introduction & agenda
DESCRIPTION
Introduction & Agenda. Why we need VFDs What is a VFD Savings Where VFDs are used How VFDs are used Motor Questions Honeywell VFD Product Line Tools. Why Do We Need VFDs?. Green. Energy. Smart. Savings. Why Do We Need VFDs?. Buildings use 40% of US Energy - PowerPoint PPT PresentationTRANSCRIPT
3
Introduction & Agenda
• Why we need VFDs• What is a VFD• Savings• Where VFDs are used• How VFDs are used• Motor Questions• Honeywell VFD Product Line• Tools
4
Why Do We Need VFDs?
Green Energy
Smart Savings
5
Why Do We Need VFDs?
• Buildings use 40% of US Energy • 74% of U.S. Electricity used by
Commercial Buildings (source: US DOE, 2008 Building Energy Data Book)
• ½ of electricity used to move air and water
• How a VFD’s Save Electricity (Money)?- Vary Speed of a motor
- Most motors are oversized for peak demand
- Motor Maintenance Savings
- Soft Start
- Reduced Green House gases (externalities)
• Improved Comfort
VFDs Are a Key Component to an Energy Strategy
6
What is a VFD?
V1
C
+
-
MotorVariable Frequency Drive(VFD)
V3 V5
V2 V4 V6
RectifierBridge DC Bus –
circuit
IGBT (Insulated
Gate BipolarTransitor)
Inverter
Power Supply
Energy Savings based on Proven Technology
EM
C F
ilter
3 Phase
Input AC
Ch
ok
e
DC Choke
7
What is a VFD?
Control Section
Digital & Analog I/O, Control Loops,
Parameters & Applications
Power Section
Motor Control & Protection
User Interface
Keypad, Display, PC &
Fieldbus Connections
8
• Affinity Laws-Pumps & Fans
-Centrifugal & Axial
Savings
Flow Rate Rotational Speed
System Friction Rotational Speed2
Horsepower Rotational Speed3
Percent Frequency PercentSpeed (Hertz) Savings100% 60 0%90% 54 27%80% 48 49%70% 42 66%60% 36 78%50% 30 88%40% 24 94%30% 18 97%20% 12 99%10% 6 100%0% 0 100%
Variable Frequency Drive Electricity Savings
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Pump Speed (%)
Pum
p Po
wer D
eman
d (%
)
VFD & Pump CV Pump
88%
66%
97%
27%
Percent Savings
9
Savings - Typical HVAC System Load
• % O
per
atin
g T
ime
•0
•2
•4
•6
•8
•10
•12
•% Flow or Volume•100•50 •75•25•5
•Data Supplied by the U/K Dept of Trade & Industry
•Variable Flow is Possible
10
• Pump Systems• Methods
-By-Pass
-Modify Impeller
-Change Impeller
-Throttling Valve
-New Pump
-VFD
Savings
Flow Rate (%)P
ow
er (
%)
1000
100
Speed
11
• Fan Systems• Methods
-By-Pass
- Inlet Vane Pitch
-Control Damper
-New Fan
-Eddy Current Drive
-VFD
Savings
Po
wer
(%
)
Speed (%)
12
Where VFDs Are Used
• Supply and return fans• Cooling Towers• Compressors• Stairway and parking
ventilation• Boiler pumps and fans • Kitchen Hoods• Roof Top Units• Air Handlers• Elevators• Escalators
VFDs are crucial part of energy management system
13
Where VFDs are Used – Fans and Pumps
14
Where VFDs are Used - Packaged Equipment
15
How VFDs Are Used: Fan Application – VAV System
•Cooling & heating coils
•Filter
•Supply fan
•Damper
•Pressure & flow sensor
•VAV box
•VAV box
•VAV box
•Damper
•Return fan
•Flow sensor
•Damper
•Damper
•Damper
16
•Cooling & heating coils
•Filter
•Supply fan
•Pressure & flow sensor
•VAV box
•VAV box
•VAV box
•Return fan
•Flow sensor
•Damper
•Damper
•Damper
How VFDs Are Used: Fan Application – VAV System
17
Where Drives are Used: Cooling Tower Fans
• Reduced wear and tear• Improved control• Fewer start/stops• Energy Savings
•Chiller•Cooling tower
•Fan
•Condensor pump
18
•Chillers
•Primary system
•Secondary system
•Primary pumps
•Secondary pumps
•Cooling coils
Where Drives are Used: Primary Chilled Water Pump
• Chilled water, hot water, domestic, boiler feed
