instantaneous active and reactive power … active and reactive power control in off-grid smart...
TRANSCRIPT
INSTANTANEOUS ACTIVE AND REACTIVE POWER CONTROLIN OFF-GRID SMART HOUSE
Takashi Oki1, Hidehito Matayoshi1, Hayato Tahara1, Gul Ahmad Ludin1,Sharma Aditya1 and Tomonobu Senjyu1
1Faculty of Engineering, University of the Ryukyus,Okinawa, Japan 903-0213
ABSTRACT
Reduction of carbon dioxide emissions is a big chal-lenge for the entire world. Therefore, a residentialphotovoltaic (PV) system has recently begun to spreadand the increasing penetration rate of the renewableenergy is expected. However, output power from PVdepends on isolation condition and entails uncertainty.So if many PV systems are integrated into the elec-trical power system, voltage and frequency fluctua-tion in the power system will occur. Therefore, re-duction of PV generation or isolation from the powersystem is required to the demand side. In this study,the completely off-grid smart house which is not con-nected with the power system is proposed. In thehouse, off-grid PV system, storage battery, electricalvehicle (EV), and Home Energy Management System(HEMS) are introduced.
INTRODUCTION
The carbon dioxide reduction is a big challenge forthe entire world. Accordingly, the energy efficiency ofhousehold is recognized major problem. As a methodto this problem, Home Energy Management System(HEMS) is presented in (Yoshikawa and Awai, 2011;Niyato et al., 2011; Han and Lim, 2010; Son et al.,2010; Jin and Kunz, 2011). HEMS automatically per-form energy saving without manual action. In off-grid smart house, the power from PV system and thechanges of consumption causes steep fluctuation of thepower supply voltage. This fluctuation have adverseeffect to the home electric appliances. In previousstudies, related to inverter control, the inverter is op-erated with feedback control based on the root meansquare or average value of voltage in (Jung et al., 2007;Hu et al., 2011; Tirumala et al., 2002). These con-trol methods cat not suppress steep voltage fluctuation.For solving this problem,this research study appliesthe inverter control method based on single phase dqtransformation system (Yamauchi et al., 2012; Miyagiet al., 2014). In order to put the off-grid smart houseinto practice, a consideration of the state of charge(SOC) for a fixed battery is needed. In this study,the HEMS adjusts the energy consumption of elec-tric appliances considering the battery remaining ca-pacity to avoid the shortage of energy. Furthermore,efficient operation of PV is performed by Maximum
Power Point Tracking (MPPT) (Esram and Chapman,2007). The effectiveness of this study is verified byMATLAB/SimPowerSystems.
SYSTEM MODELThe smart house model is shown in Figure 1. In thismodel, HEMS is able to control electric appliances.The communication between HEMS and appliancesis performed by wireless communication techniques.The fixed battery with a capacity of 2 kWh and an in-verter with a rated output of 3kW has been introduced.Simulation circuit is illustrated in Figure 2. The DC-DC buck-boost converter which is connected to PVpanels executes the MPPT control of PV. To keep avoltage in the DC-Link, the DC-DC boost converteris connected to the DC-Link. Moreover, a fixed bat-tery is also connected to the DC-Link. In this way, thepower losses can be decreased, because the power in-verter for a battery is not required. There is another ad-vantage that it will maintain the level of output powerfrom PV.
PV SystemThe model of the PV array is simulated by basic equa-tion and current source (Itako and Mori, 2005). Table1 shows the parameters of PV. The Single-Ended Pri-mary Inductance Converter (SEPIC) is used as a DC-DC converter for PV (Duran et al., 2011). Figure 3illustrates SEPIC. SEPIC has both advantages protec-tion for the occurrence of a short-circuit and same po-larity of input and output voltages.
Fixed Battery SystemA fixed battery is connected to DC-DC boost con-verter, which is shown in Figure 4. The DC-DC con-verter boosts the output voltage of a battery from 200Vto 350V. The Droop control method is applied for thepurpose of maintaining the voltage in the DC-Link.The current command value for the DC-DC converteris determined by the PI control using SOC for a fixedbattery. The bttery control system is shown in Fig-ure 5. The allowable voltage range in the DC-Link is±20V (VDC=330∼370V).
