installation, operation and maintenance instructions · safety considerations hazards may exist...
TRANSCRIPT
Installation, Operation andMaintenance Instructions
HRV650 • HRV700 • HRV1150
HRV1150
- 2 -
Table of Contents
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
InstallationInspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mounting Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Internal Grilles and Diffusers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
ControlsGeneral Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Frost Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Remote Wall Control (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Airflow Measurement and BalancingFlow Station Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Balancing Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
System ServiceBi-Monthly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Annual Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Appendix A: Mounting Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Appendix B: Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Appendix C: Flow Station Positions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Appendix D: Drain Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Appendix E: Terminal Control Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Appendix F: Electrical Connection Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Appendix G: Make-up Heat Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Appendix H: Trouble Shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Manufacturer reserves the right to discontinue or change specifications or designs without notice or obligation.
Safety ConsiderationsHazards may exist within this equipment because it
contains electrical and powerful moving components.
Only qualified service personnel should install or service
this equipment. Untrained personnel can perform basic
maintenance such as maintaining filters. Observe pre-
cautions marked in the literature and on labels attached
to the unit. Follow all safety codes.
Installation
InspectionInspect the exterior of the unit for shipping damage by
ensuring that there is no damage to the door, door latches,
door hinges, damper, duct collars, cabinet, etc. Inspect the
interior of the unit for damage by ensuring that the fan
motors and housings, heat exchanger, insulation,
dampers, actuators and drain pans are all intact.
If transportation damage is found, file a claim immediately
with the transportation agency. Remove all packaging, tape,
etc. from the cabinet.
Mounting Location RequirementsWhen determining an installation location, the unit must
be mounted in a heated area to prevent condensate drain
lines from freezing. The mounting location should be
away from occupied areas to provide quiet operation. The
area should also be easily accessible for maintenance.
NOTE: These Heat Recovery Ventilators have minimum
clearance requirements when mounting. See
Appendix B for specific clearance requirements.
Mounting options must allow 6" [152mm] clear-
ance in front of control cover for access.
A mounting location close to an exterior partition will
minimize the length of insulated duct. The unit should be
close to a drain and 120 volt, 60 Hz power supply. The
unit should be mounted away from hot chimneys, electri-
cal panels and other hazards. The area should also be
easily accessible for maintenance.
Mounting OptionsThere are several options for hanging or floor mounting
the unit.
NOTE: In all cases, the unit must be level. Consult local
building code for restrictions in your area regard-
ing installation.
Hang the unit with the reinforced rubber straps provid-
ed as shown in Appendix A. Check with local building
codes regarding the use of rubber straps in commercial
buildings. Attach the straps to the unit with two #8 screws
provided. Then attach the other end of the strap to the
ceiling joists, trusses, custom frame, etc.
The unit can also be hung with 3/8" [10mm] threaded
rod and U channels or angles (not supplied) as shown in
Appendix A.
When installing the unit, keep in mind that access to the
control panel may be required. Supply and exhaust ducts
to outside may have 1" to 2" [25 to 51mm] of insulation on
them. Rubber vibration isolation may be required and is
recommended for quiet operation.
The unit can also be mounted on a metal or wooden
curb (not supplied) bolted to the floor as shown in
Appendix A. Space must be left under the unit to allow
connection of drain lines. A gradual slope is required
for the condensate water to drain by gravity (minimum
1/4"/foot) [6mm/305mm]. If this is not possible, a pump
should be used. If attachment of the unit to the curb
is required, ensure that screws, bolts and mounting
hardware do not interfere with moving parts or that the
integrity of the cabinet insulation is not affected.
DuctworkThe supply and exhaust duct connections on the unit
are as follows:
NOTE: Duct sizes are for connection purposes only.
Ducts should be sized to keep noise and pressure
drop to a minimum.
The supply and exhaust ducts connected to outside, as
well as any ducts passing through an unconditioned
space, must have a minimum insulation value of R5. In
addition, a continuous integral vapor barrier over the duct
insulation must be used.
Air balancing dampers are recommended for both sup-
ply and exhaust ducts to allow for adjustment of airflow.
Also, flexible canvas connectors should be installed close
to the unit in the supply duct to the building and the
exhaust duct from the building to reduce noise transmis-
sion from the unit to the building (see Appendix C).
All ports on the 600 cfm and 1200 cfm units have 1"
[25mm] flanges to facilitate the installation of the duct-
work. Please note that the "Fresh Air from Outside" port
has a frost control damper incorporated with it. Ensure
that any mechanical fasteners used to connect the duct
do not interfere with the operation of the damper. Screws
can be installed on the side of the cabinet rather than
the flange for this port only. For port locations see
Appendix B.
All ports on the 700 cfm unit have 2" [51mm] flanges to
facilitate the installation of the ductwork. Please note the
"Fresh Air From Outside" connection is factory set to be
the left side upper port. It is possible to reverse the opera-
tion of the frost control damper in order to use the port on
top of the cabinet for "Fresh Air From Outside" connection.
UNIT DUCT SIZE
600 cfm or 700 cfm 14" x 8" [356 x 203mm]
1150 cfm 20" x 8" [508 x 203mm]
WARNINGDisconnect the main power switch to the unit before
performing service or maintenance. Electric shock can
cause personal injury.
- 3 -
To change the "Fresh Air From Outside" from the side
to the top use the following directions. For port locations
see Appendix B.
Remove the cover of the damper motor with a flat screw
driver. Reverse the Orange and Red wires by moving the
Orange from terminal #2 to terminal #3 and moving the
Red wire from terminal #3 to terminal #2. The end result,
in order to have the "Fresh Air From Outside" connection
to the top port, will be; #1 - White, #2 - Red, #3 - Orange.
Internal Grilles and DiffusersLocate exhaust grilles and supply diffusers to provide
effective ventilation and avoid short circuiting of airflows.
Adjustable dampers should be provided at every grille
and diffuser location to make balancing of the system
possible.
A proper selection of style and size of grilles and dif-
fusers is required to minimize pressure drop. The velocity
of the airflow should not exceed 400 ft/min [2 m/sec] for
normal applications.
The duct system should be designed according to the
high speed flow rate of the unit. In order to keep the noise
and pressure drop to a minimum, a maximum air velocity
of 1100 ft/min [5.6 m/sec] should be used in calculations
in duct design. The duct runs should be kept as short as
possible with the minimum amount of elbows and transi-
tions. The manufacturer recommends the use of smooth
radius elbows or square elbows with turning vanes to
achieve maximum performance.
DrainsThe drain fittings provided with the unit will accept a
3/4" [19mm] NPT coupler (supplied by others). The drain
line for the unit must be fabricated on-site and connected
to the building main. A loop in the hose or trap in the cop-
per or plastic pipe must be provided to prevent sewer
gases from entering the unit when connecting to a drain
as illustrated in Appendix D.
