holcim lynwood quarry external lighting review report
TRANSCRIPT
PREPARED BY:
WEBB AUSTRALIA GROUP (ACT) PTY LTD ABN 14 064 354 776 [email protected] www.webbaustralia.com.au
SUITE 3, 10-12 COLBEE COURT PHILLIP ACT 2606 AUSTRALIA T +61 2 6285 4365 F + 61 2 6285 4253
CONSULTING ENGINEERS ELECTRICAL LIGHTING MECHANICAL SECURITY COMMUNICATIONS AUDIO VISUAL
BRISBANE CANBERRA GOLD COAST MELBOURNE NEWCASTLE SUNSHINE COAST SYDNEY
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW
REPORT
L490arep001_C.docx Page 2 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW
REPORT
Copyright © 2014 Webb Australia Group (ACT) Pty Ltd. All rights reserved.
This report may not be reproduced or transmitted in any
form or by any means in part or in whole without written permission of
Webb Australia Group (ACT) Pty Ltd ABN 14 064 354 776.
Issued As: PRELIMINARY
___________
FINAL
Authorised By: JOHN GRIGGS
Date: 7 MAY 2014
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 3 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
TABLE OF CONTENTS
1 EXECUTIVE SUMMARY .....................................................................................................................4
2 INTRODUCTION ................................................................................................................................5
3 EXISTING LIGHTING INSTALLATION ................................................................................................5
4 LIGHTING DESIGN – MINIMUM REQUIREMENTS ............................................................................6
5 LIGHTING CONSTRAINTS .................................................................................................................8
5.1 RELEVANT DEVELOPMENT CONSENT CONDITIONS ................................................................................ 8
5.2 AS 4282:1995 CONTROL OF OBTRUSIVE EFFECTS OF OUTDOOR LIGHTING ............................................ 8
6 FINDINGS BY CALCULATION ............................................................................................................9
6.1 RESULTS OF MAINTAINED HORIZONTAL ILLUMINANCE CALCULATIONS .............................................. 9
6.2 RESULTS OF INITIAL HORIZONTAL ISOLUX CALCULATIONS ................................................................. 10
6.3 RESULTS OF INITIAL VERTICAL ILLUMINANCE CALCULATIONS RE. AS 4282 ....................................... 10
6.4 RESULTS OF INITIAL LUMINOUS INTENSITY CALCULATIONS RE. AS 4282 .......................................... 11
6.5 I TABLE EXAMINATION ......................................................................................................................... 11
6.6 RESULTS OF CALCULATIONS WITH 700
TILT ......................................................................................... 12
7 ASSESSMENT ................................................................................................................................. 13
7.1 MINIMUM REQUIREMENTS .................................................................................................................. 13
7.2 EXTENT OF 1 LUX HORIZONTAL ILLUMINANCE..................................................................................... 13
7.3 VERTICAL ILLUMINANCE ....................................................................................................................... 13
7.4 LUMINOUS INTENSITY .......................................................................................................................... 13
7.5 HOLCIM DEVELOPMENT CONSENT CONDITIONS .................................................................................. 14
8 CONCLUSION AND RECOMMENDATIONS ..................................................................................... 15
APPENDICES .......................................................................................................................................... 16
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 4 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
1 EXECUTIVE SUMMARY
The existing lighting installation at Lynwood Quarry was energised for testing while not having been aimed in
accordance with the design requirements.
At (say) 700
tilt, the visual impact was observed from the surrounding areas. The maximum
recommendations of AS 4282 are estimated to have been exceeded in all directions.
The lighting design has been assessed, based on the luminaires being aimed in accordance with the design
requirements.
Findings confirmed some areas, such as the road ways and parking area are over illuminated, with average
horizontal illuminance levels well in excess of the minimum average design values.
Isolux calculations identified horizontal illuminance (spill light) exceeding 1 lux extends outside the notional
site boundary.
Vertical illuminance at notional vertical planes 100m beyond the furthest luminaire in each direction was
found to be below the maximum value recommended by AS 4282.
Luminous intensity of the site lighting installation at notional vertical planes was found to be below the
maximum value recommended by AS 4282 at 1000m. No dwellings are located within 1000m.
The maximum luminous intensity of the flood light luminaires was found to be below the maximum value
recommended by AS 4282 when viewed from distances less than to the nearest dwelling.
