illinois tollway m-its base sheet revisions

18
Illinois Tollway M-ITS Base Sheet Revisions Section M Base Sheet Drawings Drawing Modification Summary Effective: 2021-03-01 New Sheet Retired Standard M-ITS-1000 M-ITS-1001 M-ITS-1103 M-ITS-1104 M-ITS-1200 to M-ITS-1213 M-ITS-1217 M-ITS-1300 M-ITS-1302 DMS Front Access-Butterfly Electrical Plan . Revised asembly details for DMS Butterfly Type 2 Front Access pushed further away to the edge of the DMS clears Lane 1 . Revised to show the fiber optic conduit and power conduit interface with the ITS Enclosure for location and size . Added Note 13: Fiber cable shall run straight down from the Gator patch through the left most conduit. Power cable shall be pulled through the conduit to the right of the fiber conduit. No slack shall be placed in the cabinet, slack shall be put in power and fiber optic handholes . Revised layout to remove Cohu Surge Suppressor Part AS . Revised details for Part V to remove dash line for DITEK surge suppressor . Revised description for Item V to remove Cohu camera . Revised Item AQ to remove reference to Cohu PoE power injector . Remove Item AS for Cohu PoE injector not required anymore . Revised Note 4: to say Not used Roadway Weather Information System (ITS)-Series 1300 RWIS Pole, Sensor Mounting Detail . Added Note 8: Wind sensor can be installed on the secondary pole it primary pole is close to tree line . Added Note 9: All cables installed in a pole shall use a grommet to connect to ITS device installed on the pole Pole Assembly (ITS)-Series 1000 Dynamic Message Sign (ITS)-Series 1100 . Sheet 1of3: Added title for one section detail; Added note on wires from solar panels to battery box then to ITS enclosure then Cat6 cables to ITS devices installed on the ITS pole . Sheet 2of3: Added title for ITS Disconnect Switch Cast-in place . Sheet 3of3: Added new assembly detail for ITS Disconnect Switch Pre-cast (simplified installation) DMS Front Access-Cantilever Electrical Plan Elevation Views Pole Mounted ITS Element Assembly General Notes Pole Mounted ITS Element Assembly . Added Note 22.: Cables shall enter poles through a gromet. Gromet size shall be chosen so that the center hole forms a water tight seal around the cables Cabinet Wiring (ITS)-Series 1200 M-ITS-1200: Cabinet Layout and Wirring ITS Pole Mounted Enclosure (1-MVDS) M-ITS-1201: Cabinet Layout and Wirring ITS Pole Mounted Enclosure (2-MVDS) M-ITS-1202: Cabinet Layout and Wirring ITS Pole Mounted Enclosure (3-MVDS) M-ITS-1203: Cabinet Layout and Wirring ITS Pole Mounted Enclosure (1-CCTV camera) M-ITS-1204: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (1-CCTV and 1-MVDS) M-ITS-1205: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (1-CCTV camera and 2-MVDS) M-ITS-1206: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (1-CCTV and 3-MVDS) M-ITS-1207: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (2-CCTV cameras) M-ITS-1208: Caninet Layout and Wiring ITS Pole Mounted Enclosure (2-CCTV Cameras and 1-MVDS) M-ITS-1209: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (2-CCTV cameras and 2-MVDS) M-ITS-1210: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (2-CCTV cameras and 3-MVDS) M-ITS-1211: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (1-MVDS) Solar Generator and FOC M-ITS-1212: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (2-MVDS) Solar Generator and FOC M-ITS-1213: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (3-MVDS) Solar Generator and FOC . Revised assembly details for DMS Type 2 Cantilever pushed further away so the edge of the DMS clears Lane 1 Cabinet Wiring Diagram In Pavement Detection System AP, PoE and Injector ITS Assembly . Revised to show the fiber optic conduit and power conduit interface with the ITS Enclosure for location and size . Added Note 13: Fiber cable shall run straight down from the Gator patch through the left most conduit. Power cable shall be pulled through the conduit to the right of the fiber conduit. No slack shall be placed in the cabinet, slack shall be put in power and fiber optic handholes . Added Note to Designer: The DSE shall specify the Gator Patch length per site Typical RWIS Site Installation Plan . Added Note 5: Note to Designer: In the event the Primary and Secondary poles cannot be installed within the 40 foot maximum radius of the bridge deck, the DSE shall consult with the Tollway and GEC on an alternate placement solution . Added Note 6: Note to Designer: Installation of the Primary and Secondary pole for bridge installation: pole to be installed near immediate entrance of the bridge so non-invasive laser temperature sensor can monitor bridge deck temperature and bridge approach temperature

Upload: others

Post on 30-May-2022

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Illinois Tollway M-ITS Base Sheet Revisions

Illinois Tollway M-ITS Base Sheet Revisions

Section M Base Sheet Drawings

Drawing Modification Summary Effective: 2021-03-01

New Sheet Retired Standard

M-ITS-1000

M-ITS-1001

M-ITS-1103

M-ITS-1104

M-ITS-1200

to

M-ITS-1213

M-ITS-1217

M-ITS-1300

M-ITS-1302

DMS Front Access-Butterfly Electrical Plan

. Revised asembly details for DMS Butterfly Type 2 Front Access pushed further away to the edge of the DMS clears Lane 1

. Revised to show the fiber optic conduit and power conduit interface with the ITS Enclosure for location and size

. Added Note 13: Fiber cable shall run straight down from the Gator patch through the left most conduit. Power cable shall be pulled

through the conduit to the right of the fiber conduit. No slack shall be placed in the cabinet, slack shall be put in power and fiber optic

handholes

. Revised layout to remove Cohu Surge Suppressor Part AS

. Revised details for Part V to remove dash line for DITEK surge suppressor

. Revised description for Item V to remove Cohu camera

. Revised Item AQ to remove reference to Cohu PoE power injector

. Remove Item AS for Cohu PoE injector not required anymore

. Revised Note 4: to say Not used

Roadway Weather Information System (ITS)-Series 1300

RWIS Pole, Sensor Mounting Detail

. Added Note 8: Wind sensor can be installed on the secondary pole it primary pole is close to tree line

. Added Note 9: All cables installed in a pole shall use a grommet to connect to ITS device installed on the pole

Pole Assembly (ITS)-Series 1000

Dynamic Message Sign (ITS)-Series 1100

. Sheet 1of3: Added title for one section detail; Added note on wires from solar panels to battery box then to ITS enclosure then Cat6

cables to ITS devices installed on the ITS pole

. Sheet 2of3: Added title for ITS Disconnect Switch Cast-in place

. Sheet 3of3: Added new assembly detail for ITS Disconnect Switch Pre-cast (simplified installation)

DMS Front Access-Cantilever Electrical Plan

Elevation Views Pole Mounted ITS Element Assembly

General Notes Pole Mounted ITS Element Assembly

. Added Note 22.: Cables shall enter poles through a gromet. Gromet size shall be chosen so that the center hole forms a water tight

seal around the cables

Cabinet Wiring (ITS)-Series 1200

M-ITS-1200: Cabinet Layout and Wirring ITS Pole Mounted Enclosure (1-MVDS)

M-ITS-1201: Cabinet Layout and Wirring ITS Pole Mounted Enclosure (2-MVDS)

M-ITS-1202: Cabinet Layout and Wirring ITS Pole Mounted Enclosure (3-MVDS)

M-ITS-1203: Cabinet Layout and Wirring ITS Pole Mounted Enclosure (1-CCTV camera)

M-ITS-1204: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (1-CCTV and 1-MVDS)

M-ITS-1205: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (1-CCTV camera and 2-MVDS)

M-ITS-1206: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (1-CCTV and 3-MVDS)

M-ITS-1207: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (2-CCTV cameras)

M-ITS-1208: Caninet Layout and Wiring ITS Pole Mounted Enclosure (2-CCTV Cameras and 1-MVDS)

M-ITS-1209: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (2-CCTV cameras and 2-MVDS)

M-ITS-1210: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (2-CCTV cameras and 3-MVDS)

M-ITS-1211: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (1-MVDS) Solar Generator and FOC

M-ITS-1212: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (2-MVDS) Solar Generator and FOC

M-ITS-1213: Cabinet Layout and Wiring ITS Pole Mounted Enclosure (3-MVDS) Solar Generator and FOC

. Revised assembly details for DMS Type 2 Cantilever pushed further away so the edge of the DMS clears Lane 1

Cabinet Wiring Diagram In Pavement Detection System AP, PoE and Injector ITS Assembly

. Revised to show the fiber optic conduit and power conduit interface with the ITS Enclosure for location and size

. Added Note 13: Fiber cable shall run straight down from the Gator patch through the left most conduit. Power cable shall be pulled

through the conduit to the right of the fiber conduit. No slack shall be placed in the cabinet, slack shall be put in power and fiber optic

handholes

. Added Note to Designer: The DSE shall specify the Gator Patch length per site

Typical RWIS Site Installation Plan

. Added Note 5: Note to Designer: In the event the Primary and Secondary poles cannot be installed within the 40 foot maximum radius

of the bridge deck, the DSE shall consult with the Tollway and GEC on an alternate placement solution

. Added Note 6: Note to Designer: Installation of the Primary and Secondary pole for bridge installation: pole to be installed near

immediate entrance of the bridge so non-invasive laser temperature sensor can monitor bridge deck temperature and bridge approach

temperature

Page 2: Illinois Tollway M-ITS Base Sheet Revisions

Illinois Tollway Base Sheet Revisions

Section M Base Sheet Drawings

Drawing Modification Summary Effective: 2020-03-01

M-ITS-1400

M-ITS-1500

M-ITS-1503

M-ITS-1700

M-ITS-1701

M-ITS-1815

M-ITS-1900

M-ITS-2000

M-ITS-2100

M-ITS-2101

. Added material type for ITS conduit attached to bridge: PVC coated steel or FRE conduit per plan

100 FT. Monopole Closed Circuit Television (CCTV) Camera Tower

. Sheet 1of4: Added details for ITS and support for ITS Enclosure foundation: 16" Dia. X 4' @ 3000PSI Circular Concrete Foundation

. Sheet 4of4: Added details to install the ITS Enclosure and ITS Disconnect Switch onto the concrete slab of 100 foot monotube

100 FT. Monopole (ITS)-Series 2000

. Added wires for second pair of flashing lights and connection to the circuit breakers

. Added Item AT: ELTEC FS-4 DC Flasher

. Added Item AU: 9 PIN Harness for FS-4

. Rved dashline for DITEK surge supressor for Cohu camera

. Revised Item V: removed reference to DITEK for Cohu camera

. Revised Item AS to say N/A

Conduit Details at Integral Abutment Bridge (ITS)-Series 1900

Conduit Details at Integral Abutment Bridge with MSE Wall (Sheet 3)

Flashing Sign Beacon Installation Breakaway Electrical Detail

IPDC Facility (ITS)-Series 1800

IPDC and Combination Plaza/IPDC Concrete Foundation

. Added new sheet for IPDC and Combination Plaza/IPDC Concrete Foundation details

. Added details for power cable disconnect box Breakaway

. Added details for the 4 flashing lights installed on the static sign with flashing sequence and light mounting details onto the sign

