intgrated protection and control system
DESCRIPTION
INTGRATED PROTECTION AND CONTROL SYSTEM. DDS. INTEGRATED CONTROL. INTEGRATED PROTECTION. APPLICATION FIELDS. SUB-TRANSMISSION SUBSTATIONS DOUBLE/SINGLE BUSBAR LAYOUTS, BREAKER AND A HALF ETC. DISTRIBUTION SUBSTATIONS SINGLE AND DOUBLE BUSBAR LAYOUTS TRANSMISSION SUBSTATIONS - PowerPoint PPT PresentationTRANSCRIPT
gGE Power ManagementDDS Integrated P&C System
INTGRATED PROTECTION AND CONTROL SYSTEM
DDS
INTEGRATED PROTECTION
INTEGRATED CONTROL
gGE Power ManagementDDS Integrated P&C System
APPLICATION FIELDS
SUB-TRANSMISSION SUBSTATIONS DOUBLE/SINGLE BUSBAR LAYOUTS, BREAKER AND A HALF
ETC.
DISTRIBUTION SUBSTATIONS SINGLE AND DOUBLE BUSBAR LAYOUTS
TRANSMISSION SUBSTATIONS NO KV LIMITATION
gGE Power ManagementDDS Integrated P&C System
Neutral Current Transducer
Voltage Transducer
Phase Current Transducer
kW/kVAR Transducer
Power Factor Transducer
Other Transducers
CT´s
CT´s
OutputsInputs
PowerSupply
Modem RemoteTerminal
Unit
Alarms and TripsProtection Relay
Host
Radio
Traditional SCADA RTU
gGE Power ManagementDDS Integrated P&C System
DigitalOutputs
DigitalInputs
Comm.Port
GE PM SOLUTION
DMS INTEGRATED MODULE
CT´s VT´s AnalogInputs
gGE Power ManagementDDS Integrated P&C System
• Power Supply Module (possible redundancy)• Magnetic Module: 8 CT/VT• Digital Inputs: 21• Digital Outputs: 12• Digital I/O: 7 inputs
8 outputs
•Analog inputs module, 4 inputs
DMS Units Hardware Module
• CPU: 16 bit MP based• Communications CPU: 16 bit
MP based, RS-232, RS-485, Fiber Optics communications available.
• Front bus + MMI module (+ Graphic LCD + 6 control
keys)
CONTROLSUB-MODULE
Com
mun
. CP
U
Con
trol
CP
U
gGE Power ManagementDDS Integrated P&C System
DMS UNITS CONTROL FUNCTIONS
ALARMS
SELECT
SELECT
REMOTE
79
ALARMSMAINMENU
F1
F2
F3
F4
B2
B1
SWITCHGEAR CONTROL Up to 7 switchgear (or dynamic elements) control
and real time monitoring.
MIMIC DISPLAY Allows real time monitoring (1 or 2 contacts
selectable) and local operation of switchgear.
gGE Power ManagementDDS Integrated P&C System
F1
F2
F3
F4
Ia: 62.00A
Ib: 60.00A Vab: 0.00 kV
Ic: 60.00A Vbc: 0.00 kV
In: 0.00A Vca: 0.00 kV
I2: 0.00A VBB: 0.00 kV
P: 0.00W Q: 0.00 Mvarcos:0.99
INPUTS/OUTPUTS
METERING Default metering for every unit: Ia, Ib, Ic, In, I2,
Vab, Vbc, Vca, Vbus, P, Q, f, Cos phi.
DMS UNITS CONTROL FUNCTIONS
gGE Power ManagementDDS Integrated P&C System
F1
F2
F3
F4
52 MAINTENANCE ALARM *16:27:39 26029752 STATUS * 16:30:30 260297
CURSOR F1:MEASUR. F2:ACK. F3:ACK-ALL
[ACTIVE ALARM, NOT ACKNOWL.]
