58

    58

    1

    9

    20 of 21

  • 7/27/2019 ITCC- BMS IO-PG

    21/21

    Project : ITCC CLUSTER

    Subject : BMS I nput / Output List - Plumbing & Fir e Protection Note: Fire Protection Control with Fire Alarm Panel

    AI DI AO DOItem Qty. Point Description

    Required Points BACnetNetwork

    Thermostat

    Software

    Integration

    OPC

    ClientRemarks

    Electric Fire pumps (Electric Driven Fire Pump & Jockey Pump)

    1 Pump On/Off Status 1 From Pump Control Panel

    2 Water flow status 1 Flow switch

    3 Pump Trip Alarm 1 From Pump Control Panel

    4 Pump Auto / Manual Status 1 From Pump Control Panel

    5 Pump Start/stop command 1 Relay Output From BMS

    6 Pump motor temperature high 1 From Pump Control Panel7 Low pressure discharge switch 1 Liquid pressure switch

    8 Low pressure switch 1 Liquid pressure switch

    TOTAL 1 6 1

    Total Eelctric Driven Fire Pumps Points 2 12 0 2

    Total Electric Driven Fire Pumps Points

    2

    16