. Added Note 1: see plans for required conductor sizes

. Added Note 2: All three conductors shall be in one harness

. Added Note 3: As an alternative to the conduit body on fondation, use thermoplastic junction boxes

. Added Note 4: Slack in line side cable shall be provided in handhole

. Added Note to Designer: Install new CCTV within 500 feet upstream of the static beacon sign

. Added note to Designer: If an existing ITS enclosure lies within the immediate proximity of the flashing sign then power can be

connected to that enclosure, otherwise install a new ITS enclosure near the flashing sign

Cabinet Layout and Wiring ITS Pole Mounted Enclosure

Flashing Sign Beacon (ITS)-Series 1700

. Added note to Designer: The 2 CCTV shall be placed on the leg facing the roadway with a clear field of view

. Added Note 23: The CCTV cameras shall be mounted on the same tower leg with an Axis T92B62 mounting arm with T94A01D

pendant kit, or equivalent as approved by the engineer. There will be 24in vertical spacing between the cameras

Solar Powered Generator (ITS)-Series 1400

Solar Power Generator Details

. Added Note to Designer: The simplified solar power arrangement shall only be used for a maximum of 3 MVDS. For all other

arrangments use the 1400 Series

ITS Details Tower Mount Camera Details

Tower Mounted CCTV (ITS)-Series 1500

. Removed details for Part AS: removed PoE power injector

. Remove Item AS: removed reference to Cohu PoE injector

Video Power Junction Box (ITS)-Series 2100

Video Power Junction Box Model A: 4 PoE CCTV arrangment without communication switch

. New drawing created to standardize Video Power Junction Box arrangment - With Cisco 4000 switch when the box is installed at a

distance greater than 300 feet from the Cisco switch in the Plaza Communication Room

Video Power Junction Box Model B: 4 PoE CCTV arrangment Cosco 4000 switch

. New drawing created to standardize Video Power Junction Box arrangment - Without Cisco switch when the box is installed and can

use Cat 6 cables when distance is less than 300 feet from Plaza Communication room

Page 3: Illinois Tollway M-ITS Base Sheet Revisions

SYMBOL CABLE DESCRIPTION REMARKS

1-1/C #6 (GRD)

NOTE 1

1-4/C #12 SHLD

1-3PR #22 SHLD

1-3/C #12 SHLD

1-6PR #22 SHLD

1-1/C #8 (GRD)

1-3/C #16 SHLD

1-1/C #4/0 (GRD BUS)

NOTE 2

NOTE 1 & 2

NOTE 1 & 2

NOTE 3

NOTE 1

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

1-1/C #2 (GRD)

NOTE 4

NOTE 4

1-9/C #12 SHLD

1-4PR #24 (CATEGORY 6)

1PR #22 SHLD

4

3/4

1-1/C #6 (GRD)

1-1/C #10 (GRD)

3-1/C #10

CABLE DESCRIPTIONCONDUIT

SIZE(INCHES)

REMARKSSYMBOL

101

102

103

104

105

106

107

108

109

110

1-1/C #10 (GRD)

4-1/C #103/4

1-1/C #12 (GRD)

2-1/C #12

1-1/C #12 (GRD)

3-1/C #12

1

3-1/C #3/0

3-1/C #3/0

1-1/C #4 (GRD) 3

2

NOTE 5

NOTE 5

NOTE 5

NOTE 5

NOTE 6

112

111

113

114

1

1ACCESS

SECURITY-CARD

1-1/C #12 (GRD)

4-1/C #12

1-1/C #12 (GRD)

5-1/C #12

1-1/C #12 (GRD)

5-1/C #12

1-1/C #12 (GRD)

6-1/C #12

1-1/C #12 (GRD)

7-1/C #12

1-1/C #8 (GRD)

2-1/C #8

4

5

6

7

8

9

10

1-1/C #8 (GRD)

2-1/C #2

1-1/C #8 (GRD)

2-1/C #4

1-1/C #8 (GRD)

2-1/C #6

2-1/C #2/O

2-1/C #4/O

2-1/C 250 Kcmil

1-1/C #4 (GRD)

2-1/C 350 Kcmil

1-1/C #2 (GRD)

1-1/C #2 (GRD)

5.

6.

1

3-1/C #1/0

7.

1-1/C #1 (GRD)

115

116

1-1/C #2 (GRD)

3-1/C #2

1-1/C #8 (GRD)

2-1/C #2

2

2

2-1/C #12, 1-1/C #12 (GRD)

6-1/C #22 SHLD

1-9/C #22 IND SHLD

1-4PR #24 (RS-422)

NOTE 2DESIGNER

NOTE 2DESIGNER

NOTE 2DESIGNER

NOTE 2DESIGNER

NOTE 2DESIGNER

NOTE 2DESIGNER

NOTE 2DESIGNER

ELECTRICAL WORK" (JT130754).

UNDER THE ITEM "INTERMEDIATE POWER DISTRIBUTION AND COMMUNICATION FACILITY

REQUIRED TO PROVIDE A COMPLETE AND OPERATIONAL FACILITY WILL BE PAID FOR

POWER DISTRIBUTION AND COMMUNICATION FACILITY" (JT130752). ELECTRICAL WORK

BUILDING FOUNDATION WILL BE PAID FOR UNDER "CONCRETE FOUNDATION, INTERMEDIATE

"INTERMEDIATE POWER DISTRIBUTION AND COMMUNICATION FACILITY" (JT130750). THE

THE IPDC FACILITY PREFABRICATED BUILDING WILL BE PAID FOR UNDER THE ITEM

EXPOSED CONDUIT SHALL BE 1". EMBEDDED OR UNDERGROUND CONDUIT SHALL BE 2".

EXPOSED CONDUIT SHALL BE 3/4". EMBEDDED OR UNDERGROUND CONDUIT SHALL BE 1".

D-LAN-CAT-.6+.

SHALL BE PHOENIX CONTACT (OR EQUIVALENT) DATATRAB

D-UFB-V11/BS-B. THE TVSS ADAPTER FOR CATEGORY 6 CABLES

SHALL BE PHOENIX CONTACT (OR EQUIVALENT) DATATRAB

TO THE CISCO SWITCH. THE TVSS ADAPTER FOR RS-422 CABLES

IN-LINE 485 ADAPTERS MUST BE INSTALLED AT ALL CONNECTIONS

CATEGORY 6 CABLES ENTERING THE IPDC FACILITY.

PROVIDE SURGE PROTECTION ADAPTERS FOR ALL RS-422 AND 4.

(K-2) STANDARD.

FOR CONTROL USE SHALL BE COLOR CODED PER ICEA-NEC

MULTI-CONDUCTOR SHIELDED CABLE #14 AWG THROUGH #18 AWG3.

ELECTRICAL WORK."

"INTERMEDIATE POWER DISTRIBUTION AND COMMUNICATION FACILITY

CODED AS SPECIFIED IN THE ILLINOIS TOLLWAY SPECIAL PROVISION

MULTI-CONDUCTOR SHIELDED CABLE #12 AWG SHALL BE COLOR2.

COATED RIGID STEEL.

EMBEDDED CONDUIT IS 1". EMBEDDED CONDUIT SHALL BE PVC

MINIMUM SIZE OF EXPOSED CONDUIT IS ƒ". MINIMUM SIZE OF1.

M-ITS-1800

DATE

03-31-2017

GROUNDING CABLE/CONDUIT SCHEDULE

IPDC FACILITY COMMUNICATIONS AND

CABLE/CONDUIT SCHEDULE

IPDC FACILITY POWER

SCHEDULES AND NOTES

IPDC FACILITY CABLE/CONDUIT

NOTES TO DESIGNER

LOCATED A MAXIMUM OF 0.75 MILE FROM THE IPDC FACILITY.

AND REMOTE GANTRY PANELS. GANTRY PANELS SHALL BE

REQUIREMENTS ARE DEPENDENT ON PLACEMENT OF CAMERAS

REMOTE GANTRY PANELS ARE REPRESENTATIVE. ACTUAL

CABLE/CONDUIT REQUIREMENTS SHOWN TO CAMERAS AND

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

NOTES:

Page 4: Illinois Tollway M-ITS Base Sheet Revisions

MAIN CIRCUIT BREAKER

AUTOMATIC TRANSFER SWITCH

MAIN LUG ONLY

ABOVE FINISH FLOOR

TERMINAL STRIP INTERCONNECT CENTER

GENERATOR CONTROL SWITCH

MAIN DISTRIBUTION PANEL

MANUAL TRANSFER SWITCH

JUNCTION BOX

UNINTERRUPTIBLE POWER SUPPLY

GROUND FAULT INTERRUPTER

MAIN SERVICE DISCONNECT

MULTI-MODE FIBER

HANDHOLE

1. ALL TYPE 'B' FIXTURES SHALL BE MOUNTED AT THE SAME

ANGLE ADAPTER

20A, 120V

20A, 120V

400A, 600V

30A, 600V

SINGLE-POLE SWITCH 20A, 120V

18" AS NOTED

3'-0" ABOVE

3'-0" ABOVE

GRADE

GRADE

4'-0"

GRADE

3'-0" ABOVE

HUBBELL #HBL1221

HUBBELL #HBL5362

3P, 3W, WEATHERPROOF RECEPTACLE

WITH SPRING DOOR, BACK BOX, &

3P, 3W, WEATHERPROOF RECEPTACLE

CROUSE-HINDS "ARKTITE"

CROUSE-HINDS "ARKTITE"

SERIES #AREX40318

SERIES #ARE3313WITH SPRING DOOR & BACK BOX

120 V

120 V

HOLOPHANE

FINISHED FLOOR

MOUNT 8' ABOVE

FINISHED GRADE

NOTE 1

EMERGENCY LIGHT UNIT WITH 2-1 WATT, 120 VFINISHED FLOOR

MOUNT 8' ABOVE

MOUNT 9'-0" ABOVE

SYMBOL DESCRIPTION VOLTAGE LAMPS REMARKS

LIGHTING FIXTURE SCHEDULE

MFR. AND CAT. NO.