NOTE: Consult local building code for plumbing require-
ments in your area. If copper pipe is to be used,
ensure not to solder to the 3/4" [19mm] coupler
while it is attached to the plastic drain fitting as
deformation may occur. Ensure adequate slope is
present to allow good drainage (minimum 1/4"/foot
or 6mm/305mm).
Electrical Connections
Power
A terminal block and strain relief bushing or a junction
box is provided for line voltage to make the necessary
power connections.
The electrical requirements are as follows:
Control Box Access For Low Speed Setting
(600 cfm/1150 cfm only)Disconnect power to the unit. Remove the four screws
securing the cover plate as shown in Appendix F. Lift off
the control cover plate and switch the red wire as shown
in Appendix F.
Controls
General Information
Fan Interlock Switch (FF)External fan control can be achieved by connecting an
external fan source (G) through dry contacts (FF). These
contacts are closed on a call for ventilation or frost control.
Speed Selection (600 cfm/1150 cfm only)There are three speed settings available with the con-
trols, only two of which can be functional at any one time.
The units are factory set to use the low and high speed
taps on the blower motors. If necessary, the medium
speed tap can be used instead of the low speed tap. See
Appendix F for instructions on how to make this change.
Units without the remote wall control option can be shut
off by opening the contact between LOW - COM or HIGH
- COM as shown in Appendix E-2.
Sequence of OperationBefore start-up, check the unit for obstructive packaging,
objects near or in blowers, dampers, heat exchangers, etc.
Once installation is complete, check all modes of operation
to ensure that the unit is working properly. Close the doors
and check for operation on LOW, COM and HIGH. Use a
wall control or the dry contact switching to run fan speeds
as shown in Appendix E-2.
The 700 cfm unit is two speed. Low speed can be initi-
ated by creating a closure across LOW - COM or high
speed can be initiated by creating a closure across HIGH
- COM.
VOLTAGE 120V 120V 120V
MCA 8.6 5.6 13.3
MOP 12 8 15
600 cfm 700 cfm 1150 cfm
- 4 -
- 5 -
Unit Check Points:
___ Power connected, no ventilation call - Both fans are
off, frost control damper (if equipped) closes off
fresh air from outside.
___ Power connected, low speed call - Both fans on low
speed, internal frost control damper (if equipped)
opens fresh air from outside. If equipped with recir-
culation module, the internal frost control damper
closes recirculation opening.
___ Power connected, high speed call - Both fans on
high speed, frost control damper opens fresh air
from outside. If equipped with recirculation module,
the internal frost control damper closes recirculation
opening.
___ Power connected, occupied timer/sensor connec-
tion open (unoccupied mode) - Both fans are off,
frost control damper closes fresh air from outside. If
equipped with recirculation module, the internal frost
control damper opens recirculation opening.
___ Power connected, FF control contacts close during
unit ventilation or frost control cycle.
Frost ControlThe unit functions are controlled by integrated controls
in the unit which may include Exhaust Only Defrost or
Recirculation Defrost (via the recirculation module - 600
cfm and 1200 cfm units only). In cold temperatures, frost
control cycles will remove frost from the heat exchanger
to maintain good operation.
Exhaust Only Defrost (Optional)Frost removal occurs when the supply blower de-ener-
gizes, the supply air damper and the heat exchange
damper close and the exhaust fan continues to circulate
only warm inside air through the flat plate heat exchang-
er to maintain ventilation. This process prevents the build
up of ice in the heat exchanger. Frost control is tempera-
ture initiated at 23°F to -22°F [-5°C to -30°C] and time
based.
Recirculation Defrost Module
The Recirculation Defrost Module is only available with
the 600 cfm and 1150 cfm units. The frost control cycle is
electronically controlled in response to the outside
temperature 23°F to -22°F [-5°C to -30°C]. On a call for
frost control, the supply air damper in the recirculation
module closes, exhaust fan is de-energized and the sup-
ply fan continues to recirculate warm air through the flat
plate heat exchanger. It is possible to extend the frost con-
trol times during very cold weather by removing the jumper
JU1-F on the circuit board. For dimension and weight
changes to the 600 cfm and 1150 cfm models with the
recirculation defrost module, see Appendix B-2 and B-4.
Remote Wall Control (Optional)
Remote mounted wall control options are solid state
controls that can be used to control the ventilators from a
remote location. The connection from the ventilator to the
control is low voltage and requires a 4 conductor (24
gauge minimum) LVT cable. Models are available with a
dehumidistat control and speed switching. The following
three options are available:
Standard Wall Control
Dehumidistat to engage high speed exchange. Slide
switch operation supporting continuous low exchange
and continuous high exchange.
Xtra Wall Control
Dehumidistat to engage high speed exchange.
Electronic push button operation supporting intermittent
(stand-by) ventilation, continuous low exchange, continu-
ous high exchange, maintenance indicator light and
exchange indicator light.
AquaAir Wall Control
Ideal for pool dehumidification. Dehumidistat to engage
high speed exchange. Electronic push button operation
supporting intermittent (stand-by) ventilation, continuous
low exchange, continuous high exchange, maintenance
indicator light and exchange indicator light.
Airflow Measurement and BalancingOnce installation is complete, the supply and exhaust
airflows should be balanced to ensure proper operation
and a good quality installation. A well designed duct
system with properly sized duct runs and equal static
pressure losses of both the supply and exhaust will aid in
balancing the unit. However, it will be necessary to take
flow measurements with the proper equipment to ensure
a balanced system. Magnehelic gauges and Flow
Measuring Stations (FMS) are available for 14" x 8" [356
x 203mm] or 20" x 8" [508 x 203mm] rectangular duct and
a range of round duct sizes. Please ask your supplier for
more information.
Flow Station PositionsWhether flow stations are permanently installed or used
temporarily, the position they are placed in is very impor-
tant to ensure accuracy as shown in Appendix C. The
best locations for mounting the FMS is in the long straight
sections of ducting where airflow has stabilized across
the area of the duct. This position will provide the most
accurate measurements.
The next best location for the FMS is immediately
before or after a 90 degree elbow and 12" [305mm] from
any damper. In straight sections of pipe, the FMS should
be installed at least 30" [762mm] from any fan outlet. This
applies to the "Supply Air Opening" connection on the
heat recovery ventilator and the "Exhaust Air Opening"
connection.
WARNINGA negative building pressure may develop during the
frost control cycle with possible backdrafting fumes from
combustion equipment.
- 6 -
With airflow measuring stations permanently installed,
balancing is done by measuring airflow on one side of the
heat recovery ventilator and then the other. Adjustments
can then be made to the damper to equalize airflows.
