Page 1: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

1

By Ertanto Vetra

Refrigeration System

Page 2: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Outlines

• Introduction

• Overview

• Ideal Vapor Compression Refrigeration Cycle

• PH Diagram

2

Page 3: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Introduction

3

Page 4: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Introduction

4

Page 5: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Introduction

5

4K-14E-1

4E-2

4C-1

4C-6

4E-3

4C-44C-34C-24C-12

4E-7 4E-10

4E-84E-12

4E-9

3C-10

4E-13 4E-14

3E-123E-5

4C-5

4E-4

3E-13

LC

UIC

UIC

PC

LCLC

LC

LC

LC

LC

UIC

HC

LC

PC

LC

LC

Page 6: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Overview

6

• Cooling capacity of a refrigeration system = the rateof heat removal from the refrigerated space(expressed in tons of refrigeration)

• The capacity of a refrigeration system that canfreeze 1 ton (2000 lbm) of liquid water at 0°C (32°F)into ice at 0°C in 24 h is said to be 1 ton.

• One ton of refrigeration is equivalent to 211 kJ/minor 200 Btu/min.

• The cooling load of a typical 200-m2 residence is inthe 3-ton (10-kW) range

Page 7: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Ideal Vapor Compression Refrigeration Cycles

7

Page 8: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Ideal Vapor Compression Refrigeration Cycles

8

Page 9: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Ideal Vapor Compression Refrigeration Cycles

9

Evaporator 41

Compressor 12

Condenser 23

J-T Expansion 34

Page 10: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

P-H Diagram (Propane)

10

Page 11: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

PH Diagram Exercise

An ideal Propane Refrigeration Cycle is used to cool a processstream from 5°C to -35°C. The cycle rejects heat to theenvironment using a cooling water with the inlet CW temp =35 °C. If it is assumed that the minimum temperatureapproach in the exchanger is 5 °C. Determine:• P-H Diagram Plot• The Operating Pressure of Propane Evaporator &

Condenser• Duty of Propane Evaporator, Condenser, Compressor, and

cycle COP– Compare with the results obtained by using property tables

(A16 to A18)

11

Page 12: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

12

Page 13: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

P-H Diagram (Propane)

13

1

23

4

Page 14: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Refrigerant Selection

14

Page 15: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

15

Page 16: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

16

Page 17: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

17

Page 18: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

18

Page 19: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

19

Page 20: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

20

Page 21: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Refrigerant Selection

• Two important parameters that need to be considered are thetemperatures of the two media (the refrigerated space andthe environment) with which the refrigerant exchanges heat.

• To have heat transfer at a reasonable rate, a temperaturedifference of 5 to 10°C should be maintained between therefrigerant and the medium with which it is exchanging heat.

• If a refrigerated space is to be maintained at -10°C, forexample, the temperature of the refrigerant should remain atabout -20°C while it absorbs heat in the evaporator.

21

Page 22: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Freezing pointEvaporator T should be well

above freezing T at operating P

Vacuum operationEvaporator P below atm P should be avoided. (however in some cases is still possible with some precautions)

Refrigerant Selection

22

Latent heat of vaporizationHigher latent heat lower flow rate of refrigerant, reduces the compression power

General considerationsAlways available, nontoxic, non flammable,non corrosive & have a low GHG emission. NG processing using C1,C2,or C3 refrigerant Olefins plant using ethylene, propylene Halocarbons refrigerant are nonflammable

Page 23: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

23Analyze These…

Page 24: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Cascade Cycle

24

Page 25: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Exercise – Cascade Cycle

Consider a two-stage cascade refrigeration system operating between the pressure

limits of 0.8 and 0.14 MPa. Each stage operates on an ideal vapor-compression

refrigeration cycle with refrigerant-134a as the working fluid. Heat rejection from the

lower cycle to the upper cycle takes place in an adiabatic counter-flow heat exchanger

where both streams enter at about 0.32 MPa. If the mass flow rate of the refrigerant

through the upper cycle is 0.05 kg/s, determine

1. The mass flow rate of the refrigerant through the lower cycle,

2. The rate of heat removal from the refrigerated space and the power input to the

compressor, and

3. The coefficient of performance of this cascade refrigerator.

25

Page 26: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

26

Page 27: Introduction Overview PH Diagram - Weeblytmg3201.weebly.com/uploads/1/1/8/3/11832443/09-refrigeration_system.pdfConsider a two-stage cascade refrigeration system operating between

Multistage Compression with Intercooling