ice storage systems · • #5 – reduce cost of delivering comfort • #6 – system efficiency...

61

Upload: others

Post on 02-Nov-2019

1 views

Category:

Documents


0 download

TRANSCRIPT

  • • #1 – Reduce building load• Building orientation, construction, and integrated design

    • #2 – Demand control ventilation• #3 – Net Energy Use (energy sharing)

    • Recycle, reclaim, integrate• Example cooling to heating ventilation air or hot water

    • #4 – Extend equipment life• #5 – Reduce cost of delivering Comfort• #6 – System efficiency not unit efficiency ratings

    • Efficiency ratings are at static conditions• Not valid from one type of equipment to another• Test points versus applied efficiency

    HVAC DESIGN GOALS

  • 6

    THE FIVE SYSTEM LOOPS

    airsideloop

    chilled-waterloop

    refrigerationloop

    heat rejectionloop

    controlsloop

  • 7

    CHILLED WATER PRODUCTION

    chilled-waterloop

    refrigerationloop

    heat rejectionloop

  • 8

    AIR-COOLED OR WATER-COOLED

    0 tons[0 kW]

    1,000 tons[3,517 kW]

    2,000 tons[7,034 kW]

    chiller capacity

    1,500 tons[5,276 kW]

    2,500 tons[8,793 kW]

    500 tons[1,759 kW]

    3,000 tons[10,551 kW]

    air-cooled

    water-cooled

  • COMPRESSOR TYPES

    9

    helical-rotary (screw)

    centrifugal

    scroll

  • 10

    ABSORPTION CHILLER TYPES

    single-effectdouble-effect

    direct-fired

  • 11

    WATERSIDE ECONOMIZER PLATE-AND-FRAME HEAT EXCHANGER

    plate-and-frame heat exchanger

    distribution pump

    equal-capacity large chillers

    bypass

    condenser water loop

  • Ideal ApplicationsRegions with year round cooling load and low ambient temperatures.Relatively warm chilled fluid.Requirement to use a water-side economizer rather than an air-side economizer.

    What is it?Fluid cooler integrated into the footprint of an Air-Cooled chiller

    WATERSIDE ECONOMIZER WITH A/C CHILLERS

  • THERMAL STORAGE SYSTEMS

    13

  • PARTIAL THERMAL STORAGE

    14

    0

    25

    50

    75

    cool

    ing

    load

    , % o

    f des

    ign

    100

    midnight 6 a.m. noon 6 p.m. midnight

    make ice

    melt ice

    chiller

  • Lower utility costsLower on-peak electrical consumption (kWh)Lower on-peak electrical demand (kW)

    Smaller equipment sizeSmaller chillerSmaller electrical service (A)

    Reduced installed costMay qualify for utility rebates or other incentives

    15

    THERMAL STORAGE SYSTEM

  • DEDICATED HEAT RECOVERY CHILLER

    55F45F

    120F

    140F

    Where to Apply

    •VAV Reheat

    •Domestic Hot Water

    •Low Temperature Heating

    Cooling Load

    Heating Load

    $0.75/Therm1.6 Kg CO2 per Therm

  • 17

    CHILLED WATER CONSUMPTION

    airsideloop

    Chilled Water produced as part of the HVAC system can also be concurrently used by other systems within a building, such as process cooling loads for Mfg.

  • • Chilled Water Air Handling Units• Chilled Water Terminal Units

    • Fan Coil• Chilled Beams• Sensible Cooling VAV

    • DOAS• Chilled Water VAV AHU

    18

    COMMON CHILLED WATER HVAC SYSTEMS

  • 19

    CHILLED-WATER AIR-HANDLING UNIT

    air-handling units

    water-cooled chiller

  • 20

    CHILLED-WATER TERMINAL SYSTEM

    chilled-water terminal unit with reheat coils

    dedicated outdoor air unit

  • 21

    CHILLED BEAMS

  • 22

    CENTRAL CHILLED-WATER VAV SYSTEM

    chilled-waterair-handlers

    VAV terminal units

    cooling tower

    boiler

    system controls

    chillerpumps

  • 23

    DEDICATED OUTDOOR-AIR SYSTEM

    VAV terminal diffusers

    chilled-water terminal units

    dedicated outdoor air unit

  • • Robust Components built to last a long time• Overall System Controllability• Application Options• Wider Operating Envelope• Air Distribution Flexibility• Maintain vs. Replace

    24

    WHY CHILLED WATER

  • 25

    STABILITY OF CONTROL

    setpointchilledwater

    DX

  • DISTRIBUTION – PIPING ENERGY

    Hydronic systems 15 times more efficient than refrigerant system

    Hydronic systems 10 times more efficient than air systems

    Distribution/Pumping Energy

    0.0%

    5.0%

    10.0%

    15.0%

    20.0%

    25.0%

    30.0%

    35.0%

    0 100 200 300 400 500

    Pipe/Duct Length

    Perc

    ent o

    f C

    ompr

    esso

    r Hor

    sepo

    wer

    Hydronic Air (Low Pressure VVT) Air (Medium Pressure VAV) Refrigerant (VRF)

    Chart1

    0000

    100100100100

    200200200200

    300300300300

    400400400400

    500500500500

    Hydronic

    Air (Low Pressure VVT)

    Air (Medium Pressure VAV)

    Refrigerant (VRF)

    Pipe/Duct Length

    Percent of Compressor Horsepower

    Distribution/Pumping Energy

    0

    0

    0

    0.01

    0.0035563973

    0.0125671983

    0.0439851939

    0.06

    0.0071127946

    0.0251343965

    0.0879703878

    0.12

    0.0106691919

    0.0377015948

    0.1319555817

    0.18

    0.0142255892

    0.050268793

    0.1759407756

    0.24

    0.0177819865

    0.0628359913

    0.2199259695

    0.3

    Definitions

    Taco System Analysis

    2/21/14

    Definitions:

    Building;

    FL = Floor Length (ft)

    FW = Floor Width (ft)

    PW = Perimeter Width

    = 20 ft (default)

    FH = Floor Height (ft)

    NF - Number of Floors

    RA = Roof Area (sq ft)

    = FL x FW

    BA = Building Area (sq ft)

    = FL x FW x NF

    PA = Perimeter Area

    = (2 x (FL + FW) x PW - (4 x PW x PW)) x NF

    V = Building Volume (cu ft)

    = A x FH x NF

    IAC = Infliltration air chages per hour (user preference)

    = 0.5 air changes/hr (default)

    IA = Infiltration Airflow (cu ft/min)

    = Building Volume (cu ft/air change) x IAC (air changes/hr) / 60 min/hr or Actual from Load Program

    Heat Loss - Design

    IHDT = Indoor Heating Design Temperature

    = 75F (default)

    HLT = Total Heat Loss (btu/hr)

    HLV = Ventilation Heat Loss (btu/hr)

    = Infiltration Airflow (cu ft/min) x

    1.085 btu/hr/cu ft/min/deg F x (Indoor Heating Design Temperature -

    Outdoor Design Heating Temperature (ASHRAE Average Annual Minimum DB deg F))

    = IA x 1.085 x (IHDT - ASHRAE Average Annual Minimum DB deg F)

    HLE = Envelope Heat Loss (btu/hr)

    = Total Heat Loss - Ventilation Heat Loss

    = HLT - HLV

    HLR = Roof Heat Loss (btu/hr)

    = Envelope Heat Loss x Roof Area (sq ft)/ Envelope Area (sq ft)

    = HLE x RA / (RA + (2 x (FL + FW) x FH x NF))

    HLW = Wall Heat Loss (btu/hr)

    = Envelope Heat Loss (btu/hr) - Roof Heat Loss (btu/hr)

    = HLE - HLR

    HLTP = Perimeter Total Heat Loss

    = Wall Heat Loss + Ventilation Heat Loss

    = HLW + HLV

    HLTI = Interior Total Heat Loss (btu/hr)

    = Roof Heat Loss

    = HLR

    Heat Loss - Hourly

    HHLT = Hourly Total Heat Loss (btu/hr)

    HHLV = Hourly Ventilation Heat Loss (btu/hr)

    = Ventilation Heat Loss x Heating Load Part Load Factor

    = HLV x HLPLF

    If Actual Envelope Loads are not Available from Load Program

    HHLE = Envelope Heat Loss (btu/hr)

    = Total Heat Loss - Ventilation Heat Loss

    = HLT - HLV

    HHLR = Hourly Roof Heat Loss (btu/hr)

    = Roof Heat Loss x Heating Load Part Load Factor

    = HLR x HLPLF

    HHLW = Hourly Wall Heat Loss (btu/hr)

    = Wall Heat Loss x Heating Load Part Load Factor

    = HLW x HLPLF

    HHLTP = Hourly Perimeter Total Heat Loss

    = Hourly Wall Heat Loss + Hourly Ventilation Heat Loss

    = HHLW + HHLV

    HHLTI = Hourly Interior Total Heat Loss (btu/hr)

    = Hourly Roof Heat Loss

    = HHLR

    If Actual Envelope Loads are Available from Load Program

    HHLR = Hourly Roof Heat Loss (btu/hr)

    = Hourly Roof Transmission Heat Loss from Load Program

    HHLW = Hourly Wall Heat Loss (btu/hr)

    = Hourly Wall Transmission Heat Loss from Load Program

    HHLG = Hourly Glass Heat Loss (btu/hr)

    = Hourly Glass Transmission Heat Loss from Load Program

    HHLE = Hourly Envelope Heat Loss (btu/hr)

    = Hourly Roof Transmission Heat Loss + Hourly Wall Transmission Heat Loss + Hourly Glass Transmission Heat Loss

    HHLTP = Hourly Perimeter Total Heat Loss

    = Hourly Wall Heat Loss + Hourly Infiltration Heat Loss

    HHLTI = Hourly Interior Total Heat Loss (btu/hr)

    = Hourly Roof Heat Loss

    Heating Part Load Factor

    HPLF = Heating Part Load Factor

    = Hourly heat loss / Total heat loss

    = HHLT / HLT

    Heat Gain - Design

    ICDT = Indoor Cooling Design Temperature

    = 73F (default)

    ILH = Indoor Latent Heat grw/lbda (Design)

    = 4.4 grw/lbda (default at 73F DB and 40% RH)

    HGT = Total Heat Gain (btu/hr)

    HGVS = Ventilation Sensible Heat Gain (btu/hr)

    = Infiltration Airflow (cu ft/min) x

    1.085 btu/hr/cu ft/min/deg F x (Outdoor Design Cooling Temperature (ASHRAE Average Annual Maximum DB deg F) -

    Indoor Cooling Design Temperature deg F)

    = IA x 1.085 x (ASHRAE Average Annual Maximum DB deg F - ICDT)

    = IA x 1.085 x (ASHRAE Average Annual Maximum DB deg F - 73)

    HGVL = Ventilation Latent Heat Gain (btu/hr)

    = IA cu ftda/min x 60 min/hr x

    (Outdoor Latent Heat (ASHRAE 0.4% Specific Humidity) - Indoor Latent Heat) grw/cu ftda / 7000 grw/lbw x 1000 btu/lbw

    = IA x 60 x (ASHRAE 0.4% MCWB - ILH) / 7000 x 1000

    = IA x 8.57 x (ASHRAE 0.4% MCWB - 4.4)

    = If ventilation latent heat gain is < 0 then set ventilation latent heat gain = 0

    HGV = Ventilation Heat Gain

    = Ventilation Sensible Heat Gain + Ventilation Latent Heat Gain

    = HGVS + HGVL

    HGPS = People Sensible Heat Gain (btu/hr)