INVERTER CONTROL METHODIn this section, the inverter control method based oninstantaneous active and reactive power is explained.
Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
- 2593 -
DC
DC
PV
DC
AC
Power
Conditioner
DC
DC
Battery
HEMSPower Control
Wi-FiZigBee
DC-DC
Converter
Loads
Figure 1 Configuration of smart house
PV
200V
Battery
VDC
DC
DC
L3
Vr =
iL
S1
S2
S3
S4
DC
DC
ipv
ib
Lf
Cf
L1L2
L4100VVp =
100VVn =
200V
10Ah
2kW
2kWh
3kW
Lf
6kVA
Figure 2 Simulation circuit
IPV
C3
C 2L1
S
D1
PV
+
-
L2
C 1
IDC
VDC
VPV
VPV
IPV
MPPT control+
-
Vmax
PI PWM
SEPIC
Figure 3 SEPIC
S2
Ldc
Cdc
S1
Battery200V
Figure 4 Battery converter
VDC
V*
DC
Rb
ξb
ξ*
b
PI2
I*
b+
+
+
+
-
PWM
I*
b
- -
+PI1
Ib
PI3+
-Droop control
Figure 5 Battery control system
Phase DetectionThe voltage of power supply in the smart house is af-fected by the fluctuation of PV output power. Hence,
Table 1 PV panel constantsPV short-circuit current[A] 18.3PV open circuit voltage[V] 230.0Diode saturation current[A] 1.94×10−16
PV Short-circuit currentat18.3
at standard temperature[A]Diode saturation current
1.94 ×10−16
at standard temperature[A]Standard cell temperature[K] 298Amount of solar radiation[kW/m2] 1Area of a solar panel [m2] 1.47Number of solar panels 14The total area of solar panels [m2] 20.58Energy gap[V] 1.767 ×10−19
Elementary charge[C] 1.6 ×10−19
Boltzmann’s constant 1.38 ×10−23
Constant independent of temperature 2.0 ×10−2
Junction constant1.95
(determined by the materialConstant determined by the material 2.8
the Phase-locked loop circuit that can estimate phasein a high accuracy is required. This research uses theALOF-PLL circuit to estimate the phase (Han et al.,2009).
The Single Phase dq Transformation SystemThe root mean square value (RMS) VRMS is calcu-lated from AC voltage v =
√2V sin(ωt) as follows:
VRMS =
√1
T
∫ T
0
v2dt
=
√1
T
∫ T
0
(√2V sinωt)2dt (1)
If this equation is used to estimate the phase of thevoltage, the command signal is delayed. The delayhas the risk of an accident with appliances. The con-trol method using the single-phase dq transformation,estimates an instantaneous voltage value. Figure 6 il-lustrates Single-phase dq transformation system. In-put voltage V is converted into digital signals v andv′. Where, the digital signal v′ is delayed δθ from v inthe phase by a delay block. Figure 7 shows the digitalsignals v and v′. The ∆v that is difference between vand v′ can be calculated as follows:
∆v = v − v′ =√2V sinωt−
√2V sin(ωt− δθ)
=√2V sinωt−
√2V sinωt cos δθ
+√2V cosωt sin δθ (2)
where, V sinωt and V sinωt cos δθ are eliminatedin the analogue/digital conversion processing. Then,only
√2V cosωt sin δθ keep remains. Moreover, ∆v
is obtained as shown in Figure 8. The β axis com-ponent vβ can be obtained by holding the ∆v for 10µs and multiplying by K = 1/ sin(δθ) as shown in
Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
- 2594 -
Delayv β
vα vα
2+vβ
2Vd
_ K Hold
Circuit
10µs5µs
AD
100ksps
vv
v’ ∆v
Figure 6 Single-phase dq transformation system
0.29995 0.3 0.3001-20
-10
0
10
Time t [s]
v , v
’[V
] v
v’
0.30015
Figure 7 v and v′
0.29995 0.3 0.30010
0.5
1
Time t [s]
∆v[V
]
0.30015
Figure 8 Differntial value , ∆v
