honeywell tracetm · this patch software change notice contains important information that must be...
TRANSCRIPT
HONEYWELL TRACETM
R130
___________________________________
Patch-2 Software Change Notice
___________________________________
HTDOC-X587-en-620A
September 2019
HTDOC-X587-en-620A 2
DISCLAIMER
This document contains Honeywell proprietary information. Information contained herein
is to be used solely for the purpose submitted, and no part of this document or its contents
shall be reproduced, published, or disclosed to a third party without the express
permission of Honeywell International Sàrl.
While this information is presented in good faith and believed to be accurate, Honeywell
disclaims the implied warranties of merchantability and fitness for a purpose and makes
no express warranties except as may be stated in its written agreement with and for its
customer.
In no event is Honeywell liable to anyone for any direct, special, or consequential damages.
The information and specifications in this document are subject to change without notice.
Copyright 2019- Honeywell International Sàrl
ABOUT THIS DOCUMENT
HTDOC-X587-en-620A 3
Table of contents 1 ABOUT THIS DOCUMENT .............................................................................................................................. 4
2 WHAT’S NEW IN HONEYWELL TRACE R130 PATCH-2 ................................................................... 5
3 INSTALLING R130 PATCH-2 .................................................................................................................. 10
3.1 Supported Migration Scenarios ................................................................................................................... 10
3.2 Installer Package ................................................................................................................................................. 10
3.3 Install Instructions .............................................................................................................................................. 11
4 PATCH 2 – RESOLVED ISSUES ............................................................................................................... 18
5 PATCH 1 - RESOLVED ISSUES ................................................................................................................ 20
6 KNOWN ISSUES ............................................................................................................................................ 22
7 NOTICES.......................................................................................................................................................... 23
ABOUT THIS DOCUMENT
HTDOC-X587-en-620A 4
1 About this document
This Patch Software Change Notice contains important information that must
be read prior to installing and working with Honeywell Trace R130 Patch-2.
Trace R130 Patch-2 is a cumulative release that contains the following: Trace
R130 Patch-1, the hotfixes released after Patch1, enhancements, and fixes.
For more information about enhancements, see the section What’s New. For
information about fixes, see the section Resolved Issues
WHAT’S NEW IN HONEYWELL TRACE R130 PATCH-2
HTDOC-X587-en-620A 5
2 What’s New in Honeywell Trace R130 Patch-2
The following feature enhancements are available in R130 Patch-2:
Parameter related information are now included in the CL View also.
Previously, only point names were displayed under the Referenced
Tags. Now, parameters related details are also displayed.
Tags based grouping of the referenced tags is enabled for CL,
PointScript, CAB instance, and Display View. You can view
tag.parameter(s) details on expanding the required Tag.
WHAT’S NEW IN HONEYWELL TRACE R130 PATCH-2
HTDOC-X587-en-620A 6
Provision to view I/O modules and channels is enabled for the DHP
[EPLCG] node in the Hardware View of the TPS system.
New option is introduced in the TPS Data Collection page to
selectively collect DS [Display] files. The DS files will be collected only
if this option is selected.
WHAT’S NEW IN HONEYWELL TRACE R130 PATCH-2
HTDOC-X587-en-620A 7
New icon [R] is introduced to indicate the Reserved Channels in the
Hardware View to ease the identification of reserved vs free channels
and allocation appropriately.
Option to select any Display Object on the Reference Tags list will
highlight the selected object on the Display view for HMI display.
WHAT’S NEW IN HONEYWELL TRACE R130 PATCH-2
HTDOC-X587-en-620A 8
Group number and position number data appears for Experion Groups
and Trend references.
The tags referred in a display will list all display files instead of each
object in a display. Each object reference can be viewed on the
selected display file.
WHAT’S NEW IN HONEYWELL TRACE R130 PATCH-2
HTDOC-X587-en-620A 9
INSTALLING R130 PATCH-2
HTDOC-X587-en-620A 10
3 Installing R130 Patch-2
This section provides information about how to install Trace R130 Patch-2.
