honorable mention educational facilities ......prior to renovation, the school had a three-year...
TRANSCRIPT
![Page 1: HONORABLE MENTION EDUCATIONAL FACILITIES ......Prior to renovation, the school had a three-year average baseline energy use intensity (EUI) of 58.3 kBtu/ft 2 ·yr (662.1 MJ/m 2 ·yr)](https://reader034.vdocuments.us/reader034/viewer/2022050218/5f63e447d67c8001ef3bbb1d/html5/thumbnails/1.jpg)
A S H R A E J O U R N A L a s h r a e . o r g M AY 2 0 1 74 6
BY ADAM PIERCE, P.E., MEMBER ASHRAE
BUILDING AT A GLANCE
Adam Pierce, P.E., is a principal with CMTA Energy Solutions, a division of CMTA, in Louisville, Ky.
Creating a Contract for Success
HONORABLE MENTIONEDUCATIONAL FACILITIES, EXISTING
A Kentucky school plagued with severe operational and indoor environmental issues paid hundreds of thou-sands of dollars in O&M expenses over 10 years for temporary solutions. The even bigger problem? The school district didn’t have the available capital funding to replace the HVAC system.
Traditional funding revenues were already commit-ted to other school facility debt. So, the school district entered into a guaranteed energy savings contract to fund the new system. Money saved from reduced energy and O&M is reallocated to cover the debt service.
No Budget, No Problem This worst-to-first story began
with a school that had failed
dampers, excessive humidity
levels, and an obsolete building
automation system. It ended
with a renovation and Energy
Star score of 100.
Cox’s Creek Elementary School
Location: Cox’s Creek, Ky.
Owner: Nelson County Board of Education
Principal Use: School building
Includes: 40 rooms including 20 classrooms, cafete-ria, gymnasium, music room, library/media center
Employees/Occupants: 55 staff, 472 students in grades K – 5
Gross Square Footage: 52,833
Conditioned Space Square Footage: 52,833
Substantial Completion/Occupancy: August 1, 2014
Occupancy: 96% asa
National Distinctions/Awards: Energy Star
PHOT
O CR
EDIT
: WES
BAT
TOCL
ETTE
2017 ASHRAE TECHNOLOGY AWARD CASE STUDIES35 Years of Excellence
©ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.cmtaegrs.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE’s permission. For more information about ASHRAE, visit www.ashrae.org.
![Page 2: HONORABLE MENTION EDUCATIONAL FACILITIES ......Prior to renovation, the school had a three-year average baseline energy use intensity (EUI) of 58.3 kBtu/ft 2 ·yr (662.1 MJ/m 2 ·yr)](https://reader034.vdocuments.us/reader034/viewer/2022050218/5f63e447d67c8001ef3bbb1d/html5/thumbnails/2.jpg)
M AY 2 0 1 7 a s h r a e . o r g A S H R A E J O U R N A L 4 7
ABOVE The school is benefiting from an improved indoor learning environment, as well as from significantly reduced operational costs. LEFT Geothermal water source heat pumps serve the building's heating and cooling needs.
Cox's County Elementary School is one of 12 in the
Nelson County School district, located in the heart
of the Bluegrass in Cox’s Creek, Ky. The 52,800 ft2
(4905 m2) facility has approximately 450 students
in grades K – 5 and was constructed in 1991. By 2014,
deficiencies with the existing HVAC system included
failed outdoor air and relief air dampers, an obsolete
building automation system that was not supported,
excessive humidity levels and accompanying issues,
poor thermal comfort, as well as high maintenance
and repair costs.
Guaranteed Energy Savings Contract (GESC)Traditionally in Kentucky, funding school capital
construction projects is accomplished through a com-
bination of state and local tax revenues. Each district’s
capacity to bond building projects is determined by
their uncommitted property tax base. Over the course
of the prior 15 years, Nelson County Schools had made
significant investments in new facilities, and their
property tax revenue had largely been committed to
that debt. There simply was no capacity remaining to
fund an HVAC renovation at Cox’s Creek Elementary
School. The energy and operations and maintenance
cost savings realized as a result of the upgrades pro-
vided the mechanism to fund the annual debt service
Energy EfficiencyPrior to renovation, the school had a three-year
average baseline energy use intensity (EUI) of
58.3 kBtu/ft2·yr (662.1 MJ/m2·yr) (60% electric, 40% pro-
pane). The school’s existing HVAC system was a two-pipe
hot/chilled water unit ventilator system, with a split air-
cooled chiller and propane hot water boiler. At approxi-
mately 23 years old, this system had reached the end of
its useful life, and a major system replacement was nec-
essary to allow effective operation into the future. A new
geothermal heating and cooling system with a dedicated
outdoor air system (DOAS) was selected for the school
because of its low life-cycle cost, energy efficiency, and
ease of maintenance by district personnel. The upgrades
were designed in accordance with ASHRAE Standard
90.1-2013.