When using the temporary method, an FMS is installed
in one air duct of the heat recovery ventilator and the flow
recorded. The FMS is then relocated to the other air duct
and the airflow is recorded again. Dampers can then be
adjusted to equalize airflow. This procedure should be
repeated to ensure that the unit is balanced properly.
Balancing ProcedureBefore proceeding with balancing, all windows, over-
head doors and walk-in doors should be closed and
exhaust systems should be turned off.
The connections between the flow stations and the
ducts must be sealed with tape. Mount the magnehelic
gauge in a convenient location where it is level and will
not vibrate or be bumped. Zero the gauge. Measure the
exhaust air first as it is often the lowest due to a longer
duct system.
With the fan speed at maximum, connect the hoses
from the FMS to the magnehelic gauge. If the needle falls
below zero, reverse the hose connections. Ensure that
the damper is wide open. Take a reading from the mag-
nehelic gauge and record it. Remove the FMS and place
it in the supply duct. This process is not necessary if the
FMS is to be permanently mounted.
Repeat the procedure. If the reading is higher in the
supply duct, adjust the damper until the reading is the
same. If the reading is lower, return the FMS to the
exhaust duct and adjust the damper to obtain the same
reading as the supply duct.
System Service
Bi-Monthly Maintenance
Bi-monthly maintenance should include:
Air Filters
The standard foam filters are washable. Under normal
conditions it is recommended that they be cleaned every
two months. More frequent cleaning may be required
under extremely dirty operating conditions. Use a vacuum
cleaner to remove the heaviest portion of accumulated
dirt, then wash with warm water.
A medium efficiency filter for the supply airstream is
available from your supplier. This filter is disposable and
should be replaced when it becomes dirty.
Drain Pans and Interior of Unit
With the filters removed from the unit, the foil faced
insulation surfaces and drain pans should be wiped clean
with a soft cloth and mild cleaning solution. Ensure that
the drain fittings are free from dirt and draining freely.
Annual Maintenance
Annual maintenance should include:
Air Filters
Vacuum and wash standard foam filters. Replace
medium efficiency filter if present.
Drain Pans and Interior of Unit
Wash the foil faced insulation surfaces and wipe the
drain pans with a soft cloth and mild cleaning solution.
Check the drain fittings to ensure they are draining freely.
Flat Plate Heat Exchanger
The flat plate heat exchanger must be handled with
care. In order to ensure maximum efficiency of the parti-
tions, it is recommended that it be washed once a year
following the season of most intense use. Allow the flat
plate heat exchanger to soak for three hours in warm
water and mild soap. Rinse under a heavy stream of
water. When replacing the flat plate heat exchanger sec-
tions, make sure the flutes on the heat exchanger are
positioned in the supply airstream. Failure to do so will
result in low airflow on the exhaust airstream due to sys-
tem pressure trapping or holding condensate in the flutes.
WARNINGDisconnect power before maintaining the unit.
WARNINGDisconnect power before maintaining the unit.
Washable Foam Filter orMEF Filter - optional
Washable Foam Filter
Washable Foam Filter
MEF Filter - optional
Figure 1: 600 cfm and 1150 cfm
Figure 2: 700 cfm
Fans
Blower wheels and fan housing should be checked for
dirt build-up. If they appear dirty, it may be necessary to
remove the blower assembly and then vacuum the dust
out through the fan mouth. See figures 3 and 4 for instruc-
tions on removing the blower assembly.
System Operation Check
Verification of all control modes should be checked to
ensure proper operation. Refer to the Controls Section,
Sequence of Operation.
Testing and Replacement of the Damper Actuator
Check damper operation by switching between LOW -
COM or HIGH - COM on the dry contact terminal or by
switching through the modes on the optional remote wall
control. If the damper does not respond in one or both
directions, check all connections.
700 cfm ONLY: Check for 24 volt output between the
White/Red and the White/Orange wires at the damper
motor. If 24 volts can be measured at the damper motor,
the problem is either in the connections, the frost control
relay or the main circuit board.
600/1150 cfm ONLY: (CAUTION: 120 VAC) With the unit
powered but off, check for 120 volt output across the
white/black wires. If 120 volt can be measured at the
motor, replace the motor. If 120 volt cannot be measured
at the motor, check for 120 volts across pins J1-9 and
J1-1 at the printed circuit board.
Main Circuit Board Replacement
The main circuit board must be replaced if an electronic
problem arises. For example, the unit suddenly stops, the
unit stays in frost control mode all the time or if control
functions are not working properly.
Ensure that power is reaching the board. Test the
blower motors and damper actuators for operation when
directly connected to the appropriate power voltage. If the
motor and damper actuators function normally, replace
the main circuit board.
Motor and Blower Removal and Installation
Disconnect power from the unit. To determine if the fan
motor is burned out, disconnect the four-wire service con-
nector between the motor and cabinet. Connect the motor
directly to a 120 volt power source with an electrical cable
as follows:
If the motor functions normally, there is a problem with
the wiring connections or the main circuit board. Check all
wiring and replace main circuit board if necessary.
If the blower does not run, it must be replaced. To
replace the motor, remove the flat plate heat exchanger
from the unit. Disconnect the four-wire service connector
from the unit. Remove the fasteners holding the motor
assembly in place. Lift the assembly up and out, using
one hand under the motor and one hand to steady it.
Remove the assembly carefully from the unit to avoid
damage to the insulation, shelf, etc. Install the repaired
motor assembly by following these instructions in reverse.
WARNINGHot water and strong cleaning agents could damage
the polypropylene heat exchanger. Ensure the heat
exchanger is returned to the unit in the correct orienta-
tion. Use the sticker as a guide.
Figure 4: Blower Assembly Removal
700 cfm
RED + WHITE Low speed
BLUE + WHITE Medium speed
BLACK + WHITE High speed
Capacitor
Locking PlateRemove thesetwo screws
ServiceConnector
Thumbscrew
Figure 3: Blower Assembly Removal
600 cfm and 1150 cfm
- 7 -
- 8 -
3/8" [10mm]Threaded Rod(Supplied by others)
Rubber VibrationIsolater
Cabinet MountedU Channel
Wooden Curb(Supplied by others)
Bolt to Floor
Space must be left to allowconnection of drain lines with adequate slope for drainageDry Contacts
Dry Contacts
Space must be left to allow connectionof drain lines with adequate slope for drainage
Wooden Curb (Supplied by others)
Bolt to Floor
Rubber Vibration Isolator(Supplied by others)
U Channel(Supplied by others)
3/8" [10mm]Threaded Rod(Supplied by others)
NOTE: Diagrams show standard unit configuration.For units with the reversed door option, thedoor will be located here.