3.1 Supported Migration Scenarios You can install the Trace R130 Patch-2 in the following progression:
1. Migration
Trace R121 Trace R130.1 Trace R130 Patch-2
2. New Installation
Trace R130.1 Trace R130 Patch-2
3. Upgrade
Trace R130.1 Trace R130 Patch-1 + Hotfixes (which is not
mandatory) Trace R130 Patch-2
3.2 Installer Package The Trace_R130.1_Patch2.zip package contains individual installer for each
Trace nodes in the following folder:
L3Server
L4Server
Offline_DataCollector
RemoteNode
INSTALLING R130 PATCH-2
HTDOC-X587-en-620A 11
3.3 Install Instructions Install the patch Trace_R130.1_Patch2.zip on Honeywell Trace Server (L3
and L3.5), Trace Data Collector, and Remote nodes.
If installing on… Follow these steps
Trace Server at L3 / Offline
Trace Server
1. Make sure the Data Collection is not in progress. If
Data Collection is in progress, wait until the
collection is complete.
2. Close all the instance of Trace application and
Microsoft SQL.
3. Extract the Trace_R130.1_Patch2.zip file.
4. Copy the L3Server_update.exe from
Trace_R130.1_Patch2\L3Server and paste in your
Trace Server machine.
5. Right-click the L3Server_update.exe, select Run as
Administrator, and click Yes.
6. Honeywell Trace L3 Server Patch appears. Click
Update.
7. Select Automatically close and attempt to restart
applications and click OK.
INSTALLING R130 PATCH-2
HTDOC-X587-en-620A 12
ATTENTION:
You may encounter the following message occasionally.
Click OK to ignore and proceed with the installation.
8. Click Finish.
9. Restart the machine, click Yes.
INSTALLING R130 PATCH-2
HTDOC-X587-en-620A 13
Trace Server at L3.5 / L4 1. Make sure the Data Collection is not in progress. If
Data Collection is in progress, wait until the
collection is complete.
2. Close all the instance of Trace application and
Microsoft SQL.
3. Extract the Trace_R130.1_Patch2.zip file.
4. Copy the L4Server_Update.exe from
Trace_R130.1_Patch2\L4Server and paste in your
Trace Server machine.
5. Right-click the L4Server_Update.exe, select Run as
Administrator, and click Yes.
6. Honeywell Trace L4 Server Patch appears. Click
Update.
INSTALLING R130 PATCH-2
HTDOC-X587-en-620A 14
ATTENTION:
You may encounter the following message occasionally.
Click OK to ignore and proceed with the installation.
7. Click Finish.
8. Restart the machine, click Yes.
Trace Server at L3
To establish sync between L3 and L3.5/L4:
1. Run the Trace Admin Console for Sync.
INSTALLING R130 PATCH-2
HTDOC-X587-en-620A 15
Trace remote node 1. Make sure the Data Collection is not in progress. If
Data Collection is in progress, wait until the
collection is complete.
2. Extract the Trace_R130.1_Patch2.zip file.
3. Copy the RemoteNode_Update.exe from
Trace_R130.1_Patch2\RemoteNode and paste in
your Trace remote node machine.
4. Install the RemoteNode_Update.exe located in
Trace_R130.1_Patch2\RemoteNode. Click Update.
NOTE:
Only for PHD node, provide the host name of PHD
Database Server.
5. Click Finish.
INSTALLING R130 PATCH-2
HTDOC-X587-en-620A 16
Trace Data Collector 1. Make sure the Data Collection is not in progress. If
Data Collection is in progress, wait until the
collection is complete.
2. Close all the instance of Trace application.
3. Extract the Trace_R130.1_Patch2.zip file.
4. Copy the Offline_DataCollector_Update.exe from Trace_R130.1_Patch2\Offline_DataCollector and paste in your machine where Trace Data Collector is installed.
5. Install the Offline_DataCollector_Update.exe. Click
Update.
6. Select Automatically close and attempt to restart
applications, and click OK.
INSTALLING R130 PATCH-2
HTDOC-X587-en-620A 17
ATTENTION:
You may encounter the following message occasionally.
Click OK to ignore and proceed with the installation.
7. Click Finish.
8. Restart the machine, click Yes.
PATCH 2 – RESOLVED ISSUES
HTDOC-X587-en-620A 18
4 Patch 2 – Resolved Issues
The following is the list of resolved issues in Patch-2.
PAR # Issue - Description
1-BPY8N41 Trace login takes longer time to load the dashboard page.
1-BPY8N4B Unable to login Trace due to failed Trace License service.
