Page 1: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

www.commscope.com

SYSTIMAX® InstaPATCH® 360 Traffic Access Point (TAP) Solution

Design Guide

Page 2: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

2

Contents

Introduction 3

How Does a TAP Work? 3

The TAP Ecosystem 4

InstaPATCH 360 TAP Module Family 4

InstaPATCH 360 TAP Fan-out Array Cords 5

InstaPATCH 360 TAP Pre-terminated Fiber Cables 5

Traffic Monitoring System 5

Fiber Cabling System Design with TAPs 6

Example 1—10Gbps Ethernet 6

Example 2—8Gbps Fibre Channel 8

Optical Channel Loss Evaluation with TAPs 10

Loss Evaluation of Main Traffic Channels 10

Loss Evaluation of Shorter Monitor Channels 11

Loss Evaluation of Longer Monitor Channels 12

TAP Installation 12

Ordering Information 13

References 15

Page 3: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

3

IntroductionThe need for real-time network traffic monitoring in today’s intelligent data center has become compelling. Data center network administrators need to gain better visibility of their networks, optimize the performance of mission-critical applications and, more importantly, secure their networks.

In fiber-optic networks, a traffic access point (TAP) can be integrated into the fiber cabling infrastructure, enabling network traffic monitoring from physical layer (layer 1) and above in real-time fashion with zero packet loss. Because TAPs continuously pass all traffic running between the endpoint network devices with zero latency—while duplicating that exact same traffic to the monitor ports simultaneously—TAPs are one of the most efficient ways to monitor traffic and network link quality in data center and telecom carrier networks.

This design guide will help you understand and design fiber cabling systems using CommScope SYSTIMAX® InstaPATCH® 360 TAP solutions to support applications and enable real-time network traffic monitoring at the same time.

How Does a TAP Work?TAP modules provide an important feature for data center monitoring and management. A TAP module is a compact package of fiber-optic couplers or splitters that can be used to passively divert a fixed percentage of light energy away from main transportation channels as a way to monitor the traffic status or content in real time without disrupting the main channel traffic. The optical couplers or splitters inside a TAP module are the key components that split the light energy from the input port into two output ports according to designed split ratio.

Figure 1 shows example signal paths of 12-fiber multimode fiber (MMF) TAP Modules. On the right side of the diagram the rear surface of the TAP modules provide one Multiple-Fiber Push-On/Pull-off (MPO) connector serving the main traffic channels for connecting to a trunk cable, and another MPO connector (red) serving the monitoring channels for connecting to monitoring equipment via MPO-LC array cords. On the left side of the diagram the front surface of the modules provide 12 LC receptacles for patching.

Couplers are unidirectional components and are arranged in an alternating sequence for duplex transceiver connectivity at the LC connectors. As shown in the upper part of Figure 1, Channel 1 of the LC connectors receives traffic from Channel 1 of the MAIN MPO port after a portion of its optical signal is split into Channel 1 of the TAP MPO connector. Other odd-numbered LC connectors follow the same signal flow. The lower part of Figure 1 shows Channel 2 of the LC connectors, which serves only for signal input, and its signal is split between Channel 2 of the MAIN MPO and the TAP MPO connectors. Other even-numbered LC connectors follow the same signal flow.

Page 4: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

4

Figure 1. Fiber TAP signal path illustrations

TAP modules, therefore, must be tested or deployed with channel directionality in mind. The transmitter (or the meter source) must always be connected to the input of the coupler. Also, the receiver (or the meter detector) must always be connected to the outputs of the optical coupler. Connecting in an opposite direction will not affect the main traffic, but will result in a lack of output from the monitoring channels.

The TAP EcosystemThe TAP ecosystem mainly consists of the InstaPATCH 360 pre-terminated fiber cables, InstaPATCH 360 TAP modules, InstaPATCH 360 TAP Fan-out Array Cords, and the monitoring equipment. The TAP modules, combined with the array cords, provide flexible choices to network designers for various network configurations. The monitoring equipment is designed to detect and analyze traffic collected from the TAP.