ReinforcedRubber Strap
Recirculation Module
Recirculation Module
Recirculation Module
700 cfm
Appendix A
Mounting Diagrams
600 cfm and 1150 cfm
- 9 -
4.00
0" [1
02]
8.00
0"[2
03]
8.00
0"[2
03] 3.
535"
[90]
4.00
0"[1
02]
28.0
05"
[711
]
14.0
00"
[356
]
5.85
9"[1
49]
13.3
75"
[340
]
23.5
00"
[597
]
2.75
0"[7
0]
14.0
00"
[356
]6.
500"
[165
] 8.00
0"[2
03]
8.00
0"[2
03]
14.1
03"
[358
]7.
705"
[196
]
4.00
0"[1
02]
24.5
00"
[622
]
12.0
05"
[305
]
4.02
8"[1
02]
34.0
00"
[864
]
19.2
07"
[488
]5.
125"
[130
]10
.005
"[2
54]
12.0
00"
[305
]15
.000
"[3
81]
EX
HA
US
T A
IRO
PE
NIN
G
SU
PP
LY A
IRO
PE
NIN
G
LIN
E V
OLT
AG
E IN
EX
HA
US
T A
IRO
UT
DO
OR
AIR
RE
TU
RN
AIR
SU
PP
LY A
IRLO
W V
OLT
AG
ET
ER
MIN
AL
ST
RIP
S
CO
NT
RO
L B
OX
AC
CE
SS
RE
VE
RS
ED
DO
OR
OP
TIO
N
LEF
T S
IDE
VIE
W
CDB
A
TO
P V
IEW
NO
TE
: F
or u
nits
with
the
reve
rsed
doo
r op
tion,
inte
rior
com
pone
nts
will
app
ear
as a
mirr
or im
age
of th
e ab
ove
diag
ram
.
FR
ON
T V
IEW
ST
RA
P M
OU
NT
ING
LOC
AT
ION
OU
TD
OO
R A
IRO
PE
NIN
G
RE
TU
RN
AIR
OP
EN
ING
RIG
HT
SID
E V
IEW
NO
TE
: A
min
imum
of 1
2.00
0" [3
05] c
lear
ance
from
any
ob
stru
ctio
n is
req
uire
d fo
r re
mov
al o
f the
con
trol
box
.N
OT
E:
A m
inim
um o
f 15.
000"
[381
] cle
aran
ce fr
om a
ny o
bstr
uctio
n is
req
uire
d fo
r re
mov
al o
f hea
t rec
over
y co
res,
fans
, etc
.T
he a
cces
s do
or c
an b
e re
mov
ed fr
om th
e ca
bine
t with
onl
y 2.
000"
[51]
of c
lear
ance
.
CO
NT
RO
L P
LAT
E
AC
CE
SS
DO
OR
HE
AT
RE
CO
VE
RY
CO
RE
RE
VE
RS
ED
DO
OR
OP
TIO
N
Dim
ensi
ons
in [
] ar
e m
illim
eter
s
Cen
ter
of g
ravi
ty
Dire
ctio
n of
airf
low
NO
TE
S:
PT
SH
RV
600i
PO
LY C
OR
EH
RV
600i
ALU
MIN
UM
CO
RE
LBS
38.4
924
.96
51.2
933
.26
148.
00
Kg
17.4
511
.32
23.2
615
.08
67.1
3
PT
SA B C D
TO
TAL
LBS
44.2
128
.67
58.9
238
.21
170.
00
20.0
013
.00
26.7
217
.30
77.1
1
Kg
A B C
TO
TAL
D
Line
vol
tage
in14
gau
ge w
ire n
ut
Con
dens
ate
drai
n fit
ting
(2x)
B3/
4" m
pt
CO
NN
EC
TIO
N T
AB
LE
CO
NN
EC
TIO
N S
IZE
S
NO
TE
: T
his
mod
el h
as a
dam
per
loca
ted
on th
e ou
tdoo
r in
take
con
nect
ion.
Thi
s da
mpe
r w
ill c
lose
dur
ing
a fr
ost c
ontr
ol c
ycle
or
whe
n th
e un
it is
pla
ced
in th
e 'O
FF
' pos
ition
with
pow
er m
aint
aine
d to
the
unit.
Thi
s da
mpe
r is
not
des
igne
d as
a b
ackd
raft
dam
per
and
will
rem
ain
open
if p
ower
is d
isco
nnec
ted
from
the
unit
for
any
reas
on.
A
FR
ON
T V
IEW
RIG
HT
SID
E V
IEW
BC
ON
DE
NS
AT
E D
RA
IN
A
Appendix B
Unit Dimensions
B-1: 600 cfm (without recirculation module)
- 10 -
28.1
20"
[714
]
14.0
00"
[356
]
4.00
0" [1
02]
1.75
0"[4
4]
8.00
0"[2
03]
2.75
0"[7
0]
19.2
07"
[488
]5.
125"
130]
AC
CE
SS
DO
OR
ST
RA
P M
OU
NT
ING
LOC
AT
ION
NO
TE
:F
or u
nits
with
the
reve
rsed
doo
r op
tion,
inte
rior
com
pone
nts
will
app
ear
as a
mirr
or im
age
of th
e ab
ove
diag
ram
.
49.5
50"
[1,2
59]
LIN
E V
OLT
AG
E IN
CO
NT
RO
L B
OX
DR
Y C
ON
TAC
TS
RE
VE
RS
ED
DO
OR
OP
TIO
N
FR
ES
H A
IRT
O B
UIL
DIN
G
EX
HA
US
T A
IRT
O O
UT
SID
E
8.00
0"[2
03]
4.00
0"[1
02]
24.5
00"
[622
]
3.53
0"[9
0]
12.0
00"
[305
]15
.000
"[3
81]
AC
CE
SS
DO
OR
HE
AT
RE
CO
VE
RY
CO
RE
RE
VE
RS
ED
DO
OR
OP
TIO
N
CO
NT
RO
L P
AN
EL
NO
TE
: A
min
imum
of 1
2.00
0" [3
05] c
lear
ance
from
any
obs
truc
tion
is r
equi
red
for
rem
oval
of t
he c
ontr
ol b
ox.
NO
TE
: A
min
imum
of 1
5.00
0" [3
81] c
lear
ance
from
any
obs
truc
tion
is r
equi
red
for
rem
oval
of
hea
t rec
over
y co
res,
fans
, etc
.T
he a
cces
s do
or c
an b
e re
mov
ed fr
om c
abin
et w
ith o
nly
2.00
0" [5
1] o
f cle
aran
ce.
8.00
0"[2
03]
8.00
0"[2
03]
14.1
00"
[358
]
14.0
00"
[356
]7.