    = Building Area (sq ft) / 200 sq ft / person x 200 btu/hr/person

    HGPL = People Latent Heat Gain (btu/hr)

    = Building Area (sq ft) / 200 sq ft / person x 200 btu/hr/person

    HGP = People Heat Gain

    = People Sensible Heat Gain + People Latent Heat Gain

    = HGPS + HGPL

    HGL = Light Heat Gain (btu/hr)

    = Building Area (sq ft) x 2 watts/sq ft x 3.4 btu/hr/watt

    = A x 6.8

    HGEQ = Equipment Heat Gain (btu/hr)

    = Building Area (sq ft) x 1 watts/sq ft x 3.4 btu/hr/watt

    = A x 3.4

    HGE = Envelope Heat Gain (btu/hr)

    = Total Heat Gain - Ventilation Heat Gain - People Heat Gain - Light Heat Gain - Equipment Heat Gain

    = HGT - HGV - HGP - HGL - HGEQ

    HGR = Roof Heat Gain (btu/hr)

    = Envelope Heat Gain x Roof Area (sq ft) / Envelope Area (sq ft)

    = HGE x RA / (RA + ((FL + FW) x FH x NF))

    HGW = Wall Heat Gain (btu/hr)

    = Envelope Heat Gain (btu/hr) - Roof Heat Gain (btu/hr)

    = HGE - HGR

    HGTP = Total Perimeter Heat Gain (btu/hr)

    = Wall Heat Gain + Ventilation Heat Gain

    = HGW + HGV

    HGTIV = Total Interior Heat Gain Variable (btu/hr)

    = Roof Heat Gain

    = HGR

    HGTIC = Total Interior Heat Gain Constant (btu/hr)

    = People Heat Gain + Light Heat Gain + Equipment Heat Gain

    = HGP + HGL + HGEQ

    HGTI = Total Interior Heat Gain

    = Total Interior Heat Gain Variable + Total Interior Heat Gain Constant

    Heat Gain - Hourly

    HHGT = Hourly Total Heat Gain (btu/hr)

    HHGVS = Hourly Ventilation Sensible Heat Gain (btu/hr)

    = HGVS (Ventilation Sensible Heat Gain) x Cooling Load Part Load Factor or Actual from Load Program if Occupied

    = HGVS x CLPLF

    = 0 if Unoccupied

    HHGVL = Hourly Ventilation Latent Heat Gain (btu/hr)

    = HGVL (Ventilation Latent Heat Gain) x Cooling Load Part Load Factor or Actual from Load Program if Occupied

    = HGVL x CLPLF

    = 0 if Unoccupied

    HHGV = Hourly Ventilation Heat Gain

    = Hourly Ventilation Sensible Heat Gain + Hourly Ventilation Latent Heat Gain

    = HHGVS + HHGVL

    HHGPS = Hourly People Sensible Heat Gain (btu/hr)

    = HGPS (Heat Gain People Sensible) or Actual From Load Program if Occupied

    = 0 if Unoccupied

    HHGPL = Hourly People Latent Heat Gain (btu/hr)

    = HGPL (Heat Gain People Latent) or Actual From Load Program if Occupied

    = 0 if Unoccupied

    HHGP = Hourly People Heat Gain

    = Hourly People Sensible Heat Gain + Hourly People Latent Heat Gain

    = HHGPS + HHGPL

    HHGL = Hourly Light Heat Gain (btu/hr)

    = HGL (Light Heat Gain) or Actual From Load Program if Occupied

    = 0 if Unoccupied

    HHGEQ = Hourly Equipment Heat Gain (btu/hr)

    = HGEQ (Equipment Heat Gain) or Actual From Load Program if Occupied

    = 0 if Unoccupied

    If Actual Envelope Loads are not Available from Load Program

    HHGE = Hourly Envelope Heat Gain (btu/hr)

    = Hourly Total Heat Gain - Hourly Ventilation Heat Gain - Hourly People Heat Gain - Hourly Light Heat Gain - Hourly Equipment Heat Gain

    = HHGT - HHGV - HHGP - HHGL - HHGEQ

    HHGR = Hourly Roof Heat Gain (btu/hr)

    = Roof Heat Gain x Cooling Load Part Load Factor

    = HGR x CLPLF

    HHGW = Hourly Wall Heat Gain (btu/hr)

    = Wall Heat Gain x Cooling Load Part Load Factor

    = HGW x CLPLF

    HHGTP = Hourly Total Perimeter Heat Gain (btu/hr)

    = Toal Perimeter Heat Gain x Cooling Load Part Load Factor

    = HGTP x CLPLF

    HHGTIV = Hourly Total Interior Heat Gain Variable (btu/hr)

    = Roof Heat Gain x Cooling Load Part Load Factor

    = HGR x CLPLF

    HHGTIC = Hourly Total Interior Heat Gain Constant (btu/hr)

    = Hourly People Heat Gain + Hourly Light Heat Gain + Hourly Equipment Heat Gain

    = HHGP + HHGL + HHGEQ

    HHGTI = Hourly Total Interior Heat Gain

    = Hourly Total Interior Heat Gain Variable + Hourly Total Interior Heat Gain Constant

    = HHGTIV + HHGTIC

    If Actual Envelope Loads are Available from Load Program

    HHGR = Hourly Roof Heat Gain (btu/hr)

    = Hourly Roof Transmission Heat Gain + Hourly Roof Solar Heat Gain from Load Program

    HHGW = Hourly Wall Heat Gain (btu/hr)

    = Hourly Wall Transmission Heat Gain + Hourly Wall Solar Heat Gain from Load Program

    HHGG = Hourly Glass Heat Gain (btu/hr)

    = Hourly Glass Transmission Heat Gain + Hourly Glass Solar Heat Gain from Load Program

    HHGE = Hourly Envelope Heat Gain (btu/hr)

    = Hourly Roof Heat Gain + Hourly Wall Heat Gain + Hourly Glass Heat Gain

    = HHGR +HHGW + HHGG

    HHGTP = Hourly Total Perimeter Heat Gain (btu/hr)

    = Hourly Wall Transmission Heat Gain + Hourly Wall Solar Heat Gain + Hourly Infiltration Heat Gain from Load Program

    HHGTIV = Hourly Total Interior Heat Gain Variable (btu/hr)

    = Hourly Roof Transmission Heat Gain + Hourly Roof Solar Heat Gain + Hourly Floor Heat Gain

    HHGTI = Hourly Total Interior Heat Gain

    = Hourly Total Interior Heat Gain Variable + Hourly Total Interior Heat Gain Constant

    = HHGTIV + HHGTIC

    Cooling Part Load Factor

    CPLF = Cooling Part Load Factor

    = Hourly heat Gain / Total heat gain

    = HHGT / HGT

    Load Hours

    Define one weekly occupied schedule per job

    HOF = Hourly Occupied Factor (1 if occupied and 0 if unoccupied)

    AOF = Annual Occupied Factor

    = Fraction of annual hours building is occupied

    OH = Occupied Hours / Week (hr/wk)

    = 12 hr/day x 5 days/wk (default)

    = 60 (default)

    UH = Unoccupied Hours / Week (hr/wk)

    = 12 hr/day x 5 days/wk + 24 hr/day x 2 days/wk (default)

    = 108 (default)

    TH = Total Hours / Week (hr/wk)

    = 24 hr/day x 7 days/wk (default)

    = 168 (default)

    Bin Hours

    BH = Hours in Bin (1 for hourly calculation)

    Heating Hours

    HBH = Heating Bin Hours (hr) for Bins Below Balance Point of XX degrees (default = 65F)

    Cooling Hours

    CBH = Cooling Bin Hours (hr) for Bins Above Balance Point of XX (default = 65F)

    Average Temperature

    AHT = Average Heating Temperature (deg F)

    = Sum for All Bins Σ (Average Temperature of XX Bin - Average Bin Temperature) (deg F) / (Total Heating Hours) x Hours for Bin

    For XX = 65F

    = Sum for All Bins below 65 Σ (62.5 - Average Bin Temperature) (deg F) / (Total Heating Hours) x Hours for Bin

    Balance Point

    BP = Outside temperature at which building can heat itself with internal heat gain

    = 65F (default)

    Flow:

    Air

    Constant Volume

    Fan Horsepower Constant Volume = Flow x Static Pressure x Conversion Factor / Fan Efficiency /Motor Efficiency

    = Flow (cfm) x S.P. (in. W.C.) x 6356 (cfm x in W.C. /hp) / Fan Efficiency / Motor Efficiency

    Variable Volume

    Cycle Constant Volume = Fan Horsepower Constant Volume x Equivalent Full Load Hours

    Cooling Part Load Eff.

    Cooling Part Load Efficiencies

    2/21/14

    Cooling Part Load Factor (CPLF)

    Type of EquipmentConstant Speed CompressorVariable Speed CompressorVariable Speed Frictionless Compressor

    Chillers

    Water Cooled

    Maximum Cooling Source Part Load COP Factor1.401.602.00

    Increase in Part Load Factor at 100% Load0.00%0.00%0.00%

    Increase in Part Load Factor at 75% Load50.00%40.00%40.00%

    Increase in Part Load Factor at 50% Load100.00%100.00%100.00%

    Increase in Part Load Factor at 25% Load90.00%90.00%90.00%

    Air Cooled

    Maximum Cooling Source Part Load COP Factor1.602.00

    Increase in Part Load Factor at 100% Load0.00%0.00%

    Increase in Part Load Factor at 75% Load50.00%40.00%

    Increase in Part Load Factor at 50% Load100.00%100.00%

    Increase in Part Load Factor at 25% Load90.00%90.00%

    Condensing Units

    Water Cooled

    Maximum Cooling Source Part Load COP Factor1.30

    Increase in Part Load Factor at 100% Load0.00%

    Increase in Part Load Factor at 75% Load50.00%

    Increase in Part Load Factor at 50% Load100.00%

    Increase in Part Load Factor at 25% Load90.00%

    Air Cooled

    Maximum Cooling Source Part Load COP Factor1.50

    Increase in Part Load Factor at 100% Load0.00%

    Increase in Part Load Factor at 75% Load50.00%

    Increase in Part Load Factor at 50% Load100.00%

    Increase in Part Load Factor at 25% Load90.00%

    VRF

    Water Cooled

    Maximum Cooling Source Part Load COP Factor1.80

    Increase in Part Load Factor at 100% Load0.00%

    Increase in Part Load Factor at 75% Load40.00%

    Increase in Part Load Factor at 50% Load100.00%

    Increase in Part Load Factor at 25% Load90.00%

    Air Cooled

    Maximum Cooling Source Part Load COP Factor1.90

    Increase in Part Load Factor at 100% Load0.00%

    Increase in Part Load Factor at 75% Load40.00%

    Increase in Part Load Factor at 50% Load100.00%

    Increase in Part Load Factor at 25% Load90.00%

    Heat Pumps

    Water Source

    Maximum Cooling Source Part Load COP Factor1.501.70

    Increase in Part Load Factor at 100% Load0.00%0.00%

    Increase in Part Load Factor at 75% Load35.00%35.00%

    Increase in Part Load Factor at 50% Load75.00%75.00%

    Increase in Part Load Factor at 25% Load100.00%100.00%

    Geothermal

    Maximum Cooling Source Part Load COP Factor1.501.70

    Increase in Part Load Factor at 100% Load0.00%0.00%

    Increase in Part Load Factor at 75% Load35.00%35.00%

    Increase in Part Load Factor at 50% Load75.00%75.00%

    Increase in Part Load Factor at 25% Load100.00%100.00%

    PTAC Units

    Maximum Cooling Source Part Load COP Factor1.50

    Increase in Part Load Factor at 100% Load0.00%

    Increase in Part Load Factor at 75% Load50.00%

    Increase in Part Load Factor at 50% Load100.00%

    Increase in Part Load Factor at 25% Load90.00%

    Pumps

    Maximum Part Load COP Factor at 25% Load

    Increase in Part Load Factor at 100% Load0.00%

    Increase in Part Load Factor at 75% Load50.00%

    Increase in Part Load Factor at 50% Load100.00%

    Increase in Part Load Factor at 25% Load90.00%

    Fans

    Maximum Part Load COP Factor at 25% Load

    Increase in Part Load Factor at 100% Load0.00%

    Increase in Part Load Factor at 75% Load50.00%

    Increase in Part Load Factor at 50% Load100.00%

    Increase in Part Load Factor at 25% Load90.00%

    Cooling Part Load Eff.

