installation and operation manual - klimasbt.com©khűtős_rendszerek/1... · installation and...
TRANSCRIPT
INSTALLATION ANDOPERATION MANUAL
EUWAN5KAZW1EUWAN8KAZW1EUWAN10KAZW1EUWAN12KAZW1EUWAN16KAZW1EUWAN20KAZW1EUWAN24KAZW1
EUWAP5KAZW1EUWAP8KAZW1EUWAP10KAZW1EUWAP12KAZW1EUWAP16KAZW1EUWAP20KAZW1EUWAP24KAZW1
EUWAB5KAZW1EUWAB8KAZW1EUWAB10KAZW1EUWAB12KAZW1EUWAB16KAZW1EUWAB20KAZW1EUWAB24KAZW1
Packaged air-cooled water chillers
1
1
25
23
16 15 28 277 12 16 266 5 10 16
94 1818 17 13 202913 + 14 113 138
2
24
19 8
2
2
4
7
2
9
8
3
11
12
6
1
5
10
3
3
B
A
C
12
Zan
dvoo
rdes
traa
t 300
, B-8
400
Oos
tend
e, B
elgi
um
Dai
kin
Eu
rop
e N
.V.
EN
6033
5-2-
40,
Low
Vol
tage
73/
23/E
EC
Mac
hine
ry S
afet
y 98
/37/
EE
CE
lect
rom
agne
tic C
ompa
tibili
ty 8
9/33
6/E
EC
*
Kat
suyu
ki S
awai
Ass
ista
nt D
irect
or Q
ualit
y A
ssur
ance
Ost
end,
3rd
of M
ay 2
004
CE -
DECL
ARAT
ION-
OF-C
ONFO
RMIT
YCE
- KO
NFOR
MIT
ÄTSE
RKLÄ
RUNG
CE -
DECL
ARAT
ION-
DE-C
ONFO
RMIT
ECE
- CO
NFOR
MIT
EITS
VERK
LARI
NG
CE -
DECL
ARAC
ION-
DE-C
ONFO
RMID
ADCE
- DI
CHIA
RAZI
ONE-
DI-C
ONFO
RMIT
A
CE -
¢H§ø
™H ™
YMM
OPºø
™H™
CE -
DECL
ARAÇ
ÃO-D
E-CO
NFOR
MID
ADE
СЕ -
ЗАЯВ
ЛЕНИ
Е-О
-СО
ОТВ
ЕТСТ
ВИИ
CE -
OPFY
LDEL
SESE
RKLÆ
RING
CE -
FÖRS
ÄKRA
N-OM
-ÖVE
RENS
TÄMM
ELSE
CE -
ERKL
ÆRI
NG O
M-S
AMSV
ARCE
- IL
MOI
TUS-
YHDE
NMUK
AISU
UDES
TACE
-
PRO
HLÁŠ
ENÍ-O
-SHO
DĚ
CE -
IZJA
VA-O
-USK
LAĐE
NOST
ICE
- M
EGFE
LELŐ
SÉG
I-NYI
LATK
OZA
T
CE -
DEKL
ARAC
JA-Z
GO
DNO
ŚCI
CE -
DECL
ARAŢ
IE-D
E-CO
NFO
RMIT
ATE
CE -
I
ZJAV
A O
SKL
ADNO
STI
CE -
VAST
AVUS
DEKL
ARAT
SIO
ON
CE -
ДЕКЛ
АРАЦ
ИЯ-З
А-СЪ
ОТВЕ
ТСТВ
ИЕ
CE -
ATIT
IKTI
ES-D
EKLA
RACI
JA
CE -
ATBI
LSTĪ
BAS-
DEKL
ARĀC
IJA
CE -
VYHL
ÁSEN
IE-Z
HODY
CE -
UYUM
LULU
K-Bİ
LDİR
İSİ
01
d
eclar
es u
nder
its so
le re
spon
sibilit
y tha
t the
air
cond
itionin
g m
odels
to w
hich
this
decla
ratio
n re
lates
:
02
e
rklär
t auf
seine
alle
inige
Ver
antw
ortu
ng d
aß d
ie M
odell
e de
r Klim
ager
äte
für d
ie die
se E
rklär
ung
besti
mm
t ist:
03
d
éclar
e so
us sa
seule
resp
onsa
bilité
que
les a
ppar
eils d
'air c
ondit
ionné
visé
s par
la p
rése
nte
décla
ratio
n:
04
ve
rklaa
rt hie
rbij o
p eig
en e
xclus
ieve
vera
ntwo
orde
lijkhe
id da
t de
airco
nditio
ning
units
waa
rop
deze
verk
laring
bet
rekk
ing h
eeft:
05
d
eclar
a ba
ja su
únic
a re
spon
sabil
idad
que
los m
odelo
s de
aire
acon
dicion
ado
a los
cuale
s hac
e re
fere
ncia
la de
clara
ción:
06
d
ichiar
a so
tto su
a re
spon
sabil
ità ch
e i c
ondiz
ionat
ori m
odell
o a
cui è
rifer
ita q
uesta
dich
iaraz
ione:
07
‰ËÏÒ
ÓÂÈ Ì
 ·
ÔÎÏÂ
ÈÛÙÈ΋
Ù˘
¢ı
‡ÓË
fiÙÈ Ù
· ÌÔ
ÓÙ¤Ï
· Ùˆ
Ó ÎÏ
ÈÌ·Ù
ÈÛÙÈÎÒ
Ó Û˘
Û΢
ÒÓ
ÛÙ·
ÔÔ›·
·Ó·Ê
¤ÚÂÙ
·È Ë
·Ú
Ô‡Û·
‰‹Ï
ˆÛË
:
08
d
eclar
a so
b su
a ex
clusiv
a re
spon
sabil
idade
que
os m
odelo
s de
ar co
ndici
onad
o a
que
esta
dec
laraç
ão se
refer
e:
09
заяв
ляет
, иск
лючи
тель
но по
д сво
ю от
ветс
твен
ност
ь, чт
о мод
ели к
онди
цион
еров
возд
уха,
к кот
орым
отно
ситс
я нас
тоящ
ее за
явле
ние:
10
e
rklæ
rer u
nder
ene
ansv
ar, a
t klim
aanlæ
gmod
eller
ne, s
om d
enne
dek
larat
ion ve
drør
er:
11
d
eklar
erar
i ege
nska
p av
huv
udan
svar
ig, a
tt luf
tkond
itione
rings
mod
eller
na so
m b
erör
s av d
enna
dek
larat
ion in
nebä
r att:
12
e
rklæ
rer e
t full
stend
ig an
svar
for a
t de
luftko
ndisj
oner
ingsm
odell
er so
m b
erør
es av
den
ne d
eklar
asjon
inne
bære
r at:
13
ilm
oitta
a yk
sinom
aan
omall
a va
stuull
aan,
että
täm
än ilm
oituk
sen
tark
oitta
mat
ilmas
toint
ilaitte
iden
mall
it:
14
proh
lašuje
ve sv
é pln
é od
pově
dnos
ti, že
mod
ely kl
imat
izace
, k n
imž s
e to
to p
rohlá
šení
vzta
huje:
15
izjav
ljuje
pod
isklju
čivo
vlasti
tom
odg
ovor
nošć
u da
su m
odeli
klim
a ur
eđaja
na
koje
se o
va iz
java
odno
si:
16
telje
s fele
lőssé
ge tu
datá
ban
kijele
nti, h
ogy a
klím
aber
ende
zés m
odell
ek, m
elyek
re e
nyil
atko
zat v
onat
kozik
:
17
dekla
ruje
na w
łasną
i wyłą
czną
odp
owied
zialno
ść, ż
e m
odele
klim
atyz
ator
ów, k
tóry
ch d
otyc
zy n
iniejs
za d
eklar
acja:
18
decla
ră p
e pr
oprie
răsp
unde
re că
apa
rate
le de
aer
cond
iţiona
t la ca
re se
refe
ră a
ceas
tă d
eclar
aţie:
19
z vso
odg
ovor
nostj
o izj
avlja
, da
so m
odeli
klim
atsk
ih na
prav
, na
kate
re se
izjav
a na
naša
:
20
kinnit
ab o
ma
täiel
ikul v
astu
tuse
l, et k
äeso
leva
dekla
ratsi
ooni
alla
kuulu
vad
kliim
asea
dmet
e m
udeli
d:
21
декл
арир
а на
своя
отг
овор
ност
, че
моде
лите
кли
мати
чна
инст
алац
ия, з
а ко
ито
се о
тнас
я та
зи д
екла
раци
я:
22
visišk
a sa
vo a
tsako
myb
e sk
elbia,
kad
oro
kond
icion
avim
o pr
ietais
ų m
odeli
ai, ku
riem
s yra
taiko
ma
ši de
klara
cija:
23
ar p
ilnu
atbil
dību
apli
ecina
, ka
tālāk
uzs
kaitīt
o m
odeĮ
u ga
isa ko
ndici
onēt
āji, u
z kur
iem a
ttieca
s šī d
eklar
ācija
:
24
vyhla
suje
na vl
astn
ú zo
dpov
edno
sť, ž
e tie
to kl
imat
izačn
é m
odely
, na
ktoré
sa vz
ťahu
je to
to vy
hláse
nie:
25
ta
mam
en ke
ndi s
orum
luluğ
unda
olm
ak ü
zere
bu
bildir
inin
ilgili
olduğ
u kli
ma
mod
eller
inin
aşağ
ıdak
i gibi
oldu
ğunu
bey
an e
der:
01
are
in co
nform
ity w
ith th
e fo
llowi
ng s
tand
ard(
s) o
r oth
er n
orm
ative
doc
umen
t(s),
prov
ided
that
thes
e ar
e us
ed in
acc
orda
nce
with
our
instru
ction
s:
02
der/d
en fo
lgend
en N
orm
(en)
ode
r eine
m a
nder
en N
orm
doku
men
t ode
r -do
kum
ente
n en
tspric
ht/e
ntsp
rech
en, u
nter
der
Vor
auss
etzu
ng,
daß
sie g
emäß
uns
eren
Anw
eisun
gen
einge
setzt
wer
den:
03
sont
confo
rmes
à la/
aux n
orm
e(s)
ou au
tre(s
) doc
umen
t(s) n
orm
atif(
s), p
our a
utan
t qu'i
ls so
ient u
tilisé
s con
form
émen
t à no
s ins
tructi
ons:
04
confo
rm de
volge
nde n
orm
(en)
of éé
n of m
eer a
nder
e bind
ende
docu
men
ten z
ijn, o
p voo
rwaa
rde d
at ze
wor
den g
ebru
ikt ov
eree
nkom
stig
onze
instr
uctie
s:
05
está
n en
conf
orm
idad
con
la(s)
sigu
iente
(s) n
orm
a(s)
u o
tro(s
) doc
umen
to(s
) nor
mat
ivo(s
), sie
mpr
e qu
e se
an u
tiliza
dos d
e ac
uerd
o co
nnu
estra
s ins
trucc
iones
:
06
sono
con
form
i al(i)
seg
uent
e(i)
stand
ard(
s) o
altr
o(i)
docu
men
to(i)
a c
arat
tere
nor
mat
ivo, a
pat
to c
he v
enga
no u
sati
in co
nfor
mità
alle
nostr
e ist
ruzio
ni:
07
›ӷ
È Û‡
Ìʈӷ
ÌÂ
ÙÔ(·
) ·Î
fiÏÔ˘
ıÔ(·
) Ú
fiÙ˘
Ô(·)
‹ ¿
ÏÏÔ
¤ÁÁÚ
·ÊÔ(
·) Î
·ÓÔÓ
ÈÛÌÒ
Ó, ˘
fi Ù
ËÓ
ÚÔ¸
fiıÂÛ
Ë fiÙ
È ¯Ú
ËÛÈÌÔ
ÔÈÔ‡
ÓÙ·È
Û‡ÌÊ
ˆÓ·
ÌÂ
ÙȘ
Ô‰ËÁ
›Â˜
Ì·˜:
08
estã
o em
con
form
idade
com
a(s
) seg
uinte
(s) n
orm
a(s)
ou
outro
(s) d
ocum
ento
(s) n
orm
ativo
(s),
desd
e qu
e es
tes
sejam
utili
zado
s de
acor
do co
m a
s nos
sas i
nstru
ções
:
09
соот
ветс
твую
т сл
едую
щим
стан
дарт
ам и
ли д