• Multiple pump applications
- Lead-Lag
- Multi-follower
19
VFD
• PID Application
20
VFD
• T775 Application
21
DDC Interface
22
Motors / Concerns
Motor Name Plate Data is Fundamental to Drive Selection
23
Motors
Inverter Duty Rated Motors Preferred
24
Products – NX Family
Brief review of Honeywell’s Energy Saving VFDs
NXS Product Family NXL Product Family NXB Cool Blue Bypass
1.5 - 250 HP 480Vac 1 - 40 HP 480Vac 1.5 - 250 HP 480Vac
1 - 125 HP 208/230Vac .5 - 3 HP 208/230Vac 1 - 125 HP 208/230Vac3 - 100 HP 575Vac 3DI, 2AI, 1AO, 2RO 3 - 100 HP 575Vac
6DI, 2AI, 1AO, 2RO NEMA 1, 12, 3R IO dependant upon Drive
NEMA 1, 12, 3R Available 3 Day Service Class NEMA 1, 12, 3R Available
3 Day Service Class Built in AC Choke & RFI Filter * 10-20 Day Service Class
Built in AC Choke & RFI Filter Modbus Standard Field Bus dependant upon Drive
Option Cards for BACnet, Option Cards for BACnet, Lon, Fused Disconnect Option
Modbus, Lon, N2 N2, Profibus and others 2 or 3 Contactor Bypasses
Profibus, and others *No A208/230Vac C Choke on Open Chassis Auto-Bypass Option
Obsolete
25
Products – SmartVFD family
Honeywell’s Energy Saving VFDs next generation
SmartVFD HVAC SmartVFD Bypass SmartVFD Compact
1.5 - 250 HP 480Vac 1.5 - 250 HP 480Vac .5 - 7.5 HP 480Vac 3~/3~
1 - 125 HP 208/230Vac 1 - 125 HP 208/230Vac .5 - 3 HP 230Vac 1~ or 3~/3~
3 - 100 HP 575Vac NXS Now 3 - 100 HP 575Vac (2012) NXS Now .25 - 1.5 HP 115V 1~/230V 3~
6DI, 2AI, 1AO, 2RO IO and Fieldbus same as drive 1 - 7.5 HP 575Vac 3~/3~
NEMA 1, 12, 3R Available 3 Day Service Class Open Chassis with NEMA1 kit
3 Day Service Class 10 Day Service Class (20 Day NEMA 12/3R) 3 Day service Class
Built in DC Choke & RFI Filter Field Bus same as Smart VFD HVAC Modbus Standard
BACnet, Modbus, N2 Standard Fused Disconnect Option RFI filter Standard
Lon Card option available 2 and 3 Contactor Bypass Options available 6DI or 3DI options available
Enhanced Keypad Auto-bypass option
26
SmartVFD HVAC
• Intuitive Interface• Easy Commissioning• Standard Communication• Reliable Protection• Effective Operation/Monitoring
The SmartVFD for Smart Buildings
27
Intuitive Interface
• High resolution Display• Startup Wizard• PID Setup wizard• Intuitive commissioning• Manual in keypad• Help screens• Real time clock• Local/Remote Button• Memory in keypad
Intuitive, Effective, Consistant SMART
28
Built-In Protection
• DC Choke- Built in resistors for
upfront protection
- Meets EN61800-3-12
• Conformal Coated/ Varnished boards
• C2 class EMC filter standard
• Built in Fan- NEMA12 extra fan
Harmonic, RFI, Environmental Protection
29
SMART Software
• Power loss ride through• Fire mode• Memory in keypad• Pump and Fan Cascade• Ramp Time Optimizer• Maintenance Counters• Pump Soft Fill• 2 PID Controllers• Fault Reset• Motor Pre-heat
The SmartVFD for Smart Buildings
32
Smart VFD HVAC Control Board
•ARM9 Processor (200MHz)
•Flash Memory 32Mb
•RAM Memory 128Mb
•ARM9 Processor (200MHz)
•Flash Memory 32Mb
•RAM Memory 128Mb
33
Easy Communications
• Standard- RS485
BACnet N2 Modbus
- Ethernet Modbus/TCP BACnet/IP
- Option Cards LonWorks
Built-in Communications
34
Smart VFD HVAC Fieldbus RS-485
• RS485 2 Wire Connection
-BACnet
-N2
-Modbus• RS485 4 Wires
-Keypad
-PC Tools
RS-485 2W
RS-485 2W
RS-485 4W
RS-485 4W
35
Smart VFD HVAC Fieldbus Ethernet
• Ethernet connection is integrated to the main processor
• Supported General Protocols- TCP/IP (basic protocol)- DHCP, AUTOIP, IPConfig
• Supported Industrial Protocols- Modbus/TCP- BacNet IP- Vacon HMI protocol (for PC tool usage)- Ethernet/IP and Profinet (Future option)