    11

    York

    Curve Fit

    Percent Load

    Load Factor

    Part Load Factor

    1

    1

    Cooling Part Load Data

    11

    McQuay

    Curve Fit

    Percent Load

    Load Factor

    Part Load Factor

    1

    1

    Air Srce Ht Pump Capacity Curve

    Part Load Factors

    Cooling Part Load Data

    2/21/14

    ChillersChillersChillersChillersWater Source Heat Pumps (Cooling)Water Source Heat Pumps (Cooling)Water Source Heat Pumps (Cooling)Water Source Heat Pumps (Cooling)Water Source Heat Pumps (Cooling)Water Source Heat Pumps (Cooling)Water Source Heat Pumps (Heating)Water Source Heat Pumps (Heating)Condensing UnitsRooftop UnitsPTAC UnitsVRFVRF

    Water Cooled - Scroll Constant Speed Step UnloadingWater Cooled - Variable Speed CentrifugalAir Cooled - Constant Speed Scroll Step UnloadingAir Cooled - Variable Speed ScrewClosed Loop - Constant SpeedClosed Loop - Variable SpeedGeothermal Closed Loop - Constant SpeedGeothermal Closed Loop - Variable SpeedGeothermal Open Loop - Constant SpeedGeothermal Open Loop - Variable SpeedClosed Loop - Constant SpeedClosed Loop - Variable SpeedAir Cooled - Constant Speed Scroll Step UnloadingAir Cooled - Constant SpeedAir Cooled - Constant SpeedAir Cooled - Variable SpeedWater Cooled - Variable Speed

    McQuay WGZ 045A (45 ton) Scroll (30 - 100 tons)Carrier Evergreen 23XXRMcQuay AGZ 045 (45 tons) Scroll (10 - 130 tons)York YVAA 200 tonsWaterFurnace NV036McQuay Inverter 036 (3 tons)McQuay Inverter 036 (3 tons)McQuay Invertor DrivenClimateMaster QE1860 (4 tons)ClimateMaster QE1860 (4 tons)McQuay Inverter 036 (3 tons)WaterFurnace NV036McQuay ACZ020B (20 tons) Scroll (10 to 40 tons)McQuay MPS026 (25 tons)McQuay PDAA 007 (7,000 btuh)Mitsubishi PURY -P96YKMU-A (-BS) Ducted 8 TonDaikin RWEYQ72PYDN Ducted 6 Ton Heat Recovery

    Percent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Air TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Air TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP Factor

    10015.24.451.001000.48025.07.321.001009.92.901.001001.00012.03.521.001008518.15.301.00(1)1008619.15.600.911007720.35.951.001007720.35.951.001005934.310.051.00(1)1005934.310.051.001007017.55.131.001007019.65.741.00(1)1009510.93.191.00(1)1009010.83.161.00(1)1009010.93.191.00(1)10012.23.571.00(1)100144.101.00

    7517.85.221.17750.34035.310.341.417513.23.871.33750.73016.44.821.37757522.36.531.231008521.16.181.00757720.35.951.00757728.08.201.38755934.310.051.00755943.012.601.25757017.55.131.00757019.85.801.01758513.03.811.19758012.03.521.11758012.03.521.107515.004.391.237518.005.271.29

    5020.35.951.34500.28042.912.561.715015.34.481.55500.55021.86.391.80506526.67.791.47(1)807731.29.141.48507720.35.951.00507742.012.312.07505934.310.051.00(1)505951.915.211.51507017.55.131.00507020.05.861.02(1)508014.64.281.34507013.53.961.25507013.53.961.245019.005.571.565023.006.741.64

    2520.45.981.34250.25048.014.061.922515.84.631.60250.50024.07.032.00256526.67.791.47757530.08.791.42257720.35.951.00257750.014.652.46255934.310.051.00255951.915.211.51257017.55.131.00257020.25.921.03256514.64.281.34256013.53.961.25256013.53.961.242522.006.451.802526.007.621.86

    020.45.981.3400.25048.014.061.92015.84.631.6000.50024.07.032.00026.67.791.47506534.09.961.61020.35.951.00050.014.652.46034.310.051.00051.915.211.51017.55.131.00020.25.921.03014.64.281.34013.53.961.25013.53.961.24022.006.451.80026.007.621.86

    256534.09.961.61

    Catalog IPLV19.2Calculated IPLV40.1Catalog IPLV14.5Calculated IPLV19.7Calculated IEER23.8034.09.961.61Calculated IEER20.3Calculated IEER33.9Calculated IEER34.3Calculated IEER46.1Calculated HSPFCalculated HSPFCatalog IPLV14.3Catalog IEER12.8Catalog IEERCatalog IEER(1)19.7Catalog IEER(1)24.1

    Calculated IPLV19.2Catalog IPLV40.0Calculated IPLV14.4Calculated IEERCalculated IEERCalculated IEERCalculated IEERCalculated IEERCalculated IEERFor AHRI Climate Zone 417.5For AHRI Climate Zone 419.8Calculated IEERCalculated IEER12.8(1)Catalog Rating12.8Calculated IEER20.0Calculated IEER23.9

    Calculated IEERCalculated IEERCalculated IEERw/5% for Chilled Waterw/5% for Condenser WaterCalculated IEER31.3w/5% for Condenser Waterw/5% for Condenser Waterw/5% for Condenser Waterw/5% for Condenser WaterCalculated IEERCalculated IEERw/5% for Evaporator(1)Catalog Rating(1)AHRI Rating(1)AHRI Rating

    w/15% for Cooling Towerw/5% for Chilled Waterw/5% for Chilled WaterPump HP17.6Pump HP22.1Calculated IEERPump HP19.3Pump HP32.2Pump HP32.6Pump HP43.8w/5% for Condenser Waterw/5% for Condenser WaterFan HP12.2Calculated IEER17.6Calculated IEER19.8

    Cond. and CW Pump HP15.9Pump HP32.7Pump HP13.3w/5% for Condenser Water(1)Catalog RatingPump HP16.6Pump HP18.9(1)Catalog Ratingw/12% for Pumping Energyw/17% for Pumping

    Pump HP29.1and Cooling Tower Energy

    (1)Catalog RatingGround loop condition per AHRI is 77F. Used 77F for ground loop ratings to be conservative.

    Air Cooled - Constant Speed ScrollGeothermal Open Loop - Variable Speed

    Water Cooled - Screw Constant Speed Continuous UnloadingWater Cooled - Variable Speed FrictionlessAir Cooled - Variable Speed ScrewGeothermal Closed Loop - Variable SpeedAir Cooled - Variable Speed

    McQuay WGS 170 (170 ton) Screw (120 - 200 tons)Smardt 250 tonsCarrier (10 tons) -McQuay PathfinderClimateMaster QE1860 (4 tons)ClimateMaster QE1860 (4 tons)ClimateMaster QE1860 (4 tons)ClimateMaster QE1860 (4 tons)WaterFurnace NV036ClimateMaster QE1860 (4 tons)WaterFurnace NV036McQuay DPS 010 (10 tons) Invertor CompressorDaikin REYQ96PBYD Ducted 8 Ton Heat Recovery

    Percent LoadKW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorWaterFurnace NV036Percent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorWaterFurnace NV036Percent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP Factor

    1000.71516.84.921.001000.60020.05.861.0010010.53.081.001001.00012.03.521.00(2)1008621.66.330.97(2)1008621.66.331.02(2)1008621.66.331.00(2)1008621.66.330.771005928.98.471.00Percent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP Factor1007012.23.571.001004015.04.391.00(1)1009012.53.661.00(1)10012.13.551.00

    750.58020.76.061.23750.45026.77.811.337513.203.871.26750.73016.44.821.371008519.05.571.001008519.05.571.00(1)807721.66.331.00(1)1007721.66.331.00755928.98.471.00(1)1005929.08.501.00757012.23.571.00754014.54.250.97758016.04.691.487515.004.391.24

    500.50024.07.031.43500.33036.410.651.825016.234.761.55500.55021.86.391.82(1)807721.66.331.14(1)807721.66.331.14757721.66.331.00757730.08.791.39505928.98.471.00755931.49.201.08507012.23.571.00504014.04.100.93507022.06.452.045019.005.571.56

    250.52622.86.681.36250.30040.011.722.002518.295.361.74250.50024.07.032.00757526.07.621.37757525.07.321.32507721.66.331.00(1)507740.211.781.86255928.98.471.00(1)505933.19.701.14257012.23.571.00254014.04.100.93256022.06.452.042522.006.451.80

    00.52622.86.681.3600.30040.011.722.00018.295.361.7400.50024.07.032.00506532.09.381.68506548.014.062.53257721.66.331.00257740.211.781.86028.98.471.00255934.09.961.17012.23.571.00014.04.100.93022.06.452.04022.006.451.80

    (1)256532.09.381.68256548.014.062.53021.66.331.00040.211.781.86034.09.961.17

    Catalog IPLV0.53622.4Calculated IPLV32.6Catalog IPLV14.5Calculated IPLV19.7(1)205934.310.051.81(1)205951.915.212.73Calculated IEER28.9Calculated HSPFCalculated HSPFCatalog IEER19.4Catalog IEER(1)19.7

    Calculated IPLV22.4Catalog IPLVCalculated IPLV15.1Catalog IPLV19.6034.310.051.81051.915.212.73Calculated IEER21.6Calculated IEER33.5Calculated IEERCalculated IEER32.1For AHRI Climate Zone 412.2For AHRI Climate Zone 414.6Calculated IEER19.4Calculated IEER20.0

    Calculated IEERCalculated IEERCalculated IEERCalculated IEERCalculated IEERCalculated IEERw/5% for Condenser WaterCalculated IEERCalculated IEERCalculated IEER(1)Catalog Rating(1)AHRI Rating

    w/15% for Cooling Towerw/15% for Cooling Towerw/5% for Chilled Waterw/5% for Chilled WaterCalculated IEER28.0Calculated IEER33.2w/5% for Condenser Waterw/5% for Condenser WaterPump HP27.5w/5% for Condenser Waterw/5% for Condenser Waterw/5% for Condenser WaterCalculated IEER17.6

    Cond. and CW Pump HP18.4(1)Cond. and CW Pump HP25.9Pump HP13.8Pump HP17.6Calculated IEERCalculated IEERPump HP20.5Pump HP31.9Pump HP30.5Pump HP11.6Pump HP13.6w/12% for Pumping Energy

    w/5% for Condenser Waterw/5% for Condenser Water(1)Catalog Rating(1)Catalog Rating(1)Catalog Rating

    Catalog RatingPump HP26.1Pump HP30.9(2)Catalog rating appears to be incorrect as published on website. Website lists gound loop rating conditions at 86F. This is water source loop rating conditions.

