instruction manual ¥ ‡ ł control these valves to the open and closed positions via a built-in...

27
Instruction Manual Pneumatic actuator unit Type PA¢1/PA2¢ ¥ Piping Systems

Upload: trinhduong

Post on 07-May-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

Instruction Manual

Pneumatic actuator unitType PA¢1/PA2¢

¥ ‡Piping Systems

Page 2: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡2

The technical data is notbinding and not an expresslywarranted characteristic of thegoods. It is subject to change.Please consult our GeneralConditions of Supply.

Page 3: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 3

Table of Contents

Page1. Introduction/General Information 4

2. Manufacturer‘s Declaration 4

3. Intended Use 5

4. Safety Information 64.1 Due Care Required of Operator4.2 Special Hazards4.3 Transport and Storage

5. Actuator Design 9

6. Valve Design 10

7. Overview of System Components 13

8. Wiring Diagrams 14

9. Technical Data of the Actuator 15

10. Installation of the MFM on the Ball Valve 16with Built-in Limit Switch

11. Technical Data of MFM 18

12. Fastening Plate 20

13. Accessories 21

14. Subassemblies/Parts 26

Page 4: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡4

¢. Introduction

This instruction manual contains all the pertinentinformation on the design, installation and opera-tion of the pneumatic actuator types PA11/PA21 .

General Information

Hazard notices

Hazard notices are used in this manual to warnyou of possible injuries or damages to property.Please read and abide by these warnings at alltimes!

Warning symbols Meaning

Imminent acute danger!Failure to comply could result in deathor extremely serious injury.

Possible acute danger!Failure to comply could result inserious injury.

Dangerous situation!Failure to comply could lead to injuryor damage to property.Caution

Danger

Warning

2. EC Manufacturer‘s Declaration

The manufacturer, Georg Fischer Piping SystemsLtd, CH-8201 Schaffhausen, declares that thepneumatic actuators PA11/PA21 are not ready-to-use machines in the sense of the EC Directiveconcerning machines and cannot therefore meet allthe requirements of this directive.

Page 5: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 5

Operation of these actuators is prohibited untilconformity of the entire system into which thevalve and the actuator have been installed isestablished according to the EC Directives listedbelow.

98/37 EG EC Machine Guideline

Modifications to the actuator which have aneffect on the technical data given in this instruc-tion manual and its intended use, i.e. signifi-cantly alter the actuator, render thismanufacturer‘s declaration null and void.

Warning

3. Intended Use

The descriptions and instructions in the followingapply to the pneumatic actuators:

Type PA11 Pneumatic part-turn valve actuatorDA/FC/FO

Type PA21 Pneumatic part-turn valve actuatorDA/FC/FO

When built into ‡ valves and connected to asystem control, the purpose of these actuators is toł actuate ball valves with a control pressure

of 2.8 to 7 bar and up to a driving torque of20 Nm, and

ł depending on the type of pneumatic actuator,double acting (type designation DA) or singleacting with spring for fail-safe to CLOSE (typedesignation FC) or single acting for fail-safe toOPEN (type designation FO),

Page 6: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡6

ł control these valves to the OPEN and CLOSEDpositions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡works or already mounted by the customer,

ł indicate these positions OPEN and CLOSED viaan electric signal to the system control, if theactuator is equipped for this with the respectivesubassembly,

ł enable control of these positions through manualoperation in case of failure in the compressed airsupply, if the actuator is equipped for this withthe respective subassembly.

The actuator is not intended for uses other thanthose stated here. Prohibited in particular are:ł control pressures above 7.5 bar,ł manual operation with forces higher than permit-

ted according to prEN12570 (maximum retentionforces for operation of valves),

ł operating solenoid valves and position feedbackunits under water.

The actuator can only function properly if it hasbeen connected professionally as per the wiringdiagrams on page 66 for double acting opera-tion and for fail-safe OPEN or fail-safe CLOSEoperation, respectively.

4. Safety Tips

4.1 Due care required of the operator

The pneumatic actuators described herein weredesigned and manufactured with consideration toa risk analysis and the respective harmonized Euro-pean standards. They correspond to the latesttechnology and meet the mentioned prescribedsafety standards.