• Cable max length 100m (to switch)• Future
- FTP - HTTP, simple web browser interface
EthernetEthernet
36
Maintenance
• Keep it dry• Keep it clean• Tight connections (Not too tight)• Fan clearance• Remove fan in demo• Right Enclosure
37
Review Demo VFD Wiring, Switches
38
2 Position Slide Switches
• ON RS485 OFF• Current AO1 Voltage• Current AI2 Voltage• Current AI1 Voltage
39
SmartVFD BYPASS
• Low total installed cost• Compact size• Easy component access • NEMA 1, 12, 3R• All configurations
- Disconnect
- 2-contactor
- 3-contactor
- 3-contactor with AutoBypass
Height Comparison Cool Blue Next Gen 2ctr (1 - 7.5HP) 40 in 30 in 3ctr (1 - 7.5HP) 40 in 37 in 2ctr (10-20HP) 46 in 33 in 3ctr (10-20HP) 46 in 40 in 2ctr (20-40HP) 53 in 43 in 3ctr (20-40HP) 53 in 53 in
40
Auto Bypass
•Drive fault will cause automatic BYPASS
41
Available configurations
•Disconnect, 2-contactor, 3-contactor
Drive
Drive
Fused/CBDisconnect
OverloadProtection
Drive
Fused Disconnect
42
Honeywell’s Micro Drive Overview
• Many Micro VFDs have too many or too few capabilities
• Chose the options to meet the application:- HP and Voltage- Interface
- Filter
- Enclosure
- Inputs and Outputs
• 3 Year Warranty - Longer than all competitors
• Small installed size • Fast installation• Intuitive commissioning • Easy communication
Optimize Capabilities, Minimize Waste
43
Physical Options inputs/Outputs and Communications
• Power Range- 208/240VAC, 1~in/3~out, .25HP to 3HP- 460VAC, 3~in/3~out, .5 to 7.5HP- 208/240 VAC 3~in/3~out, .25HP to 3HP- 575VAC 3~in/3~out, 1HP – 7.5HP- 115Vac 1~in/230Vac 3~out, .25HP – 1.5HP
• Two Application Interfaces (API) available- Full API
LCD, 2 Analog In, 1 Analog Out, 6 Digital In, 1 Digital Out, 2 Relay Outputs
- Limited API LCD, 1 Analog In, 1 Analog Out, 3 Digital In, 1
Relay Output• Modbus connection standard in both API• Enclosure - Open Chassis or NEMA 1 kit• Optional EMC Filter on some versions
FRAME H W D
MI1 6.2” 2.6” 3.9”
MI2 7.7” 3.5” 4.0”
MI3 10.2” 3.9” 4.3”
44
Fast Installation
• Din Rail and Screw Mountable
• Book shelf, Side-by-side installation - No side clearance required
•Screw Holes •Screw Holes
•Din Rail Clip
•Book Shelf Mounting
45
Intuitive Commissioning - KeyPad
• Click-Wheel Interface• Intelligent menu
navigation• Status Indicators
- Ready, Run, Stop, Alarm, Fault
• Control Indicators- Forward, Reverse, I/O, Keypad,
Fieldbus
• Menu Indicators- Reference, Monitor, Parameter,
Fault
46
Intuitive Commissioning - MCA
• Micro Communications Adapter
• Upload and Download parameters without powering the drive
• PC Connection to the drive for - Commissioning
- Control
- Monitoring
47
Honeywell Warranty Process Review
• 2 Year Standard Warranty• 3 Year Warranty with Commissioning
Training• Warranty period is from date of
purchase• Process:
- Call HON technical support for trouble shooting help
- No resolution, Warranty coordinator will issue RGA
- PO needed for advanced replacement
- Under warranty – Credit Adv Rep PO
- Warranties covered if the process is followed and product is not abused
Critical to Call Hot Line ~ No Return Goods
48
Tools
• Beyondinnovation.honeywell.com
- Pricing tools
- Product manuals
- Sales brochures
- Instruction sheets
- Submittal documents
- Marketing materials• Specify.honeywell.com
- CE spec information• Customer.honeywell.com/vfd
- Under Software:
- PC commissioning and control tool
- Firmware updates
- Energy savings calculators• Technical Support Hotline
- (888) 516-9347, option 4
49
Smart VFD HVAC Type code