No remedial works are required to achieve compliance with the obtrusive lighting recommendations of AS
4282.
A reduction in the illumination levels of areas identified as over illuminated may be possible by replacement
of luminaires, if considered necessary.
Provision of screening, where required, may limit the visual impact the lighting installation would have on
affected dwellings at elevations below the site.
Provision of screening may prevent or minimise unwanted lighting impacts on the broader community,
consistent with the conditions of the Holcim Development Consent.
Responses to a range of matters arising from the draft issue of this report are provided in Appendix 7.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 5 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
2 INTRODUCTION
Residents surrounding the Lynwood Quarry, currently being developed by Holcim, have raised their concerns
regarding the likely impact the external site lighting at the quarry will have on the local environment and the residents
enjoyment of the rural landscape when the quarry commences operations later this year. Encorporate Pty Ltd,
representing the interests of the residents, engaged Webb Australia Group to undertake an independent review of the
current lighting design and to provide an assessment of the following:
Calculated lighting levels achieved against the stated design criteria
Calculated vertical illuminance at the affected dwellings against obtrusive lighting requirements of AS 4282
Luminous intensity of luminaires as viewed from direction of residences against the maximum permissible by
AS 4282
Compliance against the Holcim Development Consent Conditions
Prepare a report on the outcomes of the above assessment
This report addresses the impact the proposed external lighting may have on the surrounding environment and
residents, whether the lighting will comply with Australian Standard AS 4282 and the relevant terms of the Holcim
Development Consent conditions.
3 EXISTING LIGHTING INSTALLATION
From the drawings and information provided, the existing lighting installation consists of the following.
LUMINAIRE DESCRIPTION LOCATIONS
1.
(R)
42W Compact Fluorescent road luminaire with aeroscreen flat
glass lens (Sylvania Urban Eco JA9700) mounted on a timber pole
at 7.5m above finished ground level (FGL) on a 0.3m outreach arm,
tilted up 50
Rail siding
2.
(F)
400W Metal Halide full cut-off flood light (Pierlite Maxi Master
GMRS400 MH) bracket mounted on a timber pole at 12.5m above
FGL, titled 50
. Single and twin arrangements
Car Park
3.
(F1)
2 x 400W Metal Halide full cut-off flood light (Pierlite Tarmac APR-
2X400 MH) bracket mounted on a timber pole at 15m above FGL,
tilted 50
. Single and twin arrangements
Roadways, intersections,
Weighbridges, Rail load-out facility,
Dam Pump stations, and other
vehicle areas
Based on information provided, lighting levels achieved by the luminaires installed and aimed as advised by GHD has
been calculated for the site. GHD advised all luminaires were to be aimed as follows:
Orientation Perpendicular to corresponding roadway
Tilt 50
Holcim advised the luminaires were not aimed when initially installed but were energised for testing with luminaires
tilted to approximately 750
. Subsequently, we have been advised all luminaires have been aimed with 50
tilt, however
they have not been energised or operated subsequent to aiming or the initial testing. The lighting is not expected to
be operated again until commissioning, which is planned for May/ June 2014.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 6 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
4 LIGHTING DESIGN – MINIMUM REQUIREMENTS
Webb Australia was not party to the client consultation process, however, in the absence of any Australian Standard
specifically applicable to the lighting of quarries, the lighting designers resort to applying principles in International
Standard CIE 129, AS 1680.2.4, accepted industry practice and the development of the brief by consultation with the
client.
The statement provided by the lighting designer (GHD) which identifies the design criteria used, is as follows:
The lights have been designed to point downwards at an angle of 5 degrees from the vertical
The lighting which has been installed to service the road intersections has been designed to produce an
average 40 lux on the ground
The lighting which has been installed to service the infrastructure components (weighbridge, refuelling, truck
wash, etc) has been designed to produce an average level on the ground between 60 lux (minimum) and 80
lux (maximum)
From the information provided by GHD, by the application of Australian Standards and from our investigation of
accepted industry practice, we have summarised the minimum lighting requirements for areas that may be
considered relevant to the site, in the table below.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 7 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
Table 4.1: Minimum Illuminance Requirements
Area
Minimum Average Maintained Horizontal Illuminance (Lux)
AS 1680.2.4:
1997
AS 1158.3.1:
2005
CIE129:
1998
BMA –PR01 GHD AS 1680.5:
2012
Railway Freight
track areas
10
Access
roadways
7 (P1) Category 20 10
Intersections 40
Light vehicle
carparks
7 (P11b)
Category
10
Heavy vehicle
areas
30
Stockpile 30
Water Pumping
Stations
40
Materials
handling-
wagon loading
& unloading
40 50
Weighbridge,
refuelling, truck
wash
60-80
Open area,
machines (site
inducted
personnel)
10
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 8 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
5 LIGHTING CONSTRAINTS
Although the minimum lighting requirements must be achieved for operational and safety reasons, there are also
upper limits that may be applied to outdoor lighting installations, to minimise the obtrusive effects of the lighting on
the surrounding area and the environment. These constraints applicable to the Holcim Lynwood Quarry are as
follows.