руги
м но
рмат
ивны
м до
куме
нтам
, при
усл
овии
их
испо
льзо
вани
я со
глас
но н
ашим
инст
рукц
иям:
10
over
holde
r fø
lgend
e sta
ndar
d(er
) ell
er a
ndet
/and
re r
etnin
gsgiv
ende
dok
umen
t(er),
for
udsa
t at
diss
e an
vend
es i
henh
old t
il vo
reins
truks
er:
11
resp
ektiv
e ut
rustn
ing ä
r utfö
rd i
över
enss
täm
mels
e m
ed o
ch fö
ljer f
öljan
de s
tand
ard(
er) e
ller a
ndra
nor
mgiv
ande
dok
umen
t, un
der
föru
tsättn
ing a
tt an
vänd
ning
sker
i öve
rens
stäm
mels
e m
ed vå
ra in
struk
tione
r:
12
resp
ektiv
e ut
styr e
r i o
vere
nsste
mm
else
med
følge
nde
stand
ard(
er) e
ller a
ndre
nor
mgiv
ende
dok
umen
t(er),
und
er fo
rutss
etnin
g av
at
disse
bru
kes i
hen
hold
til vå
re in
struk
ser:
13
vasta
avat
seu
raav
ien s
tand
ardie
n ja
muid
en o
hjeell
isten
dok
umen
ttien
vaat
imuk
sia e
delly
ttäen
, et
tä n
iitä k
äyte
tään
ohje
idem
me
muk
aises
ti:
14
za p
ředp
oklad
u, že
jsou
využ
ívány
v so
uladu
s na
šimi p
okyn
y, o
dpov
ídají
nás
ledují
cím n
orm
ám n
ebo
norm
ativn
ím d
okum
entů
m:
15
u sk
ladu
sa sl
ijede
ćim st
anda
rdom
(ima)
ili d
rugim
nor
mat
ivnim
dok
umen
tom
(ima)
, uz u
vjet d
a se
oni
koris
te u
sklad
u s n
ašim
upu
tam
a:
16
meg
felel
nek a
z aláb
bi sz
abvá
ny(o
k)na
k vag
y egy
éb ir
ánya
dó d
okum
entu
m(o
k)na
k, ha
azo
kat e
lőírá
s sze
rint h
aszn
álják
:
17
spełn
iają
wym
ogi n
astę
pując
ych
norm
i inn
ych
doku
men
tów
norm
aliza
cyjny
ch, p
od w
arun
kiem
że
używ
ane
są z
godn
ie z
nasz
ymi
instru
kcjam
i:
18
sunt
în co
nfor
mita
te cu
urm
ător
ul (u
rmăt
oare
le) st
anda
rd(e
) sau
alt(
e) d
ocum
ent(e
) nor
mat
iv(e)
, cu
cond
iţia ca
ace
stea
să fie
utili
zate
înco
nfor
mita
te cu
instr
ucţiu
nile
noas
tre
19
sklad
ni z n
asled
njim
i sta
ndar
di in
drug
imi n
orm
ativi
, pod
pog
ojem
, da
se u
pora
bljajo
v sk
ladu
z naš
imi n
avod
ili:
20
on va
stavu
ses j
ärgm
is(t)e
stan
dard
i(te)
ga võ
i teist
e no
rmat
iivse
te d
okum
entid
ega,
kui n
eid ka
suta
taks
e va
stava
lt meie
juhe
ndite
le:
21
съот
ветс
тват
на
след
ните
ста
ндар
ти и
ли д
руги
нор
мати
вни
доку
мент
и, п
ри у
слов
ие,
че с
е из
полз
ват
съгл
асно
наш
ите
инст
рукц
ии:
22
atitin
ka že
miau
nur
odytu
s sta
ndar
tus i
r (ar
ba) k
itus n
orm
inius
dok
umen
tus s
u są
lyga,
kad
yra
naud
ojam
i pag
al m
ūsų
nuro
dym
us:
23
tad,
ja lie
toti a
tbils
toši
ražo
tāja
norā
dījum
iem, a
tbils
t sek
ojošie
m st
anda
rtiem
un
citiem
nor
mat
īviem
dok
umen
tiem
:
24
sú v
zhod
e s n
asled
ovno
u(ým
i) no
rmou
(am
i) ale
bo in
ým(i)
nor
mat
ívnym
(i) d
okum
ento
m(a
mi),
za p
redp
oklad
u, že
sa p
oužív
ajú v
súlad
es n
ašim
náv
odom
:
25
ürün
ün, t
alim
atlar
ımıza
gör
e ku
llanı
lmas
ı koş
uluyla
aşa
ğıda
ki sta
ndar
tlar v
e no
rm b
elirte
n be
lgeler
le uy
umlud
ur:
01
Dire
ctive
s, as
am
ende
d.
02
Dire
ktive
n, g
emäß
Änd
erun
g.
03
Dire
ctive
s, te
lles q
ue m
odifié
es.
04
Rich
tlijne
n, zo
als g
eam
ende
erd.
05
Dire
ctiva
s, se
gún
lo en
men
dado
.
06
Dire
ttive,
com
e da
mod
ifica.
07
√‰Ë
ÁÈÒv, fi
ˆ˜
¤¯Ô˘
Ó ÙÚ
ÔÔ
ÔÈËı
›.
08
Dire
ctiva
s, co
nform
e alt
eraç
ão e
m.
09
Дире
ктив
со в
семи
поп
равк
ами.
10
Dire
ktive
r, m
ed se
nere
ænd
ringe
r.
11
Dire
ktiv,
med
före
tagn
a än
dring
ar.
12
Dire
ktive
r, m
ed fo
reta
tte e
ndrin
ger.
13
Direk
tiivejä
, sell
aisina
kuin
ne ov
at mu
utettu
ina.
14
v plat
ném
zněn
í.
15
Smjer
nice,
kako
je iz
mije
njeno
.
16
irány
elv(e
k) és
mód
osítá
saik
rend
elkez
éseit
.
17
z póź
niejsz
ymi p
opra
wkam
i.
18
Dire
ctive
lor, c
u am
enda
men
tele
resp
ectiv
e.
19
Dire
ktive
z vs
emi s
prem
emba
mi.
20
Dire
ktiivi
d ko
os m
uuda
tuste
ga.
21
Дире
ктив
и, с
техн
ите
изме
нени
я.
22
Dire
ktyvo
se su
pap
ildym
ais.
23
Dire
ktīvā
s un
to p
apild
inājum
os.
24
Smer
nice,
v pla
tnom
znen
í.
25
Değiş
tirilm
iş ha
lleriy
le Yö
netm
elikle
r.
01
follow
ing th
e pr
ovisi
ons o
f:
02
gem
äß d
en V
orsc
hrifte
n de
r:
03
confo
rmém
ent a
ux st
ipulat
ions d
es:
04
over
eenk
omsti
g de
bep
aling
en va
n:
05
siguie
ndo
las d
ispos
icion
es d
e:
06
seco
ndo
le pr
escr
izion
i per
:
07
ÌÂ Ù
‹ÚËÛ
Ë Ùˆ
v ‰È·Ù
¿Íˆ
v Ùˆ
v:
08
de a
cord
o co
m o
pre
visto
em
:
09
в со
отве
тств
ии с
поло
жени
ями:
10
unde
r iag
ttage
lse a
f bes
tem
mels
erne
i:
11
enlig
t villk
oren
i:
12
gitt i
henh
old til
bes
tem
mels
ene
i:
13
noud
atta
en m
äärä
yksiä
:
14
za d
održ
ení u
stano
vení
pře
dpisu
:
15
prem
a od
redb
ama:
16
köve
ti a(z
):
17
zgod
nie z
posta
nowi
eniam
i Dyr
ektyw
:
18
în u
rma
prev
eder
ilor:
19
ob u
pošte
vanju
dolo
čb:
20
vasta
valt n
õuet
ele:
21
след
вайк
и кл
аузи
те н
а:
22
laika
ntis
nuos
tatų
, pat
eikiam
ų:
23
ievēr
ojot p
rasīb
as, k
as n
oteik
tas:
24
održ
iavajú
c usta
nove
nia:
25
bunu
n ko
şulla
rına
uygu
n ola
rak:
01
Note
*
as se
t out
in the
Tech
nical
Cons
tructi
on Fi
le
Daiki
n.TCF
.012
and j
udge
d pos
itively
by
KEMA
acco
rding
to
the
Certi
ficate
6332
9-KRQ
/ECM
96-52
56
.
02
Hinw
eis *
wie i
n der
Tech
nisch
en K
onstr
uktio
nsak
te
Daiki
n.TCF
.012
aufge
führt
und v
on
KEMA
posit
iv au
sgez
eichn
et ge
mäß
Zerti
fikat
6332
9-KRQ
/ECM
96-52
56
.
03
Rema
rque
*
tel qu
e stip
ulé da
ns le
Fich
ier de
Con
struc
tion T
echn
ique
Daiki
n.TCF
.012
et ju
gé po
sitive
ment
par
KEMA
confo
rmém
ent
au
Certi
ficat
6332
9-KRQ
/ECM
96-52
56
.
04
Beme
rk *
zoals
verm
eld in
het T
echn
isch C
onstr
uctie
doss
ier
Daiki
n.TCF
.012
en in
orde
bevo
nden
door
KEMA
overe
enko
mstig
Certi
ficaa
t 633
29-K
RQ/E
CM96
-5256
.
05
Nota
*
tal co
mo se
expo
ne en
el A
rchivo
de C
onstr
ucció
n Téc
nica
Daiki
n.TCF
.012
y juz
gado
posit
ivame
nte po
r
KEMA
segú
n el
Certi
ficad
o 633
29-K
RQ/E
CM96
-5256
.
06
Nota
*
delin
eato
nel F
ile Te
cnico
di C
ostru
zione
Daiki
n.TCF
.012
e giu
dicato
posit
ivame
nte da
KEMA
seco
ndo
il
Certi
ficato
6332
9-KRQ
/ECM
96-52
56
.
07
™ËÌÂ
›ˆÛË
*
fiˆ˜
ÚÔÛ
‰ÈÔÚ
›˙ÂÙ
·È Û
ÙÔ ∞
گ›Ô
∆¯Ó
È΋˜
∫·Ù
·ÛÎÂ
˘‹˜
Daiki
n.TCF
.012
Î·È Î
Ú›ÓÂ
Ù·È ı
ÂÙÈο
·fi
ÙÔ
KEMA
Û‡Ì
ʈӷ
ÌÂ
ÙÔ
¶ÈÛÙ
ÔÔÈË
ÙÈÎfi
6332
9-KRQ
/ECM
96-52
56
.
08
Nota
*
tal co
mo es
tabele
cido n
o Fich
eiro T
écnic
o de C
onstr
ução
Daiki
n.TCF
.012
e co
m o p
arece
r pos
itivo d
e
KEMA
de ac
ordo c
om o
Certi
ficad
o
6332
9-KRQ
/ECM
96-52
56
.
09
Прим
ечан
ие *
как у
каза
но в
Дось
е тех
ниче
ског
о тол
кова
ния
Daiki
n.TCF
.012
и в с
оотв
етст
вии с
поло
жите
льны
м ре
шени
ем
KEMA
со
глас
но
Свид
етел
ьств
у
6332
9-KRQ
/ECM
96-52
56
.
10
Bemæ
rk *
som
anfør
t i de
n Tek
niske
Kon
struk
tions
fil
Daiki
n.TCF
.012
og po
sitivt
vurde
ret af
KEMA
i hen
hold
til
Certi
fikat
6332
9-KRQ
/ECM
96-52
56
.
11
Infor
matio
n *
utrus
tning
en är
utför
d i en
lighe
t med
den T
eknis
ka K
onstr
uktio
nsfile
n
Daiki
n.TCF
.012
som
posit
ivt in
tygas
av
KEMA
vilke
t ock
så
framg
år av
Certi
fikat
6332
9-KRQ
/ECM
96-52
56
.
12
Merk
*
som
det fr
emko
mmer
i den
Tekn
iske K
onstr
uksjo
nsfile
n
Daiki
n.TCF
.012
og gj
enno
m po
sitiv
bedø
mmels
e av
KEMA
ifølge
Serti
fikat
6332
9-KRQ
/ECM
96-52
56
.
13
Huom
*
jotka
on es
itetty
Tekn
isess
ä Asia
kirjas
sa
Daiki
n.TCF
.012
ja jo
tka
KEMA
on hy
väks
ynyt
Serti
fikaa
tin
6332
9-KRQ
/ECM
96-52
56
muk
aises
ti.
14
Pozn
ámka
*
jak by
lo uv
eden
o v so
ubor
u tec
hnick
é kon
struk
ce
Daiki
n.TCF
.012
a po
zitivn
ě zjiš
těno
KEMA
v so
uladu
s
osvě
dčen
ím
6332
9-KRQ
/ECM
96-52
56
.
15
Napo
mena
*
kako
je iz
ložen
o u D
atotec
i o te
hničk
oj ko
nstru
kciji
Daiki
n.TCF
.012
i poz
itivno
ocije
njeno
od st
rane
KEMA
prem
a
Certi
fikatu
6332
9-KRQ
/ECM
96-52
56
.
16
Megje
gyzé
s *
a(z)
Daiki
n.TCF
.012
műs
zaki
kons
trukc
iós do
kume
ntáció
alap
ján, a
(z)
KEMA
igaz
olta a
meg
felelé
st a(
z)
6332
9-KRQ
/ECM
96-52
56
tanús
ítván
y
szer
int.
17
Uwag
a *
zgod
nie z
arch
iwaln
ą dok
umen
tacją
kons
trukc
yjną
Daiki
n.TCF
.012
, poz
ytywn
ą opin
ią
KEMA
i
Świad
ectw
em
6332
9-KRQ
/ECM
96-52
56
.
18
Notă
*
confo
rm ce
lor st
abilit
e în D
osar
ul teh
nic de
cons
trucţi
e
Daiki
n.TC
F.012
şi ap
recia
te po
zitiv
de
KEMA
în co
nform
itate
cu
Certi
ficat
ul
6332
9-KR
Q/EC
M96-
5256
.
19
Opom
ba *
kot je
določ
eno v
tehn
ični m
api
Daiki
n.TCF
.012
in od
obre
no s
stran
i
KEMA
v sk
ladu s
certi
fikato
m
6332
9-KRQ
/ECM
96-52
56
.
20
Märk
us
*
nagu
on nä
idatud
tehn
ilises
doku
menta
tsioo
nis
Daiki
n.TCF
.012
ja he
aks k
iidetu
d
KEMA
järg
i vas
tavalt
serti
fikaa
dile
6332
9-KRQ
/ECM
96-52
56
.
21
Забе
лежк
а *
какт
о е за
ложе
но в
Акта
за те
хнич
еска
конс
трук
ция
Daiki
n.TCF
.012
и оц
енен
о пол
ожит
елно
от
KEMA
съгл
асно
Серт
ифик
ат
6332
9-KRQ
/ECM
96-52
56
.
22
Pasta
ba *
kaip
nuro
dyta
Tech
ninėje
kons
trukc
ijos b
yloje
Daiki
n.TCF
.012
ir pa
tvirtin
ta
KEMA
paga
l
pažy
mėjim
ą
6332
9-KRQ
/ECM
96-52
56
.
23
Piez
īmes
*
kā no
teikts
tehn
iskajā
doku
mentā
cijā
Daiki
n.TCF
.012
, atbi
lstoš
i
KEMA
pozit
īvajam
lēmu
mam
ko ap
liecin
a
serti
fikāts
6332
9-KRQ
/ECM
96-52
56
.
24
Pozn
ámka
*
ako j
e to s
tanov
ené v
Súb
ore t
echn
ickej
konš
trukc
ie
Daiki
n.TCF
.012
a kla
dne p
osúd
ené
KEMA
podľa
Certi
fikátu
6332
9-KRQ
/ECM
96-52
56
.
25
Not
*
Daiki
n.TCF
.012
Tekn
ik Ya
pı Do
syas
ında b
elirtil
diği g
ibi ve
6332
9-KRQ
/ECM
96-52
56
serti
fikas
ına g
öre K
EMA
tarafı
ndan
olum
luola
rak d
eğer
lendir
ilmişt
ir.
3PW18288-1EU
WA
*5K
AZ
W1*
**, E
UW
A*8
KA
ZW
1***
, EU
WA
*10K
AZ
W1*
**, E
UW
A*1
2KA
ZW
1***
, EU
WA
*16K
AZ
W1*
**, E
UW
A*2
0KA
ZW
1***
, EU
WA
*24K
AZ
W1*
**,
* = ,
, -,
1, 2
, 3, .
..9, A
, B, C
, ...,
Z
CONTENTS Page
Introduction ..................................................................................... 1
Technical specifications..................................................................... 2Operation range......................................................................................... 2Main components ...................................................................................... 2Safety devices............................................................................................ 3
Electrical specifications ..................................................................... 3Main components ...................................................................................... 3Safety devices............................................................................................ 3Internal wiring - Parts table........................................................................ 4
Installing the unit ............................................................................ 4
Selection of location .......................................................................... 4
Description Dimensions .................................................................... 4
Inspecting and handling the unit ....................................................... 5
Unpacking and placing the unit ......................................................... 5
Important information regarding the refrigerant used........................ 5
Checking the water circuit ................................................................. 5
Connecting the water circuit .............................................................. 5
Water charge, flow and quality .......................................................... 6Water quality specifications ....................................................................... 6Charging water .......................................................................................... 6
Piping insulation ................................................................................ 7
Field wiring ........................................................................................ 7Parts table.................................................................................................. 7Power circuit and cable requirements........................................................ 7Connection of the power supply ................................................................ 7
Operating the unit ........................................................................... 7
Before operation................................................................................ 7Checks before initial start-up ..................................................................... 7Water supply.............................................................................................. 8Power supply connection and crankcase heating...................................... 8Pump start up ............................................................................................ 8
Operation .......................................................................................... 8Digital controller ......................................................................................... 8Working with the units................................................................................ 9Advanced features of the digital controller............................................... 11
Troubleshooting ............................................................................... 14
Maintenance.................................................................................... 15Important information regarding the refrigerant used .............................. 16Maintenance activities ............................................................................. 16Disposal requirements ............................................................................. 16
Thank you for purchasing this Daikin air conditioner.
INTRODUCTION
This operation manual concerns packaged air-cooled water chillersof the Daikin EUWA(*)-KAZ series. These units are designed foroutdoor installation and used for cooling applications. The units areavailable in 7 standard sizes ranging from 5 to 24 Hp. All sizes areavailable in 3 versions, varying in level of equipment.
The EUWA(*) units can be combined with Daikin fan coil units or airhandling units for air conditioning purposes.They can also be usedfor supplying water for process cooling.
The manual describes the procedures for unpacking, installing andconnecting the EUWA(*) units as well as instructions for adequateoperation and maintenance of the unit and will provide help ifproblems occur.
(*) = N, P, B
EUWAN5~24KAZW1EUWAP5~24KAZW1EUWAB5~24KAZW1
Packaged air-cooled water chillersInstallation and
operation manual
READ THIS MANUAL ATTENTIVELY BEFORE STARTINGUP THE UNIT. DO NOT THROW IT AWAY. KEEP IT INYOUR FILES FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OFEQUIPMENT OR ACCESSORIES COULD RESULT INELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OROTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLYTO USE ACCESSORIES MADE BY DAIKIN WHICH ARESPECIFICALLY DESIGNED FOR USE WITH THE EQUIP-MENT AND HAVE THEM INSTALLED BY A PROFES-SIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,ALWAYS CONTACT YOUR DAIKIN DEALER FORADVICE AND INFORMATION.
Read the chapter "Operation" on page 8 before changingthe parameters.
Installation and operation manual
1EUWA(*)5~24KAZW1
Packaged air-cooled water chillers4PW17895-1C
TECHNICAL SPECIFICATIONS
Single circuit units
Double circuit units
Operation range Main components (See figure 1)
Displayed unit = EUWAB12KAZW1.
1 Condenser
The function of the condenser is to change the state of therefrigerant from gaseous to liquid. The heat gained by the gas inthe evaporator is discharged through the condenser to theambient air, and the vapour condenses to liquid.
2 Compressor
The compressor acts as a pump and circulates the refrigerant inthe refrigeration circuit. It compresses the refrigerant vapourcoming from the evaporator at the pressure at which it can easilybe liquefied in the condenser.
3 Refrigerant filter
The filter installed behind the condenser removes small particlesfrom the refrigerant to prevent blockage of the tubes.
4 Expansion valve
The liquid refrigerant coming from the condenser enters theevaporator via an expansion valve. The expansion valve bringsthe liquid refrigerant to a pressure at which it can easily beevaporated in the evaporator.
5 Evaporator
The main function of the evaporator is to take heat from thewater that flows through it. This is done by turning the liquidrefrigerant, coming from the condenser, into gaseousrefrigerant.
6 Pressure port refrigerant circuit
These ports make it possible to measure refrigerant pressure inthe pipes.
7 Charge valve
Allows refrigerant charge in the circuit.
8 Water in/outlet connection
The water inlet and outlet connection allows an easy connectionof the unit to the water circuit of the air handling unit or industrialequipment.
Unit (Hp) 5 8 10 12Version N P B N P B N P B N P B
Dimensions H x W x D (mm) 1230x1290x734 1230x1290x734 1450x1290x734 1450x1290x734Weight• machine weight (kg) 150 168 180 215 229 241 245 259 271 248 262 274• operation weight (kg) 152 171 239 218 232 300 248 262 330 251 265 335
Connections• water inlet MBSP 1-1/4” 1-1/4” 1-1/4” 1-1/4”• water outlet MBSP 1-1/4” 1-1/4” 1-1/4” 1-1/4”
Internal water volume (l) 2 3 59 3 3 59 3 3 59 3 4 60Expansion vessel• Volume (l) — 12 12 — 12 12 — 12 12 — 12 12• Pre-pressure (bar) — 1.5 1.5 — 1.5 1.5 — 1.5 1.5 — 1.5 1.5
Safety valve water circuit (bar) — 1x3.0 1x3.0 — 1x3.0 1x3.0 — 1x3.0 1x3.0 — 1x3.0 1x3.0
Unit (Hp) 16 20 24Version N P B N P B N P B
Dimensions H x W x D (mm) 1321x2580x734 1541x2580x734 1541x25805x734Weight• machine weight (kg) 430 448 440 490 508 520 496 514 526• operation weight (kg) 436 457 525 496 518 586 503 524 592
Connections• water inlet MBSP 2” 2” 2”• water outlet MBSP 2” 2” 2”
Internal water volume (l) 6 9 65 6 10 66 7 10 66Expansion vessel• Volume (l) — 12 12 — 12 12 — 12 12• Pre-pressure (bar) — 1.5 1.5 — 1.5 1.5 — 1.5 1.5
Safety valve water circuit (bar) — 1x3.0 1x3.0 — 1x3.0 1x3.0 — 1x3.0 1x3.0
A Outdoor temperature
a Standard (water)
b Option (glycol)
°CDB °C dry bulb
LEWT Leaving evaporator water temperature
Pull down operation area
Protect the water circuit against freezing.
When the units operate below –5°C and are installed in a rather windy region, a windscreen is required.
EUWA(*)5~24KAZW1Packaged air-cooled water chillers4PW17895-1C
Installation and operation manual
2
9 Pump (only EUWAP, EUWAB)
The pump circulates the water in the circuit.