    (1)Catalog Rating(1)Catalog RatingGround loop condition per AHRI is 77F. Used 77F for ground loop ratings to be conservative.

    (2)Catalog rating appears to be incorrect as published on website. Website lists gound loop rating conditions at 86F. This is water source loop rating conditions.(2)Catalog rating appears to be incorrect as published on website. Website lists gound loop rating conditions at 86F. This is water source loop rating conditions.(2)Catalog rating appears to be incorrect as published on website. Website lists gound loop rating conditions at 86F. This is water source loop rating conditions.

    Ground loop condition per AHRI is 77F. Used 77F for ground loop ratings to be conservative.Ground loop condition per AHRI is 77F. Used 77F for ground loop ratings to be conservative.Ground loop condition per AHRI is 77F. Used 77F for ground loop ratings to be conservative.

    Water Source Heat Pumps (Heating)

    Water Cooled - Centrifugal Constant Speed Continuous UnloadingAir Cooled - Constant Speed Screw Continous UnloadingAir Cooled - Variable Speed FrictionlessGeothermal Open Loop - Variable Speed

    McQuay WPV 280 (280 tons) Centrifugal (200 - 400 tons)McQuay WMC (Frictionless) 150 tonsMcQuay AGS 440 (440 tons) Screw (230 - 475 tons)Airedale TurbochillWaterFurnace NV036WaterFurnace NV036WaterFurnace NV036WaterFurnace NV036WaterFurnace NV036

    Percent LoadKW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP Factor

    1000.62019.45.671.001000.68017.65.171.00(1)10010.43.051.001001.111.33.301.00(1)1008518.15.301.001007721.06.151.00(1)1007721.06.151.001007019.65.741.001005016.24.751.00

    750.53022.66.631.17750.51023.56.891.337512.43.631.19750.814.74.301.22757525.07.321.38757721.06.151.00757722.26.501.06757019.65.741.00755015.64.570.96

    500.51523.36.831.20500.37032.49.501.845014.94.371.43500.618.85.501.56(1)506529.58.641.63507721.06.151.00(1)507723.06.741.10507019.65.741.00505014.94.370.92

    250.51023.56.891.22250.34035.310.342.002516.04.691.54250.525.67.502.13256529.58.641.63257721.06.151.00257724.07.031.14257019.65.741.00255014.94.370.92

    00.51023.56.891.2200.34035.310.342.00016.04.691.5400.525.67.502.13029.58.641.63021.06.151.00024.07.031.14019.65.741.00014.94.370.92

    Calculated IPLV0.52223.0Catalog IPLV0.41229.1(1)Catalog IPLV13.9Calculated IPLV17.8Calculated IEER26.5Calculated IEER21.0Calculated IEER22.6Calculated HSPFCalculated HSPF

    Catalog IPLV0.520Calculated IPLV0.41528.9Calculated IPLV13.9Catalog IPLVCalculated IEERCalculated IEERCalculated IEERFor AHRI Climate Zone 419.6For AHRI Climate Zone 415.6

    Calculated IEERCalculated IEERCalculated IEERCalculated IEERw/5% for Condenser Waterw/5% for Condenser Waterw/5% for Condenser WaterCalculated IEERCalculated IEER

    w/15% for Cooling Towerw/15% for Cooling Towerw/5% for Chilled Waterw/5% for Chilled WaterPump HP24.6Pump HP20.0Pump HP21.5w/5% for Condenser Waterw/5% for Condenser Water

    and CW Pump HP19.4Cond. and CW Pump HP23.0Pump HP12.7Pump HP16.1(1)Catalog Rating(1)Catalog RatingPump HP18.6Pump HP14.6

    (1)Catalog Rating

    Water Cooled - Centrifugal Constant Speed Continuous UnloadingAir Cooled - Constant Speed Screw Continous UnloadingGeothermal Closed Loop - Constant Speed

    McQuay WDC Dual Compressor Centrifugal (400 - 2500 tons)McQuay Pathfinder Screw (170 - 550 tons)WaterFurnace NV036

    Percent LoadKW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)KW/TONEERCOPCooling Compressor Part Load COP FactorPercent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP Factor

    1000.51023.56.891.0010012.23.571.001004015.04.391.00AHRI Climate Zone 4Bin%Bin Hours

    750.42028.68.371.217514.04.101.35754015.04.391.00620.132

    500.38031.69.251.345017.04.981.63504015.04.391.00570.111

    250.38031.69.251.342520.05.861.92254015.04.391.00520.103

    00.38031.69.251.34020.05.861.92015.04.391.00100% Load0.346

    470.093

    Calculated IPLV0.39830.2Catalog IPLV16.2Calculated HSPF420.100

    (1)Catalog IPLV0.52030.0Calculated IPLV16.1For AHRI Climate Zone 415.0370.109

    Calculated IEERCalculated IEERCalculated IEER320.126

    w/15% for Cooling Towerw/5% for Chilled Waterw/5% for Condenser Water75% Load0.428

    and CW Pump HP25.1Pump HP14.7Pump HP14.3270.087

    220.055

    (1)Catalog Rating170.036

    120.026

    50% Load0.204

    70.013

    20.006

    Geothermal Open Loop - Constant Speed-30.002

    -80.001

    WaterFurnace NV03625% Load0.022

    Percent Load (PL)Entering Water TemperatureEERCOPCooling Compressor Part Load COP Factor

    1005016.24.751.00

    755016.24.751.00

    505016.24.751.00

    255016.24.751.00

    016.24.751.00

    Calculated HSPF

    For AHRI Climate Zone 416.2

    Calculated IEER

    w/5% for Condenser Water

    Pump HP15.4

    AHRI Climate Zone 4Bin%Bin Hours

    620.132

    570.111

    520.103

    100% Load0.346

    470.093

    420.100

    370.109

    320.126

    75% Load0.428

    270.087

    220.055

    170.036

    120.026

    50% Load0.204

    70.013

    20.006

    -30.002

    -80.001

    25% Load0.022

    Air Srce Ht Pump Capacity Curve

    Percent Load

    COP Load Factor

    Part Load COP Factor

    y = -6E-05x2 + 0.0023x + 1.3378

    Air Srce Ht Pump COP Curve Fit

    Percent Load

    COP Load Factor

    Part Load COP Factor

    y = -8E-05x2 + 0.005x + 1.3405

    VRF Heating Part Load

    Percent Load

    Load Factor

    Part Load Factor

    Pump Part Load Eff.

    Percent Load

    COP Load Factor

    Part Load COP Factor

    y = -6E-05x2 + 0.0002x + 1.5508

    Pumping Energy

    1

    Percent Load

    Load Factor

    Part Load Factor

    y = -7E-05x2 - 0.0009x + 1.7644

    1

    Pumping Energy1

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Central Plant Sources

    Percent Load

    Load Factor

    Part Load Factor

    y = -6E-05x2 - 0.0025x + 1.8375

    Distribution Systems

    Percent Load

    COP Load Factor

    Part Load COP Factor

    y = -6E-05x2 + 0.0002x + 1.5508

    Terminal Units

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Consolidated

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -7E-05x2 - 0.0009x + 1.7644

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    1

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    1

    1

    Percent Load

    Load Factor

    Part Load Factor

    y = -7E-05x2 - 0.0009x + 1.7644

    1

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    COP Load Factor

    Part Load COP Factor

    y = -6E-05x2 + 0.0002x + 1.5508

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    Percent Load

    Load Factor

    Part Load Factor

    Percent Load

    Load Factor

    Part Load Factor

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    1

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    1

    1

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    1

    1

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    1

    1

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    1

    1

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    1

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    COP Load Factor

    Part Load COP Factor

    Percent Load

    Load Factor

    Part Load Factor

    y = -6E-05x2 - 0.0025x + 1.8375

    Percent Load

    Load Factor

    Part Load Factor

    y = -8E-05x2 - 0.001x + 1.8837

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -7E-05x2 - 0.0009x + 1.7644

    Percent Load

    Load Factor

    Part Load Factor

    y = -7E-05x2 - 0.0009x + 1.7644

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Percent Load

    Load Factor

    Part Load Factor

    y = -7E-05x2 - 0.0009x + 1.7644

    Percent Load

    Load Factor

    Part Load Factor

    y = -7E-05x2 - 0.0009x + 1.7644

    Percent Load

    Load Factor

    Part Load Factor

    y = -9E-05x2 - 1E-04x + 1.8661

    Air Source Heat Pump

    2/21/14

    Heat Pump Heating CapacityHeating Consumption for

    Century (Nominal 36,000 Cooling Capacity)TotalHeating COPHeating CapacityHeating Load (BTUH)Electrical DemandHeat EnergyBackup HeatBackup EnergyWeighted AverageWeighted AverageEquivalent Full

    Ambient AirHeating(BTUH) for NominalDesign =100,000(KW)(BTU)(BTUH)(BTU)Temperature byTemperature byLoad Heating Hours

    TemperatureCapacityCooling Capacity =36,000Bin HoursBin Hours

    (Deg. F)(Btuh)Mid-ptsDB (F)Hrs(65-Bin Temp)(Bin Temp)

    -10179506564 to 662633.5847,08803.90000.02.60

    0182006362 to 642613.5146,0082,9413.8767,647000.12.58

    10189006160 to 623023.4444,9283,0303.8915,152000.22.818

    20196005958 to 601973.3743,8488,8243.81,738,235000.21.717

    30213505756 to 583063.3042,76811,7653.83,600,000000.42.636

    40262505554 to 564653.2341,68814,7063.86,838,235000.73.814

    50392005352 to 542953.1640,60817,6473.85,205,882000.52.352

    60490005150 to 523053.0939,52820,5883.86,279,412000.62.363

    70539004948 to 502973.0238,44823,5293.76,988,235000.72.270

    4746 to 483152.9537,36826,4713.78,338,235000.92.283

    Comfortmaker (Nominal 36,000 Btuh Cooling Capacity)4544 to 463422.8836,28829,4123.710,058,824001.02.3101

    Ambient AirHeating4342 to 443162.8135,20832,3533.710,223,529001.02.0102

    TemperatureCapacity4140 to 422002.7434,12835,2943.77,058,8241,166233,2240.71.271

    (Deg. F)(Btuh)3938 to 403282.6733,04838,2353.612,541,1765,1871,701,4321.31.9125

    -103736 to 384532.6031,96841,1763.618,652,9419,2084,171,4371.92.5187

    0140003534 to 363452.5330,88844,1183.615,220,58813,2304,564,2281.61.8152

    10172003332 to 343322.4629,80847,0593.615,623,52917,2515,727,2731.61.6156

    20210003130 to 322262.3928,72850,0003.511,300,00021,2724,807,4721.21.1113

    30266002928 to 302002.3227,64852,9413.510,588,23525,2935,058,6351.10.9106

    40321002726 to 281922.2526,56855,8823.510,729,41229,3145,628,3561.10.8107

    50378002524 to 261352.1825,48858,8243.47,941,17633,3364,500,2960.80.579

    60433002322 to 24912.1124,40861,7653.45,620,58837,3573,399,4600.60.356

    70490002120 to 22802.0423,32864,7063.45,176,47141,3783,310,2310.50.352

    Heating Capacity Equation (Normalized for Nominal Cooling Capacity)m = slopeb = x-axis intersection1918 to 201121.9722,24867,6473.37,576,47145,3995,084,6950.80.376

    Trane (Nominal 36,000 Btuh Cooling Capacity)y = (mx + b) / Nominal Cooling Capacity= rise / run= 120001716 to 18721.9021,16870,5883.35,082,35349,4203,558,2570.50.251