HVFDSD3C0020G200 Smart VFD 3-Phase 460v, 2HP, Graphical Keypad, NEMA12, EMC
HVFDSD3C0020T100 Smart VFD 3-Phase 460v, 2HP, Text Keypad, NEMA1, EMC
50
How to Select the Drive - Questions to ask
NEMA rating? How harsh is the environment?Filtering requirements?Full load current (A) and HP of motor ?Power supply voltage?Single phase or 3 phase input?Does the application need a bypass?Is there a disconnect on site?
51
Tools - Product Selection
52
Tools – VFD PC Programming
• Commission• Control• Upload/Download• Monitor/Trend• Faults• Print/Save
54
Take-off Service
• Complete schedule and quote creation from blueprints and specs- We ask that drawings are submit in PDF or TIFF format via
email (no downloads via database)
• Partial jobs are OK• Cross-reference service• Contact Info:
- [email protected] - Tel: (888) 664-4092 - Fax: (877) 880-3386
Information OUT ∝ Information IN
55
Questions
http//.customer.honeywell.com/VFDBeyondinnovation.honeywell.com
Technical Support – 888 516 9347 option 4
56
Summary Questions
• If I reduce power to a motor by _____% I will save 58% in energy.• Honeywell drives come standard with DC chokes and RFI filters. T or F• What’s the DC choke’s function?• The keypad is portable and can hold 3 programs. T or F• Smart drives can be integrated into a Lon system. T or F• When sizing a vfd the hp is more important than amperage. T or F• Three reasons to buy a vfd?• Honeywell vfd’s have a 1 year warranty. T or F• It’s safe to open the vfd control compartment if the vfd is off. T or F• Will the drive tell you the time and date?• Can I start and stop the drive from the internal timeclock?
LAB 1Start up Wizard & Keypad basics
58
Start up Wizard Lab
• Run the Start-Up Wizard- Change the date and time to 8:33AM, June 6, 2012
- RPM 1880
- Nominal Current 6Amps
• Test out the drive with the demo unit- Flip DIN1 – start forward
- Move AL1 – ramp up the motor
- Toggle Din3 – what happens?
- Toggle Din6 – what happens?
• Reset factory defaults and let other person have a try
LAB 2Monitoring
60
Monitoring Lab
• Return to Main menu• Enter Monitor Menu• Select motor Torque in the Multi-monitor screen and
select OK• Scroll up to Energy Counter and hit enter• Run the demo, DI 1, Turn Analog knob, and notice
the values change.• Change whatever other values you would like
scrolling up and down through monitor values
LAB 3Fault Review
62
Smart VFD HVAC Faults in General
• Active faults- Max 10 Active faults simultaniously
• Faulthistory - Max 40 faults in history
• Different fault types:- FAULT = Stops the Motor if not programmed otherwise
- ALARM = Tells about unwanted conditions. No affect on motor
- INFO = Might need resetting but wont have an affect on the motor
63
Smart VFD HVAC If a fault happens
• The fault is displayed on the screen (screen blinks)• Stop button works as reset (press 1s)• Remote reset from Fieldbus or I/O• The fault can be accessed and reseted from the diagnostics menu• Faultcodes: Chapter 3.7.2 In the application manual
• Flip Din3 – external Fault• Go the active Fault screen• Review the fault history
LAB 4Other Parameters
65
Quick Setup
• Change Min Frequency to 10hz- Turn on drive to minimum and confirm
• Change acceleration and deceleration time to 2 minutes – run and test
• Change acceleration and deceleration time to 2 seconds – run and test
• Change Preset Frequency 1 to 25Hz Flip DIN4 to test• Change Preset Frequency 2 to 30Hz Flip DIN5 to test• Change I/O A Control reference to AI2 - test• In User Settings save parameters to the keypad
- Then download from the keypad.