10 Pressure regulating valve
The pressure regulating valve is used to regulate the water flow inthe system.
11 Expansion vessel (only EUWAP, EUWAB)
The water in the water circuit expands with rising temperatures.The expansion vessel stabilizes the pressure changes withchanging water temperatures by giving free space to thechanging water volume.
12 Buffer tank (only EUWAB)
The buffer tank reduces the variation in water temperature in thewater circuit. This prevents frequent compressor starts andstops.
13 Drain valve
The drain valve permits complete drainage of the chiller watersystem during maintenance or in case of shut down.
14 Fill valve (only EUWAP, EUWAB)
The water circuit can be filled with water via this fill valve.
15 Air purge valve
Remaining air in the chiller water system will be automaticallyremoved via the air purge valve.
16 Pressure ports water circuit
It is possible to detect any blockage in the water circuit or amalfunction of the pump by means of the 3 pressure ports.
U 7/16 flare pressure ports are provided to connect a device formeasuring the pump pressure and the evaporator pressuredrop. The waterflow can be deducted from these pressures(Refer to "Figures pressure characteristics" on page 8).
17 Water filter
The filter installed in front of the pump removes dirt from thewater to prevent damage to the pump or blockage of theevaporator. The water filter should be cleaned on a regular base.
18 Ball valve
A ball valve is installed in front of and behind the water filter toallow filter cleaning without having to drain the water circuit.
19 Manometer
The manometer allows readout of available water pressure toload.
20 Sensor for inlet water temperature
The measured inlet water temperature is used by the controllerfor regulating the outlet water temprature.
21 Low pressure gauge (optional)
Measurement on low pressure side compressor.
22 High pressure gauge (optional)
Measurement on high pressure side compressor.
Safety devices (See figure 1)
23 High-pressure switch
The high-pressure switch is installed on the discharge pipe ofthe unit and measures the condenser pressure (pressure at theoutlet of the compressor). When the pressure is too high, thepressure switch is activated. The unit stops.
When activated, it resets automatically, but the controller needsto be reset manually.
24 Low pressure switch
The low pressure switch is installed on the suction pipe of theunit and measures the evaporator pressure (pressure at the inletof the compressor). When the pressure is too low, the pressureswitch is activated. The unit stops.
25 Discharge thermal protector (general safety device)
The discharge thermal protector is activated when thetemperature of the refrigerant leaving the compressor becomestoo high. The unit stops.
26 Flow switch
The flow switch measures the flow in the water circuit. In casethe flow does not reach the minimum allowed water flow, the unitwill be shut down.
27 Safety valve (only EUWAP, EUWAB)
The safety valve prevents water pressure from exceeding 3 bar. Itprotects the tank against burst. Activation of this safety has noinfluence on the operation of the unit.
28 Sensor for outlet water temperature
The outlet water temperature sensor measures the temperatureof the water at the evaporator outlet. The protection device shutsdown the unit when the temperature of the chilled waterbecomes too low in order to prevent freezing of the water duringoperation.
When water temperature becomes back to normal, the protectorresets automatically, but the controller needs to be resetmanually.
29 Freeze protection (optional)
Heaters protect the chiller water system against freezing.
ELECTRICAL SPECIFICATIONS
Main components (See figure 2) ( only for 16~24 Hp units)
Refer to the wiring diagram supplied with the unit.
1 Power supply intake (L1, L2, L3, N, PE)
The power cables from the local supply panel can be inserted inthe unit through this foreseen entrance.
2 Main switch (S12M)
Power to unit can be disconnected by means of this switch.
3 Switch for pump (S21P)
Pump can be switched between automatically (steered bycontroller) or manually on (for servicing purpose) by means ofthis switch.
4 Digital controller (A1P)
Controls the functioning of the unit.
5 I/O PCB (A2P) (input/output)
The I/O PCB (A2P) is used to connect all internal wiring andfield wiring. It includes some control and safety functions as well.
6 Softstarter (A5P) (possible optional for 5~12 Hp only)
The softstarter reduces the starting current of the compressor.
Safety devices (See figure 2) ( only for 16~24 Hp units)
5 I/O PCB (A2P) (input/output)
The I/O PCB (A2P) contains a reverse phase protector.
The reverse phase protector detects if the 3 phases of the powersupply are connected correctly. If a phase is not connected or if2 phases are inverted, the unit can not start up.
Unit (Hp) 5 8 10 12 16 20 24
Power circuit• Phase 3+N• Frequency (Hz) 50• Voltage (V) 400• Voltage tolerance (%) ±10• Recommended fuses EUWAN (A) 20 25 25 32 40 50 63
EUWAP+B (A) 20 25 32 40 50 50 63
Installation and operation manual
3EUWA(*)5~24KAZW1
Packaged air-cooled water chillers4PW17895-1C
7 Fan motor thermal protector (Q11F, Q12F, Q21F, Q22F)
The fan motors are equipped with a thermal protector. Theprotectors are activated when the temperature becomes toohigh. When temperature returns to normal, the protector resetsautomatically.
8 Overcurrent relay for compressor (K4S, K5S)
The overcurrent relay protects the compressor motor in case ofoverload, phase failure or too low voltage. The relay is factoryset and may not be adjusted. When activated, the overcurrentrelay has to be reset in the switch box and the controller needsto be reset manually.
9 Overcurrent relay for pump (K6S)
The overcurrent relay protects the pump motor in case ofoverload, phase failure or too low voltage. The relay is factoryset and may not be adjusted. When activated, the overcurrentrelay has to be reset in the switch box and the controller needsto be reset manually.
10 Fuse for control circuit (F1U)
The fuse for control circuit protects cables of control circuit andcontroller components in case of short circuit.
11 Fuse for control circuit (F4)
The fuse for control circuit protects cables of control circuit andheater(s) for freeze protection in case of short circuit.
12 Fuse for digital controller (F3U)
The fuse protects cables of digital controller and digital controllerin case of short circuit.
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit. Theabbreviations used are listed below.
A1P........................ PCB: controller PCB
A2P........................ PCB: I/O PCB (input/output)
A3P..............** ...... PCB: Address card for BMS
A5P..............** ...... Softstarter for circuit 1
A7P..............** ...... PCB: remote user interface
C1,C2,C3,C4 ......... Capacitors for fanmotors
E1H,E2H................ Crankcase heater circuit 1, circuit 2
E3H,E4H......** ...... Evaporator heatertape
E5H............... * ...... Field heater
E6H..............** ...... Buffertank heater
F1,F2,F3 .......# ...... Main fuses for the unit
F4 .......................... Fuse for I/O PCB and evaporator heatertape
F5 ...............## ...... Surge proof fuse (optional for BMS)
F6 .............. (#) ...... Fuse for pumpmotor
F7,F8 ..................... Fuse for fan motor circuit 1, circuit 2
F1U........................ Fuse for I/O PCB
F3U........................ Fuse controller PCB
H3P............... * ...... Indication lamp alarm
H4P............... * ...... Indication lamp operation compressor 1
H5P............... * ...... Indication lamp operation compressor 2
H6P............... * ...... Indication lamp general operation
K1M,K2M............... Compressor contactor circuit 1, circuit 2
K4S,K5S ................ Overcurrent relay circuit 1, circuit 2
K6S.............(*) ...... Overcurrent relay pump
K1P.............(*) ...... Pumpcontactor
M1C,M2C............... Compressor motor circuit 1, circuit 2
M11F,M12F............ Fanmotors circuit 1
M21F,M22F............ Fanmotors circuit 2
M1P ....................... Pumpmotor (only P and B models)
PE.......................... Main earth terminal
Q1D,Q2D ............... Discharge thermal protector circuit 1, circuit 2
Q11F,Q12F ............ Thermal protector fan circuit 1
Q21F,Q22F ............ Thermal protector fan circuit 2
R3T ........................Evaporator inlet water temperature sensor
R4T ........................Evaporator outlet water temperature sensor
R6T ........................Ambient temperature sensor
R7T,R8T.................Coil temperature sensor for circuit 1, circuit 2
S1HP,S2HP............High pressure switch circuit 1, circuit 2
S4LP,S5LP .............Low pressure switch circuit 1, circuit 2
S7S ...............*.......Switch for remote cooling/heating selection
S9S ...............*.......Switch for remote start/stop
S10L.......................Flowswitch
S12M......................Main isolator switch
S21P ......................Switch for pump: manual/auto
TR1 ........................Transfo 230 V ➞ 24 V for supply of controller PCB
TR2 ........................Transfo 230 V ➞ 24 V for supply of I/O PCB (A2P)
X1~82A/B/M...........Connectors
Y1R,Y2R................Reverse valve circuit 1, circuit 2
INSTALLING THE UNIT
SELECTION OF LOCATION
The unit should be installed in a location that meets the followingrequirements:
1 The foundation is to be in such way that it causes no vibrationsor noise when the unit is in operation.
2 The space around the unit is adequate for servicing and theminimum space for air inlet and air outlet is available.
If several units are being installed side by side, the minimumservice space between them must be taken into account.
3 There is no danger of fire due to leakage of inflammable gas.
4 Ensure that water cannot cause any damage to the location byadding water drains to the foundation and prevent water traps inthe construction.
5 Select the location of the unit in such a way that neither thedischarged air nor the sound generated by the unit disturbanyone.
6 Make sure that the air inlet and outlet of the unit are notpositioned towards the main wind direction. Frontal wind willdisturb the operation of the unit. If necessary, use a windscreento block the wind.
7 In heavy snowfall areas, select an installation site where snowwill not affect operation of the unit.
DESCRIPTION DIMENSIONS
For dimensions of the unit, refer to the outlook diagram delivered withthe unit.
Not included with standard unit
Not possible as option Possible as option
Obligatory # ##
Not obligatory * **
( ) Applicable for unit without integrated pump
Space for air inlet B1/B2
Space for air outlet ≥3 m
Service space
EUWA(*)5~24KAZW1Packaged air-cooled water chillers4PW17895-1C
Installation and operation manual
4
INSPECTING AND HANDLING THE UNIT
The units are packed in a wooden crate and attached on a woodenpallet.
At delivery, the unit should be checked and any damage should bereported immediately to the carrier claims agent.
When handling the unit, take into account the following:
1 Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
2 Lift the unit preferably with a crane and 2 belts in accordance with theinstruction sticker on the unit.
3 When lifting the unit with a crane, always use protectors to preventbelt damage and pay attention to the position of the unit’s centre ofgravity.
4 Bring the unit as close to its final installation position in its originalpackage to prevent damage during transport.
UNPACKING AND PLACING THE UNIT
1 Remove the wooden crate from the unit.
2 Remove the screws fixing the unit to the pallet.
3 The unit must be installed on a solid longitudinal foundation(steelbeam frame or concrete).
4 Fasten the unit in place using four anchor bolts M12.
5 Make sure that the unit is levelled in both directions.
6 If the unit is operating below –5°C ambient, the unit must beinstalled out of the wind. If this is not possible, a windscreenmust be installed.
IMPORTANT INFORMATION REGARDING THE REFRIG-ERANT USED
This product contains fluorinated greenhouse gases covered by theKyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: R407C
GWP(1) value: 1652.5
(1) GWP = global warming potential
The refrigerant quantity is indicated on the unit name plate.
CHECKING THE WATER CIRCUIT
The units are equipped with a water inlet and water outlet forconnection to a water circuit. This circuit must be provided by alicensed technician and must comply with all relevant European andnational regulations.
Before continuing the installation of the unit, check the followingpoints:
Only for EUWAN version
■ A circulation pump must be provided in such a way that itdischarges the water directly into the water heat exchanger.
■ Provide adequate safeguards in the water circuit to make sure thatthe water pressure will never exceed the maximum allowableworking pressure (10 bar).
For all versions
■ A kit containing 2 ball valves and 1 filter is delivered with the unit.For location of the kit within the unit, refer to the outlook diagramand to the sticker on the frontplate of the unit. Install this kit at thewater inlet of the unit. Refer to figure 3.