0.29995 0.3 0.30010
100
200
300
400
Time t [s]
vβ[V
]
0.30015
Figure 9 beta axis component, vβ
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8-500
0
500
v[V
]
Time t [s]
Figure 10 Input voltage, v
Figure 9. By defining v as the α-axis component, thed-axis component Vd and q-axis component Vq are ob-tained as follows:
Vd = vα sinωt+ vβ cosωt =√v2α + v2β (3)
Vq = vα cosωt− vβ sinωt = 0 (4)
The instantaneous magnitude√2V of input voltage v
can be obtained calculating Vd using vα and vβ . Theinput voltage v is shown in Figure 10. Furthermore,Figure 11 illustrates magnitude of input voltage Vm ascalculated by the proposed system and the RMS valueVRMS which is calculated by conventional method.It is obvious that output response of the single-phasedq transformation system is faster than the system re-sponse using RMS value.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.80
100
200
300
Vm, V
RMS[V
]
Time t [s]
Vm = V
d / 2
VRMS
Figure 11 Magnitude of input voltage, Vm and VRMS
Vm
Im
θ
from ALOF-PLL sinθ
cosθ
P=VmImcosθ
Q=VmImsinθ
Figure 12 Active and reactevi power detection circuit
Active and Reactive Power DetectionFigure 12 shows the active and reactive powers detec-tion circuit. This circuit calculate active and reactivepowers P , Q using the single-phase dq transformationsystem, and phase difference, θ, between Vr and Iinvas follows:
Pinv = VmIm cos θ (5)Qinv = VmIm sin θ (6)
Command Value Determination for Inverter Con-trolA single-phase inverter, controls the magnitude andphase of the output current. In this research, due to us-ing PQ feedback control, the current command valueis determined by the PQ information that has beendetected by the active and reactive powers detectioncircuit. Then, rearranging Equations (5) and (6), themagnitude of the output current command value Icomand the phase difference θ are calculated as follow:
Icom =
√P 2inv +Q2
inv
Vm(7)
θ = arcsinQinv
VmIm(8)
By substituting the command values P ∗inv, Q
∗inv for
Pinv , Qinv in above equation, the inverter output cur-rent command can be determined as follow:
Iref =√2Icom sin(ωHt∗ + θ) (9)
In this study, the inverter uses control method based onthe instantaneous active and reactive powers feedbackcontrol. The inverter control system is shown in Figure13. The load voltage Vr and DC-Link voltage VDC arecontrolled by the inverter using PWM control.
Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
- 2595 -
Pinv
Qinv
VDC
*
Vr*
Vr =Vm
VDC PI
+-
Pinv*2
+Qinv*2
VmVm
Iref
Pinv*
Qinv*
sin(ωHt*+θ)
ωHt*
PWM
fs=20kHz
ωUt
++
+
-
-
+
Im
Before phase synchronization
PI
After phase synchronization
Figure 13 Inverter control system
SOC < 70%
Limit load according to load priority
Turn off according to load priority
Yes
Yes
No
No
SOC < 50%
SOC < 70.02%
Yes
Turn on / No limit load
No
Figure 14 Load management algorithm for HEMS
HEMSEnergy management in the proposed smart house isachieved by the HEMS. The algorithm of energy man-agement is shown in Figure 14. The power consump-tion of appliances are adjusted considering SOC forthe battery. The adjusting of power consumption isperformed based on priority level of all appliances.