SYMBOL RATING MFR. AND CAT. NO. MOUNTING HEIGHT

NOTE:ABBREVIATIONS

LED LAMPS

LED

LED2-1 WATT H.E. WILLIAMS

EMER/LED WHTSDT

HUBBELL #GFR5362SGWEATHERPROOF DUPLEX RECEPTACLE

WITH GROUND FAULT PROTECTION

SINGLE MODE FIBER

DUPLEX RECEPTACLE

EXPOSED GROUND CONDUCTOR

GROUND ROD

INDICATES CIRCUIT TURNING UP

HOME RUN TO PANEL AS NOTED

INDICATES CIRCUIT TURNING DOWN

UNDERGROUND CONDUIT OR

CONDUIT IN SLAB

GROUNDING TRIAD

UNDERGROUND GROUND CONDUCTOR

EXPOSED CONDUIT

CABLE DUCT

CONDUIT OR CABLE DUCT

IN CASING

LEGEND

WIRING DEVICE SCHEDULE

DESCRIPTION30A DENOTES 30 AMPERES

PANEL CIRCUIT BREAKER

2P DENOTES 2 POLES

MECHANICALLY HELD LIGHTING COIL

CONTROL RELAY COIL

WITH LIGHTNING PROTECTION

SURGE PROTECTION DEVICE

STANDBY GENERATOR

SELF CONTAINED UTILITY METERING

2PDT DENOTES 2 POLE DOUBLE-THROW

400A DENOTES 400 AMPERES

MANUAL TRANSFER SWITCH

50A DENOTES 50 AMPERES

CIRCUIT BREAKER

DISCONNECT SWITCH

60A DENOTES 60 AMPERES

JUNCTION BOX

3W DENOTES 3 WIRE

2P DENOTES 2 POLE

OR

AUTOMATIC TRANSFER SWITCH (ATS)

N DENOTES NORMAL SOURCE

E DENOTES EMERGENCY SOURCE

L DENOTES LOAD

LEGEND NUMBER FOR CABLE & CONDUIT

(SEE CABLE AND CONDUIT SCHEDULES)

3W DENOTES 3 WIRE

1} DENOTES 1 PHASE

480-120/240V DENOTES VOLTAGE

25 KVA DENOTES TRANSFORMER RATING

TRANSFORMER

SYMBOL

SYMBOL LIST

400 DENOTES 400 AMPERE ATS RATING

QUAD RECEPTACLE 20A, 120V (2) HUBBELL #HBL5362 18" AS NOTED

4' INDUSTRIAL LED FIXTURELED

ATLAS LIGHTING

ILW48LED4D

SURGE PROTECTION DEVICE

SHIELDED

GROUND

SMOKE DETECTOR

EXHAUST FAN

DOOR ALARM SWITCH

M120SFTBWGBZW4GLED10C100040KT3-

LIGHTNING PROTECTION

DESCRIPTION

FIRE ALARM PANEL

INTERMEDIATE POWER DISTRIBUTION AND COMMUNICATION

TRANSIENT VOLTAGE SURGE SUPPRESSION

CLOSED CIRCUIT TELEVISION

ELEVATION WITH A MINIMUM MOUNTING HEIGHT AS INDICATED

COMPACT WALL-MOUNTED LED EXTERIOR FIXTURE WITH

WIRE GUARD & SINGLE FACTORY INSTALLED FUSE

IN THE LIGHTING FIXTURE SCHEDULE.

WEATHERPROOF

VIDEO POWER JUNCTION BOX

IPDC FACILITY INTERIOR LIGHTING

LINE CONDITIONER

M-ITS-1801

MCB

ATS

MLO

AFF

TSIC

GFI

GCS

MDP

MTS

JB

UPS

MSD

SMF

MMF

HH

B

A

C

B

C

GFI

$

WP

G

G

DATE

03-31-2017

WITH LPSPD

60A

50A

2PDT. SW.

400A

2P,3W

400

ATS

25 KVA

1}, 3W

1

L

N E

JB J

WH

30A

2P

G

C

CR

480-120/240

SPD

SHLD

GRD

S

M

LP

FAP

IPDC

TVSS

CCTV

AND EQUIPMENT SCHEDULES

SYMBOL LIST, ABBREVIATIONS

IPDC FACILITY LEGEND,

WP

VPJB

LC

NOTE TO DESIGNER

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

Page 5: Illinois Tollway M-ITS Base Sheet Revisions

3'

4'

4.7'

4.7'6.7' 3.7' 4'

4'

3'

5'

12'

5'

5' 30'

8'

PE

R

RO

AD

WA

Y

PL

AN

SS

HO

UL

DE

R

WID

TH

IPDC FACILITY SITE PLAN

7'3'

6'

4'

4'

4'

DATE

M-ITS-1802

3-01-2019

EXISTING ROW

APPLICABLE

AGGREGATE PAD AS

RETAINING WALL OR

BACK OF SINGLE FACE BARRIER WALL

BACK OF GUTTER

FOUNDATION

GANTRY

HANDHOLE

LIGHTING

HANDHOLE

COMMUNICATION

ITS

EDGE OF SHOULDER

4.7

5'

HANDHOLE

POWER

ITS

SURFACEAGGREGATE

MD

P

MTS

ATS

M M

JB

JB

JB

JB

JB

SS

RACK 1RACK 2RACK 3UPS/LCRACK

BATTERY

HVAC

HVAC

VPJB

UPS-1

SP

D

EQUIPMENT ROOM

FIRE EXTINGUISHER

FAP

4' X 8' WALLBOARD GCS

HVAC CONTROL PANEL

25 KVA TRANSFORMER

LOUVER

EXHAUST

THERMOSTAT

HEATER

ELECTRIC

CHARGER

BATTERY

(BY OTHERS)

DISCONNECT SWITCH

ROADWAY LIGHTING

(BY OTHERS)

ROADWAY LIGHTING UTILITY METER

CAMERA

SECURITY

INTERIOR

TRANSFORMER DISCONNECT SWITCH

C

B

PANEL

CONTROL

GENERATOR

LOUVER

INTAKE

HIRSCH PANEL

CARD READER PANEL

GENERATOR ROOM

GAS)(NATURAL

GENERATORSTANDBY

(BY OTHERS)

ROADWAY LIGHTING CONTROLLER

(SEE NOTE 1)

BUILDING

PREFABRICATED

IPDC FACILITY

DISCONNECT

MAIN SERVICE

IPDC FACILITY

BUILDING FOUNDATION

PREFABRICATED

IPDC FACILITY

CARD READERCARD READER

NOTE 3)(SEE DESIGNER

SEE DESIGNER NOTE 2

1.

2.

3.

NOTES TO DESIGNER

4.

TO THE SATISFACTION OF THE ENGINEER.

WALLS AGAINST RODENT OR PEST INFESTATION OR ACCESS,

AND ANY PROTRUSION/ACCESS CUT THROUGH BUILDING

CONTRACTOR SHALL SEAL DOOR OPENING, DOOR FRAMING, 2.

WITH IPDC FACILITY PREFABRICATED BUILDING.

SEE SPECIAL PROVISIONS FOR REQUIREMENTS ASSOCIATED 1.

NOTES:

NOT TO SCALE

OF PAVEMENT

ROADWAY EDGE

IPDC FACILITY SITE PLAN

CCTV CAMERA

CORNER MOUNTED

CCTV CAMERA

CORNER MOUNTED

NOTES TO DESIGNER5.

(TYPICAL)

2'-MOUNTING ARM

LONGER BATTERY RUNTIME IS SELECTED.

RUNTIME. THE DESIGNER SHALL RESIZE AS REQUIRED IF A

BASE SHEETS ARE BASED ON A 30-MINUTE BATTERY

THE BATTERY RACK AND HVAC EQUIPMENT SHOWN ON THESE

BASED ON THE ACTUAL PLACEMENT OF THE IPDC FACILITY.

DIRECTION. THE DESIGNER SHALL ADJUST ACCORDINGLY

IPDC FACILITY IS INSTALLED ALONG THE WESTBOUND

DIRECTIONAL INDICATIONS USED ON THIS SHEET ASSUME THE

TOLLWAY BY THE DESIGNER.

TYPICAL, BUT SHALL BE CONFIRMED WITH THE ILLINOIS

INSTALLATION OF A GANTRY AT EACH IPDC FACILITY IS

INSERTION OF THE SHEET INTO THE PLAN SET.

BOXES SHALL BE REMOVED BY THE DESIGNER PRIOR TO

INSERTION INTO A CONTRACT. ALL "NOTE TO DESIGNER"

DESIGN OF THIS SHEET UPON ITS COMPLETION AND

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

BY THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IT IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT

LOCK THE DOOR IN AN OPEN POSITION.

DOORS SHALL SWING OPEN 170° AND HAVE A MECHANISM TO

3.

(TYP.)

BOLLARD

4•" REMOVABLE

UTILITY METER

IPDC FACILITY

BUILDING.

YELLOW REFLECTIVE TAPE TO PROTECT THE HVAC UNITS AND

INSTALL REMOVABLE STAINLESS STEEL BOLLARDS WITH

Page 6: Illinois Tollway M-ITS Base Sheet Revisions

NORTH ELEVATION

EAST ELEVATION

WEST ELEVATION

SOUTH ELEVATION

30'-0"

7'

30'-0"

3'

(9'-

0"

MIN. IN

SID

E

CL

EA

R

HEIG

HT)

A

PP

RO

X.

10'-

0"

OU

TSID

E

HEIG

HT

12'-0"

3'

12'-0"

7'

3'

DATE

M-ITS-1803

3-01-2019

NOT TO SCALE

NOT TO SCALENOT TO SCALE

NOT TO SCALE

ASSEMBLY (TYP.)

SKID

UNITS

HVAC

(9'-

0"

MIN. IN

SID

E

CL

EA

R

HEIG

HT)

A

PP

RO

X.

10'-

0"

OU

TSID

E

HEIG

HT

READER

CARD

READER

CARD

PACK LIGHT

LED WALL

PACK LIGHT

LED WALL

RECEPTACLES

GENERATOR

PORTABLE

ASSEMBLY (TYP.)

SKID

(BY OTHERS)

RGS CONDUIT

3" PVCC

RGS CONDUIT

4" PVCC

(BY OTHERS)

DISCONNECT SWITCH

METER HOUSING AND

ROADWAY LIGHTING

(BY OTHERS)

ELECTRIC SERVICE

TO ROADWAY LIGHTING

PACK LIGHT

LED WALL

RECEPTACLES

GENERATOR

PORTABLE

DOOR HANDLE

CARD READER

UNITS

HVAC

PACK LIGHT

LED WALL

EXHAUST LOUVER

(9'-

0"

MIN. IN

SID

E

CL

EA

R

HEIG

HT)

A

PP

RO

X.

10'-

0"

OU

TSID

E

HEIG

HT

PACK LIGHT

LED WALL

UNIT 1

HVAC

UNIT 2

HVAC

SWITCHES

AND DISCONNECT

METER HOUSINGS

RECEPTACLE

DUPLEX

WEATHERPROOF

SLOPED ROOF SYSTEM (TYP.)

FOUNDATION

CONCRETE

HANDLE

DOOR

READER

CARD

PACK LIGHT

LED WALL

SLOPED ROOF SYSTEM (TYP.)

RECEPTACLE

CONTROL

GENERATOR

PORTABLE

PACK LIGHT

LED WALL

RECEPTACLE

POWER

GENERATOR

PORTABLE

FOUNDATION

CONCRETE

RECEPTACLE

DUPLEX

WEATHERPROOF

RECEPTACLE

DUPLEX

WEATHERPROOF

SWITCHES

DISCONNECT

HOUSINGS AND

METER

PACK LIGHT

LED WALL

HANDLE

DOOR

READER

CARD

INTAKE LOUVER(9'-

0"

MIN. IN

SID

E

CL

EA

R

HEIG

HT)

A

PP

RO

X.

10'-

0"

OU

TSID

E

HEIG

HT

FOUNDATION

CONCRETE

6" MIN.

FOUNDATION

CONCRETE

SURFACEAGGREGATE

SIGN

IDENTIFICATION PACK LIGHT

LED WALL

(BY OTHERS)

PHOTOCELL

ROADWAY LIGHTING

(BY OTHERS)

PHOTOCELL

ROADWAY LIGHTING

METER HOUSING

IPDC FACILITY

ELECTRIC SERVICE

TO IPDC FACILITY

(TYP.)