66
Other Parameters
• Auto-Restart- Enable Auto-Restart
- Enable external fault auto restart – 4 times
- Test using the external fault functionality
- Place the Auto-restart parameter in favorites
- Confirm the parameter is in the favorites menu
• Motor Control- Change the Switching Frequency to 5kHz
Can affect the noise of the motor
67
Prohibit Frequencies
• Complete this lab as a team• Prohibit frequency• Set range 1 low at 30 and high at 35• Set range 2 low at 45 and high at 50• Start vfd, twist pot slowly to observe• Save your program to the keypad and download your
program from the keypad (M6)
68
Motor Pre-Heat
• Complete this lab individually• Motor Preheat Function• Turn DIN 1 OFF• Go to M3.1.2.3 PREHEAT FUNCTION• Select TEMP LIMIT, enter 40 / 38 degrees C, Hit BACK• Select ADD TO FAVORITES, Hit OK• Note DO 1 is energized and display reads HEATING• Go to 2.2.11 (BASIC MONITORING)• Note UNIT TEMPERATURE• Go to M7 Favorites, Select PREHEAT TEMP LIMIT• Enter a temperature 5 / 7 degress C below Unit Temp• Note DO 1 is De-energized, Hit BACK• Select REM FROM FAVORITES to remove from Favorites list
LAB 4PID Wizard
70
PID Wizard
• Via the Basic parameters enable the PID Wizard- Programming assuming the following
0-2 inches of water column range Measured to the tenths place Sensor wired into AI1 Normal pressure relationship – Not inverted Set point 1.5 inches Set Sleep Mode
71
Lab 12
• Complete this lab individually• PID setup• Go to QUICK SETUP, change MIN FREQ to 0 and activate PID
MINI WIZARD• Enter following selections:• In wg for engineering units• 0 for process unit minimum• 5 for process unit maximum• 2 for process unit decimals• AI1 for FB (feedback) 1 source• 0-10 V for AI1 signal range• NORMAL for error inversion• KEYPAD SP 1 for SP (setpoint) 1 source• 2 for Keypad SP 1• NO for Sleep Function• Press OK to exit• Turn DIN1 on, twist pot and observe• Go to MONITOR, PID CONTROLLER 1, twist pot, observe• Go to 3.12.1.2 and set your INTEGRATION TIME
LAB 5Keypad Control
73
Lab 14
• Complete this lab individually• Keypad Control• Will override DIN’s but not active fault• Press LOC/REM button, Select LOCAL• Press LOC/REM button again, select CONTROL PLACE• Note multimonitor screen below, insert tod in top right• Hit OK on speed reference bar (blinks). Ramp the motor
up and down using the up and down arrow keys • Hit the STOP button, follow instructions• Return to CONTROL PLACE, ramp up and down• Return to IO control by pressing LOC/REM again and
selecting REMOTE• Process simplified next rev
74
http//.customer.honeywell.com/VFDBeyondinnovation.honeywell.comTechnical Support – 888 516 9347
75
Lab 1
• Relax • Complete this lab as a team• Keypad Review• Menu Review• Restore Factory Defaults
- M6 User Settings; M6.5 Parameter Backup; M6.5.1 Restore factory defaults
- Unit restarts
- Select ENGLISH, US, Set TIME, DATE (day.month), YEAR
- Startup wizard = Yes
- Select FAN, 1720 RPM, 3.55A
• Puts you back in Basic Monitor Mode
76
Lab 2
• Complete this lab individually• Review QUICK SETUP (M1) parameters & observe vfd
behavior• EXPLAIN DIN 1-6 - Write down DIN settings? • Select M1 (scroll to following settings)
- Change MOTOR COS PHI to .85 / .80
Push ok on parameter, push ok on EDIT, make change (scroll east, west, example)
- Change I/O CTRL REF to AI1
- Change PRESET FREQ 1 to 20 / 25
- Change PRESET FREQ 2 to 40 / 45