5.1 RELEVANT DEVELOPMENT CONSENT CONDITIONS
The relevant terms of the Development Consent conditions for Lynwood Quarry are as follows:
“50. The Applicant shall take all practicable measures to prevent and or minimise any off-site lighting
impacts from the development”; and
“51. All external lighting associated with the development shall comply with Australian Standard AS 4282
(INT) 1995 – Control of obtrusive effects of outdoor lighting”.
5.2 AS 4282:1995 CONTROL OF OBTRUSIVE EFFECTS OF OUTDOOR LIGHTING
The recommended maximum values of light technical parameters (LTPs) for the control of obtrusive light, as
applicable to the Holcim Quarry, extracted from Table 2.1* of AS 4282(for residential areas with dark surrounds
throughout curfewed hours) are summarised as follows:
Illuminance in vertical plane (at windows of dwellings of nearby residential properties) 1 lux
Luminous Intensity emitted by luminaires in direction of residential properties 500 Cd
*Refer to Appendix 1 for replication of Table 2.1 in full.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 9 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
6 FINDINGS BY CALCULATION
A series of lighting calculations have been undertaken to assess the existing lighting installation, as follows:
Calculation Assessment Criteria Appendix
1 Maintained horizontal illuminance Assess if over illuminated against
minimum requirements
2
2 1 lux horizontal illuminance (initial values) Provide a rudimentary assessment
of extent of spill light
3
3 Vertical illuminance (initial values) AS 4282 Table 2.1 4
4 Luminous intensity (initial values) AS 4282 Table 2.1 4
5 Vertical illuminance with luminaires tilted to
700
(initial values)
AS 4282 Table 2.1 5
6 Luminous intensity with luminaires tilted to 700
(initial values)
AS 4282 Table 2.1 5
Note: “Maintained values are calculated values at the end of the maintenance cycle.
“Initial” values are calculated values with new lamps and clean luminaires at the beginning of the maintenance cycle.
6.1 RESULTS OF MAINTAINED HORIZONTAL ILLUMINANCE CALCULATIONS
Maintained horizontal illuminance calculations were under taken for separate areas where lighting has been installed.
Where the calculation area is clearly defined, calculation average values could be used to assess the lighting against
the light technical parameters (LTPs) recommended by AS 1158.3.1 or other design criteria (Table 4.1).
The findings are as follows:
Area Calculated Average
Value (lux)
Recommended minimum
Average Design Value
range (lux)*
Assessed as over
Illuminated
Entry roadway (1) 44.9 7 – 20 Yes
Access roadway (2) (to
carpark)
24.8 3.5 – 20 No
Railway Siding 2.0 10 No
Weighbridge roadway 64.2 60 – 80 No
Parking Area 33.8 7 – 10 Yes
Intersection (East) 13.4 40 No
Intersection (West) 55.2 40 No
*Minimum average values extracted from Table 4.1.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 10 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
For areas where the calculation area could not be defined, average values do not provide a useful measure of
assessment. Therefore, maximum values have been used to provide an indication of lighting performance.
Calculated maximum values of such areas, in descending order of magnitude, include:
Area Maximum (Lux) Assessed as over
Illuminated
Workshop North 139 Potentially
Admin Workshop area 108 Potentially
Workshop East 100 Potentially
N. Crib Room 83 No
Dam I Pump Station 57 No
Dam F Pump Station 53 No
Far East 45 No
Refer to Appendix 2 for more information.
Note: The primary activity of some of the areas above is unclear, consequently the appropriate design illuminance is
uncertain.
6.2 RESULTS OF INITIAL HORIZONTAL ISOLUX CALCULATIONS
A calculation of initial values of horizontal illuminance for the site may be found at Appendix 3. This calculation
includes an isolux plot of the 1 lux value which shows diagrammatically where the 1 lux value extends. Horizontal
illuminance outside the areas shown is below 1 lux.
6.3 RESULTS OF INITIAL VERTICAL ILLUMINANCE CALCULATIONS RE. AS 4282
In the absence of details of locations of affected dwellings, the limits of AS 4282 compliance have been calculated in
the four directions of the compass from the installation.
Values of initial vertical illuminance were calculated in vertical planes in the north, south, east and west axes, 100m
from the nearest luminaire to that plane. No dwellings are located within the area bounded by the vertical calculation
planes.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 11 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
The maximum calculated values are as follows:
Vertical Plane Max Evert
@ 100m
(Lux)
North 0.3
South 0.1
East 0.3
West 0.3
All calculated values of vertical illuminance at 100m are less than 1 lux and are below the maximum recommended
value for vertical illuminance by AS 4282 for residential areas with dark surrounds throughout curfewed hours.
6.4 RESULTS OF INITIAL LUMINOUS INTENSITY CALCULATIONS RE. AS 4282
Values of initial luminous intensity of the site when viewed from the four points of the compass at 100m, 200m and
1000m from the nearest luminaire were calculated. The maximum calculated values are as follows:
Maximum I (cd) Values at
Segment Vertical Plane 100m 200m 1000m
4 North 1912 639 314
2 South 2973 470 298
3 East 2847 639 309
1 West 942 544 308
All calculated values of luminous intensity at 100m and 200m from the nearest luminaire exceed the 500 cd
maximum recommended by AS 4282.
All calculated values of luminous intensity of 1000m from the nearest luminaire are below the 500 cd maximum
recommended by AS 4282 for residential areas with dark surrounds throughout curfewed hours.
There are no dwellings located within the 1000m calculation area.
6.5 I TABLE EXAMINATION
The Luminous Intensity (I) tables for the two flood light luminaires were examined to identify the vertical angle at
which the luminous intensity falls below 500 cd, as follows.
APR2400 2 x HPIT400W
From an examination of the Candela tabulation table for the 2 x 400W Tarmac, the 500 cd threshold occurs between
the vertical angles of 750
and 850
. By interpolation, the 500 cd is estimated to occur at approximately 820
(vertical).
As the luminaires are tilted 50
, the 500 cd threshold is raised to occur at approximately 870
.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 12 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
For a mounting height of 15m, luminous intensity of these luminaires would drop below 500 cd beyond 300m.
(Assumes a horizontal topography and luminaires tilted to 50
).
GMRS400MH
From an examination of the Candela tabulation table for the 400W Maxi Master, the 500 cd threshold occurs
between the vertical angles of 650
and 750
. As the luminaires are tilted 50
, the 500 cd threshold is raised to occur
between 700
and 800
.
For a mounting height of 15m, luminous intensity of these luminaires would drop below 500cd in less than 100m.
(Assumes a horizontal topography and luminaires tilted to 50
).
6.6 RESULTS OF CALCULATIONS WITH 700
TILT
Values of vertical illuminance and luminous intensity were calculated, as calculated above, but with the luminaires
tilted to 700
, to enable a comparison of the obtrusive light observed during testing and what may be expected after
aiming with 50
tilt.
The maximum calculated vertical illuminance values are as follows.
Vertical Plane
Max Evert
(Lux)@ 100m
50
TILT 700
TILT
North 0.3 2.3
South 0.1 2.3
East 0.3 2.4
West 0.3 4.7
This calculation confirms vertical illuminance in all four directions exceed the 1 lux recommended maximum value
when the luminaires are tilted at 700
.
The maximum calculated luminous intensity values are as follows.
Seg
Vertical Plane
Max I (cd) Values at
1000m
50
TILT 700
TILT
4 North 314 18650
2 South 298 18650
3 East 309 18639
1 West 308 18646
This calculation confirms the luminous intensity in all four directions exceeds the 500 cd recommended maximum
value when the luminaires are tilted at 700
.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 13 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
7 ASSESSMENT
7.1 MINIMUM REQUIREMENTS
The Standards for minimum illuminance requirements for the various areas are established for operational and safety
requirements (refer Table 4.1). These Standards are primarily concerned with minimum levels being achieved and do
not set any maximum illuminance levels. Exceeding the minimum levels is permissible. It is common design practice
to exceed the minimum requirements by a comfortable margin to ensure the levels do not fall below the minimum
requirements at any time during the luminaire maintenance cycle (i.e. between relamping and/or cleaning intervals).
Set against the minimum requirements, AS4282 provides recommendations on the maximum values of obtrusive light
permitted by the installation.
Upon review of the lighting design, two areas were identified where the illuminance achieved by the design is well in
excess of the minimum requirements (i.e. the entry roadway and the parking area). Although the lighting design
appears to be over-illuminated in these areas, the maximum values of obtrusive light recommended by AS4282 are
not exceeded. The design satisfies the minimum requirements by a substantial margin and still complies with the
obtrusive lighting recommendations of AS4282.
The impact of “over-engineering” of the lighting in these two areas would include marginally higher installation and
operational costs for the quarry and an elevated illuminance level.
It may be possible to replace the luminaires with new fixtures with lower wattage lamps as a remedial measure and
still achieve the minimum illuminance requirements, however, compliance with the lighting design criteria would have
to be confirmed by the lighting designer.
7.2 EXTENT OF 1 LUX HORIZONTAL ILLUMINANCE
The boundary of the quarry site is unclear, however the 1 lux isolux line appears to extend beyond the western site
boundary and beyond the railway area to the South and East. This incursion is considered marginal. The horizontal
illuminance falls below 1 lux elsewhere within the mine site.
Horizontal illuminance is not a specified LTP used for the assessment of obtrusive light, however this calculation helps
to gain an appreciation of the extent of spill light.
Raytrace images of the horizontal illuminance of the site when viewed from various directions at elevated positions
are included in Appendix 6.
7.3 VERTICAL ILLUMINANCE
The vertical illuminance values calculated in all 4 directions are found to be within the maximum recommendations of
AS 4282 at 100m and therefore, are compliant with code requirements in this respect.
7.4 LUMINOUS INTENSITY
The luminous intensity values calculated in all 4 directions are found to be within the maximum recommendations of
AS 4282 at less than 1000m and therefore, are compliant with code requirements in this respect also.
By examination of the luminaire I Tables, the luminous intensity of the flood light luminaires, when tilted at 50
, falls
below 500 cd beyond 300m (approx.) assuming a horizontal topography, confirming compliance with AS 4282 is
achieved for surrounding areas at or above the elevation of the quarry.
Luminaire tilt must remain fixed at 50
for all luminaires to ensure code compliance is maintained.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 14 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
7.5 HOLCIM DEVELOPMENT CONSENT CONDITIONS
The Holcim Quarry Development Consent Condition No. 50 states “The Applicant shall take all practicable measures
to prevent and or minimise any off-site lighting impacts from the development”.
As the quarry lighting will be visible from beyond the boundary of the site, there will be some off-site lighting impacts.
The Development Consent conditions require that such impacts be prevented or minimised by the undertaking of all
practicable measures to do so.
This report has only considered measures employed by the lighting design to control the obtrusive effects of the site
lighting. These include:
The use of aeroscreen luminaires with flat glass lenses
Constrained the tilt to 5 degrees
With a few exceptions, luminaires near the site perimeter are generally facing into the site and away from
nearby dwellings.
These methods are considered responsible approaches by the lighting designer to controlling obtrusive light.
There are other, non-lighting measures that may be employed to further reduce the impacts of the lighting, such as:
The erection of screens
Planting of trees
Formation of earth embankments
Screens may be considered an interim solution until trees can be established to form a dense vegetation barrier
which may provide a more permanent solution.
Identification of locations where further measures are required and the extent and selection of appropriate,
practicable measures, would require further assessment and consultation.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 15 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
8 CONCLUSION AND RECOMMENDATIONS
Although the assessment of obtrusive light is the focus of this report it must be viewed in the context of the original
purpose of the lighting installation, i.e.,to provide fit for purpose, functional lighting and a safe night time operational
environment. Safety is the primary function of the lighting installation. In our opinion, by the installation of full cut-off,
aeroscreen (flat glass) luminaires, the lighting design achieves compliance with the obtrusive lighting requirements
without compromising operational lighting requirements or safety.
The concerns of the residents have been vindicated in that the lighting, as observed when turned on for testing, was
well in excess of the maximum recommendations of AS 4282.
Provided the lighting is re-aimed in accordance with the design, i.e. with 50
tilt, the lighting calculations demonstrate
compliance with AS 4282 will be achieved for all surrounding dwellings of the same elevation, or above.
No remedial works are required to achieve compliance with the obtrusive lighting recommendations of AS 4282.
Where dwellings are identified below the elevation of the quarry and with an unobstructed line of site, compliance
with the Standard may need to be reviewed, subject to the proximity and location of the affected dwellings.
The Holcim Development Consent Conditions go further than the recommendations of AS 4282, requiring all
practicable measures be taken to prevent and or minimise off-site lighting impacts.
Additional measures may be required to further reduce the impacts of the lighting on the broader community, areas
zoned for future residential development or for specific dwellings where sensitivities persist, to satisfy the
Development Consent Conditions.
Such measures may include, but not be limited to, the following:
Replacement of selected luminaires with lower wattage fixtures
Relocation/ reorientation of selected light poles and luminaires
Erection of screens
Planting of trees
Formation of earth embankments
Should concerns persist after the lights have been energised, it may be appropriate to conduct on-site assessment to
confirm the extent of the matter and further develop recommendations of practicable measures for consideration, to
control off-site lighting impacts for those specific areas of concern.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 16 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
APPENDICES
1. AS 4282: Table 2.1
2. Maintained Horizontal Illuminance
3. Initial Horizontal Illuminance Isolux Plot
4. Obtrusive Lighting Calculations
5. Obtrusive Lighting Calculations (70deg Tilt)
6. Raytrace Images from Elevated Positions
7. Responses to Client’s Questions
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 17 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
Appendix 1: AS 4282: Table 2.1
RECOMMENDED MAXIMUM VALUES OF LIGHT TECHNICAL PARAMETERS
FOR THE CONTROL OF OBTRUSIVE LIGHT
(See Clause 2.7)
1 2 3 4 5
Light
technical
parameter
Application or calculation conditions
(see also Figure 2.1 and Section 5)
Recommended maximum values
In commercial
areas or at
boundary of
commercial
and residential
areas*
Residential areas
Light
surrounds**
Dark
surrounds***
Illuminance
in vertical
plane
(Ev)
Pre-curfew:
Limits apply at relevant boundaries of nearby
residential properties, in a vertical plane parallel
to the relevant boundary, to a height
commensurate with the height of the potentially
affected dwellings. Values given are for the
direct component of illuminance
25 lx
10 lx
10 lx
Curfewed hours:
Limits apply in the plane of the windows of
habitable rooms of dwellings on nearby
residential properties. In the absence of
development (i.e. vacant allotment), the limits
apply on the potentially affected property, in a
vertical plane parallel to the relevant boundary, at
the minimum setback permitted for a dwelling,
to a height commensurate with land use zoning
provisions. Values given are for the direct
component of illuminance
1 lx
2 lx
1 lx
Luminous
intensity
emitted by
luminaires
(I)
Pre-curfew:
Limits apply to each luminaire (irrespective of the
number on a head frame) in the principal plane,
for all angles at and above the control direction,
when aimed in accordance with the installation
design
Limits as determined from Table 2.2.
Alternatively, the limits and method of assessment
associate with curfewed hours may be applied, at
the discretion of the designer (see Clauses 2.7.1
and 2.7.2)
Curfewed hours:
Limits apply in direction where views of bright
surfaces of luminaires are likely to be
troublesome to residents, from positions where
such views are likely to be maintained, i.e. not
where momentary or short-term viewing is
involved
2500 cd
1000 cd
500cd
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 18 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
AS 4282: Table 2.1 (continued)
1 2 3 4 5
Light
technical
parameter
Application or calculation conditions
(see also Figure 2.1 and Section 5)
Recommended maximum values
In commercial
areas or at
boundary of
commercial
and residential
areas*
Residential areas
Light
surrounds**
Dark
surrounds***
Threshold
increment
(TI)
Limits apply at all times where users of transport
systems are subject to a reduction in the ability
to see essential information. Values given are for
relevant positions and viewing directions in the
path of travel
20% based on
adaptation
luminance (L)
of 10 cd/m2
20% based on
adaptation
luminance (L) of
1 cd/m2
20% based on
adaptation
luminance (L)
of 0.1 cd/m2
*Applies to residential accommodation in commercial areas or at the boundary between commercial and residential
areas. The term ‘commercial’ is used as a generic description for zoning which provides for urban uses other than
residential.
**Where the affected property abuts roads that are lit to Category V5 or higher in accordance with AS/NZS 1158.1.1.
***Where the affected property abuts roads that are lit to Category B1 or lower in accordance with AS 1158.1, or
where there is no lighting.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 19 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 20 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 21 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 22 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 23 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
Appendix 6: Raytrace images from elevated positions
Viewer Position NNW Viewer Position East
Viewer Position South Viewer Postion SE
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 24 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
APPENDIX 7: RESPONSES TO CLIENT’S QUESTIONS
Upon review of the draft issue of the report a number of questions/ comments were raised, with reponses being
provided by Webb Australia shown in red, below:
Q1. It sounds like it could be good news. I am reading that you expect no real impact from the quarry lighting?
A. Yes, it is good news. We expect that the impact from the quarry lighting will be noticeable, but not significant
when viewed from the proximity of the surrounding dwellings.
Q2. On what basis do they need such high lighting levels “for operational and safety requirements”? I take it there are
no Standards for such requirements? Does an employee car park need that much lighting? Does a road way need so
much lighting in addition to headlights? It sounds like there are no real set standards here. Is that the case? Then it is
up to GHD to design (and charge for)whatever they think is a good idea. Is this the case? Is it “over-engineered”? Is
Holcim paying more than they need to? Could you elaborate?
A. There are Standards for minimum illuminance requirements for the various areas that are established for
operational and safety requirements (refer Table 4.1 of the report). These Standards are primarily concerned with
minimum levels being achieved and do not set any maximum illuminance levels. Exceeding the minimum levels is
permissible. It is common design practice to exceed the minimum requirements by a comfortable margin to ensure
the levels do not fall below the minimum requirements at any time during the luminaire maintenance cycle (i.e.
between relamping and/or cleaning intervals).
Set against the minimum requirements, AS4282 provides recommendations on the maximum values of obtrusive light
permitted by the installation.
Our review of the lighting design has identified two areas where the illuminance achieved by the design is well in
excess of the minimum requirements (i.e. the entry roadway and the parking area). Although the lighting design
appears to be over-illuminated in these areas, the maximum values of obtrusive light recommended by AS4282 are
not exceeded. The design satisfies the minimum requirements by a substantial margin and still complies with the
obtrusive lighting recommendations of AS4282.
The impact of “over-engineering” of the lighting in these two areas would include marginally higher installation and
operational costs for the quarry and an elevated illuminance level.
As stated in the report, it may be possible to replace the luminaires with new fixtures with lower wattage lamps as a
remedial measure and still achieve the minimum illuminance requirements, however, compliance with the lighting
design criteria would have to be confirmed by the lighting designer.
Q3. Several charts assess the light intensity at 100m, 200m and 1000m. In particular at part 6.4 and 6.6. Is it
possible to assess the intensity/impact at 10,000 – where we are?
A. An assessment of the lighting from a distance of 10,000m could be undertaken, however, the report has
established the impact of the lighting at 1,000m is below the maximum recommendations of AS4282. If the lighting
complies with the requirements of the Standard at 1km away, it will be even better at a distance of 10km.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 25 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
Q4. You don’t say much about the terms of the Development Consent, in particular s 50 – “take all practicable
measures to prevent and or minimise any off-site lighting impacts” Should we read into this that there won’t be any
off-site lighting impacts? Can you elaborate?
A. The quarry lighting will be visible and be seen from beyond the boundary of the site, so we are not saying there
won’t be any off-site lighting impacts.
To completely eliminate or prevent any off-site impacts of the lighting would require the provision of physical barriers
surrounding the quarry, designed to restrict spill light beyond the boundaries of the site. This could be in the form of
trees, earth embankments or structures forming screens. The necessity and practicability of these methods is open
for discussion, however it is recommended that the decision to proceed with such rectification measures should be
deferred until such time as the impacts of the lighting can be assessed visually.
The lighting design has incorporated the use of aeroscreen luminaires with flat glass lenses and constrained their tilt
to 5 degrees to minimise the upward light component. The drawings provided indicate that where the highest
wattage lights are closest to the site perimeter, with a few exceptions, they are generally facing into the site and
away from nearby dwellings. These methods are considered responsible approaches by the lighting designer to
controlling obtrusive light.
Where areas of sensitivity persist, the erection of screens may provide an effective interim solution, until dense
vegetation (trees) can be established to provide a more permanent solution.
Q5. Could you comment on the application of s. 2 and 3 of AS4282 as noted in my letter to Pru Goward of the 5th
Feb, attached, p. 2. Are you saying that the proposed lighting will not have any “perceived change in amenity of the
night sky, against the ambient lighting prior to the installation of the introduced lights”?
A. AS4282 recommends limits on the levels of obtrusive light that may be applicable to various outdoor lighting
installations, and does so, giving consideration to the ambient lighting existing in that environment. The values that
are permissible by the Standard are more than zero, which means that some (limited) obtrusive light is
permissible. The Standard accepts that some degree of tolerance by those affected may be necessary. The
Standard also accepts that a complying installation will not necessarily receive no adverse reaction from those
affected by the spill light.
In this case, there may be a perception of change in the amenity of the night time view relative to the ambience that
existed prior to the installation of the quarry site lighting, however, this has been quantified and falls within the
acceptable terms of the Standard.
Q6. Much of your report is based on a 5 degree lighting tilt. How can we be certain this will be maintained. Will lights
be locked into this position? Could they move back to a 70 degree tilt again?
A. We understand the lights have been fixed in position with a 5 degree tilt, as required by the lighting
design. General maintenance (cleaning and lamp changes) can occur without the need to adjust the aiming or tilt of
the luminaires.
Whist no guarantee can be provided, there is no expectation that the luminaires are likely to be re-aimed at 70 degree
tilt.
Q7. S. 3 suggests the poles are timber. I think, in fact, they are steel. Does this matter?
A. The type of pole will have no effect on the performance of the lighting installation.
HOLCIM LYNWOOD QUARRY
EXTERNAL LIGHTING REVIEW REPORT
L490arep001_C.docx Page 26 of 26 WEBB AUSTRALIA GROUP (ACT) PTY LTD
7 MAY 2014 ISSUE C ABN 14 064 354 776
Q8. Can you suggest any reduction in lights for the areas that are “over illuminated”?
A. As stated in the report, it may be possible to replace the luminaires with new fixtures with lower wattage lamps
as a remedial measure and still achieve the minimum illuminance requirements, however, compliance with the
lighting design criteria would have to be confirmed by the lighting designer.
Q9. Are you able to offer a rough guesstimate of the cost of this “over Illumination” ( I know we have touched on this
before)
A. As stated above, the impact of “over-engineering” of the lighting in the two areas identified would include
marginally higher installation and operational costs for the quarry. These costs have not been quantified.
Q10. Can you provide further detail on the Viewtrace Images in Appendix 6. Can we see these for 10kms distance
and from the NNW ( I assume this is to be our view of the quarry?) ?
A. The ray traced images included in the report are not to scale and are indicative only. The elevation and distance of
the viewing positions from the site are not quantified, but they do provide an approximation of what the site may
appear like from a distance, at an elevated position and from the directions noted.
Q11. From the above, you can see that my focus is very much on what we will see at night from approximately
10kms NNW from the quarry. Can you expand on this or provide any more detail?
A. As the apparent brightness diminishes with distance, we can expect that with an unobstructed view of the site
from a distance of 10km to the NNW at night, the site will be discernible. The impact of the site lighting will be
visible against the blackness of the surrounding, unilluminated (dark) countryside. The final assessment of
acceptability will be a personal matter, as perceptions may differ between individuals. The only way to be certain
about one person’s perception of what they will see when the lights are turned on is to allow them to make their own
assessment when the lights are energised.
Q12. How much worse will it be for those at similar or lower elevations and perhaps only 5 Kms way in a more
westerly direction?
A. The view from lower elevations will be different from elevated positions, as the ground illuminated by the lighting
may not be visible from the lower elevations, while the lights themselves may come into view.
The luminous intensity of the luminaires when viewed from such angles is likely to be in excess of 500 cd, the
maximum recommended by AS4282. The precise luminous intensity would depend on the relative elevation of the
view point and the distance from the lights.
This could be further investigated, subject to the provision of survey data of affected dwellings (i.e. dwellings at lower
elevations with unobstructed view of the lights) and of light pole locations.