NOTE 3

SEE DESIGNER

(SEE SHEET M-ITS-1814)

SIGN

IDENTIFICATION

NOTES:

IPDC FACILITY PREFABRICATED BUILDING.

SEE SPECIAL PROVISIONS FOR REQUIREMENTS ASSOCIATED WITH1.

PREFABRICATED BUILDING.

REQUIRED TO PROVIDE DRAINAGE AWAY FROM THE IPDC FACILITY

THE DESIGNER SHALL SPECIFY FINISHED FLOOR ELEVATIONS AS

ON THE ACTUAL PLACEMENT OF THE IPDC FACILITY.

DIRECTION. THE DESIGNER SHALL ADJUST ACCORDINGLY BASED

IPDC FACILITY IS INSTALLED ALONG THE WESTBOUND

DIRECTIONAL INDICATIONS USED ON THIS SHEET ASSSUME THE

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT IS

3.

2.

1.

NOTES TO DESIGNER

CCTV CAMERA 1

CORNER MOUNTED

CCTV CAMERA 2

CORNER MOUNTED

CCTV CAMERA 2

CORNER MOUNTED

CCTV CAMERA 1

CORNER MOUNTED

CCTV CAMERA 1

CORNER MOUNTED

CCTV CAMERA 2

CORNER MOUNTED

CCTV CAMERA 1

CORNER MOUNTED

CCTV CAMERA 1

CORNER MOUNTED

ELEVATION

IPDC FACILITY EXTERIOR

NOTES TO DESIGNER

THE DOOR IN AN OPEN POSITION.

DOORS SHALL SWING OPEN 170AND HAVE A MECHANISM TO 4.

RECEPTACLE

DUPLEX

WEATHERPROOF

RECEPTACLE

DUPLEX

WEATHERPROOF

SPIKES

BIRD DETERRENT

SPIKES

BIRD DETERRENT SPIKES

BIRD DETERRENT

SPIKES

BIRD DETERRENT

RECEPTABLE (L6-30R)

240V 30A LOCKING

Page 7: Illinois Tollway M-ITS Base Sheet Revisions

EQUIPMENT ROOM EAST ELEVATION

EQUIPMENT ROOM WEST ELEVATION

EQUIPMENT ROOM SOUTH ELEVATION

EQUIPMENT ROOM NORTH ELEVATION

M-ITS-1804

DATE

03-31-2017

NOTES:

NOT TO SCALE

NOT TO SCALE

NOT TO SCALE

NOT TO SCALE

9'-

0"

MIN. IN

SID

E

CL

EA

R

HEIG

HT

9'-

0"

MIN. IN

SID

E

CL

EA

R

HEIG

HT

DISCONNECT

TRANSFORMER

TRANSFORMER

25 KVA

DOOR(BY OTHERS)

CONTROLLER

LIGHTING

ROADWAY

FAPUPS-1

(TYPICAL)

RECEPTACLE

DUPLEX

4' X 8' WALLBOARD

MTS GCS

PANEL

HIRSCH

PANEL

READER

CARD

(TYPICAL)

RECEPTACLE

DUPLEX

9'-

0"

MIN. IN

SID

E

CL

EA

R

HEIG

HT

UNIT

HVAC

UNIT

HVAC

9'-

0"

MIN. IN

SID

E

CL

EA

R

HEIG

HT

MDPATS

PANEL

CONTROL

HVAC

3" CONDUIT

2" CONDUIT

4-4" CONDUITS 3-4" CONDUITS

4" CONDUIT

6-4" CONDUITS

VPJB

ELEVATIONS

IPDC FACILITY INTERIOR

DISCONNECT

MAIN SERVICE

IPDC FACILITY

LIGHT SWITCH

SPD

1" CONDUIT

CAMERA

SECURITY

INTERIOR

EXTINGUISHER

FIRE

ELEVATION

FINISHED FLOOR

INTERIOR

ELEVATION

FINISHED FLOOR

INTERIOR

ELEVATION

FINISHED FLOOR

INTERIOR

ELEVATION

FINISHED FLOOR

INTERIOR

ON THE ACTUAL PLACEMENT OF THE IPDC FACILITY.

DIRECTION. THE DESIGNER SHALL ADJUST ACCORDINGLY BASED

IPDC FACILITY IS INSTALLED ALONG THE WESTBOUND

DIRECTIONAL INDICATIONS USED ON THIS SHEET ASSUME THE

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

2.

1.

NOTES TO DESIGNER

1.

SHEETS FOR COMPLETE CONDUIT REQUIREMENTS.

DIAGRAM (M-ITS-1807), AND PANELBOARD SCHEDULE (M-ITS-1808)

REFER TO EQUIPMENT LAYOUT (M-ITS-1806), SINGLE LINE

FOR CLARITY, NOT ALL EXPOSED CONDUITS ARE SHOWN.

Page 8: Illinois Tollway M-ITS Base Sheet Revisions

IPDC FACILITY UNDERGROUND CONDUIT PLAN

PE

R

RO

AD

WA

Y

PL

AN

S

SH

OU

LD

ER

WID

TH

DATE

M-ITS-1805

3-01-2019

CONDUIT PLAN

IPDC FACILITY UNDERGROUND

(BY OTHERS)

REQUIRED IN LIGHTING PLAN

LIGHTING CONDUITS/DUCTS AS

B

MD

P

MTS

ATS

C

M M

JB

JB

SS

RACK 1RACK 2RACK 3UPS/LCRACK

BATTERY

EXISTING ROW

APPLICABLE

AGGREGATE PAD AS

RETAINING WALL OR

BACK OF SINGLE FACE BARRIER WALL

BACK OF GUTTER

FOUNDATION

GANTRYHANDHOLE

LIGHTING

HANDHOLE

COMMUNICATION

ITS

EDGE OF SHOULDER

HANDHOLE

POWER

ITS

CONDUITS

6-4" PVC

3-1‚" HDPE CONDUITS (ITS FIBER AND FUTURE CABLES)

CONDUITS

2-4" PVC

BOXES

DATA JUNCTION

TO MEDIAN ITS

2-1" PVC CONDUITS

BOXES

POWER JUNCTION

TO MEDIAN ITS

2-3" PVC CONDUITS

CONDUITS

2-4" PVC

LOCAL POWER)

CONDUITS (ITS

2-3" HDPELOCAL POWER)

CONDUITS (ITS

2-3" HDPE

FUTURE CABLES)

FIBER AND

CONDUITS (ITS

3-1‚" HDPE

HVAC

HVAC

VPJB

UPS-1

SP

D

EQUIPMENT ROOM

FAP

4' X 8' WALLBOARD

GCS

HVAC CONTROL PANEL

25 KVA TRANSFORMER

THERMOSTAT

PANEL

CONTROL

GENERATOR

CHARGER

BATTERY

CONDUITS

3-4" PVC

SWITCH

DISCONNECT

TRANSFORMER

CONDUITS

2-4" PVC

OTHERS)

FOR LIGHTING (BY

4-4" PVC CONDUITS

HEATER

ELECTRIC

GENERATOR ROOM

CARD READER PANEL

HIRSCH PANEL

CONDUIT

4" PVC

(BY OTHERS)

DISCONNECT SWITCH

ROADWAY LIGHTING

ELECTRIC SERVICE (BY OTHERS)

3" PVC CONDUIT TO ROADWAY LIGHTING

METER (BY OTHERS)

ROADWAY LIGHTING UTILITY

GAS)(NATURAL

GENERATORSTANDBY

4" PVC CONDUIT TO IPDC FACILITY ELECTRIC SERVICE

IPDC FACILITY UTILITY METER

(BY OTHERS)

CONTROLLER

ROADWAY LIGHTING

PREFABRICATED BUILDING

IPDC FACILITY

9-1‚" HDPE CONDUITS (ILLINOIS TOLLWAY/LEASED/3RD PARTY FIBER)

COORDINATED BY OTHERS.

ROADWAY LIGHTING ELECTRIC SERVICE WILL BE

UTILITY SERVICES WITH COMED AND NICOR.

THE CONTRACTOR SHALL COORDINATE ALL WORK FOR

WITH PROPOSED EQUIPMENT.

IN THE IPDC FACILITY PREFABRICATED BUILDING FLOOR

THE CONTRACTOR SHALL COORDINATE PENETRATIONS

2.

1.

NOTES:

NOTE 2

SEE DESIGNER

NOTES TO DESIGNER

NOT TO SCALE

OF PAVEMENT

ROADWAY EDGE

JB

JB

CARD READER

JB

SERVICE DISCONNECT

IPDC FACILITY MAIN

2.

1.

NOTES TO DESIGNER3.

NOTE 3)(SEE DESIGNER

ON THE ACTUAL PLACEMENT OF THE IPDC FACILITY.

DIRECTION. THE DESIGNER SHALL ADJUST ACCORDINGLY BASED

IPDC FACILITY IS INSTALLED ALONG THE WESTBOUND

DIRECTIONAL INDICATIONS USED ON THIS SHEET ASSUME THE

TOLLWAY BY THE DESIGNER.

TYPICAL, BUT SHALL BE CONFIRMED WITH THE ILLINOIS

INSTALLATION OF A GANTRY AT EACH IPDC FACILITY IS

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

Page 9: Illinois Tollway M-ITS Base Sheet Revisions

IPDC FACILITY EQUIPMENT LAYOUT

DATE

M-ITS-1806

3-01-2019

12

3

B

HVAC

HVAC

MD

P

MTS

ATS

6

104

5

102

104

102

106 CHARGER

BATTERY

8

102

C

102

104

102

11 12

13 13

M

JB

JB

JB

113

113 113

30'-0"

LOUVER

INTAKE

LOUVER

EXHAUST

113

FAN-EF1

EXHAUST

JB

HEATER

ELECTRIC

THERMOSTAT

14

PANEL

CONTROL

GENERATOR

3

3

113

HEATER

WATER

JACKET

106

3

106

1

2

S10

S

10

3

106

106 9

101

FIRE EXTINGUISHER

1063

12'-

0"

4

15

RACK 1RACK 2RACK 3UPS/LCRACK

BATTERY

(BY OTHERS)

ROADWAY LIGHTING UTILITY METER

NOTE 5

NOTE 4

SWITCHALARMDOOR

SWITCHALARMDOOR

101

WALLBOARD

4'X8'

114

CABLE TRAY

3

(NATURAL GAS)

GENERATOR

STANDBY

GENERATOR ROOM

EQUIPMENT ROOM

ELECTRIC SERVICE

TO IPDC FACILITY

(BY OTHERS)ROADWAY LIGHTING CONTROLLER

CAMERASECURITYINTERIOR

NOTES:

1.

2.

3.

4.

5.

1

2SWITCH

GENERATOR CONTROL

5

3

4

6

7

VIDEO POWER JUNCTION BOX

8 UPS-1

9

LEGEND

10

11

12

CARD READER PANEL

13 CARD READER

14 HVAC CONTROL PANEL

HIRSCH PANEL

FIRE ALARM PANEL

NOT USED

SMOKE DETECTOR

SURGE PROTECTION DEVICE

25 KVA TRANSFORMER

15 TRANSFORMER DISCONNECT SWITCH

IPDC FACILITY MAIN SERVICE DISCONNECT

IPDC FACILITY UTILITY METER

NOT TO SCALE

NOTE TO DESIGNER

LAYOUT

IPDC FACILITY EQUIPMENT

CCTV CAMERA

CORNER MOUNTED

CCTV CAMERA

CORNER MOUNTED

JB

M

(BY OTHERS)

DISCONNECT SWITCH

ROADWAY LIGHTING

2.