100"
[180
]
FR
ES
H A
IRF
RO
M O
UT
SID
E
EX
HA
US
T A
IRF
RO
M B
UIL
DIN
G
4.00
0"[1
02]
1.75
0"[4
4]
NO
TE
: D
imen
sion
s in
[ ]
are
mill
imet
ers
HR
V60
0i P
OLY
CO
RE
with
rec
ircul
atio
n m
odul
eH
RV
600i
ALU
MIN
UM
CO
RE
with
rec
ircul
atio
n m
odul
e
197
LBS
(90
kg)
231
LBS
(10
5 kg
)
LEF
T S
IDE
VIE
W
FR
ON
T V
IEW
RIG
HT
SID
E V
IEW
FR
ON
T V
IEW
RIG
HT
SID
E V
IEW
For
Rec
irc D
efro
st O
nly
34.0
00"
[864
]
OU
TD
OO
R A
IR
RE
TU
RN
AIR
EX
HA
US
T A
IR
SU
PP
LY A
IR
Line
vol
tage
in14
gau
ge w
ire n
utC
onde
nsat
e dr
ain
fittin
g (2
x)A B
3/4"
mpt
CO
NN
EC
TIO
N T
AB
LE CO
NN
EC
TIO
N S
IZE
S
CO
ND
EN
SA
TE
DR
AIN
B
A
Appendix B Continued
Unit Dimensions
B-2: 600 cfm with recirculation module
- 11 -
41.2
06"
[1,0
47]
40.3
26"
[1,0
24]
20.0
00"
[508
]
5.71
5"[1
45]
20.6
20"
[524
]
14.2
50"
[362
]
34.0
00"
[864
]
5.12
5"[1
30]
19.2
07"
[488
]
4.02
8"[1
02]
11.3
25"
[288
]
12.0
00"
[305
]15
.000
"[3
81]
20.0
00"
[508
]
4.00
0"[1
02]
2.75
0"[7
0]
11.0
00"
[279
]20
.000
"[5
08]
9.87
8"[2
51]
24.5
00"
[622
]
8.00
0"[2
03]
8.00
0"[2
03]
4.00
0"[1
02]
8.00
0"[2
03]
10.0
00"
[254
]
FR
ES
H A
IRT
O B
UIL
DIN
G
EX
HA
US
T A
IRT
O O
UT
SID
E
LIN
E V
OLT
AG
E IN
LOW
VO
LTA
GE
TE
RM
INA
L S
TR
IPS
CO
NT
RO
L B
OX
AC
CE
SS
CO
NT
RO
L C
OV
ER
AC
CE
SS
DO
OR
HE
AT
RE
CO
VE
RY
CO
RE
RE
VE
RS
ED
DO
OR
OP
TIO
N
AC
CE
SS
DO
OR
EX
HA
US
T A
IRF
RO
M B
UIL
DIN
G
FR
ES
H A
IRF
RO
M O
UT
SID
E
ST
RA
P M
OU
NT
LOC
AT
ION
RE
VE
RS
ED
DO
OR
OP
TIO
N
CDB
A
TO
P V
IEW
OU
TD
OO
R A
IR
RE
TU
RN
AIR
NO
TE
: F
or u
nits
with
the
reve
rsed
doo
r op
tion,
inte
rior
com
pone
nts
will
app
ear
as a
mirr
or im
age
of th
e ab
ove
diag
ram
.
NO
TE
: A m
inim
um o
f 12.
000"
[305
] cle
aran
ce fr
om a
ny o
bstr
uctio
nis
req
uire
d fo
r re
mov
al o
f the
con
trol
box
.N
OT
E: A
min
imum
of 1
5.00
0" [3
81] c
lear
ance
from
any
obs
truc
tion
is r
equi
red
for
rem
oval
of h
eat r
ecov
ery
core
s, fa
ns, e
tc.
The
acc
ess
door
can
be
rem
oved
from
the
cabi
net w
ith o
nly
2.00
0" [5
1] o
f cle
aran
ce.
EX
HA
US
T A
IR
SU
PP
LY A
IR
LEF
T S
IDE
VIE
W
Dim
ensi
ons
in [
] ar
e m
illim
eter
sC
ente
r of
gra
vity
Dire
ctio
n of
airf
low
NO
TE
S:
PT
SH
RV
1200
i PO
LY C
OR
EH
RV
1200
i ALU
MIN
UM
CO
RE
LBS
54.0
238
.98
54.0
238
.98
186.
00
Kg
24.5
017
.68
24.5
017
.68
84.3
6
PT
SA B C D
TO
TAL
LBS
60.4
143
.59
60.4
143
.59
208.
00
27.4
019
.77
27.4
019
.77
94.3
4
Kg
A B C
TO
TAL
D
Line
vol
tage
in14
gau
ge w
ire n
utC
onde
nsat
e dr
ain
fittin
g (2
x)
A B3/
4" m
pt
CO
NN
EC
TIO
N T
AB
LE
CO
NN
EC
TIO
N S
IZE
S
NO
TE
: T
his
mod
el h
as a
dam
per
loca
ted
on th
e ou
tdoo
r in
take
con
nect
ion.
Thi
s da
mpe
r w
ill c
lose
dur
ing
a fr
ost c
ontr
ol c
ycle
or
whe
n th
e un
it is
pla
ced
in th
e 'O
FF
' pos
ition
with
pow
er m
aint
aine
d to
the
unit.
Thi
s da
mpe
r is
not
des
igne
d as
a b
ackd
raft
dam
per
and
will
rem
ain
open
if p
ower
is d
isco
nnec
ted
from
the
unit
for
any
reas
on.
FR
ON
T V
IEW
FR
ON
T V
IEW
RIG
HT
SID
E V
IEWR
IGH
T S
IDE
VIE
W
CO
ND
EN
SA
TE
DR
AIN
B
A
Appendix B Continued
Unit Dimensions
B-3: 1150 cfm (without recirculation module)
- 12 -
8.00
0"[2
03]
1.75
0"[4
4]
10.0
00"
[254
]20
.000
"[5
08]
2.75
0"[7
0] LIN
E V
OLT
AG
E IN
DR
Y C
ON
TAC
TS
49.5
50"
[1,2
59]
ST
RA
P M
OU
NT
ING
LOC
AT
ION
FR
ES
H A
IRF
RO
M O
UT
SID
E
EX
HA
US
T A
IRF
RO
M B
UIL
DIN
G
5.12
5"[1
30]
HE
AT
RE
CO
VE
RY
CO
RE
RE
VE
RS
ED
DO
OR
OP
TIO
N
AC
CE
SS
DO
OR
15.0
00"
[381
]12
.000
"[3
05]
CO
NT
RO
L C
OV
ER
AC
CE
SS
DO
OR
20.0
00"
[508
]
20.0
00"
[508
]
10.0
00"
[254
]
19.2
07"
[488
]C
ON
TR
OL
BO
X
NO
TE
:F
or u
nits
with
the
reve
rsed
doo
r op
tion,
inte
rior
com
pone
nts
will
app
ear
as a
mirr
or im
age
of th
e ab
ove
diag
ram
.