    Ambient AirHeatingCapacity = (m * (Ambient Air) + b) / Nominal Cooling Capacity= (45000 - 10000) / (60 - (-5))1514 to 16641.8320,08873,5293.24,705,88253,4413,420,2500.50.147

    TemperatureCapacity= (538 * Ambient Air + 12000) / 36000= 35000 / 651312 to 14621.7619,00876,4713.24,741,17657,4633,562,6800.50.147

    (Deg. F)(Btuh)= .015 * Ambient Air + .333= 5381110 to 12561.6917,92879,4123.14,447,05961,4843,443,0910.50.144

    -10600098 to 10251.6216,84882,3533.12,058,82465,5051,637,6240.20.021

    010900Heating Capacity Equation76 to 841.5515,76885,2943.0341,17669,526278,1040.00.03

    1016400Heating Capacity = (.015* Ambient Air + .333) * Nominal Cooling Capacity54 to 631.4814,68888,2352.9264,70673,547220,6420.00.03

    202060032 to 471.4113,60891,1762.8638,23577,568542,9790.10.06

    302660010 to 261.3412,52894,1182.7564,70681,590489,5380.10.06

    4032600-1-2 to 011.2711,44897,0592.797,05985,61185,6110.0-0.01

    5039000-3-4 to -211.2010,368100,0002.5100,00089,63289,6320.0-0.01

    6045700Total6,659212,023,97565,515,1480.02,074

    7052600Average Heating Temperature21.740.7

    Total Backup Energy by Formula = Total Heat Loss (btu/hr) - Average Heat Pump Capacity (btu/hr) x EFLHH65

    =(Total Heat Loss (btu/hr) - ((0.015 x AHT + 0.333) x Heat Pump Nominal Cooling Capacity)) x EFLHH65

    =136,971,510

    -10-10-10

    000

    101010

    202020

    303030

    404040

    505050

    606060

    707070

    Century

    Comfortmaker

    Trane

    Ambient Air Temperarure (0F)

    Heating Capacity (Btuh)

    Air Source Heat Pump COP

    17950

    6000

    18200

    14000

    10900

    18900

    17200

    16400

    19600

    21000

    20600

    21350

    26600

    26600

    26250

    32100

    32600

    39200

    37800

    39000

    49000

    43300

    45700

    53900

    49000

    52600

    Air Source Heat Pump

    2/21/14

    Average Heating COP

    Century

    Ambient AirHeating

    TemperatureCOP

    (Deg. F)

    -101.89

    01.92

    101.98

    202.01

    302.1

    402.43

    503.24

    604.02

    704.35

    Comfortmaker

    Ambient AirHeating

    TemperatureCOP

    (Deg. F)

    -101.1

    01.49

    101.78

    202.09

    302.42

    402.76

    503.1

    603.38

    704.35

    COP Equationm = slopeb = x-axis intersection

    Traney = mx + b= rise / run= 1.3

    Ambient AirHeatingCOP = m * (Ambient Air) + b= (3.6 - 0.8) / (70 - (-10))

    TemperatureCOP= .035 * Ambient Air + 1.3= 2.8 / 80

    (Deg. F)= .035

    -101

    01.3

    101.78

    202.05

    302.46

    402.82

    503.16

    603.46

    703.73

    Heating Capacity Curve Fit

    Comfortmaker

    Trane

    Ambient Air Temperarure

    Heating COP

    Air Source Heat Pump Heating COP

    VRF Part Load Factors

    Heating Part Load Data

    2/21/14

    VRF

    Air Cooled - Variable Speed

    Mitsubishi - PUHY-P120YHMU (page 60 of Mitsubishi catalog)

    Ambient Temperature (F)Percent CapacityHeating Capacity (btuh)Heating Capacity (watts)Percent Power InputPower Input (watts)COPAHRI COP at 47FAHRI COP

    100.012000035.29.33.43

    6064.07680022.542.03.95.793.92

    5064.07680022.548.04.45.063.43

    4064.07680022.556.05.24.342.94

    3064.07680022.568.06.33.572.42

    2064.07680022.585.07.92.861.94

    1064.07680022.5105.09.72.311.57

    052.06240018.3103.09.51.921.30

    -1010.0120003.5102.09.40.370.25

    Calculated IEER62.2

    AHRI Rating

    Calculated IEER52.9

    w/15% for Pumping Energy

    Heating COP Curve Fit

    Ambient Temperature (F)

    Heating Capacity (Btuh)

    Heating Capacity

    Ambient Temperature (F)

    COP

    Heating COP

    Sensorless Pump DatabaseOriginal DB

    Pump:KV1506AE2HCB098MRev 14/9/13

    FlowDesignDelta PPipePumpPumpDrive:

    FlowPercent ofHeadHeadHeadEfficiencyEfficiency

    gpmDesignft.ft.ft.%FactorVFD HzTYPEUnitsCondition 1Condition 2Condition 3Condition 4Condition 5Condition 6Condition 7Condition 8Condition 9Condition 10

    62 HzHeadft42.54343.49443.37542.01139.61435.22528.62521.63412.4054.063

    Delta TFlowgpm0.00011.30524.70035.21444.59555.95667.71777.96089.93899.045

    0.00.00VFD PowerHP0.4640.5730.7030.8070.8940.9911.0711.1301.1861.216

    12.50.2534.00.02.149.6%1.00Motor Speedrpm

    25.00.5034.00.08.549.6%1.00Efficiencypercent0.0%21.7%38.5%46.3%49.9%50.2%45.7%37.7%23.8%8.4%

    37.50.7534.00.019.149.6%1.00Shutoff HP % of BEP HP46.8%

    50.01.0034.00.034.049.6%1.00

    VFD HzTYPEUnitsCondition 1Condition 2Condition 3Condition 4Condition 5Condition 6Condition 7Condition 8Condition 9Condition 10

    Delta P = 25% of Design60 HzHeadft39.93440.75740.72839.42236.73432.77926.60519.93012.0633.719

    0.00.00Flowgpm0.00011.38322.93433.92244.44654.52365.93376.01386.39995.957

    12.50.2534.08.510.126.0%0.52VFD PowerHP0.4290.5320.6340.7380.8320.9120.9881.0411.0831.115

    25.00.5034.08.514.939.0%0.79Motor Speedrpm0.022.037.245.849.649.544.836.724.38.1

    37.50.7534.08.522.846.0%0.93Efficiencypercent0.0%22.0%37.2%45.8%49.6%49.5%44.8%36.7%24.3%8.1%

    50.01.0034.08.534.049.6%1.00Shutoff HP % of BEP HP47.0%

    Delta P = 50% of DesignVFD HzTYPEUnitsCondition 1Condition 2Condition 3Condition 4Condition 5Condition 6Condition 7Condition 8Condition 9Condition 10

    0.00.0050 HzHeadft27.61728.19728.18527.40525.39023.03218.80412.9258.0772.462

    12.50.2534.017.018.128.0%0.56Flowgpm0.00010.12618.61727.10036.98244.29354.16164.70872.58879.991

    25.00.5034.017.021.340.0%0.81VFD PowerHP0.2770.3280.3810.4360.4980.5380.5840.6210.6440.662

    37.50.7534.017.026.646.5%0.94Motor Speedrpm

    50.01.0034.017.034.049.6%1.00Efficiencypercent0.0%22.0%34.8%43.0%47.6%47.9%44.0%34.0%23.0%7.5%

    Pump Part Load Efficiency Factor (PPLEF)Shutoff HP % of BEP HP51.5%

    Delta P = 75% of DesignDelta P

    0.00.00PPLEF = 1.4882 x PLF(3) - 3.3493 x PLF(2) + 2.8111 x PLF + .0496VFD HzTYPEUnitsCondition 1Condition 2Condition 3Condition 4Condition 5Condition 6Condition 7Condition 8Condition 9Condition 10

    12.50.2534.025.526.030.0%0.60Delta T40 HzHeadft17.67017.99818.01017.32416.39414.59111.6638.9205.1401.575

    25.00.5034.025.527.642.0%0.85PPLEF = 1Flowgpm0.0008.54915.53923.55128.85535.99144.15750.47858.05563.952

    37.50.7534.025.530.347.0%0.95VFD PowerHP0.1500.1850.2150.2470.2680.2930.3160.3310.3440.354

    50.01.0034.025.534.049.6%1.00Motor Speedrpm

    Efficiencypercent0.0%21.0%32.9%41.7%44.6%45.3%41.2%34.4%21.9%7.2%

    Delta P = 90% of DesignFlow (Load)DesignDelta PPipePumpPumpPumpShutoff HP % of BEP HP51.2%

    0.00.00Fraction ofHeadHeadHeadHeadEfficiencyHP

    12.50.3334.0030.030.332.0%0.65DesignFactorVFD HzTYPEUnitsCondition 1Condition 2Condition 3Condition 4Condition 5Condition 6Condition 7Condition 8Condition 9Condition 10

    25.00.6734.0030.031.040.0%0.8130 Hz HeadHeadft9.8089.99410.0109.7699.0517.9806.4204.8182.7960.766

    37.51.0034.0030.032.348.0%0.97Delta P = 25% of DesignFlowgpm0.0005.82911.46916.22522.01527.51233.18138.07843.55848.093

    50.01.3334.0030.034.049.6%1.000.051.000.250.000.250.180.07VFD PowerHP0.0760.0890.1030.1140.1270.1380.1470.1530.1580.162

    0.251.000.250.050.300.570.13Motor Speedrpm

    Delta P = 100% of Design0.501.000.250.190.440.800.27Efficiencypercent0.0%16.5%28.1%35.1%39.6%40.2%36.6%30.3%19.5%5.7%

    0.00.000.751.000.250.420.670.900.56Shutoff HP % of BEP HP55.1%

    12.50.2534.034.034.028.0%0.561.001.000.250.751.001.001.00

    25.00.5034.034.034.040.0%0.81VFD HzTYPEUnitsCondition 1Condition 2Condition 3Condition 4Condition 5Condition 6Condition 7Condition 8Condition 9Condition 10

    37.50.7534.034.034.047.0%0.95Delta P = 50% of Design20 HzHeadft4.1994.2814.2774.1373.8483.4642.8132.2891.2150.197

    50.01.0034.034.034.049.6%1.000.051.000.500.000.500.180.14Flowgpm0.0005.8487.65311.83015.20418.19121.86124.27728.60132.303

    0.251.000.500.030.530.570.23VFD PowerHP0.0370.0420.0450.0490.0520.0550.0570.0590.0610.063

    SAT Program Pump Efficiency Factor (PEF) Curve0.501.000.500.130.630.800.39Motor Speedrpm0.015.118.425.228.428.927.223.814.42.6

    0.00.000.050.751.000.500.280.780.900.65Efficiencypercent0.0%15.1%18.4%25.2%28.4%28.9%27.2%23.8%14.4%2.6%

    12.50.2534.034.034.028.0%0.561.001.000.500.501.001.001.00Shutoff HP % of BEP HP67.3%