1.

ON THE ACTUAL PLACEMENT OF THE IPDC FACILITY.

DIRECTION. THE DESIGNER SHALL ADJUST ACCORDINGLY BASED

IPDC FACILITY IS INSTALLED ALONG THE WESTBOUND

DIRECTIONAL INDICATIONS USED ON THIS SHEET ASSUME THE

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

NOTE 2)

(SEE DESIGNER

(TYPICAL)

2'-MOUNTING ARM

6.

NOTE 6

NOTE 6

7.

NOTE 7

HVAC SYSTEM SHALL HAVE A POSITIVE PRESSURE.

INSTALL DOOR CLOSER WITH HOLD OPEN FEATURE.

ON WALLBOARD.

TERMINATE ALARM CABLES ON TERMINAL BLOCK ON TSIC INSTALLED

THE INSTALLATION AND REMOVAL OF THE GENERATOR SET.

THE DOORWAY FOR THE GENERATOR ROOM SHALL BE WIDE ENOUGH TO ALLOW FOR

TSIC TERMINAL BLOCK LAYOUT SHEET (M-ITS-1813) FOR DETAILS.

TERMINATE ALARM CABLES ON TERMINAL BLOCK ON TSIC BOARD. SEE IPDC FACILITY

SEE IPDC FACILITY SINGLE LINE DIAGRAM SHEET (M-ITS-1807).

SEE IPDC FACILITY CABLE/CONDUIT SCHEDULES AND NOTES SHEET (M-ITS-1800).

Page 10: Illinois Tollway M-ITS Base Sheet Revisions

101

101

102

102

103

102

102

104

104

104 102

METERING

UTILITY

NOTE 13PDT

30A

GCS

CONTROL

B

POWER

C

WITH LP

SPD

MDP

SINGLE LINE DIAGRAM

G N

1}, 3W120/240VUTILITY SERVICE

103

2P

100A

1}, 3W

240-480V

25KVA

2P

60A

WITH LP

SPD

1}, 3W

480-120/240V

25KVA

UPS-1 PANEL

100A

120/240V, 1}, 3W, 200A

CAMERA CAMERA

120/240V, 1}, 3W, 200A

CAMERA CAMERA

GP-1

PANELBOARD SCHEDULE

BRANCH BREAKERS FOR BUILDING LOADS PER

114

115

116

116

55

8

8

108

5 5

120VAC

OUTDOOR LIGHTING CONTACTOR WIRING DIAGRAM

H N

HOA

CR

LIGHTING CONTACTOR

MECHANICALLY HELD

CLOSEDCR

CR OPEN

SPARE

MDP (11)

BLDG. LIGHTS

TO OUTDOOR

200A

1}, 3W

120/240V

50KW

GENERATOR

STANDBY

2PDT

200A

MTS2P, 3W

200A

ATS

200A

200A

200A

200A

MOTION DETECTORC

MDP (11)

1.

NOTES:

2.

BUILDING SHALL BE PROVIDED BY OTHERS UNDER SEPARATE CONTRACT.

AND ALL ROADWAY LIGHTING APPURTENANCES WITHIN THE IPDC FACILITY PREFABRICATED

THE ROADWAY LIGHTING METER HOUSING, DISCONNECT SWITCH, LIGHTING CONTROLLER,

CONTACT IN ATS TO INITIATE ENGINE STARTING CONTROLS.

(SEE DESIGNER NOTE 4)

BYPASS SWITCH

40 KVA UPS WITH

NOTE 5)

(SEE DESIGNER

DISCONNECT

SERVICE

MAIN

DATE

03-31-2017

M-ITS-1807

WH

EN

L

G

C

REMOTELY

EQUIPMENT LOCATED

PREFABRICATED BUILDING

IN IPDC FACILITY

EQUIPMENT LOCATED

LINE DIAGRAM

IPDC FACILITY SINGLE

NOTES TO DESIGNER

1.

CALCULATED LOAD.

SHALL INCREASE THE SERVICE SIZE IF REQUIRED BY THE

200A IS THE MINIMUM PERMITTED SERVICE SIZE. THE DESIGNER

ON THE CALCULATED LOAD.

THE UPS SIZE SHALL BE DETERMINED BY THE DESIGNER BASED

MILE FROM THE IPDC FACILITY.

PANELS. GANTRY PANELS SHALL BE LOCATED A MAXIMUM OF 0.75

ARE DEPENDENT ON PLACEMENT OF CAMERAS AND REMOTE GANTRY

GANTRY PANELS ARE REPRESENTATIVE. ACTUAL REQUIREMENTS

CABLE/CONDUIT REQUIREMENTS SHOWN TO CAMERAS AND REMOTE

PRECISE REQUIREMENTS WILL VARY BY SITE.

IPDC FACILITY AND ONE REMOTE GANTRY PANEL ARE SHOWN.

TWO REMOTE CAMERA/MVDS ENCLOSURES POWERED FROM THE

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

2.

3.

4.

5.

Page 11: Illinois Tollway M-ITS Base Sheet Revisions

GEN. BATTERY CHARGER

OUTDOOR LIGHTS

400 INTERIOR RECEPTACLES

SWITCHED INTERIOR LIGHTS

160

GEN. JACKET WATER HTR. 1500

OUTDOOR RECEPTACLE

OUTDOOR RECEPTACLE

200

200

30

28

26

24

22

20

18

16

14

12

29

27

25

23

21

19

17

15

10

13

11

9

7

5

3

8

6

4

1/3

21

SURFACE

SUBTOTAL "B"

SUBTOTAL "A"

AMPS/LOAD (WATTS)

BA A B

LOAD (WATTS)

MAINS

BUS RATING

MOUNTINGPHASE/WIRE

VOLTAGE

PANELBOARD

DESCRIPTIONCKT

NO. POLES

AMPS/

POLES

CKT

NO.DESCRIPTION

20/1

20/1

20/1

CKT

BKR

CKT

BKR

15/1

20/1

20/1

20/1

15/1

TOTAL WATTS "A,B"

1000

100030/2

36

34

32

35

33

31

30/2

20/1

20/1

20/1

100

42

40

38

41

39

37 20/1

20/1

20/1

SPARE SPARE

20/1

20/1

20/1-

-

-

GANTRY PANEL GP-1100/2

200

HIRSCH PANEL

SMOKE DETECTOR 50

SPARE

SPARESPARE

SPARE

-

-

16

14

12

15

10

13

11

9

7

5

3

8

6

4

1/3

2

SURFACE

MDP

SUBTOTAL "B"

SUBTOTAL "A"

AMPS/

BA A B

LOAD (WATTS)

MAINS

BUS RATING

MOUNTINGPHASE/WIRE

VOLTAGE

POLES

AMPS/

POLES

CKT

NO.DESCRIPTION

CKT

BKR

CKT

BKR

20/1

30/2

15/1

TOTAL WATTS "A,B"

20

18

19

17

20/1

20/1

SPARE

SPARE

20/1

-

-

26

24

22

25

23

21 20/1

20/1

20/1

SPARE

20/1

20/1

20/1-

HVAC UNIT

200/2

30

28

29

27

20/1

20/1

SPARE SPARE

20/1

20/1-

-

-

SPARESPARE -

BATTERY LIGHT* 300

* PROVIDE WITH HANDLE LOCKING DEVICE.

FIRE ALARM PANEL 100

1000

1000

- SPARE

1

20/1

DESCRIPTIONNO.

LOAD (WATTS)CKT

PANELBOARD 200A

200A MCB

240/120V

200A

200A MCB

240/120V

30/2

15/1

30

28

26

24

22

20

18

16

14

12

29

27

25

23

21

19

17

15

10

13

11

9

7

5

3

8

6

4

15/1

15/1

1/3

21

SURFACE

SUBTOTAL "B"

SUBTOTAL "A"

AMPS/LOAD (WATTS)

BA A B

LOAD (WATTS)

MAINS

BUS RATING

MOUNTINGPHASE/WIRE

VOLTAGE

PANELBOARD

DESCRIPTIONCKT

NO. POLES

AMPS/

POLES

CKT

NO.DESCRIPTION

30/2

30/2

20/1

15/1

15/1

CKT

BKR

CKT

BKR

SPARE

SPARE

SPARE SPARE

-

-

15/1

20/1

20/1

20/1-

30/2

15/1

15/1

15/1

15/1

15/1

15/1

15/1

15/1

-

TOTAL WATTS "A,B"

1000

1000

30/2ITS DATA CABINET

-

-

1000

1000

1000

1000

SPARE

ENCLOSUREREMOTE CAMERA/MVDS ITS

ENCLOSUREREMOTE CAMERA/MVDS ITS

SPARE 31 20/1 20/1 - 32 SPARE-

SPARE - - SPARE

100A MCB

100A

GP-1

240/120V

SPARE-

-

SPARE -

SPARE

SPARE-

-

-

2040

5890

-

3800

3200

-

-

3290

2690

1410

1660

8750

7450

9110

-20/1

20/1

20/1

20/1

RACK RECEPTACLE

RACK RECEPTACLE

RACK RECEPTACLE

RACK RECEPTACLE

360

360

360

360

SPARE

SPARE

-

-

SPARE

SPARE

-

-

VIDEO POWER JUNCTION BOX 200 20/1

SPARE -

30/2

15/1

SPARE - 20/1

20/1 SPARE

20/1

SPARE -

30/2

20/1

20/1

20/1 TSIC EQUIPMENT BOARD

TSIC EQUIPMENT BOARD

SPARE

200

-

-

-

20/1

-

-

SPARE

SPARE

-SPARE 15/1

20/1

20/1

20/1

20/1

20/1

GEN ROOM RECEPTACLES

30/2 HVAC UNIT

2000

2000

SPARE

2000

2000

30/2

OUTDOOR RECEPTACLE

200

200

INTERIOR RECEPTACLES

INTERIOR RECEPTACLES

400

400

400

INTERIOR LIGHTS GEN RM.

-

-

-

160

4800

4760

SPD PANEL

ENCLOSUREREMOTE CAMERA/MVDS ITS

ENCLOSUREREMOTE CAMERA/MVDS ITS

SPD PANEL 30/2

OUTDOOR RECEPTACLE SPARE

-

-

UPS-1

UPS-1

30/2

= 19270W = 19.3KW = 21.2KVA

600

200

300

10160

12160

10570

= 12980W = 13.0KW = 16.3KVA

29400W = 29.4KW = 32.3KVA

LANE CONTROL SIGN

LANE CONTROL SIGN

LANE CONTROL SIGN

LANE CONTROL SIGN

LANE CONTROL SIGN

DYNAMIC MESSAGE SIGN

LANE CONTROL SIGN

LANE CONTROL SIGN

LANE CONTROL SIGN

LANE CONTROL SIGN

LANE CONTROL SIGN

LANE CONTROL SIGN

LANE CONTROL SIGN

600

400

400

400

400

890

890

600

400

400

400

400

400

400

DATE

M-ITS-1808

SCHEDULES

IPDC FACILITY PANELBOARD

1.