NO
TE
: A m
inim
um o
f 12.
000"
[305
] cle
aran
ce fr
om a
ny o
bstr
uctio
nis
req
uire
d fo
r re
mov
al o
f the
con
trol
box
.N
OT
E: A
min
imum
of 1
5.00
0" [3
81] c
lear
ance
from
any
obs
truc
tion
is r
equi
red
for
rem
oval
of h
eat r
ecov
ery
core
s, fa
ns, e
tc.
The
acc
ess
door
can
be
rem
oved
from
cab
inet
with
onl
y 2.
000"
[51]
of c
lear
ance
.
RE
VE
RS
ED
DO
OR
OP
TIO
N
EX
HA
US
T A
IRT
O O
UT
SID
E
FR
ES
H A
IRT
O B
UIL
DIN
G
41.2
40"
[1,0
47]
24.5
00"
[622
]
8.00
0"[2
03]
4.00
0"[1
02]
3.53
0"[9
0]
8.00
0"[2
03]
8.00
0"[2
03]
4.00
0"[1
02]
1.75
0"[4
4]
NO
TE
: D
imen
sion
s in
[ ]
are
mill
imet
ers
HR
V12
00i P
OLY
CO
RE
with
rec
ircul
atio
n m
odul
eH
RV
1200
i ALU
MIN
UM
CO
RE
with
rec
ircul
atio
n m
odul
e
247
LBS
(11
2 kg
)26
9 LB
S (
122
kg)
LEF
T S
IDE
VIE
WF
RO
NT
VIE
W
FR
ON
T V
IEW
RIG
HT
SID
E V
IEW
RIG
HT
SID
E V
IEW
Line
vol
tage
in14
gau
ge w
ire n
utC
onde
nsat
e dr
ain
fittin
g (2
x)B
3/4"
mpt
CO
NN
EC
TIO
N T
AB
LEC
ON
NE
CT
ION
SIZ
ES
A
For
Rec
irc D
efro
st O
nly
CO
ND
EN
SA
TE
DR
AIN
B
A
Appendix B Continued
Unit Dimensions
B-4: 1150 cfm with recirculation module
- 13 -
10.0
00"
[254
]
Cen
ter
of g
ravi
ty
Dire
ctio
n of
airf
low
HR
V70
0iLB
SK
g32
.74
14.8
568
.46
31.0
535
.20
15.9
773
.60
33.3
821
0.00
1.87
5"[4
8]
EX
HA
US
TA
IRO
PE
NIN
G
SU
PP
LYA
IRO
PE
NIN
G
20.7
50"
[527
]
8.00
0"[2
03]
10.7
50"
[273
]
7.50
0" [1
91]
10.6
05"
[269
]
12.1
04"
[307
]
2.15
7"[5
5]
2.00
0"[5
1]
37.0
00"
[940
]
24.7
36"
[628
]
31.0
80"
[789
]51
.000
"[1
,295
]
21.0
00"
[533
]
HE
AT
RE
CO
VE
RY
CO
RE
AC
CE
SS
DO
OR
47.0
00"
[1,1
94]
8.00
0"[2
03]
DE
FR
OS
T A
IRO
PE
NIN
G
EX
HA
US
TA
IRO
UT
DO
OR
AIR
OU
TD
OO
RA
IRO
PE
NIN
G
RE
TU
RN
AIR
OP
EN
ING
RE
TU
RN
AIR
SU
PP
LYA
IR
3.62
5"[9
2]2.
000"
[51]
14.0
00"
[356
]
1.87
5"[4
8]3.
750"
[95]
40.5
00"
[1,0
29]
8.00
0"[2
03]
12.2
50"
[311
]
8.00
0"[2
03]
15.2
50"
[387
]
2.00
0"[5
1]
LIN
E V
OLT
AG
E IN
NO
TE
: A m
inim
um o
f 12.
000"
[305
] cle
aran
ce fr
om a
ny o
bstr
uctio
n is
re
quire
d fo
r po
wer
hoo
k-up
, low
vol
tage
rem
ote
conn
ectio
n an
d co
ntro
l pan
el a
cces
s.
NO
TE
: A m
inim
um o
f 21.
000"
[533
] cle
aran
ce fr
om a
ny o
bstr
uctio
nis
req
uire
d fo
r re
mov
al o
f hea
t rec
over
y co
res,
fans
and
con
trol
box
acc
ess.
The
acc
ess
door
can
be
rem
oved
from
cab
inet
with
onl
y 2.
000"
[51]
of c
lear
ance
.
LOW
VO
LTA
GE
TE
RM
INA
L S
TR
IPS
8.00
0"[2
03]
A B C DT
OTA
L95
.25
22.5
00"
[572
]
AB
CD
TO
P V
IEW
Dim
ensi
ons
in [
] ar
e m
illim
eter
sN
OT
ES
:
PT
S Line
vol
tage
in14
gau
ge w
ire n
ut
Con
dens
ate
drai
n fit
ting
(2x)
A B3/
4" m
pt
CO
NN
EC
TIO
N T
AB
LE CO
NN
EC
TIO
N S
IZE
S
LEF
T S
IDE
VIE
WF
RO
NT
VIE
WR
IGH
T S
IDE
VIE
W
RIG
HT
SID
E V
IEW
CO
ND
EN
SA
TE
DR
AIN
B
A
Appendix B Continued
Unit Dimensions
B-5: 700 cfm
- 14 -
Flow Measuring Station (FMS)
Balancing Damper
Canvas Vibration Isolator
Min. 12"[305mm]
Min. 30"[762mm]
Reverse Door Option
Exhaust AirFrom Building
Fresh Air From Outside
Min. 8" [203mm]
(Optional) Canvas Vibration Isolator
Min. 12"[305mm]
Min.12"[304mm]
Flow MeasuringStation (FMS)
Balancing Damper(not supplied)
Canvas Vibration Isolator
Dry Contacts
Min. 12"[304mm]
Min. 30"[762mm]
700 cfm
Appendix C
Flow Station Positions
600 cfm and 1150 cfm
- 15 -
Min. 3"[76mm]
Min. 1"[25mm]
3/4" NPTCoupler
Water Trap
Plastic HoseTo Drain
NOTE: All hose, pipe and couplers to be supplied by others.