Warning

Page 7: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 7

Safety on the job can, however, only be realized ifall the necessary measures have been taken. It istherefore the responsibility of the system engineerand the operator of such systems into which thevalve with pneumatic actuator has been built toplan such measures and make sure they are carriedout.

The operator must make certain in particular thatł the valve with pneumatic actuator is only used as

it was intended for (see Section 3),ł the design parameters control air pressure and

voltage of electric subassemblies of the pneu-matic actuator, as indicated in the scope of or-der and delivery, are true and accurate,

ł the pneumatic actuator is only operated when inperfect working condition and the safety devicesfor the system supply of compressed air are re-gularly checked to make sure they are in perfectorder,

ł only qualified and authorized personnel plan,connect, and work with the actuator and thatemployees are instructed periodically in jobsafety matters according to the local regulations– especially as pertaining to electrical equip-ment, and

ł personnel is familiar with and observes this in-struction manual and the information containedherein.

4.2 Special hazards

Single acting, fail-safe OPEN and CLOSE (typedescription FO and FC) pneumatic actuators havepre-loaded springs that bring the valve into thepredefined position in case of compressed air loss.Dismantling these actuators is dangerous and mayonly be done by following special repair instruc-tions (available from ‡!) and under theguidance of a safety expert. Dismounting from thevalve may only be done in the safety position aftercutting off the compressed air supply.

Warning

Page 8: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡8

Prior to any work on the electric subassemblies ofthe pneumatic actuator, the electrical connectionsof the control voltage should be disconnected.Any necessary live-line adjustments may only bedone with special insulated tools.

Furthermore, the operating instructions of themanual valve must also be observed. They arean integral component of this manual.

4.3 Transport and storage

The actuators must be handled, transported andstored with care. Please note the following points:ł The actuators should be transported and/or

stored in their original unopened packaging.ł The actuators must be protected from harmful

physical influences such as dust, heat (humidity).ł It is important that the connections are neither

damaged by mechanical nor thermal influences.ł Prior to installation, the actuators should be in-

spected for transport damages. Damaged actu-ators must not be installed.Warning

Page 9: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 9

5. Actuator Design

The pneumatic actuator PA ¢1/PA2¢ features thefollowing components:ł Housing with screwed on spring cover, position

indicator and Namur air connectionł Spring cover with mounted, preloaded spring

assemblył Namur air connection with internal reversing

bore for the DA functionł Piston with rackł Pinion shaft

For special applications, actuators can be equip-ped with various supplementary kits/accessories.(see Accesssories).

1 Spring cover2 Optical position indicator3 Housing of PP-GF4 Piston with rack5 Pinion shaft6 Preloaded spring assembly7 Connection for control air

Rp1/8“

!

$% &

/

Page 10: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡10

1

4

3

2

5

3a

open

close

Mounting without manual override

ł Screw the adapter plate with the fixed clampstightly onto the actuator (note the cam positions).

ł Mount the multifunctional module on the ballvalve without built-in limit switches.

1. Housing2. Housing cover3. Indexing disk* with switching cams 3a4. Screws5. Connector plug 3P + E per

DIN EN 175301-803*(formerly DIN 43650)

*only for MF module version with pre- assembled microswitches

ł Remove housing cover.ł The MF module can be mounted on the ball

valve type 546 in the opened or closed ballposition.

6. Valve Design

The PA11 and PA21 pneumatic actuators can bemounted on ball valves type 546. By using the cor-rect coupling piece and selecting a suitable adap-ter plate, the actuators are connected to the multi-functional module with the provided clamps.Depending on the function of the actuator, FC,FO or DA, it is essential that the position of thevalve agrees with the position of the actuator.The individual components and how they are as-sembled with or without manual override areshown on page 64.

Page 11: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 11

ł Spigot is asymmetrical.

ł The spigot position must be identical with one ofthe two illustrations.

A Spigot position for closed ball valve.

B Spigot position for open ball valve.

ł Place the MF module on the ball valve.

ł Make sure the contours match!