ALARMS PANEL 96 Configurable alarms (32 protection, 48 control,
16 comm.) Alarm format: Date, time, Description text. Alarm status(active/non active, acknowledged/not
acknowledged)
Alarm acknowledgement through graphical display (local HMI)
DMS UNITS CONTROL FUNCTIONS
gGE Power ManagementDDS Integrated P&C System
OPERATIONS & BAY INTERLOCKINGS Up to 16 operations: 2 fixed (block / unblock
control)14 programmable
operations Configurable parameters for each operation.
Operation description (text) Operation conditions (4 per operation) Failure conditions (3 per operation) Success conditions (1 per operation) Timers Operation Output 1
per operation Success Operation confirm
Up to 4 programmable “static” interlockings.
DMS UNITS CONTROL FUNCTIONS
gGE Power ManagementDDS Integrated P&C System
Analog inputs: Up to 4 chanels Selectable (each one independently) as: 0-1 mA, 0-5
mA, 4-20 mA, -2.5/+2.5 mA, -10/10 V.
Pulse Inputs: (Any digital input can be a pulse counting input)
9 digit counter (up to 999999999 Kwh or Mwh) 1-65000 Kwh per pulse 4 choices KWh, KVArh, MWh, MVArh
Inputs for tap load changer position monitoring:
Up to 8 digital inputs in Gray/BCD/Binary code or through analog input.
DMS UNITS CONTROL FUNCTIONS
gGE Power ManagementDDS Integrated P&C System
CAPTURE
PROTECTION CONTROL
LEVEL 0
LEVEL 1
LEVEL 2
LEVEL 3 REMOTE CONTROL
CAPTURE
IEC 870-5
GENERAL APPLICATION
TRANSMISSIONSUBSTATIONS
Protection and Control for:• Line• Transformer• Busbars
SCHEMES:• Breaker and a half• Double busbar• Single busbar
SUBSTATION ARCHITECTURE
gGE Power ManagementDDS Integrated P&C System
Protection System Integration Architecture
HV Bays
Transformer BaysMV Bays
PhoneAccess
GPS Sync.
PC laptop for local access
LEVEL 2
LEVEL 1
Transmission Lines
ALPS RELAY
IEC870-5-101
CONTROL
FAC
OTHER IED´S
gGE Power ManagementDDS Integrated P&C System
Modem
HV Bays
Transformer Bays MV Bays
SCADA
Printer
GPS Sync.
PC Dual
PC laptop for local access
Communicationchannel
(LEVEL 3)
LEVEL 2
LEVEL 1
GENESIS SOFTWARE
MLINK 115 kbps
FAC
Available LEVEL 1 units:
DMS, DTP, DFF,
DBF, DRS, MOV,
DTR, SMOR, ALPS
PROTECTIONS
IEC870-101
Control System Architecture
gGE Power ManagementDDS Integrated P&C System
SUBSTATION BAYS
SUB-TRANSMISSION OR DISTRIBUTION HV LINE
HV BUS COUPLER & METERING POWER TRANSFORMER MV FEEDER CAPACITOR BANK MV BUS COUPLER & METERING AUXILIARY/GENERAL SERVICES
gGE Power ManagementDDS Integrated P&C System
RAID2 Power Supplies
SCSI BusSCSI Bus
CPU - 1 CPU - 2
TCP/IP
RS-232 SwitchModem
IEC 870/5- 101Serv-Switch
FAC2000
g
Detail of Level 2 with Redundancy
SCREEN
KEYBOARD
MOUSE
RS232
DMS (x number of units)
DTP (x number of units)
RS-232 SwitchModemIEC 870/5- 101
Available LEVEL 1 units :
DMS, DTP, DFF,
DBF, DRS, DTR,
MOV, SMOR, ALPS
PROTECTIONS
gGE Power ManagementDDS Integrated P&C System
LEVEL 2 CONTROL FUNCTIONS
CONTROL FUNCTIONS Programmable configuration of the substation Control of the HV equipment Switchgear status indication Instantaneous metering of the substation Programmable Interlockings between bays Automatic Functions
- Load shedding for under voltage/frequency
- Sequential Operations between bays- Reactive power control combined with transformer tap changer
gGE Power ManagementDDS Integrated P&C System
CONTROL FUNCTIONS (Cont.) Metering Tariffication Alarm Treatment Maintenance Engineering
- Breaker monitoring (I2 t) Substation event register RTU for connection to remote central
dispatching centers
LEVEL 2 CONTROL FUNCTIONS
gGE Power ManagementDDS Integrated P&C System
GE-NESIS
WINDOWS BASED SOFTWARE WITH APPLICATIONS
GE_LOCAL
GE_INTRO
GE_OSC
GE_POWER
GE_CONF
GE_FILE
gGE Power ManagementDDS Integrated P&C SystemAPPLICATIONS DESCRIPTION
GE-LOCAL: LOCAL COMMUNICATION FOR SETTINGS, INFORMATION REQUEST AND ON-LINE VIEW OF PARAMETERS
Single line diagram position view, including status and metering values.