Min. 1"[25mm]
Min. 3"[76mm]
Plastic Drain Fitting
To Drain
Copper orPlastic Pipe
Min. 3"
[76mm]
Min. 1"
[25mm]
3/4" NPT
Coupler
Water Trap
Plastic HoseTo Drain
NOTE: All hose, pipe and couplers to be supplied by others.
Min. 1"
[25mm]
Min. 3"
[76mm]
Plastic Drain Fitting
To Drain
Copper or
Plastic Pipe
700 cfm
Appendix D
Drain Connections
600 cfm and 1150 cfm
- 16 -
WALL CONTROL
CLASS 2 VOLTAGE
Black
OCCUPIEDTIMER/SENSOR
F
F
LOW
COMMON
HIGH
Red
Green
Yellow
NOTE: Connections are all dry contacts except wall control and 24VAC power supply.
Use of 24VAC circuit requires isolating contacts (ex. thermostat) to preventinterconnection of Class 2 outputs.
WallControl
JUM
PE
R
WALL CONTROL
CLASS 2 VOLTAGE
Black
OCCUPIEDTIMER/SENSOR
F
F
LOW
COMMON
HIGH
Red
Green
Yellow
NOTE: Connections are all dry contacts except wall control and 24VAC power supply.
Use of 24VAC circuit requires isolating contacts (ex. thermostat) to preventinterconnection of Class 2 outputs.
A low voltage remote control wiring interface is
provided on the unit. The connections for the low voltage
remote wiring are located on two terminals adjacent to
the exhaust fan outlet (or adjacent to the supply fan out-
let on the 700 cfm unit). All field installed wiring must be
low voltage class II.
Remote Wall Control
Optional wall control requires a 4-wire LVT 24 gauge
(or equivalent). This remote wall control runs on 12 VDC.
Low Voltage Controls
All other terminals are dry contacts.
Low voltage terminal control consists of the following:
Wall Control
4-wire LVT 24 gauge minimum.
Occupied (Night Setback) Timer/Sensor
24 VAC, needs dry contact.
LOW - COM - HIGH
Remote fan switching requires a single pole, double
throw switch (SPDT).
Fan Interlock switch (FF)
Dry contact closes on ventilation or frost control. Used
to control external fan source (G).
Three types of remote wall controls are available:
1. Standard Wall Control with fan switch and dehu-
midistat control.
2. Xtra Wall Control with fan mode selection, dehu-
midistat control and maintenance indicator.
3. AquaAir Wall Control with fan mode selection,
dehumidistat control and high speed recirculation
mode.
The remote wall controls work with the integrated elec-
tronic controls within the unit to control ventilation
sequences. Each wall control has different features and
requires 4-wire connection to the unit as shown below.
Without the wall control, fans can be operated with a
remote fan switch as shown in Appendix E-4.
NOTE: An occupied timer or sensor device cannot be
used with the Xtra wall control.
Appendix E
Terminal Control Diagrams
E-1: Terminal Label E-2: Wall Control Connection
- 17 -
JUMPER(factory installed)
OCC. CONTROL(field installed)NSB Timer
1
M
2 3 4 5
JUM
PE
R
WALL CONTROL
CLASS 2 VOLTAGE
Black
OCCUPIEDTIMER/SENSOR
F
F
LOW
COMMON
HIGH
Red
Green
Yellow
NOTE: Connections are all dry contacts except wall control and 24VAC power supply.
Use of 24VAC circuit requires isolating contacts (ex. thermostat) to preventinterconnection of Class 2 outputs.
WALL CONTROL
CLASS 2 VOLTAGE
Black
OCCUPIEDTIMER/SENSOR
24 (-) VAC
24 (+) VAC
F
F
LOW
COMMON
HIGH
Red
Green
Yellow
NOTE: Connections are all dry contacts except wall control and 24VAC power supply.
Use of 24VAC circuit requires isolating contacts (ex. thermostat) to preventinterconnection of Class 2 outputs.
JUM
PE
R
REMOTE FAN SWITCH
LOW HIGH
WALL CONTROL
CLASS 2 VOLTAGE
Black
OCCUPIEDTIMER/SENSOR
F
F
LOW
COMMON
HIGH
Red
Green
Yellow
NOTE: Connections are all dry contacts except wall control and 24VAC power supply.
Use of 24VAC circuit requires isolating contacts (ex. thermostat) to preventinterconnection of Class 2 outputs.
Occupancy control is achieved by connection to the
terminal interface shown below. These terminals require
a dry contact which could be provided by a number of
types of controls such as a timer, light sensor, occupancy
sensor, building management system or other. The unit
will not operate unless these contacts are closed!!
The illustration below shows a factory installed jumper
and programmable timer option.
NOTE: An occupied timer or sensor device cannot be
used with the Xtra wall control.
Remote fan control can be achieved by connecting dry
contact controls to the terminal interface at terminals
labeled: LOW - COM - HIGH. These controls could be
the following: SPDT switch, dehumidistat, CO2 sensor,
light sensor, timer, building management system, etc.
The illustration below represents a switch connected to
the unit.
Appendix E Continued
Terminal Control Diagrams
E-3: Occupied Timer/Sensor Connection E-4: Remote Fan Control
- 18 -
Control cover plate
Control box
Remote control access plateRemote wiring terminal block
HRV Cabinet
NOTE: Autotransformers (if equipped) are mounted on the back of the control box.
FU10155A-600i8A-1200i
XF1015
1200i600i
855VAXF1015
415VA
PJ2003
PJ2014
PJ1007
PJ1001A
UCB1021
CR1029
CR1023
1
2
3
4
5
6
A
B
CO
M
NC
NO
PJ2
011
PJ1
001
CR
1024C
R1026
1
0
48
26
1
0
48
26
FILTRAN
NOTE: Low speed motor selection may be replaced by medium speed. To make this change, replace the low speed wires (red) on relay CR1024 with the medium speed wires (blue).
Low Speed Setting Wire Connections 600 cfm and 1150 cfm
Appendix F
Electrical Connection Diagrams
Control Box Assembly 600 cfm and 1150 cfm
- 19 -
Although t
he 6
00 c
fm,
700 c
fm a
nd 1
150 c
fm m
odels
have g
ood e
ffic
iencie
s,
the s
upply
air c
ould
be c
old
er
than t
he a
mbie
nt
room
air.
It
is p
ossib
le t
o e
limin
ate
the d
iscom
fort
associa
ted w
ith t
his
tem
pera
ture
diffe
rence b
y insta
lling a
n e
lectr
ic d
uct
heate
r. T
his
will
tem
per
the
air b
efo
re it
is d
istr
ibute
d t
hro
ughout
the b
uild
ing.