■ Drain taps must be provided at all low points of the system to permitcomplete drainage of the circuit during maintenance or in case ofshut down. A drain plug is provided to drain the water from thechiller water system.
■ Air vents must be provided at all high points of the system. Thevents should be located at points which are easily accessible forservicing. An automatic air purge is provided on the chiller watersystem.
■ Take care that the components installed in the field piping canwithstand at least the sum of opening pressure of the safety valve +the static height of the pump.
■ For EUWAP and EUWAB: 6 bar.
■ For EUWAN: depending on the selected pump and safetyvalve.
CONNECTING THE WATER CIRCUIT
Water connections must be made in accordance with the outlookdiagram delivered with the unit, respecting the water in- and outlet.
If air, moisture or dust gets in the water circuit, problems may occur.Therefore, always take into account the following when connectingthe water circuit:
1 Use clean pipes only.
2 Hold the pipe end downwards when removing burrs.
3 Cover the pipe end when inserting it through a wall so that no dustand dirt enter.
4 Use a good thread sealant for the sealing of the connections. Thesealing must be able to withstand the pressures and temperatures ofthe system, it must also be resistant to the used glycol in the water.
5 Because brass is a soft material, use appropriate tooling forconnecting the water circuit. Inappropriate tooling will cause damageto the pipes. Refer to figure 3.
1 Prepare a water drainage channel around thefoundation to drain waste water from around the unit.
2 If the unit is to be installed on a roof, check thestrength of the roof and its drainage facilities first.
3 If the unit is to be installed on a frame, install awaterproofing board with a distance of 150 mmunder the unit in order to prevent infiltration of watercoming from under the unit.
4 In case of indoor installation, make sure to connect adrainhose to the drain connection (Ø16).
Not installing the filter kit can lead to severe damageof the unit.
Be careful not to deform the unit piping by using excessiveforce when connecting the piping. Deformation of thepiping can cause the unit to malfunction.
1 To secure the piping of the chiller
2 To connect the ball valve
Installation and operation manual
5EUWA(*)5~24KAZW1
Packaged air-cooled water chillers4PW17895-1C
WATER CHARGE, FLOW AND QUALITY
For all versions
To assure proper operation of the unit a minimum water volume isrequired in the system and the water flow through the evaporatormust be within the operation range as specified in the table.
Only for EUWAP, EUWAB versions
Connecting pressure gauges to the water circuit (field supply)
It is desirable to know the static height over the pump, for regulatingthe water flow (refer to "Pump start up" on page 8). For this reasonyou need to install pressure gauges or a differential pressure gaugeon the pressure ports.
Maximum allowed installation height in function of the water volume
Make sure to respect following limitations:
If the EUWA is installed at the highest point of the system, then thereis no height difference to be considered.
If the EUWA is placed on a height level other than the highest point,refer to figure 7 to read the maximum allowed height difference infunction of the water volume.
e.g.: If water volume=180 l, the maximum allowed installation heightdifference is 9 m.
Setting the pre-pressure of the expansion vessel
The pre-pressure (Pg) on the expansion vessel has to be set beforefilling the system with water or water/glycol solution in function of themaximum installation height difference (H).
Use dry compressed air or nitrogen for this operation.
The pre-pressure (Pg) to be set is calculated as below:
Pg=(H/10+0.3) bar
H=Maximum installation height of the circuit above the EUWA unit (m)
Water quality specifications
Charging water
For all versions
1 Connect the water supply to the drain and fill valve
2 Open the pressure regulating valve (only for EUWAP andEUWAB) and shut-off valves
3 Use the air purge valves on the unit and purge valves installed inthe highest places in the circuit to remove all air when filling thesystem
Only for EUWAP, EUWAB versions
Water must be filled until the system reaches the required
pressure (Pr). The pressure can be read on the manometer.
The value of the required water pressure (Pr) is depending on thetotal water volume in the system and the pressure in the expansionvessel (see previous chapter).
Refer to figure 7 – Required water pressure in function of watervolume and pre-pressure:
1. Calculate the total water volume in the entire system.
2. Check in figure 7 where the horizontal line of the set prepressure(Pg) cuts the vertical line of the system water volume.
3. At the cutting point, read the required water pressure (Pr) from thelines in the figure.
Unit (Hp)Minimum water
volume (l)(*)
(*) a = cooling temperature difference (refer to "Defining the cooling temperature difference" on page 11).
Minimum water flow (l/min)
Maximum water flow (l/min)
5 162/a 25 658 255/a 35 10210 324/a 40 12912 378/a 51 15216 264/a 65 21220 333/a 75 26724 396/a 83 317
circulating water supply water
tendency if out of criteria
Items to be controlled
pH at 25°C 6.8~8.0 6.8~8.0 corrosion + scale
Electrical conductivity
[mS/m]at 25°C <40 <30 corrosion + scale
Chloride ion [mg Cl-/l] <50 <50 corrosion
Sulfate ion [mg SO42-/l] <50 <50 corrosion
M-alkalinity (pH4.8)
[mg CaCO3/l] <50 <50 scale
Total hardness [mg CaCO3/l] <70 <70 scale
Calcium hardness [mg CaCO3/l] <50 <50 scale
Silica ion [mg SiO2/l] <30 <30 scale
Items to be referred to
Iron [mg Fe/l] <1.0 <0.3 corrosion + scale
Copper [mg Cu/l] <1.0 <0.1 corrosion
Sulfide ion [mg S2-/l] not detectable not detectable corrosion
Ammonium ion [mg NH4+/l] <1.0 <0.1 corrosion
Remaining chloride [mg Cl/l] <0.3 <0.3 corrosion
Free carbide [mg CO2/l] <4.0 <4.0 corrosion
Stability index — — corrosion + scale
The chillers are only to be used in a closed water system.Application in an open water circuit can lead to excessivecorrosion of the water piping.
If the water system is drained during some period, rinseout the pump chamber with demineralised water. This toprevent the impeller to be blocked by dried inpurities.
To do this, use the drain tap of the pump. Fill and empty thepump a few times until the removed water is completelyclear. Keep the connections closed to prevent corrosionand dirt entering the water system.
Use of glycol is allowed, but the amount should not exceed40% of the volume. A higher amount of glycol may causedamage to some hydraulic components.
A Water volume (l)
B Installation height difference (m)
C Pre-pressure
D Factory setting (1.5 bar)
circulating water supply water
tendency if out of criteria
1 2
34
1 Water out
2 Impeller
3 Water in
4 Drain tap
EUWA(*)5~24KAZW1Packaged air-cooled water chillers4PW17895-1C
Installation and operation manual
6
Example 1
Total system water volume=130 l
Highest point of circuit above the EUWA =5 m
Pg=(5/10+0.3)=0.8 bar
Pr=±2.0 bar
Example 2
Total system water volume=190 l
Highest point of circuit above the EUWA unit=5 m
Pg=(5/10+0.3)=0.8 bar
Pr=±1.7 bar
PIPING INSULATION
The complete water circuit, inclusive all piping, must be insulated toprevent condensation and reduction of the cooling capacity.
FIELD WIRING
Parts table
Refer to the wiring diagram supplied with the unit.
Following parts are to be connected during installation:
N.............................Neutral
P.............................Main earth terminal
F1,F2,F3.................Main fuses (field supply, obligatory)
H3P ........................Indication lamp alarm (field supply, not obligatory)
H5P,H6P.................Indication lamp compr circuit 1, circuit 2 (field supply, not obligatory)
S9S ........................Switch for remote start/stop (field supply, not obligatory)
E5H ........................Field heater (field supply, optional)
X2M(E5H) ..............Terminal for field heater connection (optional)
---............................Field wiring
Power circuit and cable requirements
A power circuit must be provided for connection of the unit. Thiscircuit must be protected with the required safety devices, i.e. a slowblow fuse on each phase and an earth leak detector. For maximumcable section (mm2) refer to the table.
Connection of the power supply
1 Using the appropriate cable, connect the power circuit to the N,L1, L2 and L3 terminals of the main switch as shown on thewiring diagram.
2 Connect the earth conductor (yellow/green) to the earthingterminal PE.
OPERATING THE UNIT
BEFORE OPERATION
Checks before initial start-up
After the installation of the unit, check the following before switchingon the circuit breaker:
1 Field wiring
Make sure that the field wiring between the local supply paneland the unit has been carried out according to the instructionsdescribed in the the chapter "Field wiring" on page 7, accordingto the wiring diagrams and according to European and nationalregulations.
2 Fuses or protection devices
Check that the fuses or the locally installed protection devicesare of the size and type specified in the chapter "Electricalspecifications" on page 3. Make sure that neither a fuse nor aprotection device has been bypassed.
3 Earth wiring
Make sure that the earth wires have been connected properlyand that the earth terminals are tightened.
4 Internal wiring
Visually check the switch box on loose connections or damagedelectrical components.
5 Fixation
Check that the unit is properly fixed, to avoid abnormal noisesand vibrations when starting up the unit.
NOTE In this example it is allowed to keep the pre-pressurefactory setting from 1.5 bar. In this case the initialwater-pressure must be ±2.2 bar
NOTE In this example it is not allowed to keep the pre-pressure factory setting from 1.5 bar.
NOTE A terminal is foreseen in the switchbox on which aheater (tape) can be connected for preventing the waterpiping from freezing during the cold weather months.Refer to the wiring diagram supplied with the unit.
All field wiring and components must be installed by alicensed electrician and must comply with relevant Euro-pean and national regulations.
The field wiring must be carried out in accordance with thewiring diagram supplied with the unit and the instructionsgiven below.
Be sure to use a dedicated power circuit. Never use apower supply shared by another appliance.
Description Legend 5~24 Hp
Powerlines L1, L2, L3, N 10
Main earth cable PE 10
NOTE Select the power cable in accordance with relevantlocal and national regulations.
Switch off the main isolator switch before making anyconnections.
For units equipped with freeze protection:
Keep in mind that the heaters are automatically switchedoff when the main isolator switch is switched off. For thisreason the main switch should be switched on during thecold weather months.
Make sure that the main switch of the unit is switched off.
Installation and operation manual
7EUWA(*)5~24KAZW1
Packaged air-cooled water chillers4PW17895-1C
6 Damaged equipment
Check the inside of the unit on damaged components orsqueezed pipes.
7 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is arefrigerant leak, call your local Daikin dealer.
8 Oil leak
Check the compressor on oil leakage. If there is an oil leak, callyour local Daikin dealer.
9 Air inlet/outlet
Check that the air inlet and outlet of the unit is not obstructed bypaper sheets, cardboard, or any other material.
10 Power supply voltage
Check the power supply voltage on the local supply panel. Thevoltage must correspond to the voltage on the identification labelof the unit.
11 Ball valve and filter kit
Make sure that the ball valve and filter kit are correctly installed.
12 Pressure regulating valve and shut-off valve
Check that the pressure regulating valve (only for EUWAP andEUWAB) and the shut-off valves are fully open.
Water supply
Fill the water piping, taking into account the minimum water volumerequired by the unit. Refer to the chapter "Water charge, flow andquality" on page 6.
Make sure that the water is of the quality as mentioned in the chapter"Water quality specifications" on page 6.
Purge the air at the high points of the system (automatic air purgeinside the chiller) and check the operation of the circulation pump andthe flow switch.
Power supply connection and crankcase heating
To switch on the crankcase heater proceed as follows:
1 Switch on the main switch of the unit. Make sure that the unit is“OFF”.
2 The crankcase heater is switched on automatically.
3 Check the supply voltage on the supply terminals L1, L2, L3, (N)by means of a voltmeter. The voltage must correspond to thevoltage indicated on the identification label of the unit.
If the voltmeter reads values which are not within the rangesspecified in the technical data, check the field wiring and replacethe supply cables if necessary.
4 Check the service leds H1P and H2P on the I/O PCB (A2P).
If the H1P led is off and the H2P is on, then the phase order isnot correct. Switch off the main switch and call a licensedelectrician to connect the wires of the power supply cable in thecorrect phase order.
After six hours, the unit is ready for operation.
