High Voltage Insulation Diagnostics

Presented by: Bostjan Flis

[email protected]

WELCOME!

Page 2: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

Content overview

Application areas of HV insulation testing What influences insulation resistance Symptoms of bad insulation Testing methods Insulation testing with DC test voltage - insulation characteristics Insulation testing with DC test voltage - test parameters Limit values Connection schemes Test data evaluation i.e. statistics keeping General requirements for HV insulation testers Metrel HV insulation testers Metrel's solution providing, services and development

Page 3: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

Application areas of HV insulation testing

Insulation resistance testing is part of predictive maintenance of:

- Rotary machines (generators, motors)

- Transformers (industry, utilities, power distribution)

- Cables

- Measuring transducers

- Distribution boards

Benefits:

- Lower TCO (total cost of ownership)

- increased electrical safety

- prevention against fire hazard

Page 4: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

What influences insulation resistance

- Thermal exposure

- Overload

- Moisture

- Electrical shocks

- Mechanical shocks (vibrations, bad transportation)

- Dirt (oil, dust, conductive materials)

- General ageing of insulation

Symptoms of bad insulation

- Insulation breakdowns in a form of electrical short-circuits- Fire- Long-term downgrading values of insulation resistance- Insulation resistance values under by standards determined values

Page 5: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

Insulation testing methods

- AC insulation testing (50/60Hz, 1 minute)

- Insulation surge breakdown testing

- Insulation testing with switching voltage

- Insulation testing with DC voltage

- Dielectric losses (tgδ)

- Partial discharges

- U – I characteristics

Page 6: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

Insulation testing with DC test voltage - insulation characteristics

Riso Cpi

Rpi Ciso

Riss1

Riss2

Itot

+

Guard

U

ICiso IRCpi IRiso

IRiss U Test voltage

Riss1 and Riss2 Insulation surface resistance

Riso Insulation resistance

Ciso Capacitance of an insulation system

Rpi Polarisation resistance

Cpi Polarisations capacitance

Itot Total insulation current

IRiss Insulation surface leakage current

IRiso Resisitve part of the insulation current

IRCpi Polarisation current

ICiso Capacitive part of the insulation current

uA

0

10

20

30

40

t [s] 0 200 400 600 800

IRiso

Itot

IRiss

IRCpi

ICiso

Page 7: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

Insulation parameters

Polarisation Index (PI)

PI = R tot (10 Min) / R tot (1Min)

Dielectric absoption ratio (DAR)

DAR = R tot (1 Min) / R tot (30 Sek)

Dielectric discharge (DD)

DD = I DIS (1 min) / (U * C ISO ) I DIS ….a discharge current measured 1 minute after disconnecting the insulation system from the test voltage C ISO …. capacitance of the insulation systemU …test voltage

Discharge of Ciss

Itot

t [s] 10 20 30 40 50 60 0 0

Bad insulation

Good insulation

Discharging of Cpi

Page 8: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

Limit values for insulation testing with DC voltage

Insulation resistance

Limit value

General applications > 1MΩ per 1kV der Nennspannung des Prüflings

Rotary machines according to IEEE 43-2000

a./ 1 MΩ + 1 MΩ/1kVb./ 5 MΩ for motors under 600Vc./ 100 MΩ for motors above 600V

Switching- and control devices according to IEC 60439-1 > 1kΩ for 1V of the UN of the test object

Splitting transformers and safety low voltage transformers according to IEC 61558

a./ Basis insulation > 2MΩb./ Additional insulation > 5MΩc./ Reinforced insulation > 7MΩ

Polarisation index (PI)

PI WertEvaluation

1 to 1.5 BAD (valid for older types of insulation materials)

2 to 4 SUFFICIENT (valid for older types of insulation materials)

> 4 VERY GOOD (also for the modern type of insulation materials)

Dielektric absorption ratio (DAR)

DAR valueEvaluation

< 1 BAD

1 ≤ DAR ≤ 1.25 SUFFICIENT

> 1.4 VERY GOOD

kVMΩ ni UR

Thumb rule(motors and generators):

Page 9: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

Connection schemes

Precondition!

- Measuring object has to be disconnected from power supply network (voltage – free)

- Surface of the insulation system has to be dry and clean

VNNN

G

VNNN

G

VNNN

G

Power transformer

HV vs LV

HV vs G

LV vs G

Device A Device B Device N

Power supply

PE - ground

Port A Port A Port A

Port B Port B

PE PE

Port C1

Port C2 Port C2

Port C1 C

Port C

Multiple devices

Page 10: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

Test data evaluation i.e. statistics keeping

Statistics

- Always assure the same measuring conditions

(connection, temperature, test voltage, diagnostics parameters)

- Regular test intervals (6 months or one year)

- Results keeping for the entire life period of the equipment

- Observation of downgrading trends

Temperature coefficient(all values are to be calculated on 75ºC)

rKRR

1// i10/75i10 0304,028,210rK

Page 11: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

General requirements for HV insulation testers

Test functions:- Insulation resistance

- Step voltage test

- Capacitance

- PI, DD, DAR

- Current in µA and mA range

- Voltage AC/DC

Accessories:

- Shielded test leads

- High quality test terminals (HV, antistatic, high surface resistance)

- PC Software for downloading of test results and creating test reports

Other features:

- Guard terminal to eliminate surface insulation currents

- Automatic discharging of the test object after measurement

- Built-in timer

- On-Line graph R = f(t)

- EM immunity for usage in HV environments

- EM Filters for improved accuracy

- Good charging system (accus or mains or both)

Page 12: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

Metrel HV insulation testers

Integrated features:•Test voltage up to 10kV DC•Resistance measuring range up to 10TΩ•Automated calculation of PI, DAR and DD for profound insulation diagnostics•On-Line R=f(t) display•Test voltage setting in 25V steps•Shielded 12kV test leads to reduce influence of external EM fields•CAT IV/600V over-voltage category for utilities and industrial applications•New TeraLink PRO Windows PC Software for TeraOhm 5kV Plus•Handbook “Modern insulation testing” on CD

Page 13: High Voltage Insulation Diagnostics Presented by: Bostjan Flis bostjan.flis@metrel.si WELCOME!

Metrel's solution providing, services and development

Product training in Metrel training centre

On-Line technical support

Application training and publications

Repair & Calibration training

Calibration equipment

Repair & Calibration services

Advanced technical solutions for all product‘s segments

(Hardware, Firmware, PC Software)

Customised solutions (Instruments, Software, Accessories)