PRECISE REQUIREMENTS WILL VARY BY SITE.

IPDC FACILITY AND ONE REMOTE GANTRY PANEL ARE SHOWN.

TWO REMOTE CAMERA/MVDS ENCLOSURES POWERED FROM THE

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

2.

NOTES TO DESIGNER

3-31-2017

Page 12: Illinois Tollway M-ITS Base Sheet Revisions

12'-

0"

30'-0"

3.

2.

4.

1.

(M-ITS-1801) FOR ADDITIONAL DETAILS.

SEE IPDC FACILITY LEGEND, SYMBOL LIST, ABBREVIATIONS, AND EQUIPMENT SCHEDULES SHEET

TRAY.

SHOWN. THE RECEPTACLES SHALL BE MOUNTED TO THE SIDE OF THE CABLE

PROVIDE QUAD RECEPTACLES (4 TOTAL) FOR THE EQUIPMENT RACKS AS

AND 1/C #12 GRD. UNLESS OTHERWISE NOTED.

RECEPTACLE AND LIGHTING CONDUIT SHALL BE 3/4" WITH 2-1/C #12

SEE IPDC FACILITY CABLE/CONDUIT SCHEDULE AND NOTES SHEET (M-ITS-1800).

ST

AN

DA

RD 90"

RA

CK

4"

DATE

M-ITS-1809

3-01-2019

B

GFI

WP

2018

22

11

A

A A

A

9

9 9 9

99

JB

JB

B

2422

JB

JB10

A

JB

A

A

A

B

11

$

8 9 7

23

20

26

23

21

19

CC

24

23

26

JB

B

11

B

C

MDP

PANEL

HIRSCH

1614

UPS-1

$

MDP

77

108

107

108

107

109

107

106

108107

108

111109

106

108

108

106

108

107

106

107

107

RACK 1RACK 2RACK 3UPS/LC

RACK

BATTERY

(BY OTHERS)

PHOTOCELL

ROADWAY LIGHTING

IPDC FACILITY LIGHTING AND RECEPTACLE PLAN

NOT TO SCALE

108

111

EQUIPMENT ROOM

(NATURAL GAS)GENERATOR

STANDBY

ROOMGENERATOR

HVAC

HVAC

RACK

4-POST

NOM.

19"

SWITCH

BYPASS

WITH

UPS/LC

RACK

4-POST

RACK

4-POST

RACK 3

SPARE

NOM.

19"

RACK

4-POST

108108

7

CABLE TRAYNOTE 3 (TYP.)

RECEPTACLE (ORANGE)

4"X4" BOX WITH QUAD

RACK

BATTERY

10 8 9

RACK 1

NETWORK

AND

FIBER

LOCAL

RACK 2

AND POWER

CONTROL

SIGN

RACK

2-POST

23"

(FACING NORTH)

COMMUNICATIONS AND EQUIPMENT RACK ELEVATION

NOT TO SCALE

NOTES:

1.

ON THE ACTUAL PLACEMENT OF THE IPDC FACILITY.

DIRECTION. THE DESIGNER SHALL ADJUST ACCORDINGLY BASED

IPDC FACILITY IS INSTALLED ALONG THE WESTBOUND

DIRECTIONAL INDICATIONS USED ON THIS SHEET ASSUME THE

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

2.

NOTES TO DESIGNER

RECEPTACLE PLAN

IPDC FACILITY LIGHTING AND

NOTE 2)

(SEE DESIGNER

ATS

14

GFI

WP

GFI

WP

GFI

WP

22

GFI

WP

27-29

RECEPTABLE (L6-30R)

240V 30A LOCKING

Page 13: Illinois Tollway M-ITS Base Sheet Revisions

NOT TO SCALE

PROPOSED STUB UP

12

FOUNDATION

GANTRY

IPDC FACILITY ELECTRICAL GROUNDING LAYOUT

NOTE 2

DESIGNER

GROUND TRIAD DETAILNOT TO SCALE

(TYP)12

2" 2"

GROUND WELL ELEVATION DETAIL

9'-0" MINIMUM

PENETRATION

WASH GRAVEL

EXOTHERMIC WELD

NEENAH FOUNDRY R-7506-E

(TYP)

8"

16"

12

NOT TO SCALE (NOTE 1)

5"

13"

23"

CONCRETE

GROUND ROD

LID OR APPROVED EQUAL

10" } FLOOR BOX FRAME &

1" } COARSE

COPPER GROUND BAR (NOTES 4 AND 12)

13 SPACES @ 2" O.C.

ƒ"

1"

1" 4

"

2"

30"| „"

5/8" TYP TYP. 44 PLACES7/16" DIA. HOLES (TAPPED)

SUPPORT SPACING DETAIL

MASTER GROUND BUS BAR

NOT TO SCALE

NOT TO SCALE (NOTE 1)

10"o FLOOR BOX FRAME & LID

NEENAH FOUNDRY R-7506-E

GROUND WELL PLAN DETAIL

OR APPROVED EQUAL

CONCRETE

1"o ACCESS HOLE

13"

11 1/2"

EQUAL. TO BE SIZED AS REQUIRED.

TYPE LP FITTING OR APPROVED

GROUND CABLE (TYP.)

NOT TO SCALE

BAR CONNECTION DETAIL

MASTER GROUND BUS

USING EXOTHERMIC WELD (NOTE 6)

BOND LUG TO COPPER GROUND BAR

NOTES:

MOUNTING BRACKET WITH INSULATOR.

FEET ABOVE FINISHED FLOOR AND MOUNTED TO WALL USING A

THE GROUND BUS BARS MUST BE MOUNTED APPROXIMATELY 8

WITHOUT NOTICEABLE SAGS AND BENDS.

AS NECESSARY TO KEEP THE CONDUCTOR SECURELY IN PLACE

STANDOFFS. THE STANDOFFS SHALL BE INSTALLED AT INTERVALS

SUPPORTED 2 INCHES FROM THE WALL SURFACE ON INSULATED

FEET ABOVE FINISHED FLOOR. THE CONDUCTOR SHALL BE

INSTALLED HORIZONTALLY ALONG THE WALL APPROXIMATELY 8

THE INTERNAL PERIMETER GROUND BUS CONDUCTOR MUST BE

CONNECTIONS MUST BE EXOTHERMICALLY WELDED.

PERIMETER GROUND CONDUCTOR WITH A #2 AWG GROUND CABLE. ALL

BUILDING SHALL BE BONDED TO THE MAIN GROUND BUS OR THE INTERNAL

ALL EQUIPMENT LOCATED INSIDE THE IPDC FACILITY PREFABRICATED

PERIMETER GROUND BUS CONDUCTOR.

OF THE TWO CONDUCTORS THAT MAKE UP THE INTERNAL

A FOUR INCH GAP SHALL BE PROVIDED BETWEEN THE ENDS

COMPRESSION TERMINAL.

SHALL BE BOLTED TO THE RACK USING A SEAMLESS HEAVY DUTY

EQUIPMENT RACK TO THE GROUND BUS AS SHOWN. THE CABLE

PROVIDE A #2 AWG GROUND CABLE FROM THE FRAME OF EACH

CABLE TRAY ABOVE EQUIPMENT RACKS.

THE COPPER GROUND BUS BAR SHALL BE MOUNTED TO THE

BURNDY CORP.).

WELD PER MANUFACTURER SPECIFICATION (ERICO PRODUCTS OR

BUS BARS SHALL BE SOLID COPPER.

BOLTS, NUTS, AND WASHERS USED FOR CONNECTION TO GROUND

VERSION OF ASTM SPEC. B-187 OF LATEST DATE.

ELECTRICAL CONDUCTOR AND SHALL COMPLY WITH THE CURRENT

COMMERCIALLY PURE, ELECTROLYTIC COPPER, FOR USE AS AN

ALL COPPER GROUND BARS SHALL BE OF HARD DRAWN,

UNDER BUILDING.

PROVIDE 1" SCHEDULE 40 PVC CONDUIT FOR ALL GROUND CABLES

GROUND WELLS ARE REQUIRED AT EVERY GROUND ROD.

IN A PAVED AREA, INCORPORATE GROUND WELL IN THE POUR.

DETAIL SHOWS INSTALLATION IN UNPAVED AREA. WHEN INSTALLING

12.

11.

10.

9.

8.

7.

6.

5.

4.

3.

2.

1.

DATE

M-ITS-1810

3-01-2019

GROUNDING PLAN

IPDC FACILITY

TSIC

G

G

G

G

G

G

G G

G

G

G

G

GG

G

G

G

GG

G

TRIAD

GROUND

G

G

G

GG

G

30"L X 4"W X 1/4" THICK

MASTER GROUND BUS BAR

THICK

2'L X 2"W X 1/4"

GROUND BUS BAR

(TYP.)

2'L X 2"W X 1/4" THICK

GROUND BUS BAR

THICK

2'L X 2"W X 1/4"

GROUND BUS BAR

EQUIPMENT ROOM

GENERATOR ROOM

(NATURAL GAS)GENERATOR

STANDBY

(TYP.)

NOTE 3

G

G

12

14

NOTE 11

AFF (TYP.)

CONDUCTOR 8'-0"

GROUND BUS

INTERNAL PERIMETER

(TYP.)

NOTE 8

(TYP.)

NOTE 10

NOTE 7

NOTE 7

12

12

12

14

12

12

14

14

14

12

12

1212

10'-

0"

GG

G

1.

2.

NOTES TO DESIGNER

CONFIRMED WITH THE TOLLWAY BY THE DESIGNER.

A GANTRY AT EACH IPDC FACILITY IS TYPICAL, BUT SHALL BE

TOP OF FRE CONDUIT TO GANTRY COLUMN. INSTALLATION OF

WHERE A GANTRY IS PRESENT, WELD GROUND CABLE COILED AT

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

NOTES TO DESIGNER3.

NOTE 3)(SEE DESIGNER

ON THE ACTUAL PLACEMENT OF THE IPDC FACILITY.

DIRECTION. THE DESIGNER SHALL ADJUST ACCORDINGLY BASED

IPDC FACILITY IS INSTALLED ALONG THE WESTBOUND

DIRECTIONAL INDICATIONS USED ON THIS SHEET ASSUME THE

Page 14: Illinois Tollway M-ITS Base Sheet Revisions

2.

3.

4.

5.

1.

NOTES:

(TYP)

N

G

BC

STANDBY

GENERATOR

GN

NG

TO MASTER GROUND BUS BAR

NOTE 4

14 12

NOTE 2

GROUND BUS

NOTE 4

14

C BN G

ATS

NOTE 4

MDP

14

IPDC FACILITY GROUNDING SCHEMATIC

DISCONNECT

MAIN SERVICE

IPDC FACILITY

GROUNDING SHALL BE PER MOTOROLA R56 STANDARD.

PROVIDE EXOTHERMIC CONNECTION TO INTERNAL PERIMETER BUS CONDUCTOR.

UPS PANEL TO MASTER GROUND BUS BAR.

PROVIDE 3/4" SCHEDULE 40 PVC CONDUIT FOR GROUND CABLE CONNECTING

POWER CABLE INFORMATION.