Pump start up (only for EUWAP and EUWAB)
1 Turn the pump switch to manual. The pump must run now.
2 Set the desired flow by turning the pressure regulating valve.
3 Put the switch to auto. The pump will stop.
4 Switch the chiller on. The pump will be started by the chiller.
Detailed instructions for switching the unit on and operating theunit, can be found in the chapter "Working with the units" onpage 9.
5 Check if the ∆t of the chiller is within expectations. If necessary,regulate the flow by using the pressure regulating valve.
Figures pressure characteristics- Pump characteristics (See figure 4)
- External static pressure (See figure 5)
- Pressure drop curves evaporators (See figure 6)
OPERATION
The units are equipped with a digital controller offering a user-friendlyway to set up, use and maintain the unit.
This part of the manual has a task-oriented, modular structure. Apartfrom the first section, which gives a brief description of the controlleritself, each section or subsection deals with a specific task you canperform with the unit.
Digital controller
User interface
The digital controller consists of a numeric display, four labelled keyswhich you can press and four LEDs providing extra user information.
Figure - Digital controller
Operating the system with closed valves will damagethe pump.
In order to avoid compressor damage, it is necessary toswitch on the crankcase heater for at least six hoursbefore starting the compressor after a long period of stand-still.
NOTE ■ The desired flow is depending on the capacity of thechiller and the desired temperature differencebetween water inlet and outlet (∆t).
■ If manometers are installed, the flow can bededuced from the pressure difference over thepump. For pump and resistance characteristics, refer toparagraph "Figures pressure characteristics" onpage 8.
1 pump 5, 8, 10, 12 Hp 4 pump 5, 8, 10, 12 Hp (optional)
2 pump 16, 20 Hp 5 pump 16, 20, 24 Hp (optional)
3 pump 24 Hp
1 EUWAP5, EUWAB5 5 EUWAP16, EUWAB16
2 EUWAP8, EUWAB8 6 EUWAP20, EUWAB20
3 EUWAP10, EUWAB10 7 EUWAP24, EUWAB24
4 EUWAP12, EUWAB12
1 EUWA(*)5 5 EUWA(*)16
2 EUWA(*)8 6 EUWA(*)20
3 EUWA(*)10 7 EUWA(*)24
4 EUWA(*)12
comp
x 100
clear
PRGmute
SEL
EUWA(*)5~24KAZW1Packaged air-cooled water chillers4PW17895-1C
Installation and operation manual
8
Keys provided on the controller:
Each key, except for the lower left key, combines two functions: E/O, A/Y and I/Z. The function carried out when the userpresses one of these keys depends on the status of the controllerand the unit at that specific moment.
LEDs provided on the controller:
Direct and user parameters
The digital controller provides direct and user parameters. The directparameters are important for the everyday usage of the unit, e.g. toadjust the temperature setpoint or to consult actual operationalinformation. The user parameters on the contrary provide advancedfeatures such as adjusting time delays or disabling the buzzer.
Each parameter is defined by a code and a value. For example, theparameter used to select local or remote on/off control has code h7and value 1 or 0.
Working with the units
This chapter deals with the everyday usage of the EUWA units. Here,you will learn how to perform routine tasks, such as:
■ "Switching the unit on" on page 9 and "Switching the unit off" onpage 9,
■ "Adjusting the cooling temperature setpoint" on page 9,
■ "Consulting actual operational information" on page 10,
■ "Resetting alarms" on page 10,
■ "Resetting warnings" on page 11.
Switching the unit on
To switch the EUWA unit on, proceed as follows:
1 When the on/off digital input user parameter h7 is set to 0 (=No),press the I key for approximately 5 seconds to switch the uniton.
When the on/off digital input user parameter h7 is set to1 (=Yes), you can also switch the unit on using the remote on/offswitch (installed by the customer).
In both cases an initialization cycle is started and the T LEDstarts blinking. The I LED lights up, indicating that the unit isswitched on. Once all the timers have reached zero, the unitstarts up and the T LED lights up permanently. The numericdisplay shows the actual inlet water temperature of theevaporator.
2 When the unit is started up for the first time, or when the unit hasbeen out of operation for a longer period, it is recommended togo through the following checklist.
Abnormal noise and vibrations
Make sure the unit does not produce any abnormal noises orvibrations: check the fixations and piping. If the compressormakes any abnormal noises, this may also be caused by anovercharge of refrigerant.Working pressure
It is important to check the high and low pressure of therefrigerant circuit to ensure the proper operation of the unit andto guarantee that the rated output will be obtained.
3 If the unit does not start after a few minutes, consult the actualoperational information available in the list of direct parameters.Also refer to the chapter "Troubleshooting" on page 14.
Switching the unit off
To switch the EUWA unit off, proceed as follows:
1 When the on/off digital input user parameter h7 is set to 0 (=No)and the unit is on, press the I key for approximately 5 secondsto switch the unit off.
The I LED and the T LED are extinguished.
2 When the on/off digital input user parameter h7 is set to1 (=Yes), switch the unit off using the remote on/off switch.
The I LED and the T LED are extinguished.
Adjusting the cooling temperature setpoint
The EUWA units enable definition and modification of the coolingtemperature setpoint. The default, limit and step values for thecooling setpoint are:
■ Default value 12.0 °C
■ Limit values 7.0 to 25.0°C
■ Step value 0.1°C
Ekey, to enter the scroll list of user parameters, to confirm a parameter modification and to return to normal operation.
O key, to de-activate the buzzer in the case of an alarm.
Akey, to scroll through the list of direct or user parameters or to raise a setting.
Y has no effect on EUWA units.
Rkey, to enter the scroll list of direct parameters or to switch between a parameter's code and its value.
Ikey, to start the unit in cooling mode or to switch the unit off when cooling mode is active.
Zkey, to scroll through the list of direct or user parameters or to lower a setting.
T
LEDs, indicate the status of compressor 1 (left LED) and compressor 2 (right LED). The T LEDs do not light up when the compressor is not active, blinks when the compressor cannot start up although extra load is requested (e.g. timer active) and lights up permanently when the compressor is active.
Y LED, is not active.
I LED, indicates that cooling mode is active.
ULED, indicates that the value on the numeric display should be multiplied by 100.
NOTE Temperature readout tolerance: ±1°C.
Legibility of the numeric display may decrease in directsunlight.
The pressures measured will vary between a maximumand minimum value, depending on the water and outdoortemperatures (at the moment of measurement).
Cooling mode Minimum Nominal Maximum
( –5°C) ( 35°C) ( 38°C)
(LW 4°C) (LW 7°C) (LW 20°C)
Low pressure 3 bar 4 bar 6.5 barHigh pressure 7 bar 21 bar 24 bar
outdoor temperature LW leaving water temperature
NOTE In case of remote on/off control (h7 = 1), it is recom-mended to install an on/off switch near the unit inseries with the remote switch. The unit can then beswitched off from either place.
Installation and operation manual
9EUWA(*)5~24KAZW1
Packaged air-cooled water chillers4PW17895-1C
To adjust the cooling temperature setpoint, proceed as follows:
1 Press the R key for approximately 5 seconds to enter the list ofdirect parameters.
The direct parameter code r1 defining the cooling temperaturesetpoint appears on the display.
2 Press the R key.
The actual cooling temperature setpoint appears on the display.
3 Press the A or Z key to raise, respectively lower thetemperature setting.
4 Press the R key to return to parameter code r1.
5 To save the adjusted temperature setpoint, press the E key. Tocancel the modification wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the listof direct parameters and returns to its normal operation,displaying the inlet water temperature.In the second case the display starts flashing. Approximately40 seconds later, the controller leaves the list of directparameters without saving the modified parameter. The inletwater temperature reappears on the display.
Consulting actual operational information
The actual operational information that can be consulted in the list ofdirect parameters consists of:
■ r6: outlet water temperature evaporator,
■ c9: total running hours of the compressor1,
■ ca: total running hours of the compressor2,
■ cv: total running hours of the pump.
To consult the actual operational information, proceed as follows:
1 Press the R key for approximately 5 seconds to enter the list ofdirect parameters.
The direct parameter code r1 defining the cooling temperaturesetpoint appears on the display.
2 Depending on the information to be consulted, select parametercode r6, c9, ca or cv using the A and/or Z key.
3 Press the R key to consult the actual value of the selectedparameter.
4 Press the R key to return to the parameter codes.
5 To consult other actual operational information, repeat frominstruction 2 onwards.
6 To return to normal operation, press the E key or waitapproximately 40 seconds.
In the first case, the controller immediately leaves the list ofdirect parameters and returns to normal operation displaying theinlet water temperature.In the second case, the display will start flashing. Approximately40 seconds later, the controller leaves the list of direct para-meters. The inlet water temperature reappears on the display.
Resetting alarms
When an alarm is detected, the following happens:
■ the buzzer is activated (if enabled by means of user parameter p4),
■ the alarm relay is energized,
■ the display starts flashing, alternately showing the alarm code andthe inlet water temperature.
The following alarm codes may appear on the screen:
■ a1: indicates an anti-freeze alarm,
■ e1: indicates that the NTC probe used to measure theevaporator inlet water temperature is defective,
■ e2: indicates that the NTC probe used to measure the outletwater temperature is defective,
■ e3: indicates that the fuse for evaporator heatertape (F4) isblown or that there is a reverse phase error or that there is aproblem with the I/O PCB (A2P).
■ ee,ep: indicates that the EEPROM on the controller PCB inside theunit is defective,
■ei,e0: indicates that the supply voltage is exceedingly low (ei) orexceedingly high (e0). In these cases contact a licensedelectrician,
■ el: indicates that the power supply has a "remarkable noise". Inthis case contact a licensed electrician,
■ f l: indicates that there was no sufficient water flow either duringthe period of 15 seconds after the pump was started or for 5seconds while the compressor is active or that theovercurrent protection of the pump is activated,
■ h1: indicates that a high pressure switch, the discharge thermalprotection or the overcurrent protection of the compressormotor is activated or that the NTC probe used to measurethe ambient temperature is defective,
■ l1: indicates that the low pressure switch is activated.
To reset an alarm, proceed as follows:
1 Press the O key to acknowledge the alarm.
The buzzer is de-activated.
2 Find the cause of shutdown and correct.
Refer to the chapter "Troubleshooting" on page 14.
3 If the alarm codes a1, f l, h1 or l1 appear on the display, resetthe alarm manually by pressing the A and Z keysimultaneously for approximately 5 seconds.
In all other cases the alarm is reset automatically.
Once the alarm is reset, the error code no longer appears on thedisplay. The controller continues its normal operation, displayingthe inlet water temperature.
NOTE By pressing any button while the display is flashingand cancelling of all changes is in progress, the can-celling process is stopped, the display stops flashingand the user can continue to change the settings.
NOTE To reset the timers c9, ca and cv, refer to chapter"Resetting warnings" on page 11.
In case the unit is equipped with freeze protection, it ishighly recommended to install the remote indicatorlamp alarm (H3P) (see wiring diagram supplied withthe unit). By doing so, breakdown of the fuse forevaporator heatertape (F4) will be detected soonerand freezing of the circuit will be avoided during thecold weather months.
NOTE If the alarm codes f l and h1 are flashing alternately,the alarm is most probably caused by the reversephase protector or by the fuse for evaporator heater-tape (F4) that was blown.
EUWA(*)5~24KAZW1Packaged air-cooled water chillers4PW17895-1C
Installation and operation manual
10
Resetting warnings
During normal operation, the display of the controller may startflashing, alternately showing the inlet water temperature and thefollowing warning code:
■ n1: indicates that the compressor1 requires maintenance: thetotal running hours of the compressor1 (direct parameter c9)has exceeded the setting of the timer threshold formaintenance warning (user parameter cb).
■ n2: indicates that the compressor2 requires maintenance: thetotal running hours of the compressor2 (direct parameter ca)has exceeded the setting of the timer threshold formaintenance warning (user parameter cb).
To reset the maintenance warning n1 or n2, proceed as follows:
1 Enter the list of direct parameters by pressing the R key forapproximately 5 seconds.
The parameter code r1 appears on the display.
2 Select parameter code c9 or ca using the A and/or Z key.
3 Press the R key to switch to the parameter value.
4 Press the A and Z keys simultaneously for approximately5 seconds.
The timer's value becomes 0.
5 Press the R key to return to parameter code c9 or ca.
6 Press the E key to return to normal operation.
Advanced features of the digital controller
This chapter gives an overview of the direct parameters and userparameters provided by the controller. In the following chapter, youwill learn how you can set up and configure the EUWA unit usingthese parameters.
Overview of the direct parameters
The list of direct parameters is accessible by pressing the R key forapproximately 5 seconds.
When scrolling through the list of direct parameters using the A and/or Z key, the parameters appear in the following order:
■ r1: to define the cooling temperature setpoint,
■ r2: to define the cooling temperature difference,
■ r6: to check the evaporator outlet water temperature,
■ c9: to check the total running hours of the compressor1,
■ ca: to check the total running hours of the compressor2,
■ cv: to check the total running hours of the pump.
Overview of the user parameters
The list of user parameters is only accessible by means of the userpassword. When scrolling through the list of parameters using the Aand/or Z key, you see the direct parameters and user parameters.The user parameters appear in the following order:
■ :d: to define the measurement unit (°C or °F),
■ c7: to define the time delay between the pump startup and thecompressor startup,
■ c8: to define the time delay between the unit shutdown and thepump shutdown,
■ cb: to define the time threshold for maintenance warning,
■ p4: to disable the buzzer or to define the activation period of thebuzzer in case of an alarm,
■ h6: to activate or to deactivate the remote cool/heat control,
■ h7: to activate or de-activate the remote on/off control,
■ h9: to lock or unlock the controller keyboard,
■ ha: to define the unit's serial address,
■ h8,hb,c6: not used.
Tasks carried out using direct parameters
Entering the list of direct parameters
1 Press the R key for approximately 5 seconds.
The controller enters the list of direct parameters, displayingparameter code r1.
Defining the cooling temperature difference
To control the cooling load, the unit with 1 compressor is equippedwith a single-step thermostat. The unit with 2 compressors isequipped with a two-step thermostat. The thermostat's "coolingtemperature difference" can be modified by means of directparameter r2.
The default, limit and step values are:
■ Default value 3.0°C
■ Limit values 0.3 to 19.9°C
■ Step value 0.1°C
To define the cooling temperature difference, proceed as follows:
1 Enter the list of direct parameters.
2 Press the A key once.
Direct parameter code r2 appears on the display.
3 Press the R key to switch to the parameter value.
4 Select the appropriate setting using the A and/or Z key.
5 Press the R key to switch to the list of parameter codes.
6 To adjust or to consult other direct parameters before saving themodifications, select another direct parameter using the A and/or Z key and then repeat from instruction 3 onwards.
NOTE Do not forget to carry out the required maintenanceactivities after resetting the timers.
Besides resetting timer c9 (running hours of thecompressor 1) and ca (running hours of thecompressor 2), it is also possible to reset timer cvwhich defines the total running hours of the pump. Todo this, consult the timer's value (refer to paragraph"Consulting actual operational information" onpage 10) and press the A and Z keys simultane-ously for approximately 5 seconds while the timer'svalue is displayed. The timer's value becomes 0. Thensuccessively press the R key and the E key to returnto normal operation.
for 1 compressor for 2 compressors
12 15
°C
compressor
inlet water
temperature of evaporator
ON OFF
12 15
°C
13.5
compressor(s)
inlet water
temperature of evaporator
ON
ON OFF
OFF compressor2
compressor1
Installation and operation manual
11EUWA(*)5~24KAZW1
Packaged air-cooled water chillers4PW17895-1C
7 To save the modifications, press the E key. To cancel themodifications, wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the listof direct parameters and returns to normal operation, displayingthe inlet water temperature.
In the second case, the display starts flashing. Approximately40 seconds later, the controller leaves the list of directparameters without saving the modifications. The inlet watertemperature reappears on the display.
Tasks carried out using user parameters
Entering the list of user parameters
Access to the list of user parameters is protected by the userpassword (a 3-digit number between 0 and 199).
To enter the list of user parameters, proceed as follows:
1 Press the E key for approximately 5 seconds.
The number 00 starts flashing on the display.
2 Enter the correct password using the A and/or Z key.
The password's value is 22.
3 Press the R key to confirm the password and to enter the list ofuser parameters.
The controller displays parameter code :d (which is the first userparameter).
Defining the measurement unit
Depending on the setting of user parameter :d, all temperaturevalues are displayed in °C or in °F. The conversion formulas from °Cto °F and vice versa are:
■ T°C = (T°F – 32) / 1.8
■ T°F = (T°C x 1.8) + 32
If user parameter :d is set to 0, all temperatures appearing on thedisplay will be expressed in °C. If user parameter :d is set to 1 alltemperatures will be expressed in °F.
To define the measurement unit, proceed as follows:
1 Enter the list of user parameters.
Parameter code :d appears on the display.
2 Press the R key to switch to the parameter value.
3 Select the appropriate setting using the A and/or Z key.
4 Press the R key to return to the list of parameter codes.
5 To adjust or to consult other user parameters before saving themodifications, select another user parameter using the A and/or Z key and then repeat from instruction 2 onwards.
6 To save the modifications, press the E key. To cancel themodifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the listof user parameters and returns to normal operation, displayingthe inlet water temperature.In the second case, the display starts flashing. Approximately40 seconds later, the controller leaves the list of userparameters without saving the modifications. The inlet watertemperature reappears on the display.
Defining the time delay between pump and compressor startup
User parameter c7 allows you to define the time delay between thepump startup and the compressor startup. The default, limit and stepvalues for the time delay are:
■ Default value 15 sec
■ Limit values 0 to 150 sec
■ Step value 1 sec
To define the time delay, proceed as follows:
1 Enter the list of user parameters.
Parameter code :d appears on the display.
2 Select parameter code c7 using the A and/or Z key.
Parameter code c7 appears on the display.
3 Press the R key to switch to the parameter value.
4 Select the appropriate setting using the A and/or Z key.
5 Press the R key to return to the list of parameter codes.
6 To adjust or to consult other user parameters before saving themodifications, select another user parameter using the A and/or Z key and then repeat from instruction 3 onwards.
7 To save the modifications, press the E key. To cancel themodifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the listof user parameters and returns to normal operation, displayingthe inlet water temperature.In the second case, the display starts flashing. Approximately40 seconds later, the controller leaves the list of userparameters without saving the modifications. The inlet watertemperature reappears on the display.
Defining the time delay between unit and pump shutdown
User parameter c8 allows you to define the time delay between theunit shutdown and the pump shutdown, more specifically the periodduring which the pump will still be active after the unit has been shutdown. The default, limit and step values for the time delay are:
■ Default value 0 min
■ Limit values 0 to 150 min
■ Step value 1 min
To define the time delay, proceed as follows:
1 Enter the list of user parameters.
Parameter code :d appears on the display.
2 Select parameter code c8 using the A and/or Z key.
3 Press the R key to switch to the parameter value.
4 Select the appropriate setting using the A and/or Z key.
5 Press the R key to return to the list of parameter codes.
6 To adjust or to consult other user parameters before saving themodifications, select another user parameter using the A and/or Z key and then repeat from instruction 3 onwards.
7 To save the modifications, press the E key. To cancel themodifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the listof user parameters and returns to normal operation, displayingthe inlet water temperature.In the second case, the display starts flashing. Approximately40 seconds later, the controller leaves the list of userparameters without saving the modifications. The inlet watertemperature reappears on the display.
Defining the timer threshold for maintenance warning
User parameter cb allows you to define a timer threshold (runninghours of the compressor) after which the controller will generate amaintenance warning or request. The default, limit and step valuesfor the timer threshold are:
■ Default value 0 hours
■ Limit values 0 to 10,000 hours
■ Step value 100 hours
EUWA(*)5~24KAZW1Packaged air-cooled water chillers4PW17895-1C
Installation and operation manual
12
To define the timer threshold, proceed as follows:
1 Enter the list of user parameters.
Parameter code :d appears on the display.
2 Select parameter code cb using the A and/or Z key.
3 Press the R key to switch to the parameter value.
4 Select the appropriate setting using the A and/or Z key.
5 Press the R key to return to the list of parameter codes.
6 To adjust or to consult other user parameters before saving themodifications, select another user parameter using the A and/or Z key and then repeat from instruction 3 onwards.
7 To save the modifications, press the E key. To cancel themodifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the listof user parameters and returns to normal operation, displayingthe inlet water temperature.In the second case, the display starts flashing. Approximately40 seconds later, the controller leaves the list of userparameters without saving the modifications. The inlet watertemperature reappears on the display.
Enabling or disabling the buzzer
When an alarm is detected, the buzzer is activated for the perioddefined by user parameter p4. The default, limit and step values forthe activation period are:
■ Default value 1 min
■ Limit values 0 to 15 min
0 buzzer disabled
15 buzzer active until muted by the user
■ Step value 1 min
To enable the buzzer for a certain period or to disable the buzzer,proceed as follows:
1 Enter the list of user parameters.
Parameter code :d appears on the display.
2 Select parameter code p4 using the A and/or Z key.
3 Press the R key to switch to the parameter value.
4 Select the appropriate setting using the A and/or Z key.
5 Press the R key to return to the list of parameter codes.
6 To adjust or to consult other user parameters before saving themodifications, select another user parameter using the A and/or Z key and then repeat from instruction 3 onwards.
7 To save the modifications, press the E key. To cancel themodifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the listof user parameters and returns to normal operation, displayingthe inlet water temperature.
In the second case, the display starts flashing. Approximately40 seconds later, the controller leaves the list of userparameters without saving the modifications. The inlet watertemperature reappears on the display.
Selecting local or remote on/off control
User parameter h7 in combination with the remote on/off switch(installed by the customer) allows the user to switch the unit onwithout using the I key on the controller.
■ When user parameter h7 is set to 0 (= No), the unit can only beswitched on by means of the I key on the controller.
■ When user parameter h7 is set to 1 (= Yes), the unit can be switchedon by means of the remote on/off switch and the I key on thecontroller.
To select local or remote on/off control, proceed as follows:
1 Enter the list of user parameters.
Parameter code :d appears on the display.
2 Select parameter code h7 using the A and/or Z key.
3 Press the R key to switch to the parameter value.
4 Select the appropriate setting using the A and/or Z key.
5 Press the R key to return to the list of parameter codes.
6 To adjust or to consult other user parameters before saving themodifications, select another user parameter using the A and/or Z key and then repeat from instruction 3 onwards.
7 To save the modifications, press the E key. To cancel themodifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the listof user parameters and returns to normal operation, displayingthe inlet water temperature.In the second case, the display starts flashing. Approximately40 seconds later, the controller leaves the list of userparameters without saving the modifications. The inlet watertemperature reappears on the display.
Locking the controller keyboard
Once user parameter h9 is set to 0, the following advanced featurescan no longer be carried out by means of the controller:
■ modifying direct and user parameters (parameters can be displayedbut not modified),
■ resetting the timers.
When user parameter h9 is set to 1, the above-described advancedfeatures can be carried out using the controller.
To lock or unlock the controller keyboard, proceed as follows:
1 Enter the list of user parameters.
Parameter code :d appears on the display.
2 Select parameter code h9 using the A and/or Z key.
3 Press the R key to switch to the parameter value.
4 Select the appropriate setting using the A and/or Z key.
5 Press the R key to return to the list of parameter codes.
6 To adjust or to consult other user parameters before saving themodifications, select another user parameter using the A and/or Z key and then repeat from instruction 3 onwards.
NOTE If the unit is always working in normal conditions, nospecific maintenance is requested. In this case thewarning function can be disabled by setting parametercb to 0.