InstaPATCH 360 TAP Module Family

The optical TAP is a completely passive device integrated in the optical network physical layer and is invisible to potential intruders. Due to different network application environments, the TAP family has a variety of different formats, such as number of fibers, fiber type, and split ratio. Figure 2 shows some examples of the CommScope TAP family, including combinations of 12-fiber or 24-fiber, MMF or Single-mode fiber (SMF), and 70/30 or 50/50 split ratio.

Figure 2. Front and rear views of InstaPATCH 360TM TAP modules

(a) SMF 12-fiber,

Front view

(b) SMF 12-fiber,

Rear view

(d) MMF 24-fiber,

Rear view

(c) MMF 24-fiber,

Front view

Page 5: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

5

The MMF TAPs are designed to operate at 850nm wavelength. The MMF TAP can be deployed with bend-insensitive or traditional OM3 or OM4 fiber cabling. The single-mode fiber TAPs are optimized for operation at 1310nm wavelength.

The designed split ratios of the TAP modules are selected for compatibility with the supported applications. The available split ratios are 70/30 and 50/50. The first number of each split ratio indicates the percent of the input power split off to the main channel output. The second number indicates the percent of the input power split off to the monitor output. The optical power budgets of some applications, such as those for Ethernet on MMF, are sufficiently robust to support transmission through the higher loss of a 50% split or a 70% split, while others, such as many of those for Fibre Channel on MMF, are not as robust and must rely on the stronger signals from a 70% split. Refer to SYSTIMAX 360 Traffic Access Point (TAP) Solutions Performance Specification Volume 5 for channel topology design limits for all supported applications.1

The InstaPATCH 360TM modules insert into the panel openings of InstaPATCH 360 shelves and panels and can be placed side by side with InstaPATCH 360DM modules. This permits flexibility in patch panel placement in new or retrofit situations. InstaPATCH 360TMs follow the alpha/beta orientation conventions of Method B array polarity just like 360DMs.

InstaPATCH 360 TAP Fan-out Array Cords

In addition to the TAP modules, the InstaPATCH 360 TAP solution includes a family of MPO-LC Fan-out Array Cords that provide great flexibility for network designers. The InstaPATCH 360 TAP Fan-out Array Cords are designed to be connected to the TAP port(s) of InstaPATCH 360 TAP modules, and pass network traffic to a third-party network monitoring system. The InstaPATCH 360 TAP Fan-out Array Cords are configured as unpinned MPO to 12 simplex LC array cord assemblies. They are available in Plenum or LSZH materials, and LazrSPEED 550 fiber (OM4) or TeraSPEED fiber (single-mode).

InstaPATCH 360 Pre-terminated Fiber Cables

InstaPATCH 360 cables terminated with unpinned MPO plugs attach to InstaPATCH 360TM modules. They are available in Plenum or LSZH sheath materials. LazrSPEED 300 (OM3) and LazrSPEED 550 (OM4) cables are used with multimode 360TM modules, and TeraSPEED (OS2) cables are used with single-mode 360TM modules.

Traffic Monitoring System

Another major part of the monitoring system is the monitoring and analysis equipment, including receivers, analysis hardware and software, as shown in Figure 3. The monitoring system receives the signal from the TAP and analyzes the traffic. Commercially available monitoring systems include those from Virtual Instruments®, GigaMON® and others.

Page 6: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

6

Figure 3. A typical TAP-based monitoring system

Fiber Cabling System Design with TAPsWhile industry standards for Ethernet and Fibre Channel are not expressly designed to support the added loss of TAPs, it is possible with careful engineering and high performance cabling systems to deploy TAPs in networks and retain useful channel topologies.3–5 When approaching the design of a TAP solution for a particular application, many factors need to be taken into consideration. These include the loss of the TAP splitter, length and number of connections within the main and two monitor channels, the intended application (e.g. 8G Fibre Channel or 10G Ethernet), and the monitor equipment capability. Fortunately the SYSTIMAX InstaPATCH 360 Fiber TAP Solution Performance Specification provides channel topology limits that account for many of these factors to simplify the design process. The following two sections provide practical design examples using this Performance Specification for a 50/50 MMF TAP solution and a 70/30 MMF TAP solution.

Example 1—10Gbps Ethernet

Figure 4 shows an example of a 10Gbps Ethernet network retrofitted with an optical TAP. In this case, an InstaPATCH 360 standard module (360DM module) located at the cross-connect point—which is the middle point of the channel—is replaced with an InstaPATCH 360 TAP module (360TM module).