Note the square (a) and round (b) contours as wellas the position of the asymmetrical recesses (c) ofthe stem.

ł Tighten the 4 pre-assembled screws (Torx). TheMF module is now firmly connected with the ballvalve.

ł Insert the coupling and the coupling piece in themultifunctional module.

ł Fasten the actuator with the adapter plate to themultifunctional housing using the providedclamps.

Page 12: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡12

Mounting with manual override

First screw the parts for the manual override ontothe actuator (note the position of the cams).ł Coupling lever with intermediate piece on topł Control leverł Intermediate piece belowł Proceed according to the instructions for mount-

ing without manual override

Actuator type PA¢1/2¢

Coupling lever withintermediate piece on top

Control lever

Intermediate piecebelow

Adapter plate withclamps

Coupling piece

Multifunctional module

Ball valve type 546

With manual override Without manual override

Page 13: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 13

7. Overview of System Components

Ball Valve Type 230

1 Actuator PA11/PA212 Adapter plate DN¢0–50 with

coupling3 Multifunnctional module DN¢0–504 Ball valve type 546 DN¢0–50

1PA11

2

3

DN 10/15

4

DN 20

4

DN 25

4

DN 32

4

DN 40

4

DN 50

4

2

3

2

3

2

3

1PA21

F04 F05 (ISO 5211)

Page 14: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡14

8. Wiring Diagrams

AttentionPlease observe the following:For the correct functioning of the actuator, the posi-tion of the actuator must agree with the position ofthe valve.Actuator open > Valve openActuator closed > Valve closed

When installing an actuator with a Georg Fischerball valve, it is important to note the position of theball valve spigot.

Fail-safe to close(FC)

1 solenoid valve3/2 wayde-energized closed

Fail-safe to open(FO)

1 solenoid valve3/2 wayde-energized closed

Double acting(DA)

1 solenoid valve5/2 way(alternative 4/2 way)

5/2 way valve 4/2 way valve

Page 15: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 15

9. Technical Data of theActuator

Actuator

Control medium Neutral, non-aggressive gases(Control with fluids on request)

Temperature control medium max. 40 °C

Control pressures (reference values)

-15

-10

-5

0

5

10

15

20

25

30

0 1 2 3 4 5 6 7

PA11 DA PA11 FC/FO 0°M

PA11 FC/FO 30°M

PA11 FC/FO 60°M

PA11 FC/FO 90°M

M

PA ¢1 Torque characteristics

Torque at the actuator spindle

for different pressures and positions

Torq

ue [

Nm

]

Control pressure [bar]

Airtorque

Torquebalance

Springtorque

-30

-20

-10

0

10

20

30

40

50

60

0 1 2 3 4 5 6 7

PA21 DA

PA21 FC/FO 0°M

PA21 FC/FO 30°M

PA21 FC/FO 60°M

PA21 FC/FO 90°M

PA21 Torque characteristics

Torque at the actuator spindle

for different pressures and positions

Torq

ue [

Nm

]

Control pressure [bar]

Airtorque

Torquebalance

Springtorque

Control connection Rp1/8“

Control time ¢–2 s, with throttle valve to 5 s

Actuating angle 90° R

Mode of operation – Fail-safe close (FC)– Fail-safe open (FO)– Double acting (DA)

Allowable –10° to +50°Cambient temperature

Allowable humidity 0–¢00%

Max. allowable 7 barcontrol pressure

Position indicator optical

Housing material PP fiberglass-reinforced

Control volume DN Single Doublein dm3 acting acting

(FC/FO) (DA)mm dm3 dm3

10 1) 2)15

PA ¢1 20 0.15 0.18 0.1525

32PA 2¢ 40 0.28 0.35 0.28

50

¢) open2) closed

Page 16: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡16

1

4

3

2

5

3a

open

close

Exploded drawing

1 Housing2 Housing cover3 Indexing disk

with switching cams 3a4 Screws5 Connector plug 3P + E per DIN EN

¢75301-803*(formerly DIN 43650)

The MF module can be mounted on the ball valvetype 546 in the opened or closed ball position.

Spigot is asymmetrical

The spigot position must be identical to one ofthe two illustrations.

10. Installation of theMultifunctional Module withBuilt-in Limit Switch

Prior to installation, inspect the MF module fortransport damages. We recommend leaving theMF module in its original packaging until you areready to install it.The MF module has been fitted with the respectiveswitches and function-tested ex works! It is not ne-cessary to remove the cover.

Design of the MF- module with built-in switch

Page 17: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 17

A Spigot position for closed ball valve.

B Spigot position for open ball valve.

ł Place the MF module on the ball valve.

ł Make sure the contours match!

Note the square (a) and round (b) contours as wellas the position of the asymmetrical recesses (c) ofthe stem.

ł Tighten the 4 pre-assembled screws (Torx). TheMF module is now firmly connected with the ballvalve.

Put the cams (3a) in the respective positions.

For open ball valve.

For closed ball valve.

The MF module is now ready for actuatormounting: see (6).

Page 18: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡18

11. Technical Features of theMultifunctional Module

This module is for electric signalling of the valvepositions of the Georg Fischer ball valves type 546.The multifunctional module can be screwed directlyonto the ball valve.

CE marking

According to the EC Directive 98/37/EC (formerly89/392/EEC) pertaining to machines, these actua-tors/valves are not considered machines, but canbe built into installations which are considered assuch.

We expressly point out that operation isprohibited until conformity of the machine (sys-tem) into which this product has been installedwith the EC Directive 98/37/EC concerning ma-chines has been established.

Design of the multifunctional moduleincluding feedback unit

1 Housing2 Cover3 Indexing disk4 Switch holder5 Microswitch «OPEN»6 Microswitch «CLOSE»7 Connector plug 3P + E

per DIN EN ¢7530¢-803(formerly DIN 43650)

8 Seal

Page 19: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 19

Switch type Capacity Code no.

Microswitch 250 V W 167 482 626 DN 10–¢5Ag, Ni 6 A *) 167 482 627 DN 20–25

167 482 628 DN 32–40167 482 629 DN 50

Microswitch 4 – 30 V= 167 482 635 DN 10–¢5with gold contact 1 – ¢00 mA 167 482 636 DN 20–25Au 167 482 637 DN 32–40

167 482 638 DN 50

* ohm resistive load.For inductive load, provide for protective circuitry!

Configuration of the multifunctional module includingelectric feedback unit

Dimension Dimension Dimension DimensionDN ¢5 DN 20 and DN 25 DN 32 and DN 40 DN 50

General technical dataof the multifunctional module

Protection rating with DIN plug: IP 65Protection rating with cable gland: IP 67Ambient temperature: –¢0 °C to +50°C

A closedB openC blackD blue (short cable)E blue (long cable)

Circuit diagram

Page 20: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡20

Switch type Capacity Code no.

Inductive switch 5 – 3 V 167 482 653 DN 10–¢5NPN 0.1 A 167 482 654 DN 20–25

167 482 655 DN 32–40167 482 656 DN 50

Inductive switch 5 – 30 V= 167 482 662 DN 10–¢5PNP 0.1 A 167 482 663 DN 20–25

167 482 664 DN 32–40167 482 665 DN 50

A closedC blueD blackE blackF brownb open

Circuit diagram

Switch type Capacity Code no.

Inductive switch 8 V = 167 482 671 DN 10–¢5Namur 167 482 672 DN 20–25(intrinsically safe) 167 482 673 DN 32–40Approvals: 167 482 674 DN 50ATEX 2023x, CSAEMV per EN60947-5-2norm conformityEN 60947-5-6

A closedB openC blueD brown

Circuit diagram

General technical data of themultifunctional module

Protection rating with DIN plug: IP 65Protection rating with cable gland: IP 67Ambient temperature: –¢0 °C to + 50°C

Page 21: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 21

12. Fastening Plate

With the fastening plate for the ball valve type546, forces are absorbed which could occur duringvalve operation (e.g. initial breakaway torque). Inimplementing the fastening plate, working forcesare not transmitted to the piping system.

In piping systems which are subject to temperaturefluctuations, longitudinal or bending forces occur ifthermal expansion is hindered. So as not to impairvalve functioning, these forces must be absorbedby the appropriate fixed points in front of or behindthe valve.

The fastening plate is available in two sizes for thedimension range DN 10 to DN 50. Two screws tofasten on the ball valve are included in the scopeof delivery.

Warning

Measurement d 16–32 mm d 40–63 mm

DN 15–25 DN 32–50

L 106 149

B 48 54

H 20 20

L1 92 134

L2 62 104

L3 31 52

L4 41 62

L5 25 45

H1 14 14

H2 24 24

D 6.5 8.5

Fasteningscrews M6x14 M8x18

Page 22: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡22

13. AccessoriesPilot solenoid valve type PV 93

Mode of operation:fail safe to close

Version 200/230 V, 50/60 Hz 199 190 263for direct mounting 100/115 V, 50/60 Hz 199 190 264(incl. base plate 24 V= 199 190 265and screw) 24 V, 50/60 Hz 199 190 266For AS interface 24 V=, 2 Watt 199 190 478

3.5–6 bar

Version for 200/230 V, 50/60 Hz 199 190 267mounting on battery 100/115 V, 50/60 Hz 199 190 268mounting plate. 24 V= 199 190 269Coil with connector 24 V, 50/60 Hz 199 190 270flange

Battery 4x 199 190 271mounting plate 6x 199 190 272

8x 199 190 273Blank cover plate with 199 190 2741 O-ring and2 screws

For further technical information, see separate PV 93 datasheet

Accessory for type 5470 and typeMNL532NAMUR connector board for PA¢1/PA2¢

¢99 ¢90 378

Page 23: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 23

Pilot solenoid valve type MNL5323/2–5/2 way pilot solenoid valve

for pneumatic actuatorsVersion: with NAMUR connector and 2 air flowthrottles

Mode of operation:3/2 way valve when de-energized, pressure con-nection 1 closed, outlet 3 vented.5/2 way valve when de-energized, pressure con-nection 1 connected with outlet 4, outlet 3 vented.Material of body: anodized aluminumElectrical connection: coupler socket

Voltage DN NBRCode

230 V, AC 5 199 190 360110 V, AC 5 199 190 35948 V, AC 5 199 190 36124 V, AC 5 199 190 35824 V, DC 5 199 190 357

Pilot solenoid valve type 54704/2 way pilot solenoid valve

for pneumatic actuators DA (double acting)Version: with NAMUR connector

Mode of operation G:4/2 way valve, when de-energized, pressure con-nection 1 connected with outlet 2, outlet 4 vented.Material of the body: polyamideElectrical connection: coupler socket

for AC voltage 50/60 Hz and DC voltage

Voltage DN NBRCode

230 V, AC/DC 4 199 190 302110 V, AC/DC 4 199 190 30324 V, AC/DC 4 199 190 304

Page 24: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡24

Pilot solenoid valve type PV 2000

2 x 3/2 and 5/2 way valvesfor battery mountingElectrical control via multiple plug or bus module

Type overview

Description Code

Connector module with 199 190 424D-Sub plugEnd module 199 190 4265/2 way valve 199 190 4232 x 3/2 way valve 199 190 422

D-Sub plug,25-pin,with cableConnecting cable25 x 0.34 mm2, PVC,color coded perDIN 47¢00Protection ratingIP 40

For further technical information, see separatedatasheet

Cable length Code

1 .5 m 199 190 432

3 m 199 190 433

5 m 199 190 434

Digital electro-pneumatic positioner typeDSR 20¢

for actuator PA¢1/PA2¢in the fail safe to close (FC) or fail safe to open (FO)mode

Description Code

1 Positioner DSR 20¢ 199 190 4122 Namur console 199 190 281

For further technical information, see separate data-sheet

Page 25: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡ 25

Options

Stroke limiterThe stroke limiter is mounted ex works and enableslimiting the actuating angle up to 45° alternativelyin the closed or open direction for the FC and FOfunctions. For the DA function, limitation is onlypossible in the open direction.

Covering cap

Adjustmentscrew

Safety nut

Page 26: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

¥ ‡26

14. Parts/Subassemblies

Description Code

Actuator PA ¢1, DN 10–25 FC 198 150 127DN 10–25 FO 198 150 128DN 10–25 DA 198 150 129

Actuator PA2¢, DN 32–50 FC 198 150 130FO 198 150 131DA 198 150 132

Actuator PA ¢1, DN 32–50 FC 198 150 144with stroke limiter FO 198 150 145

DA 198 150 146

Actuator PA2¢, DN 32–50 FC 198 150 147with stroke limiter FO 198 150 148

DA 198 150 149

Emergency manual override DN ¢0–25 198 000 500Emergency manual override DN 32–50 198 000 501

Multifunctional module without limit switches (empty)

Dimensions Code

DN 10/15 167 482 680DN 20/25 167 482 681DN 32/40 167 482 682DN 50 167 482 683

Adapter plate incl. coupling

Dimensions Code

DN 10/15 198 150 556DN 20/25 198 150 557DN 32/40 198 150 558DN 50 198 150 559

Ball valve type 546 see separate datasheet

Page 27: Instruction Manual ¥ ‡ ł control these valves to the OPEN and CLOSED positions via a built-in solenoid valve. The sole-noid valve must be either supplied ex ‡ works or already

Fi 5703/4 (6.03) ¢98 ¢5¢ ¢¢5 © Georg Fischer Rohrleitungssysteme AG, CH-820Ý Schaffhausen/Schweiz, 2003 Printed in Switzerland

¥ ‡Piping Systems

A Georg Fischer Rohrleitungssysteme GmbH, Sandgasse 16, 3130 HerzogenburgTel. +43(0)2782/856 43-0, Fax +43(0)2782/856 64, e-mail: [email protected]

AUS George Fischer Pty Ltd, 186–190 Kingsgrove Road, Kingsgrove NSW 2008, Tel. +61(0)2/95 54 39 77, Fax +61(0)2/95 02 25 61B/L Georg Fischer NV/SA, Digue du Canal 109-¢¢¢ — Vaartdijk 109-¢¢¢, 1070 Bruxelles/Brüssel

Tél. +32(0)2/556 40 20, Fax +32(0)2/524 34 26, e-mail: [email protected] George Fischer Ltda, Av. das Nações Unidas 21689, 04795-100 São Paulo, Brasil,

Tel. +55(0)11/5687 1311, Fax +55(0)11/5687 6009CH Georg Fischer Rohrleitungssysteme (Schweiz) AG, Amsler-Laffon-Strasse ¢, Postfach, 8201 Schaffhausen

Tel. +41(0)52 631 30 26, Fax +41(0)52 631 28 97, e-mail: [email protected] Georg Fischer Piping Systems Ltd Shanghai, No. 2Ý8 Kang Qiao Dong Rd., Shanghai 201319

Tel. +86(0)2¢/58 13 33 33, Fax +86(0)2¢/58 13 33 66, e-mail: [email protected] Fischer Piping Systems (Trading) Ltd Shanghai, No 516 Fute Bei Road, Waigaoqiao Free Trade Zone, 200131 PudongShanghai, Tel. +86(0)21/5868 0278, Fax +86(0)21/5868 0264, e-mail: [email protected]

D Georg Fischer GmbH, Daimlerstraße 6, 73095 Albershausen, Tel. +49(0)7161/302-0, Fax +49(0)7161/302 111e-mail: [email protected], Internet: http://www.rls.georgfischer.deGeorg Fischer DEKA GmbH, Kreuzstrasse 22, 35232 Dautphetal-MornshausenTel. +49(0)6468/915-0, Fax +49(0)6468/915 221/222, e-mail: [email protected], Internet: http://www.dekapipe.de

DK/IS Georg Fischer A/S, Rugvænget 30, 2630 Taastrup, Tel. +45 70 22 19 75, Fax +45 70 22 19 76e-mail: [email protected], Internet: http://www.georgfischer.dk

E Georg Fischer S.A., Alcalá, 85, 2a, 28009 Madrid, Tel. +34(0)9¢/781 98 90, Fax +34(0)9¢/426 08 23,e-mail: [email protected]

F George Fischer S.A., 105–1¢3, rue Charles Michels, 93208 Saint-Denis Cedex 1Tél. +33(0)1/49 22 ¢3 4¢, Fax +33(0)¢/49 22 ¢3 00, e-mail: [email protected]

GB George Fischer Sales Limited, Paradise Way, Coventry, CV2 2ST, Tel. +44(0)2476/535 535, Fax +44(0)2476/530 450e-mail: [email protected], Internet: http://www.georgefischer.co.uk

GR Georg Fischer S.p.A., Athens Branch, 101, 3rd September Str., 10434 AthenTel. +30(0)1/882 0491, Fax +30(0)1/881 0291, e-mail: [email protected]

I Georg Fischer S.p.A., Via Sondrio 1, 20063 Cernusco S/N (MI), Tel. +3902/921 861, Fax +3902/921 407 85-6e-mail: [email protected]

ID George Fischer Representative Office, c/o Wisma Aria, 3rd Floor, Jl. H.O.S. Cokroaminoto 81, Jakarta 10310, IndonesiaTel. +62(0)21/391 48 62, Fax +62(0)21/391 48 63

IND George Fischer Piping Systems Ltd, India Branch Office, Solitaire Corporate Park, 532, Building No. 5, 3rd Floor, ChakalaGhatkopar Link Road, Andheri (E), 400 093 Mumbai, Tel. +91(0)22/820 2362, Fax +91(0)22/820 2462,e-mail: [email protected]

J Georg Fischer Ltd, 13–8, Nanbanaka 1-chome, Naniwa-ku, 556-0011 OsakaTel. +81(0)6/6635 2691, Fax +81(0)6/6635 2696, e-mail: [email protected]

N Georg Fischer AS, Rudsletta 97, ¢35¢ Rud, Tel. +47(0)67 18 29 00, Fax +47(0)67 13 92 92, Internet: http://www.georgfischer.noNL Georg Fischer N.V., Postbus 35-8160, 8161 PA Epe, Tel. +31(0)578/678222, Fax +31(0)578/621768

e-mail: [email protected], Internet: http://www.georgfischer.nlPL Georg Fischer Sp. z o.o., ul. Radiowa 1A, 01-485 Warszawa, Tel. +48(0)22/638 91 39, Fax +48(0)22/638 00 94RO Georg Fischer Rohrleitungssysteme AG, Rep. Office Romania, 11 Barbu Delavrancea, 70000 Bucharest - Sector 1

Tel. +40(0)1/222 91 36, Fax +40(0)1/222 91 77, e-mail: [email protected] Georg Fischer Piping Systems Ltd, Moscow Representative Office, Sheremetievskaya ul., 47, 127521 Moscow

Tel. +7 095/219 9604, Fax +7 095/232 3625, e-mail: [email protected]/FIN Georg Fischer AB, Box 113, 12523 Älvsjö-Stockholm, Tel. +46(0)8/506 77 500, Fax +46(0)8/749 23 70

e-mail: [email protected], Internet: http://www.georgfischer.seSGP George Fischer Pte Ltd, ¢5 Kaki Bukit Road 2, KB Warehouse Complex, 4¢7 845 Singapore

Tel. +65(0)67 47 06 ¢¢, Fax +65(0)67 47 05 77, e-mail: [email protected] George Fischer Inc., 2882 Dow Avenue, Tustin, CA 92780-7258 Tel. +1(714) 731 88 00, Toll Free 800/854 40 90

Fax +1(714) 73¢ 62 01, e-mail: [email protected], Internet: http://www.us.piping.georgefischer.comExport Georg Fischer Rohrleitungssysteme AG, Ebnatstrasse ¢¢¢, Postfach, CH-820¢ Schaffhausen, Tel. +41(0)52 63¢ ¢¢ ¢¢

Fax +41(0)52 63¢ 28 93/631 28 58, e-mail: [email protected], Internet: http://www.piping.georgfischer.com