Access to information: Status, Metering, Events, Oscillography and Alarms for every position.
Viewing and change of settings. Access to Bay operations
gGE Power ManagementDDS Integrated P&C SystemAPPLICATIONS DESCRIPTION
GE_LOCAL
gGE Power ManagementDDS Integrated P&C System
GE-INTRO: CONFIGURATION AND ASSIGNMENT OF THE DDS INPUTS/OUTPUTS, ALARMS AND CONTROL LOGIC
Function: Protection inputs, outputs & events
configuration. Control inputs, outputs & events configuration. Control programming. Alarm configuration Graphical display configuration
APPLICATIONS DESCRIPTION
gGE Power ManagementDDS Integrated P&C SystemAPPLICATIONS DESCRIPTION
GE_INTRO
gGE Power ManagementDDS Integrated P&C System
GE-POWER: LEVEL 2 PROGRAM THAT ALLOWS REAL-TIME CONNECTION TO LEVEL 1 DEVICES
Single line Substation diagram including metering values and status.
Zoomed single line diagrams per position. Access to information: Status, Metering,
Events, Oscillography and Alarms for every position.
Remote viewing and change of settings. Access to switchgear operation.
APPLICATIONS DESCRIPTION
gGE Power ManagementDDS Integrated P&C System
GE-CONF: SUBSTATION CONFIGURATION
Functions: User configuration, privileges and
passwords. Position configuration. Per position: Status, metering and values
configuration for transfer to level 2. Per substation Data base generation.
APPLICATIONS DESCRIPTION
gGE Power ManagementDDS Integrated P&C SystemAPPLICATIONS DESCRIPTION
GE_POWER
GE_CONF
gGE Power ManagementDDS Integrated P&C SystemAPPLICATIONS DESCRIPTION
GE_POWER
GE_CONF
gGE Power ManagementDDS Integrated P&C SystemAPPLICATIONS DESCRIPTION
GE_POWER
GE_CONF
gGE Power ManagementDDS Integrated P&C System
GE-FILE: REPORTS AND DEMAND PROFILE GENERATION
Functions: Events, logs, alarms, etc. report
generator Operation reports and Demand Profile
generation per bay.
APPLICATIONS DESCRIPTION
gGE Power ManagementDDS Integrated P&C SystemAPPLICATIONS DESCRIPTION
GE_FILE
gGE Power ManagementDDS Integrated P&C System
GE-OSC: OSCILLOGRAPHY RECORDS DISPLAY AND ANALYSIS
Functions: Displays COMTRADE files (ASCII or binary),
including: Waveform Fasors Fault reports Digital signals operations
R-X Diagram module for distance relays analysis.
APPLICATIONS DESCRIPTION
gGE Power ManagementDDS Integrated P&C SystemAPPLICATIONS DESCRIPTION
GE_OSC