Page 7: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

7

Figure 4. Retrofit example: 10GE channel with 50/50 TAP module replacing MPO/LC module at central cross connect

A quick check of the Performance Specification reveals that the 10GBASE-S power budget supports both 50/50 and 70/30 split ratios for the main channel. The ability to support a 50/50 split ratio also permits the monitor equipment to use minimally standards-compliant transceivers, and therefore the monitor channels may also be designed using the same topology limit tables as the main channel. This choice offers a straight forward design that requires no design consultation with the monitor equipment company. In comparison, the selection of the 70/30 split ratio, while improving the signal strength of the main channels, requires better than minimally compliant transceivers in the monitor gear and therefore necessarily involves consultation with the monitor gear company for design limits. Here we will illustrate the design approach using a 50/50 split ratio TAP module.

Looking at Figure 4, determine the main channel length by adding up the cord and cable lengths that form the main channel from left to right:

10m+80m+5m+80m+10m=185m

The length of the monitor channel from the left side is:

10m+80m+5m=95m

The length of the monitor channel from the right side is:

10m+80m+5m+5m=100m

In this network configuration, the main traffic channel has four MPO connections and four LC connections (the connections to the active equipment are not counted), and the channel length is 185m. The longer monitoring channel, which is the right side in this case, has three MPO connections and three LC connections, and the channel length is 100m. The shorter monitor channel, which is on the left side in this case, has three MPO connections and one

Page 8: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

8

LC connection, and the channel length is 95m. Of these three channels, the main channel is the most demanding having both the longest length and the highest number of connections. Table 1 is an extract from the SYSTIMAX InstaPATCH 360 Fiber Tap Solutions Performance Specifications —Volume Five for 10GBASE-S on LazrSPEED 550 and the 50/50 split ratio TAP. The cell at the intersection of 4 MPOs and 4 LCs indicates a supportable distance of 240 m, which greater than the length of the main channel, so the design is supportable with LazrSPEED 550 cabling. Checking the LazrSPEED 300 capability in Table 2 we see that it supports 130m with four MPO connections and four LC connections, so LazrSPEED 300 is not an option for this channel topology.

LazrSPEED 550, 50/50 split ratio

# LC Connections* with:

1 MPO 2 MPOs 3 MPOs 4 MPOs 5 MPOs 6 MPOs

1 970 (295) 940 (285) 900 (275) 870 (265) 840 (255) 790 (240)

2 950 (290) 920 (280) 870 (265) 840 (255) 800 (245) 770 (235)

3 920 (280) 890 (270) 850 (260) 820 (250) 770 (235) 740 (225)

4 900 (275) 870 (265) 820 (250) 790 (240) 750 (230) 710 (215)

5 870 (265) 840 (255) 800 (245) 750 (230) 720 (220) 670 (205)

6 850 (260) 800 (245) 770 (235) 720 (220) 690 (210) 640 (195)

Table 1. Channel topology limits for 10GBASE-S on LazrSPEED 550 for a 50% TAP channel

LazrSPEED 300, 50/50 split ratio

# LC Connections* with:

1 MPO 2 MPOs 3 MPOs 4 MPOs 5 MPOs 6 MPOs

1 660 (200) 590 (180) 560 (170) 520 (160) 460 (140) 430 (130)

2 620 (190) 560 (170) 520 (160) 490 (150) 430 (130) 390 (120)

3 590 (180) 520 (160) 490 (150) 460 (140) 390 (120) 330 (100)

4 560 (170) 520 (160) 460 (140) 430 (130) 360 (110) 300 (90)

5 520 (160) 490 (150) 430 (130) 360 (110) 330 (100) 260 (80)

6 490 (150) 430 (130) 390 (120) 330 (100) 260 (80) 200 (60)

Table 2. Channel topology limits for 10GBASE-S on LazrSPEED 300 for a 50% TAP channel

Example 2—8Gbps Fibre Channel

Figure 5 shows an example of an 8G Fibre Channel (8GFC) link designed with an optical TAP. The TAP is inserted into the fiber patch panel on the right side near the FC Storage Area Network (SAN) switch.

Page 9: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

9

Figure 5. Example 8GFC channel with TAP placed near SAN switch.

A quick check of the Performance Specification reveals that the minimally standards-compliant 8GFC power budget for MMF supports only the 70% output of a 70/30 TAP module for the main channels. The 30% output for the monitor channels requires better than minimally standards-compliant transceivers in the monitor gear and therefore necessarily involves consultation with the monitor gear company for design limits for the monitor channels. The intended MMF bandwidth grade (i.e. LazrSPEED 550 (OM4), LazrSPEED 300 (OM3)), the monitor channel lengths and maximum channel losses will be required by the monitor company to perform the analysis. Section 5 provides guidance on how to determine the maximum channel loss using the SYSTIMAX Solutions Link Loss Calculator2.

Looking at Figure 5, determine the main channel length by adding up the cord and cable lengths that form the main channel from left to right:

10m+90m+10m=110m

The length of the monitor channel from the storage array side is:

10m+90m+10m=110m

The length of the monitor channel from the SAN switch side is:

10m+10m=20m

In this network configuration, the main traffic channel has two MPO connections and two LC connections (the connections to the active equipment are not counted), and the channel length is 110m. Table 3 is an extract from the SYSTIMAX InstaPATCH 360 Fiber Tap Solutions Performance Specifications—Volume Five for 8GFC on LazrSPEED 550 and the 70/30 split ratio TAP. The cell at the intersection of 2 MPOs and 2 LCs indicates a supportable distance of 115 m, which is greater than the 110 m length of the main channels, so the design is supportable with LazrSPEED 550 cabling for the main channels.

Page 10: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

10

The longer monitor channel has three low-loss MPO connections, one low-loss LC connection, and the length is 110m. The shorter monitor channel has one low-loss MPO connection, one low-loss LC connection, and the length is 20m. Follow the procedure of Section 5 to provide the monitor company the information they need to evaluate your channel design for compatibility with their equipment.

LazrSPEED 550, 70/30 split ratio, MAIN (70%) output

# LC Connections* with:

1 MPO 2 MPOs 3 MPOs 4 MPOs 5 MPOs 6 MPOs

1 480 (145) 430 (130) 360 (110) 280 (85) 200 (60) 100 (30)

2 440 (135) 380 (115) 310 (95) 230 (70) 130 (40) 0 (0)

3 390 (120) 330 (100) 250 (75) 150 (45) 30 (10) 0 (0)

4 340 (105) 280 (85) 180 (55) 70 (20) 0 (0) 0 (0)

5 300 (90) 210 (65) 100 (30) 0 (0) 0 (0) 0 (0)

6 250 (75) 130 (40) 0 (0) 0 (0) 0 (0) 0 (0)

Table 3. Channel topology limits for 8GFC on LazrSPEED 550 for 70% TAP channel

Optical Channel Loss Evaluation with TAPsThe following subsections are presented in three parts, each of which examines one of the three different channels topologies created when deploying TAPs—one main channel topology and two monitor channel topologies. Channel loss evaluation of the two monitor channels is necessary when designing channels with 70/30 TAP modules. Channel loss evaluation provides the monitor equipment company information to evaluate the proposed channel for interoperability with their equipment. This is because the high loss of a 30% split requires better than minimally complaint receivers which are proprietary to the monitor company.

While the main channel loss is independent of the placement of the TAP module within the channel, the monitor channel loss depends on the placement of the TAP module. This is because there are two different channel topologies from monitor to each end of the channel. These two monitor channel topologies are usually of different lengths. Consequently in the following evaluation we refer to these two channel topologies as “shorter monitor channels” and “longer monitor channels”.

Loss Evaluation of Main Traffic Channels

Figure 6 shows the main traffic channels of an optical link with a 70/30 TAP inserted. The pink arrow shows one direction signal flow, but traffic in the other direction sees the same loss. All cabling is LazrSPEED 550 (OM4). The trunk cable is 80m long, the LC/LC equipment cords are 10m each. Using SYSTIMAX Solutions Link Loss Calculator Version 7.1 plug in the following factors: a 70 percent TAP with two low-loss MPO connections, two low-loss LC connections, and 100m of “LazrSPEED® with InstaPATCH @ 850nm” fiber cable. Using those inputs, the maximum loss of the main channels is calculated as 2.88dB.

Page 11: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

11

Figure 6. Illustration of the main traffic channel signal paths

Loss Evaluation of Shorter Monitor Channels

Figure 7 shows the monitor channel signal path from the end closest to the monitor. The LC/LC equipment cord is 10m long, and the fan-out array cord connected to the monitoring port is also 10m long. Using SYSTIMAX Solutions Link Loss Calculator, Version 7.1 plug in the following factors: select the 30 percent TAP, one low-loss MPO connection, one low-loss LC connection, and 20m “LazrSPEED® with InstaPATCH @ 850nm” fiber cable. Using those inputs the maximum loss of the even-numbered monitor channels is calculated as 7.13dB.

Figure 7. Illustration of the monitor channel signal paths for signals from the near end of the channel

Page 12: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

12

Loss Evaluation of Longer Monitor Channels

Figure 8 shows the monitor channel signal path from the end farthest from the monitor. The trunk cable is 80m long. Both LC/LC equipment cord and fan-out array cord are 10m long. Using SYSTIMAX Solutions Link Loss Calculator, Version 7.1 plug in the following factors: select a 30 percent TAP, three low-loss MPO connections, one low-loss LC connection, and 100m “LazrSPEED® with InstaPATCH @ 850nm” fiber cable. Using those inputs the maximum loss of the odd-numbered monitor channels is calculated as 7.73dB.

Figure 8. Illustration of the monitor channel signal paths for signals from the far end of the channel

Provide the calculated maximum losses, monitor channel lengths, and fiber type including bandwidth grade of MMF (i.e. OM3 or OM4) to the monitor gear company for channel evaluations when using 70/30 TAP modules.

TAP InstallationPlease refer to the Instruction Sheet for InstaPATCH 360 TAP modules for detailed installation information in eCatalog.

InstaPATCH 360 TAP solution should be utilized in conjunction with the InstaPATCH 360 pre-terminated fiber solutions. Due to the insertion losses of field-installable MPOs, it’s not recommended to use InstaPATCH 360 TAP solution with fiber trunks terminated with field installable MPOs.

Page 13: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

13

Ordering InformationInstaPATCH 360 TAP solution can be ordered by contacting CommScope Sales. Please visit the CommScope eCatalog at the following link. http://www.commscope.com/Product-Catalog/Enterprise/Product/Fiber/

MATERIAL ID PRODUCT CODE DESCRIPTION

760188284 360TM-12LC-LS-70:30 TAP module, 12F duplex LCs, OM4, 70/30 signal split (Main/TAP)

760188292 360TM-12LC-LS-50:50 TAP module, 12F duplex LCs, OM4, 50/50 signal split (Main/TAP)

760188300 360TM-12LC-SM-70:30 TAP module, 12F duplex LCs, OS2, 70/30 signal split (Main/TAP)

760188318 360TM-12LC-SM-50:50 TAP module, 12F duplex LCs, OS2, 50/50 signal split (Main/TAP)

760188607 360TM-24LC-LS-70:30 TAP module, 24F duplex LCs, OM4, 70/30 signal split (Main/TAP)

760188615 360TM-24LC-LS-50:50 TAP module, 24F duplex LCs, OM4, 50/50 signal split (Main/TAP)

760188623 360TM-24LC-SM-70:30 TAP module, 24F duplex LCs, OS2, 70/30 signal split (Main/TAP)

760188631 360TM-24LC-SM-50:50 TAP module, 24F duplex LCs, OS2, 50/50 signal split (Main/TAP)