SEE IPDC FACILITY SINGLE LINE FACILITY DIAGRAM SHEET (M-ITS-1807) FOR

SEE IPDC FACILITY CABLE/CONDUIT SCHEDULES AND NOTES SHEET (M-ITS-1800).

DATE

03-31-2017

M-ITS-1811

SCHEMATIC

IPDC FACILITY GROUNDING

NOTE TO DESIGNER

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

Page 15: Illinois Tollway M-ITS Base Sheet Revisions

11

10

10

7

7

8

2

1

4

5

6

H N

H N TB-1

TB-2

TB-3

TB-4

TB-5

TB-6

12

POWER CONNECTIONS

SEE DETAIL OF VPJB

INPOWER

AC PLUGS

12

3

3

GND

3

1 1

2 1

SQUARE D, CLASS 9070, PART SQ 9070T5SQD13

CONTROL POWER TRANSFORMER 120V AC-24V AC 500VA

3

4 1

5 1

6 LOT

7 2

8 1

1 ADVANCE TSP-W66 48VDC SURGE SUPPRESSOR

10

ATLANTIC SCIENTIFIC 24590

CAT 6 HIGH POE SURGE PROTECTOR,

11 1

WIRE CLAMPS, ALLEN BRADLEY CATALOG NO. 1492-HJ86

TERMINAL BLOCKS, 6 POLE PANEL MOUNT BLOCK SCREW TERMINAL WITH

HOFFMAN CATALOG NO. X-G52K

GROUND BAR SYSTEM WITH INSULATED MOUNTING BRACKET,

QUAD BOX WITH 2-DUAL AC OUTLETS, POWER SOURCE UPS PANEL (120VAC)

12 2 24VAC SURGE PROTECTORS, COOPER CROUSE-HINDS ZONE BARRIER ZB24580

3

POE INJECTOR

CAMERAS

CAT 6 TO SECURITY

(NOTE 3)

SECURITY CAMERAS

2-3/C #12 TO

11

NC COM

2 21 1

3

NC COM

24V AC HOT/NEUTRAL

120V AC

120V AC

NOTE 6

POE INJECTOR

SECOND HDIP

(120V AC) AND

ON QUAD BOX

OUTLET #2

CISCO SWITCH

CAT 6 FROM

NOTE 6

POE INJECTOR

FIRST HDIP

(120V AC) AND

ON QUAD BOX

OUTLET #1

TIED BACK TO ITEM 3

NOTE: COMMON POINT

HOFFMAN CATALOG NO. A-20N16BLP, WITH 20N16MP PANEL

30"Hx24"Wx8"D NEMA 1 ENCLOSURE WITH 26"Hx22.5"W BACK PANEL

THROUGH TSIC

CISCO SWITCH

ROUTED FROM

2-CAT 6 JUMPERS

THROUGH TSIC

FROM CISCO SWITCH

CAT 6 JUMPER ROUTED

DIGITAL LUGGERS DIN 3 RELAY

FOR WIRING SCHEMATIC

SEE DETAIL OF VPJB

CATALOG NO. F1X1LG6 WITH COVER C1LG6

PANDUIT PLASTIC WIRING DUCT SNAP-IN SLOT COVER 1"Wx1"H,

9

2

POWER LEADS

MARKING STRIPS AND JUMPERS ALLEN BRADLEY CATALOG NO. 1492-FB1M30-D1

COMPLETE WITH 10AMP FUSE, MOUNTING RAIL, ANCHORS, BARRIERS,

TERMINAL BLOCKS, FUSE SWITCH TYPE WITH BLOWN FUSE INDICATOR

TO UPS-1

3/C #12 SHLD, 3/4"C

ENTERING THE CAMERA.

THE OUTDOOR CAMERA HOUSING. THIS WILL PREVENT ANY MOISTURE

THE CONTRACTOR SHALL SEAL CONDUIT WITH ELECTRICAL PUTTY AS IT ENTERS

CAMERAS TO THE CISCO SWITCH.

SYSTEM OPERATION INCLUDING ETHERNET CONNECTIONS FROM THE

THE CONTRACTOR SHALL PROVIDE ALL POWER AND GROUND WIRING REQUIRED FOR

FOR MAINTENANCE.

PROVIDE A MINIMUM OF 12" OF CABLE SLACK AT CAMERA TO ALLOW

GROUND CABLES SHALL BE GREEN INSULATED TYPE RHW CONDUCTORS.

CAMERA MUST BE GROUNDED IN HOUSING.

MOUNT POE INJECTORS TO BACKBOARD (ITEM 7).

INJECTORS.

IN QUAD BOX (120V AC) CIRCUITS TO CONTROL POWER TO THE POE

DETAILS OF VIDEO POWER JUNCTION BOX ILLUSTRATES ITEM 11 WIRED

ITEM 11 CABLE DIAGRAM SHALL INCLUDE POE CONNECTIONS (ITEM 7).

ITEM 7 SHALL PLUG INTO QUAD OUTLET.

(INCLUDES POWER AND CAT6)

ALL ELECTRICAL CABLES TO CAMERAS SHALL HAVE SURGE PROTECTION

LABEL JUNCTION BOX, TERMINAL STRIPS AND ALL WIRE AND CABLES.

TO SECURITY CAMERAS (24V AC).

VIDEO JUNCTION BOX SHALL BE WIRED TO ACCOMODATE POWER

11.

10.

9.

8.

7.

6.

5.

4.

3.

2.

1.

(WIRING SCHEMATIC)

SEE DETAIL OF VPJB

DATE

03-31-2017

M-ITS-1812

CCTV CAMERA

INDOOR IPDC FIXED

(WITHIN CONDUIT)

CATEGORY 6A

(WITHIN CONDUIT)

CATEGORY 6A

CABLING IN CONDUIT

MANUFACTURER RECOMMENDED

CATEGORY 6A

CONTROL CABLING IN CONDUIT

MANUFACTURER RECOMMENDED ATS

IN 2" CONDUIT

RECOMMENDED ATS CONTROL CABLING

CATEGORY 6A AND MANUFACTURER

NOTES:

LEGEND QTY DESCRIPTION

DETAIL OF VIDEO POWER JUNCTION BOX (VPJB)

WITH SURGE PROTECTION

PTZ CCTV CAMERA

EXTERIOR IPDC

GENERATOR

CONTROLLERS

LCS AND DMS

FA

FAP

CONT

HVACATS

PANEL

HIRSCHUPS

CISCO ETHERNET SWITCH

CONT

GEN

NOT TO SCALE (WIRING SCHEMATIC)

BY THE MANUFACTURER AND PER NEC REQUIREMENTS.

REMOTE POWER SUPPLIES SHALL BE AS RECOMMENDED

CABLES IN CONDUIT FROM UPS PANEL TO LCS

RESET.

PLUGGED INTO AC PDU TO ALLOW REMOTE POWER

LCS AND DMS TYPE 2 CONTROLLERS SHALL BE1.

2.

NOTES:

GCS

TYPICAL IPDC FACILITY NETWORK DIAGRAM

MISCELLANEOUS DETAILS

DIAGRAM AND

IPDC FACILITY NETWORK

POWER JUNCTION BOX

IPDC FACILITY VIDEO

NOT TO SCALE (WIRING SCHEMATIC)

NOT TO SCALE

IPDC FACILITY PREFABRICATED BUILDING

NOTE TO DESIGNER

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

Page 16: Illinois Tollway M-ITS Base Sheet Revisions

1

NOTES:

6" 6"

SPARE

TERMINAL STRIP INTERCONNECT CENTER (TSIC) ELEVATION

DESCRIPTIONITEM QUANTITY

EQUIPMENT LEGEND

2

3

4

5

6

1 LOT7

1 LOT

NUMBER X-GS6K.

EQUIPMENT GROUND BUS BAR. HOFFMAN CATALOG

1 LOT 3 PAIR #22 CABLE WITH INDIVIDUALLY SHIELDED PAIRS.

1 LOT

8

9

10

11

NUMBER UK5N.

UNIVERSAL TERMINAL BLOCK. PHOENIX CONTACT CATALOG

5 EA.

3 EA.

25 EA.

10 EA.

NUMBER UDK-4-MTK-P/P.

GROUND TERMINAL BLOCK. PHOENIX CONTACT CATALOG

2 EA.

x 900mm, PHOENIX CONTACT CATALOG NUMBER 0801762.

MOUNTING RAIL; COPPER UNPERFORATED, 35mm x 7.5mm

21 EA.

13

(TYP)

4

BLK

WHT

BLK

RED

BLK

WHT

BLK

RED

NOTE 9

GEN ALARM

HIGH TEMP

10

10

10

10

SPARE

NOTE 10

NOTE 10

NOTE 12

NOTE 12

VIDEO/CONTROL

CCTV

SECURITY

6

5

TERMINAL STRIP LAYOUT

BAR (TYPICAL)

GROUND BUS

EQUIPMENT

PLUG PT5-HF-12DC-ST WITH BASE ELEMENT PT2x2-BE.

CONTACT "PLUGTRAB PT" SERIES CATALOG NUMBER FOR

TERMINAL BLOCK WITH DATA SIGNAL PROTECTION. PHOENIX

FOR PLUG PT2x1-5DC-ST WITH BASE ELEMENT PT2x1-BE.

PHOENIX CONTACT "PLUGTRAB PT" SERIES CATALOG NUMBER

TERMINAL BLOCK WITH DISCRETE SIGNAL PROTECTION.

SERIES CATALOG NUMBER FOR BASE ELEMENT PT2x1-BE.

TERMINAL BLOCK BASE. PHOENIX CONTACT "PLUGTRAB PT"

CABLE MARKERS. BRADY TYPE PWC-PK-3.

NUMBER DATATRAB D-LAN-CAT.6+.

CAT 6 SURGE SUPPRESSOR. PHOENIX CONTACT CATALOG

COLOR COMBINATION

MFGR'S COLOR CODE CHART

BLACK PAIRED WITH RED

CABLE-1

BLACK PAIRED WITH GREEN

BLACK PAIRED WITH WHITE

OR MANHATTAN #M43103.

SHIELDED PAIRS SHALL BE BELDEN #88777

3 PR. #22 CABLE WITH INDIVIDUALLY

NOT TO SCALE (SEE NOTES 1 AND 3)

(TYP)

TYPICAL

NOTE 2

NOTE 6

PLYWOOD BOARD

2"

2"

TY

P

CCTV

TY

P

8"

NOTE 5

WIRING DUCT 4

NOTE

AL

AR

MS

(TYP) (TYP)

2"

NOT TO SCALE (SEE NOTES 7 AND 8)

CONTROL PANEL

TO GENERATOR

CONTROL PANEL

TO HVAC

TO ATS

DETECTOR

TO SMOKE

NOTE 12

NOTE 10BLK

RED

SPARE

TO HIRSCH PANEL

FIRE/SMOKE

POWER LOSS 1

POWER LOSS 2

LOW TEMP

1-1/C #6 GROUND CABLE. (NOTES 3 AND 6)

6"

3

2

PAIR NO.

CABLE COLOR CODE CHART

3 PAIR DATA/COMMUNICATIONS

NUMBER ZB 5.