Key on the controller Remote On/off switch UNIT RESULT
ON ON ON
ON OFF OFF
OFF ON OFF
OFF OFF OFF
Installation and operation manual
13EUWA(*)5~24KAZW1
Packaged air-cooled water chillers4PW17895-1C
7 To save the modifications, press the E key. To cancel themodifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the listof user parameters and returns to normal operation, displayingthe inlet water temperature.In the second case, the display starts flashing. Approximately40 seconds later, the controller leaves the list of userparameters without saving the modifications. The inlet watertemperature reappears on the display.
Defining the unit's serial address
To control the unit from a supervisory system, an address card(optional module) should be installed in the unit. The unit's serialaddress required for communication with the supervisory system isdefined by parameter ha. The default, limit and step values for theserial address are:
■ Default value 1
■ Limit values 1 to 16
■ Step value 1
To define the unit's serial address, proceed as follows:
1 Enter the list of user parameters.
Parameter code :d appears on the display.
2 Select parameter code ha using the A and/or Z key.
3 Press the R key to switch to the parameter value.
4 Select the appropriate setting using the A and/or Z key.
5 Press the R key to return to the list of parameter codes.
6 To adjust or to consult other user parameters before saving themodifications, select another user parameter using the A and/or Z key and then repeat from instruction 3 onwards.
7 To save the modifications, press the E key. To cancel themodifications wait approximately 40 seconds.
In the first case, the controller saves the changes, leaves the listof user parameters and returns to normal operation, displayingthe inlet water temperature.
In the second case, the display starts flashing. Approximately40 seconds later, the controller leaves the list of userparameters without saving the modifications. The inlet watertemperature reappears on the display.
TROUBLESHOOTING
This section provides useful information for diagnosing andcorrecting certain troubles which may occur in the unit.
Before starting the trouble shooting procedure, carry out a thoroughvisual inspection of the unit and look for obvious defects such asloose connections or defective wiring.
Before contacting your local Daikin dealer, read this chapter carefully,it will save you time and money.
When a safety device was activated, stop the unit and find out whythe safety device was activated before resetting it. Under nocircumstances safety devices may be bridged or changed to a valueother than the factory setting. If the cause of the problem cannot befound, call your local Daikin dealer.
Symptom 1: The unit does not start, but the T LED lights up
Symptom 2: The unit does not start, but the T LED is flashing
Symptom 3: The unit does not start and the T LED does not light up
When carrying out an inspection on the switch box of theunit, always make sure that the main switch of the unit isswitched off.
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting is not correct.
Check the controller setpoint.
Power supply failure. Check the voltage on the supply panel.
Blown fuse or interrupted protection device.
Inspect fuses and protection devices. Replace by fuses of the same size and type (refer to chapter "Electrical specifications" on page 3).
Loose connections. Inspect connections of the field wiring and the internal wiring of the unit. Tighten all loose connections.
Shorted or broken wires. Test circuits using a tester and repair if necessary.
POSSIBLE CAUSES CORRECTIVE ACTION
The remote ON/OFF input is enabled and the remote switch is off.
Put the remote switch on or disable the remote ON/OFF input.
The anti-recycling timer is still active. The cicuit can only start up after approximately 4 minutes.
The guard timer is still active. The circuit can only start up after approximately 1 minute.
POSSIBLE CAUSES CORRECTIVE ACTION
One of the following safety devices is activated:• Reverse phase protector• Overcurrent relay (K*S)• Discharge thermal protector (Q*D)• Evaporating temperature• Thermostat (S*T)• Flow switch (S10L)• High pressure switch (S*HP)
Check on the controller and refer to symptom 4 "One of the following safety devices is activated" on page 15. Refer to the explanation of the digital controller in the chapter "Resetting alarms" on page 10.
The unit is in anti-freeze alarm. Check on the controller and refer to symptom 4 "One of the following safety devices is activated" on page 15. Refer to the explanation of the digital controller in the chapter "Resetting alarms" on page 10.
The remote ON/OFF input is enabled and the remote switch is off.
Put the remote switch on or disable the remote ON/OFF input.
The keyboard is locked. The user parameter h9 is set to 0.
Unlock the controller keyboard.
EUWA(*)5~24KAZW1Packaged air-cooled water chillers4PW17895-1C
Installation and operation manual
14
Symptom 4: One of the following safety devices is activated
Symptom 5: Unit stops soon after operation
Symptom 6: Unit runs continuously and the water temperature remains higher, respectively lower than the temperature set on the controller
Symptom 7: Excessive noises and vibrations of the unit
Symptom 8: Water flow is too low
Symptom 9: Pump is making noise (cavitation)
MAINTENANCE
In order to ensure optimal availability of the unit, a number of checksand inspections on the unit and the field wiring have to be carried outat regular intervals.
If the unit is used for air conditioning application, the describedchecks must be executed at least once a year. In case the unit isused for other applications, the checks must be executed every 4months.
Symptom 4.1: Overcurrent relay of compressor
POSSIBLE CAUSES CORRECTIVE ACTION
Failure of one of the phases. Check fuses on the supply panel or measure the supply voltage.
Voltage too low. Measure the supply voltage.
Overload of motor. Reset. If the failure persists, call your local Daikin dealer.
RESET Push the red button on the over-current relay inside the switch box. The controller still needs to be reset.
Symptom 4.2: Low pressure switch
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow to water heat exchanger too low.
Increase the water flow.
Shortage of refrigerant. Check for leaks and refill refrigerant, if necessary.
Unit is working out of its operation range.
Check the operation conditions of the unit.
Inlet temperature to the water heat exchanger is too low.
Increase the inlet water temperature.
Flow switch is not working or no water flow.
Check the flow switch and the water pump.
RESET After pressure rise, the low pressure switch resets automatically, but the controller still needs to be reset.
Symptom 4.3: High-pressure switch
POSSIBLE CAUSES CORRECTIVE ACTION
Condenser fan does not operate properly.
Check that the fans turn freely. Clean if necessary.
Dirty or partially blocked condenser. Remove any obstacle and clean condenser coil using brush and blower.
Inlet air temperature of the condenser is too high.
The air temperature measured at the inlet of the condenser may not exceed 43°C.
RESET After pressure decrease, the high pressure switch resets automatically, but the controller still needs to be reset.
Symptom 4.4: Fan thermal protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Mechanical failure (fan is blocked). Check that the fan rotates freely.
Air flow in the unit too low or outdoor temperature too high.
Clean the air heat exchanger properly.
RESET After temperature decrease, the thermal protector is reset automatically.
If the protector is activated frequently, replace the motor or call your local Daikin dealer.
Symptom 4.5: Reverse phase protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Two phases of the power supply are connected in the wrong phase position.
Invert two phases of the power supply (by licensed electrician).
One phase is not connected properly.
Check the connection of all phases.
RESET After inverting two phases or fixing the power supply cables properly, the protector is reset automatically, but the controller still needs to be reset.
Symptom 4.6: Discharge thermal protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Unit is working outside the operation range.
Check the operation condition of the unit.
RESET After temperature decrease, the thermal protector resets automatically but the controller still needs to be reset.
Symptom 4.7: Flow switch is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow too low. Check the water pump.
RESET After finding the cause, the flow switch is reset automatically, but the controller still needs to be reset.
POSSIBLE CAUSES CORRECTIVE ACTION
One of the safety devices is activated.
Check safety devices (refer to "One of the following safety devices is activated" on page 15).
Voltage is too low. Test the voltage in the supply panel and, if necessary, in the electrical compartment of the unit (voltage drop due to supply cables is too high).
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting on the controller is too low.
Check and adjust the temperature setting.
The heat production in the water circuit is too high.
The cooling capacity of the unit is too low. Call your local Daikin dealer.
Water flow is too high. Recalculate the water flow.
POSSIBLE CAUSES CORRECTIVE ACTION
Unit has not been fixed properly. Fix the unit as described in the installation manual.
POSSIBLE CAUSES CORRECTIVE ACTION
Shut-off valve is not completely open.
Open the shut-off valve completely.
There is air in the system. Purge the air.
The filter is not clean. Clean the filter.
There is an obstruction in the circuit. Remove the obstruction.
Pressure regulating valve is not enough open.
Open more.
The chosen pump has not enough capacity.
Check ∆p over pump.Install heavier pump.
POSSIBLE CAUSES CORRECTIVE ACTION
Shut-off valve is not completely open.
Open completely.
There is air in the system. Purge air.
The filter is not clean. Clean filter.
Pre-pressure and required water pressure are not according to installation instructions or expansion vessel is broken.
Recalculate the values as described in chapter "Setting the pre-pressure of the expansion vessel" on page 6 and "Charging water" on page 6.
Before carrying out any maintenance or repair activity,always switch off the circuit breaker on the supply panel,remove the fuses or open the protection devices of the unit.
Do never clean the unit with water under pressure.
Installation and operation manual
15EUWA(*)5~24KAZW1
Packaged air-cooled water chillers4PW17895-1C
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by theKyoto Protocol.
Refrigerant type: R407C
GWP(1) value: 1652.5
(1) GWP = global warming potential
Periodical inspections for refrigerant leaks may be requireddepending on European or local legislation. Please contact your localdealer for more information.
Maintenance activities
1 Air heat exchanger
Remove dust and any other contaminant from the coil fins usinga brush and a blower. Blow from the inside of the unit. Take carenot to bend or damage the fins.
2 Field wiring and power supply
■ Check the power supply voltage on the local supply panel.The voltage must correspond to the voltage marked on theidentification label of the unit.
■ Check the connections and make sure they are properlyfixed.
■ Check the proper operation of the circuit breaker and theearth leak detector provided on the local supply panel.
3 Internal wiring of the unit
Visually check the switch box on loose connections (terminalsand components). Make sure that the electrical components arenot damaged or loose.
4 Earth connection
Make sure that the earth wires are still connected properly andthat the earth terminals are tightened.
5 Refrigerant circuit
■ Check for leaks inside the unit. In case a leak is detected, callyour local Daikin dealer.
■ Check the working pressure of the unit. Refer to paragraph"Switching the unit on" on page 9.
6 Compressor
■ Check on oil leaks. If there is an oil leak, call your local Daikindealer.
■ Check for abnormal noises and vibrations. If the compressoris damaged, call your local Daikin dealer.
7 Fan motor
■ Clean the cooling ribs of the motor.
■ Check on abnormal noises. If the fan or motor are damaged,call your local Daikin dealer.
8 Water supply
■ Check if the water connection is still well fixed.
■ Check the water quality (refer to the installation manual of theunit for specifications of the water quality).
9 Flowswitch
Make sure that there is no dirt accumulated on the paddle of theflowswitch
10 Water filter
Clean the water filter.
Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of otherparts must be done in accordance with relevant local and nationallegislation.
The wiring and power supply must be checked by alicensed electrician.
EUWA(*)5~24KAZW1Packaged air-cooled water chillers4PW17895-1C
Installation and operation manual
16
NOTES NOTES
4
4
0.00
100.00
200.00
250.00
150.00
50.00
300.00
400.00
350.00
450.00
0.00 50.00 100.00 150.00 200.00 250.00
WF (l/min)
SP (kPa)
1
2
4
3
5
5
5
0.00
50.00
100.00
150.00
200.00
250.00
300.00
350.00
0.00 20.00 40.00 60.00 80.00 100.00 120.00 160.00140.00 180.00 200.00
1
2
3
5
6
7
4
WF (l/min)
ESP (kPa)
6
6
1.00
10.00
100.00
1000.00
1.00 10.00 100.00 100.00
1
2
3 5
6
7
4
WFE (l/min)
PD (kPa)
7
7
Pr= 1.4Pr= 1.3Pr= 1.5Pr= 1.7
Pr= 1.6Pr=
1.8Pr= 1.
9Pr= 2
.0Pr=
2.1
Pr=
2.2
0.50.60.70.80.91.01.11.21.31.41.51.61.71.81.92.0
0-23456789
1011121314151617
280260240220200180160140120100A= Water volume (l)
D= Factory setting 1.5 bar
B= In
stal
latio
n he
ight
diff
eren
ce (m
)
C= P
re-p
ress
ure
(bar
)
Zandvoordestraat 300, B-8400 Oostende, Belgium 4PW17895-1C