The t
able
belo
w g
ives t
he h
eating r
equirem
ents
at
diffe
rent
tem
pera
ture
s a
nd a
irflow
s.
OU
TD
OO
R A
IR -
40°F
[-4
0°C
]O
UT
DO
OR
AIR
-2
2°F
[-3
0°C
]O
UT
DO
OR
AIR
-4
°F [
-20
°C]
OU
TD
OO
R A
IR 1
4°F
[-1
0°C
]O
UT
DO
OR
AIR
32°F
[0°C
]
Desir
ed
Air
Tem
pera
ture
Desir
ed
Air
Tem
pera
ture
Desir
ed
Air
Tem
pera
ture
Desir
ed
Air
Tem
pera
ture
Desir
ed
Air
Tem
pera
ture
Supply
Air
Supply
Air
55°F
[13°C
]68°F
[20°C
]73°F
[23°C
]55°F
[13°C
]68°F
[20°C
]73°F
[23°C
]55°F
[13°C
]68°F
[20°C
]73°F
[23°C
]55°F
[13°C
]68°F
[20°C
]73°F
[23°C
]55°F
[13
°C]
68°F
[20°C
]73°F
[23°C
]
(cfm
)(L
/s)
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
1250
590
14.6
19.9
21.9
11.2
16.5
18.5
7.8
13.1
15.2
4.4
9.7
11
.81
.06
.38
.4
1200
566
13.5
18.6
20.6
10.4
15.5
17.4
7.2
12.3
14.3
4.0
9.1
11
.10
.85
.97
.9
1150
542
12.6
17.4
19.3
9.6
14.5
16.4
6.6
11.5
13.4
3.6
8.5
10
.40
.75
.57
.4
1100
675
11.2
15.9
17.7
8.5
13.2
15.0
5.8
10.5
12.3
3.1
7.7
9.6
0.4
5.0
6.8
1050
495
10.7
15.2
16.9
8.1
12.6
14.3
5.5
10.0
11.7
2.9
7.4
9.1
0.4
4.8
6.5
1000
472
9.9
14.1
15.7
7.4
11.7
13.3
5.0
9.3
10.9
2.6
6.9
8.5
0.2
4.4
6.1
900
425
8.5
12.4
13.8
6.4
10.2
11.7
4.3
8.1
9.6
2.2
6.0
7.5
0.1
3.9
5.4
800
377
7.0
10.4
11.7
5.2
8.6
9.9
3.4
6.8
8.2
1.7
5.0
6.4
-3
.34
.6
700
330
5.1
8.1
9.3
3.7
6.7
7.9
2.3
5.3
6.5
0.9
3.9
5.1
-2
.53
.7
NO
TE
: T
he d
ata
does n
ot re
flect a r
eduction in
effectiveness d
ue to fro
sting. B
ased o
n the s
tandard
air a
t: 1
.2 K
g/m
3 a
nd C
p =
1.0
KJ/K
g°C
13.3
5 lb/ft3
and C
p =
.24 B
tu/lbm
°F
Appendix G
Make-up Heat Requirements
1150 cfm600 cfm and 700 cfm
OU
TD
OO
R A
IR -
40°F
[-4
0°C
]O
UT
DO
OR
AIR
-2
2°F
[-3
0°C
]O
UT
DO
OR
AIR
-4
°F [
-20
°C]
OU
TD
OO
R A
IR 1
4°F
[-1
0°C
]O
UT
DO
OR
AIR
32°F
[0°C
]
Desir
ed
Air
Tem
pera
ture
Desir
ed
Air
Tem
pera
ture
Desir
ed
Air
Tem
pera
ture
Desir
ed
Air
Tem
pera
ture
Desir
ed
Air
Tem
pera
ture
Supply
Air
Supply
Air
55°F
[13°C
]68°F
[20°C
]73°F
[23°C
]55°F
[13°C
]68°F
[20°C
]73°F
[23°C
]55°F
[13°C
]68°F
[20°C
]73°F
[23°C
]55°F
[13°C
]68°F
[20°C
]73°F
[23°C
]55°F
[13
°C]
68°F
[20°C
]73°F
[23°C
]
(cfm
)(L
/s)
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
700
330
7.4
10.4
11.5
5.6
8.6
9.7
3.9
6.8
8.0
2.1
5.1
6.2
0.3
3.3
4.4
650
307
6.6
9.4
10.5
5.0
7.8
8.9
3.4
6.2
7.3
1.8
4.6
5.6
0.2
3.0
4.0
600
283
5.9
8.5
9.4
4.5
7.0
8.0
3.0
5.6
6.5
1.6
4.1
5.1
0.1
2.7
3.7
550
259
5.2
7.6
8.5
3.9
6.3
7.2
2.6
5.0
5.9
1.3
3.7
4.6
0.1
2.4
3.3
500
236
4.0
6.1
7.0
3.0
5.1
5.9
1.9
4.0
4.9
0.9
3.0
3.8
-1
.92
.7
450
212
3.0
4.9
5.6
2.1
4.0
4.8
1.3
3.2
3.9
0.4
2.3
3.1
-1
.52
.2
400
189
2.2
3.9
4.6
1.5
3.2
3.9
0.9
2.5
3.2
0.2
1.9
2.5
-1
.21
.8
600 a
nd
700
CF
M U
NIT
115
0
CF
M U
NIT
SYMPTOMS POSSIBLE CAUSES SOLUTIONS
Inside air is too dry. Over ventilation - speed setting Adjust speed setting.
too high.
Dehumidistat setting is too low. Set dehumidistat control in a
higher position (if applicable).
Persistent condensation on Improper adjustment of Adjust dehumidistat control knob
windows, walls, ceilings, etc. dehumidistat control. to a lower setting.
Improper ventilation rate. Install a dehumidistat (option).
Window frame is too cold or leaky. Repair window frame.
Unit stops functioning. Electrical supply interrupted. Check the unit circuit breaker.
Air from supply diffusers too cold. Imbalance of supply and exhaust air. Check filters and heat exchangers
for blockage.
Check balance of airflows.
Outdoor temperature very cold. Install electric duct heater if necessary.
Unit makes annoying noise. Blower wheel out of alignment. Remove the motor/blower assembly
and adjust blower wheel.
Heat exchanger freezing up. Imbalance of supply and exhaust air. Check filters and heat exchangers
for blockage.
Check balance of airflows.
Frost control damper not functioning. Check for operation of both
frost control damper actuators.
Low exhaust airflow in winter Heat exchanger flutes are positioned Remove flat plate heat exchanger
season. in the exhaust airstream. sections and re-position the flute side
of the heat exchanger into the supply
airstream.
Appendix H
Trouble Shooting
Venmar CES products are licensed to use
the following labels of approval: