5/17/2016 1 @ the Bullitt Center The Integrated Design Lab The Discovery Commons http://www.bullittcenter.org http:/www.joelrogers.photoshelter.com http:/www.djc.om Going Deep on Plug Loads: Strategies from the Bullitt Center 12 th Annual Energy/Facilities Connections (EFC) Conference 4 May 2016 Leavenworth, WA Christopher Meek, AIA , IESNA Associate Professor + Director Integrated Design Lab University of Washington Department of Architecture [email protected] www.idlseattle.com © UW Integrated Design Lab, 2015 The Bullitt Center - http://www.bullittcenter.org/ “The greenest commercial building in the world.” © UW Integrated Design Lab, 2015 Image: Architectural Record

Upload: others

Post on 22-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

1

@ the Bullitt Center                              The Integrated Design Lab              The Discovery Commons

http://www.bullittcenter.org http:/www.joelrogers.photoshelter.com http:/www.djc.om

Going Deep on Plug Loads: Strategies from the Bullitt Center12th Annual Energy/Facilities Connections (EFC) Conference4 May 2016Leavenworth, WA

Christopher Meek, AIA , IESNA Associate Professor + Director                                                                         Integrated Design Lab

University of Washington Department of Architecture [email protected]

www.idlseattle.com© UW Integrated Design Lab, 2015

The Bullitt Center

- http://www.bullittcenter.org/

“The greenest commercial building in the world.”

© UW Integrated Design Lab, 2015

Image: Architectural Record

Page 2: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

2

The Bullitt FoundationThe Miller Hull Partnership

PAE EngineersSolar Design AssociatesLuma Lighting Design

The Berger PartnershipSpringline Design

DCI EngineersUW Integrated Design Lab

2020 EngineeringRDH

Point32Schuchart Construction

ClientArchitectureMechanical & ElectricalSolar Array ConsultantLightingLandscapeCivilStructuralDaylighting and Solar Shading DesignNatural Waste Treatment SystemsBuilding EnvelopeDeveloperGeneral Contractor

Design and Construction Team

Page 3: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

3

Page 4: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

4

Page 5: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

5

Page 6: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

6

Net Zero Operation: CBECS Median US Office Building

Page 7: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

7

Net Zero Operation: Seattle Energy Code Building

Net Zero Operation: LEED Platinum Building

Page 8: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

8

Net Zero Operation: Bullitt Center Design

Solar Budget: Net‐Metering

Page 9: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

9

0

100,000

200,000

300,000

400,000

500,000

600,000

700,000

SOLAR

DOMEST HOT WTR

ELEVATOR

VENTFANS

PUMPS & AUX

SPACE COOLING

SPACE HEATING

MISC EQUIP

IT SERVER

LIGHTS

The Road to Net Zero

Net‐Zero Operation

Annual Energy (kW

h)

0

100,000

200,000

300,000

400,000

500,000

600,000

700,000

SOLAR

DOMEST HOT WTR

ELEVATOR

VENTFANS

PUMPS & AUX

SPACE COOLING

SPACE HEATING

MISC EQUIP

IT SERVER

LIGHTS

The Road to Net Zero

Net‐Zero Operation

Annual Energy (kW

h)

Page 10: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

10

Ground Source Heat Pump

Heavy Timber Structure: A 250 Year Building

Page 11: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

11

Courtesy: 2020 Engineering

Water Conservation

Water and Waste Systems: rainwater harvesting and composting toilets

Modeled End‐Use Energy Distribution

© UW Integrated Design Lab, 2014

Diagram: PAE Engineering

Page 12: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

12

CBECS Climate Zone 3 Averages

Plug loads are ~ 17% on an EUI of 92 kBtu/ft²‐yr (15.6)

Plug Load Energy in NW Buildings

Office Building: Seattle Energy Code 2009 (SEC, 2009)

EUI ~42 kBtu/ft²‐yrPlug loads alone = ~12.8 kBtu/ft²‐yr

Plug Loads Consume Approx. 29%* of Seattle Energy Code Office Building Site Energy and 

38% of  Site Electricity (SEC, 2009)

© UW Integrated Design Lab, 2015

*This is based on modeling done in 2009 – I presume the wattage is dropping somewhat die to adoption of 

more laptop computers.