    25.00.5034.034.034.040.0%0.81

    37.50.7534.034.034.047.0%0.90Delta P = 75% of Design

    50.01.0034.034.034.049.6%1.000.051.000.750.000.750.180.21

    0.251.000.750.020.770.570.34

    0.501.000.750.060.810.800.51

    0.751.000.750.140.890.900.74

    Fraction1.001.000.750.251.001.001.00

    Shutoff

    ShutoffDesignHeadShutoffShutoffFractionDelta P = 100% of Design

    HeadHeadof BEPHPHPShutoff HP0.051.001.000.001.000.180.27

    ftftHeadof BEP HP0.251.001.000.001.000.570.44

    0.501.001.000.001.000.800.62

    4.235.000.120.0371.00.040.751.001.000.001.000.900.83

    9.835.000.280.0761.00.081.001.001.000.001.001.001.00

    17.735.000.500.1501.00.15

    27.635.000.790.2771.00.28Delta T

    39.935.001.140.4291.00.430.051.000.000.000.000.180.00

    0.251.000.000.060.060.570.03

    0.501.000.000.250.250.800.16

    0.751.000.000.560.560.900.47

    1.001.000.001.001.001.001.00

    Minimum Shutoff Pump Horsepower = 0.1105 x (Delta P % of Design Head)(2) + 0.2515 x (Delta P % of Design Head) + .001

    Percent Shutoff HP of BEP HP

    Percent Shutoff Head (Delta P) of BEP (Design) Head

    Percent Shutoff HP of BEP (Design) HP

    Percent Shutoff HP of BEP HP (Minimum Shutoff Pump Horsepower)

    y = 0.1105x2 + 0.2515x + 0.001

    Delta P = 25% of Design Head

    Delta P = 50% of Design Head

    Delta P = 75% of Design Head

    Delta P = 90% of Design

    Delta P = 100% of Design Head

    Delta T

    Pump Efficiency Factor Curve

    (Heating or Cooling) Part Load Factor

    Pump Part Load Efficiency Factor

    Pump Part Load Efficiency Factor for Different Delta P

    y = 1.4882x3 - 3.3493x2 + 2.8111x + 0.0496

    Pumping Horsepower

    2/21/14

    Heat Gain

    = 200' x 200' x 25 btuh/sq. ft.1000000btuhDistribution/Pumping Energy Percent of Compressor Horsepower

    83tonsPipe/Duct Length0100200300400500

    FlowsHydronic (Conventional)Hydronic (2 Pipe)2.4%2.7%3.1%3.5%3.8%4.2%

    Hydronic (Conventional) = Heat Gain / 500 / 10F delta T200gpmHydronic (Chilled Beam/LOFlo)Hydronic (1 Pipe)1.5%1.7%1.9%2.1%2.3%2.5%

    Hydronic (Heat Pump) = Heat Gain / 500 / 10F delta T *1.25 (heat of rejection)250gpmAir (Fan Coil)Air (Low Pressure Rooftop)6.8%8.0%9.3%10.5%11.8%13.1%

    Hydronic (1 pipe LOFlo Primary) = Heat Gain / 500 / 18F delta T111Air (VAV)Air (Medium Pressure VAV)15.5%19.9%24.3%28.7%33.1%37.5%

    Hydronic (1 pipe LOFlo Secondary) = Heat Gain / 500 / 5F delta T400gpmRefrigerant (VRF - AHRI)VRF1.0%6.0%12.0%18.0%24.0%30.0%

    Air = Heat Gain / 1.085 / 25F delta T36866cfm

    Efficiencies

    Pump80%

    Fan65%

    Motor90%

    Compressor Horsepower

    EER (btuh/watt)13

    COP = EER (/ 3.4133.8

    Compressor Horsepower

    = Heat Gain (btuh) / COP / 3.413 (btuh/watt)

    / 1,000 (watts/kw) / .75 (kw/hp)103hp

    Pipe Pressure Drop

    Pipe Length (ft)0100200300400500

    Hydronic (Conventional)

    Pipe Length (ft)0100200300400500

    Head (ft)

    Fixed

    Chiller Evaporator101010101010

    Pump Accessories555555

    Cooling coil555555

    Control Valve101010101010

    Balance Valve555555

    Subtotal353535353535

    Variable Pipe Friction

    = 4' / 100' x pipe length x 1.3 equivalent length0510162126

    Total354045515661

    Pump Horsepower

    = Flow x Head / 3960 / Pump Efficiency / Motor Efficiency2.462.823.183.553.914.28

    Hydronic (Chilled Beam LOFlo Primary)

    Pipe Length (ft)0100200300400500

    Head (ft)

    Fixed

    Chiller Evaporator101010101010

    Pump Accessories555555

    Subtotal151515151515

    Variable Pipe Friction

    = 4' / 100' x pipe length x 1.3 equivalent length0510162126

    Total152025313641

    Pump Horsepower

    = Flow x Head / 3960 / Pump Efficiency / Motor Efficiency0.580.790.991.191.401.60

    Hydronic (Chilled Beam LOFlo Secondary)

    Pipe Length (ft)0100200300400500

    Head (ft)

    Fixed

    Cooling coil555555

    Control Valve000000

    Balance Valve000000

    Subtotal555555

    Variable Pipe Friction

    = 4' / 100' x 30' pipe length x 1.3 equivalent length222222

    Total777777

    Pump Horsepower

    = Flow x Head / 3960 / Pump Efficiency / Motor Efficiency0.920.920.920.920.920.92

    Hydronic (Chilled Beam LOFlo Total)

    Pump Horsepower (Total)1.501.711.912.112.322.52

    Air (Rooftop)

    Duct Length (ft)0100200300400500

    Static Pressure

    Fixed

    Unit Casing0.050.050.050.050.050.05

    Cooling coil0.250.250.250.250.250.25

    Filter0.200.200.200.200.200.20

    Balance Damper0.100.100.100.100.100.10

    Grille0.100.100.100.100.100.10

    Subtotal0.700.700.700.700.700.70

    Variable Duct Friction

    = 0.1" / 100' x duct length x 1.3 equivalent length0.000.130.260.390.520.65

    Total0.700.830.961.091.221.35

    Fan Horsepower

    = Flow x Static Pressure / 6356 / Fan Efficiency / Motor Efficiency6.948.239.5210.8112.1013.39

    Air (VAV)

    Duct Length (ft)0100200300400500

    Static Pressure

    Fixed

    Unit Casing0.100.100.100.100.100.10

    Cooling coil0.750.750.750.750.750.75

    Filter0.500.500.500.500.500.50

    VAV Box Damper0.250.250.250.250.250.25

    Balancing Damper0.100.100.100.100.100.10

    Grille0.100.100.100.100.100.10

    Subtotal1.601.601.601.601.601.60

    Variable Duct Friction

    = 0.35" / 100' x duct length x 1.3 equivalent length0.000.460.911.371.822.28

    Total1.602.062.512.973.423.88

    Fan Horsepower

    = Flow x Static Pressure / 6356 / Fan Efficiency / Motor Efficiency15.8620.3824.8929.4033.9138.42

    Refrigerant (VRF)

    Compressor capacity pipe length correction factor

    Pipe length (ft)0100200300400500

    Equivalent pipe length = pipe length x 1.3 (ft)0150300450600750

    Equivalent pipe length = pipe length x 1.3 (m)04691137183229

    Sources

    Daikin (equivalent pipe length)1.0000.9300.8600.8100.7800.760

    Mitsubishi (equivalent pipe length)1.0000.9300.8650.8100.7500.700

    AHRI (pipe length)0.9900.9400.8800.8200.7600.700

    ASHRAE Guide1.0000.9850.9650.9500.9300.920

    Daikin (equivalent length)Mitsubishi (equivalent length)AHRI Standard 1230-2013 (pipe length)ASHRAE Guide

    Hydronic (1 Pipe)

    Hydronic (2 Pipe)

    Air (Low Pressure Rooftop)

    Air (Medium Pressure VAV)

    VRF

    Pipe Length

    Percent of Compressor Horsepower

    Distribution/Pumping Energy

    Pumping Horsepower

    2/21/14

    Heat Gain

    = 200' x 200' x 25 btuh/sq. ft.1000000btuhDistribution/Pumping Energy Percent of Compressor Horsepower

    83tonsPipe/Duct Length0100200300400500

    FlowsHydronicHydronic0.0%0.4%0.7%1.1%1.4%1.8%

    Hydronic (Conventional) = Heat Gain / 500 / 10F delta T200gpmAir (Low Pressure VVT)Air (Low Pressure VVT)0.0%1.3%2.5%3.8%5.0%6.3%

    Hydronic (Heat Pump) = Heat Gain / 500 / 10F delta T *1.25 (heat of rejection)250gpmAir (Medium Pressure VAV)Air (Medium Pressure VAV)0.0%4.4%8.8%13.2%17.6%22.0%

    Hydronic (1 pipe LOFlo Primary) = Heat Gain / 500 / 18F delta T111Refrigerant (VRF - AHRI))Refrigerant (VRF)1.0%6.0%12.0%18.0%24.0%30.0%

    Hydronic (1 pipe LOFlo Secondary) = Heat Gain / 500 / 5F delta T400gpm

    Air = Heat Gain / 1.085 / 25F delta T36866cfm

    Efficiencies

    Pump80%

    Fan65%

    Motor90%

    Compressor Horsepower

    EER (btuh/watt)13

    COP = EER (/ 3.4133.8

    Compressor Horsepower

    = Heat Gain (btuh) / COP / 3.413 (btuh/watt)

    / 1,000 (watts/kw) / .75 (kw/hp)103hp

    Hydronic System Horsepower

    Pipe Length (ft)0100200300400500

    Head (ft)

    Pipe Friction

    = 4' / 100' x pipe length x 1.3 equivalent length0510162126

    Pump Horsepower

    = Flow x Head / 3960 / Pump Efficiency / Motor Efficiency0.000.360.731.091.461.82

    Air (Low Pressure VVT) Horsepower

    Duct Length (ft)0100200300400500

    Static Pressure

    Duct Friction

    = 0.1" / 100' x duct length x 1.3 equivalent length0.000.130.260.390.520.65

    Fan Horsepower

    = Flow x Static Pressure / 6356 / Fan Efficiency / Motor Efficiency0.001.292.583.875.166.44

    Air (Medium Pressure VAV) Horsepower

    Duct Length (ft)0100200300400500

    Static Pressure

    Variable Duct Friction

    = 0.35" / 100' x duct length x 1.3 equivalent length0.000.460.911.371.822.28

    Fan Horsepower

    = Flow x Static Pressure / 6356 / Fan Efficiency / Motor Efficiency0.004.519.0213.5318.0522.56

    Refrigerant (VRF) Horsepower

    Compressor capacity pipe length correction factor

    Pipe length (ft)0100200300400500

    Equivalent pipe length = pipe length x 1.3 (ft)0150300450600750

    Equivalent pipe length = pipe length x 1.3 (m)04691137183229

    Sources

    Daikin (equivalent pipe length)1.0000.9300.8600.8100.7800.760

    Mitsubishi (equivalent pipe length)1.0000.9300.8650.8100.7500.700

    AHRI (pipe length)0.9900.9400.8800.8200.7600.700

    ASHRAE Guide1.0000.9850.9650.9500.9300.920

    AHRI Standard 1230-2013 (pipe length)

    Daikin (equivalent length)Mitsubishi (equivalent length)

    Hydronic

    Air (Low Pressure VVT)

    Air (Medium Pressure VAV)

    Refrigerant (VRF)

    Pipe/Duct Length

    Percent of Compressor Horsepower

    Distribution/Pumping Energy

    Taco System Analysis

    2/21/14

    ParameterCentral Plant Heating and Cooling Sources

    Heating SourceCooling Source

    BoilerFurnaceElectric Resistance HeatingPTACPackaged RooftopVariable Refrigerant FlowHeat PumpChillerSplit System Condensing UnitVariable Refrigerant FlowHeat PumpPTACPackaged Rooftop