- Change ACCEL TIME 1 to 20 / 30 (120 example)
- Change DECEL TIME 1 to 15 / 25
• Go to parameter M3.2.4 set to RAMPING• EXPLAIN SEQUENCE
77
Lab 2 Continued
• Turn on DIN 1, Twist VOLTAGE INPUT – Observe• Turn on DIN 2 – Nothing• Turn on DIN 4 – Vfd goes to preset 1 speed – turn off• Turn on DIN 5 – Vfd goes to preset 2 speed• Turn on DIN 4 – Vfd goes to preset 3 speed (not in
Quick Setup)• Turn on DIN 3 – External shutdown contact –
observe display – turn off• Turn on DIN 6 – External fault reset
78
Lab 3
• Complete this lab individually• Monitoring Menu Review• Select M2 (note number (8))• Note MULTIMONITOR icon• Review 8 monitoring point groups (Hit ok on each)• Go to M2.2• Start vfd and twist AI1• Note difference between Output Frequency and Freq
Reference (accel, decel delay)• Scroll to Analog Input 1, twist pot, observe• Scroll to Analog Output 1 (meter), twist pot, observe
value and meter
79
Lab 3 Continued
• Select MULTIMONITOR• Scroll to lower left block, hit OK, scroll to REAL
TIME CLOCK, hit OK• How many point options are available to display?• Scroll to lower right block, hit OK, scroll to ANALOG
INPUT 1, hit OK• Twist pot, observe• Scroll to lower middle block, hit OK, make your
selection
80
Lab 4
• Complete this lab individually• Fan won’t run until damper interlock is made• Explain DIG IN SLOT A. 2 • Turn DIN 1 off• Go to parameter M3.5.1.11 RUN INTERLOCK 1• Hit OK and EDIT (scroll through options on both
sides of .)• Set to DigINSlotA.2 / 4• Turn DIN 1 on; Result?• Turn DIN 2 / 4 on; Result?• Return to parameter M3.5.1.11, set to DigINSlot0.2 / 4• Turn on DIN 1; fan should run
81
Lab 7
• Complete this lab individually• Fault Review (M4 Diagnostics Menu)• Max 10 Active Faults simultaneously• Max 40 Faults in history• FAULT, ALARM, INFO• Blinking fault displayed on keypad• Fault codes listed in chapter 3.7.2 in Application Manual
82
Lab 7 Continued
• Turn on DIN 1, twist pot• Turn on DIN 3, external shutdown switch• Display blinking fault, Hit OK, Read info, Notice Fault Code,
Hit OK• Fault name displayed, Hit OK, Select DETAILS• Review fault details, Hit BACK• Turn off DIN 3, Hit BACK• Select RESET FAULTS, Select RESET FAULTS (Active Faults
= 0)• Motor starts
• Turn on DIN 3, Turn off DIN 3• Hit BACK, Hit BACK, Select RESET FAULTS, Select RESET
FAULTS, Motor runs
83
Lab 7 Continued
• Complete this as a team• Go to PROTECTIONS (M3.9)• Select M3.9.2 EXTERNAL FAULT• Select EDIT, Review options• Select ALARM• Turn on DIN 3, Note alarm, Motor continues to run• Reset (clear) ACTIVE FAULT• Go back to M3.9.2 and make EXTERNAL FAULT a FAULT• Review options in M3.9.1 AI LOW FAULT
84
Lab 8
• Complete this lab individually• Motor Preheat Function• Turn DIN 1 OFF• Go to M3.1.2.3 PREHEAT FUNCTION• Select TEMP LIMIT, enter 40 / 38 degrees C, Hit BACK• Select ADD TO FAVORITES, Hit OK• Note DO 1 is energized and display reads HEATING• Go to 2.2.11 (BASIC MONITORING)• Note UNIT TEMPERATURE• Go to M7 Favorites, Select PREHEAT TEMP LIMIT• Enter a temperature 5 / 7 degress C below Unit Temp• Note DO 1 is De-energized, Hit BACK• Select REM FROM FAVORITES to remove from Favorites list
85
Lab 9
• One person program 9 other person 10• Use internal timeclock to start stop vfd• Turn all DIN’s off• Insert time of day in multimonitor – note time• Go to parameter 3.11.1.1 – 00:00 (Interval 1)• .2 – 23:00• .3 – Sunday• .4 – Saturday• .5 – TimeChannel.1• Go to parameter 3.5.1.1 – TimeChannel.1• Vfd should start• Press STOP button on keypad, follow instructions to