Page 13: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

13

Bullitt Center

EUI ~16 kBtu/ft²‐yr (Now operating ~10 kBtu/ft²‐yr)Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐ with controls

If plug load reduction performance is not persistent over time the project will not meet net‐zero operation.

© UW Integrated Design Lab, 2015

Plug Load Energy in NW Buildings

Office Building: Seattle Energy Code 2009 (SEC, 2009)

EUI ~42 kBtu/ft²‐yrPlug loads alone = ~12.8 kBtu/ft²‐yr

Plug Loads Consume Approx. 29%* of Seattle Energy Code Office Building Site Energy and 

38% of  Site Electricity (SEC, 2009)

Page 14: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

14

Daylighting!

Page 15: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

15

Page 16: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

16

© UW Integrated Design Lab, 2015

Page 17: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

17

Page 18: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

18

“Tenant Engagement” (Office Equipt. Plug Loads)

Page 19: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

19

Energy Conservation Measures

TYPICAL BUILDING

With ENERGY 

CONSERVATION

With OCCUPANT 

ENGAGEMENT

DESIGN = 38%

DESIGN + PEOPLE= 70%

Page 20: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

20

Green Lease at Bullitt Center

• Many provisions…• Includes tenant energy budget apportioned by 

square footage of leased area.

© UW Integrated Design Lab, 2015

UW Leased Area: 7950 ft²Annual Energy budget: 5452 kWh

Plug Load Energy Allocation Density: 0.69 kWh/ft²Plug Load “Density” @ 2000 hrs: 0.345 W/ft² (whole building)@ 200 ft²/person: ~70 W/workstation

Office Plug Load Survey: Workstations

Page 21: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

21

Office Plug Load Survey: Copy Room

Office Plug Load Survey: Kitchen

Page 22: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

22

Monitors Computer

2 – 20” CFL-LCD 1 - Desktop@ 75 Watts each @ 100 Watts

2 – 22” LED-LCD 1 - Desktop@ 40 Watts each @ 80 Watts160 watts

2 – 22” LED-LCD 1 - Laptop@ 14 Watts each @ 62 Watts90 watts

Work Station Efficienciestypical

good (2009)

better (2010)

250 watts

Graphic: PAE Engineering

14watts

14watts

42 watts

22” LED-LCD

14watts

22” LED-LCD

Thin‐client Workstation

Page 23: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

23

Smart Plug Strips

control: switches and sensorsmeter: plugs and lights monitor: visualize and inform

Image: Enmetric Plug Load Manager/UW IDL

Comprehensive Plug‐Load/Task Lighting Management

Web‐based Real Time Plug Load Data Collection, Scheduling, and Reporting at Each Receptacle.

© UW Integrated Design Lab, 2014

Page 24: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

24

Enmetric Plugstripshttps://prod.enmetric.com/Username: [email protected]: idl@enm

Live Demo*

* fingers crossed

M&V and Occupant FeedbackOccupant Feedback and Energy Performance Documentation

© UW Integrated Design Lab, 2015

Page 25: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

25

Predicted vs. ActualBullitt Center Performance

-40,000

-30,000

-20,000

-10,000

0

10,000

20,000

30,000

40,000

50,000

60,000

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug

Elec

tric

Con

sum

ptio

n, k

Wh

Bullitt Center PerformanceActuals, 10/1/15

SCL Power Used PV Exported to SCL PV Used by BullittSavings over Baseline Bullitt Building Use Est. Code BaselineSCL Net Meter - SVC 4 Proposed Tenant Building

Graph: PAE Engineering

Thank you!

Christopher Meek, AIA, IESAssociate Professor and Director                                                                               Integrated Design Lab

University of Washington Department of Architecture [email protected] www.idlseattle.com

© UW Integrated Design Lab, 2015

Page 26: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

26

Dynamic Solar Shading: Glare Control and Daylight Persistence Measure

Baseline Windows Automated Exterior Blinds

© UW Integrated Design Lab, 2015

Page 27: Going Deep on Plug Loads - Aventri · Plugs alone = ~7.6 (3.1) kBtu/ft²‐yr‐with controls If plug load reduction performance is not persistent over time the project will not meet

5/17/2016

27

Dynamic Luminance Map: Automated Blinds Deployment© UW Integrated Design Lab, 2015