Table 3. List of InstaPATCH 360 TAP modules

Page 14: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

14

MATERIAL ID PRODUCT CODE DESCRIPTION

760196501 360TM ARRAY, PLNM, LS, MP(f)-LC(s), M05

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OM4, plenum, 5m

760196519 360TM ARRAY, PLNM, LS, MP(f)-LC(s), M06

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OM4, plenum, 6m

760196527 360TM ARRAY, PLNM, LS, MP(f)-LC(s), M07

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OM4, plenum, 7m

760196642 360TM ARRAY, PLNM, LS, MP(f)-LC(s), M19

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OM4, plenum, 19m

760196659 360TM ARRAY, PLNM, LS, MP(f)-LC(s), M20

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OM4, plenum, 20m

760196303 360TM ARRAY, PLNM, SM, MP(f)-LC(s), M05

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OS2, plenum, 5m

760196311 360TM ARRAY, PLNM, SM, MP(f)-LC(s), M06

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OS2, plenum, 6m

760196329 360TM ARRAY, PLNM, SM, MP(f)-LC(s), M07

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OS2, plenum, 7m

760196444 360TM ARRAY, PLNM, SM, MP(f)-LC(s), M19

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OS2, plenum, 19m

760196451 360TM ARRAY, PLNM, SM, MP(f)-LC(s), M20

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OS2, plenum, 20m

760197327 360TM ARRAY, LSZH, LS, MP(f)-LC(s), M05

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OM4, LSZH, 5m

760197335 360TM ARRAY, LSZH, LS, MP(f)-LC(s), M06

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OM4, LSZH, 6m

760197343 360TM ARRAY, LSZH, LS, MP(f)-LC(s), M07

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OM4, LSZH, 7m

760197467 360TM ARRAY, LSZH, LS, MP(f)-LC(s), M19

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OM4, LSZH, 19m

760197475 360TM ARRAY, LSZH, LS, MP(f)-LC(s), M20

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OM4, LSZH, 20m

760198143 360TM ARRAY, LSZH, SM, MP(f)-LC(s), M05

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OS2, LSZH, 5m

760198150 360TM ARRAY, LSZH, SM, MP(f)-LC(s), M06

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OS2, LSZH, 6m

760198168 360TM ARRAY, LSZH, SM, MP(f)-LC(s), M07

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OS2, LSZH, 7m

760198283 360TM ARRAY, LSZH, SM, MP(f)-LC(s), M19

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OS2, LSZH, 19m

760198291 360TM ARRAY, LSZH, SM, MP(f)-LC(s), M20

TAP fan-out cables, MPO (unpinned), 12 simplex LCs, OS2, LSZH, 20m

Table 4. Partial list of InstaPATCH 360TM TAP Fan-out Array Cords with metric lengths

Note: The available lengths of the array cords (partially listed here) are from 1 to 20 meters, with an incremental length of 1 meter. Unlisted array cords are also available in lengths from 4 to 65 feet with an incremental length of 1 foot.

Page 15: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

15

References1. SYSTIMAX® InstaPATCH® 360 Traffic Access Point (TAP) Solutions Performance

Specifications, Vol.5, June 18, 2014.

2. SYSTIMAX Solutions—Link Loss Calculator, Version 7.1.

3. IEEE 802.3, “IEEE standards for Ethernet”, December 2012.

4. ANSI/INCITS 479-2011, “Information technology—Fibre Channel—Physical Interfaces— 5 (FC-PI-5)”, November 2011.

5. INCITS/TR-46-2011, “Information technology—Fibre Channel Methodologies for Signal Quality specification (FC-MSQS) (ANSI/INCITS Technical Report)”, 2011.

Page 16: InstaPATCH 360 Traffic Access Point Design Guide · 2019-12-28 · traffic and network link quality in data center and telecom carrier networks. This design guide will help you understand

We’re proud to be a part of your network’s story.Here at CommScope, we embrace our role as a trusted resource, partner, and facilitator. We create the infrastructure that connects the world and evolves with every advance in technology. By investing all of our capabilities, resources, relationships, and products into your toughest challenges, we continue our long history of solving problems together—paving the way for new ideas and fresh ways of thinking.

We’re a trusted resource and partner around the world because we’re invested in you: your people, your networks, your success. It inspires us to build relationships and infrastructure…connect people and technologies across protocols, oceans, and time zones…and share what we learn along the way.

This is our promise to you. This is CommScope.

www.commscope.comVisit our website or contact your local CommScope representative for more information.

© 2014 CommScope, Inc. All rights reserved.

All trademarks identified by ® or ™ are registered trademarks or trademarks, respectively, of CommScope, Inc. This document is for planning purposes only and is not intended to modify or supplement any specifications or warranties relating to CommScope products or services. CommScope is certified according to ISO 9001, TL 9000, and ISO 14001.