hvac for thermal test on clic prototype modules in building 169 preliminary design f. audinet, c....
TRANSCRIPT
HVAC for thermal test on CLIC prototype modules
in building 169
Preliminary design
F. Audinet, C. Martel : Cern GS-SE-HE
Wednesday, 25th July 2012
LocalisationCern Meyrin site – reference building 169-S-011
S-011
CLIC TUNNEL LAB
• Initial design (temperature control only)
CLIC TUNNEL LAB
CLIC TUNNEL LAB
HVAC PRINCIPLE (1)(T° + air speed)
Air transfer
100 cm
CLIC TUNNEL LAB
HVAC PRINCIPLE (2)
PROJECTS PARAMETERS• Preliminary design : July 2012.• Detail design: August 2012.• Installaltion October 2012.
• Estimated costs : 300 to 350 kCHF
CLIC TUNNEL LAB
HVAC DESIGN PARAMETERS• Internal heat dissipation: 6 KW• Number of people: 5• Variable airflow rate: from 5000 to 32000 m3/h• Variable air speed (central section) from 0.25 to 0.8 m/s• Ambient temperature: from 20 to 40°C• Fresh air inlet: 500 m3/h• Filtration class: F8
CLIC TUNNEL LAB