restart
86
Lab 10
• One program 9 other 10• Use internal timeclock to invoke preset speed• Turn all DIN’s off• Insert time of day in multimonitor – note time• Note preset speed 1 setting and put in Favorites• Go to parameter 3.11.2.1 – 00:00 (Interval 2)• .2 – 23:00• .3 – Sunday• .4 – Saturday• .5 – TimeChannel.2• Go to parameter 3.5.1.16 – TimeChannel.2• Vfd should run at preset speed 1• Press STOP button on keypad, follow instructions to restart
87
Lab 11
• Restore factory defaults• Setup drive• Setup mini wizard using defaults
88
Lab 12
• Complete this lab individually• PID setup• Go to QUICK SETUP, change MIN FREQ to 0 and activate PID
MINI WIZARD• Enter following selections:• In wg for engineering units• 0 for process unit minimum• 5 for process unit maximum• 2 for process unit decimals• AI1 for FB (feedback) 1 source• 0-10 V for AI1 signal range• NORMAL for error inversion• KEYPAD SP 1 for SP (setpoint) 1 source• 2 for Keypad SP 1• NO for Sleep Function• Press OK to exit• Turn DIN1 on, twist pot and observe• Go to MONITOR, PID CONTROLLER 1, twist pot, observe• Go to 3.12.1.2 and set your INTEGRATION TIME
89
Lab 13
• Complete this lab as a team• Prohibit frequency• Set range 1 low at 30 and high at 35• Set range 2 low at 45 and high at 50• Start vfd, twist pot slowly to observe• Save your program to the keypad and download your
program from the keypad (M6)
90
Lab 14
• Complete this lab individually• Keypad Control• Will override DIN’s but not active fault• Press LOC/REM button, Select LOCAL• Press LOC/REM button again, select CONTROL PLACE• Note multimonitor screen below, insert tod in top right• Hit OK on speed reference bar (blinks). Ramp the motor
up and down using the up and down arrow keys • Hit the STOP button, follow instructions• Return to CONTROL PLACE, ramp up and down• Return to IO control by pressing LOC/REM again and
selecting REMOTE• Process simplified next rev
97
Demo PC Software
98
http//.customer.honeywell.com/VFDBeyondinnovation.honeywell.comTechnical Support – 888 516 9347
99
Lab 4
• Complete this lab individually• Create a maintenance alarm (fault)• Select MULTIMONITOR (M2.1)• Place MaintenanceCounter1 in lower left (scroll to
lower left and hit OK, find MaintenanceCounter1 and hit OK)
• Set DIN1 to OFF• Go to M3 (Go up)• Go to M3.15.1 select RUNTIME / REVOLUTIONS• Go to M3.15.2 enter .01 hours / 1K• Go to Multimonitor• Set DIN1 to ON, wait time, rpm• Observe alarm
100
Lab 4 Continued
• Reset alarm• Go to M3.15.1 and set to NOT USED• Go to M3.15.4 and select RESET• Go to M4.1 and review ACTIVE FAULTS• Time in lower right corner, how much?• What is it?• Press OK and DETAILS• Go to M4.2 and RESET FAULTS• Fault will be removed from ACTIVE and stored in
FAULT HISTORY• More on FAULTS in later lab
101
Lab 6
• Complete this lab individually• External Fault Auto Reset• Start vfd, twist pot, run motor, turn DIN 3 on, observe• Turn DIN 6 on then off to reset fault• Go to M3.10.1 and set to ENABLED (please note this
parameter is also in Quick Setup)• Go to M3.10.3 and set to 7 / 10 seconds• Go to M3.10.12 and set to YES• M3.10.4 and 5, read HELP, don’t change• Turn DIN 1 on, twist pot, wait 10 seconds• Turn DIN 3 on, wait 5 seconds, turn DIN 3 off• Observe behavior• Next person repeat• Fault active and history lab next