The water source heat pumps used were high effi-
ciency two-stage units, which provide part-load efficien-
cies as low as 0.4 kW/ton (0.1 kW/kW) using the 70°F
(21°C) geothermal loop water. The DOAS rooftop units
are equipped with exhaust air heat recovery wheels
to precondition outdoor air prior to supplemental
mechanical heating or cooling. All HVAC controls were
replaced with modern web-based DDC controls. Other
energy-efficient system upgrades include demand con-
trolled ventilation strategies, variable speed pumping,
PHOT
O CR
EDIT
: WES
BAT
TOCL
ETTE
PHOTO CREDIT: WES BATTOCLETTE
Energy Cost
Maintenance Cost
Excess Savings Returned to OwnerSavings to Fund Project
Operations Budget After Improvements
Energy Cost
Maintenance Cost
Operations Budget Before Improvements
FIGURE 1 Operations budget before (left) and after (right) improvements.
payments for the guaranteed
energy savings contract (GESC) the
school board decided to use as an
innovative project delivery method.
The expense is budgeted and paid
for annually out of the operational
budget. Figure 1 illustrates how
guaranteed energy savings pro-
vide alternative funding for much
needed upgrades.
2017 ASHRAE TECHNOLOGY AWARD CASE STUDIES
![Page 3: HONORABLE MENTION EDUCATIONAL FACILITIES ......Prior to renovation, the school had a three-year average baseline energy use intensity (EUI) of 58.3 kBtu/ft 2 ·yr (662.1 MJ/m 2 ·yr)](https://reader034.vdocuments.us/reader034/viewer/2022050218/5f63e447d67c8001ef3bbb1d/html5/thumbnails/3.jpg)
A S H R A E J O U R N A L a s h r a e . o r g M AY 2 0 1 74 8
Per the GESC, a performance guarantee was estab-
lished that quantified energy use reductions at the
facility. Figure 2 illustrates baseline energy conditions,
performance guarantee energy levels, and two full years
of actual post-retrofit energy data.
The baseline period energy use prior to the reno-
vation was 58.3 kBtu/ft2·yr (662.1 MJ/m2·yr), and
the guaranteed performance was 38.4 kBtu/ft2·yr
(436.1 MJ/m2·yr) after renovation. The actual use
is approximately 24 kBtu/ft2·yr (272.6 MJ/m2·yr).
Comparing the baseline period to the post-retrofit
period energy use shows a 60% energy use reduc-
tion, and the performance guarantee metrics have
been greatly exceeded. Labeled in 2015, Cox’s Creek
Elementary School is among only nine schools in
Kentucky that have ever achieved an Energy Star score
of 100.
Indoor Air Quality and Thermal ComfortPrior to renovation, the district was in a crisis situ-
ation regarding the indoor building environment at
Cox’s Creek Elementary School, particularly during
the cooling season. The building's relative humidity
was elevated to the point that condensation had satu-
rated the chilled water piping insulation. Outdoor air
and relief air dampers had failed in numerous loca-
tions, some open and some closed. Photo 1 shows that
the maintenance staff had identified the relief hoods
as a source of infiltration and attempted to seal them
with plastic to prevent outdoor air infiltration at those
locations.
Due to poor control and overcooling in some areas,
chilled water supply temperatures were raised to nearly
60°F (16°C) by the maintenance staff, further com-
pounding the humidity problems. The controls for the
kitchen range hood exhaust fans had been bypassed and
were operating 24/7, causing infiltration of untreated
outdoor air due to negative pressure. Staff members
were complaining of illness, and the community had
become aware that the building had major issues.
The existing two-pipe system was designed with
the ability to provide free cooling via the unit ventila-
tor economizer when the boiler was enabled. Due to
the lack of serviceability of the existing HVAC controls
and damper actuator failures, the free cooling was not
operational, and the outdoor air dampers had been
manually shut. The changeover from heating to cooling
was manual, and the entire building was without any
PHOTO 1 Prior to the renovation, maintenance staff attempted to seal relief hoods with plastic to prevent indoor air infiltration.
Jun Dec Jun Dec Jun Dec MayMo
nthly
Ene
rgy U
se (M
MBt
u)
Baseline Period Post Installation Period600
500
400
300
200
100
0
Monthly Energy Use Baseline Model Performance Guarantee
FIGURE 2 Cox's Creek Elementary School—Energy Savings Verification. Baseline energy conditions, performance guarantee energy levels, and two full years of actual post-retrofit energy data.
geothermal domestic water heating,
and LED exterior lighting.
The local electric utility company
has an “All Electric School” electric
rate structure designed to incentiv-
ize building owners to heat with
electricity in lieu of natural gas or
propane. Because the boiler was
being replaced with a geothermal
well field, the decision was made to
convert remaining equipment and
appliances from propane to elec-
tric. This eliminated the need for
propane in the future and reduced
the electric energy cost per kWh by
approximately 15%.
2017 ASHRAE TECHNOLOGY AWARD CASE STUDIES
![Page 4: HONORABLE MENTION EDUCATIONAL FACILITIES ......Prior to renovation, the school had a three-year average baseline energy use intensity (EUI) of 58.3 kBtu/ft 2 ·yr (662.1 MJ/m 2 ·yr)](https://reader034.vdocuments.us/reader034/viewer/2022050218/5f63e447d67c8001ef3bbb1d/html5/thumbnails/4.jpg)
A S H R A E J O U R N A L a s h r a e . o r g M AY 2 0 1 75 2
simultaneous heating and cooling capability. Thermal
comfort was very poor during the spring and fall when
some zones needed heat, while others needed cooling.
During the renovation, all existing outdoor air intake
louvers were infilled. Rooftop relief hoods were removed
with openings sealed and insulated. The DOAS units
were designed to provide precisely controlled and con-
ditioned outdoor air and exhaust air service for the
entire facility. The ventilation rates were calculated in
accordance with ASHRAE Standard 62.1-2013.
Using ASHRAE Standard 55-2013 as the design basis for
the thermal environmental conditions, the geothermal
water source heat pumps provide space heating and air
conditioning. Water source heat pumps are a popular
HVAC system selection in this climate zone due in large
part to the inherent ability of the equipment to simulta-
neously heat and cool various zones, solving one of the
deficiencies of the original two-pipe system.
Additionally, the use of the two-stage water source
heat pumps allows reduced cooling capacities at part-
load conditions, which reduces compressor cycling and
allows better dehumidification at the individual zones
as the cooling coils remain active for longer periods of
time.
Operation and MaintenanceThe district’s O&M costs at Cox’s Creek Elementary
School were escalating year over year and greatly
exceeded the amounts they were spending at their other
similarly sized schools. A historical review of annual
maintenance and repair costs was performed to deter-
mine potential cost savings that could be realized upon
completion of the HVAC renovation. O&M challenges
associated with the existing situation included the
following:
• Daily replacement of ceiling tiles damaged by con-
densation and mold growth;
• Hiring insulation contractors to replace saturated
chilled water pipe insulation;
• Hiring environmental contractors to assess IAQ and
remediate mold growth;
• Hiring environmental contractors to clean unit
2017 ASHRAE TECHNOLOGY AWARD CASE STUDIES
Advertisement formerly in this space.Advertisement formerly in this space.
![Page 5: HONORABLE MENTION EDUCATIONAL FACILITIES ......Prior to renovation, the school had a three-year average baseline energy use intensity (EUI) of 58.3 kBtu/ft 2 ·yr (662.1 MJ/m 2 ·yr)](https://reader034.vdocuments.us/reader034/viewer/2022050218/5f63e447d67c8001ef3bbb1d/html5/thumbnails/5.jpg)
A S H R A E J O U R N A L a s h r a e . o r g M AY 2 0 1 75 4
ventilators;
• Reliability and repair costs associated with the
existing chiller;
• Failed attempts at hiring contractors to service ob-
solete controls system; and
• Managing odd return filter size inventory for vari-
ous unit ventilator cabinet sizes.
The system upgrade and selection of the geothermal
water source heat pump system addressed every O&M
challenge the district was facing at that facility. By select-
ing the geothermal system, traditional central plant
equipment such as boilers and cooling towers were
eliminated. Without this equipment the district no longer
incurs the cost of outsourcing maintenance to mechani-
cal service and water treatment contractors. The district
maintenance personnel have familiarity with and the
capability to service water source heat pumps.
By converting from chilled water to geothermal, the
threat of condensation forming on the piping was miti-
gated. The ceiling tile was replaced during the renova-
tion, and there has been no need to replace tiles since.
The space temperature and humidity conditions are
controlled so the potential for mold damage is gone.
The return air filtration is accomplished with 2 ft × 2
ft (610 mm × 610 mm) ceiling-mounted filter grilles
requiring standard 20 in. × 20 in. (508 mm × 508 mm)
filters. The geothermal well field is maintenance free
and can be used again when the system must be reno-
vated during the next HVAC system life cycle.
Figure 3 was developed using the historical cost data
from the district’s accounting system. The trend of base-
line O&M cost escalation between fiscal years 2012 – 2014
conveys the pain the district was feeling as they
attempted to salvage the HVAC system. As can be seen
by the reduction in O&M cost in the two years following
completion of the project, those operational issues have
been addressed as a result of the upgrades.
Cost EffectivenessThe project’s first cost was $1.55 million. By using the
guaranteed cost savings, the school district was able to
replace the aging HVAC infrastructure with modern
2017 ASHRAE TECHNOLOGY AWARD CASE STUDIES
Advertisement formerly in this space.Advertisement formerly in this space.
![Page 6: HONORABLE MENTION EDUCATIONAL FACILITIES ......Prior to renovation, the school had a three-year average baseline energy use intensity (EUI) of 58.3 kBtu/ft 2 ·yr (662.1 MJ/m 2 ·yr)](https://reader034.vdocuments.us/reader034/viewer/2022050218/5f63e447d67c8001ef3bbb1d/html5/thumbnails/6.jpg)
A S H R A E J O U R N A L a s h r a e . o r g M AY 2 0 1 75 6
systems with no traditional capital and with no change
to the operating budget.
For a GESC funding mechanism to work, it is essential
that energy and maintenance savings are maximized
while project first cost is minimized. This is a delicate
balancing act that forces the design team to deliver an
exceptionally performing product in the most cost-
effective manner possible. Several design strategies
were implemented to reduce the overall project cost
while maintaining performance. The hydronic piping
throughout the building had been recently re-insulated
by the owner and was reused to serve the new geother-
mal heat pump system. Each heat pump was designed to
serve two adjacent classrooms and operate off averaging
thermostats to reduce equipment and labor cost.
Additionally, the size of the geothermal well field was
able to be reduced by 33% due to exceptional conductivity
performance of its location. These design tactics and others
were able to reduce the overall project cost by approxi-
mately 20%. Ultimately this project delivered a cost-effec-
tive MEP renovation to the owner that also significantly
reduces the annual operating cost of the building.
Environmental ImpactThe environmental impact of this project was an
important consideration during planning. The reduc-
tion in energy use is attributable to the chosen and
implemented energy conservation measures. The
annual energy savings has a direct, quantifiable envi-
ronmental impact. In Kentucky, 93% of electricity is gen-
erated via coal-fired power plants. Thus, the reduction
in energy use corresponds to a large reduction in green-
house gas emissions. This project prevents 177 tons of
CO2 from being emitted into the atmosphere annually.
Overall, it eliminates the need to mine and burn nearly
200,000 lb (90 700 kg) of coal every year.
This has far-reaching implications beyond greenhouse
gas mitigation. Removing the need for coal eliminates
solid fly ash waste, acid mine water pollution, and envi-
ronmental destruction. Every year the school operates,
approximately 72,800 lb (33 000 kg) of coal ash is miti-
gated as a direct consequence of this project. Further,
while more difficult to quantify, not needing to trans-
port 200,000 lb (90 700 kg) of coal from the source to the
utility certainly has a non-negligible positive environ-
mental impact.
The new HVAC system also completely eliminated the
need for propane. Propane accounted for about 40% of
the school’s energy use prior to the project, so the envi-
ronmental impact of eliminating it was significant. This
prevents about 70 tons of CO2 emissions from being
released to the atmosphere annually and removes the
need to transport propane to the school.
Selecting the geothermal ground loop heat exchanger
was an investment for the current HVAC system and for
multiple HVAC system life cycles, as the well field has a
service life expectancy of 50-plus years. This will con-
serve materials and resources during future renovation
projects as well.
ConclusionUsing a guaranteed energy savings contract provided
Cox's Creek Elementary School a way to overcome its
capital funding hurdle. It increased energy efficiency by
60% in a renovated facility and provides a better indoor
learning environment for its students.
$70,587EUI: 58.3
$58,962EUI: 38.5
Baseline Performance Post Installation Post Installation Guarantee Year 1 Year 2
4,0003,5003,0002,5002,0001,5001,000
5000
Annu
al En
ergy
Use
(MM
Btu)
$37,018EUI: 24.1
$36,759EUI: 24.0
FIGURE 3 (Left) Operations and maintenance cost by fiscal year. FIGURE 4 (Right) Baseline energy vs. guaranteed vs. actual data.
$111,940
$158,278
$63,289
$27,051
FY12 FY13 FY14 FY15 – 16
$180,000
$160,000
$140,000
$120,000
$100,000
$80,000
$60,000
$40,000
$20,000
0
O&M
Costs
2017 ASHRAE TECHNOLOGY AWARD CASE STUDIES