TERMINAL BLOCK MARKERS. PHOENIX CONTACT CATALOG

1

1 EA

2 EA.

BLK

RED

NOTE 10 NOTE 12

SWITCH

CISCO 3850

TYPICAL

NOTE 9

NOTE 2

TYPICAL

BOX

POWER JUNCTION

CAT 6A TO VIDEO

NOTE 9

MARKER. THE MARKERS SHALL BE NUMBERED AS DIRECTED BY THE ENGINEER.

EACH TERMINAL BLOCK WIRING TERMINAL SHALL BE IDENTIFIED WITH A TERMINAL14.

EACH CABLE SHALL BE IDENTIFIED WITH A CABLE MARKER.13.

THE SHIELD GROUND WIRE IS NOT TO BE TERMINATED.

GROUND BUS BAR WITH A BURNDY TYPE YAEV LUG. THE COMPONENT END OF

SHIELD GROUND WIRE TIED BACK IN 3" PIGTAIL AND TERMINATED TO TSIC12.

THE CONTRACTOR SHALL IDENTIFY EACH CABLE ON AS-BUILT DRAWINGS.11.

COIL SPARE PAIRS FOR FUTURE USE.10.

BUS BAR.

ROUTE #6 COPPER GROUND CABLE FROM GROUND TERMINAL BLOCK TO GROUND9.

ARE SHOWN DIAGRAMMATICALLY. WIRING DUCT IS NOT SHOWN ON THIS SHEET.

TERMINAL BLOCKS, TERMINAL BLOCK MARKER STRIPS, AND GROUND BUS BARS8.

FOR A COMPLETE LAYOUT OF THE TSIC.

(TSIC) LOCATED IN THE IPDC FACILITY PREFABRICATED BUILDING - SEE THIS SHEET

TERMINAL BLOCKS ARE LOCATED ON THE TERMINAL STRIP INTERCONNECT CENTER7.

12 4 PAIR #24 CAT 6 CABLE

1 LOT

11

COMMUNICATION FACILITY ELECTRICAL WORK")

"INTERMEDIATE POWER DISTRIBUTION AND

WITH THE ILLINOIS TOLLWAY SPECIAL PROVISION

(CABLE TRAY SYSTEM SHALL BE IN ACCORDANCE

CABLE TRAY UP TO CEILING

IPDC FACILITY PREFABRICATED BUILDING AS SHOWN ON PLANS.

PROVIDE A 4'X8'X3/4" THICK PLYWOOD BOARD FOR THE TSIC IN THE6.

CORNER STRIP PART NUMBER CSP3LG-Q.

PANDUIT PART NUMBER E2X3LG6 WITH COVER PART NUMBER C2LG6 AND

PROVIDE WIRE DUCT AS SHOWN ON THE DRAWING. WIRE DUCT SHALL BE5.

DETAILS.

DIN RAIL MOUNTED TERMINAL BLOCKS. SEE THIS SHEET FOR TERMINAL BLOCK4.

UNLESS NOTED OTHERWISE.

ALL EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR3.

INTERNAL PERIMETER GROUND BUS CONDUCTOR.

ROUTE #6 COPPER GROUND CABLE FROM THE GROUND BUS BAR TO2.

FOR THE TSIC INSTALLATION LOCATION.

IPDC BUILDINGS. SEE IPDC FACILITY EQUIPMENT LAYOUT SHEET (M-ITS-1806)

TERMINAL STRIP INTERCONNECT CENTERS (TSIC) ARE LOCATED IN THE1.

DATE

03-31-2017

M-ITS-1813

1

3

5

1

3

5

1

3

5

1

3

5

1

3

5

7

9

11

7

9

11

7

9

11

7

9

11

7

9

11

8

10

12

8

10

12

8

10

12

8

10

12

8

10

12

2

4

6

4

6

2

4

6

2

4

6

2

4

6

2

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

3

3

3

2

9

1

1

1

3

5

1

3

5

1

3

5

7

9

11

7

9

11

7

9

11

8

10

12

8

10

12

8

10

12

2

4

6

2

4

6

2

4

6

1

8

2

7

4

3

1

2

BLOCK LAYOUT

IPDC FACILITY TSIC TERMINAL

11

11

12

11

13

13

13

NOTE TO DESIGNER

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

Page 17: Illinois Tollway M-ITS Base Sheet Revisions

IPDC IDENTIFICATION SIGN

12"

5"

2"

5"

I90-IPDC 54.8

ROADWAY

MILEPOST

1.5" RADIUS, 0.5" BORDER, BLACK ON WHITE

NOT TO SCALE

M-ITS-1814

24"

NOTES:

1.

2.

DATE

03-31-2017

IDENTIFICATION SIGN

IPDC FACILITY

NOTE TO DESIGNER

SHEET INTO THE PLAN SET.

REMOVED BY THE DESIGNER PRIOR TO INSERTION OF THE

CONTRACT. ALL "NOTE TO DESIGNER" BOXES SHALL BE

OF THIS SHEET UPON ITS COMPLETION AND INSERTION INTO A

DESIGNER SHALL ACCEPT THE RESPONSIBILITY OF THE DESIGN

ARE AVAILABLE ON THE ILLINOIS TOLLWAY WEBSITE. THE

MICROSTATION FILES AND THE "CADD STANDARDS MANUAL"

THE DESIGNER PRIOR TO INSERTION INTO A CONTRACT.

IS NOT A STANDARD DRAWING. IT REQUIRES COMPLETION BY

THIS BASE SHEET SHOWS TYPICAL NEW CONSTRUCTION BUT IT

STANDARD SPECIFICATIONS.

USING BOLTS AND WASHERS ACCORDING TO ARTICLE 720.04 OF THE

IPDC FACILITY IDENTIFICATION SIGNS SHALL BE MOUNTED ONTO THE BUILDING

OF ARTICLE 720.02 OF THE STANDARD SPECIFICATIONS.

IPDC FACILITY IDENTIFICATION SIGN MATERIAL SHALL MEET THE REQUIREMENTS

Page 18: Illinois Tollway M-ITS Base Sheet Revisions

SECTION A-A

PLAN VIEW

SECTION B-B

TABLE

FOUNDATION LENGTH

MIN."

21

7 MIN."

21

7

14'-0"

A

A

B B

(BY DESIGNER)

FILL

(BY DESIGNER)

ANCHOR BOLTS

(BY DESIGNER)

FILL

(BY DESIGNER)

ANCHOR BOLTS

(BY DESIGNER)

ANCHOR BOLTS

IPDC BUILDING TYPE

STANDARD IPDC

COMBINATION PLAZA/IPDC

A=32'

A=40'

DIMENSION

(SEE FOUNDATION LENGTH TABLE)

A

NOTES TO DESIGNER

DESIGN LOADING:

DESIGN STRESSES FOR REINFORCED CONCRETE:

DESIGN SPECIFICATIONS:

GENERAL NOTES:

REINFORCEMENT BARS:

CONTINUED A MINIMUM OF ONE FOOT BELOW FINISHED GROUND LEVEL.

EXCEPT WHERE SHOWN OTHERWISE. CHAMFER ON VERTICAL EDGES SHALL BE

ALL EXPOSED CONCRETE EDGES SHALL HAVE A ƒ" x 45° CHAMFER,1.

CONSTRUCTION SPECIFICATIONS:

5.

4.

3.

2.

1.

DATE

3.

2.

1.

BRIDGE CONSTRUCTION ADOPTED JANUARY 1, 2016.

ILLINOIS DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR ROAD AND

SPECIAL PROVISIONS ADOPTED JANUARY 1, 2021.

ILLINOIS DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATIONS AND RECURRING

CONSTRUCTION.

DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE

ILLINOIS TOLLWAY SUPPLEMENTAL SPECIFICATIONS ISSUED MARCH, 2021 TO THE ILLINOIS

3-01-2021

UNLESS OTHERWISE SHOWN.

BE 3" FOR SURFACES FORMED AGAINST EARTH AND 2" FOR ALL OTHER SURFACES

COVER FROM THE FACE OF CONCRETE TO FACE OF REINFORCEMENT BARS SHALL

REINFORCEMENT BAR BENDING DIMENSIONS ARE OUT-TO-OUT.

CONCRETE STRUCTURES".

EDITION OF ACI 315, "MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED

REINFORCEMENT BENDING DETAILS SHALL BE IN ACCORDANCE WITH THE LATEST

REINFORCEMENT BARS DESIGNATED "(E)" SHALL BE EPOXY-COATED.

508 AND ARTICLE 1006.10.

CONFORM TO THE REQUIREMENTS OF IDOT STANDARD SPECIFICATIONS SECTION

REINFORCEMENT BARS, INCLUDING REINFORCEMENT BARS, EPOXY-COATED SHALL

LIVE LOAD, CONTROLLING CASE OF THE FOLLOWING:

KNOWN LOADING PROVIDED BY ITS

3,000 LB. CONCENTRACTED FORCE OR

200 P.S.F.

ILLINOIS TOLLWAY GEOTECHNICAL ENGINEER MANUAL DATED MARCH 2021.

ILLINOIS DEPARTMENT OF TRANSPORTATION BRIDGE MANUAL, JANUARY 2012.

ACI 318-19 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE, 2019.

AND OTHER STRUCTURES, 2016.

ASCE 7-16 MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS

INTERNATIONAL BUILDING CODE, 2018.

ILLINOIS TOLLWAY STRUCTURE DESIGN MANUAL ISSUED MARCH, 2021.

6.

5.

4.

3.

2.

1.

SELF WEIGHT OF SLAB

30,000 POUNDS (12'x30' BUILDING) OR 35,000 POUNDS (12'x38' BUILDING)DEAD LOAD:

WIND SPEED: 120 M.P.H. APPLIED TO BUILDING WALLS, PER ASCE 7-16

SNOW LOAD: 50 P.S.F.

fy = YIELD STRENGTH OF REINFORCEMENT BARS (GRADE 60)

f'c = COMPRESSIVE STRENGTH OF CONCRETE (CLASS SI)

= 60,000 P.S.I.

= 3,500 P.S.I.

(BY DESIGNER)

REBAR (E)(BY DESIGNER)

REBAR (E)

PRESSURE OF 2,000 P.S.F.

THE DESIGN IS BASED ON AN ALLOWABLE SOIL BEARING

REPLACEMENT MINIMUM LOADS SHOWN.

LOADS SHOWN ARE MINIMUM. IF ACTUAL LOADS ARE LARGER,

SUPPORT THE BUILDING AND MEET LOCAL CODES.

WALLS AND REINFORCING DETAILS AS NECESSARY TO

THE DESIGNER SHALL DESIGN THE TOP SLAB, FOOTERS,

THE BUILDING FRAME.

FLAT TOP SLAB AS SHOWN IN THE DRAWING TO SUPPORT

BUILDING MANUFACTURER. THE FOUNDATION MUST HAVE A

THIS DRAWING IS A CONCEPT FOUNDATION FROM A

SET.

DESIGNER PRIOR TO INSERTION OF THE SHEET INTO THE PLAN

ALL "NOTE TO DESIGNER" BOXES SHALL BE REMOVED BY THE

M-ITS-1815

CONCRETE FOUNDATION

PLAZA/IPDC

IPDC AND COMBINATION