    Air SourceWater SourceGeothermal Water to AirClosed LoopGeothermal Water to AirOpen LoopGeothermal Water to AirStanding ColumnAir SourceWater SourceWater Source Condenser Water Heat OnlyGeothermal Water to AirClosed LoopGeothermal Water to AirOpen LoopGeothermal Water to AirStanding ColumnGeothermal Water to WaterClosed LoopGeothermal Water to WaterOpen LoopGeothermal Water to WaterStanding ColumnWater Cooled ElectricScroll CompressorWater Cooled ElectricScrew CompressorWater Cooled ElectricCentrifugal CompressorWater Cooled ElectricFrictionless CompressorWater Cooled AbsorptionAir Cooled Electric Scroll CompressorAir Cooled Electric Screw CompressorAir Cooled Electric Centrifugal CompressorAir Cooled Electric Frictionless CompressorAir Cooled AbsorptionCondensing Unit, Evaporative CooledCondensing Unit, Air CooledAir SourceWater SourceGeothermal Water to AirClosed LoopGeothermal Water to AirOpen LoopGeothermal Water to AirStanding ColumnAir SourceWater SourceWater Source Condenser Water Heat OnlyGeothermal Water to AirClosed LoopGeothermal Water to AirOpen LoopGeothermal Water to AirStanding ColumnGeothermal Water to WaterClosed LoopGeothermal Water to WaterOpen LoopGeothermal Water to WaterStanding Column

    Constant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable SpeedConstant SpeedVariable Speed

    Central Plant

    Electrical Demand (kw)

    Pump Electrical Demand (Primary and Secondary)

    Heating Pump Horsepower

    CPHPHB = Central Plant Heating Pump Head, Boiler (ft head)

    = Central Plant Heating Pump Head, Boiler (ft head), Primary Only5

    = Central Plant Heating Pump Head, Boiler (ft head), Primary for Primary/Secondary5

    = Central Plant Heating Pump Head, Boiler (ft head), Secondary for Primary/Secondary0

    CPHPHHC = Central Plant Heating Pump Head, Heating Coil (ft head) (one of 3 following equations)

    = Central Plant Heating Pump Head, Heating Coil (ft head), Primary Only

    = Central Plant Heating Pump Head, Heating Coil (ft head), Primary for Primary/Secondary

    = Central Plant Heating Pump Head, Heating Coil (ft head), Secondary for Primary/Secondary

    CPHPHCV = Central Plant Heating Pump Head, Control Valve (ft head) (one of 3 following equations)

    = Central Plant Heating Pump Head, Control Valve (ft head), Primary Only

    = Central Plant Heating Pump Head, Control Valve (ft head), Primary for Primary/Secondary

    = Central Plant Heating Pump Head, Control Valve (ft head), Secondary for Primary/Secondary

    CPHPHPA = Central Plant Heating Pump Head, Pump Accessories (ft head)

    CPHPHBV = Central Plant Heating Pump Head, Balance Valve (ft head)

    PDPD = Pipe Design Pressure Drop (user preference)

    = 4 ft / 100 ft (Default)

    1P2PLR = 1 Pipe to 2 pipe system pipe length ratioSee PumpsSee PumpsSee PumpsSee PumpsSee PumpsSee PumpsSee PumpsSee PumpsSee Pumps

    = 0.7 (default)See PumpsSee PumpsSee PumpsSee PumpsSee PumpsSee PumpsSee PumpsSee PumpsSee Pumps

    HPML = Hydronic Pipe Maximum Length (ft pipe)

    CPHPHDSS = Central Plant Heating Pump Head, Distribution System Secondary (ft head) (one of 2 following equations)

    CPHPHDSS = PDPD / 100 (ft pipe) x (Building Perimeter (ft pipe) or Hydronic Pipe Maximum Length (ft pipe)) x 1.5 Equivalent Length x 1P2PLR, (Single pipe)

    = PDPD / 100 x (2 x (FL + FW + (NF x FH)) or HPML) x 1.5 x 1P2PLR

    CPHPHDSS = PDPD / 100 (ft pipe) x (Building Perimeter (ft pipe) or Hydronic Pipe Maximum Length (ft pipe)) x 1.5 Equivalent Length (2 pipe)

    = PDPD / 100 x (2 x ((FL + FW + (NF x FH)) or HPML) x 1.5

    CPHPHDSP = Central Plant Heating Pump Head, Distribution System Primary (ft head)

    = PDPD / 100 (ft pipe) x Mechanical Room (50 ft pipe) x 1.5 Equivalent Length

    = PDPD / 100 x 50 x 1.5

    CPHPHPP = Central Plant Heating Pump Head, Piping (ft head) Primary (varies with load as square of flow or load)

    = (CPHPHB + CPHPHPA + CPHPHDSP + CPHPHDSS (0 for Primary/Secondary)) x HPLF2

    CPHPHPS = Central Plant Heating Pump Head, Piping (ft head) Secondary (varies with load as square of flow or load)

    = (CPHPHB + CPHPHPA + CPHPHDSS) x HPLF2

    CPHPHTU = Central Plant Heating Pump Head, Terminal Unit (ft head) (one of following 2 equations)

    CPHPHTU = Central Plant Heating Pump Head, Terminal Unit (ft head) (varies with load as square of flow or load for Delta T control)

    = (CPHPHC + CPHPCV + CPHPHBV) x HPLF2

    CPHPHTU = Central Plant Heating Pump Head, Terminal Unit (ft head) (constant, does not vary with load, Delta P for Delta P control)

    = CPHPHC + CPHPCV + CPHPHBV

    HHTDP = Hydronic Heating Temperature Difference Primary (user preference)

    = Default

    HHTDS = Hydronic Heating Temperature Difference Secondary (user preference)

    = Default

    HHTTS = Hydronic Heating Temperature Difference Terminal Unit (user preference)

    = Default

    CPHPF(P/S) = Central Plant Heating Pump Flow Primary or Secondary (gpm)

    = Hourly Total Heat Loss (btu/hr) / 60 min/hr / 8.33 lb/gal / 1btu/lb/deg F /

    Hydronic Heating Temperature Difference Primary or Secondary (deg F)

    = HHLT / 500 / HHTD(P/S)

    CPFLPE(P/S) = Central Plant Full Load Pump Efficiency Primary or Secondary (user preference)

    = 70% (default)

    CPFLME(P/S) = Central Plant Full Load Motor Efficiency Primary or Secondary (user preference)

    = 90% (default)

    CPHPHPCV = Central Plant Heating Pump Horsepower Conversion Factor

    = 1 / Central Plant Full Load Pump Efficiency (bhp/hp) / Heating Pump Part Load Efficiency Factor / 3960 (gpm x ft head / hp) / Central Plant Motor Efficiency

    = 1 / CPFLPE / HPPLEF / 3960 / CPME

    CPHPPHP= Central Plant Heating Primary Pump Horsepower (hp)

    = Heating Flow (gpm) x (Central Plant Heating Pump Head, Piping (ft head) Primary + Central Plant Heating Pump Head, Terminal Unit (ft head)) x Central Plant Heating Pump Horsepower Conversion Factor

    (Minimum Heating Flow (gpm) = 25% for lubrication of seals)

    = CPHPF x (CPHPHPP + CPHPHPTU (0 if Primary/Secondary)) x CPHPHPCV

    CPHPSHP= Central Plant Heating Secondary Pump Horsepower (hp)

    = Heating Flow (gpm) x (Central Plant Heating Pump Head, Piping (ft head) Secondary + Central Plant Heating Pump Head, Terminal Unit (ft head)) x Central Plant Heating Pump Horsepower Conversion Factor

    (Minimum Heating Flow (gpm) = 25% for lubrication of seals)

    = (CPHPF x (CPHPHPS + CPHPHPTU) x CPHPHPCV) (0 if Primary Only)

    Heating Pump Demand (kw)

    HPC = .746 killowatts/horsepower

    CPHPD = Central Plant Heating Pump Demand (kw)

    = Central Plant Heating Pump Horsepower (hp) x HPC (kilowatts/horsepower)

    = CPHPHP x HPC

    MHDF = Monthly Heating Demand Factor

    = (Balance Point - Monthly Minimum) / (Balance Point - Average Annual Minimum) (=1 if > 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if 1 and 0 if

  • HYDRONICS ARE SAFE AND SUSTAINABLE

    Chart1

    0000

    50505050

    100100100100

    150150150150

    200200200200

    250250250250

    Refrigerant (Split System)

    Refrigerant (VRF)

    Hydronic (Electric Chiller and Heat Pump)

    Hydronic (Absorption Chiller and Heat Pump)

    Tons of Cooling

    Pounds of Refrigerant

    Refrigerant Charge

    0

    0

    0

    0

    242.8571428571

    225

    50

    0

    485.7142857143

    450

    100

    0

    728.5714285714

    675

    150

    0

    971.4285714286

    900

    200

    0

    1214.2857142857

    1125

    250

    0

    Sheet1

    Refrigerant Charge

    1/7/14

    SystemRefrigerant ChargeRange(lbs/ton)Refrigerant ChargeUsed(lbs/ton)Refrigerant Charge

    RefrigerantTons of Cooling050100150200250

    DX Split System (See calculation below)Refrigerant Split SystemRefrigerant (Split System)02434867299711214

    Total Charge for 35 feet of Refrigerant Pipe (Charlotte HVAC Guide)2 - 43.0000Rerfrigerant VRFRefrigerant (VRF)02254506759001125

    Condensing Unit (McQuay AGZ 10 - 30 tons)1.5 - 2.02.0000Hydronic Electirc Chiller and Heat PumpsHydronic (Electric Chiller and Heat Pump)050100150200250

    Pipe Charge (per foot)0.0286Hydronic Absorption ChillersHydronic (Absorption Chiller and Heat Pump)000000

    Total Charge for 100 feet of refrigerant line4.8571

    VRF (Applying VRF - Don't Overlook Standard 15 - ASHRAE 2012-7)3 - 64.5000

    Hydronic System

    Air Cooled Chiller (Daikin/McQuay ALS Rotary Screw 120-210 tons)0.9 - 1.11.0000

    Water Cooled Chiller (Trane Series R 80-250 tons)0.8 - 1.11.0000

    Water Cooled Heat Pump (McQuay Large Water Source Heat Pumps 6 - 25 tons)0.8 - 1.21.0000

    Absorption Chillers00.0000

    Sheet1

    Refrigerant (Split System)

    Refrigerant (VRF)

    Hydronic (Electric Chiller and Heat Pump)

    Hydronic (Absorption Chiller and Heat Pump)

    Tons of Cooling

    Pounds of Refrigerant

    Refrigerant Charge

    Sheet2

    Sheet3

  • NET ENERGY – SYSTEM VS. UNIT EFFICIENCY

    Two buildings have the same load – but the Hydronic System always wins due to reduced energy use. Why?

    LOWEST OPERATING COST, PLUS:SIMULTANEOUS HEAT RECLAIM – Lowest cost, when applied to the whole building design for increased opportunity to share energyCYCLICAL – Better practice, heating and cooling offset each other but do not have to occur simultaneously

    Available only with hydronic systemsSTORAGE – Best practice based on cost

    Available only with hydronic systems

  • OTHER CONSIDERATIONS

    Preference of building ownerAvailable construction budgetSize and shape of buildingFunction of building (comfort requirements)Architectural limitationsLife-cycle costEase of operation and maintenanceTime available for construction

  • Good Reasons to use DX

    Tom LennonRegional Manager AAON, Inc.