1-BPY8N4J CDS parameters (including arrays) and references are missing for
the AM points in TPS system.
1-BPY8N5V Loading peer reference takes longer time.
1-BPY8N81 Fetching snapshot status message was displayed in all the page in
Trace application when data collection was in progress.
1-BPY8N8A Trace snapshot collection fails when large number of displays are
collected in Experion PKS system.
1-BPY8NB9 Sync between L3 and L3.5/L4 fails when ICMP ping is blocked by
the firewall.
1-BPY8NBH PVRAWHI and PVRAWLO parameters are missing in Trace property
for SM AI Points in TPS system.
1-BPY8NCW If multiple TPS systems were selected while adding PHD
application, Trace is unable to resolve all PHD references.
1-BPY8NHK PHD data collection fails when the collector node does not have
PHD config tool installed.
1-BPYHMG6 TPS points are not resolved in EPKS HMI displays for ESVT systems
with DSA/Safety Manager tags.
1-BPYKY0M Network View does not appear for all clusters in a single EMDB
wherein each cluster has top-level switch.
1-BPYKYCS Tag list in the Hardware View populates other controller points.
1-BPYKYD0 Global search was not performed on the latest snapshot by default.
PATCH 2 – RESOLVED ISSUES
HTDOC-X587-en-620A 19
PAR # Issue - Description
1-BPYKYD8 Invalid Display reference anomalies in Experion HMI displays.
1-BPYKYDG Hardware View does not show FIM2 in the C200 remote chassis.
1-BPYKYDY Experion displays are not collected occasionally.
1-BPYKYE6 Unable to navigate to Hardware View from global search result for
TPS channels.
1-BPYKYEY Unable to acknowledge changes in the Logical View.
1-BPYKYF6 Unable to login to Trace after migrating to R130 occasionally.
1-BPYR5OC Unable to generate Trace reports after migrating to R130
occasionally.
PATCH 1 - RESOLVED ISSUES
HTDOC-X587-en-620A 20
5 Patch 1 - Resolved Issues
The following is the list of resolved issues in Patch-1.
JIRA PAR Issue - Description/Recovery/Workaround
RTRACE – 1924 When connections are shown on TRS, the index parameters were also
shown on the respective ends of the connections.
RTRACE – 1847 The TRS connections were missing because references for
downstream system for connections were not resolved.
RTRACE - 1950 When a system is deleted, its displays and references deletions were
also shown as changes in Change Detection.
RTRACE – 1912 For TPS, in Change Detection Page, for CL changes, object name was
appearing as a hyperlink.
RTRACE – 1940 For TPS, in Display View, on the right-side of the window, search box
was retaining previous search string.
RTRACE -1936 From any modification tab, if user performs suppression, it wasn’t
getting reflected in UI.
RTRACE -1852 For TPS, in Display View, navigation for few Referenced tags was not
working for .DS files.
RTRACE -1944 For Allen-Bradley ControlLogix, in few scenarios, Trace failed to
retrieve the correct Sheet Count for the respective FBD Tag which
results in missing FBD Logic in Allen-Bradley ControlLogix System.
RTRACE – 1935 In case of Logic Point, if there is any tag (for example, Array, Logic, or
Digital Composite) is configured as Input/Output Connections, Trace
wasn’t capturing those references.
RTRACE – 1933 For TPS, the tags referred indirectly in CL file, the information is listed
in TRS Tabular view, but it was not appearing as a link.
RTRACE – 1553 If the two AM Nodes are configured as Redundant, Trace failed to
identify that information when the Node numbers are not
consecutive.
RTRACE – 1415 Trace failed to consider those parameters while parsing the
Checkpoint file, which results in mismatch compared to Source
System.
PATCH 1 - RESOLVED ISSUES
HTDOC-X587-en-620A 21
JIRA PAR Issue - Description/Recovery/Workaround
RTRACE -1951 Migrated L3 (old machine to new machine) and fresh L3.5
synchronization was failing.
BW- 36350 Post-Experion data collection, there was an "i" icon that appears to
right of system name. Clicking or placing cursor over the icon wasn't
opening the screen tip containing details.
RTRACE -1931 In TPS, for few .htm files, the referred links/tags were not listed in the
Referred Links/tags pane.
RTRACE -1955 Experion parsing failed due to displays collection failure.
RTRACE -1953 TPS data collection was failing because user action was required
while reading the .PCT file.
RTRACE -1952 In the migration scenario, Change Detection was slow.
RTRACE -1946 IAA report generation was failing in few L3 migrated machines.
RTRACE-1932 When .htm files are searched from Global Search, a window opens
displaying the following message, "Currently, the view for this display
is not available."
RTRACE-1614 Stored Procedure fine tuning and caching performance has
improved after migrating from R121 to R130.
RTRACE-1947 ESVT system license consumes pure TPS and pure EPKS license.
KNOWN ISSUES
HTDOC-X587-en-620A 22
6 Known Issues
The following is the list of known issues.
PAR # Issue - Description/Recovery/Workaround
RSWORD-967 Flexera License Utility throws error when an expired or outdated
“Response.bin” file is uploaded to activate the license.
RSWORD-968 When an unused Activation key is used for returning license, Flexera
is creating .bin file, which it should not create (as it cannot be used).
RSWORD-969 When Flexera License Activation Utility screen is left idle for more
than 20 minutes, application throws an error for the first operation
done past this idle period.
Workaround: Refresh the screen post-idle time.
RSWORD-970 Flexera License Activation Utility accepts only GUID, whereas it is
accepting any number of characters.
RSWORD-980 In License Activation Utility, online license activation may fail
throwing “Generic communications error.”
RTRACE – 1949 For Trace Data Collector, in few scenarios, the status shown is
“Initiating” even though the overall Snapshot status has failed. This
occurs when Resume button is clicked during the snapshot failure.
RTRACE – 1960 External tag references with respect to communication between
Allen-Bradley ControlLogix and Experion PKS via EIM are not
appearing.
NOTICES
HTDOC-X587-en-620A 23
7 Notices
Trademarks
Experion®, PlantScape®, SafeBrowse®, TotalPlant®, and TDC 3000® are
registered trademarks of Honeywell International, Inc.
OneWireless™ is a trademark of Honeywell International, Inc.
Other trademarks
Microsoft and SQL Server are either registered trademarks or trademarks of
Microsoft Corporation in the United States and/or other countries.
Trademarks that appear in this document are used only to the benefit of the
trademark owner, with no intention of trademark infringement.
Third-party licenses
This product may contain or be derived from materials, including software, of
third parties. The third party materials may be subject to licenses, notices,
restrictions and obligations imposed by the licensor.
The licenses, notices, restrictions and obligations, if any, may be found in the
materials accompanying the product, in the documents or files
accompanying such third party materials, in a file named third_party_ licenses
on the media containing the product, or at
http://www.honeywell.com/ps/thirdpartylicenses.
Documentation feedback
You can find the most up-to-date documents on the Honeywell Process
Solutions support website at:
http://www.honeywellprocess.com/support
If you have comments about Honeywell Process Solutions documentation,
send your feedback to:
Use this e-mail address to provide feedback, or to report errors and omissions
in the documentation. For immediate help with a technical problem, contact
your local Honeywell Process Solutions Customer Contact Center (CCC) or
Honeywell Technical Assistance Center (TAC).
NOTICES
HTDOC-X587-en-620A 24
How to report a security vulnerability
For the purpose of submission, a security vulnerability is defined as a software
defect or weakness that can be exploited to reduce the operational or security
capabilities of the software.
Honeywell investigates all reports of security vulnerabilities affecting
Honeywell products and services.
To report a potential security vulnerability against any Honeywell product,
please follow the instructions at:
https://honeywell.com/pages/vulnerabilityreporting.aspx
Submit the requested information to Honeywell using one of the following
methods:
Send an e-mail to [email protected].
or
Contact your local Honeywell Process Solutions Customer Contact Center
(CCC) or Honeywell Technical Assistance Center (TAC) listed in the “Support”
section of this document.
Support
For support, contact your local Honeywell Process Solutions Customer
Contact Center (CCC). To find your local CCC visit the website,
https://www.honeywellprocess.com/en-US/contact-us/customer-support-
contacts/Pages/default.aspx.
Training classes
Honeywell holds technical training classes that are taught by process control
systems experts. For more information about these classes, contact your
Honeywell representative, or see http://www.automationcollege.com.
NOTICES
HTDOC-X587-en-620A 25