SIMULATION RESULTSIn the proposed smart house, in order to avoid deple-tion of the SOC for a storage battery, HEMS adjuststhe power consumption based on priority of loads. Thepriority of critical loads in order of highest to lowest isL1, L2, L3, L4. L1 is supplied with a stable powerduring all the time. In order to confirm load controlby the HEMS during simulation time that is 4 sec-onds, the initial value of SOC for the storage batteryis set 70.003%. When the SOC for the storage bat-tery is less than 70%, the loads are controlled by theHEMS. The simulation result is illustrated in Figures15∼26. Figure 15 shows the inverter output currentIinv. The inverter output current is decreased by the
0 0.5 1 1.5 2 2.5 3 3.5 4−20
−10
0
10
20
Time t [s]
Iin
v [
A]
Figure 15 Inverter output current, Iinv
0 0.5 1 1.5 2 2.5 3 3.5 4−400
−200
0
200
400
Time t [s]
Vr [
V]
Figure 16 Receiving voltage, Vr
0 0.5 1 1.5 2 2.5 3 3.5 4-1000
0
1000
2000
3000
Time t [s]
Pin
v [
W]
, Q
inv [
var]
Pinv
Qinv
Figure 17 Output active and reactive power of inverter,Pinv , Qinv
HEMS due to low SOC for the storage battery. Figure16 shows receiving voltage Vr which is 200V. Accord-ing to Figure 16, regardless of the adjusting of load,the receiving voltage was maintained at a 200V. Theinverter output active and reactive powers Pinv , Qinv
are shown in Figure 17. In Figure 17, it is clear that in-verter output active and reactive powers are decreasingduring low consumption of load. Figures 18, 19 showsthe DC-Link voltage VDC and the output current of thestorage battery, Ib respectively. The DC-Link voltageVDC is maintained at a 350V by the control of the in-verter and the storage battery. Figure 20 shows theSOC ξb for the storage battery. The different SOCsfor the storage battery are illustrated due to with orwithout load control. The frequency of receiving volt-age fH is shown in Figure 21. According to Figure21, the frequency of receiving voltage is maintained at60Hz. Figures 22, 23, 24 show the amount of solarradiation, IN , the output current of the PV, IPV , andthe output voltage of the PV, VPV respectively. TheMPPT control is performed by using the hill climb-ing method in 1.4s cycles. Figure 25 shows the loadcurrents IL1, IL2, IL3, IL4 with load control. In thisFigure, it is clear that the load currents IL2, IL3 andIL4 are limited by HEMS when SOC of battery is low.On the other hand, Figure 26 shows the load currentsIL1, IL2, IL3, IL4 without load control. In this Figure,the load currents are constant.
Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
- 2596 -
0 0.5 1 1.5 2 2.5 3 3.5 4250
300
350
400
Time t [s]
VD
C [
V]
Figure 18 DC-Link voltage, VDC
0 0.5 1 1.5 2 2.5 3 3.5 4−5
0
5
10
Time t [s]
Ib [
A]
With load control
Without load control
Figure 19 Output current of storage battery, Ib
0 0.5 1 1.5 2 2.5 3 3.5 469.97
69.98
69.99
70
70.01
Time t [s]
ξb [
%]
With load control
Without load control
Figure 20 State of charge for storage battery, ξb
0 0.5 1 1.5 2 2.5 3 3.5 40
20
40
60
80
Time t [s]
fH
[H
z]
Figure 21 Frequency of receiving voltage, fH
0 0.5 1 1.5 2 2.5 3 3.5 4
0.7
0.8
0.9
1
Time t [s]
IN
[kW
/m2]
Figure 22 Insolation, IN
0 0.5 1 1.5 2 2.5 3 3.5 4−10
0
10
20
Time t [s]
IP
V [
A]
Figure 23 Output current of PV, IPV
CONCLUSIONIn this paper, the completely off-grid smart housewhich is not connected with the power system is pro-posed. The off-grid PV system, storage battery, EV,
0 0.5 1 1.5 2 2.5 3 3.5 4−100
0
100
200
300
Time t [s]
VP
V [
V]
Figure 24 Putput voltage of PV, VPV
0 0.5 1 1.5 2 2.5 3 3.5 4−10
−5
0
5
10
Time t [s]
IL
1 [
A]
(a) Load current with control, IL1
0 0.5 1 1.5 2 2.5 3 3.5 4−4
−2
0
2
4
Time t [s]
IL
2 [
A]
(b) Load current with control, IL2
0 0.5 1 1.5 2 2.5 3 3.5 4−10
−5
0
5
10
Time t [s]
IL
3 [
A]
(c) Load current with control, IL3
0 0.5 1 1.5 2 2.5 3 3.5 4−10
−5
0
5
10
Time t [s]
IL
4 [
A]
(d) Load current with control, IL4
Figure 25 Load currents with control
and HEMS have been introduced into the smart house.In the off-grid smart house, the bad influence to appli-ances due to fluctuation of the PV output power is rec-ognized problem. Furthermore, because the house cannot receive the electric power from power grid, the de-pletion of energy in storage battery should be avoided.By applying the dq transformation system to controlthe inverter instead of conventional control system,instantaneous inverter control is achieved. This hassuppressed the voltages and frequency fluctuation ofpower supply. Moreover, in order to save the elec-tric energy, the HEMS controlled power consumptionof electric appliances considering SOC for the storagebattery.
Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
- 2597 -
0 0.5 1 1.5 2 2.5 3 3.5 4−10
−5
0
5
10
Time t [s]
IL
1 [
A]
(a) Load current without control, IL1
0 0.5 1 1.5 2 2.5 3 3.5 4−4
−2
0
2
4
Time t [s]
IL
2 [
A]
(b) Load current without control, IL2
0 0.5 1 1.5 2 2.5 3 3.5 4−10
−5
0
5
10
Time t [s]
IL
3 [
A]
(c) Load current without control, IL3
0 0.5 1 1.5 2 2.5 3 3.5 4−10
−5
0
5
10
Time t [s]
IL
4 [
A]
(d) Load current without control, IL4
Figure 26 Load currents without control
REFERENCESDuran, E., Andujar, J. M., Segura, F., and Barragan,
A. J. 2011. A high flexibility dc load for fuel celland solar arrays power sources based on dc-dc con-verters. IDEAS, vol. 88:pp. 1690–1702.
Esram, T. and Chapman, P. L. 2007. Comparison ofphotovoltaic array maximum power point trackingtechniques. IEEE Trans. on Energy Conversion, vol.22:pp. 439–449.
Han, D.-M. and Lim, J.-H. 2010. Design and imple-mentation of smart home energy management sys-tems based on zigbee. IEEE Trans. on ConsumerElectronics, vol. 56, no. 3:pp. 1417–1425.
Han, Y., Xu, L., Khan, M. M., Yao, G., Zhou, L.-D., and Chen, C. 2009. A novel synchroniza-tion scheme for grid-connected converters by us-ing adapive linear optimal filter based pll(alof-pll).
Elsevier, Simulation Modeling Practice and Theory17, pages pp. 1299–1345.
Hu, S.-H., Kuo, C.-Y., Lee, T.-L., and Guerrero2011. Droop-controlled inverters with seamlesstransition between islanding and grid-connected op-erations. Energy Conversion Congress and Exposi-tion (ECCE), IEEE, pages pp. 2196–2201.
Itako, K. and Mori, T. 2005. A current sensorless mpptcontrol method for a stand-alone-type pv genera-tion. IEEJ Trans., vol. 125-D, no. 10:905–910.
Jin, C. and Kunz, T. 2011. Smart home networking: Combining wireless and powerline networking.Wireless Communications and Mobile ComputingConference (IWCMC), 2011 7th International, Con-ference Publications, pages pp. 1276–1281.
Jung, S., Bae, Y., Choi, S., and Kim, H. 2007. A lowcost utility interactive inverter for residential fuelcell generation. IEEE Trans. on Power Electronics,vol. 22:pp. 2293–2298.
Miyagi, M., Shiroma, Y., A. Yona, T. S., and Fun-abashi, T. 2014. Uninterruptible smart houseequipped with the phase synchronization controlsystem. International Journal of Electrical Powerand Energy Systems, Elsevier, Vol. 63:pp. 302–310.
Niyato, D., Xiao, L., , and Wang, P. 2011. Machine-to-machine communications for home energy manage-ment system in smart grid. IEEE CommunicationsMagazine, vol. 49:pp. 53–59.
Son, Y.-S., Pulkkinen, T., Moon, K.-D., and Kim, C.2010. Home energy management system based onpower line communication. IEEE Trans. on Con-sumer Electronics, vol. 56, no. 3:pp. 1380–1386.
Tirumala, R., Mohan, N., , and Henze, C. 2002.Seamless transfer of grid-connected pwm invertersbetween utility-interactive and stand-alone modes.Applied Power lectronics Conference and Exposi-tion (APEC) 2002, Seventeenth Annual IEEE, Vol.2:pp. 1081–1086.
Yamauchi, H., Miyagi, M., Uchida, K., Yona, A.,and Senjyu, T. 2012. Advanced smart housewith an electric vehicle. International Confer-ence on Renewable Energy Research and Applica-tions(ICRERA), 2012 IEEE, pages pp. 1–6.
Yoshikawa, T. and Awai, I. 2011. Hems withreasonant-type wireless power transmission. IMWS,pages 167–170.
Proceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
- 2598 -