  • Good reasons to use DX

    1. It can be cheaper to own and operate.a. Frequently less first cost as both field labor and equipment cost can be

    significantly less. No pumps, little piping, no dedicated machine rooms in many instances.

    b. Energy costs may be significantly less utilizing air source or water source heat pump systems as well as eliminating pumping cost. Larger units are available with Evap condensing to reduce lift to below most water cooled chillers.

    c. Self contained controls that are BACnet ready provide an inexpensive way to offer even smaller facilities big system BAS benefits.

  • Good reasons to use DX

    Frequently less first cost as both field labor and equipment cost can be significantly less. No pumps, little piping, no dedicated machine rooms in many instances.

  • Good reasons to use DX

    Energy costs may be significantly less utilizing air source or water source heat pump systems as well as eliminating pumping cost. Larger units are available with Evapcondensing to reduce lift to below most water cooled chillers.

  • Good reasons to use DX

    Self contained controls that are BACnet ready provide an cost effective way to offer even smaller facilities big system BAS benefits.

  • Relative Humidity +/- 5%

    DB Temperature+/- 1/2° F

    Good reasons to use DX

    2. Better comforta. Variable Capacity Compressors (Digital, Variable

    Speed, and 2-step) can provide stable LAT with precise humidity control

    Modulating Hot Gas Reheat allows precise RH control for even high OSA percentage units.

  • Full Load Air Handler Psychrometrics

    Outside Air700 CFM95° F DB75° F WB

    Mixed Air80.2° F DB66.1° F WB

    Coil L/A52.9° F DB52.1° F WB Supply Air 2695 CFM

    54.7° F DB

    Room Load60,000 Btu/hr

    Sensible15,000 Btu/hr Latent

    Room Conditions75° F DB50 % RH

    O/A M/A

    R/A

    S/A

    E/AExhaust Air700 CFM

    Supply Fan Unit Gross Cap.TSP = 2.5 in. wg. Tot = 111,964 Btu/hrBHP = 1.93 Sensible = 80,634 Btu/hr Latent = 31,330 Btu/hr

    Design Conditions

    9.3 Tons

  • Part Load Psychrometrics

    Outside Air700 CFM95° F DB75° F WB

    Mixed Air85.4° F DB70.4° F WB

    Coil L/A54.3° F DB

    523.5° F WB

    Supply Air 1343 CFM54.7° F DB

    Room Load30,000 Btu/hr

    Sensible15,000 Btu/hr Latent

    Room Conditions75° F DB

    58.4 % RH

    O/A M/A

    R/A

    S/A

    E/AExhaust Air700 CFM

    Supply Fan Unit Gross Cap.TSP = 0.62 in. wg. Tot = 72,028 Btu/hrBHP = 0.24 Sensible = 46,032 Btu/hr Latent = 25,996 Btu/hr

    Reduced Sensible Load

    6.0 Tons

    Increase in RH %

  • Part Load Psychrometrics

    Outside Air700 CFM95° F DB75° F WB

    Mixed Air95.0° F DB75.0° F WB

    Coil L/A54.6° F DB53.7° F WB Supply Air 700 CFM

    54.7° F DB

    Room Load15,000 Btu/hr

    Sensible15,000 Btu/hr Latent

    Room Conditions74.1° F DB72.2 % RH

    O/A M/A

    R/A

    S/A

    E/AExhaust Air700 CFM

    Supply Fan Unit Gross Cap.TSP = 0.17 in. wg. Tot = 49,772 Btu/hrBHP = 0.03 Sensible = 31,265 Btu/hr Latent = 18,506 Btu/hr

    Loss of Temp ControlLost of Humidity Control

    Further Reduction in Sensible Load

    Minimum airflow

  • Modulating Hot Gas Reheat

    Control Board

    Modulating Valve

  • Outside Air700 CFM95° F DB75° F WB

    Mixed Air80.2° F DB66.1° F WB

    Coil L/A52.9° F DB52.1° F WB Supply Air 2695 CFM

    54.7° F DB

    Room Load60,000 Btu/hr

    Sensible15,000 Btu/hr Latent

    Room Conditions75° F DB50 % RH

    O/A M/A

    R/A

    S/A

    E/AExhaust Air700 CFM

    Supply Fan Unit Gross Cap.TSP = 2.65 in. wg. Tot = 111,964 Btu/hrBHP = 2.29 Sensible = 80,634 Btu/hr Latent = 31,330 Btu/hr

    Mod Gas Reheat

    0 Btu/hr, .15” APD

    Design Conditions

    9.3 Tons

    Full Load Air Handler PsychrometricsWith MHGRH

    BHP increase 18.6%

  • VAV System Psychrometrics with Modulating Hot Gas Reheat

    Outside Air700 CFM95° F DB75° F WB

    Mixed Air85.4° F DB69.4° F WB

    Coil L/A48.8° F DB48.1° F WB Supply Air 1347 CFM

    54.7° F DB

    Room Load30,000 Btu/hr

    Sensible15,000 Btu/hr Latent

    Room Conditions75° F DB50 % RH

    O/A M/A

    R/A

    S/A

    E/AExhaust Air700 CFM

    Supply Fan Unit Gross Cap.TSP = .62 in. wg. Tot = 85,342 Btu/hrBHP = 0.24 Sensible = 54,026 Btu/hr Latent = 31,315 Btu/hr

    Mod Gas Reheat

    8037 Btu/hr

    Reduced Sensible Load

    7.1Tons an increase due to humidity controlBHP reduced 87.5%

    No increase in RH %

  • VAV System Psychrometrics with Modulating Hot Gas Reheat

    Outside Air700 CFM95° F DB75° F WB

    Mixed Air89.6° F DB72.0° F WB

    Coil L/A45.0° F DB44.3° F WB Supply Air 956 CFM

    60.7° F DB

    Room Load15,000 Btu/hr

    Sensible15,000 Btu/hr Latent

    Room Conditions75° F DB50 % RH

    O/A M/A

    R/A

    S/A

    E/AExhaust Air700 CFM

    Supply Fan Unit Gross Cap.TSP = .31 in. wg. Tot = 78,129 Btu/hrBHP = 0.09 Sensible = 46,813 Btu/hr Latent = 31,316 Btu/hr

    Mod Gas Reheat

    15232 Btu/hr

    6.5 TonsBHP reduced 95.3%

    No increase in RH %

    Further Reduction in Sensible Load

  • DOAS Units

    DX is typically the only viable solution for a DOAS unit.

    1. Chilled water systems may require glycol which penalizes not only all heat exchangers, but all supply air fans as well due to thicker coils with more FPI.

    2. Preheat will not allow for close humidity control – reheat is essential and prohibited by many codes unless utilizing Hot Gas.

    3. Suitably low DEW point supply air would take lower water temps then typically practical. With DX saturated air at as low as 41 F is usually available.

    4. Air source or water source heat pumps give close heating control without overheating in shoulder months utilizing gas or electric heat only in colder conditions.

    5. Variable capacity compressors as part of a DOAS unit utilizing heat pumps operation and modulating heat makes VAV DOAS a true option.

  • DOAS Units

  • Thank You!

  • ASHRAE DX vs Chilled Water Debate :VRF Overview

    Zack Koch

    ©2013 Mitsubishi Electric & Electronics USA, Inc.

  • VRF is a combination of traditional

    systems

  • Basic System (1 to 1)

    Common Uses Individual room School office Server room Additions Problem areas

    Condensing Unit Indoor Unit

    Refrigerant Piping

  • Refrigerant Piping

    Refrigerant Piping

    Commercial System

    Condensing Unit Indoor Units

    Heat Pump

    Up to 50 indoor units per system

    All in cooling mode

  • Commercial System

    Condensing Unit Indoor Units

    Heat Pump

    Up to 50 indoor units per system

    Refrigerant Piping

    All in heating mode

  • Commercial SystemHeat Pump

    Restaurants

    Lobbies

    Churches

    Apartments

    Large open areas

    Zones with similar load profiles

  • Commercial System

    Condensing Unit Indoor Units

    Heat Pump with Heat Recovery (2 Pipe)

    Refrigerant Piping

    Up to 50 indoor units per system

    Branch CircuitController

    Cooling

    HeatingSimultaneous

    2 Pipes

    2 Pipes

  • Commercial System

    Condensing Unit Indoor Units

    Heat Pump with Heat Recovery (3 Pipe)

    Refrigerant Piping Changeover Box

    Cooling

    HeatingSimultaneous

  • Commercial SystemSimultaneous Heating and Cooling Applications

    Many zones with different load profiles

    Multi-family Senior living centers Schools Student housing Hotels Offices Medical facilities

  • 30Hz

    On

    60Hz

    0Hz

    Set Point Temp.

    Compressor Energy Consumption

    Precise Temperature Control & Energy Efficiency Inverter-driven Compressor

    80°F

    77°F

    75°F

    73°F150Hz

  • Modular and compact designLocation flexibility – often spread around the property

  • MaintenanceITEM Traditional VRF

    Water treatment XCooling tower X

    Pump seals X

    10 year overhaul X

    Boiler analysis X

    Chiller maintenance X

    Tube brushing X

    Belt changes X

    Strainer cleaning X

    Filter changes X

    Condenser cleaning X

    X

    X

    Controllability

    Energy

    LEED

    Maintenance

    CostExpandabilit

    yWarranty 1 yr. 10 yr.

  • • Many zones• Sound sensitive• Limited space for ductwork• Owner requirement Cost conscious Energy conscious Maximize USF (usable square footage)

  • • Multi-family• Schools• Senior living centers• Student housing• Hotels• Churches• Retrofit application

  • Quiz

    1. What system type can take advantage of a water side economizer?

    2. True or False:• Heat recovery can only be utilized in a chilled

    water system.

    3. DX systems with digital and variable speed compressors offer precise humidity control.

  • Quiz

    4. Up to how many indoor unit can be connected to a VRF condensing unit?

    5. Which system(s) offer the lowest first costs?

    Chilled Water�vs.�Direct Expansion (DX)�vs.�VRF��Panel DiscussionChilled Water System�Industry ExpertsDirect Expansion System�Industry ExpertVRF System�Industry ExpertsHVAC Design GoalsThe five system loopsChilled Water ProductionAir-cooled or water-cooledCompressor typesAbsorption Chiller typesWaterside economizer �plate-and-frame heat exchangerSlide Number 12Thermal Storage Systems Partial Thermal StorageThermal Storage SystemDedicated Heat Recovery ChillerChilled Water ConsumptionCommon Chilled Water HVAC SystemsChilled-water air-handling unitChilled-water terminal systemChilled beamsCentral chilled-water vav systemDedicated outdoor-air systemWhy Chilled WaterStability of controlDISTRIBUTION – PIPING ENERGYHYDRONICS ARE SAFE AND SUSTAINABLENet Energy – System vS. unit efficiencyOther ConsiderationsGood Reasons to use DXGood reasons to use DXGood reasons to use DXGood reasons to use DXGood reasons to use DXGood reasons to use DXFull Load Air Handler Psychrometrics Part Load Psychrometrics Part Load Psychrometrics Modulating Hot Gas ReheatSlide Number 40VAV System Psychrometrics with Modulating Hot Gas ReheatVAV System Psychrometrics with Modulating Hot Gas ReheatSlide Number 43Slide Number 44Slide Number 45ASHRAE DX vs Chilled Water Debate :� VRF OverviewVRF is a � combination of traditional systemsBasic System (1 to 1)Commercial SystemCommercial SystemCommercial SystemCommercial SystemCommercial SystemCommercial SystemPrecise Temperature Control & Energy Efficiency Modular and compact designMaintenanceSlide Number 58Slide Number 59Slide Number 60Slide Number 61